The document discusses the AVENAR panel 8000 fire alarm system. It is a modular fire panel that can be expanded up to 32 loops and customized for medium to large applications. It has a touch screen display, integrated Ethernet, and supports both analog addressable and conventional technologies.

Uploaded by

Malik islamov
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
698 views10 pages

Fpa 8000 Panel

The document discusses the AVENAR panel 8000 fire alarm system. It is a modular fire panel that can be expanded up to 32 loops and customized for medium to large applications. It has a touch screen display, integrated Ethernet, and supports both analog addressable and conventional technologies.

Uploaded by

Malik islamov
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Fire Alarm Systems - AVENAR panel 8000

AVENAR panel 8000

VdS

u Completely modular fire panel, expandable up


to 32 loops, provides customized solutions for
medium to large size applications

u High resolution display with bright colors to


indicate alarms and events

u 8" touch pad with fixed and programmable


buttons, thus adaptable to the situation

u Integrated Ethernet switch for networking and


interfaces to remote services, building
management and voice alarm systems

u Adaptable to local requirements and regulations

The fire panel allows mixed operation of analog kits also allow installation in 19" racks. Both housing
addressable and conventional technology. It supports types can be extended with up-to four housings to
connecting periphery in either stub or loop topologies. increase the number slots for the functional modules.
Analog addressable fire detectors, manual call points, The panel controller is the central component of the
signaling devices, inputs and outputs are identified fire panel. A color display shows all messages. The
and managed by the fire panel as single elements. As touch screen is for operation of the entire system. The
required by the building structure the peripherals are user-friendly interface adapts to various situations.
grouped software wise in logical zones. This causes correct operation that is simple and clear
The completely modular designed fire panel uses as well as targeted and intuitive.
functional modules that are clicked in a slot on a rail. Panels and keypads of the AVENAR series and of the
The rail provides power and internal communication FPA-5000 series (MPC-xxxx-B and MPC-xxxx-C) can be
to the functional modules. A wide range of functional combined in one panel network using the Ethernet
modules are available providing: addressable loops, and the CAN bus interfaces. The remote keypad is for
conventional zones, inputs and outputs, and decentralized operation of the panel or of the panel
interfaces to various devices. The fire alarm panel can network.
be equipped with 46 functional modules, of which a Integration into large-scale systems can be done by an
maximum of 32 can be analog addressable loop Ethernet interface to the Bosch Hierarchy panel
modules. This results in a tailor-made fire panel (UGM) or to Building Integration System (BIS).
suitable for medium to large size applications. Integration into third party management systems is
Two different types of housings are available to possible with the availability of OPC server and
assemble the fire panel: Software Development Kit.
• Wall mount housing A data interface enables monitoring and full control of
• Frame mount housing Bosch voice alarm systems. This makes the fire panel
The slim wall mount housings are for mounting a complete safety solution.
directly to the wall. Frame mount housings require an The fire panel is configured on a laptop using the
additional frame between the housing and the wall. FSP-5000-RPS programming software. The
The frame lets space for e.g. cabling, media programming software enables further adaptation,
converters, and larger batteries. Special installation e.g. to country-specific requirements and regulations.
Fire Alarm Systems - AVENAR panel 8000 2 | 10

System overview – Optional 19'' rack mounting kits

2. Panel controller
X +AU X3 +AU
X +AU

– Standard license: EN54 compliant fire detection


AU X2 AU X-5 +AU
X-6

2
BM0

– Premium license: EN54 compliant fire detection,


1 various Ethernet interfaces and comfort fea-
tures
– Panel redundancy: with additional panel con-
4
IN

OUT

troller or with keypad

1. Functional modules
– Analogue addressable loops: standard or high
performance
– Conventional detection zones
6
8 – Conventional notification zones
– In- and output interfaces
– Serial communication interfaces
7
– LED annunciators

2. Power supply
– Battery capacity
– Battery autonomy: up-to 72 hours standby and
5
IN

OUT
additional 30 minutes alarm condition
Alarm indication
All messages are shown on the display with a bright
+ - - + - + + - - + - +
color. The displayed messages contain the following
NO1

NO2
NC1

NC2

+ - a -b + + - a -b +
C1

C2

AUX1 OUT1 IN1 AUX2 OUT2 IN2 AU XL1S NAU 1 X L2S N 2


LSN 0300 A

3 9
ZONE4
Störung

information:
ZONE3
CZM0004A

RMH0002A

Störung
ANI0016A

F1 F2
ZONE2 RELAIS2
Störung Störung

ZONE1 RELAIS1
Störung Störung

• Message type
AUX3 OUT3 IN3 AUX4 OUT4 IN4 FB1 FB2
+ - - + - + + - - + - + + - + -

Fig. 1: Example configuration • Type of the triggering element


• Description of the exact location of the triggering
1 Panel controller 2 BCM‑0000‑B Battery
element
Controller Module
• Logical zone and sub-address of the triggering
3 Functional modules 4 PRS-0002-C Panel Rail Short element
5 PRD 0004 A Panel Rail Long 6 Power supply bracket 18 Icon LEDs give continuous information about the
7 Power supply unit 8 HBC 0010 A Panel Housing for operating status of the panel or the system. A red icon
10 modules LED shows an alarm. A blinking yellow icon LED
shows a fault. A steady yellow icon LED shows a
9 Batteries
disabled function. A green icon LED shows proper
Functions operation.
Two status LEDs, one red and one yellow, are
AVENAR panel 8000 is a completely modular fire panel programmable. The red one shows a self-defined
for medium to large size systems. All panel alarm. The yellow one shows a self-defined fault or
components are separately available to provide deactivation.
compete flexibility and tailor made solutions for Additional annunciator modules, each with 16 red and
complex applications. Safety Systems Designer 16 yellow LEDs are available to indicate a larger
supports the planning of the fire panel. The software number of self-defined alarms, faults or deactivations.
provides information about the size and number of
Operation and processing of messages
housings, the modules, interfaces various systems and
For operating the panel, an 8 inch touch pad as input
the energy balance calculation.
medium is put upon the display. There are 6 buttons
Depending on specific requirements, the planning
with fixed functionality as well as 3 programmable
involves choosing from the following options:
function keys.
1. Housing Examples for the assignment of the function keys:
– Frame mounting: slim design • Set the panel controller to day mode, set the panel
controller to night mode
– Wall mounting: additional space for cabling, me-
• Enable detection points or outputs, disable
dia converters and larger batteries
detection points or outputs
Fire Alarm Systems - AVENAR panel 8000 3 | 10

• Set standard sensor sensitivity, set alternative started from the VAS. A malfunction on the VAS will
sensor sensitivity generate a fault message on the user interface of the
Each function key has a virtual status indicator. fire panel.
At any time, an operator with sufficient user rights can
Saving and printing messages
control the function keys.
The history log keeps incoming alarms and events
Overview of evacuation zones and outputs internally. The history log has a capacity to store
At any time, the operator can get a clear overview of 10000 messages. The messages can be shown on the
each evacuation zone and of each output connected display, and you can export the messages.
to the fire protection equipment. Each zone and each Additionally, you can connect a log printer via a serial
output is marked with a programmable text label and interface module for real-time printing incoming
a clearly distinctive color reflecting the state: Green messages.
shows idle state, power is available. Red shows an
Languages
activation during fire alarm condition, and fuchsia an
The operator can change the language of the user
activation without a fire alarm condition. Yellow shows
interface. A quick user guide for each language is
a fault or disabled state. An operator with sufficient
available. Following languages are included in the
user rights is able to start the evacuation in selected
package: English, German, Bulgarian, Croatian, Czech,
zones and activate outputs connected to the fire
Danish, Dutch, Estonian, French, Greek, Hungarian,
protection equipment through the user interface.
Italian, Latvian, Lithuanian, Polish, Portuguese,
Smart Safety Link Romanian, Russian, Serbian, Slovak, Slovenian,
Smart Safety Link is the most reliable and secure Spanish, Swedish and Turkish.
interface to combine a fire detection and a voice alarm The quick user guides of following languages are
system (VAS). Smart Safety Link offers exceptional available only online at www.boschsecurity.com:
flexibility and options for expandability. Hebrew and Ukrainian.
The bi-directional data communication establishes a
Operator management
supervised connection between the fire detection
The system can have up to 200 different registered
panel and the VAS. Both the fire panel and the VAS
operators. Login is permitted with a user ID and an 8-
indicate a fault message when the connection is
digit pin code.
interrupted. In case of an interrupted connection, the
There are four different authorization levels.
user can start the evacuation of the complete building
Depending on the authorization level it is possible for
manually by using a call station of the VAS. An
the operator to do certain functions according to
interruption of the interface does not lead to an
EN54-2.
automatic evacuation of the building. When the
interface is re-established, the fire panel automatically Licenses
re-synchronizes the current alarm state with the VAS. The panel controller is delivered with a hard coded
In case of a fire condition, the fire panel can software license. This software license is implemented
automatically start voice announcements using virtual during production and cannot be modified, revoked or
VAS triggers that are activated by rules which are transported. The license defines the maximum panel
configured in FSP-5000-RPS. The fire panel generates network size and availability of certain features and
a supervisory message when an evacuation event is interfaces.
Fire Alarm Systems - AVENAR panel 8000 4 | 10

Standard license FPE-8000-SPC Premium license FPE-8000-PPC


Ethernet interface to

Building management system (OPC server, BIS, FSM-5000-FSI) •

UGM-2040 Hierarchy panel •

Voice alarm system (Smart Safety Link) •

Monitoring and control

Status overview • •

Simultaneous control • •

Individual control •

Modularity (maximum number)

Slots for functional modules (max number including slots for LSN 46 46
modules)

LSN modules (max number)

LSN 0300 A modules (1 slot per module) 32 32

LSN 1500 A modules (2 slots per module) 11 11

Panel redundancy

Redundant panel controller • •

Keypad as redundant panel controller • •

Network

Panel network panels, remote keypads panels, remote keypads, servers

Max. number of nodes 32 32

Functional modules Module Description Function


Functional modules are independent encapsulated
units. They are placed into a slot of a panel rail. The CZM 0004 Conventional Connecting conventional peripheral
power supply and the data traffic with the panel are A zone module devices using four monitored conventional
therefore provided automatically. The module is lines
identified by the panel with no further settings and ENO 0000 Connecting fire service equipment
External
operates in the default operating mode (plug and B complying with DIN 14675
notification
play).
module
Wiring to external components is performed using
compact connector/screw terminals. After a FPE-5000- Module interface Connection to UGM systems
replacement, only the connectors need to be
UGM to UGM
reinserted, there is no need for extensive rewiring.
IOP 0008 A Input-output Individual displays or flexible connection of
Module Description Function module various electrical devices, with 8
independent digital inputs and 8 open
ANI 0016 A Annunciator Indicating system statuses, with 16 red
collector outputs
module and 16 yellow freely programmable LEDs
IOS 0020 A Communication With S20 and RS232 interfaces
BCM-0000- Battery Controlling the power supply to the panel module, 20mA
B controller and the battery charge level
module
Fire Alarm Systems - AVENAR panel 8000 5 | 10

Module Description Function • Fault


• Heat
IOS 0232 A Communication Connection of two devices using two
• Water
module, RS232 independent serial interfaces, e.g. Plena or
Only some of these message types are available for
a printer.
selection depending on the element type. The
LSN 0300 A LSN bus module Connection of an LSN loop with up to elements and inputs that can trigger an alarm include
300mA 254 LSN improved elements or 127 LSN all manual and automatic detectors, as well as the
classic elements at a maximum line current modules and interface modules listed below on the
of 300 mA basis of the available inputs.

LSN 1500 A LSN bus module Connection of an LSN loop with up to


1500mA 254 LSN improved elements at a maximum Modules Detection Points
line current of 1500 mA or 127 LSN classic
elements at a maximum line current of CZM 0004 A Up to 4 (1 detection point per zone)
300 mA
IOP 0008 A Up to 8 (1 detection point per monitored input)
NZM 0002 Notification Allows connection of two conventional,
A appliance zone monitored notification appliance circuit RMH 0002 A Up to 2
module lines
ENO 0000 B requires 1 detection point only if a FSE release
RMH 0002 Relay module Monitored connection of external elements element is connected and programmed using the
A high-voltage with feedback, with two changeover FSP-5000-RPS programming software
contact relays suitable for switching mains
voltage FPP‑5000‑TI 2

RML 0008 Relay module For low voltage switching, with eight
A low-voltage changeover contact relays Interface Detection Points
Modules

i Notice
FLM-420/4CON Up to 2

Safety Systems Designer can be used to plan FLM-420-I8R1 Up to 8


fire alarm systems that conform to the relevant
limits (e.g. in terms of cable length and power FLM-420-I2 Up to 2
supply).
FLM-420-O8I2 Up to 2
i Notice
FLM-420-O1I1 Up to 1
Safety Systems Designer for fire alarm systems
enables the system dimensions, the energy re-
FLM-420-RHV Up to 2
quirements and the quantity and prices of the
elements required to be estimated at each dif-
FLM-420-RLE-S Up to 2
ferent phase in the planning process.The soft-
ware is designed for planners and engineering
Networking
offices that want to produce a quotation for a
Up to 32 panel controllers, remote keypads and OPC
fire alarm system.
servers can be combined to form a network.
Detection points Panels and keypads display all messages, or you can
Each element or input that can trigger an alarm counts form a group of panels and keypads. Within one
as an detection point. One stand-alone panel manages group, only messages of this group are displayed.
up to 4096 detection points. A panel operated in a A variety of fire alarm network topologies are possible:
network is limited to 2048 points. • CAN loop
All elements and inputs that do not use the Input type • Ethernet loop
in the Message type setting are regarded as detection • Ethernet/CAN double loop
points. Therefore, all elements and inputs for which
• CAN loop with Ethernet segments
one of the following settings is programmed as the
• Ethernet backbone with sub-loops (Ethernet/CAN)
Message type are regarded as detection points:
• Fire
• Internal fire
• Supervisory
• Multi-criterion
• Smoke
Fire Alarm Systems - AVENAR panel 8000 6 | 10

Region Regulatory compliance/quality marks


Switzerland VKF AEAI 31626 AVENAR panel 8000 | AVENAR
Ethernet panel 2000 | AVENAR keypad 8000

Europe CE AVENAR panel 8000 | AVENAR keypad


8000

Poland CNBOP 4290/2021 AVENAR panel 8000

Czech Republic TZÚS 080-023743 AVENAR panel 8000 |


CAN CAN CAN
AVENAR panel 2000 | AVENAR keypad
8000

Installation/configuration notes

• The FSP-5000-RPS programming software enables


adaption to project- and country-specific
Interfaces requirements.
The panel controller features The programming software and the associated
• 2 CAN interfaces (CAN1/CAN2) for networking documentation can be found at
• 1 Rail connector www.boschsecurity.com for those with access
• 4 Ethernet interfaces (1 / 2 / 3 / 4) for networking, rights.
prescribed usage: Information about the programming software is also
included in FSP-5000-RPS online help.
– 1 and 2 (blue): Panel network
General planning instructions
– 3 (green): Building management system, hier-
archy panel, voice alarm system • Country-specific standards and guidelines must be
considered during planning.
– 4 (red): Remote Services
• The regulations issued by regional authorities and
• 2 signal inputs (IN1/IN2) institutions (e.g. fire service) must be adhered to.
• 1 USB function interface for configuration via • Please note that standards and guidelines may
FSP-5000-RPS require that a maximum of one function in more
• 1 Memory card interface than one zone may fail.
Regulatory information For example, if the auxiliary power fails, only the
fire detectors and/or manual call points of one zone
Region Regulatory compliance/quality marks may fail.
• We recommend the use of loops wherever possible,
Germany VdS-S VdS-S_S221001_AVENAR series
as they offer far greater security than stub lines.
Europe CPR 0786-CPR-21699 AVENAR panel 8000 • Terminating each stub and each T-tap with EOL
modules is essential to set up a complete fire alarm
Morocco CMIM AVENAR panel 8000 | AVENAR keypad system with extended line monitoring (creeping
8000 short circuit and creeping open monitoring).
• Conventional detectors of the Bosch portfolio for
Malaysia BOMBA 23-340 AVENAR panel 8000 | AVENAR fire products can be connected using one of the
keypad 8000 following methods:
Israel SII 7152327281/2 AVENAR panel 8000 – Using the CZM 0004 A 4 Zone Conventional
Module
Serbia KVALITET AVENAR panel 8000 The module provides four DC primary lines
(zones).
Slovakia PHZ 2021002517-2 AVENAR panel 8000 |
– Using an FLM-420/4‑CON GLT interface module
AVENAR panel 2000 | AVENAR keypad
on the LSN bus for two zones
8000
• Consider the system limit for the number of LSN
Ukraine DCS 0000957-20 AVENAR panel 8000 | elements.
AVENAR keypad 8000 • Each element and input which is able to set off an
alarm requires a detection point. Inputs are
United Arab MOI 2013-3-56006 AVENAR panel 8000 |
considered as detection points if they are
Emirates AVENAR panal 2000
programmed accordingly using the FSP-5000-RPS
Germany VdS G 220047 AVENAR panel 8000 Programming Software.
Fire Alarm Systems - AVENAR panel 8000 7 | 10

• In accordance with EN 54-2, no more than 512 Building Management System


detectors and their functions may fail if a system • If connected to a building management system
component fails. (Bosch Building Integration System BIS) via an
• 12 V/45 Ah batteries can only be used with the Ethernet interface using an OPC server, the
frame installation housings. following must be noted:
• Use fuses complying with national regulations to In a multi-building network, it is essential to clarify
protect the power lines. with the network administrator whether the net-
• Recommended fire detector cable: J-Y(St)Y 2 x 2 x work is designed for multi-building connections
0,8 mm, red. (e.g. no interference due to differences in ground-
System limits for each LSN module ing potential).
Panel Controller Firmware
• It is possible to combine LSN interface modules,
Two firmware versions are available for the panel
LSN detectors and notification appliances on one
controller of the fire panel: version 3.x and version
loop or stub line.
4.x.
• For a mixed connection of LSN classic elements and Firmware V3.x enables networking compatibility with
LSN improved elements, a maximum of the legacy FPA-5000 series panels (MPC-xxxx-B and
127 elements are permitted. MPC-xxxx-C) and the FMR-5000 keypad.
• The use of unshielded cables is possible. This implies that when AVENAR panel and AVENAR
• Limits per LSN 0300 module: keypad are running firmware V3.x, they only contain
– Up to 127 LSN classic elements or 254 LSN im- bound product features and peripherals that are also
proved elements can be connected available for the FPA-5000 series.
From January 1, 2022 to December 31, 2025, panel
– Current consumption of up to 300 mA firmware version 3.x is in maintenance mode. During
– Cable length of up to 1600 m this period, new versions will be released only
• Limits per LSN 1500 module: containing fixes for critical bugs and critical security
gaps.
– Up to 127 LSN classic elements or 254 LSN im-
From January 1, 2022 onwards, new product features,
proved elements can be connected
new LSN peripherals, new GUI languages, and
– Up to 1500 mA current consumption if LSN im- normative changes will be only available in firmware
proved elements are connected version 4.x.
– Up to 300 mA current consumption if LSN clas- Firmware version 4.x is exclusively for AVENAR panel
sic elements are connected and AVENAR keypad.

– Cable length of up to 3000 m Technical specifications


Environmental Conditions General system limits
• Assembly and operation of the fire panel must be
carried out in a clean and dry indoor location.
Panels/remote keypads/OPC servers in the Max. number
• Permissible relative humidity: max. 95 % at 25°C, network
non-condensing
• To ensure optimum battery service life, the panel Ethernet / CAN 32
should only be operated at sites with normal room
temperatures.
• Do not operate devices showing condensation. LSN elements Max. number

Positioning Stand-alone panel 4096


• Operating and display elements should be
Per network panel 2048
positioned at eye level.
The distance between the upper edge of the hous- Total network 32768
ing and the center of the panel controller display is
around 11 cm. For example, if the eye level required
is 164 cm, the housing upper edge installation di- Detection points Max. number
mension is 175 cm.
Panel, without panel redundancy 512
• For frame installation housings, a clearance of at
least 230 mm is required to the right of the last
Stand-alone panel, with panel redundancy 4096
housing to swivel out the installed housing (e.g. for
connection, maintenance or service).
Networked panel, with panel redundancy 2048
• Sufficient space should be left below and next to
the panel for any possible extensions, e.g. for an
Total network 32768
additional power supply or an extension housing.
Fire Alarm Systems - AVENAR panel 8000 8 | 10

NAC groups Max. number Configuration limits per fire panel (FSP-5000-RPS) Max. number
NAC groups with more than one FNM-420, per loop 6 Automatic connections to remote keypad 3

Blocks of State-Dependent Rules (depending on what 8


Voice alarm system Max. number kind of activations are possible)

In CAN network, per panel (premium license) 1 Maximum number of rules within a block 254

In total Ethernet network (premium license) 1 Number of functional modules

Triggers (each trigger counts as one sounder group) 244


Number of functional modules Max. number
Ethernet interface
ANI 0016 A 32
Triggers (each trigger counts as one sounder group) 120
RS-232 interface BCM-0000-B 8

System limits per fire panel CZM 0004 A 32

Per fire panel Max. number ENO 0000 B 8

Sets, e.g. bypass group 192 FPE-5000-UGM 4


These sets include sets which are automatically
created for each LSN bus. IOP 0008 A 32
Functional modules (with panel redundancy) 42
IOS 0020 A 4
Functional modules 46
IOS 0232 A 4
Printer 4
LSN 0300 A 32
Alarm counters (external, internal, testing) 3
LSN 1500 A 11
Entries in the event database 10000
NZM 0002 A 8
FSP-5000-RPS configuration interfaces (USB) 1
RMH 0002 A 32
Maximum number of outputs (sounders, controls, etc.) 508
RML 0008 A 32
activated in parallel due to the same event

Configuration limits per fire panel Power loss of panel components

Configuration limits per fire panel (FSP-5000-RPS) Max. number Component Power loss

Timer channels 20 ANI 0016 A 0.62 W (all LEDs lit)

Time control programs 19 BCM‑0000‑B • 0.96 W (controller + green LED lit)

• 1.44 W (per AUX with 1.06 A load)


Configuration for a Specific Day 365
CZM 0004 A • 1.65 W (for a line with 100 mA load)
Permission levels 4
• 3.36 W (for 4 lines with 100 mA load
User profiles 200 each)

Sum counters and counters (in total) 60000 ENO 0000 B • 1.44 W (1 relay activated)

Exportable objects including counters in the entire 2000 • 7.80 W (4 relays activated + key
panel cluster (without pre-defined system counters) deposit heating active)

Importable objects including counters (without pre- 2000 FPE-5000-UGM 0.17 W


defined system counters)
Fire Alarm Systems - AVENAR panel 8000 9 | 10

Component Power loss Housing material Sheet steel, painted


FPE-8000-FMR max. 12 W
Housing color Slate gray, RAL 7015
FPE-8000-PPC max. 10 W
Front color Anthracite, RAL 7016
FPE-8000-SPC max. 10 W
Battery type for wall-mount version 1 12V 24-27Ah
IOP 0008 A 0.24 W
Battery type for frame-mount 12V 38-45Ah
IOS 0020 A 0.36 W version 2
1
Order info: IPS-BAT12V-27AH, F.01U.579.781
IOS 0232 A 2
0.36 W Order info: IPS-BAT12V-45AH, F.01U.579.782

LSN 0300 A
Environmental
• 1.50 W (AUX with 490 mA load)

• 2.72 W (LSN) Safety class according to EN Class 1 equipment


62368-1
NZM 0002 A 0.96 W
Permissible ambient temperature -5 °C to 50 °C
during operation
PRD 0004 A 0.07 W
Permissible storage temperature -20 °C to 60 °C
PRS-0002-C 0.07 W
Relative humidity Max. 95% non-condensing @25 °C
RMH 0002 A 1.16 W
Protection category IP 30
RML 0008 A 1.04 W (all relays activated)
Cooling Natural convection*
UPS 2416 A 28.00 W
*Do not obstruct the vent holes.
Electrical
Ordering information
Input voltage range 100 - 240 V AC FPE-8000-SPC Panel controller, standard license
central component of AVENAR panel 8000, which is
Input frequency range 50 Hz to 60 Hz delivered with standard license defining network size, as
well as fire detection features according the standards.
Power source (EN 62368-1) PS 3 The entire system is operated via a touchscreen, all
messages are shown on the color display. The user-
Electrical source (EN 62368-1) ES 3 friendly user interface adapts to various requirements.
Order number FPE-8000-SPC | F.01U.327.090
Terminals 24 V+/- ①, 24 V+/- ②: FPE-8000-PPC Panel controller, premium license
central component of AVENAR panel 8000, which is
Output voltage (min-max) 20.4 - 30 V battery-buffered delivered with premium license. In addition to network
capability and network size, as well as fire detection
Output current (min-max) (x 2) 0 - 2.8 A features according the standards, the premium license
provides interfaces for OPC, FSM-5000-FSI, UGM-2040,
Power source (EN 62368-1) PS 2 Smart Safety Link. Individual control of evacuation zones
and fire controls is provided. The entire system is
Electrical source (EN 62368-1) ES 1 operated via a touchscreen, all messages are shown on
the color display. The user-friendly user interface adapts
to various requirements.
Mechanical
Order number FPE-8000-PPC | F.01U.352.441

Flammability rating UL94-V0 Accessories


ANI 0016 A Annunciator module
LCD display (pixels) 7" color WVGA 800 x 480 displays the status of 16 individually programmable
detection points
Operating and display elements • 6 keys Order number ANI 0016 A | 4.998.137.262
• 18 LEDs
Fire Alarm Systems - AVENAR panel 8000 10 | 10

BCM-0000-B Battery controller module RML 0008 A Relay module low-voltage


monitors the power supply of the fire panel and the provides 8 change-over contact relays (type C) for low
charging of the batteries voltage
Order number BCM-0000-B | F.01U.081.384 Order number RML 0008 A | 4.998.137.265
CZM 0004 A Conventional zone module FPE-8000-CRP Cable set redundant panel controller
for connecting conventional peripherals; provides four Used to redundantly connect one panel controller to
monitored conventional lines another panel controller.
Order number CZM 0004 A | 4.998.137.270 Order number FPE-8000-CRP | F.01U.349.391
ENO 0000 B External notification module
for connecting fire service equipment in compliance with Services
DIN 14675 EWE-FPA5MPC-IW 12 mths wrty ext FPA-5000 Main
Order number ENO 0000 B | F.01U.063.204 Panel Con
12 months warranty extension
FPE-5000-UGM Module interface to UGM
Order number EWE-FPA5MPC-IW | F.01U.360.726
for connecting the fire panels FPA‑5000 and FPA-1200 to
superordinate systems (UGM 2020, FAT 2002/RE,
FSM‑2000)
Order number FPE-5000-UGM | F.01U.028.289
IOP 0008 A Input-output module
for individual displays or flexible connection of various
electrical devices, providing eight independent digital
inputs and eight open collector outputs
Order number IOP 0008 A | 4.998.137.269
IOS 0020 A Communication module, 20mA
provides one interface of each S20 and RS232
Order number IOS 0020 A | 4.998.137.266
IOS 0232 A Communication module, RS232
for connecting two devices, e.g. voice alarm system
Plena, a laptop or a printer, via two independent serial
interfaces
Order number IOS 0232 A | 4.998.137.267
LSN 0300 A LSN bus module, 300mA
for connecting an LSN loop with up to 254 LSN
improved elements or 127 classic LSN elements, with a
maximum line current of 300 mA
Order number LSN 0300 A | 4.998.137.277
LSN 1500 A LSN bus module, 1500mA
for connecting an LSN loop with up to 254 LSN
improved elements with a maximum line current of
1500 mA, or with up to 127 classic LSN elements, with a
maximum line current of 300 mA
Order number LSN 1500 A | 4.998.137.278
NZM 0002 A Notification appliance zone module
for connecting 2 separate notification appliance zone
lines, provides 2 monitored primary lines
Order number NZM 0002 A | 4.998.137.275
RMH 0002 A Relay module high-voltage
provides 2 change-over contact relays (type C) for high
voltage, for monitored connection of external elements
with feedback
Order number RMH 0002 A | 4.998.137.274

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:


Bosch Security Systems B.V. Bosch Sicherheitssysteme GmbH Bosch Security Systems, LLC Robert Bosch (SEA) Pte Ltd, Security Systems
P.O. Box 80002 Robert-Bosch-Ring 5 130 Perinton Parkway 11 Bishan Street 21
5600 JB Eindhoven, The Netherlands 85630 Grasbrunn Fairport, New York, 14450, USA Singapore 573943
Phone: + 31 40 2577 284 Tel.: +49 (0)89 6290 0 Phone: +1 800 289 0096 Phone: +65 6571 2808
www.boschsecurity.com/xc/en/contact/ Fax:+49 (0)89 6290 1020 Fax: +1 585 223 9180 Fax: +65 6571 2699
www.boschsecurity.com [email protected] [email protected] www.boschsecurity.com/xc/en/contact/
www.boschsecurity.com www.boschsecurity.com www.boschsecurity.com

Data subject to change without notice | 202203101016 | V14 | March 10, 2022 © Bosch Security Systems 2022