Attachment - 3 - Cell Sizing Sheet For Battery Capacity (Unit - Common, Cooling Water System)
Attachment - 3 - Cell Sizing Sheet For Battery Capacity (Unit - Common, Cooling Water System)
Lowest Expected
Electrolyte Temp : 25 ℃
(1) (2) (3) (4) (5) (6) (7)
Change in Duration Time to End Capacity At Required Section Size
Load Load of Period of Section T Min. Rate (3) × (6) = Rated Amp Hrs
Period (amperes) (amperes) (minutes) (minutes) (KT) Pos Values Neg Values
Section 1 - First Period Only - If A2 is greater than A1, go to Section 2.
1 A1= 2396 A1-0= 2396 M1= 1 T=M1= 1 0.80 1916.80
Sec 1 Total 1916.80
Section 2 - First Two Period Only - If A3 is greater than A2, go to Section 3.
1 A1= 2396 A1-0= 2396 M1= 1 T=M1+M2= 60 1.93 4624.28
2 A2= 1304 A2-A1= -1092 M2= 59 T=M2= 59 1.93 -2107.56
Sec 2 Sub Total 4624.28 -2107.56
Total 2516.72
Section 3 - First Three Period Only - If A4 is greater than A3, go to Section 4.
1 A1= 2396 A1-0= 2396 M1= 1 T=M1+M2+M3= 90 2.27 5438.92
2 A2= 1304 A2-A1= -1092 M2= 59 T=M2+M3= 89 2.27 -2478.84
3 A2= 908 A2-A1= -396 M3= 30 T=M3= 30 1.39 -550.44
Sec 3 Sub Total 5438.92 -3029.28
Total 2409.64
Maximum Section Size 2516.7 + Random Section Size = Uncorrected Size(US) 2516.7
US 2517 × Temp. Corr. 1 × Design Margin 1 × Aging Factor 1.25 = 3145.9
Project : MD1 CFPP CELL SIZING WORK SHEET FOR COOLING WATER SYSTEM
Lowest Expected
Electrolyte Temp : 20 ℃
(1) (2) (3) (4) (5) (6) (7)
Change in Duration Time to End Capacity At Required Section Size
Load Load of Period of Section T Min. Rate (3) × (6) = Rated Amp Hrs
Period (amperes) (amperes) (minutes) (minutes) (KT) Pos Values Neg Values
Section 1 - First Period Only - If A2 is greater than A1, go to Section 2.
1 A1= 10 A1-0= 10 M1= 1 T=M1= 1 0.29 2.90
Sec 1 Total 2.90
Section 2 - First Two Period Only - If A3 is greater than A2, go to Section 3.
1 A1= 10 A1-0= 10 M1= 1 T=M1+M2= 90 2.24 22.40
2 A2= 2 A2-A1= -8 M2= 89 T=M2= 89 2.24 -17.92
Sec 2 Sub Total 22.40 -17.92
Total 4.48
Maximum Section Size 4.5 + Random Section Size = Uncorrected Size(US) 4.48
US 4.48 × Temp. Corr. 1 × Design Margin 1 × Aging Factor 1.25 = 5.6