PRODUCT INFORMATION

PUCY-P***YKA.TH (-BS)
For Europe Regulation

EN 1 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P200YKA.TH (-BS) Indoor : PEFY-P50VMHS2-E×4 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 22.40 kW ηs,c 264.6 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 22.40 kW Tj = +35 ºC EERd 4.14 %
Tj = + 30 ºC Pdc 16.51 kW Tj = + 30 ºC EERd 5.81 %
Tj = + 25 ºC Pdc 10.62 kW Tj = + 25 ºC EERd 8.13 %
Tj = + 20 ºC Pdc 6.97 kW Tj = + 20 ºC EERd 12.08 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.032 kW
Thermostat-off mode PTO 0.076 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 79.0 dB
outdoor
mg/kWh
if engine driven: fuel
Emissions of nitrogen NOx -
input
oxides GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 2 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P250YKA.TH (-BS) Indoor : PEFY-P63VMHS2-E×4 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 28.00 kW ηs,c 270.2 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 28.00 kW Tj = +35 ºC EERd 4.10 %
Tj = + 30 ºC Pdc 20.64 kW Tj = + 30 ºC EERd 5.70 %
Tj = + 25 ºC Pdc 13.28 kW Tj = + 25 ºC EERd 8.02 %
Tj = + 20 ºC Pdc 7.14 kW Tj = + 20 ºC EERd 12.22 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.032 kW
Thermostat-off mode PTO 0.076 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 80.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 3 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P300YKA.TH (-BS) Indoor : PEFY-P50VMHS2-E×6 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 33.50 kW ηs,c 233.4 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 33.50 kW Tj = +35 ºC EERd 3.25 %
Tj = + 30 ºC Pdc 24.69 kW Tj = + 30 ºC EERd 4.84 %
Tj = + 25 ºC Pdc 15.88 kW Tj = + 25 ºC EERd 6.87 %
Tj = + 20 ºC Pdc 8.23 kW Tj = + 20 ºC EERd 10.34 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.036 kW
Thermostat-off mode PTO 0.076 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 80.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 4 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P350YKA.TH (-BS)
Indoor : PEFY-P63VMHS2-E×4 units, PEFY-P50VMHS2-E×2 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 40.00 kW ηs,c 263.8 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 40.00 kW Tj = +35 ºC EERd 4.10 %
Tj = + 30 ºC Pdc 29.49 kW Tj = + 30 ºC EERd 5.26 %
Tj = + 25 ºC Pdc 18.97 kW Tj = + 25 ºC EERd 7.65 %
Tj = + 20 ºC Pdc 12.43 kW Tj = + 20 ºC EERd 12.19 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.036 kW
Thermostat-off mode PTO 0.076 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 83.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 5 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P400YKA.TH (-BS)
Indoor : PEFY-P71VMHS2-E×5 units, PEFY-P50VMHS2-E×1 unit
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 44.00 kW ηs,c 249.0 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 44.00 kW Tj = +35 ºC EERd 3.26 %
Tj = + 30 ºC Pdc 32.43 kW Tj = + 30 ºC EERd 4.62 %
Tj = + 25 ºC Pdc 20.86 kW Tj = + 25 ºC EERd 7.60 %
Tj = + 20 ºC Pdc 8.63 kW Tj = + 20 ºC EERd 11.43 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.036 kW
Thermostat-off mode PTO 0.076 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 83.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 6 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P450YKA.TH (-BS)
Indoor : PEFY-P80VMHS2-E×4 units, PEFY-P71VMHS2-E×2 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 48.00 kW ηs,c 242.2 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 48.00 kW Tj = +35 ºC EERd 3.09 %
Tj = + 30 ºC Pdc 35.40 kW Tj = + 30 ºC EERd 4.43 %
Tj = + 25 ºC Pdc 22.77 kW Tj = + 25 ºC EERd 7.39 %
Tj = + 20 ºC Pdc 10.13 kW Tj = + 20 ºC EERd 11.35 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.036 kW
Thermostat-off mode PTO 0.081 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 10500 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 84.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 7 EN
PRODUCT INFORMATION(1)
Model(s): Information to identify the model(s) to which the information relates :
Outdoor : PUCY-P500YKA.TH (-BS) Indoor : PEFY-P63VMHS2-E×8 units
Outdoor heat exchanger of air conditioner: air
Indoor heat exchanger of air conditioner: air
Type: compressor driven vapour compression
if applicable: driver of compressor: electric motor
Item Symbol Value Unit Item Symbol Value Unit
Seasonal space
cooling energy
Rated cooling capacity Prated,c 56.00 kW ηs,c 259.0 %
efficiency

Declared cooling capacity for part load at given Declared energy efficiency ratio or gas utilization efficiency /
outdoor temperatures Tj and indoor 27º/19ºC auxiliary energy factor for part load at given outdoor
(dry/wet bulb) temperatures Tj
Tj = +35 ºC Pdc 56.00 kW Tj = +35 ºC EERd 3.52 %
Tj = + 30 ºC Pdc 41.29 kW Tj = + 30 ºC EERd 4.53 %
Tj = + 25 ºC Pdc 26.57 kW Tj = + 25 ºC EERd 7.89 %
Tj = + 20 ºC Pdc 11.82 kW Tj = + 20 ºC EERd 12.14 %

Degradation co-
efficient air Cd 0.25 -
conditioners**
Power consumption in modes other than 'active
mode'
Off mode POFF 0.000 kW Crankcase heater mode PCK 0.036 kW
Thermostat-off mode PTO 0.081 kW Standby mode PSB 0.070 kW

Other items
For air-to-air air
conditioner: Nominal air
Capacity control variable - 19200 m³/h
flow rate, outdoor
measured
Sound power level,
LWA 85.0 dB
outdoor
if engine driven: mg/kWh
Emissions of nitrogen NOx fuel
-
oxides input
GCV
GWP of the refrigerant kg CO2 eq
2088 (100
years)
MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD.
Contact details Amata Nakorn Industrial Estate, 700/406 Moo 7, Tambon Don Hua Roh, Amphur
Muang, Chonburi 20000, Thailand
** If Cd is not determined by measurement then the default degradation coefficient air conditioners shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on
the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the
manufacturer or importer.
(1) This information is based on COMMISSION REGULATION(EU)2016/2281

EN 8 EN
EN 9 EN
EN 10 EN
EN 11 EN
KL79L528H02

EN 12 EN