The document provides technical specifications for a water-cooled water-chilling heat pump unit for a hotel. It includes details on the unit size, type, quantities, refrigerant used, heating and cooling capacities, energy efficiency ratings, and dimensions. It also lists the unit's electrical information and notes some non-compliances with eco-design regulations.

Uploaded by

ragu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views

ERTWF250 With VFD

The document provides technical specifications for a water-cooled water-chilling heat pump unit for a hotel. It includes details on the unit size, type, quantities, refrigerant used, heating and cooling capacities, energy efficiency ratings, and dimensions. It also lists the unit's electrical information and notes some non-compliances with eco-design regulations.

Uploaded by

ragu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Job Information

Al Shatti Hotel

Tag WTWHP VFD


Model Number RTWF250
Unit Size 250
Unit Type Standard Efficiency with AFD
Quantity 1
Product Version 240
Unit Application WWHP Med Hi Temp

General Information
Unit Type Standard Efficiency with AFD
Unit Size 250

Refrigerant Type Pre-charge (R134a)


Heating Capacity (Gross / Net) 4.96 / 4.83
IPLV

EcoDesign Compliance
SEER 6
ETAsc 227.00 %
SEER Compliance 2018 Compliant
SEER Compliance 2021 Non compliant
SEPRHT 6.01
SEPR HT Compliance 2018 Non-compliant
SEPR HT Compliance 2021 Non-compliant
SEPRMT 4.73
SEPR MT Compliance 2018 Compliant
SCOP 6.30
ETAsh 244.00
SCOP Compliance 2017 Non compliant

11/3/2020 Product Version 240


Data generation date 11/3/2020 Page 1 of 3
Job Information

Al Shatti Hotel

Tag WTWHP VFD


Model Number RTWF250
Unit Size 250
Unit Type Standard Efficiency with AFD
Quantity 1
Product Version 240
Unit Application WWHP Med Hi Temp

WWHP

Heating mode heating rejection capacity 815.8 kW Cooling mode heating capacity 991.0 kW
Heating mode heating efficiency 2.824 COP (kW/kW) Cooling mode heating efficiency 4.960 COP (kW/kW)
Heating mode refrigeration capacity 518.9 kW Cooling mode refrigeration capacity 788.6 kW
Heating mode cooling efficiency 1.747 EER (kW/kW) Cooling mode cooling efficiency 3.945 EER (kW/kW)

Heating mode leaving fluid evap 5.50 C Cooling mode leaving fluid evap 5.50 C
Heating mode flow evap 13.70 L/s Cooling mode flow evap 20.86 L/s
Heating mode entering fluid evap 14.52 C Cooling mode entering fluid evap 14.50 C
Heating mode fluid press drop evap 12.1 kPa Cooling mode fluid press drop evap 27.8 kPa

Heating mode entering fluid cond 60.00 C Cooling mode entering fluid cond 35.00 C
Heating mode flow cond 40.83 L/s Cooling mode flow cond 47.79 L/s
Heating mode leaving fluid cond 65.00 C Cooling mode leaving fluid cond 40.00 C

Heating mode net refrigeration capacity 837.7 kW


Heating mode net total power 300.0 kW
Heating mode net refrigeration eff 1.739 COP (kW/kW)

Evaporator Information
Leaving temperature Fluid type Water
Fluid flow rate Fluid concentration evap
Entering temperature
Pressure drop
Fouling factor evap 0.0176 m2-deg K/kW

Condenser Information
Leaving temperature Cond fluid type Water
Fluid flow rate Fluid concentration cond
Entering temperature
Pressure drop
Fouling factor cond 0.0440 m2-deg K/kW

Physical Information
Length 3160 mm Width 1380 mm
Height 2080 mm Shipping weight 3807 kg
Operating weight 4103 kg Sound Pressure (10m) 71 dBA
Sound power 103 dBA

11/3/2020 Product Version 240


Data generation date 11/3/2020 Page 2 of 3
Job Information

Al Shatti Hotel

Tag WTWHP VFD


Model Number RTWF250
Unit Size 250
Unit Type Standard Efficiency with AFD
Quantity 1
Product Version 240
Unit Application WWHP Med Hi Temp

Electrical Information
Unit voltage 400.0V-50.0Hz-3Ph
Max Amps 510.00 A
Total power
Unit starting current 622.00 A
Run Load Amps 470.23 A

EcoDesign Disclaimer
3. EcoDesign - For MT Process Cooling - From 1 January 2018 this product can not be placed on the European Union/Switzerland/ Turkey
markets due to non-compliance to requirements as defined in Ecodesign Regulation (EU) 2015/1095, dated 5.May 2015
4. EcoDesign - (Tier 2) - MT Process Cooling - From 1 July 2018 this product can not be placed on the European Union/Switzerland/ Turkey
markets due to non-compliance to requirements as defined in Ecodesign Regulation (EU) 2015/1095, dated 5.May 2015

Outside the scope of AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Using
Vapor Compression Cycle Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI).

11/3/2020 Product Version 240


Data generation date 11/3/2020 Page 3 of 3