Rusbox

This document is a refrigerated room load analysis for a 20ft by 9ft by 8ft room requiring refrigeration to maintain a temperature of 34°F. It analyzes the thermal loads from the walls, ceiling, floor, product inventory of 5,000 units of beer, air infiltration, lighting, and motors. The total calculated daily thermal load is 430,818 BTU/24 hours. The recommended refrigeration system would be 23,934 BTU/hr running for 18 hours per day.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views

Rusbox

This document is a refrigerated room load analysis for a 20ft by 9ft by 8ft room requiring refrigeration to maintain a temperature of 34°F. It analyzes the thermal loads from the walls, ceiling, floor, product inventory of 5,000 units of beer, air infiltration, lighting, and motors. The total calculated daily thermal load is 430,818 BTU/24 hours. The recommended refrigeration system would be 23,934 BTU/hr running for 18 hours per day.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

RUSSELL REFRIGERATED ROOM LOAD ANALYSIS

201 Thomas French Drive, Scottsboro AL 35769 Phone: 714-529-1935 Fax: 714-529-7203

Quote Number: Date: 4/11/16


Job Name: Location:
Customer Information
Company: Contact:
Address: City/State/Zip:
Phone: Fax:
E-mail:
Quoted By
Company: Contact:
Address: City/State/Zip:
Phone: Fax:
E-mail:
Room Description
Dimensions: Length: 20 Ft Width: 9 Ft Height: 8 Ft
Refrigerated Room Temp.: 34 ºF Amb. Temp.: 95 ºF Glass Doors: 1
THICKNESS INSULATION K FACTOR TEMPERATURE
Wall #1 (N): 4 In Polystyrene 0.13 95 F
Wall #2 (E): 4 In Polystyrene 0.13 95 F
Wall #3 (S): 4 In Polystyrene 0.13 95 F
Wall #4 (W): 4 In Polystyrene 0.13 95 F
Ceiling: 4 In Polystyrene 0.13 110 F
Floor: 6 In Concrete 1.25 65 F
PRODUCT LOADS:
Description #1: beer Description #2: None
Product Load: 5,000 Product Load:
Pulldown Time: 24 Pulldown Rate: 24
Entering Temp.: 80 Entering Temp.:
Sp. Ht. Above: 0.8 Sp. Ht. Above:
Sp. Ht. Below: 0.4 Sp. Ht. Below:
Freezing Point: 28 Freezing Point:
Latent Heat: 100 Latent Heat:
Total Inventory: 0 Total Inventory:
Heat of Respir.: 0 Heat of Respir.:
*Final Prod. Temp.: 34 34
AIR CHANGE LOAD:
Infiltrating Air Temp.: 75 ºF Dry Bulb and 65 ºF Wet Bulb at 1.5 times ASHRAE standard
MISCELLANEOUS LOADS:
People 1 Lighting: 0.5 Watts per SQ. Ft.
Motor HP: 0.5 Misc. Loads 0 BTUH
CALCULATED RESULTS:
Surface Loads: 66,712 BTU/24 Hrs Percent of Total: 15%
Product Loads: 202,400 BTU/24 Hrs Percent of Total: 47%
Air Change Loads: 44,031 BTU/24 Hrs Percent of Total: 10%
Miscellaneous Loads: 117,674 BTU/24 Hrs Percent of Total: 27%
Daily Total Load: 430,818 BTU/24 Hrs
TOTAL CALCULATED REQUIREMENT 23,934 Btuh @ 18 HOURS PER DAY RUN TIME
Equipment
Number of systems: System Model Number: 0 #N/A Refrigerant
Altitude (Ft): 0 System Voltage: #N/A
Capacity per System: 0 BTUH Calculated Run Time: 0.0 Hrs
System T.D.: 0.0 Total Price: $ -
Price Each Sys.: Total Warranty: $ - Net
Warranty Price Each: Net

Comments:

In no event shall Russell be liable for special or consequential damages in connection with the use or output of
the Russell Refrigerated Room Load Analysis software. Check Inventory here: http://russell.htpgusa.com

4/11/2016