Schedule of Loads and Computations
Schedule of Loads and Computations
LOAD WATTS AMPERES VOLTS CIRCUIT SIZE OF CONDUCTORS 250 VOLTS 2-WIRE
CKT. NO.
BREAKER & CONDUIT PIPE
14-LIGHTING OUTLETS @
1 (50 VA EACH) 700 3.04 A. 230 20 A.
2-8.0 mm.
14-LIGHTING OUTLETS @ SERVICE METER
2 (50 VA EACH) 700 3.04 A. 230 20 A. M
17-LIGHTING OUTLETS @
3 (50 VA EACH) 850 3.70 A. 230 20 A.
11-CONVENIENCE OUTLETS @ 40 AT
4 1,980 8.61 A. 230 30 A.
180 VA EACH
11-CONVENIENCE OUTLETS @ 20 AT 20 AT
5 1,980 8.61 A. 230 30 A.
180 VA EACH L.O. 1 2 L.O.
20 AT 30 AT
6 1-AIRCONDITION OUTLET 1,500 6.52 A. 230 30 A. L.O. 3 4 C.O.
30 AT 30 AT
7 SPARE 230 30 A. C.O. 5 6 ACU
30 AT 30 AT
8 SPARE 230 30 A. SPARE 5 6 SPARE
TOTAL VA = 7,710 WATTS
SIZE OF FEEDER:
TOTAL CURENT = 33.52 AMP.
PVC CONDUIT PNS.14
AMPACITY OF FEEDER = 33.52 AMP. X 1.25
& 40 AT, 2P, 220V, 60 HZ MOULDED CASE CIRCUIT BREAKER DISTRIBUTION PANEL
= 41.90 AMPS.
FEED FROM: AKELCO TOTAL LOAD: 33.52 AMP.