Introduction:
MCB or MCCB are widely used in electrical distribution system for ON/OFF Electrical supply and it also gives over current
and short circuit protection. Selection of MCB or MCCB involved technical, Mechanical parameters. Some parameters are
important but some parameters are confusing and mislead to wrong selection of MCCB. Some parameters are directly
affected on cost of MCCB.
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 1/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
(D) Accessories:
Rotary Handle: Extended/ Direct
Alarm Contact:
Shunt Trip:
Under voltage Trip:
Mechanical interlocking:
Manual /Auto operation
Motorized Operation:
(F) Others:
Frequency;
Reference temperature: (if different from 30°C)
Pollution degree:
Suitability for isolation:
Type of Mounting arrangement
Electrical Life Cycles:
Mechanical Life Cycles:
Dimension: mm
Weight: Kg
Reference Standard: IEC: 60947-1/2, IS: 13947-1/2
Breaker Frame Size indicates the basic framework of the Plastic shell of MCCB that can hold the biggest rated
current.
It is the maximum current value for which the MCCB is designed (upper limit of the adjustable trip current range) and it
also determines the physical dimensions of the device.
There are varieties current ratings MCCB for the same series frame Size.
For example, DX100 Frame Size MCCB for rated current of 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A.
Same DX225 Frame Size MCCB for rated current of 100A, 125A, 160A, 180A, 200A, 225A.
In above DX100 and DX225 has two Type of frame Size for rated current of 100A, but the shape and size of breaking
capacity of circuit breakers is not the same.
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 3/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
If a fault above the Ics but below the Icu occurs, the MCCB can interrupt it successfully but will need a replacement
due to the damage suffered.
The Main difference between Ultimate Short Circuit (Icu) and Service Breaking Capacity (Ics) that Icu (Ultimate
Braking Capacity) means Circuit breaker can remove the fault and remain usable but Ics (Service Braking Capacity)
means Circuit breaker can remove the fault, but it may not be usable afterwards.
For example, if a circuit breaker has an Ics of 25,000 Amperes and an Icu of 40,000 Amperes:
Any fault below 25kA will be cleared with no problem.
A fault between 25kA and 40kA will cause permanent damage when cleared.
Any current exceeding 40 kA can’t be cleared by this breaker.
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 4/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
Type B MCCB:
Operating Current: This type of MCB trips between 3 and 5 times rated current (In).
Operating Time:04 To 13 Sec
For example a 10A device will trip at 30-50A.
Application: Domestic applications or light commercial applications where connected loads are primarily lighting
fixtures, domestic appliances with mainly restive elements.
Suitable for: Restive Load application (Lighting , Small Motor)
Surge Current: The surge current level is relatively low.
Installation at: At Sub feeder of Distribution Board.
Type C MCCB:
Operating Current: This type of MCB trips between 5 and 10 times full load current.
Operating Time:04 To 5 Sec
Application: commercial or industrial type of applications, fluorescent lighting, motors etc where there could be
chances of higher values of short circuit currents in the circuit.
Suitable for: Inductive Load application (Pumps, Motor, fluorescent lighting.)
Surge Current: The surge current level is relatively moderate level.
Installation at: At incoming / Outgoing of Distribution Board.
Type D MCCB:
Operating Current: This type of MCB trips between 10 and 20 times full load current.
Operating Time:04 To 3 Sec
Application: specialty industrial / commercial uses (Transformers or X-ray machines, large winding motors, discharge
lighting, large battery charging). Where current inrush can be very high.
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 5/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
Type K MCCB:
Operating Current: This type of MCB trips between 8 and 12 times full load current.
Operating Time:04 To 5 Sec
Application: Suitable for inductive and motor loads with high inrush currents.
Surge Current: The surge current level is relatively High
Installation at: At incoming of Distribution Board / Panels.
Type Z MCCB:
Operating Current: This type of MCB trips between 2 and 3 times full load current.
Operating Time:04 To 5 Sec
Application: These types of MCBs are highly sensitive to short circuit and are used for protection of highly sensitive
devices such as semiconductor devices.
Surge Current: The surge current level is relatively too low
Installation at: At Sub feeder of Distribution Board for IT equipment.
(D) Accessories:
(1) Rotary Handle:
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 6/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
It used to trip MCCB in under voltage condition (70 to 35% of rated Voltage).
(E) Others:
(1) Frequency:
MCB is designed and used in AC power system of 50 to 60Hz.
Electromagnetic force of magnetic release is related with power supply frequency so If Frequency is changed than
electromagnetic fore of Magnetic element is changed hence MCCB tripping current will be different.
If we used MCCB for protection in DC circuits than specially design DC circuit MCCB should be used rather than
normal type of MCCB.
(2) Isolation:
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 8/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 9/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
No. of Poles: 3
Thermal: Fixed
Magnetic: Fixed
Weight: 0.84Kg
Pollution Degree 0 to 2 3
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 10/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers
Low current circuits (homes, shops, school High power rating i.e. commercial and industrial
Suitable for
and offices). use
Example: what should we select MCB or MCCB for current carrying capacity 100A and breaking capacity 15KA and cost
is a not main criteria.
For this rating both MCB and MCCB are available so we should consider application and other facilities to choose
MCB or MCCB.
If we want to use it at indoor purpose, having less Space and if we do not need tripping adjustment and other function
or accessories than MCB is best option.
If we want to use it at indoor / Outdoor purpose, having Space and need tripping adjustment for coordination with
other MCCB, We need Interlocking for safety and other function or accessories than MCCB is best option.
Pollution Degree 2 3
Application Current AC AC or DC