How To Select MCB - MCCB - Controlmakers

The document discusses how to select the appropriate miniature circuit breaker (MCB) or molded case circuit breaker (MCCB) for an electrical distribution system. It outlines key specifications to consider, including current ratings, voltage ratings, number of poles, utilization category, and short circuit breaking capacity. The utilization categories (B, C, D curves) determine the trip characteristics and suitable applications for different types of loads like resistive, inductive, or combined loads. Selecting the proper ratings and characteristics for the MCCB ensures overcurrent and short circuit protection for the intended electrical system application and loads.

Uploaded by

Peter K Paul
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
330 views

How To Select MCB - MCCB - Controlmakers

The document discusses how to select the appropriate miniature circuit breaker (MCB) or molded case circuit breaker (MCCB) for an electrical distribution system. It outlines key specifications to consider, including current ratings, voltage ratings, number of poles, utilization category, and short circuit breaking capacity. The utilization categories (B, C, D curves) determine the trip characteristics and suitable applications for different types of loads like resistive, inductive, or combined loads. Selecting the proper ratings and characteristics for the MCCB ensures overcurrent and short circuit protection for the intended electrical system application and loads.

Uploaded by

Peter K Paul
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

How to select MCB / MCCB


BY ADMIN · JULY 27, 2017

Introduction:
MCB or MCCB are widely used in electrical distribution system for ON/OFF Electrical supply and it also gives over current
and short circuit protection. Selection of MCB or MCCB involved technical, Mechanical parameters. Some parameters are
important but some parameters are confusing and mislead to wrong selection of MCCB. Some parameters are directly
affected on cost of MCCB.

Specification / Name Plate Details of MCB/MCCB:


Following specifications are required to select appropriate MCB or MCCB.

(A) Current Related:


Frame Size (Inm): Amp
Rated current (In/ Ie): Amp
Ultimate short circuit breaking capacity (Icu): KA
Rated short-circuit breaking capacity (Ics): % of Icu

(B) Voltage Related:


Rated voltage (Ue): Volt
Rated Insulation voltage (Ui): Volt
Rated impulse withstand voltage(Uimp): KV
No’s of Pole : SP,DP,TP,TPN,FP

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 1/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

(C) Application Type:


Utilization Category/ Characteristic : B,C or D curve

(D) Accessories:
Rotary Handle: Extended/ Direct
Alarm Contact:
Shunt Trip:
Under voltage Trip:
Mechanical interlocking:
Manual /Auto operation
Motorized Operation:

(E) Protection Type:


Protection : Over current / Short circuit
Trip Mechanism: Thermal / Magnetic / Solid / Microprocessor
Trip Mechanism adjustment : Fixed / Adjustable

(F) Others:
Frequency;
Reference temperature: (if different from 30°C)
Pollution degree:
Suitability for isolation:
Type of Mounting arrangement
Electrical Life Cycles:
Mechanical Life Cycles:
Dimension: mm
Weight: Kg
Reference Standard: IEC: 60947-1/2, IS: 13947-1/2

(A) Current Related:


(1) Frame Size (Inm):
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 2/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Breaker Frame Size indicates the basic framework of the Plastic shell of MCCB that can hold the biggest rated
current.
It is the maximum current value for which the MCCB is designed (upper limit of the adjustable trip current range) and it
also determines the physical dimensions of the device.
There are varieties current ratings MCCB for the same series frame Size.
For example, DX100 Frame Size MCCB for rated current of 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A.
Same DX225 Frame Size MCCB for rated current of 100A, 125A, 160A, 180A, 200A, 225A.
In above DX100 and DX225 has two Type of frame Size for rated current of 100A, but the shape and size of breaking
capacity of circuit breakers is not the same.

(2) Rated Current (In /Ie):


It is the current value above which overload protection is tripped.
For MCB it is fixed while in MCCB the rated current is an adjustable range instead of a fixed value.
Standard rating of MCB is 1A, 2A, 3A, 4A, 6A, 10A, 13A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 100A for MCB.

(B) Voltage Related:


(3) Ultimate short-circuit breaking capacity (Icu):
Breaking capacity can be defined as the maximum level of fault current which can be safely cleared.
It is the highest fault current that the MCCB can trip without being damaged permanently.
The MCCB will be reusable after interrupting a fault, as long as it doesn’t exceed this value.
It is indicate operation reliability of MCCB
This parameter may increase or decrease the cost, so it should be properly decided. Breaking capacity should be
higher than the possible fault level. For domestic application fault level may be 10kA.

(4) Operating short-circuit breaking capacity (Ics):


It is expressed as a percentage ratio of Icu and tells you the maximum short-circuit current if a circuit breaker can
break three times and still resume normal service.
The higher the lcs, the more reliable the circuit breaker
It is the maximum possible fault current that the MCCB can clear. If the fault current exceeds this value, the MCCB will
be unable to trip and another protection mechanism must operate.

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 3/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

If a fault above the Ics but below the Icu occurs, the MCCB can interrupt it successfully but will need a replacement
due to the damage suffered.
The Main difference between Ultimate Short Circuit (Icu) and Service Breaking Capacity (Ics) that Icu (Ultimate
Braking Capacity) means Circuit breaker can remove the fault and remain usable but Ics (Service Braking Capacity)
means Circuit breaker can remove the fault, but it may not be usable afterwards.
For example, if a circuit breaker has an Ics of 25,000 Amperes and an Icu of 40,000 Amperes:
Any fault below 25kA will be cleared with no problem.
A fault between 25kA and 40kA will cause permanent damage when cleared.
Any current exceeding 40 kA can’t be cleared by this breaker.

(5) Rated working voltage (Ue):


It is the continuous operation voltage for which the MCCB is designed.
This value is typically equivalent or close to a standard system voltage.
In three phase it is usually 400V or 415 V. For single phase it is 230V or 240V.

(6) Rated Insulation voltage (Ui):


It is the maximum voltage that the MCCB can resist according to laboratory tests.
It is higher than the rated working voltage, in order to provide a margin of safety during field operation.

(7) Rated impulse withstands voltage (Uimp):


It is the value of transient peak voltage the circuit-breaker can withstand from switching surges or lighting strikes
imposed on the supply.
This value characterizes the ability of the device to withstand transient over voltages such as lightning (standard
impulse 1.2/50 μs).
Uimp = 8kV means Tested at 8 kV peak with 1.2/50μs impulse wave.

(8) Number of Poles:


No of Pole for MCCB depends on Single Phase & Three Phase Power Controlling /Protection
Single Pole (SP) MCB:
A single pole MCB provides switching and protection for one single phase of a circuit.
Used: for Single Phase circuit
Double Pole (DP) MCB:
A two Pole MCB provides switching and protection both for a phase and the neutral.
Used: for Single Phase circuit
Triple Pole (TP) MCB:
A triple/three phase MCB provides switching and protection only to three phases of the circuit and not to the neutral.
Used: for Three Phase circuit
3 Pole with Neutral (TPN (3P+N) MCB):
A TPN MCB, has switching and protection to all three phases of circuit and additionally Neutral is also part of the MCB
as a separate pole. However, Neutral pole is without any protection and can only be switched.
Used: for Three Phase circuit with Neutral
4 Pole (4P) MCB:
A 4 pole MCB is similar to TPN but additionally it also has protective release for the neutral pole. This MCB should be
used in cases where there is possibility of high neutral current flow through the circuit as in cases of an unbalanced
circuit.

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 4/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Used: for Three Phase circuit with Neutral

(9) Utilization category / Characteristic (B, C, D, K, Z curve):


Characteristic of Trip curves of MCCB tell about the trip current rating of MCCB.
MCB will trip instantaneously according to their Tripping Characteristic at 0.1 sec.
There are various type of MCCB
Type B MCCB
Type C MCCB
Type D MCCB
Type K MCCB
Type Z MCCB

Type B MCCB:
Operating Current: This type of MCB trips between 3 and 5 times rated current (In).
Operating Time:04 To 13 Sec
For example a 10A device will trip at 30-50A.
Application: Domestic applications or light commercial applications where connected loads are primarily lighting
fixtures, domestic appliances with mainly restive elements.
Suitable for: Restive Load application (Lighting , Small Motor)
Surge Current: The surge current level is relatively low.
Installation at: At Sub feeder of Distribution Board.

Type C MCCB:
Operating Current: This type of MCB trips between 5 and 10 times full load current.
Operating Time:04 To 5 Sec
Application: commercial or industrial type of applications, fluorescent lighting, motors etc where there could be
chances of higher values of short circuit currents in the circuit.
Suitable for: Inductive Load application (Pumps, Motor, fluorescent lighting.)
Surge Current: The surge current level is relatively moderate level.
Installation at: At incoming / Outgoing of Distribution Board.

Type D MCCB:
Operating Current: This type of MCB trips between 10 and 20 times full load current.
Operating Time:04 To 3 Sec
Application: specialty industrial / commercial uses (Transformers or X-ray machines, large winding motors, discharge
lighting, large battery charging). Where current inrush can be very high.

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 5/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Suitable for: Inductive- Capacitive Load application (Pumps, Motor)


Surge Current: The surge current level is relatively High
Installation at: At incoming of Distribution Board / Panels.

Type K MCCB:
Operating Current: This type of MCB trips between 8 and 12 times full load current.
Operating Time:04 To 5 Sec
Application: Suitable for inductive and motor loads with high inrush currents.
Surge Current: The surge current level is relatively High
Installation at: At incoming of Distribution Board / Panels.

Type Z MCCB:
Operating Current: This type of MCB trips between 2 and 3 times full load current.
Operating Time:04 To 5 Sec
Application: These types of MCBs are highly sensitive to short circuit and are used for protection of highly sensitive
devices such as semiconductor devices.
Surge Current: The surge current level is relatively too low
Installation at: At Sub feeder of Distribution Board for IT equipment.

(D) Accessories:
(1) Rotary Handle:

It is used to extend ON/OFF handle of MCCB when Panel Door is closed.


It is also used to indicate ON/OFF or Trip Position

(2) Shunt Trip:

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 6/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Used for Remote Tripping

(3) Alarm contact:

It gives Tripping Indication when MCCB Trip.


It does not give when MCCB is in normal condition (either ON or OFF)

(4) Auxiliary contact:

It used for remote signaling and control purpose.


It is also give ON/OFF indication of MCCB at remote location.

(5) Under Voltage Tripping:


https://controlmakers.ir/en/how-to-select-mcb-mccb/ 7/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

It used to trip MCCB in under voltage condition (70 to 35% of rated Voltage).

(6) Mechanical Interlocking:

It used to mechanical interlock of two MCCB on the same Panel.

(7) Manual / Auto:


MCCB may have provision for Auto /Manual operation.
An “auto/manual” switch in front of Panel.
When set to the “Manual” position, lock out electrical control and when set to “auto”, lock out the manual control;
remote indication

(8) Motorized operation:


MCCB may have option for manual operation or with a motor mechanism for electrically controlled

(E) Others:
(1) Frequency:
MCB is designed and used in AC power system of 50 to 60Hz.
Electromagnetic force of magnetic release is related with power supply frequency so If Frequency is changed than
electromagnetic fore of Magnetic element is changed hence MCCB tripping current will be different.
If we used MCCB for protection in DC circuits than specially design DC circuit MCCB should be used rather than
normal type of MCCB.

(2) Isolation:
https://controlmakers.ir/en/how-to-select-mcb-mccb/ 8/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

MCCB is suitability for visible isolation. It is particularly important.


If a circuit breaker is turned off, it should indicate so visibly.
It should not be able to indicate otherwise if the contacts are not open. In other words, it offers proof of isolation.

(3) Type of Mounting Arrangement:


According to mounting arrangement, MCBs can be divided into two categories.
DIN rail mount MCCB
Plug-in MCCB
DIN Rail Mount MCB
The main advantage of this type of MCB is versatility
DIN rails are used by many different types of electrical and communications equipment, and they are mainstream in
industrial settings.
They can be easily integrated into nearly any control or protection system.
A disadvantage of this type of MCB is that more work is required for installation, and plug-in MCBs may be a better
choice for simple installations.
Plug-In MCB
These MCBs are easy for installation. As name indicates, they just have to be plugged into a compatible electric
panel.
Plug-in MCBs are suitable for applications that use circuit breakers exclusively- typically residential and commercial
electrical distribution systems.
When using plug-in MCBs it is important that the breakers and the panel must match. It is not an issue when both are
of the same brand

(4) Pollution degrees:


It determines in what kind of environment circuit breakers can be installed.
In a Domestic purpose where there is no dust no humidity, the circuit breaker is comfortable.
For Domestic purpose pollution degree 2 is suitable.
But in an outdoor public installation where there may be dust which cause leakage currents and lead to dangerous
arcs.
For dusty pollution, humidity environment or outdoor type heavy-duty applications (incoming switchboards) pollution
degree 3 is suitable.

(5) Energy Class:


MCB need some time for tripping, In this time, fault current will create some energy which will exist in system.
This energy is termed as release energy. For efficient MCB operation it should be in within limited. On basis of amount
of release energy it is classified in class 1, class 2 and class 3.
Class 3 is best which allows maximum 1.5L joule/second.

Example of MCB / MCCB specification / Name Plate:


Frame: F750

Rated Operational Voltage (Ue): 415V

Rated Insulation Voltage (Ui) : 690V

Rated Impulse withstand Voltage (Uimp): 6KV

Rated Current (Ie) : 80A

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 9/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Ultimate Breaking Capacity (Icu): 10KA

Service Breaking Capacity (Ics) : 75 % of Icu

Utilization Category : A Type

No. of Poles: 3

Suitability for Isolation: Yes

Electrical Life Cycles : 5000

Mechanical Life Cycles: 25000

Release Type : Thermal – Magnetic

Thermal: Fixed

Magnetic: Fixed

Terminal Capacity Cable: 50 mm2

Dimensions (mm) WXHXD : 75X130X60

Weight: 0.84Kg

Operating Temp Range: -5 to +50°C

Reference Temperature: 50°C

Main factors affected on cost of MCCB for same rating


Short circuit Capacity
No of Poles
Type of Application (Characteristic Type)
Type of Trip Mechanism (Thermal-Thermal-Magnetic, Solid, Microprocessor)
Accessories

What should we select MCB or MCCB


The selection of MCB or MCCB depends upon your application. Main difference between MCB and MCCB is

Characteristics MCB MCCB

Standard IEC60898-1 IEC60947-2

Rated current 6A to 100A 10A to 2500A.

Interrupting rating Up to 18KA 10KA to 200KA

Trip Mechanism Thermal / Magnetic Thermal / Magnetic / Static

Fixed /AdjustableThermal operated for overload


Trip characteristics Settings Not adjusted and Magnetic operation for instant trip in Short
circuit conditions

Application Indoor Type Indoor / Outdoor Type

Pollution Degree 0 to 2 3

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 10/11
11/14/23, 11:55 AM How to select MCB / MCCB - Controlmakers

Low current circuits (homes, shops, school High power rating i.e. commercial and industrial
Suitable for
and offices). use

This is designed for unskilled user /


This is designed for skilled user and supposed
User uninstructed user and not being maintained
to be maintained properly
consequently

over current / Short Circuit / Earth Fault


Type of Protection over current protection
protection

Mounting Rail Mounted Rail / Fixed / Draw out Mounted

Operating Mechanism Electrical /Mechanical Operating Electrical /Mechanical / Motorized Operating

Example: what should we select MCB or MCCB for current carrying capacity 100A and breaking capacity 15KA and cost
is a not main criteria.

For this rating both MCB and MCCB are available so we should consider application and other facilities to choose
MCB or MCCB.
If we want to use it at indoor purpose, having less Space and if we do not need tripping adjustment and other function
or accessories than MCB is best option.
If we want to use it at indoor / Outdoor purpose, having Space and need tripping adjustment for coordination with
other MCCB, We need Interlocking for safety and other function or accessories than MCCB is best option.

Characteristics IEC 60898-1 (MCB) IEC 60947-2 (MCCB)

Rated Current: In 6 – 125A 0.5 – 160A

SC Breaking Capacity <25kA <50kA

Rated Voltage: Ue 400V 440V, 500V, 690V

Impulse Voltage: Uimp 4kV 6kV – 8kV

Pollution Degree 2 3

Curves B,C,D B,C,D,K,Z,MA

Application Current AC AC or DC

Application Residential Residential / Commercial / Industrial

https://controlmakers.ir/en/how-to-select-mcb-mccb/ 11/11