LCD Programmer Product Guide VESDA®
ii
VESDA® LCD Programmer Product Guide
Intellectual Property and Copyright
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners.
Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute,
transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis.
Disclaimer
The contents of this document is provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or
specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including
without limitation any implied warranties of merchantability and fitness for a particular purpose are expressly excluded.
General Warning
This product must only be installed, configured and used strictly in accordance with the General Terms and Conditions, User Manual and
product documents available from Xtralis. All proper health and safety precautions must be taken during the installation, commissioning
and maintenance of the product. The system should not be connected to a power source until all the components have been installed.
Proper safety precautions must be taken during tests and maintenance of the products when these are still connected to the power source.
Failure to do so or tampering with the electronics inside the products can result in an electric shock causing injury or death and may cause
equipment damage. Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the
equipment and/or failure to take proper precautions. Only persons trained through an Xtralis accredited training course can install, test and
maintain the system.
Liability
You agree to install, configure and use the products strictly in accordance with the User Manual and product documents available from
Xtralis.
Xtralis is not liable to you or any other person for incidental, indirect, or consequential loss, expense or damages of any kind including
without limitation, loss of business, loss of profits or loss of data arising out of your use of the products. Without limiting this general
disclaimer the following specific warnings and disclaimers also apply:
Fitness for Purpose
You agree that you have been provided with a reasonable opportunity to appraise the products and have made your own independent
assessment of the fitness or suitability of the products for your purpose. You acknowledge that you have not relied on any oral or written
information, representation or advice given by or on behalf of Xtralis or its representatives.
Total Liability
To the fullest extent permitted by law that any limitation or exclusion cannot apply, the total liability of Xtralis in relation to the products is
limited to:
(i) in the case of services, the cost of having the services supplied again; or
(ii) in the case of goods, the lowest cost of replacing the goods, acquiring equivalent goods or having the goods repaired.
Indemnification
You agree to fully indemnify and hold Xtralis harmless for any claim, cost, demand or damage (including legal costs on a full indemnity
basis) incurred or which may be incurred arising from your use of the products.
Miscellaneous
If any provision outlined above is found to be invalid or unenforceable by a court of law, such invalidity or unenforceability will not affect the
remainder which will continue in full force and effect. All rights not expressly granted are reserved.
Document Conventions
The following typographic conventions are used in this document.
Convention Description
Convention Description
i
LCD Programmer Product Guide VESDA®
Contact Us
ii
VESDA® LCD Programmer Product Guide
Contents
Scope ................................................................................................................................................1
iii
LCD Programmer Product Guide VESDA®
iv
VESDA® LCD Programmer Product Guide
1.1 Scope
The VESDA LCD Programmer Product Guide contains comprehensive information about the
features, installation, and use of the LCD Programmer.
The VESDA LCD Programmer Product Guide is written for people who are involved in the
design, purchase, installation, commissioning, monitoring, maintenance, and management of a
VESDA system.
Legend
A Display
B Soft Keys
C Hard Keys
1
LCD Programmer Product Guide VESDA®
The LCD Programmer module can be placed either in the center or the right plate of a
LaserPLUS or LaserSCANNER detector Front Cover, or in a VESDA Remote Mounting System.
For further information see the VESDA Remote Systems Product Guide.
Legend
A Display
B Soft Keys
C Hard Keys
2
VESDA® LCD Programmer Product Guide
Product Specifications
Supply Voltage 18 to 30 VDC
Push Button Keys 2 rows x 4 keys, each key 19 mm x 12 mm (0.75 in x 0.50 in)
USR = Operator
Default User Level
ADM = Administrator
IDs
DST = Distributor
Operating o o o o
Ambient: 0 to 39 C (32 to 103 F)
Temperature
Current at 24
Power Usage Power at 24 VDC
VDC
Min 0.6 W 20 mA
Module
Max 2.3 W 80 mA
Min 1.3 W 50 mA
Hand-held
Max 3.0 W 110 mA
Min 1.3 W 50 mA
Remote
Max 3.0 W 110 mA
3
LCD Programmer Product Guide VESDA®
Inches 3.9 x 5.1 x 1.21 4.1 x 5.3 x 2.4 5.5 x 5.9 x 3.5
Legend
B Soft Keys
C Hard Keys
4
VESDA® LCD Programmer Product Guide
User Access
Functional Authorization
Level Level
5
LCD Programmer Product Guide VESDA®
6
VESDA® LCD Programmer Product Guide
Soft Directional Key/ Soft • Moves Cursor to the left or right of the screen
Key Function • Scrolls highlighted item left/right
• Actions a soft key question
Soft Directional Key/ Soft • Moves the cursor up or down on the screen
Key Functions • Scrolls the Menu up or down
• Actions a soft key question
Hard Forward Action Key • Moves down the Menu tree by selecting the
↵ •
highlighted option
Adds selected letter
• Toggles between values
• Can be used to run Normalize, Autolearn, and
System/Address control commands
7
LCD Programmer Product Guide VESDA®
2. Logon 7. Status
16. Change-Over
Times
17. Weekend
18. Holidays
26. Normalize
27. Filter
31. Relays/Disp
Connected
34. Latching
39. Communications
40. Miscellaneous
41. LaserSCANNER
Detector
8
VESDA® LCD Programmer Product Guide
.
41. LaserSCANNER
Detector
42. Status
51. Change-Over
Times
52. Weekend
53. Holidays
54. Scanner
55. Scanner Delays
65. Normalize
66. Filter
70. Relays/Disp
Connected
73. Latching
75. Diagnostics
76. Relay Test
77. Factor Defaults
78. Communications
9
LCD Programmer Product Guide VESDA®
.
From Screen 3 From Screen 80. LaserCOMPACT
5 & 139
81. Status
95. Normalize
96. Filter
101. Diagnostics
102. Relay Test
103. Factory Defaults
104. Communications
105. Miscellaneous
106. Ancillary
107. Display/Rly
108. Status
111. Location
114. Relays/Disp
Connected
117. Latching
118. Beeper
121. Communications
122. Miscellaneous
123. Programmer
10
VESDA® LCD Programmer Product Guide
.
123. Programmer
124. Status
126. Location
130. Communications
131. Miscellaneous
132. HLI
133. Status
143. AutoLearn
137. Communications
144. Set Date & Time
145. Weekend
146. Holidays
147. Users
152. Filter
153. Reference
Detector
155. Communications
157. Miscellaneous
158. Show
Wiring Order
159.LCD
Screen
11
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
1. Main Menu - This screen is displayed when the LCD Programmer is first powered USR
up, or is in a standby mode. Press any key to go to the Logon Screen (Screen 2)
2.
Logon - Use the , , + and - keys to enter the User. USR
Use the and the ↵ keys to move the cursor to the PIN field.
Use the + and - keys to enter the PIN
3. VESDA LaserPLUS - This screen displays options available for accessing and USR
managing the parameters of VESDA Laser range of products connected to
VESDAnet. The Options are:
• Setup By Address
• Setup By Type
• System /All Devices
• Show Wiring Order
• LCD Screen
4. Setup By Address (Setup By Zone) - Once VESDA Zone numbers and names USR
are allocated, this screen lists all the VESDA Zone numbers and names on
VESDAnet. All devices without a VESDA Zone number are grouped in an
unconfigured devices menu. The Ancillary devices include programmers, HLI, and
SRMs.
5. Address (Zone) Number and Name - Lists all devices in the particular VESDA USR
Zone.
6. Address with a VESDA LaserPLUS Detector - Lists functions available for USR
accessing and managing the properties of the selected VESDA LaserPLUS
detector. Select the required option and press ↵ .
12
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
10. Select Events - This function assists in easier viewing of the logged events. The ADM
events can be sorted as per the categories displayed. After selecting the events,
proceed to Screen 9 to view the events.
• End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
• End Time - This is the time up to which events will be displayed for viewing. You
can input the required time in the time field.
• Events to view -
- Smoke Level - A against Smoke Level will display logged smoke levels
- Alarms - A against Alarms displays a log of alarms
- Faults - A against Faults displays a log of the logged faults
- User Action - To view a log of user actions place a against user action
- Clear Log - This function is only available with DST access.
To clear the log of events highlight Start and press ↵ .
Use the + key to place a and - key to insert a X and deselect the option.
11. Zone Control - The four functions under Zone/Address control are the same as USR
the functions performed by the buttons on the display module.
• Mode - This controls the mode of the Multi-Segment LCD display on any display
connected to that zone. Use the +, -, and the ↵ keys to change the mode
- Sensitivity - Displays the sensitivity level of Fire 1
- Smoke - Displays the current smoke level
- Address Number - Displays the assigned Address number for the detector
• Silence - Silences the beeping sound of the detector
• Reset - Resets fire and fault conditions
• Isolate - Starts and stops isolation of the detector
12. Smoke Thresholds - This screen lists screens 13 to 19 as options available for ADM
setting smoke thresholds.
13. Day Thresholds - This screen allows viewing and changing the current Fire 2, Fire ADM
1, Action and Alert thresholds for day time.
13
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
14. Night Thresholds - This screen allows viewing and changing the current Fire 2, ADM
Fire 1, Action and Alert thresholds for night time.
15. Alarm Delays - In this screen insert the required time delay (in seconds) before an ADM
alarm is generated at Fire 2, Fire 1, Action, or Alert level. This screen also offers
the option of simultaneous or cumulative delay times before the alarm is
generated. The instant fire alarm option can be enabled or disabled in this screen.
16. Change-Over Times - Insert the time to switch from day to night thresholds and ADM
night to day thresholds. By default day start and night start have been set at
07:00:00 and 19:00:00 respectively.
17. Weekend - Placing a against the relevant week day will denote it as being ADM
weekend. By default Saturday and Sunday are set as weekend days.
18. Holidays - Insert the first and the last day of holidays to set the different smoke ADM
thresholds during this period.
14
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
19. Smoke Change - The change in obscuration rate mentioned here will register the ADM
event in the event log. This is subject to the change occurring over the interval
DST
period that is input. You can input the required obscuration and interval.
• Change By
• Min. Interval
20. AutoLearn - The AutoLearn function will automatically set the fire thresholds. The ADM
detector measures the ambient smoke level over the set period and will establish
the smoke and alarm thresholds accordingly. Enter the number of days, hours and
minutes over which the AutoLearn function is to apply.
21. Address Number - Assign the VESDA Zone number to the detector. ADM
22. Address Name/Location - Allocate a VESDA Zone name and location and assign ADM
these to the respective detector.
23. Air Flow - This screen lists the options available to monitor and manage air flows. ADM
• Flow Thresholds
• Flow Control
• Normalize
24. Flow Thresholds - Input the required High Urgent, High Minor, Low Minor and ADM
Low Urgent air flow thresholds. Enter the time over which the air flow should be
monitored above and below the threshold levels. An appropriate urgent or minor air
flow fault will be generated once the air flow crosses the threshold and remains
above or below the threshold for the period set as “Delay”.
15
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
25. Flow Control - Allows you to change the aspirator speed for VESDA LaserPLUS ADM
and LaserSCANNER. Enter the pipes in use by placing a against the
respective pipe. Default: 3000rpm, Min. 3000rpm, Max 4200rpm
26. Normalize - The Normalize screen displays the current air flow rates and the ADM
current raw flow for each pipe in use. To normalize the air flow highlight Start and
press ↵ .
Note: Normalizing air flow takes approximately 11 minutes. Ensure that the pipes
in use have been (screen 25) before commencing normalization.
27. Filter - Displays details on the life and usage of the filter. When the filter is replaced ADM
with a new filter, highlight Start and press ↵ to restart the dust count and due date
DST
for replacement. The service interval for filter replacements can be entered to suit
the ambient conditions of the VESDA Zone in which the detector is installed.
• Life Used
• Date Due
• Service Interval
• New Filter
• Dust Count
• Dust Limit
Default: 1825 days (5 years), Min. 1 day, Max 3655 days (10 years)
28. Reference Detector - If a reference detector is connected to VESDAnet, enter the: ADM
• Reference Address Number
• Dilution Factor - This is the factor by which the background levels have to
reduce to reach the levels of the current VESDA Zone
• Delay - This is the time taken for the current VESDA Zone to return to its
ambient levels after background from the Reference Address is introduced.
29. Rebuild Address List - Highlight Start and press ↵ to rebuild the Address List. ADM
Use this option to rebuild the Address List after removing a display module
assigned to the detector.
30. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the Intelligent Power Supply is not being used enter “0”.
31. Relays/Disp Connected - This screen displays the number of relays connected to ADM
the detector. It also indicates if the detector is a LaserSCANNER.
Default: None (display only), Min./Max Selectable
32. Relay Setup - This screen and its sub-menus allow setting up the assignment of ADM
functions to the relays and to energize or de-energize the relays.
16
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
33. Relay Startup Mode - Displays the energize/de-energized condition for each relay. ADM
If required, use the + - and ↵ keys to change the energized/de-energized state of
relays.
Parameter Default
34. Latching - This screen displays the latched/unlatched relay condition for different ADM
levels of alarms and faults. In the latched condition the reporting of an alarm or a
fault continues to be reported even after the event is over. Manual intervention is
necessary to reset. If the condition is unlatched the reporting of the condition
automatically stops once the event is over. To latch an alarm or a fault place a
against the respective alarm level or fault. The isolate function is fixed for
unlatched and cannot be changed.
Parameter Default
Latching
Fire 2 Latched
Fire 1 Latched
Alert Latched
Scanning N/A
Isolate Unlatched
17
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
35. Relay Assignments - Each relay is allocated a screen. In their respective screens ADM
assign the relevant alarm, fault or isolate function. Multiple functions can be
assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the ↵ key to assign or de-assign functions.
Parameter Default
Fire 2 Relay 7
Fire 1 Relay 6
Action Relay 5
Alert Relay 4
Isolate Relay 1
36. Diagnostics - It is possible to conduct alarm and fault tests through sub-menus of ADM
this screen.
• Alarm Test - This causes the detector to generate a Fire 2 condition
• Fault Test - This causes a system fault for 30 seconds
• Flow Fault - This turns the aspirator off for 30 seconds causing an air flow fault
• Relay Test - (Refer to Screen 37).
37. Relay Test - This allows testing each relay by turning it ON and OFF. ADM
18
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
Parameter Default
UL Version Enabled
41. LaserSCANNER Detector - Lists functions available for accessing and managing USR
the properties of the selected VESDA LaserSCANNER detector. Select the
required option and press ↵ .
43. Scan Status - This screen shows the smoke level for each sector in use during a USR
scan sequence (automatic or manual).
19
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
46. Select Events - This function assists in easier viewing of the logged events. The ADM
events can be sorted as per the categories displayed. After selecting the events,
DST
proceed to Screen 45 to view the events.
• End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
• End Time - This is the time up to which events will be displayed for viewing.
You can input the required time in the time field.
• Events to view -
- Smoke Level - A against Smoke Level will display logged smoke levels
- Alarms - A against Alarms displays a log of alarms
- Faults - IA against Faults displays a log of the logged faults
- User Action - To view a log of user actions place a against User Action
- Clear Log - To clear the log of events highlight Start and press ↵ .
Note: Use the + key to place a and - key to insert a x to deselect the option.
Parameter Default
Select Events
end date Selectable
end time Selectable
Events to View
Smoke Level Enabled
Alarms Enabled
Faults Enabled
User Action Enabled
47. Address Control - The four functions under Address Control are the same as the USR
functions performed by the buttons on the VESDA Laser Display Module.
• Mode - This controls the mode of the LCD Numerical display on the VESDA
Laser Display. Use the +, -, and the ↵ keys to change the mode
- Sensitivity - Displays the sensitivity level
- Smoke - Displays the current smoke level
- Address Number - Displays the assigned VESDA Zone number for the
detector
- Current Sector - Displays the First Alarm Sector in a VESDA
LaserSCANNER Detector
• Silence - Silences the beeping sound of the detector
• Reset - Resets faults
• Isolate - Starts and stops isolation of the detector
48. Smoke Thresholds - This screen lists screens 49 to 58 as options available for ADM
setting Smoke Thresholds.
49. Day Thresholds - This screen allows viewing and changing the current Fire 2, Fire ADM
1, Action and Alert thresholds for day time.
20
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
50. Night Thresholds - This screen allows viewing and changing the current Fire 2, ADM
Fire 1, Action and Alert thresholds for night time.
51. Change-Over Times - Insert the time to switch from day to night thresholds and ADM
night to day thresholds. Day Start and Night Start have been defaulted at 07:00:00
and 19:00:00 respectively.
52. Weekend - Placing a against the relevant week day will denote it as being ADM
weekend. By default Saturday and Sunday are set as weekend days.
53. Holidays - Insert the first and the last day of holidays to set the night fire ADM
thresholds during this period.
21
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
55. Delays & Thresholds - This screen displays the delays and thresholds for the ADM
LaserSCANNER.
- Delays - The time before a LaserSCANNER will commence scanning,
once the lowest threshold is reached.
- Sector Time - The time spent looking at each sector after the initial fast
scan sequence. This allows air sample from a previous pipe to clear out
from the detector before it starts reading the air sample from the next pipe.
- Thresholds - The smoke threshold for the LaserSCANNER
- Day Threshold - The day smoke threshold for the LaserSCANNER
- Night Threshold - The night smoke threshold for the LaserSCANNER
Parameter Default Minimum Maximum
(0.0062% obs/ft)
(0.0062% obs/ft)
(0.0062% obs/ft)
22
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
58. Smoke Change - The change in obscuration rate mentioned here will register the ADM
event in the event log. This is subject to the change occurring over the interval
DST
period that is input. You can input the required obscuration and interval.
• Change By
• Min. Interval
23
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
59. AutoLearn - The AutoLearn function allows setting the thresholds automatically. ADM
The detector measures the ambient smoke levels over the set period and will
establish the smoke and alarm thresholds accordingly. Enter the number of days,
hours and minutes over which the AutoLearn function is to apply.
60. Address Number - Assign the VESDA Zone number to the detector. ADM
61. Address Name/Location - Allocate a VESDA Zone name and location and assign ADM
these to the respective detector.
62. Air Flow - This screen lists the options available to monitor and manage air flows. ADM
It has 3 sub-menus for:
• Flow Thresholds
• Flow Control
• Normalize
63. Flow Thresholds - Input the required High Urgent, High Minor, Low Minor and ADM
Low Urgent air flow thresholds. Enter the time over which the air flow should be
monitored above and below the threshold levels. An appropriate urgent or minor air
flow fault will be generated once the air flow crosses the threshold and remains
above or below the threshold for the period set as “Delay”.
64. Flow Control - The Flow Control Screen permits changing the Aspirator speed for ADM
VESDA LaserPLUS and LaserSCANNER. Enter the Pipes in Use by placing a
against the respective pipe.
Default: 3000rpm, Min. 3000rpm, Max 4200rpm
65. Normalize - The Normalize screen displays the current air flow rates and the ADM
current raw flow for each pipe in use. To normalize the air flow highlight Start and
press ↵ .
Note: Normalizing air flow takes approximately 11 minutes. Ensure that the pipes
in use have been (screen 64) before commencing normalization.
24
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
66. Filter - Displays details on the life and usage of the filter. When the filter is replaced ADM
with a new filter, highlight Start and press ↵ to restart the dust count and due date
DST
for replacement. The service interval for filter replacements can be entered to suit
the ambient conditions of the VESDA Zone in which the detector is installed. DST
• Life Used
• Date Due
• Service Interval
• New Filter
• Dust Count
• Dust Limit
Default: 1825 days (5 years), Min. 1 day, Max 3655 days (10 years)
67. Reference Detector - If a reference detector is connected to VESDAnet, enter the: ADM
• Reference Address Number
• Dilution Factor - This is the amount of offset required from the reference
detector. Setting it to 100% will cause the detector to ignore the same amount
of smoke as is being detected by the reference detector. Setting it to 50%
ignores half of the smoke detected at the reference detector. These settings
allow you to fine tune how much of the smoke detected by the reference
detector is also likely to reach each detector.
• Delay - The amount of time it will take smoke to move from the reference
detector to the other detectors.
68. Rebuild Address List - Highlight Start and press ↵ to rebuild the Address List. ADM
Use this option to rebuild the Address List after removing a display module
assigned to the VESDA Detector.
69. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the VESDA Intelligent Power Supply is not being used enter “0”.
70. Relays/Disp Connected - This screen displays the number of relays connected to ADM
the detector. It also indicates if the detector is a LaserSCANNER.
Parameter Default
71. Relay Setup - This screen and its sub-menus allow setting up the assignment of ADM
functions to the relays and to energize or de-energize relays.
25
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
72. Relay Startup Mode - Displays the energize/de-energized condition for each relay. ADM
If required, use the + - and press ↵ keys to change the energized/de-energized
state of relays.
Parameter Default
73. Latching - This screen displays the latched/unlatched relay condition for different ADM
levels of alarms in each sector, faults and scanning. In the latched condition the
reporting of an alarm or a fault continues to be reported even after the event is
over. Manual intervention is necessary to reset. If the condition is unlatched the
reporting of the condition automatically stops once the event is over. To latch an
alarm or a fault place a against the respective alarm level or fault. The isolate
function is fixed for unlatched and cannot be changed.
Parameter Default
Latching
Fire 2 Latched
Fire 1 Latched
Alert Latched
Scanning N/A
Isolate Unlatched
26
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
74. Relay Assignments - Each relay is allocated a screen. In their respective screens ADM
assign the relevant alarm, fault, scanning or isolate function. Multiple functions can
be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the ↵ key to assign or de-assign functions.
Parameter Default
Scanning Relay 12
Sector 4 Relay 11
Sector 3 Relay 10
Sector 2 Relay 9
Sector 1 Relay 8
Fire 2 Relay 7
Fire 1 Relay 6
Action Relay 5
Alert Relay 4
Isolate Relay 1
75. Diagnostics - It is possible to conduct alarm and fault tests through sub-menus of ADM
this screen.
• Alarm Test - This causes the detector to generate a Fire 2 condition
• Fault Test - This causes a system fault for 30 seconds
• Flow Fault - This causes a 30 second Air Flow fault
• Sector Test - This allows all valves to be forced closed and open
• Scan Test - This will perform a scan test
• Relay Test - (Refer to Screen 76).
76. Relay Test - This allows testing each relay by turning it ON and OFF. ADM
27
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
80. LaserCOMPACT Detector - Lists functions available for accessing and managing USR
the properties of the selected VESDA LaserCOMPACT detector. Select the
required option and press ↵ .
28
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
84. Select Events - This function assists in easier viewing of the logged events. The ADM
events can be sorted as per the categories displayed. After selecting the events,
DST
proceed to Screen 83 to view the events.
• End Date - This allows viewing of events up to the date mentioned in the date
field. You can input the required date in the date field.
• End Time - This is the time up to which events will be displayed for viewing. You
can input the required time in the time field.
• Events to view -
- Smoke Level - A against Smoke Levels will display logged smoke levels
- Alarms - To display a log of alarms place a against alarms
- Faults - Inserting a against Faults will list all the logged faults
- User Action - To view a log of user actions place a against User Action
- Clear Log - To clear the log of events highlight Start and press ↵ .
Note: Use the + key to place a and - key to insert a X and deselect the option.
Select Events
end date Selectable Selectable Selectable
end time Selectable Selectable Selectable
Events to View
Smoke Level Enabled N/A N/A
Alarms Enabled N/A N/A
Faults Enabled N/A N/A
User Action Enabled N/A N/A
85. Address Control - The four functions under Address Control are the same as the USR
functions performed by the buttons on the VESDA Laser Display Module.
• Mode - This controls the mode of the LCD Numerical display on the VESDA
Laser Display. Use the +, -, and the ↵ keys to change the mode
- Sensitivity - Displays the sensitivity level
- Smoke Level - Displays the current smoke level
- Address Number - Displays the assigned VESDA Zone number for the
detector
• Silence - Silences beeping sound of the detector
• Reset - Resets faults
• Isolate - Starts and stops isolation of the detector
29
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
87. Smoke Thresholds - This screen lists the available options for setting smoke ADM
thresholds.
• Fire
• Pre-Alarm
• Alert
• Overlay Alert
88. Alarm Delays - In this screen insert the required time delay (in seconds) before an ADM
alarm is generated at Fire, Pre-Alarm, Alert, Overlay Alert levels. This screen also
offers the option of simultaneous or cumulative delay times before the alarm is
generated. The instant fire alarm option can be enabled or disabled in this screen.
89. Smoke Change - The change in obscuration rate mentioned here will register the ADM
event in the event log. This is subject to the change occurring over the interval
DST
period that is input. You can input the required obscuration and interval.
• Change By
• Min. Interval
30
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
90. AutoLearn - The AutoLearn function allows setting the thresholds automatically. ADM
The detector measures the ambient over the set period and will establish the
smoke thresholds accordingly. Enter the number of days, hours and minutes over
which the AutoLearn function is to run.
91. Address Number - Assign the VESDA Zone number to the detector. ADM
92. Address Name/Location - Allocate a VESDA Zone name and location and assign ADM
these to the respective detector.
93. Air Flow - This screen lists the options available to monitor and manage air flows. ADM
It displays options for 2 sub-menus:
• Flow Thresholds
• Normalize
94. Flow Thresholds - Input the required High Urgent, High Minor, Low Minor and ADM
Low Urgent air flow thresholds. Enter the time over which the air flow should be
monitored above and below the threshold levels. An appropriate urgent or minor air
flow fault will be generated once the air flow crosses the threshold and remains
above or below the threshold for the period set as “Delay”.
95. Normalize - The Normalize screen displays the current air flow rates and the ADM
current raw flow for each pipe. To normalize the air flow highlight Start and
pressing ↵ .
Note: Normalizing air flow takes approximately 11 minutes.
31
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
96. Filter - Displays details on the life and usage of the filter. When the filter is replaced ADM
with a new filter, highlight Start and press ↵ to restart the dust count and due date
DST
for replacement. The service interval for filter replacements can be entered to suit
the ambient conditions of the VESDA Zone in which the detector is installed. DST
• Life Used
• Date Due
• Service Interval
• New Filter
• Dust Count
• Dust Limit
Default: 1825 days (5 years), Min. 1 day, Max 3655 days (10 years)
97. Reference Detector - If a reference detector is connected to VESDAnet, enter the: ADM
• Reference Address Number
• Dilution Factor - This is the amount of offset required from the reference
detector. Setting it to 100% will cause the detector to ignore the same amount
of smoke as is being detected by the reference detector. Setting it to 50%
ignores half of the smoke detected at the reference detector. These settings
allow you to fine tune how much of the smoke detected by the reference
detector is also likely to reach each detector.
• Delay - The amount of time it will take smoke to move from the reference
detector to the other detectors.
98. Rebuild Address List - Highlight start and press ↵ to rebuild the Address List. ADM
Use this option to rebuild the Address List after removing a display module
assigned to the detector.
99. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the Intelligent Power Supply is not being used enter “0”.
100. Button Lockout - This screen provides the option to Lock or enable the Reset/ ADM
Isolate Button on the VESDA LaserCOMPACT.
101. Diagnostics - It is possible to conduct alarm and fault tests through sub-menus of ADM
this screen.
• Alarm Test - This causes the detector to generate a Fire condition
• Fault Test - This causes a system fault for 30 seconds
• Flow Fault - Turns the aspirator off for 30 seconds causing an air flow fault.
(This causes the LED's to light up)
• Lamp Test - This causes the LCDs to light up
• Relay Test - (refer to Screen 102).
102. Relay Test - This allows testing each relay by turning it ON and OFF. ADM
32
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
Parameter Default
UL Version Enabled
106. Ancillary Devices - Should be put under the same flow line as detectors. Select USR
the device by highlighting it and press ↵ .
107. Display/Relays - Should be put under the same flow line as detectors. Select the USR
Display/Relay and press ↵ .
33
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
109. Address Control - The four functions under Address Control are the same as the USR
functions performed by the buttons on the VESDA Laser Display Module.
• Mode - This controls the mode of the LCD Numerical display on the VESDA
Laser Display. Use the +, -, and the ↵ key to change the mode
- Current Sector - Display the First Alarm Sector in LaserSCANNER Display
- Sensitivity - Displays the sensitivity level
- Smoke Level - Displays the current smoke level
- Address Number - Displays the assigned VESDA Zone number for the
detector
• Silence - Silences beeping sound of the detector
• Scan - Selecting this option in a LaserSCANNER Display commences a Scan
sequence of the assigned LaserSCANNER Detector
• Reset - Resets faults
• Isolate - Starts and stops isolation of the detector
110. Address Number - Assign the VESDA Zone number to a Laser Display/Relay. ADM
111. Location - Allocate a VESDA Zone name and location and assign these to the ADM
respective Laser Display/Relay.
112. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the VESDA Intelligent Power Supply is not being used enter “0”.
113. Button Lockout - This screen provides the option to Lock or enable the buttons on ADM
a VESDA Laser Display.
114. Relays/Disp Connected - Use the screen to enter the number of relays connected DST
to the Display. It also indicates if the detector is a LaserSCANNER.
116. Relay Startup Mode - Displays the energize/de-energized condition for each relay. ADM
If required, use the + - and ↵ keys to change the energized/de-energized state of
relays.
Parameter Default
34
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
117. Latching - This screen displays the latched/unlatched relay condition for different ADM
levels of alarms in each sector, faults and scanning. In the latched condition the
reporting of an alarm or a fault continues to be reported even after the event is
over. Manual intervention is necessary to reset. If the condition is unlatched the
reporting of the condition automatically stops once the event is over. To latch an
alarm or a fault place a against the respective alarm level or fault. The isolate
function is fixed for unlatched and cannot be changed.
Parameter Default
Fire 2 Latched
Fire 1 Latched
Alert Latched
Scanning N/A
Isolate Unlatched
118. Beeper - Placing a tick beside each of the fire and fault conditions will result in the ADM
beeper activating during this condition. If the display is allocated to a
LaserSCANNER, fire conditions for individual sectors can also be chosen for beep
on or off. To set a condition to beep place a against the respective condition.
Parameter Default
Fire 2 Latched
Alert Latched
Scanning Latched
Isolate Latched
35
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
119. Relay Assignments - Each relay is allocated a screen. In their respective screens ADM
assign the relevant alarm, fault, scanning or isolate function. Multiple functions can
be assigned to each relay. Relay 3 and relay 6 are permanently assigned to Urgent
Fault and Fire 1 functions respectively. Additional functions may be assigned to
Relays 3 and 6. Use the ↵ key to assign or de-assign functions.
Parameter Default
Scanning Relay 12
Sector 4 Relay 11
Sector 3 Relay 10
Sector 2 Relay 9
Sector 1 Relay 8
Fire 2 Relay 7
Fire 1 Relay 6
Action Relay 5
Alert Relay 4
Isolate Relay 1
36
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
Parameter Default
123. LCD Programmer - Select the LCD Programmer and press ↵ . USR
125. Address (Zone) Number - If the LCD Programmer has been allocated a Address ADM
(Zone) Number, it is displayed in this screen. This is only for VLS.
126. Location - Allocate a VESDA Zone name and location and assign these to the ADM
LCD Programmer.
127. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the VESDA Intelligent power supply is not being used enter “0”.
128. Address Control Lockout - This screen allows you to lock or unlock the button ADM
functions on any Laser Display in the VESDA Zone. This stops someone logging
on at an OPERATOR level from using the zone control or system control function.
The buttons controlled are:
• Mode/Test
• Silence/Scan
• Reset
• Isolate
37
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
134. Location - Allocate a VESDA Zone name and location and assign these to the ADM
LCD Programmer.
135. Power Supply Number - Input the number of the power supply that is assigned to ADM
the detector. If the VESDA Intelligent Power Supply is not being used enter “0”.
138. Setup By Type - The Setup By Type selection allows accessing and managing the USR
properties of all VESDA Laser family devices connected to VESDAnet. This
screen lists all the VESDA Laser family products connected to the VESDAnet.
Highlight the VESDA Laser product and press ↵ .
38
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
139. VESDA Device - This screen lists all devices of a particular VESDA Laser product USR
(e.g. Each VESDA LaserPLUS detector connected to VESDAnet will be displayed
with their respective unique detector number under the VLP/VLS screen). To
access the device through the LCD Programmer, highlight the device and
press ↵ .
Note: For details of menu descriptions refer from “Screen Number 6, on page 12”
to “Screen Number 137, on page 38.”
140. System/All Devices - This alternative permits setting up and managing the USR
parameters of the entire system connected to VESDAnet.
141. Status - This screen presents the current status for all the devices connected to USR
VESDAnet. It displays the smoke level from the detector with the highest reading.
The current status of Alarms and Faults for each device is listed under their
respective device names.
142. System Control - The four functions under System Control are the same as the USR
functions performed by the buttons on the VESDA Laser Display Module.
• Mode - This controls the mode of the LCD Numerical display on the VESDA
Laser Display. Use the +, -, and the ↵ key to change the mode
- Current Sector - Display the First Alarm Sector in LaserSCANNER Display
- Sensitivity - Displays the sensitivity level
- Smoke Level - Displays the current smoke level
- Address Number - Displays the assigned VESDA Zone number for the
detector
• Silence - Silences beeping sound of the detector
• Scan - Selecting this option in a LaserSCANNER Display commences a Scan
sequence of the assigned LaserSCANNER Detector
• Reset - Resets faults
• Isolate - Starts and stops isolation of the detector
143. AutoLearn - The AutoLearn function allows setting the thresholds automatically. ADM
The detector measures the ambient over the set period and will establish the
smoke and alarm thresholds accordingly. Enter the number of days, hours and
minutes over which the AutoLearn function is to apply.
144. Set Date & Time - This screen permits setting the date, time and day. USR
145. Weekend - Placing a against the relevant week day will denote it as being ADM
weekend. By default Saturday and Sunday are set as weekend days.
146. Holidays - Insert the first and the last day of holidays to set different smoke ADM
thresholds during this period.
39
LCD Programmer Product Guide VESDA®
Min.
Scrn
Description Access
No.
Level
147. Users - This screen presents sub menus to display and manage user information: USR
• Change User Details
• Add User
• Delete User
148. Change User Details - This screen displays the current user ID and PIN. The User USR/
ID and PIN can be changed in this screen. The Access level cannot be changed. ADM/
User details can be changed for the level at which the current User is logged on. DST
149. Add User - This screen permits adding users at the Operator and Administrator ADM/
levels. Enter the User ID and PIN of the new user. Permits deleting a User at an DST
access level below which the current user is logged on.
150. Delete User - Authorization for a user at the Operator or the Administrator level ADM/
can be deleted in this screen. Permits deleting a User at an access level below DST
which the current user is logged on.
151. Air Flow - Input the required High Urgent, High Minor, Low Minor and Low Urgent ADM
air flow thresholds. Enter the time over which the air flow should be monitored
above and below the threshold levels. An appropriate urgent or minor air flow fault
will be generated once the air flow crosses the threshold and remains above or
below the threshold for the period set as “Delay”.
152. Filter - Set the service interval for changing the filter in this screen. ADM
153. Reference Detector - If a reference detector is connected to VESDAnet, enter the: ADM
• Reference Address Number
• Dilution Factor - This is the factor by which the background levels have to
reduce to reach the levels of the current VESDA Zone
• Delay - This is the time taken for the current VESDA Zone to return to its
ambient levels after background from the Reference Address is introduced.
154. Button Lockout - This screen provides the option to Lock or enable the buttons on ADM
all VESDA Laser Display connected to VESDAnet.
40
VESDA® LCD Programmer Product Guide
Min.
Scrn
Description Access
No.
Level
156. Smoke Change - This screen sets the minimum interval over which a change in DST
the obscuration rate should occur before an alarm is triggered, or the event is
registered in the Event Log. You can enter the required interval.
157. Miscellaneous -
• Units - This gives the user an option to enter and display data in S.I. ADM
(International System of Units), or U.S. (Us Imperial measurements)
ADM
• UL Version - A against this indicates that the Devices on the system are set
to meet UL specifications.
• Isolate Remind - Provides an option to enable or disable the reminder beeper
ADM
when the Isolate function is enabled
• Support - Displays the contact phone number for support DST
• Device ID - This provides an option to Name and Number, Name Only or
ADM
Number Only devices connected to VESDAnet.
• Refresh Map - Refreshes the VESDAnet map when a Detector Chassis is ADM
changed
ADM
• Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
• Latch Faults - This provides a YES/NO option to latch/unlatch all Faults ADM
158. Show Wiring Order - Lists all the VESDA Laser family devices connected to USR
VESDAnet.
159. LCD Screen - Select this menu to set LCD screen options. USR
41
LCD Programmer Product Guide VESDA®
42
VESDA® LCD Programmer Product Guide
Index
A Beeper ............................................... 35
Button Lockout ............................. 32, 34
Add User
Users - System/All Devices ................ 40 C
Address Control ............................ 13, 20
Cfg Code ...................................... 19, 28
Address control ............................. 29, 34
Status - HLI .................................... 38
Address Control Lockout
Cfg Code Status .................................. 12
LCD Programmer .............................
37
Change User Details
Address Name/Location ....................... 24
Users - System/All Devices ................ 40
Address name/location ................... 15, 31
Change-Over Times ....................... 14, 21
Address Number ..................... 15, 29, 37
Clear Log ................................ 13, 20, 29
Address number ................ 13, 24, 31, 34
Communications ............... 18, 28, 33, 36
Address Number and Name .................. 12
HLI................................................
38
Address with a VLP detector ................. 12
LCD Programmer ............................. 38
Address with a VLS .............................. 19 System/All Devices........................... 41
ADM ..................................................... 3 Configuration Code .............................. 37
Administrator Access Level .................... 5 Connections ......................................... 4
Air Flow .................................. 15, 24, 31 Contact Us .............................................
ii
System/All Devices........................... 40 Conventions .......................................... i
Alarm Delay ........................................ 14 cumulative delay times ......................... 14
Alarm Delays ....................................... 30 Current % Flow .............................. 19, 28
Alarm Test .................................... 27, 32 Current % flow Status .......................... 12
Alarms ....................... 13, 19, 20, 28, 29 Current Access Level ........................... 37
Alarms Status ..................................... 12 Current Sector ............................... 20, 34
Alert ................................................... 30 Current User Level ............................... 37
Alert level ........................................... 14
Ancillary Devices ................................. 33 D
AutoLearn ...............................
15, 24, 31
VESDA LaserPLUS Detector .............. 39 Day Threshold .....................................
22
Automatic Log Off ................................. 7 Day Thresholds ............................. 13, 20
Def. User
B Miscellaneous - LCD Programmer ....... 38
Default User Level IDs ............................ 3
Backward Action Key ............................. 7 Delays ................................................ 22
43
LCD Programmer Product Guide VESDA®
44
VESDA® LCD Programmer Product Guide
Latch Alarms ..................... 19, 28, 33, 37 Normalize ............................... 16, 24, 31
Miscellaneous - LCD Programmer ....... 38
Latch Faults ...................... 19, 28, 33, 37 O
Miscellaneous - LCD Programmer ....... 38
Latching ................................. 17, 26, 35 Open-ended .................................. 18, 36
LCD Programmer ................................. 37 Communications - HLI....................... 38
Communications - LCD Programmer .... 38
LCD programmer keys ........................... 4
Operating Temperature .......................... 3
LCD Programmer screen description ..... 12
Overlay Alert ....................................... 30
LCD Screen ......................................... 41
Location ....................................... 34, 37
P
HLI................................................ 38
Log off ................................................. 3
Page Down ........................................... 7
Log off Automatic .................................. 7
Page Up ................................................ 7
Log off Manual ...................................... 8
Personal Identification Number (PIN) ....... 5
Logging on ........................................... 7
PIN ....................................................... 5
Logon ................................................ 12
Power Consumption .............................. 3
Power Supply Number........ 16, 25, 32, 34
M HLI................................................ 38
LCD Programmer ............................. 37
Main Menu ..........................................
12 Pre-Alarm ........................................... 30
Maximum VESDA devices addressed ....... 3 Pref. Port ................................ 18, 33, 36
Miscellaneous ................... 19, 28, 33, 37 Communications - HLI....................... 38
LCD Programmer ............................. 38 Communications - LCD Programmer .... 38
System/All Devices........................... 41 Communications - System/All Devices.. 41
Smoke Thresholds - VESDA LaserPLUS De- Address Control Lockout - LCD Programmer
tector ............................................. 14 37
45
LCD Programmer Product Guide VESDA®
System Control - System/All Devices ... 39 Smoke Thresholds ............. 13, 20, 29, 30
Soft Keys .............................................. 4
S Software Version Installed .................... 37
Standby Mode ....................................... 6
Scan .................................................. 34 Status ............................... 19, 28, 33, 37
System Control - System/All Devices ... 39 HLI ................................................ 38
Scan Status ........................................ 19 System/All Devices ........................... 39
Smoke Level ......... 13, 19, 20, 28, 29, 34 System/All Devices ........................... 40
Smoke Level Status ............................. 12 USR ..................................................... 3
46
VESDA® LCD Programmer Product Guide
47
LCD Programmer Product Guide VESDA®
48