Manual Operación Panel Simatic OP73 OP77A OP77B e
Manual Operación Panel Simatic OP73 OP77A OP77B e
1
______________
Overview
3
HMI device ______________
Planning use
Operator control
5
Operating Instructions ______________
components and LEDs
8
______________
Operating a project
10
______________
Operating alarms
11
______________
Maintenance and Service
______________
Specifications 12
A
______________
Appendix
C
______________
Glossary
Edition 01/2005
A5E00327600-01
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring to property damage only have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
Danger
indicates that death or severe personal injury will result if proper precautions are not taken.
Warning
indicates that death or severe personal injury may result if proper precautions are not taken.
Caution
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
Caution
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
Notice
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
Warning
This device may only be used for the applications described in the catalog or the technical description and only in
connection with devices or components from other manufacturers which have been approved or recommended
by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and
assembly as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Siemens AG
Automation and Drives Siemens AG 2005
Postfach 4848, 90327 Nuremberg, Germany Technical data subject to change
Online availability
Technical documentation on SIMATIC products and SIMATIC systems is available in PDF
format in various languages at the following addresses:
• SIMATIC Guide Technische Dokumentation in Deutsch:
"http://www.ad.siemens.de/simatic/portal/html_00/techdoku.htm"
• SIMATIC Guide for Technical Documentation in English:
"http://www.ad.siemens.de/simatic/portal/html_76/techdoku.htm"
Conventions
Configuration and runtime software differ with regard to their names as follows:
• "WinCC flexible 2004," for example, refers to the configuration software.
The term "WinCC flexible" is used in a general context. The full name, for example
"WinCC flexible 2004", is always used when it is necessary to differentiate between
different versions of the configuration software.
• "WinCC flexible Runtime" refers to the runtime software that can run on HMI devices.
Text is highlighted as follows to simplify reading the operating instructions:
Notation Scope
"Add screen" • Terminology that appears in the user interface, e.g., dialog names, tabs,
buttons, menu entries
• Inputs required, e.g., limit values, tag values
• Path information
"File > Edit" Operational sequences, e.g., menu commands, context menu commands
<F1>, <Alt+P> Keyboard operation
Note
Notes contain important information concerning the product, its use or a specific section of
the documentation to which you should pay particular attention.
Registered trademarks
Names labeled with a ® symbol are registered trademarks of the Siemens AG. Other names
used in this documentation may be trademarks, the use of which by third parties for their
own purposes could violate the rights of the owner.
• HMI®
• SIMATIC®
• SIMATIC HMI®
• SIMATIC ProTool®
• SIMATIC WinCC®
• SIMATIC WinCC flexible®
• SIMATIC OP 73®
• SIMATIC OP 77A®
• SIMATIC OP 77B®
Training center
Siemens AG offers a variety of training courses in order to familiarize you with automation
systems. Please contact your regional training center or the central training center in
D-90327 Nuremberg.
Phone: +49 (911) 895-3200
internet: "http://www.sitrain.com/"
Nuremberg
Johnson City
Beijing
SIMATIC Hotline
4.3 Mounting and connecting the OP 77A and OP 77B ................................................................ 4-11
4.3.1 Mounting the HMI device ......................................................................................................... 4-11
4.3.2 Connecting the HMI device ...................................................................................................... 4-12
4.3.2.1 Interfaces.................................................................................................................................. 4-13
4.3.2.2 Connecting the equipotential bonding circuit ........................................................................... 4-14
4.3.2.3 Installing the equipotential circuit ............................................................................................. 4-15
4.3.2.4 Connecting the PLC ................................................................................................................. 4-16
4.3.2.5 Connecting the configuration computer ................................................................................... 4-18
4.3.2.6 Wiring I/O to OP 77B................................................................................................................ 4-19
4.3.2.7 Connecting the power supply................................................................................................... 4-20
4.3.3 Switching on power and testing the HMI.................................................................................. 4-22
5 Operator control components and LEDs................................................................................................. 5-1
5.1 Control elements on the OP 73 front panel................................................................................ 5-1
5.2 Operator control components and LEDs on the front panel of OP 77A and OP 77B ................ 5-2
5.3 Additional elements on the OP 77A and OP 77B ...................................................................... 5-4
5.3.1 Use of a memory card on OP 77B ............................................................................................. 5-4
5.3.2 Labeling the function keys of OP 77A and OP 77B ................................................................... 5-6
5.3.3 Setting the DIL switch ................................................................................................................ 5-8
6 Configuring the operating system ........................................................................................................... 6-1
6.1 Configuring the operating system of the OP 73 ......................................................................... 6-1
6.1.1 Overview .................................................................................................................................... 6-1
6.1.2 "Info/Settings" menu................................................................................................................... 6-2
6.1.2.1 Overview .................................................................................................................................... 6-2
6.1.2.2 Setting screen contrast .............................................................................................................. 6-3
6.1.2.3 Displaying information about the HMI ........................................................................................ 6-4
6.1.2.4 Viewing information about the version of the HMI image .......................................................... 6-4
6.1.3 "Settings" menu.......................................................................................................................... 6-5
6.1.3.1 Overview .................................................................................................................................... 6-5
6.1.3.2 Setting the delay ........................................................................................................................ 6-6
6.1.3.3 Assigning, changing and deleting passwords ............................................................................ 6-6
6.1.3.4 Configuring the data channel ..................................................................................................... 6-8
6.2 Configuring the OP 77A and OP 77B operating system.......................................................... 6-12
6.2.1 Overview .................................................................................................................................. 6-12
6.2.2 "Info/Settings" menu................................................................................................................. 6-13
6.2.2.1 Overview .................................................................................................................................. 6-13
6.2.2.2 Setting screen contrast ............................................................................................................ 6-15
6.2.2.3 Displaying information about the HMI ...................................................................................... 6-15
6.2.2.4 Viewing information about the version of the HMI image ........................................................ 6-16
6.2.3 "Settings" menu........................................................................................................................ 6-17
6.2.3.1 Overview .................................................................................................................................. 6-17
6.2.3.2 Setting the delay ...................................................................................................................... 6-18
6.2.3.3 Setting the screen saver on OP 77B........................................................................................ 6-18
6.2.3.4 Changing regional settings for OP 77B.................................................................................... 6-19
6.2.3.5 Assigning, editing and deleting passwords .............................................................................. 6-19
6.2.3.6 Backup and restore functions for OP 77B................................................................................ 6-21
6.2.3.7 Configuring the data channel ................................................................................................... 6-21
6.2.4 "Printer Settings" menu of OP 77B .......................................................................................... 6-28
6.2.4.1 Overview .................................................................................................................................. 6-28
6.2.4.2 Set printer language................................................................................................................. 6-29
6.2.4.3 Setting the paper format........................................................................................................... 6-29
6.2.4.4 Setting the print orientation ...................................................................................................... 6-30
6.2.4.5 Setting the print mode .............................................................................................................. 6-30
Big changes in small plants - the new graphic HMI devices of the 70 series
The new OP 73 and OP 77 operator panels represent low-cost devices in the class of
graphic HMI devices for first-time user. These devices offer many options ranging from a
fully graphical 3" or 4.5" display unit, to their configuration in WinCC flexible in up to 32
engineering and online languages, including Asian and Cyrillic characters. The new operator
panels are therefore highly suitable for small-scale HMI tasks.
OP 73 and OP 77 replace the text-based OP3 and OP7. Existing OP3/OP7 projects in
WinCC flexible can be migrated to OP73/OP77 projects. The previous engineering work is
thus retained.
① Display
② Membrane keyboard
③ Clamping recess
④ Mounting seal
2
6
3
① Display
② Construction-related opening – not a slot for a memory card
③ LED display
④ Membrane keyboard
⑤ Clamping recess
⑥ Guides for the labeling strips
⑦ Mounting seal
2
3
7
4
① Display
② Memory card holder
③ MMC slot
④ LED display
⑤ Membrane keyboard
⑥ Clamping recess
⑦ Guides for the labeling strips
⑧ Mounting seal
Accessory kit
The accessory kit contains the following:
• A terminal block for the power supply
• Two mounting clamps for installing an OP 73
• Four mounting clamps for installing an OP 77A or OP 77B
Additional documents may be enclosed with the accessory kit.
Memory card
For the OP 77B:
An MMC (Multi Media Card), tested and approved by Siemens AG, can be used as an
external storage medium. The memory card is an option and can be ordered separately.
Notice
The MMC of the SIMATIC S7 controller cannot be used.
General
The tables below show the objects which can be integrated in a project for an OP 73,
OP 77A and OP 77B.
Alarms
Table 1-1 Range of alarm functions for the OP 73, OP 77A and OP 77B
Table 1-2 Range of functions for tags, values, lists and mathematical functions on OP 73, OP 77A and OP 77B
Screens
Table 1-3 Range of screen functions for the OP 73, OP 77A and additional recipes for OP 77B
Infotext
Table 1-4 Range of infotext functions for the OP 73, OP 77A and OP 77B
Additional functions
Table 1-5 Range of additional object functions for the OP 73, OP 77A and OP 77B
Number of connections
Interconnection OP 73 OP 77A
Number with MPI/PROFIBUS DP 2 (on the same bus) 4 (on the same bus)
Siemens PLCs
The following table shows the Siemens PLCs and protocols or profiles that can be used.
1 Set the "DP" profile in WinCC flexible if you need a transmission rate of 9.6 kbps.
Number of connections
Interconnection OP 77B
Number with MPI/PROFIBUS DP 4 (similar PLCs)
Siemens PLCs
The following table shows which Siemens PLCs can be used for OP 77 B.
Controller Protocol
SIMATIC S5 • AS 511, via adapter and converter
• PROFIBUS DP up to 12 Mbps
SIMATIC S7-200 • MPI1
SIMATIC S7-300/400 • MPI
• PROFIBUS DP up to 12 Mbps
SIMATIC 500/505 • NITP
• PROFIBUS DP up to 12 Mbps
1 Set the "DP" profile in WinCC flexible if you need a transmission rate of 9.6 kbps.
Controller Protocol
Allen-Bradley • DF1
PLC series SLC500, SLC501, SLC502, SLC503, • DH+ via DF1
SLC504, SLC505, MicroLogix • DH485 via DF1
• DH485
Allen-Bradley • DF1
PLC series PLC5/20 • DH+ via DF1
GE Fanuc Automation SNP
PLC series 90-30, 90-70, 90-Micro
LG Industrial Systems (Lucky Goldstar)/IMO Dedicated communication
PLC series GLOFA-GM/G4, G6, G7M
Mitsubishi Electric FX
PLC series MELSEC FX, MELSEC FX0
Mitsubishi Melsec Protocol 4
PLC series FX, A, Ans, Q, QnAS
OMRON Hostlink/Multilink (SYSMAC Way)
PLC series SYSMAC C, SYSMAC CV, SYSMAC CS1,
SYSMAC alpha, CP
Schneider Automation (Modicon) Modicon Modbus
PLC series Modicon 984, TSX Quantum, TSX Compact
Warning
Open equipment
The HMI device is an open equipment. This means that the HMI device may only be
installed in cubicles or cabinets, whereby the device can be operated from the front panel.
Access to the cubicle or cabinet in which the HMI device is installed should only be possible
by means of a key or tool and for personnel who have received instruction or are authorized.
Danger, high voltage
Opening the cabinet will expose high voltage parts. Contact with these parts could be fatal.
Switch off the power supply to the cabinet before opening it.
Notice
Unintentional operating situations
High frequency radiation, from mobile phones for example, can cause unintentional
operating situations.
See also
HMI device connection - conditions (Page 4-12)
Valid approvals
Caution
Valid approvals
The overview below provides information on available certifications
The HMI device itself is certified as shown on the label on its rear panel.
CE approval
The automation system meets the general and safety-related requirements of the following
EC directives and conforms to the harmonized European standards (EN) for programmable
logic controllers published in the official gazettes of the European Union:
• 89/336/EEC "Electromagnetic Compatibility" (EMC Directive)
• 94/9/EC "Equipment and Protective Systems for Use in Explosive Atmospheres"
(explosion protection directive).
EC declaration of conformity
The EC declarations of conformity are kept available for the responsible authorities at the
following address:
Siemens Aktiengesellschaft
Automation & Drives
A&D AS RD ST PLC
PO Box 1963
D-92209 Amberg
UL certification
FM approval
FM
APPROVED
Ex certification
N117
The HMI device fulfills the requirements of standard AS/NZS 2064 (Class A).
IEC 61131
The HMI device fulfills the requirements and criteria conforming to IEC 61131-2,
Programmable Logic Controllers, Part 2: Operating resource requirements and tests.
Use in industry
The HMI device is designed for industrial use. The following standards are met:
• Requirements of the emission of interference EN 61000-6-4: 2001
• Requirements for noise immunity EN 61000-6-2: 2001
Residential use
If the HMI device is used in a residential area, you must take measures to achieve Limit
Class B conforming to EN 55011 for RF interference.
Suitable measures to achieve Limit Class B for suppression of radio interference include:
• Installation of the HMI device in a grounded control cabinet
• Use of filters in electrical supply lines
Danger
Risk of explosion
Operate the HMI device only in a Zone 2 potentially explosive atmosphere if it has been
identified as approved for such environments.
• II 3 G/D EEx nA II
• IP65
• 04 ATEX 1297X
Warning
Personal injury and property damage can occur.
Personal injury and property damage can occur in potentially explosive atmospheres if an
electric plug is disconnected from the HMI device while the system is in operation.
In potentially explosive atmospheres, always turn off power to the HMI device before
disconnecting any connectors.
Warning
Observe the degree of protection
The HMI device must be installed in a metal enclosure or in a cabinet The minimum degree
of protection of these is IP54 (conforming to EN 60529). Make allowances for the ambient
conditions under which you install the HMI device. The enclosure must have a
manufacturer's declaration for Zone 2 (conforming to EN 50021).
• A label with the following warning must be attached to the inside of the switch
cabinet/cubing at a place that is clearly visible upon opening:
Warning
Further information
The "HMI device in potentially explosive atmospheres of Zone 2 and Zone 22" flyer is part of
the package and must be complied with.
Maintenance
Defective HMI devices must be returned to the manufacturer for repair. Repair may only be
carried out by the manufacturer at his site.
Location of the manufacturer:
Siemens AG
Automation & Drives
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Approval
Note
HMI devices with approval to II 3 G EEx nA II T4 may only be used on SIMATIC systems of
device category 3.
Introduction
The HMI device fulfills requirements of the EMC Directive of the domestic European market
and other requirements.
Pulse-shaped interference
The following table shows the EMC properties of the modules with respect to pulse-shaped
interference. A requirement for this is that the HMI device meets the specifications and
directives regarding electrical installation.
Sinusoidal interference
The table below shows the EMC properties of the modules with respect to sinusoidal
interference. A requirement for this is that the HMI device meets the specifications and
directives regarding electrical installation.
Additional measures
Before you connect an HMI device to the public network, ensure that it is compliant with Limit
Class B conforming to 55022.
Notice
Ensure that no condensation (dewing) develops on or inside the HMI device after
transporting it at low temperatures or after it has been exposed to extreme temperature
fluctuations.
The HMI device must have acquired room temperature before it is put into operation. Do not
expose the HMI device to direct radiation from a heater in order to warm it up. If dewing has
developed, wait approximately four hours before you switch on the HMI device.
Prerequisite for the trouble-free and safe operation of the HMI device is proper transport and
storage, installation and assembly and careful operation and maintenance.
Warranty for the HMI device is deemed void if these specifications are ignored.
Reduction of vibration
If the HMI device is subjected to greater shocks or vibrations, you must take appropriate
measures to reduce acceleration or amplitudes.
We recommend fitting the HMI device to vibration-absorbent material (on metal shock
absorbers, for example).
Mounting position
The HMI device is designed for mounting in racks, switch cabinets, switchboards and
consoles. In the following, all of these mounting options are referred to by the general term
"cabinet".
The HMI device is self-ventilated and approved for vertical and inclined mounting in
stationary cabinets.
– +
Caution
Impermissible ambient temperatures
Do not operate the HMI device without auxiliary ventilation if the maximum permissible
ambient temperature is exceeded. The HMI device may otherwise get damaged and its
approvals and warranty will be void!
Type of fixation
Spring clamps are provided for mounting the device. Hook the clamps into the recesses of
the HMI device. The overall HMI device dimensions are not exceeded by this.
① Hook
② Recessed head screw
138 +1
68 +1
Figure 3-3 Cut-out for panel-mounting the OP 73micro
135 +1
+1
171
Maintaining clearances
The following clearance is required around the HMI device in order to its ensure self-
ventilation:
50
15 15
50
1)
15 15
2)
70
50
1) Applies to OP 77A
2) Applies to OP 77B
At least 10 mm clearance is required at the rear.
Notice
Ensure that the maximum ambient temperature is not exceeded when mounting the device
in a cabinet and especially in a closed enclosure.
Test voltages
Insulation strength is demonstrated in the type test with the following test voltages
conforming to IEC 61131-2:
Class of protection
Protection Class I conforming to IEC 60536, i.e. grounding conductor to profile rail required!
Notice
Degree of protection IP65
This degree of protection is only ensured if the following conditions are satisfied:
• The material strength at the mounting cut-out is at least 2 mm.
• The deviation from the plane of the mounting cut-out in an installed HMI device is ≤ 0.5 mm.
Notice
Do not install parts damaged during shipment. In the case of damaged parts, contact your
Siemens representative.
Keep the supplied documentation in a safe place. The documentation belongs to the HMI
device and is required for subsequent commissioning.
Requirements
You need two mounting clamps from the accessories kit for the installation. The mounting
seal must be available on the HMI device. If the mounting seal is damaged, order a
replacement seal. The mounting seal is part of the associated service pack.
Mounting
Notice
Always mount the HMI device according to the instructions in this manual.
Proceed as follows:
1. Check that the mounting seal is fitted on the HMI device.
Do not install the mounting seal turned inside out. This may cause leaks in the mounting
cut-out.
2. Insert the HMI device into the mounting cut-out from the front.
3. Insert the mounting clamps into the recesses on the side of the HMI device.
Notice
Check the fit of the mounting seal on the front. The mounting seal must not protrude from
the HMI device
Otherwise, repeat steps 1 to 4.
Requirements
The HMI device must be mounted according to the specifications of these operating
instructions.
Connection sequence
Connect the HMI device in the following sequence:
1. Equipotential bonding
2. Power supply
Perform a power-up test to ensure that the correct polarity of the supply voltage.
3. PLC/configuration computer as necessary
4. Peripheral equipment as necessary
Notice
Connection sequence
Always follow the correct sequence for connecting the HMI device. Failure to do so may
result in damage to the HMI device.
See also
Safety Information (Page 2-1)
4.2.2.1 Interfaces
The figure below shows the interfaces of the HMI device.
See also
Power supply (Page 12-7)
RS 485 (IF 1B) on OP 73 (Page 12-7)
Potential differences
Differences in potential between spatially separated system parts can lead to high equalizing
currents over the data cables and therefore to the destruction of their interfaces. This
situation may arise if the cable shielding is terminated at both ends and grounded at different
system parts.
Potential differences may develop when a system is connected to different mains.
Notice
Equipotential bonding conductor
Cable shielding is not suitable for equipotential bonding. Always use the prescribed
equipotential bonding conductors. The minimum cross-section of a conductor used for
equipotential bonding is 16 mm². When you install MPI and PROFIBUS DP networks,
always use cables with a sufficient crosssection since otherwise the interface modules
may be damaged or destroyed.
Wiring diagram
3 3
5 6 7 8
See also
Electromagnetic compatibility (Page 2-7)
Wiring diagram
The figure below illustrates the connection between the HMI device and PLC.
SIMATIC S7
RS 485
RS 485
Notice
Always use the approved cables for connecting a SIMATIC S7 PLC.
Standard cables are available for the connection. For further information, refer to the
SIMATIC HMI Catalog ST 80.
See also
Interfaces (Page 4-3)
Wiring diagram
The figure below illustrates the connection between the HMI device and configuration
computer.
PC
MPI
MPI/PROFIBUS DP
PC
RS 485
RS 232
RS 232
See also
Interfaces (Page 4-3)
Starting the transfer manually (Page 7-5)
Starting the transfer automatically (Page 7-6)
Backup and restore operations in WinCC flexible (Page 7-12)
Backup and restore operations using ProSave (Page 7-14)
Updating the operating system using WinCC flexible (Page 7-20)
Updating the operating system in ProSave (Page 7-21)
Notice
Damage
Pressure on the screwdriver may damage the HMI device socket if the terminal block is
plugged in when you tighten the screws.
Always remove the terminal block to connect the wires.
GND
DC +24 V
Figure 4-7 Connecting the terminal block
Connect the power supply cables to the terminal block as shown in the figure above. Ensure
that the cables are not crossed. Refer to the label showing the pin-out on the rear of the HMI
device.
Caution
Ensure safe electrical insulation of the power supply. Always use power supply modules that
conform to IEC 364-4-41 or HD 384.04.41 (VDE 0100, Part 410).
Always use power supply modules that comply to SELV (Safety Extra-Low Voltage) and
PELV (Protective Extra Low Voltage) standards.
The power supply voltage must always be within the specified range to prevent malfunctions
on the HMI device.
Equipotential bonding
Therefore, wire the 24 V output of the power supply to the equipotential circuit.
See also
Interfaces (Page 4-3)
Procedure
Proceed as follows:
1. Plug the terminal block into the HMI device.
2. Switch on the power supply.
After power is on, the display lights up and the bootloader appears briefly.
OP 73
bootloader vx.xx
(2004-xx-xx)
If the HMI device does not start, it is possible the wires on the terminal block have been
crossed. Check the connected wires and change the connections if necessary. The
Loader opens once the operating system has started.
Loader
Transfer
Start
The HMI device automatically sets transfer mode during initial startup if it does no contain
any project data yet. The following dialog appears:
Transfer
Connecting to host.
3. Press ESC
to cancel the transfer.
Result
The Loader appears again.
Note
When restarting the system, a project may already be loaded on the HMI device. The system
then skips transfer mode and starts the project.
Close the project by pressing the corresponding control object.
Further information on this may be available in your plant documentation.
Button Action
+/– TAB
Press one of these cursor keys to select the next entry in arrow
or direction.
ENTER
• The input is confirmed.
• The submenu or dialog shown below opens.
HELP
ESC
• Move back
Returns to the next higher menu layer.
• Cancel transfer mode
Function test
Perform a function test following commissioning. The HMI device is fully functional when one
of the following states is indicated:
• The "Transfer" dialog is displayed.
• The Loader is displayed.
• A project is started.
Requirements
Four mounting clamps from the kit are needed to mount the HMI device. The mounting seal
must be available on the HMI device. If the mounting seal is damaged, order a replacement
seal. The mounting seal is part of the associated service pack.
Mounting
Notice
Always mount the HMI device according to the instructions in this manual.
Proceed as follows:
1. Check that the mounting seal is fitted on the HMI device.
Do not install the mounting seal turned inside out. This may cause leaks in the mounting
cut-out.
2. Insert the HMI device into the mounting cut-out from the front.
3. Insert the mounting clamps into the recesses on each side of the HMI device.
Insert all four clamps in the HMI device and fasten them.
4. Tighten the clamps by screwing down the recessed head screw; permitted torque:
0.15 N/m.
Notice
Check the fit of the mounting seal on the front. The mounting seal must not protrude from
the HMI device
Otherwise, repeat steps 1 to 4.
Requirements
The HMI device must be mounted according to the specifications of these operating
instructions.
Connection sequence
Connect the HMI device in the following sequence:
1. Equipotential bonding
2. Power supply
Perform a power-up test to ensure that the correct polarity of the supply voltage.
3. PLC/configuration computer as necessary
4. Peripheral equipment as necessary
Notice
Connection sequence
Always follow the correct sequence for connecting the HMI device. Failure to do so may
result in damage to the HMI device.
4.3.2.1 Interfaces
The figures below show the interfaces of the HMI device.
1 2 3
1 2 3 4 5
See also
Power supply (Page 12-7)
RS 485 (IF 1B) on OP 73 (Page 12-7)
RS 422/RS 485 (IF 1B) on OP 77B (Page 12-9)
USB on OP 77B (Page 12-10)
RS 232 (IF 1A) on OP 77B (Page 12-10)
RS 485 (IF 1B) on OP 77A (Page 12-8)
Potential differences
Differences in potential between spatially separated system parts can lead to high equalizing
currents over the data cables and therefore to the destruction of their interfaces. This
situation may arise if the cable shielding is terminated at both ends and grounded at different
system parts.
Potential differences may develop when a system is connected to different mains.
Notice
Equipotential bonding conductor
Cable shielding is not suitable for equipotential bonding. Always use the prescribed
equipotential bonding conductors. The minimum cross-section of a conductor used for
equipotential bonding is 16 mm². When you install MPI and PROFIBUS DP networks,
always use cables with a sufficient crosssection since otherwise the interface modules
may be damaged or destroyed.
Wiring diagram
3 3
5 6 7 8
See also
Electromagnetic compatibility (Page 2-7)
Wiring diagram
The figure below illustrates the connection between the HMI device and PLC.
SIMATIC S7
RS 485
RS 485
SIMATIC S5
RS 232
AS 511
TTY
RS 232
SIMATIC 500/505
SIMATIC S5
RS 485
SIMATIC S7
RS 485
SIMATIC 500/505
RS 422/RS 485
Notice
Always use the approved cables to connect a SIMATIC S7 PLC.
Applies to OP 77B:
For serial operation, connect the PLC either to the RS 232 or to the RS 422/RS 485 port.
Standard cables are available for the connection. For further information, refer to the
SIMATIC HMI Catalog ST 80.
Note
Note the diagrams of the DIL switch settings on the back of the HMI device.
The following table shows the settings of the DIL switch. The transmitting and receiving
direction is switched internally with the RTS signal.
4 3 2 1 No RTS on connector
ON
4 3 2 1 Applies to OP 77B:
PLC ON
the RS 422 port is
RS 422
enabled
4 3 2 1 Factory state
%XWWRQ 21
ON
See also
Setting the DIL switch (Page 5-8)
Wiring diagram
The figures below illustrates the connection between the HMI device and PLC.
PC
MPI
MPI/PROFIBUS DP
PC
RS 485
RS 232
RS 232
PC
USB
USB
PC
RS 232
RS 232
PC
MPI
MPI/PROFIBUS DP
Notice
Use the driver for the USB host adapter which is included in the WinCC flexible package.
Do NOT use the driver included in the adapter kit.
See also
Interfaces (Page 4-13)
Starting the transfer manually (Page 7-5)
Starting the transfer automatically (Page 7-6)
Backup and restore operations in WinCC flexible (Page 7-12)
Backup and restore operations using ProSave (Page 7-14)
Updating the operating system using WinCC flexible (Page 7-20)
Updating the operating system in ProSave (Page 7-21)
Wiring diagram
The diagram below shows the connection between the HMI device and peripherals.
A printer can be connected as a peripheral.
USB
Notice
Use the driver for the USB host adapter which is included in the WinCC flexible package. Do
NOT use the driver which is supplied with the adapter kit.
Always use cables with metal shielding braid which is grounded on both ends to connect the
printer to the HMI device.
On some printers you may also have to set the ASCII character set used in the project.
A list of printers released by Siemens AG is available in the Siemens Catalog ST 80, chapter
80. A current list of released printers is available on the Internet under Service & Support.
Notice
Rated load of the interface
The load capacity of the USB port is limited to 100 mA. Avoid any higher loads. Equipment
connected to the port may otherwise malfunction.
Note
Documentation for peripherals
Observe the printer documentation when you connect the printer.
See also
Interfaces (Page 4-13)
Notice
Damage
Pressure on the screwdriver may damage the HMI device socket if the terminal block is
plugged in when you tighten the screws.
Always remove the terminal block to connect the wires.
GND
DC +24 V
Figure 4-21 Connecting the terminal block
Connect the power supply cables to the terminal block as shown in the figure above. Ensure
that the cables are not crossed. Refer to the label showing the pin-out on the rear of the HMI
device.
Caution
Ensure safe electrical insulation of the power supply. Always use power supply modules that
conform to IEC 364-4-41 or HD 384.04.41 (VDE 0100, Part 410).
Always use power supply modules that comply to SELV (Safety Extra-Low Voltage) and
PELV (Protective Extra Low Voltage) standards.
The power supply voltage must always be within the specified range to prevent malfunctions
on the HMI device.
Equipotential bonding
Therefore, wire the 24 V output of the power supply to the equipotential circuit.
See also
Interfaces (Page 4-13)
If the HMI device does not start, it is possible the wires on the terminal block have been
crossed. Check the connected wires and change the connections if necessary. The
Loader menu opens after the operating system has started.
Loader B 7.0.0.52
Transfer
Start
Info/Settings
The HMI device automatically sets transfer mode during initial startup if it does no contain
any project data yet. This opens the following dialog:
Transfer ...
Connecting to host ...
3. Press ESC
to cancel the transfer.
Result
The Loader appears again.
Note
When restarting the system, a project may already be loaded on the HMI device. The system
then skips transfer mode and starts the project.
Close the project by pressing the corresponding control object.
Further information on this may be available in your plant documentation.
Button Action
Pressing one of these keys selects the menu command one level up.
or Pressing the key longer moves the selection continuously.
Pressing one of these keys selects the menu command one level down.
or Pressing the key longer moves the selection continuously.
ENTER
• The input is confirmed.
• The submenu or dialog shown below opens.
ESC
• Move back
Returns to the next higher menu layer.
• Cancel transfer mode
Function test
Perform a function test following commissioning. The HMI device is fully functional when one
of the following states is indicated:
• The "Transfer" dialog is displayed.
• The Loader is displayed.
• A project is started.
① Soft keys
② System keys – control keys
Standard input device at the HMI device is the keyboard. This is basically composed of two
key groups:
• Soft keys
F1 to F4
The soft keys can only be assigned within a project and do not have any function in the
Loader menu.
• System keys
These include the control keys, for example.
Notice
Unintentional actions
Unwanted actions may be triggered if the operator unintentionally actuates several keys
at once.
Never press more than two keys simultaneously.
Keyboard damage
Operation of the keys with hard, pointed or sharp objects or hard impact may lead to a
considerable reduction of the service life and even to complete failure.
Always use your fingers to operate the keys of your HMI device.
See also
Design of the OP 73micro HMI device (Page 1-1)
5.2 5.2 Operator control components and LEDs on the front panel of OP 77A
and OP 77B
1
4
2 5
Standard input device at the HMI device is the keyboard. This is basically composed of two
key groups:
• Soft keys
F1 to F4, and K1 to K4
The soft keys can only be assigned within a project and do not have any function in the
Loader menu.
• System keys
The numerical keypad and control keys belong to this group.
Notice
Unintentional actions
Unwanted actions may be triggered if the operator unintentionally actuates several keys
at once.
Never press more than two keys simultaneously.
Keyboard damage
Operation of the keys with hard, pointed or sharp objects or hard impact may lead to a
considerable reduction of the service life and even to complete failure.
Always use your fingers to operate the keys of your HMI device.
See also
Design of the OP 77A HMI device (Page 1-2)
1 3
Notice
Data loss
When requested by the HMI device to format an MCC for first time use, you should save a
backup copy of MCC data to a PC.
Notice
Data loss
All data on the MMC is lost if you attempt to remove it while the HMI device is accessing its
data.
Do not remove the MMC while data is being accessed. Observe the corresponding alarms
on the screen.
① Eject button
② MMC
Proceed as follows:
1. Press the ejection mechanism.
This slides the MMC out of the slot.
2. Store the memory card in a protective case.
Notice
Do not force the ejector. This could damage its mechanism.
15,3
8,25
160
Printable foil or paper can be used as labeling strips. Use transparent foil to retain visibility of
the function key LED. Permitted thickness of the labeling strip: 0.15 mm.
Procedure
Proceed as follows:
1. Edit and then print the template.
You can also print blank templates and label them manually.
Notice
Do not write on the keyboard to label the function keys.
Note
Wait for the printed labeling strips to dry before you insert them.
① Labeling strips
② Guide
5. Slide the labeling strips into the guide up to the end stop.
The labeling strip will protrude approximately 1 cm out of the guide. Select the template
dimensions so that the labeling is correctly placed behind the function key fields. An
interlock is not required for the labeling strips.
See also
Connecting the PLC (Page 4-16)
6.1.1 Overview
Loader
The figure below shows the Loader. It appears briefly when the HMI device starts up.
Loader
Transfer
Start
Info/Settings
Button Action
+/– TAB
By pressing one of these buttons, you select the next menu command
or in the direction of the cursor key.
ENTER
The corresponding menu opens.
HELP
ESC
Returns to the next higher menu layer.
Button Action
+/– TAB
Selects the previous or next list entry.
or
ENTER
The selected list entry is accepted.
HELP
ESC
You can undo your input as long you have not yet confirmed the
See also
Switching on power and testing the HMI (Page 4-9)
6.1.2.1 Overview
Requirements
"Info/Settings" was called in the Loader.
"Info/Settings" menu
Info/Settings
Contrast
Device Info
Version Info
Logon/Settings
Password protection
You can protect the "Logon/Settings" menu from unauthorized access by assigning a
password.
This prevents inadvertent wrong operation and increases security for the plant or machine
security because access to the settings is denied. If the user does not enter a password, this
user can only access the "Contrast", "Device Info" and "Version Info" menu commands.
When a password is assigned, the following dialog appears when the user attempts to open
the "Logon/Settings" menu:
Password
|
You need to enter the password again to access the "Logon/Settings" menu after you closed
the previous session.
Notice
Password no longer available
If the Loader password is no longer available, you can only call the "Logon/Settings" menu
again after you update the operating system.
All data on the HMI device will be overwritten when you update the operating system.
Note
The currently active entry is always indicated in a dialog.
See also
Assigning, changing and deleting passwords (Page 6-6)
Requirements
"Info/Settings ▶ Contrast" was selected from the Loader menu.
Principle
Contrast
Press Up/Down to
change contrast.
This dialog is used to adjust the contrast and therefore indirectly controls screen brightness.
Notice
Screen contrast
The screen contrast can be increased and reduced within a wide range. Note that this may
lead to the screen content becoming unrecognizable under unfavorable lighting conditions.
+/– TAB
Requirements
"Info/Settings ▶ Device Info" was selected from the Loader menu.
Principle
Device Info
Device: OP 73
Flashsize: 2 MB
This dialog is used to indicate the name of the HMI device ("Device") and the size of internal
Flash memory ("Flashsize"). The Flash memory is used to store the HMI device image and
project data. The size of the internal Flash memory does not correspond to the available
working memory for a project.
Requirements
"Info/Settings ▶ Version Info" was selected from the Loader menu.
Principle
Version Info
01.00.00.00_05.08
BL 0.17/2004-xx-xx
The "Version Info" dialog shows information on the Bootloader and the HMI device image file
and therefore the version of the operating system.
This information is required when you contact A&D Technical Support.
6.1.3.1 Overview
Requirements
"Info/Settings ▶ Logon/Settings" was selected from the Loader menu. You have entered the
password for the "Settings" menu.
"Settings" menu
Settings
Startup Delay
Password
Transfer Settings
"Startup Delay" Menu command for setting the startup delay on the HMI device
"Password" Password menu command
"Transfer Settings" Menu command for transfer settings
Select the "Settings" menu to edit the system settings for your HMI device.
Access to this menu can be protected by a password.
Procedure
Proceed as follows:
1. Close the project.
2. Open the "Logon/Settings" menu.
3. Edit the settings.
4. Close the "Logon/Settings" menu.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Startup Delay" was selected from the Loader menu.
Principle
Startup Delay
Value: 3 Sec.
The delay defines the period which the HMI device automatically delays the startup of a
stored project.
When the value "0" is set, the project starts immediately. It is then no longer possible to call
the Loader after switching on the HMI device. To handle this situation, you must have
configured an operator control object you can use to close the project.
Valid range of values: 0 s to 60 s.
Introduction
To restrict access to the "Settings" menu to specific members of staff, define a password in
the "Password" dialog.
Requirements
• "Info/Settings ▶ Logon/Settings ▶ Password" was selected from the Loader menu.
• The "Password" dialog opens.
Password
|
Note
Password entry
The last character of the password entered is shown in plain text. The remaining
characters are represented by a ∗ character.
2. Press ENTER
You have now completed entry of the password. The "Confirm Password" dialog appears.
Confirm Password
|
4. Press ENTER
,
You have now completed the password confirmation. The password is accepted if both
password entries are identical. Otherwise, an error message appears. The "Settings"
menu opens. Repeat the password input.
Result
• The "Settings" menu opens.
• The "Settings" menu is password protected.
1. Press ENTER
– do not enter any other characters.
The "Confirmation" dialog opens.
2. Press ENTER
– do not enter any other characters.
The system confirms the deletion.
Result
• The "Settings" menu opens.
• You have revoked the password protection of the "Settings" menu.
See also
Overview (Page 6-2)
Introduction
By disabling a data channel, you can protect the HMI device from unintentional overwriting of
project data and of the HMI device image.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Transfer Settings" was selected from the Loader menu.
Overview
Transfer Settings
Channel 1: serial
Channel 2: MPI/DP
MPI/DP Address
MPI/DP Baudrate
Note
You can set each dialog entry separately. Default entry for "Channel 2: MPI/DP" is
"disabled".
Serial channel
Channel 1: serial
Value: Enable
+/– TAB
This dialog is used to configure the RS495 port for serial data transfer. Select or
to make the following settings:
• "Disable"
Serial data transfer is disabled.
• "Enable"
Serial data transfer is enabled.
MPI/PROFIBUS DP channel
Channel 2: MPI/DP
Value: Disable
Use this dialog to set the transfer parameters for the MPI/PROFIBUS DP interface. Select
+/– TAB
MPI/PROFIBUS DP address
MPI/DP Address
Value: 1
Use this dialog to set the MPI/PROFIBUS DP address of the HMI device. Permitted range of
values: 0 to 126.
Note
MPI/PROFIBUS DP address
The assigned MPI/PROFIBUS DP address must be unique in the network.
+/–
Use this dialog to set the MPI/PROFIBUS DP baud rate for the HMI device. Select or
TAB
Note
MPI/DP baud rate
The MPI/PROFIBUS DP baud rate must be consistent throughout the network.
Result
The data channel is configured.
General notes
Warning
Unintentional Transfer mode
Ensure that the configuration computer does not inadvertently switch the HMI device to
Transfer mode during ongoing operation. This could cause unintentional actions to be
triggered in the plant.
Notice
Transfer mode using MPI/PROFIBUS DP
For MPI/PROFIBUS DP transfer, the bus parameters, for example the MPI/PROFIBUS DP
address of the HMI device, are read from the current project on the HMI device.
The settings for MPI/PROFIBUS DP transfer can be modified. For this, you must first close
the project and then change the settings on the HMI device. Then go back to "Transfer"
mode.
The HMI device uses the new MPI/DP settings until you transfer a new project to it. During
the next transfer of a project to the HMI device, the MPI/DP settings will be overwritten with
the values from the transferred project.
You can thus edit the MPI/DP settings irrespective of the project settings.
Transfer settings
A project can only be transferred from the configuration computer to the HMI device when at
least one of the data channels is enabled on the HMI device.
6.2.1 Overview
Loader
The figure below shows the Loader. It appears briefly when the HMI device starts up.
Loader B 7.0.0.52
Transfer
Start
Info/Settings
Button Action
By pressing one of these buttons, you select the next menu command
or in the direction of the cursor key.
ENTER
The corresponding menu opens.
ESC
Returns to the next higher menu layer.
Button Action
Selects the previous or next list entry.
or
END
9
You can use the numerical keypad for direct input of values.
0
up to
ENTER
The selected list entry is accepted.
ESC
You can undo your input as long you have not yet confirmed the
See also
Switching on power and testing the HMI (Page 4-22)
6.2.2.1 Overview
Requirements
"Info/Settings" was called in the Loader.
"Info/Settings" menu
Info/Settings
Contrast
Device Info
Version Info
Logon/Settings
Password protection
You can protect the "Logon/Settings" menu from unauthorized access by assigning a
password.
This prevents inadvertent wrong operation and increases security for the plant or machine
security because access to the settings is denied. If the user does not enter a password, this
user can only access the "Contrast", "Device Info" and "Version Info" menu commands.
When a password is assigned, the following dialog appears when the user attempts to open
the "Logon/Settings" menu:
Logon / Settings
Password:
You need to enter the password again to access the "Logon/Settings" menu after you closed
the previous session.
Notice
Password no longer available
If the Loader password is no longer available, you can only call the "Logon/Settings" menu
again after you update the operating system.
All data on the HMI device will be overwritten when you update the operating system.
Note
The currently active entry is always indicated in a dialog.
See also
Assigning, editing and deleting passwords (Page 6-19)
Requirements
"Info/Settings ▶ Contrast" was selected from the Loader menu.
Principle
Contrast
Press Up/Down to
change contrast
This dialog is used to adjust the contrast and therefore indirectly controls screen brightness.
Notice
Screen contrast
The screen contrast can be increased and reduced within a wide range. Note that this may
lead to the screen content becoming unrecognizable under unfavorable lighting conditions.
Requirements
"Info/Settings ▶ Device Info" was selected from the Loader menu.
Principle
Device Info
Device: OP 77A
Flashsize: 2 MB
Device Info
Device: OP 77B
Flashsize: 4 MB
This dialog is used to indicate the name of the HMI device ("Device") and the size of internal
Flash memory ("Flashsize"). The Flash memory is used to store the HMI device image and
project data. The size of the internal Flash memory does not correspond to the available
working memory for a project.
Requirements
"Info/Settings ▶ Version Info" was selected from the Loader menu.
Principle
Version Info
01.00.00.00_05.08
BL 0.25/2004-xx-xx
Version Info
Bootloader: 1.02/xx.x.2004
Image: B 7.0.0.xx
The "Version Info" dialog shows information on the Bootloader and the HMI device image file
and therefore the version of the operating system.
This information is required when you contact A&D Technical Support.
6.2.3.1 Overview
Requirements
"Info/Settings ▶ Logon/Settings" was selected from the Loader menu. You have entered the
password for the "Settings" menu.
"Settings" menu
Settings
Startup Delay
Password
Transfer Settings
Settings
Startup Delay
ScreenSaver
Regional Settings
Password
Backup/Restore
Transfer Settings
Printer Settings
Reset Device
"Startup Delay" Menu command for setting the startup delay on the HMI device
"Screen Saver" Menu command for the screen saver
"Regional Settings" Menu command for regional settings
"Password" Menu command for the password
"Backup/Restore" Menu command for backup/restore
"Transfer Settings" Menu command for transfer settings
"Printer Settings" Menu command for printer settings
"Reset Device" Reset menu commands, only appears if a password has been assigned.
Select the "Settings" menu to edit the system settings for your HMI device.
Access to this menu can be protected by a password.
Procedure
Proceed as follows:
1. Close the project.
2. Open the "Info/Settings" menu.
3. Edit the settings.
4. Close the "Info/Settings" menu.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Startup Delay" was selected from the Loader menu.
Principle
Startup Delay
Value: 3 sec
The delay defines the period which the HMI device automatically delays the startup of a
stored project.
When the value "0" is set, the project starts immediately. It is then no longer possible to call
the Loader after switching on the HMI device. To handle this situation, you must have
configured an operator control object you can use to close the project.
Valid range of values: 0 s to 60 s.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Screen saver" was selected from the Loader menu.
Principle
ScreenSaver
Activation: 0 min
Use this dialog to set the activation delay for the screen saver.
Valid range of values: 0 min to 60 min. The screen saver is disabled when you set 0.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Regional Settings" was selected from the Loader menu.
Principle
Region
Value: German
Use this dialog to set the date and time format, for example. The decimal places in numerical
values are delimited either by a point or comma, based on the configured regional language.
Note
If the HMI device operating system does not support a specific project language, it
automatically uses the default set in the "Regional Settings" dialog.
Introduction
To restrict access to the "Settings" menu to specific members of staff, define a password in
the "Password" dialog.
Requirements
• "Info/Settings ▶ Logon/Settings ▶ Password" was selected from the Loader menu.
• The "Password" dialog opens.
Password
Password:
Note
Password entry
The last character of the password entered is shown in plain text. The remaining
characters are represented by a ∗ character.
2. Press ENTER
.
You have now completed entry of the password. The "Confirm Password" dialog appears.
Confirmation
Password:
For the password to become valid, it must be entered again to confirm it.
3. Enter the password again.
4. Press ENTER
.
You have now completed entry of the password. The password is accepted if both
password entries are identical. Otherwise, an error message appears. The "Settings"
menu opens. Repeat the password input.
Result
• The "Settings" menu opens.
• The "Settings" menu is password protected.
1. Press ENTER
– do not enter any other characters.
The "Confirmation" dialog opens.
2. Press ENTER
– do not enter any other characters.
The system confirms the deletion.
Result
• The "Settings" menu opens.
• You have revoked the password protection of the "Settings" menu.
See also
Overview (Page 6-13)
Requirements
• "Info/Settings ▶ Logon/Settings ▶ Backup/Restore" was selected from the Loader menu.
• An MMC is inserted in the HMI device.
Principle
Backup/Restore
Action: Backup
When using an MMC, select the "Backup" and "Restore" functions from this dialog. The
selected "Backup" or "Restore" function is executed immediately when you press ENTER
.
See also
Overview (Page 7-1)
Backup and restore operations with MMC on OP 77B (Page 7-16)
Introduction
By disabling a data channel, you can protect the HMI device from unintentional overwriting of
project data and of the HMI device image.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Transfer Settings" was selected from the Loader menu.
Overview
Transfer Settings
Channel1: serial
Channel2: MPI/DP
MPI/DP Address
MPI/DP Baudrate
Transfer Settings
Channel1: serial
Select Channel2
Channel2: MPI/DP
MPI/DP Address
MPI/DP Baudrate
Transfer Settings
Channel1: serial
Select Channel2
Channel2: USB
Note
You can set each dialog entry separately.
Serial channel
Channel1: serial
Value: Enable
Use this dialog to configure the RS495 port for serial data transfer on the OP 77A. Select
• "Enable"
Serial data transfer is enabled.
Serial Settings
Value: Enable (remote on)
Use this dialog to configure the RS232 port for serial data transfer on the OP 77B. Select
Use this dialog to toggle between the MPI/PROFIBUS DP and USB ports. Select and
MPI/PROFIBUS DP channel
Channel2: MPI/DP
Value: Disable
MPI/DP Settings
Value: Enable (remote on)
Use this dialog to set the transfer parameters for the MPI/PROFIBUS DP interface. Select
MPI/PROFIBUS DP address
MPI/DP Address
Value: 1
Use this dialog to set the MPI/PROFIBUS DP address of the HMI device. Permitted range of
values: 0 to 126.
Entries can be made using the numerical keyboard or the cursor keys.
Note
MPI/PROFIBUS DP address
The assigned MPI/PROFIBUS DP address must be unique in the network.
Use this dialog to set the MPI/PROFIBUS DP baud rate for the HMI device.
Note
MPI/DP baud rate
The MPI/PROFIBUS DP baud rate must be consistent throughout the network.
Warning
Unintentional Transfer mode
Ensure that the configuration computer does not inadvertently switch the HMI device to
Transfer mode during ongoing operation. This could cause unintentional actions to be
triggered in the plant.
Result
The data channel is configured.
General notes
Notice
Transfer mode using MPI/PROFIBUS DP
For MPI/PROFIBUS DP transfer, the bus parameters, for example the MPI/PROFIBUS DP
address of the HMI device, are read from the current project on the HMI device.
The settings for MPI/PROFIBUS DP transfer can be modified. For this, you must first close
the project and then change the settings on the HMI device. Then go back to Transfer mode.
OP 77A
The HMI device uses the new MPI/DP settings until you transfer a new project to it. During
the next transfer of a project to the HMI device, the MPI/DP settings will be overwritten with
the values from the transferred project.
You can thus edit the MPI/DP settings irrespective of the project settings.
OP 77B
The HMI device uses the new MPI/DP settings until you start a new project or transfer a
project to it. During the next start or transfer of a project to the HMI device, the MPI/DP
settings will be overwritten with the values from the project.
Transfer settings
A project can only be transferred from the configuration computer to the HMI device when at
least one of the data channels is enabled on the HMI device.
Do not edit the transfer settings while a project is active or the HMI device is in transfer
mode.
Use this dialog to set the transfer parameters for the USB port. Select and to
make the following settings:
• "Disable"
USB data transfer is disabled.
• "Enable (remote off)"
USB data transfer is enabled. Automatic transfer is disabled.
• "Enable (remote on)"
USB data transfer is enabled. Automatic transfer is enabled.
Warning
Unintentional Transfer mode
Ensure that the configuration computer does not inadvertently switch the HMI device to
Transfer mode during ongoing operation. This could cause unintentional actions to be
triggered in the plant.
Result
The data channel is configured.
6.2.4.1 Overview
Requirements
"Info/Settings ▶ Logon/Settings ▶ Printer Settings" was selected from the Loader menu.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Printer Settings" was selected from the Loader menu.
Principle
Printer Language
Value: Epson9
Use this dialog to set the printer language. The following printer languages can be set:
• "Epson9"
• "Epson24"
• "Stylus Color"
• "PLC Laser"
• "PLC Inkjet"
Refer to the printer manual to find out which of these printer languages is used.
Requirements
"Info/Settings ▶ Logon/Settings ▶ Printer Settings ▶ Paper size" was selected from the
Loader menu.
Principle
Paper Size
Value: A4
Use this dialog to set the page format for printing. The following page formats are available:
• "A4"
• "Letter"
• "Legal"
• "B5"
Requirements
"Info/Settings ▶ Logon/Settings ▶ Printer Settings ▶ Orientation" was selected from the
Loader menu.
Principle
Orientation
Value: Portrait
Use this dialog to set the printer orientation. The following printer orientations are available:
• "Portrait"
The print is output in portrait format.
• "Landscape"
The print is output in landscape format.
Requirements
The "Info/Settings ▶ Logon/Settings ▶ Printer Settings ▶ Draft Mode" menu command was
selected.
Principle
Draft Mode
Value: Off
Use this dialog to set the print quality. The following settings are possible:
• "Off"
Draft mode is disabled. The print is output in best quality.
• "On"
Draft mode is enabled. The print is output in draft quality. The print speed, however, is
higher in this mode.
Transferring a project
PLC
2 4
Figure 7-2 Schematic diagram of the transfer, backup and restore functions
Operating modes
Operating modes of the HMI device:
• Offline
• Online
• Transfer
"Offline mode" and "Online mode" can be set on the configuration computer and on the HMI
device. To set these modes on the HMI device, use a corresponding operator control object
of the project.
"Offline" mode
In this mode, there is no communication between the HMI device and PLC. Although the
HMI device can be operated, it cannot exchange data with the PLC.
"Online" mode
In this mode, the HMI device and PLC communicate. You can operate the plant on the HMI
device according to your system configuration.
"Transfer" mode
In this mode, you can transfer a project from the configuration computer to the HMI device or
backup and restore HMI device data, for example.
The following options are available for setting "Transfer" mode on the HMI device:
• When the HMI device starts up
Start "Transfer" mode manually in the HMI device Loader.
• During ongoing operation
Start transfer mode manually within the project using an operator control object. The HMI
device toggles to "Transfer" mode when automatic mode is set and a transfer is initiated
on the configuration computer.
Overview
The table below shows the options for transferring data between the configuration computer
and OP 73, OP 77A and OP 77B.
7.2.1 Overview
Transfer
During transfer, the project is downloaded from the configuration computer to the HMI
device.
The "Transfer" mode can be started manually or automatically on the HMI device.
Transferred data is written directly to the flash memory on the HMI device. The transfer
function uses a data channel you need to configure before you initiate any transfers.
Introduction
You can set "Transfer" mode manually on the HMI device using a configured operator
control object and during ongoing operation.
Requirements
• The *.hmi project is opened in WinCC flexible.
• The HMI device is connected to a configuration computer.
• The data channel is configured on the HMI device.
• The HMI device Loader is opened.
Procedure
Proceed as follows to initiate the transfer:
1. Switch to "Transfer" mode on the HMI device.
2. Proceed as follows on the configuration computer:
– Select the "Project ▶Transfer ▶Transfer Settings" menu command in WinCC flexible.
– Select the HMI device and define the parameters for the connection.
– Start the download with "Transfer".
The configuration computer verifies its connection to the HMI device. If the connection is
not available or is faulty, the configuration computer outputs an alarm. If no
communication error is detected, the project is transferred to the HMI device.
Result
When the transfer is completed successfully, the data can be found on the HMI device. The
transferred project is then started automatically.
See also
Overview (Page 7-5)
Configuring the data channel (Page 6-8)
Configuring the data channel (Page 6-21)
Data transfer options (Page 7-4)
Setting the operating mode (Page 7-3)
Introduction
The HMI device can be automatically switched to "Transfer" mode during runtime as soon as
transfer is started on the configuration computer connected.
Automatic startup is particularly suited for the test phase of a new project since transfer is
completed without interfering with the HMI device.
OP 73 and OP 77A support automatic transfers only via MPI/PROFIBUS DP.
Notice
If the automatic transfer has been activated on the HMI device and a transfer is initiated on
the configuration computer, the project currently running is automatically stopped. The HMI
device then automatically switches to "Transfer" mode.
After the commissioning phase, deactivate the automatic transfer so that the HMI device
cannot be inadvertently switched to Transfer mode. The transfer mode can trigger
unintentional actions in the device.
You can set a password in the Loader of the HMI device to restrict access to the transfer
settings and thus avoid unauthorized modifications.
Applies to OP 77B:
The current project can not be closed if there is an active dialog. Close the dialog or cancel
the transfer operation on the configuration computer.
Requirements
• The HMI device is connected to a configuration computer.
• The data channel is configured on the HMI device.
• The automatic transfer is activated in the data channel for the transfer.
• The project is started.
Procedure
Proceed as follows on the configuration computer:
1. Select the "Project ▶Transfer ▶Transfer Settings" menu command in WinCC flexible.
2. Select the HMI device and define the parameters for the connection.
3. Start the download with "Transfer".
The connection to the HMI device is checked. If the connection is not available or
defective, the configuration computer issues the corresponding error message. In the
case of an error-free connection, the HMI device ends the running project and switches to
"Transfer" mode. The selected data is transferred to the HMI device.
Result
When the transfer is completed successfully, the data can be found on the HMI device. The
transferred project is then started automatically.
See also
Configuring the data channel (Page 6-8)
Configuring the data channel (Page 6-21)
Data transfer options (Page 7-4)
Overview (Page 7-5)
Introduction
There are two options on the HMI device testing a project:
• Offline testing of the project
Offline testing means that communication between the HMI device and PLC is down
while the test is being carried out..
• Online testing of the project
Online testing means that the HMI device and PLC communicate with each other during
testing.
Perform both tests, starting with the "Offline test", followed by the "Online test".
Note
Applies to OP 77B:
The project can also be debugged on a configuration computer by means of the Simulator.
For detailed information, refer to the "WinCC flexible" user manual and to the WinCC flexible
Online Help.
Testing a project
You should always test the project on the HMI device on which the project will be used.
Procedure
In "Offline" mode, you can test the various project functions on the HMI device without them
being affected by the PLC. PLC tags, therefore, are not updated.
Test the operator control objects and visualization of the project as far as possible without
connecting to the PLC.
Procedure
In "Offline" mode, you can test the various project functions on the HMI device without them
being affected by the PLC. PLC tags are updated in this case.
Test the operator control objects and views of the project.
You should especially test the project objects which require communication with the PLC:
• Alarms
• Screen selection by the PLC or on PLC request.
Applies to OP 77B:
• Recipes
• Print function
See also
Setting the operating mode (Page 7-3)
Introduction
When the "Enable Upload" check box is set on the configuration computer for transferring a
project, the corresponding compressed source file is included in the transfer operation. This
allows the upload from the HMI device to the configuration computer.
After you uploaded a compressed source file, you can be analyzed and modify the active
project. This is of particular importance when:
• The original configuration computer is not available.
• The project source file is no longer available.
Requirements
Requirements for uploading the project from the HMI:
• The HMI device is connected to a configuration computer.
• The compressed source file of the project must be available on an MMC which is inserted
in the HMI device.
• A project is open in WinCC flexible.
Notice
Project ID
The uploaded compressed source file can only be opened in the engineering software if
the following condition is satisfied:
The project ID of the currently used engineering software is higher than or equal to the
project ID of the engineering software used to create the project.
Verifying the source file
There is no check in WinCC flexible or on the HMI device to determine if the project file
on the HMI device and the compressed source file on the MMC belong to the same
project. Only the project file is transferred when the "Enable Upload" check box is
disabled. Any source file on the MMC must therefore belong to a previously transferred
project.
Procedure
Proceed as follows on the configuration computer:
1. In WinCC flexible, select the menu command "Project ▶ Transfer ▶ Communication
Settings".
The "Communication Settings" dialog opens.
2. Select the HMI device type.
3. Select the type of connection between the HMI device and the configuration computer.
4. Set the connection parameters.
5. Select "OK".
Result
When all data are uploaded to the configuration computer, the WinCC flexible engineering
software unpacks the compressed file. The uploaded project can now be opened for editing
on the configuration computer. The file is available in *.hmi format.
See also
Configuring the data channel (Page 6-21)
Setting the operating mode (Page 7-3)
7.3.1 Overview
Introduction
Data located on the HMI device can be backed up using a PC external to the HMI device
and can be restored from it.
The following data in the internal Flash memory can be backed up and restored:
• Project
• HMI device image
• Password list
• Recipe data list (applies only to OP 77B)
Based on the type of HMI device used, you can backup and restore the data using:
• MMC (applies only to OP 77B)
• WinCC flexible
• ProSave
General notes
Notice
Power failure
If an operation for restoring data is interrupted due to power failure on the HMI device, the
operating system of the HMI device may be deleted! The operating system then has to be
updated.
Compatibility conflict
If a message is output on the HMI device warning of a compatibility conflict during the
restore operation, the operating system must be updated.
Bootstrapping
You can restore project data using ProSave or WinCC flexible with or without bootstrap
loading, depending on the HMI device.
• Restoring without bootstrapping
First, set "Transfer" mode on the HMI device or use the automatic transfer function if the
project is active. Then start the restore in ProSave or WinCC flexible.
• Restoring with bootstrapping
First, start the restore in ProSave or WinCC flexible and then switch the power on the
HMI device off and on again.
Note
Restoring with bootstrapping is also possible when the HMI device operating system is
corrupt and you can therefore can no longer run the Loader of the HMI device.
Use the "Bootstrap" check box in ProSave to determine the restoring procedure.
Introduction
Backup and restore operations transfer the relevant data between flash memory on the HMI
device and a configuration computer.
Requirements
• The HMI device is connected to a configuration computer.
• No project is open in WinCC flexible.
• Relevant only for backup or for restore operations without bootstrapping:
The data channel is configured on the HMI device.
Procedure - Backup
Proceed as follows:
1. Select the menu command "Project ▶ Transfer ▶ Communication Settings" in
WinCC flexible on the configuration computer.
The "Communication Settings" dialog opens.
2. Select the HMI device type.
3. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
4. Close the dialog with "OK".
5. In WinCC flexible, select the menu command "Project ▶ Transfer ▶ Backup".
The "Backup Settings" dialog opens.
6. Select the data to be backed up.
7. Select a destination folder and a file name for the *.psb backup file.
8. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a backup is initiated.
9. Start the backup operation in WinCC flexible with "OK" on the configuration computer.
Follow the instructions in WinCC flexible.
A status view opens to indicate the progress of the operation.
Result
The system outputs a message when the backup is completed.
The relevant data is now backed up on the configuration computer.
Procedure - Restore
Proceed as follows:
1. Select the menu command "Project ▶ Transfer ▶ Communication Settings" in
WinCC flexible on the configuration computer.
The "Communication Settings" dialog opens.
2. Select the HMI device type.
3. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
4. Close the dialog with "OK".
5. In WinCC flexible, select the menu command "Project ▶ Transfer ▶ Restore".
The "Restore Settings" dialog dialog opens.
6. Select the *.psb backup file to be restored from the "Open" dialog.
The view shows from which HMI device the backup file originates and the type of data it
contains.
7. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
8. Start the restore operation in WinCC flexible with "OK" on the configuration computer.
Follow the instructions in WinCC flexible.
A status view opens to indicate the progress of the operation.
Result
The transfer is completed when the backup data is restored from the configuration computer
to the HMI device.
See also
Overview (Page 7-11)
Data transfer options (Page 7-4)
Setting the operating mode (Page 7-3)
Configuring the data channel (Page 6-21)
Configuring the data channel (Page 6-8)
Introduction
Backup and restore operations transfer the relevant data between flash memory on the HMI
device and a PC.
Requirements
• The HMI device is connected to a PC on which ProSave is installed.
• Relevant only for backup or for restore operations without bootstrapping:
The data channel is configured on the HMI device.
Procedure - Backup
Proceed as follows:
1. From the Windows Start menu, run ProSave on the PC.
2. Select the HMI device type from the "General" tab.
3. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
4. Use the "Backup" tab to select the relevant data.
5. Select a destination folder and a file name for the *.psb backup file.
6. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a backup is initiated.
7. Start the backup operation in ProSave with "Start Backup".
Follow the instructions in ProSave.
A status view opens to indicate the progress of the operation.
Result
The system outputs a message when the backup is completed.
The relevant data is now backed up on the PC.
Procedure - Restore
Proceed as follows:
1. Only relevant for restore operations with bootstrapping:
Switch off power to the HMI device.
2. From the Windows Start menu, run ProSave on the PC.
3. Select the HMI device type from the "General" tab.
4. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
5. In the "Restore" tab, select restore with/without bootstrapping by setting the "Bootstrap"
check box accordingly.
6. Select the *.psb backup file to be restored from the "Restore" tab.
The view shows from which HMI device the backup file originates and the type of data it
contains.
7. Only relevant for restore operations without bootstrapping:
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
8. Start the restore operation in ProSave with "Start Restore".
Follow the instructions in ProSave.
A status view opens to indicate the progress of the operation.
Result
The transfer is completed when the backup data is restored from the PC to the HMI device.
See also
Overview (Page 7-11)
Data transfer options (Page 7-4)
Setting the operating mode (Page 7-3)
Configuring the data channel (Page 6-8)
Configuring the data channel (Page 6-21)
Introduction
The system generates a backup copy of the operating system, applications and data in flash
memory of the HMI device and writes it to an MMC. Any backup date on the MMC will be
deleted on confirmation.
A restore operation deletes all old data from flash memory of the HMI device on
confirmation. Next, the backup data are copied from the MMC to the internal flash memory.
Requirements
You require an MMC with a minimum capacity of 32 MB.
The system outputs an alarm if no MMC is found in the MMC slot. Insert the required MMC
Procedure - Backup
Proceed as follows:
1. Insert the MMC into the memory card slot.
2. Select "Info/Settings ▶ Logon/Settings ▶ Backup/Restore" from the Loader menu.
The "Backup/Restore" dialog opens.
3. Select "Backup".
4. Press ENTER
.
If previous backup data are found on the MMC, the system outputs the following
message:
You may have an old backup
on the storage card. Do you
want to delete it?
ENTER – Yes; ESC – No
After the backup copy has been created, the following alarm appears:
Backup successfully completed.
Press OK and remove your
storage card.
Press ENTER to continue.
5. Press ENTER
.
This concludes the backup operation.
Result
The transfer is completed when all HMI data are backed up to the MMC.
Label the MMC with the date and version of the backed up project, for example, and then
store it in a safe place.
Procedure - Restore
Proceed as follows:
1. Insert the MMC into the memory card slot
2. Select "Info/Settings ▶ Logon/Settings ▶ Backup/Restore" from the Loader menu.
The "Backup/Restore" dialog opens.
3. Select "Restore".
Press ENTER
.
The system outputs the following message:
Checking data ...
The MMC content is now checked. The system outputs the following message if a valid
backup copy is found on the MMC:
You are starting RESTORE now.
All installed licenses, all files (except
files on storage card) and the regis-
try will be erased. Are you sure?
ENTER – Yes; ESC – No
An alarm is output if no valid data are found on the MMC. Select ESC
to return to the
"Logon/Settings" menu.
4. Press ENTER
to initiate the restore operation.
The system outputs the following message:
"Deleting files on flash"
The system transfers the HMI device image and outputs the following message:
Restore CE-Image
Select ESC
to cancel the restore operation.
The system outputs the following message when the transfer of the HMI device image
from MMC to the HMI device is completed:
Restore of CE image finished.
Device will be rebooted now.
Don't remove the storage card.
Press ENTER to continue.
5. Press ENTER
7. Press ENTER
Result
The transfer is completed when all backup data were copied from the MMC and are
available on the HMI device.
See also
Setting the operating mode (Page 7-3)
Backup and restore functions for OP 77B (Page 6-21)
7.4.1 Overview
Overview
A compatibility conflict may occur when transferring a project to the HMI device. This is
caused by different versions of the engineering software and the HMI device image. The
configuration computer cancels the transfer and triggers an alarm to indicate a compatibility
conflict. You must update the operating system of the HMI device.
Notice
Data loss
An operating system update deletes all data such as projects and passwords from the HMI
device.
Bootstrapping
In ProSave or WinCC flexible, you can update the operating system with or without
bootstrapping, depending on the HMI device used.
• Updating the operating system without bootstrapping
First, set "Transfer" mode on the HMI device or use the automatic transfer function if the
project is active. Then start the operating system update in ProSave or WinCC flexible.
• Updating the operating system with bootstrapping
First, start the operating system update in ProSave or WinCC flexible. Then switch the
power on the HMI device off and on again.
Note
You can also perform an operating system update with bootstrapping if the HMI device
does not yet have an operating system or if the operating system of the HMI device is
corrupt.
In ProSave or WinCC flexible, set the "Bootstrap" check box status according to your
selected operating system update mode.
Requirements
• The HMI device is connected to a configuration computer.
• No project is open in WinCC flexible.
• Relevant only to operating system update without bootstrapping:
The data channel is configured on the HMI device.
Procedure
Proceed as follows:
1. Relevant to operating system update with bootstrapping:
Switch off power to the HMI device.
2. Select the menu command "Project ▶ Transfer ▶ Communication Settings" in WinCC
flexible on the configuration computer.
This opens the "Communication Settings" dialog.
3. Select the HMI device type.
4. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
5. Close the dialog with "OK".
6. In WinCC flexible, select the menu command "Project ▶ Transfer ▶ Update operating
system".
7. Select whether to update the operating system with/without bootstrapping by setting the
"Bootstrap" check box accordingly.
8. In "Image path," select the folder which contains the HMI device image file, *.img.
The HMI device image files are available under "WinCC flexible Images" in the WinCC
flexible installation folder and on the corresponding WinCC flexible installation CD.
9. Select "Open".
In the output area, you are provided information on the version of the HMI device image
file after it is opened.
10. Only relevant for restore operations without bootstrapping:
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
11. In WinCC flexible, select "Update OS" to run the operating system update.
Follow the instructions in WinCC flexible.
A status view opens to indicate progress.
Result
The system outputs and alarm when the operating system update is completed.
This operation has deleted the project data from the HMI device.
Requirements
• The HMI device is connected to a PC on which ProSave is installed.
• Relevant only to operating system update without bootstrapping:
The data channel is configured on the HMI device.
Procedure
Proceed as follows:
1. Relevant only to operating system update without bootstrapping:
Switch off power to the HMI device.
2. From the Windows Start menu, run ProSave on the PC.
3. Select the HMI device type from the "General" tab.
4. Select the type of connection between the HMI device and the configuration computer,
then set the communication parameters.
5. Select the "OS Update" tab.
6. Select whether to update the operating system with/without bootstrapping by setting the
"Bootstrap" check box accordingly.
7. In "Image path," select the folder which contains the HMI device image file, *.img.
The HMI device image file is available on the corresponding WinCC flexible installation
CD.
8. Select "Open".
In the output area, you are provided information on the version of the HMI device image
file after it is opened.
9. Only relevant for restore operations without bootstrapping:
Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the device automatically sets
"Transfer" mode when a restore operation is initiated.
10. On the PC, select "Update OS" to run the operating system update.
Follow the instructions in ProSave.
A status view opens to indicate progress.
Result
The system outputs and alarm when the operating system update is completed.
This operation has deleted the project data from the HMI device.
8.1.1 Overview
Caution
Unintentional actions
In "Online" mode, simultaneous operation of more than two keys may cause unintentional
actions in the plant.
Never press more than two keys simultaneously.
System keys
The system keys (control keys) are used for operator input on the HMI device.
Function Action
Moving the cursor Activates the next field in horizontal direction
DEL INS
,
TAB +/–
Activates the next field in vertical direction
,
Activate field Activates the next field in the tab order defined in your project
TAB
+
SHIFT
SHIFT
Enables an overlay function of a further system key
.
ENTER
TAB +/–
ENTER
• Call editing mode – initiates input with and
• Exit editor mode and confirm input
Navigating in lists
Introduction
The HMI device supports multilingual projects. You need to configure a corresponding
operator control object which lets you change the language setting on the HMI device during
runtime.
The project always starts with the language set in the previous session.
Requirements
• The relevant project language must be available on the HMI device.
• The language changeover function must be logically linked to a configured operator
control object such as a button.
Selecting a language
You can change project languages at any time. Language-specific objects are immediately
output to the screen in the relevant language when you switch languages.
The following options are available for switching the language:
1. A configured operator control object switches from one project language to the next in a
list.
2. A configured operator control directly sets the desired project language.
Further information on this may be available in your plant documentation.
8.1.3.1 Overview
Procedure
Values are entered in the project input fields. The values are transferred from the input fields
to the PLC.
Proceed as follows:
1. Select the required input field on the screen.
Based on your configuration, you can enter the following type of values in the input field:
– Numerical
– Alphanumerical
– Symbolic
– Date/time
2. Set the value.
HELP
Numerical values
Enter the characters of numerical values using the system keyboard. Press ENTER
to edit any
character of the value with the help of the cursor keys.
DEL
Alphanumerical values
Enter the alphanumerical values, numbers and letters character by character using the
Symbolic values
Symbolic values are by selecting configured entries and not using the keyboard. These
entries are stored in symbolic IO fields.
Requirements
TAB
Navigating in fields
Button Action
DEL INS
Selects the previous or next character
or
Button Action
+/–
Changes the sign of a numerical value
+
SHIFT
+/–
TAB +/–
All characters available in the extended character set are called in
or succession.
ENTER
Validates the input
HELP
ESC
Deletes the input
Restores the original value
Options of entering numerical and alphanumerical characters:
• Overwrite the existing value
• Edit a character in an existing value
1. Press SHIFT
+ .
TAB +/–
3. Press ENTER
.
1. Press ENTER
INS DEL
4. Press ENTER
.
pressing ENTER
or . The same applies when you add characters.
The following applies for further entries:
TAB
Enable the input field to enter "–12.34". Press one of the or cursor keys until the
required character appears. Press the following keys:
ENTER
+00.0 0
DEL
5x + 00.00
+/–
- 00.00
INS
- 0 0.00
TAB
- 1 0.00
INS
-1 0 .00
TAB
-1 2 .00
INS
2x -12. 0 0
TAB
-12. 3 0
INS
-12.3 0
TAB
-12.3 4
ENTER -12.34
You can start your entries at any position of the input field. You can also change the sign at
+/–
Enable the input field to enter "OP 73". Press one of the or cursor keys until the
required character appears. Press the following keys:
ENTER A
TAB
O
INS
OA
TAB
OP
INS
SHIFT + OP
INS
OP A
+/–
OP 7
INS
OP 7A
+/–
OP 73
ENTER OP 73
3. Press SHIFT
+ .
The selected character will be deleted. The remaining characters to the right of the cursor
shift by one position to the left.
If the characters are right aligned:
The selected character will be deleted. The remaining characters to the left of the cursor
shift one position to the right.
3. Press SHIFT
+ to insert a space character.
The characters already entered move one position to the right from the cursor position.
If the characters are right aligned:
The characters already entered move one position to the left from the cursor position.
Requirements
TAB
Button Action
TAB +/–
Scrolls in a single-line list field until the required entry is found
,
ENTER
Validates the selected entry
Disables editing mode
HELP
ESC
Restores the original entry
Disables editing mode
Procedure
Proceed as follows:
Requirements
TAB
Note
When entering the date and time, please note that the format is determined by the
configured project language.
See also
Entering and editing numerical and alphanumerical values (Page 8-5)
Setting the project language (Page 8-3)
Introduction
The configuration engineer uses infotext to provide additional information and operating
instructions with respect to screens and operable screen objects.
An infotext may contain information on the value to be set in an IO field, for example.
Enter temperature
setpoint for Tank_1
(Range 40 to 80 °C)
Procedure
HELP
• If the cursor is positioned in a field for which infotext has been configured, press SHIFT
+
HELP
ESC
to view the infotext.
HELP
• If SHIFT
+ ESC
is pressed and no infotext is available for the field, the infotext configured
for the active screen is shown instead.
If an infotext is not available for this active screen, the system opens the following dialog:
No info text available!
pressing ENTER
.
8.1.4.1 Overview
Overview
Operation of a project can be protected by the configuration engineer by implementing a
security system.
The security system of the HMI device is based on authorizations, user groups and users.
If operator control objects protected by a password are operated, the HMI device requests
the entry of a password. A logon screen is displayed in which you enter your user name and
password. After logging on, you can use the operator control objects for which you have the
required authorizations.
The Logon dialog can be set up by the configuration engineer via an individual operator
control object.
In the same way, the configuration engineer can set up an operator control object to log off.
After logging off, objects assigned password protection can no longer be operated; to do so,
log on again.
Further information on this may be available in your plant documentation.
Users
Each user is assigned to exactly one user group.
Users can be created as follows:
• By the configuration engineer during configuration
• By the administrator on the HMI device
• By a user with user administration authorization on the HMI device
Logoff times
A logoff time is specified in the system for each user. If the time between any two user
actions, e.g, entering a value or changing screens, exceeds this logoff time, the user is
automatically logged off. The user must then log on again to continue to operate objects
assigned password protection.
Passwords
Users can only log on to the HMI device if they are in the list of users and have entered their
user name and password. The passwords can be assigned by the configuration engineer, by
the administrator (or by a user who has administration authorization) or by the user himself.
The authorizations of a user after logging on depends on the user group to which the user is
assigned.
Further information on this may be available in your plant documentation.
The user data is encrypted and saved on the HMI device to protect it from loss due to power
failure.
Note
Depending on the transfer settings, changes to the user data are overwritten when the
project is transferred again.
User view
Use the User view to display the users on the HMI device.
8VHUYLHZ
$GPLQ *URXS
3/&XVHU *URXS
8VHU *URXS
1HZXVHU!
All users on the HMI device system are displayed in the User view to the administrator or to
a user with administrator authorizations. When user administration authorization is lacking,
only the personal user entry is displayed.
The group to which each user is assigned is displayed next to the user names.
As administrator or user with user administration authorization, you can also add new users.
Use the "<New User>" entry.
Notice
During a restore, the currently valid user data is overwritten. The restored user data and
passwords are valid immediately.
Number of characters
Length of user name, maximum 40
Length of password, minimum 3
Length of password, maximum 24
Entry in user view, maximum 50
Requirements
Use the logon dialog to log onto the security system of the HMI device. Enter user name and
password in the logon dialog.
User:
Password:
OK Cancel
You have the following options for displaying the logon dialog:
• Touch the operator control object with password protection.
• Touch an operator control object that was configured for displaying the logon dialog.
• Press ENTER
when the user view is active.
• At the beginning of the project, the logon dialog will be automatically displayed in certain
circumstances.
Further information on this may be available in your plant documentation.
Procedure
Proceed as follows:
1. Enter the user name and password.
TAB
3. Press ENTER
.
Result
After successful logon to the security system, you can execute password-protected functions
on the HMI device for which you have authorizations.
An error message is displayed if you enter the wrong password. In this case, no user is
logged onto the project.
Requirements
You have logged onto the security system of the HMI device.
Procedure
You have the following options for logging off:
• If the logoff time has been exceeded without user activity, the user is automatically
logged off.
• Touch the operator control object that was configured for logoff.
Further information on this may be available in your plant documentation.
Result
The user is no longer logged into the project. In order to operate an operator control object
with password protection, you must first log on again.
Requirements
New users are created in the user view.
To display the user view, switch to the screen that contains the user view.
To add a new user, you must have user administration authorization.
Procedure
Proceed as follows:
+/– TAB
2. Press ENTER
.
The following dialog appears:
8VHU _
2. &DQFHO
5. Press ENTER
.
The following dialog appears:
3DVVZRUG _
2. &DQFHO
8. Press ENTER
.
The following dialog appears:
*URXS *URXS
2. &DQFHO
9. From the list of available groups, select the one granted the corresponding user access
rights and assign the user to this group.
10. Select "OK".
/RJRIIWLPH
2. &DQFHO
Result
The new user is created.
Requirements
Change user data in the user view.
To display the user view, switch to the screen that contains the user view.
The following options are available for the range of changes that can be made:
• The administrator or a user with user administration authorization can change the data for
all users on the HMI device system in the user view.
– User name
– Group assignment
– Password
– Logoff time
• Users without user administration authorization can only change their own user data.
– Password
– Logoff time
Note
You can only change the logoff time and password for the "Admin" user.
You can only change the logoff time for the "PLC_User". This user entry is used for
logging on via the PLC.
Procedure
This procedure describes changing user data by the administrator or a user with user
administration authorization.
Proceed as follows:
1. From the user view, select the profile using the cursor keys.
2. Press ENTER
.
The following dialog appears:
8VHU 8VHU
2. &DQFHO
5. Press ENTER
.
6. Enter the new password as required.
3DVVZRUG
2. &DQFHO
7. Select "OK".
8. Press ENTER
.
9. Select the new user group as required.
*URXS *URXS
2. &DQFHO
/RJRIIWLPH
2. &DQFHO
Result
The user data for the user is changed.
Requirements
You delete users in the user view: Select the screen which contains the user view.
To delete a user, you must have user administration authorization.
There are two methods of deleting a user:
• Directly in the user view
• Using the user dialog
Note
The "Admin" and "PLC_User" users exist by default and cannot be deleted.
2. Press SHIFT
+ .
Result
The user is deleted.
2. Press ENTER
.
This opens the user dialog.
8VHU 8VHU
2. &DQFHO
4. Press SHIFT
+ .
Delete all characters from the input field.
5. Select "OK".
6. Press ENTER
.
Result
The user is deleted.
Procedure
Proceed as follows:
1. Use the corresponding operator control object to close the project..
Wait for the Loader to open after you closed the project.
2. Switch off power to the HMI device.
8.2.1 Overview
ON START +
OFF STOP –
Caution
Unintentional actions
In "Online" mode, simultaneous operation of more than two keys may cause unintentional
actions in the plant.
Never press more than two keys simultaneously.
System keys
System keys are used to input commands on the HMI device and can be organized as
follows:
• Numerical keypad
• Control keys
,
Activates the next field in vertical direction
,
Select field Activates the next field in the tab order defined in your project
TAB
SHIFT
Enables the overlay function of a further key
Viewing infotext Opens a window containing infotext on the selected object Requirement:
HELP
HELP An infotext exists for the selected object only if the LED is lit.
ESC
You can undo your input as long you have not yet confirmed it with
.
ENTER
ENTER
• Confirms your entries and closes the dialog.
Navigating in lists
Introduction
The HMI device supports multilingual projects. You need to configure a corresponding
operator control object which lets you change the language setting on the HMI device during
runtime. The project always starts with the language set in the previous session.
Requirements
• The relevant project language must be available on the HMI device.
• The language changeover function must be logically linked to a configured operator
control object such as a button.
Selecting a language
You can change project languages at any time. Language-specific objects are immediately
output to the screen in the relevant language when you switch languages.
The following options are available for switching the language:
1. A configured operator control object switches from one project language to the next in a
list.
2. A configured operator control directly sets the desired project language.
Further information on this may be available in your plant documentation.
8.2.3.1 Overview
Procedure
Values are entered in the project input fields. The values are transferred from the input fields
to the PLC.
Proceed as follows:
1. Select the required input field on the screen.
Based on your configuration, you can enter the following type of values in the input field:
– Numerical
– Alphanumerical
– Symbolic
– Date/time
2. Set the value.
Numerical values
Enter the characters of numerical values using the system keyboard. Press ENTER
to edit any
character of the value with the help of the cursor keys.
INS
All values in this input field are deleted by pressing DEL
.
The new value is rejected. The original value is not restored unless you press ESC
.
• OP 77B
The new value is rejected. Restores the original value in the view.
Alphanumerical values
Enter the alphanumerical values, numbers and letters character by character using the
Symbolic values
Symbolic values are by selecting configured entries and not using the keyboard. These
entries are stored in symbolic IO fields.
Requirements
An IO field was selected with TAB
or the cursor keys.
Navigating in fields
ENTER
Validates the input
ESC
Deletes the input
Restores the original value
Options of entering numerical and alphanumerical characters:
• Overwrite the existing value
• Edit a character in an existing value
2. Press ENTER
.
1. Press ENTER
.
INS
2. Delete the field content with DEL .
4. Press ENTER
.
1. Press ENTER
.
4. Press ENTER
.
1. Press ENTER
.
4. Press ENTER
.
pressing ENTER
or . The same applies when you add characters.
The following applies for further entries:
If a value has already been entered, select the next value with or .
corresponding cursor key or until the required character appears. Press the
following keys:
ENTER A
O 1
OA
OP 1
INS
SHIFT + DEL OP
OP A
E
7 OP 7 2
OP 7A
E
7 OP 77 2
OP 77A
B
SHIFT + 2 OP 77B 2
ENTER OP 77B
Figure 8-6 Example of input using the cursor keys and the numeric keypad
Requirements
An IO field was selected with TAB
or using the cursor keys.
ENTER
Validates the selected entry
Disables editing mode
ESC
Restores the original entry
Disables editing mode
Procedure
Proceed as follows:
Requirements
A date and time field was selected with TAB
or the cursor keys.
Note
When entering the date and time, please note that the format is determined by the
configured project language.
See also
Entering and editing numerical and alphanumerical values (Page 8-24)
Setting the project language (Page 8-21)
Introduction
The configuration engineer uses infotext to provide additional information and operating
instructions with respect to screens and operable screen objects.
An infotext may contain information on the value to be set in an IO field, for example.
(QWHUWHPSHUDWXUH
VHWSRLQWIRU7DQN
5DQJHWRr&
Procedure
HELP
The availability of an infotext is indicated by the lit LED. Press HELP
to view the infotext
on the HMI device. Two cases are possible:
• If the cursor is positioned in a field for which infotext has been configured, press HELP
to
view the infotext.
• When you press HELP
and no infotext is available for the box, the system outputs the
infotext for the active screen.
If an infotext is not available for this active screen, the system opens the following dialog:
1R+HOSDYDLODEOH
8.2.4.1 Overview
Overview
Operation of a project can be protected by the configuration engineer by implementing a
security system.
The security system of the HMI device is based on authorizations, user groups and users.
If operator control objects protected by a password are operated, the HMI device requests
the entry of a password. A logon screen is displayed in which you enter your user name and
password. After logging in, you can operate the operator control objects for which you have
the necessary authorizations.
The Logon dialog can be set up by the configuration engineer via an individual operator
control object.
In the same way, the configuration engineer can set up an operator control object to log off.
After logging off, objects assigned password protection can no longer be operated; to do so,
log on again.
Further information on this may be available in your plant documentation.
Users
Each user is assigned to exactly one user group.
Users can be created as follows:
• By the configuration engineer during configuration
• By the administrator on the HMI device
• By a user with user administration authorization on the HMI device
Logoff times
A logoff time is specified in the system for each user. If the time between any two user
actions, e.g, entering a value or changing screens, exceeds this logoff time, the user is
automatically logged off. The user must then log on again to continue to operate objects
assigned password protection.
Passwords
Users can only log on to the HMI device if they are in the list of users and enters their user
name and password. The passwords can be assigned by the configuration engineer, by the
administrator (or by a user who has administration authorization) or by the user himself.
The authorizations of a user after logging on depends on the user group to the user is
assigned.
Further information on this may be available in your plant documentation.
The user data is encrypted and saved on the HMI device to protect it from loss due to power
failure.
Note
Depending on the transfer settings, changes to the user data is overwritten when the project
is transferred again.
User view
Use the User view to display the users on the HMI device.
8VHUYLHZ
$GPLQ *URXS
3/&XVHU *URXS
8VHU *URXS
1HZXVHU!
All users on the HMI device system are displayed in the User view to the administrator or to
a user with administrator authorizations. When user administration authorization is lacking,
only the personal user entry is displayed.
The group to which each user is assigned is displayed next to the user names.
As administrator or user with user administration authorization, you can also add new users.
To do so, select "<new user>".
Notice
During a restore, the currently valid user data is overwritten. The restored user data and
passwords are valid immediately.
Number of characters
Length of user name, maximum 40
Length of password, minimum 3
Length of password, maximum 24
Entry in user view, maximum 50
Requirements
Use the logon dialog to log onto the security system of the HMI device. Enter user name and
password in the logon dialog.
User:
Password:
OK Cancel
You have the following options for displaying the logon dialog:
• Touch a protected operator control object.
• Touch an operator control object which is assigned a function for opening the Logon
dialog.
• Press ENTER
when the user view is active.
• At the beginning of the project, the logon dialog will be automatically displayed in certain
circumstances.
For further information, refer to your system documentation.
Procedure
Proceed as follows:
1. Enter the user name and password.
3. Press ENTER
.
Result
After successful logon to the security system, you can execute password-protected functions
on the HMI device for which you have authorizations.
An error message is displayed if you enter the wrong password. In this case, no user is
logged onto the project.
Requirements
You have logged onto the security system of the HMI device.
Procedure
You have the following options for logging off:
• If the logoff time has been exceeded without user activity, the user is automatically
logged off.
• Touch the operator control object that was configured for logoff.
Further information on this may be available in your plant documentation.
Result
The user is no longer logged into the project. In order to operate an operator control object
with password protection, you must first log on again.
Requirements
New users are created in the user view.
To display the user view, switch to the screen that contains the user view.
To add a new user, you must have user administration authorization.
Procedure
Proceed as follows:
2. Press ENTER
.
The following dialog appears:
User: |
Password:
OK Cancel
3. Press ENTER
.
4. Enter the user name.
5. Select TAB
to move to the next input field.
6. Enter the password.
7. Select "OK".
8. Press ENTER
.
The following dialog appears:
*URXSV 2SHUDWRUV
/RJRIIWLPH
2. &DQFHO
9. From the list of available groups, select the one granted the corresponding user access
rights and assign the user to this group.
Result
The new user is created.
Requirements
Change user data in the user view.
To display the user view, switch to the screen that contains the user view.
The following options are available for the range of changes that can be made:
• The administrator or a user with user administration authorization can change the data for
all users on the HMI device system in the user view.
– User name
– Group assignment
– Password
– Logoff time
• Users without user administration authorization can only change their own user data.
– Password
– Logoff time
Note
You can only change the logoff time and password for the "Admin" user.
You can only change the logoff time for the "PLC_User". This user entry is used for
logging on via the PLC.
Procedure
This procedure describes changing user data by the administrator or a user with user
administration authorization.
Proceed as follows:
2. Press ENTER
.
The following dialog appears:
User: User 1
Password: ******
OK Cancel
4. Select TAB
to move to the next input field.
5. Edit the password as required.
6. Select "OK".
7. Press ENTER
.
The following dialog appears:
*URXSV 2SHUDWRUV
/RJRIIWLPH
2. &DQFHO
9. Select TAB
to move to the next input field.
10. Edit the logon timeout as required.
11. Select "OK".
Result
The user data for the user is changed.
Requirements
You delete users in the user view: Select the screen which contains the user view.
To delete a user, you must have user administration authorization.
There are two methods of deleting a user:
• Directly in the user view
• By means of the user dialog
Note
The "Admin" and "PLC_User" users exist by default and cannot be deleted.
1. In the user view, select or to select the user you want to delete.
INS
2. Press DEL .
Result
The user is deleted.
1. In the user view, select or to select the user you want to delete.
2. Press ENTER
.
This opens the user dialog.
User: User 1
Password: ******
OK Cancel
4. Press ENTER
.
INS
5. Press DEL .
Delete all characters from the input field.
7. Press ENTER
.
Result
The user is deleted.
Procedure
Proceed as follows:
1. Use the corresponding operator control object to close the project.
Wait for the Loader to open after you closed the project.
2. Switch off power to the HMI device.
Terms
Recipe
A recipe consists of several tags which define the data structure of a data record.
Data record
A data record contains the recipe values.
Recipe element
A recipe element consists of an element name and a value. The names assigned to the tags
are referred to as element names.
Recipe view
The recipe view is a configurable object in which recipes, data records and recipe elements
are represented in lists. These are described below.
In the system configuration you have to distinguish between the recipe view and simple
recipe view. OP 77B displays the simple recipe view.
Recipe list
This list shows the configured recipes. A recipe list may appear as illustrated below:
1 Grapefruit
2 Lemon
3 Orange
4 Apple
Button Action
INS Creates a new data record
+
SHIFT
DEL
ENTER
Opens the data record list of the selected recipe
HELP
Opens a window containing infotext on the selected object
Further keys for navigation are described in the section "Navigation in lists". The keys
described in that section are also used in the data record / element lists.
Button Action
INS Creates a new data record
SHIFT
+
DEL
ENTER
Opens the entry list of the selected data record
ESC
Displays the recipe list again
Procedure
Proceed as follows:
1. Select the first data record.
2. Press .
The corresponding recipe name is displayed, as seen in the figure below.
2 Lemon 1
1 Juice 2
2 Beverage
3 Nectar
① Data record
② Menu
③ Element name
You can configure the sorting order of the element name and value columns.
Button Action
ESC
Displays the data record list again
HELP
Opens a window containing infotext on the selected object
2. Press .
The corresponding recipe name is displayed as seen in the figure below.
2 Lemon 3 Nectar 1
l Orange 90 2
l Water 10
kg sugar 1,5
Menu
A menu provides quick access to operating functions in recipes, data records and entry lists.
Figure 9-3 Example of a menu with menu commands configured for entry lists
Each of these menu commands can be selected by entering the assigned number or by
Table 9-5 Overview of keys for use in a menu for a recipe view
Button Action
A Triggers the corresponding menu command
1 9
up to
ENTER
Triggers the menu command selected with the cursor
ESC
Shows the previously selected list
Example
Using the "Save" command - see the figure "Example of a menu with commands configured
for entry lists". The first line contains "2 Save".
Proceed as follows:
Input using the cursor keys
1. Use the cursor keys to select "Save".
2. Press ENTER
.
This saves the data record and opens the entry list again.
With numerical input
1. Enter "2".
This saves the data record and opens the entry list again.
Introduction
Based on your configuration, you can either export recipe data records to a CSV file for
editing in MS Excel, for example, or import these from a CSV file. The extent to which you
can influence these processes is determined by the project configuration. Various input fields
may be configured on the user interface:
• Input of the path to the CSV file
• Selection of the recipe data records for export
• Overwriting an existing CSV file
Requirements
Export functions are configured.
Procedure
1. Customize the export settings on the user interface of the HMI device.
2. Press the button or the key on the HMI device configured with the "Export recipe records"
function.
Result
The recipe data record are exported to a CSV file.
Note
New data records created in runtime can be exported to an external file.
Requirements
Import functions are configured.
Procedure
1. Customize the import settings on the user interface of the HMI device.
2. Use the button or the key on the HMI device which is assigned the "Import recipe
records" function.
Result
The recipe data record are imported. If the structure of the CSV file is different from the
recipe structure, deviations are treated as follows:
• Any additional values in the CSV file will be rejected.
• If the CSV file contains values of the wrong data type, the configured default value is set
in the recipe record.
Example:
The CSV file contains values that show the tank contents and were input as floating point
numbers. However, the corresponding recipe tag expects an integer value. In this case,
the system discards the imported value and uses the configured default.
• The system also applies the configured default value to the recipe data record if the CSV
file contains an insufficient number of values.
Alarms
Alarms indicate events and states on the HMI device which have occurred in the system, in
the process or on the HMI device itself. A status is reported when it is received.
An alarm could trigger one of the following alarm events:
• Activate
• Deactivate
• Acknowledge
The configuration engineer defines which alarms must be acknowledged by the user.
An alarm may contain the following information:
• Date
• Time
• Alarm text
• Location of fault
• Status
• Alarm class
• Alarm number
• Acknowledgement group
Alarm classes
Alarms are assigned to various alarm classes:
• Error
Alarms in this class must always be acknowledged. Alarms normally indicate critical
errors within the plant such as "Motor temperature too high".
• Warning
Warning alarms usually indicate states of a plant such as "Motor switched on".
• System
System alarms indicate states or events which occur on the HMI device.
• User-specific alarm classes
The properties of this alarm class are defined in the configuration.
• STEP 7 alarm classes (applies to OP 77B)
The alarm classes configured in STEP 7 are also available to the HMI device.
Further information on this may be available in your plant documentation.
Alarm buffer
Alarm events are saved to an internal, volatile buffer. The size of this alarm buffer depends
on the HMI device type.
34541
156 12:05:49 Alarm
45238
Engine 23 too hot
12584
The layout and operation of the alarm window correspond to that of the alarm view.
The alarm window is independent of the process screen. Depending on the configuration,
the alarm window appears automatically as soon as a new, unacknowledged alarm has been
received. The alarm window can be configured so that it only closes after all the alarms have
been acknowledged.
Further information on this may be available in your plant documentation.
Button Function
HELP Show an alarm infotext
SHIFT ESC
+
ENTER
Edit alarm
ACK
Acknowledge alarm
INS
Shows the full text of the selected alarm in a separate window, the alarm text
window You can scroll the alarm text window using the cursor keys.
TAB +/– Selects the next or previous alarm from the alarm view
,
Viewing infotext
An alarm can be assigned an infotext.
Proceed as follows to view the infotext:
1. Select the relevant alarm in the alarm view using the cursor keys.
HELP
2. Press SHIFT
and ESC
.
The infotext assigned to this alarm is shown.
HELP
3. Press ESC
to close the infotext.
2. Press .
This opens the alarm text window shown below.
502 15:05:49 Alarm
switch off unit 4,
disconnect main linkage,
close by-pass stop valve 2,
start cooling unit 23 and
open pipes 12 and 53,
acknowledge buttom ACK
+/– TAB
4. Press ESC
.
This closes the alarm text window.
Requirements
• The alarm which is to be acknowledged is shown in the alarm window or in the alarm
view.
• Either the alarm window or the alarm view is enabled.
• The alarm must be acknowledged.
Procedure
Proceed as follows to acknowledge an alarm:
1. From the alarm window or alarm view, select the relevant alarm using the cursor keys.
2. Press ACK
.
Result
The alarm or all alarms of the corresponding acknowledgement group are acknowledged.
Further information about acknowledgment groups may be available in your plant
documentation.
Introduction
The configuration engineer can assign additional functions to each alarm. These functions
are executed when the alarm is processed.
Requirements
• The alarm to be edited is indicated in the alarm window or in the alarm view.
• Either the alarm window or the alarm view is enabled.
Procedure
Proceed as follows to edit an alarm:
1. From the alarm view, select the alarm you want to edit using the cursor keys.
2. Press ENTER
.
Result
The system executes the additional functions of the alarm. Further information on this may
be available in your plant documentation.
Note
When you edit an unacknowledged alarm, it is acknowledged automatically.
12847
156 12:05:49 Alarm
52687
Engine 23 too hot
24558
68124
The layout and operation of the alarm window correspond to that of the alarm view.
The alarm window is independent of the process screen. Depending on the configuration,
the alarm window appears automatically as soon as a new, unacknowledged alarm has been
received. The alarm window can be configured so that it only closes after all the alarms have
been acknowledged.
For further information, refer to your plant documentation.
Button Function
HELP
Displays an alarm infotext
ENTER
Edits an alarm
ACK
Acknowledges an alarm
Displays the full text of the selected alarm in a separate window, the alarm text
window You can scroll in the alarm text window.
Selects the next or previous alarm from the alarm view
,
Viewing infotext
An alarm can be assigned an infotext.
To view the infotext:
1. Select the relevant alarm in the alarm view using the cursor keys.
2. Press HELP
.
The infotext assigned to this alarm is shown.
3. Press ESC
to close the infotext.
2. Press .
This opens the alarm text window shown below.
502 15:05:49 Alarm
switch off unit 4,
disconnect main linkage,
close by-pass stop valve 2,
start cooling unit 23 and
open pipes 12 and 53,
acknowledge buttom ACK
4. Press ESC
.
This closes the alarm text window.
Requirements
• The alarm which is to be acknowledged is shown in the alarm window or in the alarm
view.
• Either the alarm window or the alarm view is enabled.
• The alarm must be acknowledged.
Procedure
Proceed as follows to acknowledge an alarm:
1. From the alarm window or alarm view, select the relevant alarm using the cursor keys.
2. Press ACK
.
Result
The alarm or all alarms of the corresponding acknowledgement group are acknowledged.
Further information about acknowledgment groups may be available in your plant
documentation.
Introduction
The configuration engineer can assign additional functions to each alarm. These functions
are executed when the alarm is processed.
Requirements
• The alarm to be edited is indicated in the alarm window or in the alarm view.
• Either the alarm window or the alarm view is enabled.
Procedure
Proceed as follows to edit an alarm:
1. From the alarm view, select the alarm you want to edit using the cursor keys.
2. Press ENTER
.
Result
The system executes the additional functions of the alarm. Further information on this may
be available in your plant documentation.
Note
When you edit an unacknowledged alarm, it is acknowledged automatically.
Scope of maintenance
The HMI device is designed for maintenance-free operation. However, you should clean the
keyboard membrane and the display unit at regular intervals.
Preparation
Caution
Faulty operation
Always switch off the HMI device before cleaning it. This will ensure that you do not trigger
unintended functions when you touch the keys.
Use a cloth dampened with a cleaning agent to clean the equipment. Only use water with a
little liquid soap or a screen cleaning foam.
Procedure
Never spray the cleaning agent directly onto the HMI device. Apply it to a cloth. Never use
aggressive solvents or scouring powder.
Caution
Do not clean the HMI device with compressed air or steam jet blowers.
Repairs
A defective device must be returned to the manufacturer's site for repair. The HMI device
may only be repaired at the manufacturer's site.
Service pack
A service pack can be ordered for servicing purposes. It contains the following spare parts:
• Mounting seal
• Labeling strips
• Mounting clamps
• Terminal block
The service pack can be ordered from your Siemens representative.
83
67
137
6.2
186
170
134
6.2
12.2.1 Specifications, OP 73
Housing
Display
Input unit
Memory
Power supply
See also
Standards, certificates and approvals (Page 2-2)
Electromagnetic compatibility (Page 2-7)
Transport and storage conditions (Page 2-9)
Mounting information (Page 3-1)
Mounting positions and fixation (Page 3-3)
Information on insulation tests, protection class and degree of protection (Page 3-7)
Housing
Display
Input unit
Memory
Power supply
See also
Standards, certificates and approvals (Page 2-2)
Electromagnetic compatibility (Page 2-7)
Transport and storage conditions (Page 2-9)
Mounting information (Page 3-1)
Mounting positions and fixation (Page 3-3)
Information on insulation tests, protection class and degree of protection (Page 3-7)
Housing
Display
Input unit
Memory
Working memory 1 MB
Memory card MMC, optional
Power supply
See also
Standards, certificates and approvals (Page 2-2)
Electromagnetic compatibility (Page 2-7)
Transport and storage conditions (Page 2-9)
Mounting information (Page 3-1)
Mounting positions and fixation (Page 3-3)
Information on insulation tests, protection class and degree of protection (Page 3-7)
PIN Assignment
1 +24 V DC
2 GND 24 V
9 6
PIN Assignment
1 n. c.
2 GND 24 V
3 Data channel B (+)
4 RTS
5 GND 5 V, floating potential
6 +5 V DC, floating potential
7 +24 V DC, out (max. 100 mA) or +24 V DC in1
8 Data channel A (–)
9 n. c.
Caution
Power supply
When the HMI device is supplied with power from the CPU, do not connect an external
power supply to it.
9 6
PIN Assignment
1 n. c.
2 GND 24 V
3 Data channel B (+)
4 RTS 1
5 GND 5 V, floating potential
6 +5 V DC, floating potential
7 +24 V DC, out (max. 100 mA)
8 Data channel A (–)
9 RTS 1
9 6
9 6
PIN Assignment
1 DCD
2 RxD
3 TxD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 n. c.
1
2
3
4
5
6
7
8
9
PIN Assignment
1 +5 V DC, out (max. 100 mA)
2 USB-DN
3 USB-DP
4 GND 5 V
Abbreviation
The following abbreviations are commonly used for electrostatic sensitive devices:
• ESD – Electrostatic Sensitive Devices
• ESD – Electrostatic Sensitive Device as common international designation
Labels
ESD modules are labeled with the following symbol:
Electrostatic charge
Caution
Electrostatic charge
ESDs may be destroyed by voltages well below the perception threshold of persons
Voltages of this kind develop when a component or an assembly is touched by a person who
is not grounded against static electricity. Usually, it is unlikely that damage to an ESD as a
result of overvoltage is detected immediately but may become apparent only after a longer
period of operation.
Prevent electrostatic charge of your body before you touch the ESD!
Anyone who is not connected to the electrical potential of their surroundings is subjected to
electrostatic charge.
The figure indicates the maximum electrostatic charge anyone is subjected to when
contacting the materials shown. These values correspond with specifications to IEC 801-2.
[V]
Voltage
100 [%]
Relative atmospheric humidity
Figure A-2 Electrostatic voltages with which a person can be charged.
① Synthetic materials
② Wool
③ Antistatic materials such as wood or concrete
Caution
Grounding measures
When working with electrostatic sensitive devices, make sure that the person, the workplace
and the packaging are properly grounded. This helps to avoid electrostatic charge.
As a rule, only touch the ESD if this is unavoidable. Example: for maintenance. When you
touch modules, make sure that you do not touch the pins on the modules or the PCB tracks.
This prevents any discharge of static electricity to sensitive component and thus avoids
damage.
Discharge electrostatic electricity from your body if you are performing measurements on an
ESD. To do so, touch a grounded metallic object.
Always use grounded measuring instruments.
Introduction
System alarms on the HMI device provide information about internal states of the HMI device
and PLC.
The overview below shows the causes of system alarms and how to eliminate the cause of
error.
Depending on functionality, only parts of the system alarms described in this section apply to
the various HMI devices.
Note
System alarms are only indicated if an alarm window was configured. System alarms are
output in the language currently set on your HMI device.
AG
PLC of the SIMATIC S5 series such as the AG S5-115U, for example
Alarm logging
Output of user-specific alarms to a printer, in parallel to their output to the HMI device
screen.
Alarm, acknowledging
Acknowledgement of an alarm confirms that it has been noted.
Alarm, activated
Moment at which an alarm is triggered by the PLC or HMI device.
Alarm, deactivated
Moment at which the initiation of an alarm is reset by the PLC.
Alarm, user-specific
A user-specific alarm can be assigned to one of the following alarm classes:
• Error
• Warning
• User-specific alarm classes
A user-specific alarm designates a certain operating status of the plant connected to the HMI
device via the PLC.
AS
PLC of the SIMATIC S7 series such as a SIMATIC S7-300
AS 511
Protocol of the programming device interface of a SIMATIC S5 PLC
Bootloader
Used to start the operating system. Automatically started when the HMI device is switched
on. A start screen appears during startup. After the operating system has been loaded, the
Loader opens.
Bootstrapping
Function called when updating the operating system. When a functional operating system is
available, updates can be performed without bootstrapping. Otherwise, updating with
bootstrapping is necessary. In this case, the configuration computer communicates with the
HMI device by means of the HMI device bootloader.
Configuration computer
General term for programming devices (PGs) and PCs on which plant projects are created
using an engineering software.
Control request
Triggers a function via the PLC.
Controller
General term for devices and systems with which the HMI device communicates, e.g.
SIMATIC S7.
Display duration
Defines whether and how long a system alarm is displayed on the HMI device.
EMC
Electromagnetic compatibility is the ability of electrical equipment to function properly in its
electromagnetic environment without influencing this environment.
Engineering software
Software for the creation of projects for process visualization – see also project, process
visualization and runtime software
Event
Functions are triggered by defined incoming events. Events can be configured. Events which
can be assigned to a button include "Press" and "Release", for example.
Fault time
Refers to the time interval between an activated and deactivated alarm.
Field
Area reserved in configured screens for the input and output of values.
Flash memory
Non-volatile memory with EEPROM chips, used as mobile storage medium or as memory
module installed permanently on the motherboard.
Hardcopy
Output of the screen content to a printer.
Infotext
Configured information on objects within a project. An alarm infotext, for example, may
contain information on the cause of the fault and troubleshooting routines.
IO field
Enables the input or output of values on the HMI device which are transferred to the PLC.
Notation
System consisting of characters, symbols and rules. In particular used to define the write
format of a programming language in data processing.
Object
Component of a project. Example: screen or alarm. Objects are used to view or enter texts
and values on the HMI device.
Plant
General term referring to machines, processing centers, systems, plants and processes
which are operated and monitored on an HMI device.
Process visualization
Visualization of processes from the areas of production, logistics and services in text-based
and graphics format. Configured plant screens allow operator intervention in active plant
processes by means of the input and output data.
Project
Result of a configuration using an engineering software. The project normally contains
several screens with embedded system-specific objects, basic settings and alarms. The
project file of a project configured in WinCC flexible is saved under the file name extension
*.hmi.
You distinguish between the project on the configuration computer and that on an HMI
device. A project may be available in more languages on the configuration computer than
can be managed on the HMI device. The project on the configuration computer can also be
set up for different HMI devices. Only the project set up for a particular HMI device can be
transferred to that HMI device.
Project file
File which is generated based on a source file for a specific HMI device when the
configuration is completed. The project file is transferred to the corresponding HMI device
and is used to operate and monitor plants. Refer to Source file.
Recipe
Combination of tags forming a fixed data structure. The data structure configured can be
assigned data on the HMI device and is then referred to as a data record. The use of recipes
ensures that when a data record is downloaded, all the assigned data is transferred
synchronously to the PLC.
Runtime software
Process visualization software which can be used to debug a project on a configuration
computer. Also refer to "Project" and "Engineering software".
Screen
Form of the visualization of all logically related process data for a plant. The visualization of
the process data can be supported by graphic objects.
Screen object
Configured object for operating and monitoring the system, e.g. a rectangle, an IO field or a
recipe view.
Softkey
Key on the HMI device which supports user-specific functions. A function is assigned to the
key in the configuration. The assignment of the keys may be specific to an active screen or
not.
Source file
File from which various project files can be created, depending on the configuration. The
source file is not transferred and remains on the configuration computer.
The file name extension of a source file is *.hmi. Refer to Source file, compressed and
Project file.
STEP 7
Programming software SIMATIC S7, SIMATIC C7 and SIMATIC WinAC PLCs.
STEP 7 Micro/WIN
Programming software for PLCs of the SIMATIC S7-200 series.
Symbolic IO field
Box for the input/output of a parameter. Contains a list of default entries from which one can
be selected.
System alarms
Assigned to the "System" alarm class. A system alarm refers to internal states on the HMI
device and the PLC.
Tab order
In the configuration, this sets the sequence in which objects are focused on pressing the
<TAB> key.
Tag
Defined memory location to which values can be written to and read from. This can be done
from the PLC or the HMI device. Based on whether the tag is interconnected with the PLC or
not, we distinguish between "external" tags (process tags) and "internal" tags.
Transfer
The transfer of an executable project to the HMI device.
"Transfer" mode
HMI device operating mode, set to transfer an executable project from the configuration
computer to the HMI device.
Unintentional, 6-11, 6-26, 6-28 Changing the logoff time, 8-16, 8-34
Transfer settings, 6-8, 6-11, 6-22, 6-27 Changing the user name, 8-16, 8-34
Menu, 6-8 Changing user data, 8-16, 8-34
Transferring Creating, 8-14, 8-33, 8-35
Project, 7-2 Deleting, 8-18, 8-36
Transport conditions, 2-9 Limit values, 8-13, 8-31
Type of fixation, 3-4 Logging off, 8-14, 8-33
Logging on, 8-13, 8-32
U
V
Upkeep, 11-1
Upload, 7-9, 7-10 Value, 1-5
USB channel Version Info, 6-4, 6-16
Setting, 6-23 Version information
USB settings, 6-27 Calling, 6-4, 6-16
Use
Conditions, 3-1
In industry, 2-4 W
In residential areas, 2-4
Wiring diagram
In the potentially explosive atmosphere, 2-4
Connecting peripherals, 4-19
With additional measures, 3-1
Connecting the configuration computer, 4-6, 4-
User data
18
Backup and restoring, 8-12, 8-31
Connecting the equipotential bonding circuit, 4-
User group, 8-11, 8-30
5, 4-15
User view, 8-12, 8-31
Connecting the PLC, 4-6, 4-16
Limit values, 8-13, 8-31
Connecting the power supply, 4-7, 4-20
Users, 8-11, 8-30
Working on the cabinet, 2-1
Change password, 8-16, 8-34
Changing group assignments, 8-16, 8-34