Insp Checklist - Piping Alignment
Insp Checklist - Piping Alignment
SAIC NUMBER
DATE APPROVED
QR NUMBER
SAIC-G-2022
WBS / BI / JO NUMBER
25-May-05
MECH-
CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) LAYOUT DRAWING NUMBER SCHEDULED INSPECTION DATE & TIME SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO INSPECTION LEVEL
EQPT CODE
SYSTEM ID.
PLANT NO.
ACTUAL INSPECTION DATE & TIME SAUDI ARAMCO ACTIVITY NUMBER CONTRACTOR INSPECTION LEVEL
ITEM No. A. A1
ACCEPTANCE CRITERIA General Requirements Soft foot check is done with piping disconnected on each equipment foot. Note: Maximum permissible movement is 0.05 millimeter (2 mils) at each foot, or as specified by Manufacturer. Fixed and movable equipment shall be free to turn. Data of alignment are recorded in SATR-G-2004 or approved equivalent alignment form.
REFERENCE
PASS
FAIL
N/A
RE-INSP DATE
API 686, Chapter 7, Para. 5.4.4.1 API 686, Chapter 7, Para. 5.4.4.1 Contractor QP
A2
A3
A4
Provisions are made for doweling the pump and drive components to the 31-SAMMS-004, baseplate. Note: Dowels are furnished by the Vendor, but installed in the Para. 3.3.21 field at the time of final alignment. For all pumps, 3 mm (1/8 in) thick stainless steel shim packs shall be furnished. The maximum allowable number of shims under any equipment support foot is five. Alignment is within the Manufacturer's tolerances before pipes and conduit attached. Pipe strain checks have been made in accordance with the manufacturer's procedures. Alignment is within the Manufacturer's tolerances after pipes and conduit attached. 31-SAMMS-004, Para. 3.3.4 API 686, Chapter 7, Para. 5.4.2.1 API 686, Chapter 7, Para. 5.4.5 API 686, Chapter 7, Para. 5.4.5 API 686, Chapter 7, Para. 5.4.5
A5
A6
A7
A8
A9
REMARKS:
REFERENCE DOCUMENTS: 1. 31-SAMSS-004, Centrifugal Pumps, (30 September, 2003) 2. API 686, Recommended Practice for Machinery Installation and Installation Design, (First Edition, April 1996)
Contractor / Third-Party
Construction Representative*
Work is Complete and Ready for Inspection: Name, Initials and Date: Name, Initials and Date:
Saudi Aramco
PMT Representative
T&I Witnessed QC Record Reviewed Work Verified
QC Inspector
Performed Inspection Name, Initials and Date: Work / Rework May Proceed
PID Representative
T&I Witnessed Name, Initials and Date: QC Record Reviewed Work Verified
QC Supervisor
Quality Record Approved: Name, Sign and Date: *Person Responsible for Completion of Quality Work / Test
Y = YES
N = NO F = FAILED
Page 1 of 1