A REPORT ON

STRUCTURAL ANALYSIS & DESIGN


OF
RESIDENTIAL BUILDING
OF
MR. BIMAL LALCHAN
LOCATION: GHARAPJHONG RURAL MUNICIPALITY-2,
MUSTANG

i
Contents
List of Figures .............................................................................................. iii
List of Tables ................................................................................................ iv
1 Introduction .............................................................................................1
1.1 An Overview of Earthquake-Resistant Design .................................................... 1
1.2 Earthquake Resistant Design Philosophy............................................................. 2
2 Description of the Building ....................................................................4
2.1 Building Description ............................................................................................ 4
2.2 Location of Building ............................................................................................ 5
3 Numerical modeling................................................................................6
4 Structural analysis ..................................................................................9
4.1 Load cases considered ......................................................................................... 9
4.2 Load combination ................................................................................................. 9
4.3 Mass Source ......................................................................................................... 9
4.4 Dead loads ............................................................................................................ 9
4.5 Live load ............................................................................................................. 12
4.6 Seismic Analysis ................................................................................................ 13
4.6.1 Seismic coefficient method ......................................................................... 13
4.6.2 Dynamic analysis ........................................................................................ 14
4.6.3 Seismic Weight and Base Shear ................................................................. 14
4.6.4 Story Drift and displacement Calculations ................................................. 15
4.7 Modal analysis and modal mass participation.................................................... 18
4.8 Analysis of Internal Forces Developed in Frames ............................................. 18
4.9 Sample B/C ratio check ...................................................................................... 20
5 Design .....................................................................................................21
5.1 Column design summary.................................................................................... 22
5.2 Beam Design Summary...................................................................................... 26
5.3 Slab Design Summary ........................................................................................ 32
5.4 Staircase Design Summary................................................................................. 32
5.5 Foundation Design Summary ............................................................................. 32
6 CONCLUSION .....................................................................................34
7 RECOMMENDATIONS .....................................................................34
ANNEXES ....................................................................................................35
ANNEX -I: REFERENCES.......................................................................................... 35
ANNEX-II: SAMPLE DESIGN CALCULATIONS ................................................... 36
SAMPLE BEAM DESIGN BY ETABS (1-A/B, ground Floor) .............................. 36
SAMPLE COLUMN DESIGN (B5-First floor) ....................................................... 37
SAMPLE SLAB DESIGN ........................................................................................ 39
SAMPLE ISOLATED FOOTING DESIGN(D-2 grid) ............................................ 42
SAMPLE COMBINE FOOTING DESIGN(2-B/C grid) ......................................... 44
SAMPLE STAIRCASE DESIGN ............................................................................ 47

ii
List of Figures
Figure 2-1 : Ground floor Plan of Building ........................................................................ 4
Figure 2-2 : Seismic Hazard of Himalayas ......................................................................... 5
Figure 3-1 : 3D model created in ETABS .......................................................................... 6
Figure 3-2 : Ground /First/Second Floor plan modeled in ETABS .................................... 7
Figure 3-3 : Top floor plan modeled in ETABS ................................................................. 7
Figure 3-4 : Elevation on grid A-A/B-B ............................................................................. 8
Figure 3-5 : Elevation on grid C-C/D-D ............................................................................. 8
Figure 4-1 : Wall load ....................................................................................................... 10
Figure 4-2 : Floor finish load ............................................................................................ 11
Figure 4-3 : Staircase dead+ floor finish load................................................................... 11
Figure 4-4 : Live load ....................................................................................................... 12
Figure 4-5 : Staircase live load ......................................................................................... 12
Figure 4-6 : Terrace live load............................................................................................ 13
Figure 4-7 : Seismic forces at different levels .................................................................. 15
Figure 4-8 : Drift ratio in Eqx ........................................................................................... 16
Figure 4-9 : Drift ratio in Eqy ........................................................................................... 16
Figure 4-10 : Displacement in Eqx ................................................................................... 17
Figure 4-11 : Displacement in Eqy ................................................................................... 17
Figure 4-12 : Sample Bending Moment Diagram for frames along Grid C/C-1.5(DL+LL)
........................................................................................................................................... 19
Figure 4-13 : Sample Shear force Diagram for frames along Grid C/C -1.5(DL+LL) ..... 19
Figure 4-14 : Sample Axial force Diagram for frames along Grid C/C -1.5(DL+LL) ..... 20
Figure 4-15 : Sample B/C ratio check............................................................................... 20
Figure 5-1 : Rebar of column in Grid A ........................................................................... 22
Figure 5-2 : Rebar of column in Grid B ............................................................................ 22
Figure 5-3 : Rebar of column in Grid C ............................................................................ 23
Figure 5-4 :rebar of column in Grid D .............................................................................. 23
Figure 5-5 : Rebar in Ground floor beam ........................................................................ 26
Figure 5-6 : Rebar in first floor beam ............................................................................... 26
Figure 5-7 : Rebar in Second floor beam ......................................................................... 27
Figure 5-8 : Rebar in Second floor beam ......................................................................... 27
Figure 5-9 : Base reaction for footing design ................................................................... 32

iii
List of Tables
Table 2-1 : Building Description ........................................................................................ 4
Table 4-1 : Mass source ...................................................................................................... 9
Table 4-2 : Dead loads unit weight ..................................................................................... 9
Table 4-3 : Dead load applied ........................................................................................... 10
Table 4-4 : Live load applied ............................................................................................ 12
Table 4-5 : Analysis and design parameters ..................................................................... 14
Table 4-6 : Drift Calculations for Earthquake Loads........................................................ 15
Table 4-7 : Modal mass Participation ration from ETABS .............................................. 18
Table 5-1 : Column Design summary ............................................................................... 24
Table 5-2 : Beam Design Summary .................................................................................. 28
Table 5-3 : Footing Design Summary............................................................................... 33

iv
EXECUTIVE SUMMARY

This report focuses on structural design of residential building located at Mustang. It


summarizes design assumption, methodology and follows up of codes and standards for
the building with proper consideration of the earthquake resistant design criteria following
the Nepal National Building Code and Indian Standard Code 2016.

The primary objective of the project is to analyze and design the structural elements of the
buildings based on NBC and Indian standards. The seismic coefficient method is adopted
to analyze the earthquake response of the building.

Finite element analysis showed that the anticipated performance of the buildings subjected
to the design earthquake meets IS code seismic hazard level requirement for building. The
building response for drift, displacement is also calculated.

The following conclusions can be drawn from this report:

The structure is designed to complying the guidelines and the Indian standards.

Story drifts are within the acceptable limits under DBE level earthquakes.

** The structural design is carried on the architectural drawing provided. This report solely emphases and
confines itself to technical aspects of the structure and does not comment on other aspects of the structure.

v
vi
1 Introduction
1.1 An Overview of Earthquake-Resistant Design
Nepal lies in an earthquake prone zone. It is located in the boundary between Indian plate and
Tibetan plate. Thus, Nepal experiences earthquakes frequently. Earthquakes are the most
sudden, dramatic and devastating natural calamities. Although they last only for few seconds to
minutes, they are the most devastating ones. Past records of the earthquake show that eighteen
major earthquakes have hit Nepal till now. So, special consideration of earthquake forces while
designing a building is mandatory in Nepal.

Designing building against earthquake forces does not mean that we are making the building
earthquake-proof. Although earthquake proof structures may be viable in terms of engineering
but they are not financially viable. However, it is possible to design and build earthquake-
resilient (more precisely seismic resilient) structures. According to this philosophy, no matter
how much severe earthquake occurs, the building won’t collapse although it may be irreparably
damaged. In, this background, it is ensured that this building has been designed to withstand all
the acting loads including the earthquake forces making it seismic resistant.

The structural design alone is not enough to ensure the safety of a building, equally important,
is its construction. The role of a contractor is of paramount importance as he is the one to execute
the construction work at site. He is required to execute the work according to drawings supplied
by the consultant to him and detailing has to be carefully followed. A large percentage of failure
of the building is attributed to poor quality of construction. Past experiences from damages have
shown that quality of material and workmanship play an important role in good seismic
behavior of the buildings. Hence, quality assurance of construction works is the key to good
seismic performance of a building.

Severity of ground shaking at a given location during an earthquake can be minor, moderate
and strong. Relatively, minor shakings occur frequently, moderate shakings occasionally and
strong shakings rarely. For instance, on average annually about 800 earthquakes of magnitude
5.0-5.9 on Richter scale occur in the world while the number is only about 19 for magnitude of
range 7.0-7.9 on Richter scale. So, should we design and construct a building to resist that rare
1
earthquake shaking that may come only once in 500 years or even once in 2000 years at the
chosen project site, even though the life of the building itself may be only 50 or 100 years?
Since it costs money to provide additional earthquake safety in buildings, a conflict arises:
Should we do away with the design of buildings for earthquake effects? Or should we design
the buildings to be “earthquake proof” wherein there is no damage during the strong but rare
earthquake shaking? Clearly, the former approach can lead to a major disaster, and the second
approach is too expensive. Hence, the design philosophy should lie somewhere in between these
two extremes.

The engineers do not attempt to make earthquake proof buildings that will not get damaged
even during the rare but strong earthquakes; such buildings will be too robust and also too
expensive. Instead, the engineering intention is to make buildings earthquake resistant and
affordable; such buildings resist the effects of ground shaking, although they may get damaged
severely but would not collapse during the strong earthquake. Thus, safety of people and
contents is assured in earthquake-resistant buildings, and thereby a disaster is avoided. This is
a major objective of seismic design codes throughout the world.

1.2 Earthquake Resistant Design Philosophy


The earthquake design philosophy may be summarized as follows:

a) Under minor shakings which occur frequently, the main members of the buildings that carry
vertical and lateral forces should not be damaged; however non-structural parts may sustain
repairable damages. It is assured that the building will be fully operational within a short time
and the repair costs will be small

b) Under moderate shakings which are occasional, the structural elements may sustain
repairable damage, while the non-structural elements may be heavily damaged; the building
will be operational followed by repair and re-strengthening of the damaged structural elements
and replacing of damaged non-structural elements.

2
c) Under strong shakings which are rare, the main members may sustain severe damage, but the
building should not collapse; the building may become dysfunctional for further use, but will
stand so that people can be evacuated and property recovered.

The degree to which the building is to be assured against the possibility of damage must be
considered while designing the building. Important buildings like hospitals, health posts, fire
stations, post offices communication towers, electric power houses which play a critical role in
post-earthquake activities must remain functional immediately after the earthquake and hence
require higher degree of assurance against possible damage. Public buildings, educational
buildings, busy commercial complex etc. where the risk of human loss is high and some critical
structures like nuclear power plants, dams, etc. whose collapse may cause secondary disasters
are also designed to assure higher level of safety against earthquakes. Other buildings like
residential buildings, offices, mercantile buildings etc. are designed for lower level of safety,
while the design philosophy mentioned above is always maintained. However, the level of
safety to be assured in the design may also depend upon the demand of the client.

Design of buildings to resist earthquakes involves controlling the damage to acceptable levels
at a reasonable cost. Contrary to the common thinking that any crack in the building after an
earthquake means the building is unsafe for habitation, some damage in non-structural elements
may be unavoidable. Different types of damages (mainly visualized through cracks; especially
so in concrete and masonry buildings) may occur in buildings during earthquakes. Some of
these cracks are acceptable (in terms of both their size and location), while others are not. In
general, qualified technical professionals may only be knowledgeable of the causes and severity
of damage in earthquake-resistant buildings.

3
2 Description of the Building
2.1 Building Description
The building to be analyzed and designed here is a 3 story with stair cover residential building
to be constructed on behalf of Mr. Bimal Lalchan. The proposed site is located at Mustang. The
ground floor plan of the building is presented below in Figure 2-1. The building description is
presented in Table 2-1: Building Description.

Figure 2-1 : Ground floor Plan of Building

Table 2-1 : Building Description


General features
Building Type Residential Building
Location Gharapjhong Rural Municipality-2, Mustang
Ground Floor Area 1540 sq. ft.
Architectural features
Number of story Three story with stair cover
Floor to Floor Height 9’-5”
Total Height of the Building: 37’-8 “ unto top slab from plinth level
Building Lateral Dimensions (Maximum ) Max distance along X: 35’-0”

4
Max distance along Y: 44’-0”
Wall and Partition 9” and 5” Brick Masonry in cement mortar in
outside and inside respectively
Structural features
Structural System RCC Frame Structure
Foundation Type RCC Isolated Footings and Combined footing
Loads Resisting Elements
Columns 300mm X300mm
Beams Main beam: 230mm X 350mm
slab 125 mm
Geotechnical Features
Soil Test Not Available
Soil Type (assumed) Type III (Soft Soil
Seismic Zone considered: V (as per IS 1893:2016, Part-1)
Allowable bearing capacity assumed 100 KN/m 2
Material
Grade of concrete: M20 for column, beam, slab and footings.
Grade of Reinforcement steel for RCC Fe 500

2.2 Location of Building


Nepal is a highly vulnerable to earthquake hazards. As per IS 1893:2016 (Part 1), Nepal can be
predicted to lies in high seismic risk (Zones V) as shown in Figure 2-3. The site is located at
Mustang and it belongs to the higher seismic risk zone V.

Figure 2-2 : Seismic Hazard of Himalayas

5
3 Numerical modeling
A three dimensional finite element model of the whole structural system is created in
ETABS.v18. The structural system is considered as a Special Moment Resisting Frame
structure. Main components to be modeled are: Beams, Columns & Slabs. Beams and columns
are modeled as frame elements while slabs are modeled as four-nodded shell elements. The
support condition at the base is idealized as a fixed support and hence any moment release at
the base of columns is neglected. The moment release at the beam/column joints is also
neglected. Self-weight of the parapet wall is applied onto the beams in the form of uniformly
distributed loads. Stair isn’t modeled but it’s weight is applied on respective supporting beam.
The inner partition wall load is applied by creating null beam as positioned in architectural
drawing.

Figure 3-1 : 3D model created in ETABS

6
Figure 3-2 : Ground /First/Second Floor plan modeled in ETABS

Figure 3-3 : Top floor plan modeled in ETABS

7
Figure 3-4 : Elevation on grid A-A/B-B

Figure 3-5 : Elevation on grid C-C/D-D

8
4 Structural analysis
For the purpose of structural analysis various Indian Standard Codes are followed for loadings,
load combinations and other analysis procedures.

4.1 Load cases considered


Following loads have been considered in the analysis of the building as per IS 456-200 and
IS1893-2016.

I. Dead Load (DL)


II. Live load (LL)
III. Earthquake load in X-direction (EQx)
IV. Earthquake load in Y-direction (EQy)
4.2 Load combination
Following load combinations have been adopted as per IS 1893:2016 for Static Analysis.

I. 1.5(DL+LL)
II. 1.2(DL+LL±EQ(x,y))
III. 1.5(DL±EQ(x,y))
IV. 0.9DL±1.5EQ(x,y)
Where, DL= Dead load
LL = Imposed (Live) load
EQ(x,y) = Earthquake load (Along X and Y direction)

4.3 Mass Source


Following mass source have been adopted as per IS 1893:2016 for Seismic Analysis.

Table 4-1 : Mass source


Dead load including parapet, floor finish ,wall load 1
Live load 0.25

4.4 Dead loads


Dead loads are assumed to be produced by slab, beams, columns, parapet walls and floor
finish. The weight of building materials are taken as per IS 875 (Part 1-1987).

Table 4-2 : Dead loads unit weight


Materials Unit weight
Reinforced Concrete (for foundation) 25.00 KN/m³
Reinforcement Steel 78.50 KN/m³

9
Brick Masonry 19.2 KN/m3

Table 4-3 : Dead load applied


9” wall 12.67 KN/m
9” wall with opening 9.5 KN/m
5” wall 6.33 KN/m
5” wall with opening 4.75 KN/m
Parapet wall load 2.2 KN/m
Staircase dead load +floor finish on supporting beam 12.6 KN/m
Floor finish 1.2 KN/m2

Figure 4-1 : Wall load

10
Figure 4-2 : Floor finish load

Figure 4-3 : Staircase dead+ floor finish load

11
4.5 Live load
Live loads are applied on floor slabs on the basis of usage of rooms, as specified in IS 875
part II.

Table 4-4 : Live load applied


All room except family room 2.0 KN/m2
Balcony & Passage 3.0 KN/m2
Staircase live on supporting beam 5.94 KN/m
Terrace live 1.5 KN/m2

Figure 4-4 : Live load

Figure 4-5 : Staircase live load

12
Figure 4-6 : Terrace live load
4.6 Seismic Analysis

4.6.1 Seismic coefficient method


The total design lateral force or design seismic base shear ( V B) along any principal direction
shall be determined by the following expression:

VB=Ah*w

The design horizontal seismic coefficient Ah for a structure is determined by the following
expression (IS 1893 (Part I):2016):

𝐴 =

Where,

Z = Zone factor

I = Importance factor, depending upon the functional use of structure

R = Response reduction factor, depending on the perceived seismic damage performance of


the structure, characterized by ductile or brittle deformations.

Sa/g = Average response acceleration coefficient depending upon time period

For linear static method, the time period is calculated using empirical relation

T=0.075H0.75 (for RCC frame building)


13
Where, H = Height of the building above ground

W=seismic weight of building that includes total Dead load plus appropriate amount of live
load. [7.4, IS: 1893 (part1)-2016].

4.6.2 Dynamic analysis


Considering that the building is regular building lesser than 12 m located in Zone V, dynamic
analysis wasn’t performed as per IS 1893:2016.

4.6.3 Seismic Weight and Base Shear


For the purpose of analysis, seismic forces are applied in the model of the building in ETABS
Hence, the manual calculations of seismic weight, story force, base shear and the seismic forces
have not been shown. However, the ETABS outputs for base shear is shown in table below.
Also seismic forces at each level is also shown in figure

Followings factors are considered for earthquake resistant design of the building.

Table 4-5 : Analysis and design parameters


Method adopted for design Seismic coefficient method
Response function IS 1893: 2016
Seismic Zone Zone V
Zone factor 0.36
Soil Type Type III
Height of Structure, H (m) 11.48 m
Time Period 0.47 sec (both directions)
Importance factor 1
Response reduction factor 5
Design Horizontal Seismic Coefficient 9%
(Ah=ZI/2R*Sa/g)
Mass participation Above 90% along both
directions
Base shear from seismic coefficient method along –x 480 KN
Base shear from seismic coefficient method along -y 480 KN

14
Figure 4-7 : Seismic forces at different levels

4.6.4 Story Drift and displacement Calculations


Story Drift ratio for all story are checked as defined in clause 7.11.2, IS 1893-2016. It is
found that story drift ratio for all stories are within permissible limit 0.004
Table 4-6 : Drift Calculations for Earthquake Loads
Floor Displacement Displacement Drift Drift
level Along X, Δx Along Y, Δy ratio ratio
mm mm along X along Y
Third 31.51 29.22 0.0019 0.0017
Second 25.57 24.47 0.0025 0.0022
First 18.26 17.77 0.0035 0.0034
Ground 7.95 7.84 0.0027 0.0026
Base 0 0

15
Figure 4-8 : Drift ratio in Eqx

Figure 4-9 : Drift ratio in Eqy

16
Figure 4-10 : Displacement in Eqx

Figure 4-11 : Displacement in Eqy

17
4.7 Modal analysis and modal mass participation
Table 4-7 : Modal mass Participation ration from ETABS
Case Mode Period UX UY SumUX SumUY
sec
Modal 1 0.782 0.5963 0.1495 0.5963 0.1495
Modal 2 0.768 0.2492 0.5376 0.8456 0.6871
Modal 3 0.709 0.0246 0.1869 0.8702 0.874
Modal 4 0.279 0.0476 0.0126 0.9177 0.8866
Modal 5 0.268 0.0263 0.0598 0.9441 0.9464
Modal 6 0.239 0.0216 0.0173 0.9657 0.9637
Modal 7 0.193 0.0126 0.015 0.9783 0.9787
Modal 8 0.186 0.0076 0.0104 0.986 0.989
Modal 9 0.161 0.0035 0.0002 0.9894 0.9892
Modal 10 0.156 0.0091 0.0001 0.9985 0.9893
Modal 11 0.152 0.0002 0.0107 0.9986 1
Modal 12 0.139 0.0014 0.00000116 1 1

The total mass participation in both considered direction is greater than the 90% of the total
lateral force. A building has regular modes of oscillation in two principal plan directions as
the mass participation factor for first three modes is greater than 65%.

4.8 Analysis of Internal Forces Developed in Frames


Bending moments, shear forces and axial forces of the buildings were analyzed using the
ETABS. The analysis is used for identification of critical sections and to find out the design
requirements so as to design various structural components. The sample moment diagrams,
shear force diagram, axial force diagrams and torsion diagrams of the frames along some grids
are as extracted from ETABS are presented below:

18
Figure 4-12 : Sample Bending Moment Diagram for frames along Grid C/C-1.5(DL+LL)

Figure 4-13 : Sample Shear force Diagram for frames along Grid C/C -1.5(DL+LL)

19
Figure 4-14 : Sample Axial force Diagram for frames along Grid C/C -1.5(DL+LL)

4.9 Sample B/C ratio check

Figure 4-15 : Sample B/C ratio check

20
5 Design
The design of reinforced concrete structural members includes selection of material properties
(grade of steel and concrete), shape and size of cross section, factor of safety and amount of
steel required. The design of reinforced concrete members are carried out using limit state
method as per IS 456: 2000. The limit state method is the modern and latest design
methodology. This method evolved around 1970’s. Limit state method is based on the concept
of multiple safety factors and attempts to provide adequate safety at the ultimate loads and
adequate serviceability at service loads. For the design of the members, IS 456:2000 and design
aid SP 16 has been used. Footings have been checked for vertical loads due to dead load and
live load only. Square footings have been adopted from seismic point of view that reversal stress
may occur. And footing beams are provided for column at foundation for more rigidity of
building and also need for the column located at boundary. Longitudinal reinforcement in beams
and columns has been calculated based on critical load combination. Spacing of the shear
reinforcement has been calculated as per the ductility criteria as defined in IS 13920 -
1993.Some sample designs are shown later on in this report.
Beams and columns have been designed using ETABS while slab, staircase and foundations
are designed manually. Samples of manual design calculation of critical slab ,footings and
staircase are shown in this report in ANNEX-II: SAMPLE DESIGN CALCULATIONS. The
structural design of sections and reinforcements are presented in the drawing.

21
5.1 Column design summary

Figure 5-1 : Rebar of column in Grid A

Figure 5-2 : Rebar of column in Grid B


22
Figure 5-3 : Rebar of column in Grid C

Figure 5-4 :rebar of column in Grid D

23
Table 5-1 : Column Design summary
corner bar Face bar
col
ID Floor Dia no Dia no
A1 GF 20 4 16 4
C2 A1 1F 20 4 16 4
300x300 A1 2F 16 4 16 4
C2 A2 GF 20 4 16 4
300x300 A2 1F 20 4 16 4
A2 2F 16 4 16 4
A3 GF 20 4 16 4
C2 A3 1F 20 4 16 4
300x300 A3 2F 16 4 16 4
A4 GF 20 4 16 4
C2 A4 1F 20 4 16 4
300x300 A4 2F 16 4 16 4
A5 GF 16 4 16 4
C1 A5 1F 16 4 16 4
300x300 A5 2F 16 4 12 4
B1 GF 20 4 20 4
C3 B1 1F 20 4 20 4
300x300 B1 2F 20 4 16 4
B2 GF 20 4 20 4
C3 B2 1F 20 4 20 4
300x300 B2 2F 20 4 16 4
B3 GF 20 4 20 4
C3 B3 1F 20 4 20 4
300x300 B3 2F 20 4 16 4
B4 GF 20 4 20 4
C3 B4 1F 20 4 20 4
300x300 B4 2F 20 4 16 4
B5 GF 20 4 20 4
C3
B5 1F 20 4 20 4
300x300
B5 2F 20 4 16 4
C1 GF 20 4 20 4
C3
C1 1F 20 4 20 4
300x300
C1 2F 20 4 16 4
C3 C2 GF 20 4 20 4
24
300x300 C2 1F 20 4 20 4
C2 2F 20 4 16 4
C3 GF 20 4 20 4
C3
C3 1F 20 4 20 4
300x300
C3 2F 20 4 16 4
C4 GF 20 4 16 4
C2 C4 1F 20 4 16 4
300x300 C4 2F 16 4 16 4
C4 3F 16 4 12 4
C5 GF 20 4 16 4
C2 C5 1F 20 4 16 4
300x300 C5 2F 16 4 16 4
C5 3F 16 4 12 4
D1 GF 20 4 16 4
C2
D1 1F 20 4 16 4
300x300
D1 2F 16 4 16 4
D2 GF 20 4 16 4
C2
D2 1F 20 4 16 4
300x300
D2 2F 16 4 16 4
D3 GF 20 4 16 4
C2
D3 1F 20 4 16 4
300x300
D3 2F 16 4 16 4
D4 GF 20 4 16 4
C2 D4 1F 20 4 16 4
300x300 D4 2F 16 4 16 4
D4 3F 16 4 12 4
D5 GF 20 4 16 4
C2 D5 1F 20 4 16 4
300x300 D5 2F 16 4 16 4
D5 3F 16 4 12 4

For more details refer structural drawing.

25
5.2 Beam Design Summary

Figure 5-5 : Rebar in Ground floor beam

Figure 5-6 : Rebar in first floor beam

28
Figure 5-7 : Rebar in Second floor beam

Figure 5-8 : Rebar in Second floor beam

27
Table 5-2 : Beam Design Summary
Dia of rebar
Beam Id Floor Left Middle Right
T B T B T B
1-A/B Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-B/C Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-C/D Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-A/B Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-B/C Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-C/D Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-A/B Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-B/C Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-C/D Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-A/B Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-B/C Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-C/D Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-A/B Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-B/C Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-C/D Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-1/2 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-2/3 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-3/4 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-4/5 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-1/2 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-2/3 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-3/4 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-4/5 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-1/2 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-2/3 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12

30
C-3/4 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-4/5 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-1/2 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-2/3 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-3/4 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-4/5 Ground 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-A/B 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-B/C 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-C/D 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-A/B 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-B/C 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
2-C/D 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-A/B 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-B/C 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
3-C/D 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-A/B 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-B/C 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
4-C/D 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-A/B 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-B/C 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
5-C/D 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-1/2 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-2/3 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-3/4 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
A-4/5 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-1/2 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-2/3 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-3/4 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
B-4/5 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12

29
C-1/2 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-2/3 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-3/4 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
C-4/5 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-1/2 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-2/3 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-3/4 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
D-4/5 1st 2-16+2-12 2-16+1-12 2-16 2-16+1-12 2-16+2-12 2-16+1-12
1-A/B 2nd 5-12 3-12 3-12 3-12 5-12 3-12
1-B/C 2nd 5-12 3-12 3-12 3-12 5-12 3-12
1-C/D 2nd 5-12 3-12 3-12 3-12 5-12 3-12
2-A/B 2nd 5-12 3-12 3-12 3-12 5-12 3-12
2-B/C 2nd 5-12 3-12 3-12 3-12 5-12 3-12
2-C/D 2nd 5-12 3-12 3-12 3-12 5-12 3-12
3-A/B 2nd 5-12 3-12 3-12 3-12 5-12 3-12
3-B/C 2nd 5-12 3-12 3-12 3-12 5-12 3-12
3-C/D 2nd 5-12 3-12 3-12 3-12 5-12 3-12
4-A/B 2nd 5-12 3-12 3-12 3-12 5-12 3-12
4-B/C 2nd 5-12 3-12 3-12 3-12 5-12 3-12
4-C/D 2nd 5-12 3-12 3-12 3-12 5-12 3-12
5-A/B 2nd 5-12 3-12 3-12 3-12 5-12 3-12
5-B/C 2nd 5-12 3-12 3-12 3-12 5-12 3-12
5-C/D 2nd 5-12 3-12 3-12 3-12 5-12 3-12
A-1/2 2nd 5-12 3-12 3-12 3-12 5-12 3-12
A-2/3 2nd 5-12 3-12 3-12 3-12 5-12 3-12
A-3/4 2nd 5-12 3-12 3-12 3-12 5-12 3-12
A-4/5 2nd 5-12 3-12 3-12 3-12 5-12 3-12
B-1/2 2nd 5-12 3-12 3-12 3-12 5-12 3-12
B-2/3 2nd 5-12 3-12 3-12 3-12 5-12 3-12

30
B-3/4 2nd 5-12 3-12 3-12 3-12 5-12 3-12
B-4/5 2nd 5-12 3-12 3-12 3-12 5-12 3-12
C-1/2 2nd 5-12 3-12 3-12 3-12 5-12 3-12
C-2/3 2nd 5-12 3-12 3-12 3-12 5-12 3-12
C-3/4 2nd 5-12 3-12 3-12 3-12 5-12 3-12
C-4/5 2nd 5-12 3-12 3-12 3-12 5-12 3-12
D-1/2 2nd 5-12 3-12 3-12 3-12 5-12 3-12
D-2/3 2nd 5-12 3-12 3-12 3-12 5-12 3-12
D-3/4 2nd 5-12 3-12 3-12 3-12 5-12 3-12
D-4/5 2nd 5-12 3-12 3-12 3-12 5-12 3-12
4-C/D 3rd 5-12 3-12 3-12 3-12 5-12 3-12
5-C/D 3rd 5-12 3-12 3-12 3-12 5-12 3-12
C-4/5 3rd 5-12 3-12 3-12 3-12 5-12 3-12
D-4/5 3rd 5-12 3-12 3-12 3-12 5-12 3-12
Main beam size=230x350

For more details, refer structural drawings

31
5.3 Slab Design Summary
Size: 125mm
Reinforcement:
Let’s provide 8mm@150mm c/c both ways with usual layouts/curtailments wherever required
10mm@150c/c in case of cantilever slab.
For more details, refer structural drawings

5.4 Staircase Design Summary


Staircase is designed as waist slab with following design details.
Waist Slab Thickness = 125 mm,
Longitudinal reinforcement: 12mm dia. bars@ 150mm c/c,
Transverse Reinforcement: 8 mm dia. bars @ 150mm c/c

5.5 Foundation Design Summary


The foundation is designed as Isolated footing and Combine footing. Tie beams are provided in
two different levels one at the top level of footings (Lower Tie Beams) and another at the plinth
level (Upper Tie Beams).

Figure 5-9 : Base reaction for footing design

32
Table 5-3 : Footing Design Summary
Footing pad
Footing type Size(mm*mm) Depth(mm) Reinforcement
IF1(A-1,D-1) 1700 X1700 400 mm 16 mm bar @150 c/c both way
IF2(A-2,A-3,D-2,D-3) 2200X 2200 400 mm 16 mm bar @150 c/c both way
CF1(1-B/C) 3650x1500 400mm 16 mm bar @150 c/c both way
in two layer
CF2(A-4/5,B-4/5,C- 3600X1850 400mm 16 mm bar @150 c/c both way
4/5, D-4/5) in two layer (overlap in case of
grid B and C)
CF3(2-B/C,3-B/C) 4300 X 2100 400mm 16 mm bar @150 c/c both way
in two layer
Tie beam
LTB1 & UTB1 230 x300 Longitudinal bars: 3-12dia top & bottom
Stirrups : 2-legged 8dia @ 6" c/c
For more details, refer structural drawing

33
6 CONCLUSION
After the analysis of the building components, the building is found to be safe against the gravity
as well as Seismic Loads. The section sizes and reinforcements are sufficient enough to
withstand all kinds of possible axial, shear, flexural and torsional forces. The building is
designed to make it good enough to assure Life Safety under Design Basis Earthquake
considered for Zone V, Importance Factor 1.0 and soft soil condition as per IS1893:2016.
Bearing capacity of the soil is taken as 100 KN/m2. M20 grade of concrete is used for columns,
beams, slabs and foundations. Ductile detailing as per IS13920:1993 has been extensively
adopted while detailing.
7 RECOMMENDATIONS
Design and construction of the structure are inter– related jobs. A performance of a building
depends upon a work and material quality during the construction more than the intensions
pursued during structural design. A large percentage of structural failures are attributed due to
poor quality of construction. Therefore, to assure the proper safety, material and work quality
should be maintained during the construction. Structural designer will be responsible for all the
designs but not for any faulty constructions happened at site beyond his supervision. Following
recommendations are made by the structural designer.
1. It is recommended to strictly follow the section sizes and reinforcements provided in the
structural drawings.
2. It is recommended that the site engineer should be responsible to handle the problems that
may arise during construction. He/she shall also be responsible for maintaining the material and
process quality during construction.
3. It is strictly recommended that any changes in the design shall be done only with the
consultation of the structural designer.
4. It is strictly recommended to maintain the standards in the grade of cement and reinforcement
steel. It is recommended to run a cube test to ensure the strength and quality of the concrete
ratio used. It is also recommended test the reinforcement steels to ensure the quality of steel
used.

34
ANNEXES
ANNEX -I: REFERENCES
IS: 456 – 2000 Code of Practice for Plain and Reinforced Concrete

IS: 875 (Parts 1-5) Code of practice for design loads (other than earthquake)
for buildings and structures (second revision)
Part 1 – Dead loads Part
2 – Imposed load

NBC 105: 1994 Seismic Design of Buildings in Nepal

IS: 1893 – 2016 Criteria for Earthquake Resistant Design of Structures

IS: 13920 - 1993 Ductile Detailing of Reinforced Concrete Structures


subjected to Seismic forces - Code of Practice

SP: 16 – 1980 Design Aids for Reinforced Concrete to IS: 456 – 1978

SP: 34 – 1987 Handbook on Concrete Reinforcement Detailing

Jain, A.K Reinforced Concrete, Limit State Design, fifth edition,


Nem Chand and Bros, Rookie, 1999

Sinha, S. N. Reinforced Concrete Design, second edition, Tata


McGraw Hill Publishing Company Ltd, New Delhi, 1996

Pillai, U.C. and Menon,D. Reinforced Concrete Design, second edition, Tata
McGraw Hill Publishing Company Ltd, New Delhi, 2003

Neelam Sharma Reinforced cement concrete design

35
ANNEX-II: SAMPLE DESIGN CALCULATIONS

SAMPLE BEAM DESIGN BY ETABS (1-A/B, ground Floor)


IS 456:2000 + IS 13920:2016 Beam Section Design

Beam Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
ground B29 29 beam 230x350 DCon7 4117.2 4267.2 1

Section Properties
b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)
230 350 230 0 35 35

Material Properties
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Factored Forces and Moments


Factored Factored Factored Factored
Mu3 Tu Vu2 Pu
kN-m kN-m kN kN
-47.0802 5.1701 60.9845 -3.0092

Design Moments, Mu3 & Mt


Factored Factored Positive Negative
Moment Mt Moment Moment
kN-m kN-m kN-m kN-m
-47.0802 7.6692 0 -54.7494

36
Design Moment and Flexural Reinforcement for Moment, M u3 & Tu
Design Design -Moment +Moment Minimum Required
-Moment +Moment Rebar Rebar Rebar Rebar
kN-m kN-m mm² mm² mm² mm²
Top (+2 Axis) -54.7494 449 3 449 156
Bottom (-2 Axis) 0 225 3 0 225

Shear Force and Reinforcement for Shear, Vu2 & Tu


Shear Ve Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
70.0436 0 106.0095 29.6668 932.58

Torsion Force and Torsion Reinforcement for Torsion, T u & VU2


Tu Vu Core b1 Core d1 Rebar Asvt /s
kN-m kN mm mm mm²/m
5.1701 60.9845 180 300 522.46

SAMPLE COLUMN DESIGN (B5-First floor)


IS 456:2000 + IS 13920:2016 Column Section Design

Column Element Details Type: Ductile Frame (Summary)


Level Element Unique Name Section ID Combo ID Station Loc Length (mm) LLRF
1 st story C16 147 column 300x300 DCon9 0 2870.2 1

Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
300 300 56 30

Material Properties

37
Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)
22360.68 20 1 500 500

Design Code Parameters


ɣC ɣS
1.5 1.15

Axial Force and Biaxial Moment Design For Pu , Mu2 , Mu3


Design Pu Design Mu2 Design Mu3 Minimum M2 Minimum M3 Rebar Area Rebar %
kN kN-m kN-m kN-m kN-m mm² %
100.6864 33.588 64.2053 2.0137 2.0137 2257 2.51

Axial Force and Biaxial Moment Factors


K Factor Length Initial Moment Additional Moment Minimum Moment
Unitless mm kN-m kN-m kN-m
Major Bend(M3) 0.744156 2520.2 8.423 0 2.0137
Minor Bend(M2) 0.825397 2520.2 13.4352 0 2.0137

Shear Design for Vu2 , Vu3


Shear Vu Shear Vc Shear Vs Shear Vp Rebar Asv /s
kN kN kN kN mm²/m
Major, Vu2 40.8073 61.976 29.2796 40.8073 332.53
Minor, Vu3 24.7679 61.976 29.2796 16.7844 332.53

Joint Shear Check/Design


Joint Shear Shear Shear Shear Joint Shear
Force VTop Vu,Tot Vc Area Ratio
kN kN kN kN cm² Unitless
Major Shear, Vu2 N/A N/A N/A N/A N/A N/A
Minor Shear, Vu3 N/A N/A N/A N/A N/A N/A

(1.4) Beam/Column Capacity Ratio


Major Ratio Minor Ratio
N/A N/A

Additional Moment Reduction Factor k (IS 39.7.1.1)


Ag Asc Puz Pb Pu k
cm² cm² kN kN kN Unitless
900 22.6 1656.4265 295.0504 100.6864 1

Additional Moment (IS 39.7.1)


Consider Length Section KL/Depth KL/Depth KL/Depth Ma
Ma Factor Depth (mm) Ratio Limit Exceeded Moment (kN-m)
Major Bending (M3 ) Yes 0.878 300 6.251 12 No 0
Minor Bending (M2 ) Yes 0.878 300 6.934 12 No 0

38
SAMPLE SLAB DESIGN
The design calculation of slab A1-A2-B1-B2 as critical slab has been shown in sample slab
design

DESIGN OF TWO WAY SLAB:

1.0 General Data:


Depth of slab : (D) 125 mm
Grade of Concrete : (fck) 20 N/mm2
Grade of Steel : (fy) 500 N/mm2
Effective cover: (d') 20 mm
Effective depth of slab : (d) 105 mm
Effective length:
Shoter span: (lx) 3.66 m
Longer span: (ly) 4.27 m

2.0 Loading:
Dead Load: (DL) 3.125 KN/m2
Other Dead Load: (ODL) 2.2 KN/m2
Live Load: (LL) 2 KN/m2
Total Load: (w) 7.325 KN/m2

39
Factored Load: (wu) 10.9875 KN/m2

3.0 Type of slab:

1.167

Type: Two way Slab

4.0 Calculation of Moments:


Moment coefficient:
Type of Slab Panel: 4
Short span coefficient: αx
Support S 0.05769
Mid Span M 0.04335
Long span coefficient: αy
Support S 0.047
Mid Span M 0.035
Moments:

Short span moments:


Support S 8.492 KN-m
Mid Span M 6.381 KN-m

Long span moments:


Support S 6.918 KN-m
Mid Span M 5.152 KN-m

5.0 Check depth for maximum Moments:


Maximum moments: Mu 8.492 KN-m
Moment coefficient: k 0.134
< 105
effective depth: d 57 mm
OK

6.0 Calculation of reinforcement:


6.1 For shorter span
Mim'm reinforcement (Ast)min 126 mm2

40
Design moment: Mx 8.492 KN-m
Neutral axis depth : x 12 mm
Area of steel required: Ast 196 mm2
Area of steel provided: Ø 8 mm
S 150 mm
Ast 336 mm2
Pt 0.32 %
For longer span
Effective depth d 97 mm
Mim'm reinforcement (Ast)min 117 mm2
Design moment: Mx 6.918 KN-m
Neutral axis depth : x 11 mm
Area of steel required: Ast 173 mm2
Area of steel provided: Ø 8 mm
S 150 mm
Ast 336 mm2
Pt 0.347 %

7.0 Check for shear stress:


Maximum shear force: Vu 20.108 KN
Shear Stress: tv 0.192 N/mm2
β 7.257
Concrete Shear Strength: tc 0.399 N/mm2
Shear Strength factor: K 1.3
Shear Strength of Slab: t c' 0.5187 > 0.192 N/mm2
OK

8.0 Check for development length:


Ultimate moment Capacity: M1 14.12 KN-m
Maximum Shear Force: V 20.108 KN
Bond Stress: tbd 1.92 N/mm2
Development length: Ld 454 mm
Anchorage length: L0 105 mm
Available length: 1018 > Ld
OK

41
8.0 Check for deflection:

length to eff. Depth ratio: l/d 34.858


α 23
β 1
ϒ 1.800 for fs = 169.167 N/mm2
δ 1 and Pt = 0.32 %
λ 1
Coefficient: 41.400
OK

SAMPLE ISOLATED FOOTING DESIGN(D-2 grid)


Given Data
Size of column
Bc = 300 mm
Dc = 300 mm
Column Load (V) = 408.6067 KN
Bearing Capacity (qa) = 100 KN/m2
Grade of Concrete (fck) = 20 Mpa
Grade of Steel (fy)= 500 Mpa

Calculation of size of footing


wt. of foundation = 40.86 KN
Total Load (P)= 449.47 KN
Area of footing = 4.495 m2
*Note:Taking the ratio of width and length of footing same as that of column dimensions

Size of footing
L= 2.120 m
B= 2.120 m
Provided (L) = 2.200 m
Provided (B) = 2.200 m

42
Upward reaction (q') = 126.634 KN/m

Max'm B.M. = 57.144 KN-m

Calculation for depth of footing


B.M. = 0.134 fckbd2
depth (d)= 146 mm
Provided depth (d) = 350 mm

Check for Shear


Per. Shear Strength (τc) = 0.25√fck 1.118 N/mm2
a) Punching shear
depth (d)= 350 mm
Punching shear(τ'V) = 0.615 N/mm2
Ok
Provided depth (d) = 350 mm
Overall Depth (D)= 400 mm

b) One way Shear (Calculation for no shear reinforcement)


depth (d) = 350 mm
Max'm S.F. = 75.981 KN
One way Shear (τv) = 0.217 N/mm2
Provided Ast = 0.3 %
β= 7.74
Concrete Shear strength
(τc)= 0.388 N/mm2
Ok
Ast = 1050 mm2

Calculation for reinforcement

Ast = 387 mm2


Ast required = 1050 mm2

43
mm
Provided, Size = 16 dia
Spacing = 150 mm c/c
Ast Provided= 1340 mm2
Ok
Area of Steel Along width
B.M. = 57.144 KN-m
Ast = 1050 mm2
mm
Provided, Size = 16 dia
Spacing = 150 mm c/c
Ast Provided= 1340 mm2
Ok

Development Length

Bond stress(τbd)= 1.920 N/mm2


Development length (Ld)= 906 mm
Available Ld along length = 900 mm
Provide
Hook

Load Transfer from Column to Footing


Nominal bearing stress in
column = 6.810 N/mm2
Allowable bearing stress = 0.45*fck
9.000 N/mm2

SAMPLE COMBINE FOOTING DESIGN(2-B/C grid)


Combine Footing Design
Given Data
Size of column Column1 Column2
Bc = 0.3 m 0.3 m
Dc = 0.3 m 0.3 m
Column Load (working load)(V) = 396.7133 KN 394.02 KN

44
Distance bet'n column = 1.83 m
Bearing Capacity (qa) = 100 KN/m2
Grade of Concrete (fck) = 20 Mpa
Grade of Steel (fy)= 500 Mpa

Calculation of size of footing


wt. of foundation = 79.07333 KN
Total Load (P)= 869.8067 KN
Area of footing = 8.698 m2

C.G. of loads from center of Column1 = 0.912 m


Column1 Column2
Projection Available = 1.27 m 1.2 m
C.G. of loads from outer face of footing = 2.182 m
Total Footing Length ,L = 4.364 m
Adopt L= 4.3
Inner width,b = 2.023 m
Adopt B= 2.100 m
Actual Area (A) = 9.030 m2
Upward reaction (w) = 275.84 KN/m

Stress resultants in longitudinal direction


maximum positive bending moment 152.056 KNm
Point of maximum negative moment from edge of column 1
2.1573 m
Maximum negative moment 113.8616 KNm
76.04467 KNm

Thickness base on shear


a One way Shear(longitudinal)
% of steel 0.2200

B 10.6

Tc 0.4 Mpa

45
The critical section for one way shear is located at distance d from inside face of column C2
Vu1 =591.03-275.838x(1.2+0.15+d)
Concrete shear strength Vuc= =0.35x2100xd

d= 216.3 mm
d adopted 350.0
D provided 400.0

b Two way shear


The critical section is located d/2 from periphery of column C1 and C2
Factored soil pressure 131.3514 KN/m2
punching shear at column A 554.5152 KN
punching shear at column B 535.534 KN
Per. Shear Strength = 0.25√fck 1.118 N/mm2
Punching strength at column A 626.099 KN OK
Punching strength at column B 1017.411 KN OK

Check base pressure


q 96.32410484 OK

Design of longitudinal flexural reinforcement


maximum negative moment= 113.8616 KN-m

Ast percentage = 0.105


(Ast )min percentage= 0.12
Bar size 16
Spacing required 261.12 mm
Adopt spacing 150 mm

Maximum positive
moment 152.056 KN-m
Ast percentage = 0.141
(Ast )min percentage= 0.12
Bar size 16
Spacing required 407.67 mm
Adopt spacing 150 mm

Design of column strips as transverse beams

46
a Transvers beam under column C1
Factored load per unit length of beam 283.3667 KN/m
projection of beam beyond column face 0.9 mm
Bending moment 114.7635 KNm
Effective depth of transvers beam 301 mm
Width of beam 2100 mm
Ast percentage = 0.144
(Ast )min percentage= 0.12
Bar size 16 mm
Spacing required 399.18 mm
Adopt spacing 150 mm

b Transverse beam under column C2


Factored load per unit length of beam 281.4429 KN/m
projection of beam beyond column face 0.9 mm
Bending moment 113.9844 KNm
Effective depth of transvers beam 301 mm
Width of beam 2100 mm
Ast percentage = 0.143
(Ast )min percentage= 0.12
Bar size 16 mm
Spacing required 351.76 mm
Adopt spacing 150 mm

SAMPLE STAIRCASE DESIGN


Design of staircase(critical span)

1 Data
Grade of steel(fy) 500 N/mm2
Grade of concrete(fck) 20 N/mm2
Nominal cover 15 mm
diameter of main bars 12 mm
diameter of distribution bars 8 mm
Tread 280 mm
Rise 150 mm
thickness of waist slab 125 mm

47
Effective Depth= 104 mm
Thickness of landing slab 125 mm
support width 0.23 m

2 Load on waist slab


Inclined length per steps 0.318 m
Self weight of waist slab 0.99 KN/m
self weight of step 0.53 KN/m
total dead load 1.52 KN/m
total dead load(per m2) 5.42 KN
live load 3 KN
floor finish 1.2 KN
total load per sq.m. 9.62 KN
Factored load per sq.m. 14.43 KN
load per m 14.43 KN/m

3 Load on landing
self weight of slab = 3.13 KN/m2
floor finish 1.20 KN/m2
live load 3.00 KN/m2
load per m sq. 7.33 KN/m2
factored load 10.99 KN/m2
load/m 10.99 KN/m

4 Crtitical Flight
4.1 Rebar calculation
span of landing A 1 m
span of landing B 0.38 m
span of flight 2.5 m
Span of landing A with support 1.115
Span of landing B with support 0.495
effective span of flight with
support 2.5
effective span 4.11
reaction at B support 24.15 kN
reaction at A support 20.78 kN
point of maximum moment(x) 1.706 m
Max.bending moment 18.85 KNm

48
Ast required 470.03 mm2
spacing required 240.61904 mm
spacing provided 150 mm
Ast Provided 753.98224 mm2
Providing 12mm dia. @ 150mm c/c as main rebar

4.2 Check for shear


Max Vu= 24.15
Tv 0.232 N/mm2
Pt= 0.72
β 3.20
Tc 0.57 N/sq.mm
safe in shear

4.3 Development Length


M1= 18.85 KNm
V= 24.15 KN
L0 0.144 m
Ldmax= 924.77037 mm
Ld provided 679.6875 mm
OK
4.4 Deflection check
Ast Required 470.03 mm2
Ast Provided 753.98 mm2
Pt= 0.72 %
Fs 180.78
Modification Factor 1.5
a 23
L/d max= 34.5
L/d Provided= 39.52
Not safe,wall should be built before staircase concreting
5 Distribution bar
Ast required 0.12*b*D
150
spacing required 335.10
Spacing provided 150
Providing 8mm dia. @ 150mm c/c as distribution rebar

49