Code437En 1 Trans
Code437En 1 Trans
DESCRIPTION PAGE
Technical Specification of
Power Transformers
3 General Requirements
1- General Requirements
The power transformers shall be designed, manufactured, tested, packed, marked, installed and
commissioned according to the applicable requirements of the following standards and this specification.
IEC 60076-1: General
IEC 60076-2: Temperature rise
IEC 60076-3: Insulation levels and dielectric tests
IEC 60076-4: Guide to the lighting impulse and switching impulse testing of power
transformers and reactors.
IEC 60076-5: Ability to withstand short circuit
IEC 60076-8: Users Guide
IEC 60076-10: Determination of transformer and reactor sound level
IEC 60137: Bushings for alternating voltage above 1000V
IEC 60168: Tests on insulators
IEC 60185: Current transformers
IEC 60214: On load tap changer
IEC 60270: Partial discharge measurements
IEC 60296: Specification for unused mineral insulating oils for transformers and switches.
IEC 60354: Loading guide for oil – immersed power transformers
IEC 60437: RIV tests on insulators
IEC 60506: Switching impulse tests on high voltage insulators
IEC 60542: Application guide for on load tap changer
IEC 60616: Terminal & tapping marking for power transformer
IEC 60694: Common clauses for high voltage switchgear and controlgear standard
IEC 60947-1: Low voltage switchgear- General rules
ANSI C57-1200: Short circuit dynamic withstand capability of transformers
ISO 1461: Metallic coating, hot dip galvanized coating on fabricated ferrous products
requirements
BS 4232: Specification for surface finish of blast- cleaned steel for painting
All amendments, supplements and reference publications listed within the above standards shall also
apply.
The power transformers shall be complete with the required spare parts and all necessary accessories for
proper operation. Basic equipment data and ratings shall be as indicated in schedule TR (I).
Technical Specification of Power Transformers 4
The power transformers shall be outdoor, separate winding or auto- transformers, oil-immersed and oil
conservator type.
Transformer and their equipments shall deliver its full rate capacity under the specified conditions of
ambient air temperatures and elevation.
All current carrying components such as bushings, connections, components and built in current
transformers shall have a minimum load carrying capacity equal to 120% of that of the associated
windings under all service conditions.
In case of failure of forced cooling, transformers starting from hot condition, shall be capable of
remaining in operation without injurious heating for the following periods:
- At full load for not, less than 10 minutes after outage of all forced cooling.
- Transformers having no assigned rating for natural cooling shall be capable of remaining
energized for not less than 1 hour without any load current.
- Transformers fitted with two groups of coolers each capable of dissipating 50 percent of the
losses shall be capable of remaining in operation at full load for not less than 20 minutes in the
event of failure of a forced cooling associated with one stage of cooler.
AC and DC auxiliary supplies of transformer and accessories should be as specified in schedules.
Transformer shall be designed and assembled in such a manner that the average sound level due to the
operation of the transformer and accessories will not exceed from specified value.
Insulated pockets of the core are to be connected so that no potential difference will exist between them.
The transformer shall be relatively free from undue or harmful vibration of the tank or accessories, or
vibration which will cause audioable noise. Flux distortion shall be minimized to reduce noise level.
The core and coil assembly shall be provided with suitable lugs for purposes of lifting of the entire
assembly.
The core stack shall be earthed internally through grounding link, accessible from the manhole to permit
disconnecting the link and testing of the core for earth leakage.
The core shall be designed in such a way to not saturate under any credible normal operation conditions.
2-2- Windings
In the design, construction, and treatment of windings, proper consideration shall be given to all factors of
service such as dielectric and mechanical strength of insulation, coil characteristics, uniform electrostatic
flux distribution, Minimum dielectric losses, minimum restriction for free oil circulation for uniform low
operating temperature, elimination of hot spots, voltage distribution between adjacent turns and
throughout the winding, prevention of corona formation at normal operating voltages, and the control of
dielectric flux under impulse condition for high impulse strength.
The entire design, construction, and treatment of the windings and their assembly on the core shall
embody the latest improvements in the art and conform to best modern practice.
The transformer windings shall be designed to withstand specified impulse and dielectric test voltage.
Winding conductors shall be free from scale, burrs, and splinters and shall have rounded corners and shall
be uniformly insulated. End turns of coils and windings shall be provided with potential grading or
additional insulation to withstand the voltage stresses.
All conductors used for the coil structures shall be made by copper. The turns in the coils shall be
thoroughly treated in such a way to develop the full mechanical and electrical strength of the transformer
and to minimize deterioration.
The conductors shall be transposed at sufficient intervals in order to minimize eddy currents and equalize
the distribution of currents and temperature along the windings.
Coils shall be made up, shaped and braced to provide for expansion and contraction due to temperature
changes in order to avoid abrasion of insulation and to provide rigidity to resist movement and distortion
caused by abnormal operating conditions. Adequate barriers shall be provided between windings and core
and between high voltage and low voltage windings. End coils shall have necessary protection against
abnormal disturbance.
Technical Specification of Power Transformers 6
The neutral point of the star windings shall brought out via a suitable bushing and shall not be connected
to the inside part of the tank.
Both terminals of each winding should be brought out at the same side of the core, at any case half turn
winding should not be used.
Winding insulation shall be of uniform or non-uniform quality and composition, which shall provide good
insulation, minimum wrapage, resistance to deterioration in hot oil, and adequate mechanical and
dielectric strength for the service required.
The assembled core and coils shall be blocked and braced to prevent movement or damage from short
circuit stresses.
Crossover and winding tap and terminal leads shall be insulated and lashed or fastened in such a manner
as to prevent any movement which will injure the insulation and cause shorting of coil turns or windings.
Varnish and insulating compounds, when used, shall be of a type impervious to hot oil. Varnish
application on coil windings may be given only for mechanical protection and not for improvement of
dielectric properties.
Materials used in the insulation and assembly of the windings shall be insoluble, non– catalytic, and
chemically inactive in the hot transformer oil under the operating conditions.
2-6- Tank
The transformer tank shall be a hot – rolled low carbon steel plate case of substantial construction, which
shall be oil tight and provided with an oil tight cover. The tank cover shall be designed to shed water. The
joints between the tank and cover (unless the design is such that the cover and top section of the tank are
integral) and between sections of the tank, shall be provided with suitable flanges, sufficient properly
spaced bolts and gaskets (double gaskets preferred), so that the assembly will be oil tight.
The gaskets shall be made of resilient material which will not deteriorate under the action of hot oil and
will remain oil tight.
The tank shall be provided with manhole's of suitable size to afford easy access to the tap changing
mechanism, lower ends of bushings, current transformers, terminals, and the upper portions of the coils.
The transformer shall be provided with suitable eyebolts and / or lugs for lifting the essential parts, also
for lifting the completely assembled transformer. Lifting lugs shall have ample factor of safety to allow
for possible unequalized lifting forces.
Technical Specification of Power Transformers 8
The tank shall have 4 pulling eyes for all four directions. The pulling eyes shall be suitably braced to
withstand a pull at up to 15° from the horizontal.
All cover opening shall have an upright edge of not less than 5 Cms., and gaskets which can be used
again after opening (rubber type, not glued).
The transformer tank, radiators, pipes and conservator shall withstand full vacuum and be oil tight for an
over pressure on the liquid surface which measured as a column of oil, shall be equal to the internal
height of the tank.
Each tank shall be provided with a minimum of four jacking plate at the same level to enable the
transformer, complete with mounted accessories and oil, to be raised or hauled and slewed in any
direction.
The transformer tank shall be provided with a pressure relief device of adequate size to protect the tank
against an explosion due to arcing below the surface of the oil. The pressure relief should be installed on
top of the tank in order to be far from the high voltage equipments. It shall be equipped with alarm and
trip contacts suitable for operation on the station service supply voltage. Fire retardant cable from the
contacts shall be run in cable duct with cover and terminated in the terminal cabinet.
Each transformer shall be provided with two external ground pads, each with two tapped holes for
connection to the ground bus.
The transformer shall be provided with a suitable steel frame base to permit moving the transformer in
either direction when completely filled with oil.
The construction of the main tank, auxiliary tank, tap changer tank, and the oil preservation system shall
provided for temperature changes attained between no load and maximum rated load operation (taking
into consideration an allowable overload).
Oil resisting synthetic rubber gaskets shall not be used.
All pipe entries to the main tank shall have oil – tight shut – off valves arranged to given positive
indication of the open and closed positions. Drain and sampling valves shall be provided in stiffeners box
with padlock.
Provision should be made to prevent movement of internal parts of transformer during transportation.
Adequate provision should be made for reduction of losses and preventing hot spot in main tank.
The transformer tank shall be provided with at least the following valves (in addition to those required for
the proper functioning of the transformer):
- drain valve with 100 mm dia. so located as to completely drain the tank.
- Two oil filter valves on diagonally opposite corners of 50 mm dia.
- Oil sampling valves with app. 8 mm dia. at top and bottom of main tank.
- One 15 mm dia. release plug for gas/air on the top of the tank.
- Two plugged pipe outlets equipped with shut - off valve for applying and measuring vacuum.
9 Design and Construction
2-7- Tapchanger
2-7-1 Off load tapchanger
The transformer, if required, shall be equipped with external manually operated tap changer for changing
connection to the taps in tertiary windings.
Tap will be changed only when the transformer is deenergized. The tapchanger shall be mounted on the
side of the transformer case at a convenient height for operation from the floor on which the transformer
is mounted and shall include operation hand wheel indicating pointer and dial and means for locking the
tapchanger in any desired position. The complete tap changing mechanism shall be built with high
electrical, mechanical and thermal safety factors.
Te contacts shall be capable of withstanding the full short circuit current of the transformer without
injury. The tapchanger shall be capable of carrying overload currents according to IEC 60354.
The tapchanger handle shall also be provided with an electrical interlocking device, having normally open
contacts, arranged to trip the transformer when the locking pin is taken out.
Tap position indicator of each phase of tapchanger on the transformers tank shall be provided.
The contractor (diverter switch) compartment shall be provided with an inspection cover and an over–
pressure device having trip contacts. The whole unit shall be installed inside the main tank and piped to
the conservator compartment as described in the foregoing. Tapchanger pressure relief valve should be
explosive type.
The contactor compartment shall permit draining of oil and no connection shall be made between this
compartments and the transformer tank in order to prevent the mixing of the oil.
The on load tap changing equipment shall be suitable for parallel operation with any of the similar power
transformers in the same substation and be equipped with all necessary wiring, relays, control switches,
instruments, etc, required to provide complete manual and automatic control and the necessary
arrangement for the selection of any of the similar power transformer for parallel operation.
The remote electrical control shall be arranged for manual and individual or parallel automatic control.
A set of "make" contacts shall be provided for operation of the annunciator to indicate an out - of - step
condition when in parallel operation.
In addition to the components essential to the operation of OLTC, the tapchanger control cabinet shall
also house the following:
- Tap position indicator with maximum and minimum resetable drag hands. The indicator shall be
visible by a man operating the tap changer manually by the handle.
- Five digits operations counter.
- "Raise – lower" push –buttons or switch, for manual electric control.
- "manual – automatic" selector switch.
- Tap changer motor protection and control circuit devices.
- Door actuated light.
- Thermostatically controlled anticondensation heater.
- Mechanical and electrical stops to prevent operation beyond the end positions in both directions.
- Devices for remote operation from the control room/scada.
- Emergency pushbutton for tripping the driving motor circuit breaker.
2-7-5- Annunciations
The following annunciations shall be provided in the remote control panel:
- motor supply failure.
- Control supply failure.
- Drive motor autotripped .
- Tapchanger in progress.
- Out – of – step operation when the tapchanger is operating in parallel.
- Tapchanger delayed.
- Automatic / manual mode.
- Tapchanging incomplete.
2-10- Bushings
Bushings of same voltage shall be interchangeable between units. All bushings shall be so designed that
there will be no deterioration of any parts due to stresses caused by temperature changes and adequate
means shall be provided to accommodate conductor expansion. The bushings shall be oil-tight, gas-tight
and water-tight.
Bushings rated 63 kV shall be oil or condenser type and bushings rated above 63 kV shall be oil-filled
condenser type provided with magnetic oil level indicators visible from ground level and capacitance taps
for purposes of voltage measurement and dielectric loss factor testing.
The bushings shall be so constructed that potential devices may be connected without having to drain the
oil. Oil filled bushings shall be free from oil leakage. They may be either sealed type or provided with
convenient means for sampling the oil and draining the bushing from the bottom.
Two bolt terminals shall be furnished on the bushings.
All porcelain used in the bushings shall be manufactured by the wet process. The glazing of the porcelain
should be homogenous, and impervious to moisture. It shall also be free from blisters, cavities or other
flows affecting the mechanical strength or dielectric quality.
Oil-filled bushings shall be designed to prevent the accumulation of explosive gases and to provide
adequate oil circulation to remove internal heat. Oil in oil filled bushings shall meet the requirements of
the transformer oil and be suitable for the duty.
The bushing shall be so designed that when operating at normal rated voltage there will be no electrical
discharge between conductors and bushings which will cause, directly or indirectly, or by the formation
of chemically active substances, corrosion or injury to the conductors, insulators, or supports.
The bushings shall be free from external and internal corona. The winding connection for condenser
bushing shall be by means of conductor lead which shall be connected to the bushing bottom terminal.
The bushing design shall permit installation or removal of current transformers without removing the tank
cover and removal of the bushings without disturbing the current transformers.
Bushings rated for 400 A and above shall have non-ferrous flanges and hardware fittings made of steel or
malleable iron shall be galvanized.
17 Design and Construction
Bushings shall be located in the transformer so that minimum clearances applicable for the BIL are
available between live parts and live parts to earthed structure.
2-12- Accessories
All gauges, meters, relays and thermometers shall be mounted in such a way that the vibration from the
transformer is not transmitted to these equipment.
Contacts of the accessories shall be insulated from ground and shall be of positive snap action and
mercury type. Alarm and control contacts shall be open during normal conditions, and shall be self
pressure device, and shall be for the specified DC voltage of the substation.
All contacts and devices for external connections shall be connected to terminals in the terminal cabinet.
Alarm contacts shall be rated 0.5 ampere minimum and control contacts shall be rated 5 amperes
minimum. Auxiliary relays shall be used where required.
The transformer shall be provided with the following accessories:
2-12-1- Conservator
Conservator tank should have adequate capacity for the ambient temperature range specified. The tank
shall be mounted with proper slope between the ends to facilitate draining, and the lower end shall be
fitted with a drain valve of suitable size, complete with dummy plug. The conservator shall be provided
with a manhole, correctly sized, filling valve with dummy plug, and lifting eyes. The connecting pipe to
the main transformer tank shall be provided with an indicating shut-off valve located on the conservator
side of the gas detector relay.
The oil conservators shall have at least volumes of 15% of the total oil volume. The conservator shall be
provided with outlets for silicagel breather and be equipped with an oil-level indicator.
The expansion system shall be scaled in order to achieve a low air content in the oil. After filling with
degassed oil, the rate of air leakage into the transformer must be lower than 0.3% (volume dissolved
air/oil volume) after one month.
Gaseous nitrogen, shall be sealed in the space above the oil level in the conservator. The system furnished
should be automatic in operation, shall provide for expansion and contraction of oil over the temperature
variations and effectively seal the interior from atmosphere. Particular care should be taken to eliminate
gas leakage. The system shall be complete with a gas cylinder filled with high pressure gas, an automatic
reducing valve, a breathing regulator and a mechanical relief valve. Sudden pressure relay shall also be
supplied having one set of alarm contacts on the pressure switch. The relay should be connected to the
nitrogen chamber for monitoring the rate of change of pressure and it should not operate for normal
variations of pressure in the tank.
Alternatively, the conservator shall be sealed expansion tank type provided with a flexible oil resistant air
bag to prevent air from coming into contact with oil. The air bag shall be designed to withstand repeated
expansion and contraction due to changes in temperature. An alarm device shall be provided to give an
alarm in the event of rupture of the bag and entering of air into the conservator.
19 Design and Construction
2-12-2- Gas and oil actuated relay (twin float buchholtz relay)
Two element gas detector relay, arranged to collect all involved gas should be provided in the pipe
connecting the conservator to the main tank. The relay shall be equipped with two sets of contacts, one set
to operate an alarm on slow gas accumulation and one set to trip the transformer on surge accumulation.
The gas-operated relay shall be provided with test push-button and valve equipment for pumping in air
for testing the relay function.
The gas-operated relay shall be so arranged and designed that its active parts are accessible for inspection,
repairs and replacement without oil being drained from the conservator. This can be achieved by a valve
in the pipe to the conservator necessitating of a small quantity of oil or by a shunt pipe with a suitable
valve arrangement.
A five mm dia. copper pipe with protective cover or steel pipe shall be connected to relay test-cock to a
valve located near ground level to facilitate sampling of the gas.
2-12-9- Wheels
Swiveled wheels shall be suitable for use on the standard rail gauges of 1435/2940 mm, and provided so
that they can be turned through an angle of 90°. Suitable means shall be provided for anchoring of the
transformer body to the foundation or rails after dismantling wheel's of the transformer.
2-18- Rejection
The purchaser reserves the right to reject the transformer and demand a new transformer if during test or
service, any of the following discrepancies in respect of guaranteed values occurs:
- Measured losses exceed the guaranteed values by more than the tolerance allowed by IEC 60076.
- Percentage impedance measured exceeds the guaranteed value by±10% or more.
Technical Specification of Power Transformers 24
Item Tolerance
a) Total losses + 10% of the total losses
See note 1 + 15% of each component loss, provided that the
b) component losses tolerance for total losses is not exceeded
Voltage ratio at no load on principal tapping for a The lower of the following values:
specified first pair of windings a) ±0.5% of declared ratio
b) ±1/10 of the actual percentage impedance on the
principal tapping
Voltage ratio on other tappings, same pair To be agreed, but not less than the lesser of the values in
a) and b) above
Voltage ratio for further pairs To be agreed, but not less than the lesser of the values in
a) and b) above
Short- circuit impedance for:
- a separate – winding transformer with two windings, or
- a specified first pair of separate windings in a multi –
winding transformer
a) Principal tapping When the impedance value is ³10%
±7.5% of the declared value
When the impedance value is <10%
±10% of the declared value
b) Any other tapping of the pair When the impedance value is ³10%
±10% of the declared value
When the impedance value is <10%
±15% of the declared value
4. Short- circuit impedance for:
- an auto – connected pair of windings, or
- a specified second pair of separate windings
in a multi-winding transformer
2.23.2. Feature
The system shall have at least a reliable and accurate sensor to detect key gases and if possible moisture
and electronic controller to process, save, and analyze the collected data, facilities to communicate with
remote SCADA or other monitoring system.
The system should have the ability of reading composite value of gases, in ppm.
In addition the system is required to have following features:
- Hourly and daily trend (ppm changes during target period) with alarm features.
- Adjustable alarms on gas levels and trends.
- Remote communications via optional modem.
- Network capabilities.
- Sensor and system self-test and diagnostics.
- Connection to a SCADA system, either locally at the substation or remotely via optional modem.
The system shall be completed and installed on the transformer for which all provision such as oil inlet,
oil outlet, AC supply, alarm wiring, communication connection, etc shall be provided.
In any case even if supplying the system is not in scope of work of manufacturer, all necessary provision
for installation of such system by buyer shall be foreseen. i.e:
- Provision for oil inlet, oil outlet (different from sampling or filtering valves)
- Provision for AC/DC supply from cooler control cubicle and related wiring route on the body.
- Provision for routing communication and alarm cables from the unit through cooler control cubicle.
- Provision for easy attachment of the unit on tank body (suitable location).
27 Spare Parts and Tools
4. Tests
The transformer and it's accessories shall be subjected to following tests in accordance with IEC 60076,
60137 and 60044 standards.
- Visual inspection
- Measurement of winding resistance
- Measurement of voltage ratio and check of phase displacement
- Measurement of short-circuit impedance and load loss
- Measurement of no-load loss and current
- Dielectric tests
- Tests on on-load loss tap-changers
- Routine tests for bushings according to IEC 60137
- Routine tests for current transformers according to IEC 60044
- Drawing list
- Final as built DOC./Dwg
- Dismantling, reassembling and adjusting manuals
- Transformer equivalent circuit for overvoltage and network analysis
- Calculation of surge voltage transfer from primary to secondary and tertiary
An internal inspection shall be made of the transformer if external inspections or impact recorder
indicates possible shipping damage.
Dry air should be continuously supplied into the transformer while the manhole cover is removed.
Extreme care must be taken that the oxygen content is 19.5% or more whenever anyone is inside. Dew
point should be kept as close as possible to the value as measured at the factory. The transformer should
not be left open any longer than necessary preferably less than 2 h.
When the internal inspection is made, the manufacturers recommendations should be followed. Inspection
will include, for example, removal of any shipping blocking; examination for indication of core shifting;
test for unintentional core grounds; visual inspection of windings, leads, and connections including
clamping, bracing, and blocking; inspection of tap switches, including contact wipe, line– up, and
pressure; inspection of current transformers, including supports, and condition and clearance of leads;
examination of bushing draw leads; and checking for dirt, metal particles, moisture, etc. If any internal
damage that may have been due to rough handling handing is found during this inspection, the carrier and
the manufacturer should be notified. The manufacturer should also be notified if any foreign material is
discovered. The transformer should not be opened under circumstances permit the entrance of moisture
such as on days of high humidity.
7.2. Handling
The Transformer should always be handled in the normal upright position unless information from the
manufacturer indicates it can be handled otherwise. Where a transformer cannot be handled by a crane or
moved on wheels, it may be skidded or moved on rollers or slip plates, depending upon compatibility of
transformer base design and the type of surface over which it is to be moved.
Lifting lugs and eyes are normally provided for lifting the complete transformer, and the necessary
additional means are provided for lifting the various parts assembly. The lifting lugs and eyes are
designed for vertical lift only. When lifting the complete transformer or a heavy piece, the cable should be
so attached to provided a vertical force to each lug. Use Lifting cables of appropriate lengths so that the
transformer will be lifted evenly.
Jack bosses or pads on all power transformers are provided so that it can be raise by means of jacks. On
some transformers, jacks may be placed under the transformer bottom plate at points designated by the
manufacturer. The drawings or manufacturers instructions should be consulted.
7.3. Storage
If the transformer will not be installed after reception or will be stored for a long time, the storage shall be
done according to the following requirements:
- the storage process shall be in accordance with manufacturer instructions.
- If the transformer has been shipped without oil, it shall be filled with oil before storage.
33 Transportation, Storage, Installation and Commissioning
Radiators or heat exchangers, liquid piping, valves, and fittings should be thoroughly cleaned and flushed
(if contaminated) with clean, warm 25-35°C dielectric liquid before fitted to the transformer. Radiators or
heat exchangers are usually capable of withstanding full vacuum. If not, these should not be installed until
after the tank has been filled with dielectric liquid under vacuum.
Liquid – level gauge, temperature gauges, and other accessories should be installed in accordance with
manufacturers instructions.
The degree of vacuum required depends on the design of the windings and insulation and should be
determined in consultation between the manufacture and purchaser before assembly is begun. In general a
vacuum treatment at pressures of the order of 2 mmHg (absolute) may suffice for transformers rated
below 132 kV.For higher voltage transformers, vacuum treatment at pressures less than 1 mmHg absolute
pressure may be required. An additional benefit gained from the treatment at high vacuum is that the
moisture introduced into the transformer insulation during assembly can be removed before the
transformer is energized.
A vacuum pump of evacuating the tank to the required degree of vacuum in approximately 2-3 h is
recommended. Connect the vacuum pump to the vacuum fill connection on top of the transformer with
pipe or reinforced house of sufficient size to minimize line losses.
In order to obtain an accurate vacuum value, it is essential that connection of the gauge or manometer be
as close to the tank as possible and preferably at a different location on the tank than the vacuum hose.
Start the vacuum pump and continue pumping until the tank pressure is constant. Close the vacuum pump
valve and check for leaks in the tank or piping. If all joints are tight, there should be no appreciable
increase in residual pressure in a period of 30 min.
- Winding ratio test on each tap. If OLTC transformer, check winding ratio on all OLTC positions.
- Check winding resistance of all windings with a Kelvin bridge or another suitable test device and
compare with factory test results.
- Check operation of liquid and winding temperature indicating devices and their control accessories.
- Check dissolved gas, dielectric strength, power factor, interfacial tension, neutralization number, and
water contact of the dielectric liquid.
- Check oxygen content and total combustible gas content of nitrogen gas cushion in sealed tank
transformers. A total combustible gas test, where applicable, and a dissolved gas in oil test of the
dielectric fluid should also be made soon after the transformer is in service at operating temperature
to provide a suitable postenergization reference "bench mark".
- Check operation of auxiliary equipment, such as OLTCs, liquid– circulating pumps, fans, or liquid or
water flow meters in accordance with manufacturers instructions.
- Check polarity, magnetization current, and impedance.
- Check resistance, ratio, and polarity of instrument transformers when provided. These tests should be
made from terminal blocks from the control cabinet.
- Bushings tests.
- Insulation resistance test on auxiliary and control circuits.
- Check operation and wiring of auxiliary and control panels.
- Check operation of gas relay.
- Check the position of the conservator and silicagel breather.
- Check the secondary of bushing current transformers and be sure to short circuiting the cores which
will be not used.
- Check the neutral connection, piping, fire protection system (if any) and oil leakage if any.
37 Tables
SCHEDULE TR (I)
RATINGS AND CHARAGERISTICS OF POWER TRANSFORMER
Item Description Technical particulars
1 Particulars of system
1.1 Highest system voltage kV *
1.2 Nominal system voltage kV *
1.3 Number of phases 3
1.4 Nominal system frequency HZ 50
1.5 System neutral earthing Solidly earthed / resistance earthing
1.6 Max. duration of short time current sec *
2 Service conditions
2.1 Max. ambient temperature °C 40/45/50/55
2.2 Min. ambient temperature °C -40/-35/-30/-25
2.3 Average value of daily temperature °C *
2.4 Solar radiation w/m2 *
2.5 Altitude above sea level m 1000/1500/2000/2500
2.6 Pollution L/M/H/VH
2.7 Max. wind velocity m/s 30/40/45
2.8 Wind velocity at ice condition m/s 20
2.9 Ice coating thickness m/m 5/10/20/25
2.10 Ground seismic acceleration m/s2 0.2g/0.25g/0.3g/0.35g
2.11 Relative humidity % 90/95/more than 95
3 Characteristics of transformer
3.1 Class (indoor / outdoor) *
3.2 Type:
3.2.1 Auto or separate winding *
3.2.2 Core or shell *
3.2.3 Single / Three phase *
3.3 Vector group *
3.4 Rated voltage
3.4.1 HV side kV *
3.4.2 LV side kV *
3.4.3 TV side kV *
3.4.4 Permissible overexcitation % 10
Technical Specification of Power Transformers 38
SCHEDULE TR (I)
RATINGS AND CHARAGERISTICS OF POWER TRANSFORMER
Item Description Technical particulars
3.5 Highest voltage
3.5.1 HV side kV *
3.5.2 LV side kV *
3.5.3 TV side kV *
3.6 Rated power, at site condition
(irrespective of tap changer position)
3.6.1 HV side MVA *
3.6.2 LV side MVA *
3.6.3 TV side MVA *
3.7 Impedance voltage
(base of HV winding MVA and principal tap)
3.7.1 HV/LV % *
3.7.2 HV/TV % *
3.7.3 LV/TV % *
3.8 Insulation level
3.8.1 Winding
3.8.1.1 P.F.W voltage
- HV side kV *
- LV side kV *
- TV side kV *
- Neutral kV *
3.8.1.2 L.I.W voltage
- HV side kV peak *
- LV side kV peak *
- TV side kV peak *
- Neutral kV peak *
3.8.1.3 S.I.W voltage
- HV side (if applicable) kV peak *
- LV side (if applicable) kV peak *
39 Tables
SCHEDULE TR (I)
RATINGS AND CHARAGERISTICS OF POWER TRANSFORMER
Item Description Technical particulars
3.8.2 Bushing
3.8.2.1 P.F.W voltage
- HV side kV *
- LV side kV *
- TV side kV *
- Neutral kV *
3.8.2.2 L.I.W voltage
- HV side kV peak *
- LV side kV peak *
- TV side kV peak *
- Neutral kV peak *
3.8.2.3 S.I.W voltage
HV side (if applicable) kV peak *
LV side (if applicable) kV peak *
3.9 Max. temperature rise at rated power
3.9.1 Hot spot °C *
3.9.2 Winding °C *
3.9.3 Top oil °C *
3.10 Radio interference at 1 MHZ and 1.05 rated
voltage mV *
3.11 Sound level dB *
3.12 Cooling system (air or water cooled)
3.12.1 Mode of cooling (ONAN/ONAF/…)
3.12.2 HV/LV/TV rated output power at
- ONAN MVA *
- ONAF MVA *
- OFAF MVA *
Technical Specification of Power Transformers 40
SCHEDULE TR (I)
RATINGS AND CHARAGERISTICS OF POWER TRANSFORMER
Item Description Technical particulars
3.13 Tapchanger
3.13.1 Type
3.13.2 Tapping range *
3.13.3 Number of tap *
3.13.4 Max. complete operation time of tap changer sec *
3.13.5 Rated current A *
3.13.6 Operating mode (parallel/single) *
3.13.7 Automatic voltage regulator required? Yes /No *
3.13.8 Winding location *
3.13.9 Voltage class (I or II) *
3.13.10 Remote OLTC control panel required Yes /No
3.14 Method of earthing system
3.14.1 HV side *
3.14.2 LV side *
3.14.3 TV side *
3.15 Bushings
3.15.1 Rated current (HV/LV/TV) A *
3.15.2 Short circuit current (HV/LV/TV) kA *
3.15.3 Test tap required? Yes/No *
3.15.4 Minimum external creepage distance
3.15.4.1 HV side mm *
3.15.4.2 LV side mm *
3.15.4.3 TV side mm *
3.15.4.4 Neutral mm *
3.16 Short circuit duration sec 2
3.17 Symmetrical short circuit current
3.17.1 HV side kA *
3.17.2 LV side kA *
3.17.3 TV side kA *
3.18 Transformer losses (for tender evaluation of
transformer losses will be valued)
3.18.1 No load loss $/KW *
3.18.2 Load loss $/KW *
3.19 Penalty
3.19.1 No load loss (iron loss) $/KW *
3.19.2 Load loss (copper loss & cooling system) $/KW *
3.20 Manual tap changer on TV side is required Yes/No *
41 Tables
SCHEDULE TR (I)
RATINGS AND CHARAGERISTICS OF POWER TRANSFORMER
Item Description Technical particulars
3.21 Master / flower control is required? Yes/No *
3.22 Line drop compensation equipment is required? Yes/No *
3.23 Type of terminal
3.23.1 HV *
3.23.2 LV *
3.23.3 TV *
3.24 Auxiliary power supply voltage
3.24.1 AC V *
3.24.2 DC V *
3.25 BCT required? Yes /No *
3.26 Phase winding BCT characteristics
3.26.1 Ratio *
3.26.2 Accuracy *
3.26.3 No. of cores *
3.26.4 Burden VA *
3.27 Neutral BCT characteristics
3.27.1 Ratio *
3.27.2 Accuracy *
3.27.3 No. of cores *
3.27.4 Burden VA *
3.28 Max vibration (at rated condition) micron *
3.29 Type of tank (bell or conventional) *
3.30 Wheels required? Yes/No *
3.31 Magnetic oil level indicator for main tank required? Yes/No *
3.32 Type of conservator (Air bag / conventional) *
3.33 Hydraulic jacks required? Yes/No *
3.34 Oil test kit required? Yes/No *
3.35 Oil purification plant required? Yes/No *
3.36 Is on line gas monitoring (OLGM) required?
*
If no, is there need to provision for OLGM? Yes/No
3.37 Lightning arrester supports required (HV/LV/TV) Yes/No *
3.38 Access ladder required? Yes/No *
3.39 Fire protection system required? Yes/No *
3.40 Oil (class acc. To IEC 60296) *
3.41 Whether radiators shall be separately mounted? Yes/No *
3.42 Radiators (painted or hot dip galvanized) *
3.43 Size of copper ground conductor mm2 *
Technical Specification of Power Transformers 42
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
1 General
1.1 Manufacturers name and country
1.2 Type designation
1.3 Class outdoor/indoor
1.4 Applicable standards
1.5 Applicable condition:
1.5.1 Max. design ambient temperature °C
1.5.2 Min. design ambient temperature °C
1.5.3 Average daily temperature °C
1.5.4 Solar radiation w/m2
1.5.5 Design altitude above sea level m
1.5.6 Design pollution level
1.5.7 Max. permissible ice thickness mm
1.5.8 Design seismic acceleration m/s2
1.5.9 Max. permissible wind velocity m/s
2 Type of transformer
2.1 Shell or core
2.2 Auto or separate windings
2.3 Three phases or single phase units
3 Cooling type
3.1 First stage
3.2 Second stage
3.3 Third stage
4 Rated frequency HZ
5 Vector group
6 No load voltage KV
7 Normal voltage variation range %
8 Exceptional voltage variation range %
9 Rated power at IEC condition
(at first / second and third stage of cooling)
9.1 HV side MVA
9.2 LV side MVA
9.3 TV side MVA
43 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
10 Continuous maximum rating irrespective of tapping
Position when operating under the specified site
Condition (at first / second and third stage of cooling)
10.1 HV side
10.2 LV side
10.3 TV side
11 Rated ratio
12 Insulation level
12.1 Winding
12.1.1 HV side P.F.W voltage kV
12.1.2 LV side P.F.W voltage kV
12.1.3 TV side P.F.W voltage kV
12.1.4 Neural P.F.W voltage kV
12.1.5 HV side L.I.W voltage kVpeak
12.1.6 LV side L.I.W voltage kVpeak
12.1.7 TV side L.I.W voltage kVpeak
12.1.8 Neutral L.I.W voltage kVpeak
12.1.9 HV side S.I.W voltage kVpeak
12.1.10 LV side S.I.W voltage (if applicable) kVpeak
12.2 Bushing: kV
12.2.1 HV side P.F.W voltage kV
12.2.2 LV side P.F.W voltage kV
12.2.3 TV side P.F.W voltage kV
12.2.4 Neutral side P.F.W voltage kV
12.2.5 HV side L.I.W voltage kVpeak
12.2.6 LV side L.I.W voltage kVpeak
12.2.7 TV side L.I.W voltage kVpeak
12.2.8 Neutral side L.I.W voltage kVpeak
12.2.9 HV side S.I.W voltage (if applicable) kVpeak
12.2.10 LV side S.I.W voltage (if applicable) kVpeak
Technical Specification of Power Transformers 44
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
13 Maximum temperature rise above ambient tem. at
rated power
13.1 Winding
13.1.1 Hot spot °C
13.1.2 Average (measured by resistance test) °C
13.2 Oil
13.2.1 Top oil °C
13.2.2 At inlet to cooler °C
13.2.3 At outlet of cooler °C
14 Maximum flux density in iron at rated voltage and
Power frequency and at rated voltage ratio
14.1 Wound limbs T
14.2 Unwound limbs T
14.3 Yokes T
14.4 Shields T
15 Maximum flux density in iron under the most onerous
voltage conditions (10% over rated voltage on any
tapping at 50 HZ)
15.1 Wound limbs T
15.2 Unwound limbs T
15.3 Yokes T
15.4 Shields T
16 Max. current density in windings at IEC rated power
16.1 HV side A/mm2
16.2 LV side A/mm2
16.3 TV side A/mm2
16.4 Tapping windings A/mm2
17 Magnetizing current and power (HV winding)
17.1 At 90% rated voltage A&KVA
17.2 At 100% rated voltage A&KVA
17.3 At 110% rated voltage A&KVA
17.4 At the maximum system voltage A&KVA
45 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
18 Losses at site condition
18.1 Load losses at rated frequency, 75°C & rated current
on principal tapping
18.1.1 First stage of cooling KW
18.1.2 Second stage of cooling KW
18.1.3 Third stage of cooling KW
18.2 Load losses at 75°C & max rise voltage tapping
18.2.1 First stage of cooling KW
18.2.2 Second stage of cooling KW
18.2.3 Third stage of cooling KW
18.3 Load losses at 75°C & max. lower voltage tapping
18.3.1 First stage of cooling KW
18.3.2 Second stage of cooling KW
18.3.3 Third stage of cooling KW
18.4 No load losses at rated frequency & rated voltage on
principal tapping KW
18.5 Cooling plant losses at ONAF1/ONAF2/OFAF rating KW
18.6 Proportion of sum of fixed and load losses at ONAN
rating, principal tapping, in respect to the rated
power Which will be supplied during the temperature
rise test %
18.7 Total losses at 75°C and rated current and principal
tapping
18.7.1 At IEC rating including input to cooling plant KW
18.7.2 At ONAN rating KW
19 Impedances
19.1 Positive sequence impedance at 75°C on principal
tapping & on max. relevant MVA base
19.1.1 Between HV & LV %
19.1.2 Between HV & TV %
19.1.3 Between LV & TV %
19.2 Positive sequence impedance at 75°C, max.
raise voltage and on max. relevant MVA base
19.2.1 Between HV & LV %
19.2.2 Between HV & TV %
19.2.3 Between LV & TV %
Technical Specification of Power Transformers 46
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
19.3 Positive sequence impedance at 75°C, max.
Lower voltage and on max. relevant MVA base
19.3.1 Between HV & LV %
19.3.2 Between HV & TV %
19.3.3 Between LV & TV %
19.4 Zero sequence impedance at 75°C on principal
Tapping & on max. relevant MVA base
19.4.1 Between HV & LV %
19.4.2 Between HV & TV %
19.4.3 Between LV & TV %
19.5 Resistance of windings at 75°C on
Principal tapping & on max. relevant MVA base
19.5.1 HV side Ω/phase
19.5.2 LV side Ω /phase
19.5.3 TV side Ω /phase
20 Maximum fault current in winding on which
mechanical stresses are based
20.1 HV side winding
20.1.1 Symmetrical component current kA
20.1.2 Asymmetrical crest current kApeak
20.2 LV side winding
20.2.1 Symmetrical component current kA
20.2.2 Asymmetrical crest current kApeak
20.3 Tapped winding
20.3.1 Symmetrical component current kA
20.3.2 Asymmetrical crest current kApeak
20.4 TV side winding
20.4.1 Symmetrical component current kA
20.4.2 Asymmetrical crest current kApeak
47 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
21 Maximum fault current on which mechanical
Stresses are based for OLTC (main & arcing contacts)
21.1 Symmetrical current kA
21.2 Asymmetrical crest current kApeak
22 Winding cross section
22.1 Minimum cross sectional area of conductor for
22.1.1 HV winding mm2
22.1.2 LV winding mm2
22.1.3 Tapped winding mm2
22.1.4 TV winding mm2
22.2 Minimum cross sectional area of insulated conductor for
22.2.1 HV winding mm2
22.2.2 LV winding mm2
22.2.3 Tapped winding mm2
22.2.4 TV winding mm2
23 Type and arrangement of winding
23.1 HV side
23.2 LV side
23.3 Tapping
23.4 TV side
24 Conductor material
24.1 HV windings
24.2 LV windings
24.3 Tapping windings
24.4 TV windings
24.5 Type of joints
24.6 Type of insulation of winding (uniform/graded)
24.7 Insulation material
25 Exciting current
25.1 At rated voltage when excited from HV side A
25.2 At 110% rated voltage when excited from HV side A
Technical Specification of Power Transformers 48
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
26 Tap changers
26.1 Off load tap changer
26.1.1 Type
26.1.2 Manufacturer
26.1.3 Rated current A
26.1.4 Rated step voltage V
26.1.5 Total number of steps
26.1.6 Voltage class kV
26.1.7 BIL to ground kVpeak
26.1.8 BIL between divertor switch contacts kVpeak
26.1.9 BIL across regulating winding kVpeak
26.10 Position of tapping (winding)
26.2 On load tap changer
26.2.1 Type (oil /vacuum)
26.2.2 Manufacturer
26.2.3 Rated current A
26.2.4 Rated step voltage V
26.2.5 Rated switching levels kA
26.2.6 Position of tapping (winding)
26.2.7 Voltage class kV
26.2.8 BIL to ground kVpeak
26.2.9 BIL between divertor switch contacts kVpeak
26.2.10 BIL across regulating winding kVpeak
26.2.11 Type of AVR
26.2.12 Method of parallel control
- master / follower
- minimum circulating current
- reverse reactance method
49 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
26.2.13 OLTC protection system
26.2.13.1 oil flow relay type and maker
26.2.13.2 pressure relief type and maker
26.2.13.3 over pressure relay type and maker
26.2.13.4 other protection equipment type and maker
26.2.14 Type and designation of driving mechanism
26.2.15 Rated voltage of drive motor V
26.2.16 Rated voltage of control circuit V
26.2.17 Whether remote control cubicles for AVR control
Included in scope of work? Yes /No
26.2.18 Full description of remote OLTC control cubicle
included in offer? Yes /No
27 Capability of transformer to remain in operation from
hot condition without injurious heating at rated full
load in case of failure of
27.1 50% of air forced cooling min
27.2 100% of air forced cooling min
27.3 All of air and oil forced cooling min
27.4 Condition of injurious heating (hot spot temp) °C
28 Cooling system
28.1 Number of coolers or cooler banks for ONAF1/ONAF2
28.2 Number of radiator units in each bank
28.3 Manufacturer of radiators
28.4 Number of fans
28.5 Make and type of fans
28.6 Number of pumps
28.7 Make & type of pumps
28.8 Capacity of each fan and motor kW
28.9 Capacity of each pump and motor kW
28.10 Rated operating voltage of fans V
28.11 Three or single phase
28.12 Starting current of each fan A
28.13 Efficiency of each fan
28.14 Rated operating voltage of pumps V
28.15 Three or single phase
Technical Specification of Power Transformers 50
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
28.16 Staring current of each pump A
28.17 Efficiency of each pump
29 Core data
29.1 Three limb / five limb
29.2 Type of core stacking
29.3 Type of steel core lamination
29.4 Thickness of steel core lamination mm
29.5 Manufacturer of steel core material
29.6 Insulation of core
29.6.1 lamination
29.6.2 core bolts (if applicable)
29.6.3 strapping
30 Tank
30.1 Tank design (conventional /bell shaped)
30.2 Thickness of transformer tank plates
30.2.1 Cover mm
30.2.2 Sides mm
30.2.3 Bottom mm
30.2.4 Radiator Plates mm
30.2.5 Conservator mm
30.3 Vacuum withstand capability
Tank mmHg
Radiators mmHg
Conservator mmHg
30.4 Positive pressure withstand capability for
Complete transformer mmHg
31 Vibration at rated frequency and voltage at 75°C micron
32 Provisions for tank mounting lighting arrester? Yes/No
33 Anti – vibration pad? Yes/No
51 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
34 Oil
34.1 Manufacturer
34.2 Country of manufacturer
34.3 Naphtenic or paraphenic based oil?
34.4 Class (as per IEC 60296)
34.5 Type (inhibited /non – inhibited)
34.6 Details of inhibitor (if applicable)
34.7 Dielectric strength and test standard
34.7.1 New kV
34.7.2 After treatment kV
34.8 Quantity of oil: liters
34.8.1 Main tank liters
34.8.2 Conservator liters
34.8.3 Radiator liters
34.9 Total oil required for commissioning liters
34.10 Total oil provided (including 5% extra) liters
34.11 Way of shipping (in drums or by truck)
34.12 Total number of drums provided
35 Max. sound level acc. to IEC 60076-10
35.1 With auxiliaries dB
35.2 Without auxiliaries dB
36 Applicable standard for overload
37 Physical data
37.1 Overall height, including bushings mm
37.2 Overall width, including mounted accessories mm
37.3 Overall Length, including mounted accessories mm
37.4 Height over cover for lifting core and coils mm
37.5 Max. shipping dimensions (largest item) L×W×H m×m
37.6 Weight of core and coils kg
37.7 Weight of tank / cooler and fittings kg
Technical Specification of Power Transformers 52
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
37.8 Weight of oil kg
37.9 Weight of on load tap changer kg
37.10 Total weight of complete transformer kg
37.11 Max. shipping weight (heaviest item) kg
37.12 Total weight of windings (copper) kg
37.13 Total weight of core (steel lamination) kg
37.14 Total weight of steel (tank, fittings, conservator, etc) kg
38 Wheels
38.1 Plain / flanged
38.2 Unidirectional / bi – directional
38.3 Gauge mm
39 Accessories make and type
39.1 Buchholz relay
39.1.1 For conservator main compartment
39.9.2 For conservator OLTC
39.2 Temperature indicators
39.2.1 Oil
39.2.2 HV winding
39.2.3 LV winding
39.2.4 TV winding (if applicable)
39.3 Conservator type (normal / air bag)
39.4 Silicagel breather
39.5 Cables
39.6 Control cabinets
39.7 Fire extinguishing system
40 Online gas monitoring system
40.1 Whether any system is offered? Yes/No
40.2 Type
40.3 Manufacturer
40.4 Manufacturer country
53 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
40.5 Sensor range (in ppm) ppm
40.6 Accuracy of sensor %
40.7 Main key gases detected
40.8 Moisture detection Yes/No
40.9 Relative sensitivity to
40.9.1 CO %
40.9.2 C2H2 %
40.9.3 C2H4 %
40.9.4 Other %
40.10 Response time Minute
40.11 Hardware
140.12 Software
40.13 Operating temperature range (oil/Ambient) °C/°C
40.14 Dimension
DxH(Cylindrical Type) cm×cm
LxWxH (Cubic Type)
40.15 Weight kg
40.16 Functions
40.17 External displays
40.18 Output options
40.19 Power requirement W
40.20 Gas alarm indicator
40.21 Supervisory link port
40.22 Communication port
40.23 Calibrator
40.24 Host PC software
40.25 Modem
40.26 Other accessories
40.27 Mounted on tank or ground
40.28 Whether all catalogues and description of the system
attached Yes/No
Technical Specification of Power Transformers 54
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
P S T N
41 Bushings
41.1 Manufacturer
41.2 Manufacturers type and identification
41.3 Rated service voltage kV
41.4 Type (oil impregnated / resin type)
41.5 Nominal current rating A
41.6 Thermal short time current rating (2 Sec) kA
41.7 Radio interference voltage level measured at
1.1 Um/ 3 at 1 MHZ mV
41.8 Type of insulation
41.9 Quantity of oil per bushing Liters
41.10 Equipped with magnetic oil indicator? Yes/No
41.11 Electrostatic capacity of complete bushing F
41.12 Loss angle at working voltage
41.13 Test method for internal discharge tests
41.14 Voltage level for internal discharge tests kV
41.15 Total creepage distance over porcelain externally mm
41.16 Protected creepage distance mm
41.17 Maximum external diameter of ring type current
transformers which can be accommodate mm
41.18 Mass of bushing complete with fittings kg
41.19 Min corona inception voltage kV
41.20 Maximum static bushing load
41.20.1 Vertical N
41.20.2 Horizontal N
41.21 Maximum dynamic bushing load
41.21.1 Vertical N
41.21.2 Horizontal N
41.22 Whether bushings can be washed when energized
(hot washing)? Yes/No
41.23 Equipped with test tap? Yes/No
42 Bushing current transformer
42.1 Ratio
42.2 Burden VA
42.3 Accuracy
42.4 No. of cores
42.5 Knee point voltage V
42.6 No load impedance Ω
55 Tables
SCHEDULE TR (II)
GUARANTEED TECHNICAL INFORMATION OF POWER TRANSFORMER
(TO BE SUPPLIED WITH TENDER)
Item Description Technical particulars
P S T N
41.22 Whether bushings can be washed when energized
(hot washing)? Yes/No
41.23 Equipped with test tap? Yes/No
42 Bushing current transformer
42.1 Ratio
42.2 Burden VA
42.3 Accuracy
42.4 No. of cores
42.5 Knee point voltage V
42.6 No load impedance Ω