CT Catalog
CT Catalog
DATASHEET LIST
Available at www.rsisolsec.com - phone +33 2 3885 6262 - [email protected]
LOW VOLTAGE
Window type
Cable indoor 1Psc-2Gsc-2Rsc-2Msc-P25-P40-P50-P60-P80 M2CA 3
Enedis tariff metering ring type CT M2GD
High performance P80S M2CB
TRO60 M2CE
P150 M2CD
J..FB.. M2CC
Cable outdoor TA..PE.. M2GN 4
TA11PE80-1 Enedis ground fault protection M2GP
TA11PE80-2 ground fault railway substation M2GQ
J5PRC ground fault protection M2GR
Built-in primary conductor 1P - 2P - 2M -2G -2R -3P M2BA 5
Bar primary TA standard M2EA 6
TA Enedis tariff metering busbar type M2GB
TR high performance M2EB
J..R.. indoor M2EC
J..X indoor M2ED
TR33 - TR66 high vibrations M2EE
TA 280 - TA 470 M2EF
Mixed : cable or bar J..FB.. M2CC 7
TR et S resin M2DB
Split core TO M2GA 8
PO150 M2CD
TCO M2GC
Bushing
Cast resin B M2FN 9
J..FD.. M2FM
Tape wound JACO M2FK 10
CEB and J20FB1 M2FJ
Summation / Switching CT
PBT - P80ST M2HA 12
PBA - P80SA M2HB
LV VOLTAGE TRANSFORMERS
Single phase TP M2JA 14
TPN M2JB
LV REACTORS S M2KN 16
Split-core CR M2GS 19
CRFE - CRF M2GU
MEDIUM VOLTAGE
MV CURRENT TRANSFORMERS Series Datasheet Index
Wound primary Indoor CB M2PA 21
J..B.. 24kV M2PB
J..B.. 36kV M2PC
Outdoor T24E - T30E M2QA 22
J..C.. M2QC
T36E M2QB
MV VOLTAGE TRANSFORMERS
Indoor Single phase 1 pole RU M2RA 25
U26E quick connector type M2RB
E..B.. M2RE
E..G.. A/B/C/W quick connector type M2RH
Single phase 2 poles RM M2SA 26
RT M2SB
U.. B/C/D M2SC
U..G.. A/B/C/W quick connector type M2SF
U24G71A quick connector type M2SH
Single phase 1 or 2 pole with fuse UT - CT M2TA 27
Fuse holder 1 or 2 poles A or B M2TE 28
MB - GB
RB - PB
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 0 to 150 A
Secondary current Isn 5 or 1 A
• Primary current from 0 to 150A Frequency 50 or 60 Hz
• Measurement and protection Rated output 1 to 60 VA
Accuracy class 0.5 - 1 - 3
• Compact size
Security factor Fs 5 to Fs30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25°C to + 40°C
Case Thermoplastic UL94 V0 or V1
Standards IEC - IEEE - CSA - AS - BS
Moulded case current transformers for
Other characteristics on request
the measurement of AC currents up to
150 A. Highest voltage for equipment Up to 2400 V
Power-frequency withstand voltage Up to 11 kV
They are made of a non-flammable Secondary current Isn 0.005 to 10 A
Frequency 1 to 10000 Hz
plastic material, and have heavy insu-
Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clX
lation. These current transformers are
Accuracy limit factor 5 - 10 - 15 - 20 - 30
suitable for any application.
Multi-ratio On RB - PB models
Multiple cores On RB - PB models
With their compact size and their high
Ambient temperature -40 °C to +70 °C
performances, they are particularly sui-
table for withdrawable switchboards
drawers. Accessories / Options
Mounting brackets EA or EN types
Strengthened mounting brackets MN type - Navy - on PB model
Sealable terminal cover (IP20) Only for 1PB - RB - PB models
Tropicalization
Full set of primary nuts and bolts
SAVI bag
for 50 wound primary transformers
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2AA/8
WOUND PRIMARY CURRENT TRANSFORMERS - STANDARD SERIES
GB 20 10 5 40 Ip BB Vis TCVis O
TC ∅
J J FF
RB 30 20 10 40 Ip D D
PB 45 45 45 80 Ip
B Screw TC ∅ J F S1S1 S2S2
D
C P1P1
C
Dimensions S1 S2
M M
Type A B C D E F G H I J K L M N P C GG P1 EE AA
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm
1PB 58 35 55 25 48 16 13 M 6 4.2 M 5 36 23 84 60 4 M HH
G R E A
MB 66 33 43 29 55 25 17 M 8 4.2 M 5 35 23 80 45 3,5
P P H
GB 66 52 43 47 55 25 17 M 8 4.2 M 5 35 23 80 64 3,5 L ∅
OI
K K EE
RB 85 58 59 52 70 25 17 M 8 4.2 M 5 56 40 111 - 5 P NN AA
L ∅I
K E
PB 104 60 68 56 86 35 17 M 8 6.3 M 5 66 42 130 - 5 N A
RB - PB with EA type brackets
J
J FF
Installation J F
• Mounting brackets are not necessary if the CT is mounted between 2 bars or 1 bar and 1 S1S1 S2
S2
cable lug. P1P1
S1 S2
• Spacers can be inserted on RB-PB models. CC DD G
P1
• On the 1PB model, never undo hexagonal nuts P1 and P2. They must not move when tighte- C M G
MD G
ning on cable lugs. M
E A AS
E A
• M5 secondary terminal tightening torque = 2.5Nm H E A AS
BB R
H
• Primary terminal tightening torque = 6 Nm on M6, 9 Nm on M8 on bars or on cable lugs. R H
B
• In case of mounting lug, the latter must be maintained during tightening so as to limit the torque R
P
transmitted to the terminal of the device. P ∅I
P L E OI
• The useful depth of M8 thread is 7 mm for all wound primary current transformers. It is advi- L E ∅I
sable to use a brass stud to link the bar or the cable lug with the transformer primary. The stud L KK E AA
should be hand-tightened in the M8 thread. K A
S1 S2
S1 S2 P1
56 P1
56 ∅ 17
142 ∅ 17
142
Rondelle plate ∅ 8 60
Flat washer ∅ 8 60 ∅ M8
∅ M8
65
23 Goujon M8 65
23 M8 stud
Rondelle onduflex ∅ 8
Onduflex washer ∅ 8 ∅ 6,5
42 86 ∅ 6,5
HuM8 nut Ecrou HuM8 42 86
120
66 66 120
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2AA/8
1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
P80SB
Technical data
Highest voltage for equipment 0,72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 0 to 150 A
• Primary current from 0 to 150A Secondary current Isn 5 or 1 A
• Measurement and protection Frequency 50 or 60 Hz
• High performance characteristics Rated output 1 to 60 VA
Accuracy class 0.5 - 1 - 3
• Variable geometry/ adaptability
Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25°C to + 40°C
Case Thermoplastic UL94 V0
Mounting brackets EA type as standard
Moulded case current transformer Standards IEC - IEEE - CSA - AS - BS
for the measurement of AC currents
up to 150 A.
Other characteristics on request
This current transformer has been Highest voltage for equipment Up to 2400 V
designed to meet the most deman- Power-frequency withstand voltage Up to 11 kV
ding requirements, especially for
Secondary current Isn 0.005 to 10 A
protection relays.
Frequency 1 to 10000 Hz
Spacers can be inserted. Then rivets Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
are replaced with screws. Accuracy limit factor 5 - 10 - 15 - 20 - 30
Multi-ratio
Multiple cores
Ambient temperature -40 °C to +70 °C
Accessories / Options
Mounting brackets EN type
Strengthened mounting brackets EB type
Sealable terminal cover (IP20)
Tropicalization
SAVI package Full set of primary nuts and bolts for 50 pieces
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2AB/9
WOUND PRIMARY CURRENT TRANSFORMERS - HIGH PERFORMANCE P80SB SERIES
66 + Abrackets
P80SB with EN type 155 M8 stud
Onduflex washer ∅ 8
HuM8 nut
19
6,1
157
16 60
30
S1 S2 19
M5
6,1
69
157 ∅ 17
P1 154,5
16 60 M8
30
79,5
S1 S2
M5
69
17
∅177
P1 154,5
M8
79,5
54 + A
137 ∅7
16 60 + A
A 30
54 + A
S1 S2
M5
69
∅ 17
P1 137 ∅7 160
M8
16 60 + A
82,5 A 30
S1 S2
M5
69
66 + A 17
∅180
P1 160
M8
©RS ISOLSEC
82,5
PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2AB/9
1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J3FM
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 1 to 600 A
• Primary current from 1 to 600 A Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Measurement and protection
Rated output 1 to 60 VA
• Compact size
Accuracy class 0.5 - 1 - 3
Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 60 Ipn -1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Casing Thermoplastics UL 94 V0
Current transformers moulded in self Ambient temperature From - 5°C to + 40°C
extinguishing casings for the measure Standards IEC- IEEE - CSA - AS - BS - UNE
of AC currents from 1 up to 600A.
Other characteristics on request
Features heavy duty insulation. Highest voltage for equipment Up to 2400 V
Power-frequency withstand voltage Up to 11 kV
This compact range fits most switch- Secondary current Isn 0.005 to 10 A
boards used for measure. Frequency 1 to 10 000 Hz
Accuracy class 0.2 - 5P5
Continuous thermal current 1.5 Ipn - 2 Ipn
Ambient temperature From -25°C to + 70°C
Accessories / Options
Sealable cover for secondary terminal (IP31) Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2AC/8
wound PRIMARY CURRENT TRANSFORMERS - J..FM SERIES
Dimensions
Type A B E J K L M
mm mm mm mm mm mm mm
J3FM 140 110 95 30 80 63.5 115
Selection table
Ip Type Rated output
A Max en VA
cl 3 cl 1 cl 0.5
5 J3FM 50 30 15
15 J3FM 50 30 15
30 J3FM 50 30 15
50 J3FM 50 30 15
100 J3FM 60 40 15
150 J3FM 60 40 15
200 J3FM 60 40 15
250 J3FM 60 40 15
300 J3FM 60 40 15
400 J3FM 60 40 15
500 J3FM 60 40 15
600 J3FM 60 40 15
Installation
Max tightening torques :
- M5 terminals: 2 N.m
- M12 terminals: 20 N.m
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2AC/8
LOW VOLTAGE INSTRUMENT TRANSFORMERS 2
OUTDOOR CURRENT TRANSFORMERS - TA..PE.. SERIES
TA9PE40
TA6PBE
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 0 to 4000 A
Secondary current Isn 5 or 1 A
• Outdoor
Frequency 50 or 60 Hz
• Primary current from 0 to 4000 A
Rated output 1 to 100 VA
• Measurement and protection Accuracy class 0.5 - 1 - 3
Security factor 5 - 10 - 15 - 20 - 25 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Voltage limiter 90-200-450-600-1500V, see datasheet
M2MA index 17
ATEX directive As a component of an ATEX system
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2GN/10
OUTDOOR CURRENT TRANSFORMERS - ta..PE..SERIES
Selection table
Ip Type Output Ip Type Output TA6PBE - TA9PBE
A maximum VA A maximum VA
cl 3 cl 1 cl 0.5 cl 3 cl 1 cl 0.5
5 to TA6PBE 45 30 15 300 TA6PE 45 30 15
150 TA9PBE 60 45 30 TA6PE40 40 20 10
50 TA6PE 5 - - TA9PE40 60 30 20
TA9PE40 10 - - TA11PE60 60 45 30
60 TA6PE 5 - - 400 TA6PE 45 30 15
TA9PE40 10 - -
TA6PE40 30 20 10
75 TA6PE 10 - - TA9PE40 45 30 20
TA9PE40 15 - -
TA11PE60 60 45 30
100 TA6PE 15 5 - 500 TA6PE25 60 30 20
TA6PE40 10 2.5 -
TA6PE40 45 20 15
TA9PE40 20 10 -
TA11PE60 30 15 - TA9PE40 60 30 30
TA11PE60 60 45 30
125 TA6PE 20 10 -
TA6PE40 10 5 - 600 TA6PE25 60 45 30
TA9PE40 30 10 - TA6PE40 45 30 20
TA11PE60 30 15 - TA9PE40 75 60 45
TA11PE60 75 60 45
150 TA6PE 30 15 -
TA6PE40 15 10 - 750 TA6PE40 30 30 15
TA9PE40 40 15 - TA9PE40 60 45 30
TA11PE60 45 15 -
TA11PE60 75 60 45
TA6PE... TA9PE60
200 TA6PE 30 20 10
TA6PE40 20 15 5 1000 TA6PE40 45 30 20
TA9PE40 45 30 15 TA9PE40 60 45 30
TA11PE60 60 30 15 TA11PE60 75 60 45
250 TA6PE 30 20 10
TA6PE40 20 15 10 1250 TA6PE40 45 30 20
TA9PE40 45 30 15 TA9PE40 60 45 30
TA11PE60 60 45 20 TA11PE60 75 60 45
Dimensions
Type Weight A B D E F G
kg mm mm mm mm mm mm
TA6PE 2.5 131 80 75 90 - 12.5
TA6PBE 2.5 131 79 75 90 - M8
TA6PE25 2.5 131 - 75 90 - 25
TA6PE40 2.5 131 - 75 90 - 40
TA9PE 4.1 131 120 114 90 - 12.5
TA9PBE 4.1 131 120 114 90 - M8
TA9PE25 4.1 131 - 114 90 - 25
TA9PE40 4.1 131 - 114 90 - 40
TA9PE50 4.1 131 - 114 90 - 50 TA11PE - TA15PE
F
Installation
Tightening torque: Primary terminals M8: 15Nm
M6 inserts: 6Nm
M8 inserts: 10Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GN/10
LOW VOLTAGE INSTRUMENT TRANSFORMERS
STANDARD SERIES
2Psc
2Psc P80
P80
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 40 to 3000 A
Secondary current Isn 5 or 1 A
• Primary current from 40 to 3000A
Frequency 50 or 60 Hz
• Inner diameter from 15 to 80 mm Rated output 1 to 60 VA
• Measurement and protection Accuracy class 0.5 - 1 - 3
Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
Case Thermoplastic UL94 V0 or V1
Standards IEC - IEEE - CSA - AS - BS
Moulded case current transformers
for the measurement of AC cur-
Other characteristics on request
rents up to 3000A, with inner
Highest voltage for equipment Up to 2400 V
diameters from 15 to 80 mm.
Power-frequency withstand voltage Up to 11 kV
Secondary current Isn 0.005 to 10 A
They are made of a non-flammable
Frequency 1 to 10000 Hz
material and have heavy insulation.
Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
They are equipped as standard
Accuracy limit factor 5 - 10 - 15 - 20 - 30
with EA type mounting brackets.
Multi-ratio On P25 - P40 - P50 - P60 - P80 models
Multiple cores On P25 - P40 - P50 - P60 - P80 models
Ambient temperature -40 °C to +70 °C
Accessories / Options
EN type on models:
Mounting brackets
2Rsc - R36 - P25 - P40 - P50 - P60 - P80
EB type on P80 model
Strengthened mounting brackets
MN type on P25 - P40 - P50 - P60 models
Sealable terminal cover (IP20) Except on 2Psc - 2Msc - 2Gsc models
Tropicalization
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2CA/11
CABLE PRIMARY CURRENT TRANSFORMERS - STANDARD SERIES
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CA/11
LOW VOLTAGE INSTRUMENT TRANSFORMERS
3
cable primary current transformers
FOR tariff metering
Technical data
Highest voltage for equipment 0.75 kV
Power-frequency withstand voltage 4 kV
Lightening impulse test voltage 8 kV
Primary current Ipn 100 to 2000 A
Secondary current Isn 5A
•Indoor Frequency 50 Hz
• Reinforced isolation 0,75/4/8kV Rated output 7.5VA
• From 100 to 2000A Accuracy class 0.2S
• Single, double, triple ratio Continuous thermal current 1.2 Ipn
• Traceability Short-time thermal current Ith 80 Ipn
Dynamic current Idyn 2.5 Ith
• Accuracy class 0,5 to 0,2S
Insulation class E
Ambient temperature - 25°C to + 40°C
Sealable secondary terminals cover Plastic transparent
Case Self-extinguishing thermoplastic
Standards IEC 61869
These current transformers have been
specially designed to meet tariff mete- Other characteristics on request
ring requirements.
Simple primary ratio 100 - 200 - 500 - 1000 - 2000A
All devices are equipped with a sealable Double primary ratio 200-500, 500-1000, ou 1000-2000
cover. Triple primary ratio 100-200-500 ou 500-1000-2000
Accuracy load from 1 to 15 VA
An individual serial number ensures Accuracy class 0.2 - 0.5 - 0.5S
traceability of each device and links to
its own calibration certificate.
Accessories / Options
Cable entry devices are equipped with Routine test certificate For each ratio
EN type fixing brackets for P40 and P80 Certificate of conformity upon request
or EA models for P50 model. Tropicalization Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2GD/1
CABLE PRIMARY CURRENT TRANSFORMERS
Selection table
Window dimension
Power Enedis Ratio Power Class Model
diameter
26 to 320 kW 100-200-500/ 5 3.75 VA 0.5 P50 dia 49 mm
26 to 320 kW 2RTD blade connectors
52 to 130 kW 200/ 5 7.5 VA 0.5 P40 dia 39 mm
26 to 130 kW 0.2S P40 dia 39 mm
26 to 130 kW 0.2S P80 dia 80 mm
52 to 320 kW 200-500/ 5 7.5 VA 0.5 P40 dia 39 mm
26 to 320 kW 0.2S P40 dia 39 mm
26 to 320 kW 0.2S P50 dia 49 mm
26 to 320 kW 0.2S P80 dia 80 mm
130 to 320 kW 500/ 5 7.5 VA 0.5 P40 dia 39 mm
130 to 320 kW 0.5 P80 dia 80 mm
64 to 320 kW 0.2S P40 dia 39 mm
64 to 320 kW 0.2S P80 dia 80 mm
130 to 640 kW 500-1000/ 5 15 VA 0.5 P80 dia 80 mm
64 to 640 kW 7.5 VA 0.2S P80 dia 80 mm
130 to 1300 kW 500-1000-2000/ 5 3.75 VA 0.5 P80 dia 80 mm
64t o 1300 kW 7.5 VA 0.2S P80 dia 80 mm
260 to 640 kW 1000/ 5 7.5 VA 0.5 P80 dia 80 mm
130 to 640 kW 7.5 VA 0.2S P80 dia 80 mm
260 to 1300 kW 1000-2000/ 5 15 VA 0.5 P80 dia 80 mm
Secondary terminals M5
130 to 1300 kW 7.5 VA 0.2S P80 dia 80 mm
520 to 1300 kW 2000/ 5 7.5 VA 0.5 P80 dia 80 mm
260 to 1300 kW 7.5 VA 0.2S P80 dia 80 mm
Dimensions
Model A B C E F G H I J
mm mm mm mm mm mm mm mm mm
P40 104 114 138 39 106 54 56 6 -
P50 104 116 140 49 86 56 91 6,3 67
P80 177 154 163 80 157 79 85 6 -
Installation
• S2 to the ground
• Primary current flows in from P1 side
• Tightening torque of the secondary terminals M5: 1.5 Nm.
• Never leave the secondary circuit open when the primary conductor is live.
High voltages could spark between secondary terminals. They can be dange-
rous for people and cause the destruction of the device. P40 and 50 single or double ratio
P80 single or double ratio P80 triple ratio P50 triple ratio
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GD/1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
P80S40
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 40 to 3000 A
• Primary current from 40 to 3000 A Secondary current Isn 5 or 1 A
• Inner diameter from 25mm to 60mm Frequency 50 or 60 Hz
• High performance characteristics Rated output 1 to 60 VA
Accuracy class 0.5 - 1 - 3
• Variable geometry
Security factor 5 to 30
• Measurement and protection
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25°C to + 40°C
Case Thermoplastic UL94 V0
Standards IEC - IEEE - CSA - AS - BS
P80S50 - 60 66 Ø 50
P80S60 - 60 66 Ø 60
Dimension A =0 as standard size. May vary according to required characteristics
44 + A
137 ∅ 6,3
16 B+ A
A 30
S1 S2
M5
69
P1 157,5
82,5 ∅D
C+ A 155
19
6,1
157
16 B
30
S1 S2
M5
69
P1 154,5
79,5 ∅D
177
54 + A
137 ∅7
16 B+A
A 30
M5 S1 S2
69
P1 160
82,5 ∅D
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CB/9
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TRO60
TRO60
P80S40
Technical data
Maximum operating voltage 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 150 to 1000 A
• Indoor
Secondary current Isn 5 or 1 A
• Primary current from 150 to 1000 A Frequency 50 or 60 Hz
• Measurement and protection Rated output 5 - 10 - 20 - 30 VA
Accuracy class 0.5 - 1 - 3
Security factor 5 to 10
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to + 40 °C
Standards IEC - IEEE - CSA - AS - BS
Current transformers moulded in
self-extinguishing resin for the Other characteristics on request
measurement of AC currents from Highest voltage for equipment Up to 1200 V
150 to 1000A. Power-frequency withstand voltage Up to 6 kV
Frequency 1 kHz
This range has high performance
characteristics, and demonstrates Accessories / Options
an excellent resistance to shocks,
Sealable terminal cover (IP20)
vibrations, salt and moisture.
90-200-450-600-1500V see datasheet
Voltage limiter
M2MA index 17
Selection table
Ip Rated output
A Max. en VA
cl 3 cl 1 cl 0,5
200 15 10 5
300 15 10 5
500 20 15 10
1000 40 30 20
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CE/1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
P150
PO150-110 HP
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 3000 A
• Primary current from 50 to 3000A Secondary current Isn 5 or 1 A
• Inner diameter from 110 to 150 mm Frequency 50 or 60 Hz
• Indoor Rated output 0.1 to 60 VA
• Measurement and/or protection Accuracy class 0.5 - 1 - 3
Safety factor 5 to 30
• Solid core or Split-Core
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
Case Thermoplastic UL94 V0
Standards IEC - IEEE - CSA - AS - BS
Moulded non-flamable case current
transformers for the measurement of Other characteristics on request
AC currents. Highest voltage for equipment Up to 2400 V for P150 and P150-110
Power-frequency withstand voltage Up to 11 kV for P150 and P150-110
This range offers excellent accuracy Secondary current Isn 0.005 to 10 A
specifications regardless of the posi- Frequency 1 to 10000 Hz
tion of the primary conductor in the Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
window. Accuracy limit factor 5 - 10 - 15 - 20 - 30
Ambient temperature -40 °C to +70 °C
The split-core version is particularly sui-
table for retrofits and maintenance of Accessories / Options
existing facilities.
Sealable terminal cover (IP20) To protect secondary terminals
An optional plastic cover prevents ac- Secondary shunt bracket To install split-core CTs
90-200-450-600-1500V - See datasheet
cidental contact with live parts. Voltage limiter
M2MA index 17
Additional clamping rods Hi-perfs on split-core PO150 or PO150-110
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2CD/4
CABLE PRIMARY CURRENT TRANSFORMERS - P150 - PO150 SERIES
50 P150 - - - 0.1 -
P150-110 - - - 0.25 -
PO150 - - - 0.1 -
PO150-110 - - - 0.25 -
100 P150 1 0.5 - 0.5 -
P150-110 1.25 0.5 - 1 -
PO150 1 - - 0.5 -
PO150-110 0.5 - - 1 -
150 P150 2.5 1.25 - 0.5 -
P150-110 5 2.5 - 1.5 -
PO150 2.5 - - 0.5 -
PO150-110 2.5 - - 1.5 -
250 P150 5 2.5 1 2.5 0.5
P150-110 10 5 2.5 2.5 0.5
PO150 5 1.25 1 2.5 0.5
PO150-110 10 5 - 2.5 0.5
500 P150 15 15 5 5 2.5
P150-110 20 20 10 10 5
PO150 15 5 2.5 5 2.5
PO150-110 20 20 2.5 10 5
1000 P150 30 30 15 7.5 5
P150-110 30 30 30 15 7.5
PO150 30 30 5 7.5 5
PO150-110 30 30 15 15 7.5
2000 P150 30 30 30 15 10
P150-110 30 30 30 30 15
PO150 30 30 10 15 10 PO150 - PO150-110
PO150-110 30 30 15 30 15
3000 P150 30 30 30 25 15
P150-110 30 30 30 30 15
PO150 30 30 15 25 15
PO150-110 30 30 15 30 5
Dimensions - overall
Model Type A B C D F G P N
mm mm mm mm mm mm mm mm
P150 Solid core 230 270 115 43 30 150 - -
P150-110 Solid core 230 270 115 43 30 110 - -
PO150 Split core 225 270 112 43 30 150 - -
PO150-110 Split core 225 270 112 43 30 110 - -
PO150 HP Split core 225 270 112 43 30 150 18 60
PO150-110 HP Split core 225 270 112 43 30 110 18 60
Dimensions - fixings
Model E I J K L M
mm mm mm mm mm mm
P150 188 8 6-8 20 180 28
P150-110 188 8 6-8 20 180 28
PO150 188 8 6-8 20 180 28
PO150-110 188 8 6-8 20 180 28
PO150 HP - - 6-8 20 180 - PO150 HP - PO150-110 HP (Hi Perfs with clamping rods)
PO150-110 HP - - 6-8 20 180 -
Installation
• Weight (indicative) :
- P150 and PO150: 3kg
- P150-110 and PO150-110 : 4kg
• Maximum torque:
- secondary terminals M5 : 2.5 N.m
- split-core tightening screws M5 : 2.5 N.m
- tightening rod nuts M4: 3.5 N.m
• Before closing the split-core CT, make sure of the perfect cleanliness of the contact
surfaces. It is advisable to wipe the surface of the magnetic circuit with a cloth
soaked in vaseline oil.
• In the case of clamping rods, tighten the 4 off M4 threaded rods gradually, and
diagonally, in order to have an even clamping.
• Warning ! Never install a split-core CT on a live primary conductor. Unless you use
the terminals to short circuit the secondary (optional)
• Caution! Never leave the secondary circuit open while the primary conductor is
energized. High voltages might surge at secondary terminals, which might be
hazardous to people and destroy the current transformer. Unless you use a voltage
limiter device (see datasheet M2MA index 17)
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CD/4
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J..FB.. SERIES
J1FB.. J4FB..
J2FB.. J5FB..
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 10000 A
• Indoor or outdoor Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Primary current from 50 to 10000 A
Rated output 1 to 100 VA
• Inner diameter from 30 to 160 mm
Accuracy class 0.2 - 0.5 - 5P
• Measurement and protection Security factor 5 to 30
Continuous thermal current 1.2 - 1.5 - 2 Ipn
Short-time thermal current Ith 80 Ipn .1s
Dynamic current Idyn 2,5 Ith
Insulation class E
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Accessories / Options
Sealable cover (IP31) Outdoor
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2CC/7
CABLE OR BAR PRIMARY CURRENT TRANSFORMERS - J..FB.. SERIES
Selection table
Type Ip Rated output lp Rated output Installation
A. Measure Protection A. Measure Protection Max tightening torques :
- M6 terminals: 4 N.m (secondary terminals)
J1FB <400 50 - <1500 70 -
- M8 terminals: 10 N.m (fixing plate)
J1FB <400 - 20 <1500 - 65
J1FB 400< <800 15 15 1500< <10000 30 30
J2FB 400< <800 50 - 1500< <10000 70 -
J2FB 400< <800 - 20 1500< <10000 - 65
J2FB 400< <800 15 15 1500< <10000 30 30
J4FB1-… 400< <800 150 - 1500< <10000 350 -
J4FB1-… 400< <800 - 150 1500< <10000 - 225
J4FB1-… 400< <800 50 80 1500< <10000 100 150
J4FB2-… 400< <800 145 - 1500< <10000 200 -
J4FB2-… 400< <800 - 100 1500< <10000 - 200
J4FB2-… 400< <800 50 75 1500< <10000 90 125
J4FB3-… 400< <800 120 - 1500< <10000 350 -
J4FB3-… 400< <800 - 60 1500< <10000 - 150
J4FB3-… 400< <800 50 30 1500< <10000 50 75
J4FB4-… 400< <800 90 - 1500< <10000 350 -
J4FB4-… 400< <800 - 75 1500< <10000 - 150
J4FB4-… 400< <800 35 50 1500< <10000 50 100
J4FB5-… 400< <800 50 - 1500< <10000 300 -
J4FB5-… 400< <800 - 7,5 1500< <10000 - 20
J4FB5-… 400< <800 15 5 1500< <10000 25 15
J5FB1-… 400< <800 350 - 1500< <10000 350 -
J5FB1-… 400< <800 - 150 1500< <10000 - 350
J5FB1-… 400< <800 50 100 1500< <10000 50 200
J5FB2-… 400< <800 250 - 1500< <10000 350 - J1FB
J5FB2-… 400< <800 - 130 1500< <10000 - 300
J5FB2-… 400< <800 50 80 1500< <10000 50 200
J5FB3-… 400< <800 150 - 1500< <10000 350 -
J5FB3-… 400< <800 - 90 1500< <10000 - 250
J5FB3-… 400< <800 50 50 1500< <10000 50 200
J5FB4-… 400< <800 100 - 1500< <10000 350 -
J5FB4-… 400< <800 - 80 1500< <10000 - 200
J5FB4-… 400< <800 50 60 1500< <10000 50 150
J5FB5-… 400< <800 75 - 1500< <10000 350 -
J5FB5-… 400< <800 - 60 1500< <10000 - 150
J5FB5-… 400< <800 40 30 1500< <10000 40 100
J5FB6-… 400< <800 30 - 1500< <10000 250 -
J5FB6-… 400< <800 - 25 1500< <10000 - 60
JFB
J5FB6-… 400< <800 15 10 1500< <10000 25 30
Dimensions
Type Weight ØA ØB E Type G H
kg. mm. mm. mm. mm. mm.
J4FB1- … 42 232 30 315 J..FB..- 1 117 130
J4FB2- … 40 232 60 315 J..FB..- 2 117 150
J4FB3- … 39 232 88 315 J..FB..- 3 117 200
J4FB4- … 38 232 110 315 J..FB..- A 117 225
J4FB5- … 37 232 130 315 J..FB..- 4 256 250
J5FB1- … 50 260 30 350 J..FB..- 5 256 350
J5FB2- … 48 260 60 350
J5FB3- … 45 260 88 350
J2FB
J5FB4- … 42 260 110 350
J5FB5- … 39 260 130 350
J5FB6- … 35 260 160 350
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CC/7
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TA9PE40
TA6PBE
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 0 to 4000 A
• Outdoor Secondary current Isn 5 or 1 A
• Primary current from 0 to 4000 A Frequency 50 or 60 Hz
• Measurement and protection Rated output 1 to 100 VA
Accuracy class 0.5 - 1 - 3
Security factor 5 - 10 - 15 - 20 - 25 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Voltage limiter 90-200-450-600-1500V, see datasheet
M2MA index 17
ATEX directive As a component of an ATEX system
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2GN/10a
OUTDOOR CURRENT TRANSFORMERS - ta..PE..SERIES
Selection table
Ip Type Output Ip Type Output TA6PBE - TA9PBE
A maximum VA A maximum VA
cl 3 cl 1 cl 0.5 cl 3 cl 1 cl 0.5
5 to TA6PBE 45 30 15 300 TA6PE 45 30 15
150 TA9PBE 60 45 30 TA6PE40 40 20 10
50 TA6PE 5 - - TA9PE40 60 30 20
TA9PE40 10 - - TA11PE60 60 45 30
60 TA6PE 5 - - 400 TA6PE 45 30 15
TA9PE40 10 - -
TA6PE40 30 20 10
75 TA6PE 10 - - TA9PE40 45 30 20
TA9PE40 15 - -
TA11PE60 60 45 30
100 TA6PE 15 5 - 500 TA6PE25 60 30 20
TA6PE40 10 2.5 -
TA6PE40 45 20 15
TA9PE40 20 10 -
TA11PE60 30 15 - TA9PE40 60 30 30
TA11PE60 60 45 30
125 TA6PE 20 10 -
TA6PE40 10 5 - 600 TA6PE25 60 45 30
TA9PE40 30 10 - TA6PE40 45 30 20
TA11PE60 30 15 - TA9PE40 75 60 45
TA11PE60 75 60 45
150 TA6PE 30 15 -
TA6PE40 15 10 - 750 TA6PE40 30 30 15
TA9PE40 40 15 - TA9PE40 60 45 30
TA11PE60 45 15 -
TA11PE60 75 60 45
TA6PE... TA9PE60
200 TA6PE 30 20 10
TA6PE40 20 15 5 1000 TA6PE40 45 30 20
TA9PE40 45 30 15 TA9PE40 60 45 30
TA11PE60 60 30 15 TA11PE60 75 60 45
250 TA6PE 30 20 10
TA6PE40 20 15 10 1250 TA6PE40 45 30 20
TA9PE40 45 30 15 TA9PE40 60 45 30
TA11PE60 60 45 20 TA11PE60 75 60 45
Dimensions
Type Weight A B D E F G
kg mm mm mm mm mm mm
TA6PE 2.5 131 80 75 90 - 12,5
TA6PBE 2.5 131 79 75 90 - M8
TA6PE25 2.5 131 - 75 90 - 25
TA6PE40 2.5 131 - 75 90 - 40
TA9PE 4.1 131 120 114 90 - 12,5
TA9PBE 4.1 131 120 114 90 - M8
TA9PE25 4.1 131 - 114 90 - 25
TA9PE40 4.1 131 - 114 90 - 40
TA9PE50 4.1 131 - 114 90 - 50 TA11PE - TA15PE
F
Installation
Tightening torque: Primary terminals M8: 15Nm
M6 inserts: 6Nm
M8 inserts: 10Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2GN/10a
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TA11PE80-1
• Outdoor use
• Dry epoxy resin insulation
Technical data
• With ground terminal Highest voltage for equipment 0.72 kV
• Vertical or horizontal mounting Power-frequency withstand voltage 3 kV
Primary current Ipn 250 A
Secondary current Isn 5A
Frequency 50 Hz
The current transformer TA11PE80-1 is Rated output 30 VA
a window type with inner diameter
Accuracy class 10 P
of 80mm.
Accuracy limit factor 5
Intended for detecting ground fault Continuous thermal current 1.2 Ipn
current in HV/MV substation. Short-time thermal current Ith 12.5 kA/1 s
Dynamic current Idyn 2.5 Ith
This transformer is cast in epoxy resin. Insulation class E
It is equipped with IP54 secondary Ambient temperature - 25°C to + 40°C
terminal cover with 2 cable glands. Protection index IP54
An M8 ground terminal is available.
Sealable terminal cover Standard
This transformer does not require any
specific maintenance. Fixing plate Standard
The transformer is mounted with or Standards IEC - IEEE - CSA - AS - BS
without its fixing plate in any position.
©RS ISOLSEC FRANCE PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2GP/1
current transformer ta11PE80-1 HV- MV SUBSTATIONS GROUND FAULT PROTECTION RELAYS FEEDING
75
Name plate
P2
258
O 80
175
87,5
100
3
14
200
175 230
230
Fixation : 4 inserts M8-12
fixing: 4 inserts M8-12
Ajout schéma électrique en page 2 + plan bilingue 08/04/19 D
Détail du marquage sur vue ISO + visserie capot 07/12/17 C
Rajout de côtes fonctionnelles 13/02/17 B
Mise à jour 06/10/15 A
Dess : G.L. Date : 19/05/2015
RS ISOLSEC
MODIFICATIONS Date Ind. Vérif : A.R. Ech : 4:10
45 , Avenue des Acacias
Installation :
Désignation : T.I.B.T. - Encombrement Matière : Résine - resin 45120 CEPOY
Approximate weight: 15kg Diffusion : Coulée - montage TI.MT et TI.BT- Bob. Format : A4 tél : 33.(0)2.38.85.62.62 fax : 33.(0)2.38.85.62.05
• NoPoids
special precautions
approximatif: 15Kgare required for handling the transformer,
Transformateur de courant beyond
extérieur not grabbingmasse
de protection by thetype: cover
TA11PE80-1 C1764 D page 1/2
:
Couples de serrage préconisés:
• Transformer is best stored indoor,
M6 sortiesinside its original packing.
secondaires 3 N.mRemove from packing in case of outdoor storage.
• CT can be fixed without fixingM8plate using the 4off M8 inserts
fixation spread
7 N.m 120mm
-Mise à jour apart. Grease up 06/10/15 each insert
A before tightening.
Vérif : N.G.
Date : 19/05/2015
Ech : 1:2
RS ISOLSEC
MODIFICATIONS Date Ind.
• When using fixing plate, use 4 off 12mm diameter holes spread 205mm
M8 borne de mise à la terre 7 N.m
Désignation apart.
: T.I.B.T. - Encombrement Matière :
Format : A4
45 , Avenue des Acacias
45120 CEPOY
Diffusion : Coulée - montage TI.MT et TI.BT- Bob. tél : 33.(0)2.38.85.62.62 fax : 33.(0)2.38.85.62.05
©RS ISOLSEC FRANCE PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GP/1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TA11PE80-2
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2GQ/2
CURRENT TRANSFORMER TA11PE80-2 FOR MASS RELAY OF RAILWAY TRACKSIDE SUBSTATION
Name plate
Plaque aluminum
d'identification
Aluminium
128
Waterproof cover
Capot étanche IP66
20
20
Silicone gasket 82
Joint Silicone
Ground terminal
Borne de mise à la terre
M8-12
M8-12 utile
60 Maxi
38
Connection
details
30
117,5
235 Maxi
95
+4
0
62
175
80
87,5
55
46
35
120 120
Cover Fixing
Fixations 4xM6
Capot: 4 M6
200 175
Fixing : 4 inserts
Fixations M8-12 M8-12 utile
: 4 prisonniers
- Mise à jour température ambiante, classe d'isolation D 30/08/2013
Couples de serrage préconisés: - Mise à jour couples de serrage, poids-Ajout Descriptif technique C 05/06/2013
M6 sorties secondaires 6 N.m - Modification diam. du trou capot D20 + sans presse-étoupe B 14/03/2013
- Inversion du capot, sortie du presse étoupe A 12/11/2012
M6 Fixations Capot 3 N.m Dess : N.G. Date : 25/10/2012
M8 Fixations 13 N.m
- Création
MODIFICATIONS
-
Date
25/10/12
Ind. Vérif : C.P. Ech : 1:2
RS ISOLSEC
45 , Avenue des Acacias
M8 Borne de mise à la terre 13 N.m Désignation : T.I.B.T. - Encombrement Matière : 45120 CEPOY
Installation
Poids total: +/-16:Kg
Diffusion : Format : A4 tél : 33.(0)2.38.85.62.62 fax : 33.(0)2.38.85.62.05
page :
TC de
• No special precautions are required for handling theProtection Massenot
transformer, beyond type TA11PE80-2
grabbing by the coveret Capot IP66 C1389 D 1/2
• Transformer is best stored indoor, inside its original packing. Remove from packing in case of outdoor storage.
• CT can be fixed without fixing plate using the 4off M8 inserts spread 120mm apart. Grease up each insert before tightening.
• When using fixing plate, use 4 off 12mm diameter holes spread 205mm apart.
• When installing the IP54 cover, tighten the 2 fixing screws gradually and alternately to evenly crush the gasket and ensure a good sealing.
• Before energizing, check that the 2 secondary terminals are connected to the operating circuit. Never open or leave the secondary open
while that the transformer is energized. High voltages may appear at the terminals of the secondary circuit. They can be dangerous for
people and lead to the destruction of the transformer.
• This transformer does not require any specific maintenance.
• Tightening torque of secondary terminals M6: 3 Nm
• Tightening torque of M8 fixing inserts: 7 Nm
• Tightening torque of grounding terminal M8: 7 Nm
• Weight: +/- 14 kg
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GQ/2
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J5PRC
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2GR/1
CURRENT TRANSFORMER FOR MASS PROTECTION - SERIES J5PRC
Installation
• Fasten the CT on metal frame using 2 holes of diameter :12mm.
• Tightening torque for secondary terminals M8 : 7Nm
• Weight: +/- 3 kg
• Never leave the secondary circuit open when the primary conductor is live. High
voltages could spark between secondary terminals. They can be dangerous for
people and cause the destruction of the device.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GR/1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
2P - 2M - 2G 1P - 2R - 3P
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 40 to 600 A
• Primary current from 40 to 600A Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Measurement and protection
Rated output 1 to 60 VA
• Compact size
Accuracy class 0.5 - 1 - 3
• Central bush for easier connection Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith Up to 26kA.1s depending on models
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C -25°C to + 40°C
Case Thermoplastic UL94 HB or V0
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
With their compact size, they are
particularly suitable for withdrawable Mounting brackets EA or EN types
switchboard. Strengthened mounting brackets MN type - Navy - on 3P model
Sealable terminal cover ( IP20) Only for 1P - 2R - 3P models
Tropicalization
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2BA/8
CURRENT TRANSFORMERS WITH CENTRAL BUSH - STANDARD SERIES
Installation
• Tightening torque for secondary terminals M5 = 2.5 N.m
• The primary conductor consists of a central bush, to be tightened between 2 bars 1 screw H
or 1 bar and 1 cable lug, or 2 cable lugs, with a steel bolt as shown on the diagram
opposite. Tighten to the specified torque figures. 2 flat washers
In
x
Type B D L Maximum tightening torque
1P 27 M8 40 + 2X 25 N.m B
L
2P 26 M12 45 + 2X 50 N.m In x Bush
2M 31 M12 50 + 2X 50 N.m
2 Onduflex washers
2G 52 M12 70 + 2X 50 N.m
1 screw HU
2R 54 M12 75 + 2X 50 N.m ∅D
3P 60 M12 80 + 2X 50 N.m
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2BA/8
LOW VOLTAGE INSTRUMENT TRANSFORMERS
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 100 to 8000 A
Secondary current Isn 5 or 1 A
• Primary current from 100 to 8000 A Frequency 50 or 60 Hz
• For busbar up to 4 bars 160 x 5 mm Rated output 1 to 60 VA
• Measurement and protection Accuracy class 0.5 - 1 - 3
• Increased depth Security factor 5 to 30
Continuous thermal current 1.2 Ipn
• Compact size
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
Case Thermoplastic UL94 V0 or V1 or Bakelite
Standards IEC - IEEE - CSA - AS - BS
Moulded case current transformers for the
measurement of AC currents from 100A to Other characteristics on request
8000A. Highest voltage for equipment Up to 2400 V
Power-frequency withstand voltage Up to 11 kV
They are made of a non-flammable plastic Secondary current Isn 0.005 to 10 A
material and have heavy insulation. This Frequency 1 to 10000 Hz
comprehensive and compact range fits most Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
busbars, from 30mm to 160mm width. Accuracy limit factor 5 - 10 - 15 - 20 - 30
Multi-ratio On the whole range
Optional : voltage limiter to protect the Multiple cores Up to 3 cores
current transformer, in case of open circuit Ambient temperature -40 °C to +70 °C
operation
Accessories / Options
Mounting brackets EN type
Sealable terminal cover (IP20)
S1 S2 terminals On the larger side - Flying leads
Tropicalization
90-200-450-600-1500V - See datasheet
Voltage limiter
M2MA index 17
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2EA/14
BAR PRIMARY CURRENT TRANSFORMERS - TA SERIES
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2EA/14
LOW VOLTAGE INSTRUMENT TRANSFORMERS
Technical data
Highest voltage for equipment 0.75 kV
Power-frequency withstand voltage 4 kV
Lightening impulse test voltage 8 kV
•Indoor Primary current Ipn 500, 1000, or 2000 A
Secondary current Isn 5A
• from 100 to 2000A
Frequency 50 Hz
• Reinforced isolation 0,75/4/8kV
Rated output 7.5 VA
• Single, double, triple ratio Accuracy class 0.2S
• Accuracy class 0.2S to 0.5 Continuous thermal current 1.2 Ipn
• Traceabiliy Short-time thermal current Ith 80 Ipn
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Sealable secondary terminal cover Plastic transparent
Case Self-extinguishing thermoplastic
Standards IEC -61869
©RS ISOLSEC France PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2GB/1
current transformer for busbars - for tariff metering
Selection table
Power Ratio Window dimension
Power Class Model
Enedis size
130 to 320 kW 500/ 5 7.5 VA 0.5 TA 301 65x20mm
130 to 320 kW 0.5 TA24 103x38mm
130 to 320 kW 0.5 TA34 105x42mm
64 to 320 kW 0.2S TA301 65x20mm
130 to 640 kW 500-1000/ 5 7.5 VA 0.5 TA 301 65x20mm
TA24 103x38mm
TA34 105x42mm
130 to 1300 kW 500-1000-2000/ 5 3.75 VA 0.5 TA34 105x42mm
130 to 1300 kW 7.5 VA 0.5 TA34 105x42mm
64 to 1300 kW 7.5 VA 0.2S TA34 105x42mm
260 to 640 kW 1000/ 5 7.5 VA 0.5 TA301 65x20mm
260 to 640 kW 0.5 TA24 103x38mm
260 to 640 kW 0.5 TA34 105x42mm
130 to 640 kW 0.2S TA301 65x20mm
130 to 640 kW 0.2S TA24 103x38mm
130 to 640 kW 0.2S TA34 105x42mm
260 to 1300 kW 1000-2000/ 5 7.5 VA 0.5 TA34 105x42mm
130 to1300 kW 0.2S TA34 105x42mm
130 to 1300 kW 0.2S TA24 103x38mm
520 to 1300 kW 2000/ 5 7.5 VA 0.5 TA24 103x38mm
520 to 1300 kW 0.5 TA34 105x42mm
260 to 1300 kW 0.2S TA24 103x38mm
260 to 1300 kW 0.2S TA34 105x42mm
Installation
Dimensions • S2 to ground
• Primary current flows in from P1 side
Model A B C D E G H I
• Tightening torque of the secondary terminals M5: 1.5 Nm.
mm mm mm mm mm mm mm mm
88 123 132 65 20 46 65 76 • On TA models, the lock nut screws must be tightened to a maximum
TA 301
torque of 1.5 Nm.
TA 24 97 164 173 103 38 40 59 77
• Never leave the secondary circuit open when the primary conductor
TA 34 137 190 199 105 42 58 80 88 is live. High voltages could spark between secondary terminals. They
can be dangerous for people and cause the destruction of the device.
©RS ISOLSEC France PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GB/1
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TR39
TR34
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
• Indoor Primary current Ipn 150 to 15000 A
Secondary current Isn 5 or 1 A
• Primary current from 150 to 15000 A
Frequency 50 or 60 Hz
• For busbar up to 4 bars
Rated output 1 to 60 VA
300 x 20 mm Accuracy class 0.5 - 1 - 3
• Measurement and protection Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
Standards IEC - IEEE - CSA - AS - BS
Current transformers moulded in
Other characteristics on request
self-extinguishing resin for the
measurement of AC currents from Highest voltage for equipment Up to 2400 V
150 to 15000A. Power-frequency withstand voltage Up to 11 kV
Secondary current Isn 0.005 to 10 A
Frequency 1 to 10000 Hz
This range has high performance
Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
characteristics, and demonstrates
Accuracy limit factor 5 - 10 - 15 - 20 - 30
an excellent resistance to shocks,
Multi-ratio
vibrations, salt and moisture.
Multiple cores
Ambient temperature -40 °C to +70 °C
It is approved by the French Navy.
Accessories / Options
Sealable terminal cover (IP20)
S1-S2 terminals on the longer side
Outdoor version Depending on model
With flying leads
90-200-450-600-1500V - See datasheet
Voltage limiter
M2MA index 17
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2EB/12
BAR PRIMARY CURRENT TRANSFORMERS - HIGH PERFORMANCE TR SERIES
Selection table
Ip Type Output Ip Type Output TR30 - TR32 - TR34 - TR36 - TR39 - TR44 - TR54 - TR56 - TR85 - TR100 -
A maximum VA A maximum VA TR120 TR 130 - TR165 - TR265 - TR300 - TR310 -TR2212
cl 3 cl 1 cl 0.5 cl 3 cl 1 cl 0.5
5
5000 TR39 60 60 60
300 TR30 20 15 10 TR310 60 60 60
TR34 30 15 10 TR44 60 60 60 S1 S2
TR54 60 60 60
400 TR30 30 20 15 F
TR56 60 60 60
TR34 30 20 15
TR125S 60 60 60
500 TR30 45 30 20 TR2212 60 60 60
TR32 30 20 10
L B D
TR34 60 45 30 6000 TR39 60 60 60
600 TR30 60 45 30 TR310 60 60 60
TR32 45 20 15 TR130 60 60 60
TR34 60 45 30 TR85 60 60 60
TR44 60 60 60
750 TR30 60 45 30
or TR32 45 45 30 TR54 60 60 60 P1
800 TR34 60 45 30 TR56 60 60 60
TR125S 60 45 30
1000 TR30 60 45 30 G E
TR2212 60 60 60
TR32 60 45 30
7500 TR310 60 60 60 H A
TR34 60 60 45
or TR130 60 60 60 Bar fastening screws
1250 TR30 60 45 30
8000 TR85 60 60 60
TR32 60 45 30
TR54 60 60 60
TR34 60 60 60
TR56 60 60 60
1500 TR30 60 45 30 TR2212 60 60 60 Installation
or TR32 60 45 30 TR265 60 60 60 Bar fastening screws must be tightened to 0.7 N.m torque maximum
1750 TR34 60 60 60 Secondary terminals : 2.5 N.m.
10000 TR85 60 60 60
2000 TR32 60 45 30
TR100 60 60 60
TR34 60 60 60
TR265 60 60 60
TR125S
On demand :
TRS125
353
B
320
320
127
70
P1
65 110
3 vis de blocage M6 Sorties secondaires M6
3 blocking screws M6 Secondary terminals M6 158
P2 Plaque signalétique
Name plate
50
P1
Bar fastening screws must be tightened to 5 N.m torque
Simplification surface d'appuis bornier secondaire 12/03/2020 A RSmaximum
Dess : G.L.
ISOLSEC Date : 11/02/2020
page :
Transformateur de courant intérieur BT type: TR125S C2145 A 1/2
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2EB/12
BAR PRIMARY CURRENT TRANSFORMERS - HIGH PERFORMANCE TR SERIES
Dimensions
Busbar
Type Weight A B D E F G H K L M 6
kg mm mm mm mm mm mm mm mm mm mm
1 to 2 bars 63 x 5 TR 30 1.2 90 127 67 20 76 48 80 18 35 18
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2EB/12
BAR PRIMARY CURRENT TRANSFORMERS - HIGH PERFORMANCE TR SERIES
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2EB/12
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J4R4-1
J4R4-2
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 400 to 4000 A
Secondary current Isn 5 or 1 A
• Primary current from 400 to 4000 A Frequency 50 or 60 Hz
• For busbar up to 3 bars 100 x 10 mm Rated output 1 to 60 VA
• Measurement Accuracy class 0.5 – 1 – 3
• Compact size Security factor 5 to 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 60 Ipn .1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Casing Thermoplastic UL94 V0 or V1
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Accessories / Options
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET M2EC/7
BAR PRIMARY CURRENT TRANSFORMERS - J..R.. SERIES
Selection table
Ip Type Rated output
A Max en VA
cl 3 cl 1 cl 0.5
400 J4R4-1 20 15 10
500 J4R4-1 30 20 15
J4R4-2 45 20 10
600 J4R4-1 60 40 15
J4R4-2 45 30 15
750 J4R4-1 60 40 15
J4R4-2 60 45 30
1000 J4R4-1 60 40 20
J4R4-2 60 45 30
1250 J4R4-1 60 40 20
J4R4-2 60 45 30
1500 J4R4-1 60 40 20
J4R4-2 60 45 30
2000 J4R4-1 60 40 20
J4R4-2 60 45 30
2500 J4R4-2 60 45 30
3000 J4R4-2 60 45 30
4000 J4R4-2 60 45 30
Dimensions
Type A B D E F G H J K L M Busbar Installation
mm mm mm mm mm mm mm mm mm mm mm Bar fastening screws must be tightened to 0.7Nm torque maximum
J4R4-1 85 127 84 21 55 50 77 M5 27 40 30 1 to 3 bars 80x5 M5 Secondary terminals : 2.5 N.m.
J4R4-2 97 164 103 38 75 40 59 M5 28 60 30 1 to 3 bars 100x10
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2EC/7
Low voltage instrument transforpmers
TR66
Technical data
• Primary current from 100 to 10 000 A Highest voltage for equipment 0.72 kV
• window for 60 to 140 mm bars Power-frequency withstand voltage 3 kV
• Up to 2 secondary windings in same CT Primary current Ipn From 100 to 10 000 A
• High resistance to environment and Secondary current Isn 5 or 1 A
vibrations Lenght of secondary cables 2.5 m
Frequency 50 or 60 Hz
Rated output 1 to 60 VA
Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P -
This CT range is in cast resin, with excellent clPX
withstand to severe environment in terms Security factor 5 to 30
Accuracy limit factor 5 - 10 - 15 - 20 - 30
of temperature, vibrations, salt, moisture
Continuous thermal current 1.2 Ipn
and contaminants.
Short time thermal current Ith Up to 80 In
Dynamic current Idyn 2.5 Ith
Secondary terminal connections are flying
Insulation class E
leads, to avoid any potential risk of loose-
Ambient temperature -5°C to + 70°C
ning connections, or vibration resonance Standards IEC - IEEE - CSA - AS - BS
that may break terminals.
Other characteristics on request
TR33xy and TR66xy are designed to adapt Highest voltage for equipment Up to 2.4 kV
to various busbar sizes, and accommo- Power-frequency withstand voltage Up to 11 kV
date large cores and windings to match Secondary current Isn any value from 0.005 to 10 A
demanding requirements in protection Number of cores Up to 2 cores
and accuracy classes. Frequency Up to 400 Hz
Length of secondary cables Upon request. Colors may be adapted too
Fixing is performed tightening 2 horse shoe-
shape clips on amagnetic support plate,
enabling very strong hold on busbar.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non binding information - DATASHEET : M2EE/6
high vibrationS busbar Current Transformer - TR33 - TR66 series
Dimensions
Series A B C E F H I J
mm mm mm mm mm mm mm
Flexible secondary
Type Weight
kg
D
mm
G
mm cables
TR330A 2.8 66 50
TR330B 2.8 86 50
TR330C 2.8 106 50
TR331A 3.9 66 70
TR331B 3.9 86 70
TR331C 3.9 106 70
TR332A 4.9 66 80
TR332B 4.9 86 80
TR332C 4.9 106 80
TR333A 5.8 66 90
TR333B 5.8 86 90
TR333C 5.8 106 90
TR334A 6.7 66 100
TR334B 6.7 86 100
TR334C 6.7 106 100
TR335A 7.6 66 110
TR335B 7.6 86 110
TR335C 7.6 106 110
TR336A
TR336B
8.5
8.5
66
86
120
120
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non binding information - DATASHEET : M2EE/6
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TA470
TA280
Technical data
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2EF/3
BAR PRIMARY CURRENT TRANSFORMERS - TA280 - TA470 SERIES
100 TA280 2.5 - - - 1.5 0.5
TA470 2.5 - - - 1.5 0.5
500 to - 15 15 15 15 5
TA280
3 000 - 15 15 15 15 5
TA470
3 000 to TA280 - 30 30 30 30 15
10 000 TA470 - 30 30 30 30 15
Dimensions
Model Weight A B C D E F G H I J K L M
kg mm mm mm mm mm mm mm mm mm mm mm mm mm
TA280 12 387 222 241 115 280 198 363 72 9 - - 15 30
TA470 17 576 266 284 160 470 243 553 72 9 146 456 15 30
Installation
• Maximum torque:
- secondary terminals M5 : 2.5 N.m
- casing tightening : 10 N.m
• Caution! Never leave the secondary circuit open while the primary
conductor is energized. High voltages might surge at secondary
terminals, which might be hazardous to people and destroy the
current transformer. Unless you use a voltage limiter device (see
datasheet M2MA index 17)
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2EF/3
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J3X J4X
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 2000 A
Secondary current Isn 5 or 1 A
• Measurement Frequency 50 or 60 Hz
• Primary current from 50 to 2000 A Rated output 1 to 60 VA
• For busbar up to 80 x 20 mm Accuracy class 0.5 - 1 - 3
• For cable diameter up to Ø 59 mm Security factor 5 to 30
Continuous thermal current 1.2 Ipn
• Compact size
Short-time thermal current Ith 60 Ipn .1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Casing Thermoplastic UL94 V0
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Accessories / Options
Sealable cover for secondary terminal (IP31) Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2ED/9
CABLE OR BAR PRIMARY CURRENT TRANSFORMERS - J..X SERIES
Dimensions
Type A B C D E F G Busbar
mm mm mm mm mm mm mm
J3X 26 31 80 84 40 54.5 85 1 bar 30 x 10
1 cable Ø 25 mm
J4X 28 82 133 133 66 54 90 1 bar 80 x 20
1 bar 60 x 30
1 cable Ø 59 mm
Selection table
Ip Type Rated output
A Max VA
cl 3 cl 1 cl 0.5
50 J3X 5 2.5 1.25
100 J3X 12.5 7.5 3.75
250 J3X 40 25 15
J4X 20 15 7.5
J4X Primary details J3X Primary details
500 J3X 45 30 20
J4X 30 20 10
600 J3X 50 40 30
J4X 40 25 15
750 J4X 50 35 20
1000 J4X 50 40 30
1250 J4X 50 50 35
1500 J4X 50 50 35
2000 J4X 50 50 40
Installation
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2ED/9
LOW VOLTAGE INSTRUMENT TRANSFORMERS
J1FB.. J4FB..
J2FB.. J5FB..
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 10000 A
• Indoor or outdoor Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Primary current from 50 to 10000 A
Rated output 1 to 100 VA
• Inner diameter from 30 to 160 mm
Accuracy class 0.2 - 0.5 - 5P
• Measure and protection Security factor 5 to 30
Continuous thermal current 1.2 - 1.5 - 2 Ipn
Short-time thermal current Ith 80 Ipn .1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Accessories / Options
Sealable cover (IP31) Outdoor
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2CC/7a
CABLE OR BAR PRIMARY CURRENT TRANSFORMERS - J..FB.. SERIES
Selection table
Type Ip Rated output lp Rated output Installation
A. Measure Protection A. Measure Protection Max tightening torques :
- M6 terminals: 4 N.m (secondary terminals)
J1FB <400 50 - <1500 70 -
- M8 terminals: 10 N.m (fixing plate)
J1FB <400 - 20 <1500 - 65
J1FB 400< <800 15 15 1500< <10000 30 30
J2FB 400< <800 50 - 1500< <10000 70 -
J2FB 400< <800 - 20 1500< <10000 - 65
J2FB 400< <800 15 15 1500< <10000 30 30
J4FB1-… 400< <800 150 - 1500< <10000 350 -
J4FB1-… 400< <800 - 150 1500< <10000 - 225
J4FB1-… 400< <800 50 80 1500< <10000 100 150
J4FB2-… 400< <800 145 - 1500< <10000 200 -
J4FB2-… 400< <800 - 100 1500< <10000 - 200
J4FB2-… 400< <800 50 75 1500< <10000 90 125
J4FB3-… 400< <800 120 - 1500< <10000 350 -
J4FB3-… 400< <800 - 60 1500< <10000 - 150
J4FB3-… 400< <800 50 30 1500< <10000 50 75
J4FB4-… 400< <800 90 - 1500< <10000 350 -
J4FB4-… 400< <800 - 75 1500< <10000 - 150
J4FB4-… 400< <800 35 50 1500< <10000 50 100
J4FB5-… 400< <800 50 - 1500< <10000 300 -
J4FB5-… 400< <800 - 7,5 1500< <10000 - 20
J4FB5-… 400< <800 15 5 1500< <10000 25 15
J5FB1-… 400< <800 350 - 1500< <10000 350 -
J5FB1-… 400< <800 - 150 1500< <10000 - 350
J5FB1-… 400< <800 50 100 1500< <10000 50 200
J5FB2-… 400< <800 250 - 1500< <10000 350 - J1FB
J5FB2-… 400< <800 - 130 1500< <10000 - 300
J5FB2-… 400< <800 50 80 1500< <10000 50 200
J5FB3-… 400< <800 150 - 1500< <10000 350 -
J5FB3-… 400< <800 - 90 1500< <10000 - 250
J5FB3-… 400< <800 50 50 1500< <10000 50 200
J5FB4-… 400< <800 100 - 1500< <10000 350 -
J5FB4-… 400< <800 - 80 1500< <10000 - 200
J5FB4-… 400< <800 50 60 1500< <10000 50 150
J5FB5-… 400< <800 75 - 1500< <10000 350 -
J5FB5-… 400< <800 - 60 1500< <10000 - 150
J5FB5-… 400< <800 40 30 1500< <10000 40 100
J5FB6-… 400< <800 30 - 1500< <10000 250 -
J5FB6-… 400< <800 - 25 1500< <10000 - 60
JFB
J5FB6-… 400< <800 15 10 1500< <10000 25 30
Dimensions
Type Weight ØA ØB E Type G H
kg. mm. mm. mm. mm. mm.
J4FB1- … 42 232 30 315 J..FB..- 1 117 130
J4FB2- … 40 232 60 315 J..FB..- 2 117 150
J4FB3- … 39 232 88 315 J..FB..- 3 117 200
J4FB4- … 38 232 110 315 J..FB..- A 117 225
J4FB5- … 37 232 130 315 J..FB..- 4 256 250
J5FB1- … 50 260 30 350 J..FB..- 5 256 350
J5FB2- … 48 260 60 350
J5FB3- … 45 260 88 350
J2FB
J5FB4- … 42 260 110 350
J5FB5- … 39 260 130 350
J5FB6- … 35 260 160 350
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2CC/7a
LOW VOLTAGE INSTRUMENT TRANSFORMERS
S
TR
Technical data
Accessories / Options
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2DB/12
BAR OR CABLE PRIMARY CURRENT TRANSFORMERS - TR & S SERIES
Selection table
TR235…TR410
Ip Type Output Ip Type Output
A maximum VA A maximum VA
cl 3 cl 1 cl 0.5 cl 3 cl 1 cl 0.5 H 40
200 S65 30 10 - 7
300 S65 45 15 5 1000 S65 120 100 75 E Fixing: 35
S90 30 10 - to S90 100 75 50 4 holes ØM F
11 C
TR235 45 15 - 1250 TR235 100 75 50 M6 secondary terminals
A
TR260 100 75 50
400 S65 60 50 30
TR385 100 75 50
S90 60 45 30
TR410 75 60 45
TR235 50 30 15
B D
TR385 50 30 15
1500 S65 120 100 75
500 S65 75 60 45
or S90 100 75 50
S90 75 50 30
1750 TR235 100 100 75
TR235 60 45 15
TR260 100 75 50
TR260 50 30 15
TR385 100 75 50
TR385 50 30 15
TR410 100 75 50
600 S65 90 75 45
S90 75 50 30
2000 S65 120 100 75
TR235 75 50 30
to S90 100 90 75
TR260 60 45 30 S65…S303
3000 TR235 100 100 75
TR385 50 45 30
TR260 100 75 50 Fixing: 4 holes ØM
TR410 30 20 15
TR385 100 75 50 D
750 S65 90 75 50
TR410 100 75 50
or S90 75 50 30
800 TR235 90 60 45
TR260 75 45 30 4000 TR235 120 100 75
TR385 75 45 30 to TR260 120 100 75
TR410 60 45 30 8000 TR385 120 100 75
∅A ∅B C
TR410 120 100 75
Dimensions E
H
Type A B C D E F M H maxi M6 secondary terminals
mm mm mm mm mm mm mm mm
TR235 235 65 345 175 250 85 M6 150
TR260 260 90 345 175 270 85 M6 150
TR385 385 65 495 175 400 85 M6 150
TR410 410 65 495 175 420 85 M6 150
S65 65 165 90 85 55 - M6 200
S90 90 165 90 85 60 - M6 200
S105 105 235 120 120 85 - M8 200
S165 - 165 90 90 60 - M6 200
S210 - 210 100 100 60 - M8 140
S240 240 345 208 208 147 - M8 140
S303 303 490 282 282 200 - M12 200
Installation
Tightening torque:
- Inserts M6: 6Nm
- Inserts M8: 10Nm
- Inserts M12: 20Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2DB/12
LOW VOLTAGE INSTRUMENT TRANSFORMERS
TO162
TO105
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 100 to 25000 A
Secondary current Isn 5 or 1 A
• Indoor Frequency 50 or 60 Hz
• Primary current from 100 to 25000 A Rated output 1 to 200 VA
Accuracy class 0.5 - 1 - 3
• Measurement and protection
Security factor 5 to 30
• Ease of assembly
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Sealable terminal cover (IP20)
Fixing plate
Voltage limiter 90-200-450-600-1500V, see datasheet
M2MA index 17
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2GA/10
Sorties secondaires M6
∅D
∅E
∅ M6
∅D
SPLIT-CORE CURRENT TRANSFORMERS - TO SERIES C B A B
∅E
∅ M6
Selection table
Secondary terminal M6
Sorties secondaires M6
TO30 - TO80 C B A B
C
Ip Type Output Ip Type Output
A maximum VA A maximum VA
Sorties secondaires M6
cl 3 cl 1 cl cl 3 cl 1 cl C
0.5 0.5 ∅D
TO220 60 45 30 Sorties secondaires M6
TO80 10 - -
TO105 10 - - 2000 TO121 60 45 30
TO2100 30 20 15
250 TO30 20 10 - A C F
TO135 60 45 30 Secondary
TO80 15 5 -
TO162
60 45 30 terminal
M6
TO105 15 5 -
TO220 60 45 30 A C F
300 TO30 20 15 - TO340 60 45 30
TO80 20 7.5 - B E
TO105 20 7.5 - 2500 TO121 45 30 20 D
∅ M8
TO340 100 60 45
A Sorties secondaires M6 E
TO135 45 15 5 TO430 100 60 45 C D
Sorties secondaires M6 B A B M8
8 prisonniers
600 TO80 30 20 10 TO550 100 60 45
TO105 30 20
10 Secondary
terminal M6
Sorties secondaires
D M6
10000 TO110 250 150 100 TO110 Sorties
∅ secondaires M6
TO121 30 20 10 ∅ M8
∅E
C
TO340 100 60 45
TO463 30 15 7.5
TO430 100 60 45 ∅ M6
TO2100 30 15 7.5 F
∅ M8
TO550 100 60 45
TO135 60 30 10
C F B A B
750 TO80 45 30 15 12500 TO220 200 150 60 ∅D
or TO105 45 30 15 to TO340 200 150 60
800 TO121 45 30 15 15000 TO430 150 90 45 ØDSorties secondaires M6
B A B
C
TO463 45 30 15 TO550 150 90 45 E
8 prisonniers
∅ M6 M8
ØD
TO2100 45 30 15 B A B
TO135 100 45 30 20000 TO220 200 150 60 E
8 prisonniers M8
∅E B A B
Secondary
terminal
Sorties secondairesM6
M6
A C F
A C F
B E
∅ M8
D
TO135 - TO162…TO550
Secondary terminal
Sorties secondaires M6 M6 ∅ M8
B C
B C
A E
D 8 prisonniers M8
A E
D 8 prisonniers M8
Sorties secondaires M6 8 off M8 insert
Sorties secondaires M6
PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2GA/10
©RS ISOLSEC
∅ M8
∅ M8
∅
∅ M6
A C F
8
B E
∅ M8
D
Sorties secondaires M6 ∅ M8
Dimensions
Type Weight A B C D E F G H
kg mm mm mm mm mm mm mm mm
B C
TO 30 3.5 76 19 120 30 150 - - -
TO 80 6.5 75 20 120 80 190 - - -
TO 81 6.5 75 20 190 80 190 166 48 128 A E
TO 105 5.9 72 22 222 105 203 - - - D 8 prisonniers M8
Installation
• Before tightening the 4 threaded rods, make sure that the contact surfaces of the
magnetic circuit are perfectly clean. It is advisable to clean the surface of the magnetic
circuit with an oiled cloth.
• Tighten the 4 screws progressively and in diagonal order in order to get even tightening
• Maximum tightening torque: M6 threaded rods: 2 Nm
M8 threaded rods: 5 Nm
• Attention ! Never install a split core CT while primary conductor is with live voltage
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2GA/10
SPLIT-CORE CURRENT TRANSFORMERS - TO SERIES
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2GA/10
LOW VOLTAGE INSTRUMENT TRANSFORMERS
P150
PO150-110 HP
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 3000 A
• Primary current from 50 to 3000A Secondary current Isn 5 or 1 A
• Inner diameter from 110 to 150 mm Frequency 50 or 60 Hz
• Indoor Rated output 0.1 to 60 VA
• Measurement and/or protection Accuracy class 0.5 - 1 - 3
Safety factor 5 to 30
• Solid core or Split-Core
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
Case Thermoplastic UL94 V0
Standards IEC - IEEE - CSA - AS - BS
Moulded non-flamable case current
transformers for the measurement of Other characteristics on request
AC currents. Highest voltage for equipment Up to 2400 V for P150 and P150-110
Power-frequency withstand voltage Up to 11 kV for P150 and P150-110
This range offers excellent accuracy Secondary current Isn 0.005 to 10 A
specifications regardless of the posi- Frequency 1 to 10000 Hz
tion of the primary conductor in the Accuracy class 0.1 - 0.2 - 0.2S - 0.5S - 5P - 10P - clPX
window. Accuracy limit factor 5 - 10 - 15 - 20 - 30
Ambient temperature -40 °C to +70 °C
The split-core version is particularly sui-
table for retrofits and maintenance of Accessories / Options
existing facilities.
Sealable terminal cover (IP20) To protect secondary terminals
An optional plastic cover prevents ac- Secondary shunt bracket To install split-core CTs
90-200-450-600-1500V - See datasheet
cidental contact with live parts. Voltage limiter
M2MA index 17
Additional clamping rods Hi-perfs on split-core PO150 or PO150-110
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2CD/4a
CABLE PRIMARY CURRENT TRANSFORMERS - P150 - PO150 SERIES
50 P150 - - - 0.1 -
P150-110 - - - 0.25 -
PO150 - - - 0.1 -
PO150-110 - - - 0.25 -
100 P150 1 0.5 - 0.5 -
P150-110 1.25 0.5 - 1 -
PO150 1 - - 0.5 -
PO150-110 0.5 - - 1 -
150 P150 2.5 1.25 - 0.5 -
P150-110 5 2.5 - 1.5 -
PO150 2.5 - - 0.5 -
PO150-110 2.5 - - 1.5 -
250 P150 5 2.5 1 2.5 0.5
P150-110 10 5 2.5 2.5 0.5
PO150 5 1.25 1 2.5 0.5
PO150-110 10 5 - 2.5 0.5
500 P150 15 15 5 5 2.5
P150-110 20 20 10 10 5
PO150 15 5 2.5 5 2.5
PO150-110 20 20 2.5 10 5
1000 P150 30 30 15 7.5 5
P150-110 30 30 30 15 7.5
PO150 30 30 5 7.5 5
PO150-110 30 30 15 15 7.5
2000 P150 30 30 30 15 10
P150-110 30 30 30 30 15
PO150 30 30 10 15 10 PO150 - PO150-110
PO150-110 30 30 15 30 15
3000 P150 30 30 30 25 15
P150-110 30 30 30 30 15
PO150 30 30 15 25 15
PO150-110 30 30 15 30 5
Dimensions - overall
Model Type A B C D F G P N
mm mm mm mm mm mm mm mm
P150 Solid core 230 270 115 43 30 150 - -
P150-110 Solid core 230 270 115 43 30 110 - -
PO150 Split core 225 270 112 43 30 150 - -
PO150-110 Split core 225 270 112 43 30 110 - -
PO150 HP Split core 225 270 112 43 30 150 18 60
PO150-110 HP Split core 225 270 112 43 30 110 18 60
Dimensions - fixings
Model E I J K L M
mm mm mm mm mm mm
P150 188 8 6-8 20 180 28
P150-110 188 8 6-8 20 180 28
PO150 188 8 6-8 20 180 28
PO150-110 188 8 6-8 20 180 28
PO150 HP - - 6-8 20 180 - PO150 HP - PO150-110 HP (Hi Perfs with clamping rods)
PO150-110 HP - - 6-8 20 180 -
Installation
• Weight (indicative) :
- P150 and PO150: 3kg
- P150-110 and PO150-110 : 4kg
• Maximum torque:
- secondary terminals M5 : 2.5 N.m
- split-core tightening screws M5 : 2.5 N.m
- tightening rod nuts M4: 3.5 N.m
• Before closing the split-core CT, make sure of the perfect cleanliness of the contact
surfaces. It is advisable to wipe the surface of the magnetic circuit with a cloth
soaked in vaseline oil.
• In the case of clamping rods, tighten the 4 off M4 threaded rods gradually, and
diagonally, in order to have a an even clamping.
• Warning ! Never install a split-core CT on a live primary conductor. Unless you use
the terminals to short circuit the secondary (optional)
• Caution! Never leave the secondary circuit open while the primary conductor is
energized. High voltages might surge at secondary terminals, which might be
hazardous to people and destroy the current transformer. Unless you use a voltage
limiter device (see datasheet M2MA index 17)
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2CD/4a
LOW VOLTAGE INSTRUMENT TRANSFORMERS
. Indoor Use / Outdoor Use IP54 . Silicon steel core with Hi-grade
copper winding
. Rugged Design
. Self-extinguishing cast Resin . Immune to weather conditions 8
with sealing gasket between both
. Relay Class up to C600 parts of split-core
. Metering Class down to 0.3
. Fixing bracket for ease of
. Primary current from 50 to installing
6000A
. Secondary current 1 or 5A . Secondary Cover IP54 for
. Custom primary & secondary outdoor use
current available upon request
. Sealable secondary cover for
. No need to dismantle primary indoor use
to install over existing busbar
or cable . Multi-ratio
Dimensions
Type Weight A B C D E F G H I J K L
lbs in in in in in in in in in in in in
TCO165 60 6,5” 2,55” 13,38” 9,25” 5,7” 3,34” 1,97” 7,80” 4,92” 5,9” 5,7” 9,25”
TCO280 TBC 11” 4” TBC TBC TBC TBC TBC TBC TBC TBC TBC TBC
100/5A - 2.4 - - - C2
Installation
• Never install CT on live voltage. Always make sure line is OFF.
• Never leave secondary circuit open when energized.
• Before tightening the 4 screws, make sure that the contact surfaces of the magnetic core are clean.
It is advisable to clean the surface of magnetic circuit with an oiled cloth.
• Tighten the 4 screws progressively and in diagonal in order to ensure a uniform pressure on magnetic core.
• Maximum tightening torque : 1/4 “ tightening screws : 1.5 ft.lbf
1/4 “ secondary inserts : 1.8 ft.lbf
5/16 “ fixing inserts : 3.5 ft.lbf
3/16 “ cover inserts : 1.5 ft.lbf
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 50 to 60 000 A
Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Indoor or outdoor Rated output 1 to 500 VA
• Primary current from 50 to 60 000 A Accuracy class 0.5 - 1 - 3
• Inner diameter from 106 mm to 500 mm Security factor 5 to 30
• Measurement and protection Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FN/14
« BUSHING » CURRENT TRANSFORMERS - B SERIES B series
M6 secondary terminals , M8 for B450 - B455
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FN/14
LOW VOLTAGE INSTRUMENT TRANSFORMERS
JFD
Technical data
Accessories / Options
The outdoor version is equipped
with a weatherproof terminal box Sealable cover for secondary terminal (IP20) Option
fitted with 2 cable glands.
S1-S2 on P1 or P2 side Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET: M2FM/7
“ BUSHING ” CURRENT TRANSFORMERS - J..FD.. SERIES
Selection table
Ip Type Rated output Ip Type Rated output
A Max VA A Max VA
cl 3 cl 1 cl 0,5 cl 3 cl 1 cl 0,5
<450 J1FD-1 50 20 10 <5000 J1FD-1 350 350 350
J1FD-2 200 120 40 J1FD-2 350 350 350
J1FD-3 350 200 75 J1FD-3 350 350 350
J1FD-4 350 300 115 J1FD-4 350 350 350
J2FD-1 50 25 10 J2FD-1 350 350 350
J2FD-2 150 75 25 J2FD-2 350 350 350
J2FD-3 300 140 50 J2FD-3 350 350 350
J2FD-4 350 220 75 J2FD-4 350 350 350
J3FD-1 25 15 5 J3FD-1 350 350 350
J3FD-2 120 45 15 J3FD-2 350 350 350
J3FD-3 220 90 25 J3FD-3 350 350 350
J3FD-4 300 125 45 J3FD-4 350 350 350
J4FD-2 120 45 15 J4FD-2 350 350 350
J4FD-3 250 90 30 J4FD-3 350 350 350
J5FD-2 75 20 7.5 J5FD-2 350 350 350
J7FD-2 350 175 60 J7FD-2 350 350 350
<11000 J1FD-1 300 200 150
J1FD-2 350 350 300
J1FD-3 350 350 350
J1FD-4 350 350 350
J2FD-1 200 125 100
J2FD-2 350 350 275
J2FD-3 350 350 350
J2FD-4 350 350 350
J3FD-1 100 75 50
J3FD-2 300 250 150
J3FD-3 350 350 280
J3FD-4 350 350 300
J4FD-2 300 300 150 Installation
Max tightening torques :
J4FD-3 350 350 200
- M6 terminals: 4 N.m
J5FD-2 200 150 75
J7FD-2 350 350 350
Dimensions
Type Weight ØA ØB ØC ØD E (depending on type) G H ØJ
1 2 3 4
kg mm mm mm mm mm mm mm mm mm mm mm
J1FD-1..4 25 200 476 440 14 60 100 150 200 493 60 400
J2FD-1..4 23 230 476 440 14 60 100 150 200 493 60 400
J3FD-1..4 21 260 476 440 14 60 100 150 200 493 60 400
J4FD-1..4 30 300 531 486 12 - 100 160 - 545 60 453
J5FD-1..4 28 330 531 486 12 - 100 - - 545 60 453
J7FD-2 75 400 786 750 12 - 125 - - 800 60 710
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FM/7
LOW VOLTAGE INSTRUMENT TRANSFORMERS
10
JACO
Technical data
Accessories / Options
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FK/4
current TRANSFORMERS - jaco SERIE
JACO
S1
S2
OA
OB
H
Dimensions according to customer’s needs :
Installation
• Installing theses CT’s may require implementing special
supporting fixings on existing structures.
• Warning ! Never leave open the secondary cicuit of a
current transformer when fed on primary. High voltage
may surge at the secondary circuit terminals and might be
dangerous for people, and lead to the destruction of the
current transformer.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FK/4
LOW VOLTAGE INSTRUMENT TRANSFORMERS
10
CEB J20FB1
Technical data
Accessories / Options
Secondary cables According to client request
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FJ/8
WRAPPED CURRENT TRANSFORMERS ASSEMBLIES CEB - J20FB1 SERIES
CEB
J20FB1
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2FJ/8
LOW VOLTAGE INSTRUMENT TRANSFORMERS
11
MB 2P - 2M - 2G
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 1 to 600 A
Secondary current Isn 1A
• Primary current from 1 to 600 A Frequency 50 or 60 Hz
• Compact size Continuous thermal current 1.2 Ipn
Short-time thermal current Ith up to 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
These transformers have been designed to Case Thermoplastic UL94 V0
be associated with differential thermal re- Standards IEC - IEEE - CSA - AS - BS
lays such as LR1, LR2, or LT6 from Telemeca-
nique for motor protection. Other characteristics on request
Highest voltage for equipment 1200 V
They have a set saturation curve, depen- Power-frequency withstand voltage 6000 V
ding on the relay and whether 2 or 3 CTs Ambient temperature - 40°C to +70°C
are fitted and on the motor starting time.
Secondary current 5A
Due to their compact size, they are par-
ticularly suitable for withdrawable Motor
Control Centers. Accessories / Options
Mounting brackets EA type
They are compatible with Schneider Elec-
Sealable terminal cover (IP20) Only on 1PB - RB - PB models
tric relays:
Tropicalization
- MIU 21 - 16
- MIU 21 - 64
- MIU 22 - 16
- MIU 22 - 64
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FA/8
CURRENT TRANSFORMERS FOR THERMAL RELAYS
Selection guide
Relay Burden 3 CTs assembly 2 CTs assembly
short start long start short start long start
MB - GB with EA type brackets
LR1 - LR2 or similar 2Ω S 11 S 12 S 13 S 14
B Screw TC ∅ J F
LT6 S 17 S 17 - - D
S1 S2
In motor Ip S 11 S 12 S 13 S 14 S 17
C P1
from... to...(A) A Type model Type model Type model Type model Type model
0.65 - 0.90 1 S11 - 1 MB S 12 - 1 MB S 13 - 1 GB S 14 - 1 MB - - M
G E A
0.95 - 1.27 1.5 S11 - 1.5 MB S12 - 1.5 MB S13 - 1.5 GB S14 - 1.5 MB - -
H
1.26 - 1,70 2 S11 - 2 MB S12 - 2 MB S13 - 2 GB S14 - 2 MB - -
1.65 - 2.12 2.5 S11 - 2.5 MB S12 - 2.5 MB S13 - 2.5 GB S14 - 2.5 MB - - P
L ∅I
1.89 - 2.55 3 S11 - 3 MB S12 - 3 MB S13 - 3 GB S14 - 3 MB - - K E
N A
2.52 - 3.40 4 S11 - 4 MB S12 - 4 MB S13 - 4 GB S14 - 4 MB - -
3.25 - 4.25 5 S11 - 5 MB S12 - 5 MB S13 - 5 GB S14 - 5 MB - -
3.90 - 5.10 6 S11 - 6 MB S12 - 6 MB S13 - 6 GB S14 - 6 MB - -
4.87 - 6.40 7.5 S11 - 7.5 MB S12 - 7.5 MB S13 - 7.5 GB S14 - 7.5 MB - -
6.40 - 8.50 10 S11 - 10 MB S12 - 10 MB S13 - 10 GB S14 - 10 MB - -
2P - 2M - 2G with EA type brackets
8.15 - 10.50 12.5 S11 - 12.5 MB S12 - 12.5 MB S13 - 12.5 GB S14 - 12.5 MB - -
10.40 - 13.60 16 S11 - 16 MB S12 - 16 MB S13 - 16 GB S14 - 16 MB - - B Screw TC∅ J F
D
44
Dimensions S1 S2
Model A B C D E F G H I J K L M N P C
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm M
1P 58 27 45 25 48 16 15 8.5 4.2 M 5 36 23 84 - 4 G P1 E A
GB 66 52 43 47 55 25 17 M 8 4.2 M 5 35 23 80 64 3.5
In In In In In In
Installation
S1 S1 S1 S1 S1 In In In In In In
• M5 secondary terminal tightening torque = 2.5Nm
S2 S2 S2 S2 S2 S1 S1
M8 primary
P2 terminal
P2 tightening
P2 torque = 9 Nm P2 P2 S1 S1 S1
S2 S2 S2 S2 S2
P2 P2 P2 P2 P2
• For an efficient motor protection, it is recommended to use the 3 CTs assembly. When the rated current
is above 600A, use 2 CTs: the first on a busbar with 5A secondary current which will supply power to
a S11-5 or a S12-5.The thermal relay, associated to this range of CTs, can be located at any distance 3 CTs assembly 2 CTs assembly
from the motor.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FA/8
LOW VOLTAGE INSTRUMENT TRANSFORMERS
12
PBT P80ST
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 5A
Secondary current Isn 5A
• Summation of 2 to 12 currents Frequency 50 or 60 Hz
• Insulation 0.72/3 kV Rated output 1 to 60 VA
• Measurement and protection Accuracy class 0.5 - 1 - 3
Security factor 5 to 30
• Adaptability, modularity
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Case Thermoplastic UL94 HB or V0
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Mounting brackets EN type
Strengthened mounting brackets EB type on P80ST model
Tropicalization
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2HA/7
summation current transformers - PBT - P80ST series
42 + A
∅ 6,3
86
15 56 + A
M5 35
15
S1 S2
M5 P1
25
116
25
A 35
66 + A 104
44 + A
137 ∅ 6,3
16 60 + A
A 30
S1 S2
M5
M5
23 P1
157,5
23
23
60
66 + A 155
Installation
• Never short-circuit unused primary windings.
• Dimension A = 0 as standard and may vary according to specifications
• Max lightening torque : 2Nm on secondary terminals and on M5 primary terminals.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2HA/7
LOW VOLTAGE INSTRUMENT TRANSFORMERS
12
PBA
P80SA
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary current Ipn 5A
Secondary current Isn 5A
• Switching of 2 to 12 currents Frequency 50 or 60 Hz
• Insulation 0.72/3 kV Rated output 1 to 60 VA
Accuracy class 0.5 - 1 - 3
• Measurement and protection
Security factor 5 to 30
• Adaptability, modularity
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Case Thermoplastic UL94 HB or V0
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Mounting brackets EN type
Strengthened mounting brackets EB type on P80SA model
Tropicalization
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2HB/2
PBA - P80SA SERIES SWITCHING CURRENT TRANSFORMERS
42 + A
∅ 6,3
86
15 56 + A
M5 35
15
S1 S2
M5 P1
25
116
25
A 35
66 + A 104
44 + A
137 ∅ 6,3
16 60 + A
A 30
S1 S2
M5
M5
23 P1
157,5
23
23
60
66 + A 155
Installation
• Never short-circuit unused primary windings.
• Dimension A = 0 as standard and may vary according to specifications
• Max lightening torque : 2Nm on secondary terminals and on M5 primary terminals.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2HB/2
LOW VOLTAGE INSTRUMENT TRANSFORMERS - Application note
13
P150
B198 TA470
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
• Network current from 1 to 4,000A
Netwok current Ipn 1 to 4,000 A
• Windows size from 33 x 23 mm
Secondary current Isn 0.005 to 10 A
to Ø
450 mm Frequency 50 or 60 Hz
• Indoor or outdoor installation Continuous thermal current 1.2 Ipn
depending on model Short-time thermal current Ith 80 Ipn.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to +40 °C
CBCT’s, also known as zero-sequence Case Thermoplastic or polyurethane
Standards IEC - IEEE - CSA - AS - BS
transformers, are used for earth lea-
kage and earth fault protection.
Other characteristics on request
The three phase cables or single phase Highest voltage for equipment Up to 2400 V
cable pass through the transformer. Power-frequency withstand voltage Up to 11 kV
In the absence of default, no current Knee voltage Ek <10 to 100V
flows in the secondary. In case of earth Resistance of the secondary winding <0.1 to 10 Ohms
fault, the residual current flows through Ambient temperature -40 °C to +70 °C
the secondary of the CBCT and trips
the earth fault protection of the relay. Accessories / Options
See transformers datasheets www.rsisolsec.com
Our zero-sequence transformers are
Secondary shunt bracket To install split-core CTs
adaptable to all market relays.
Outdoor / split-core According to datasheets of each type
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2MZ/4
Core balance CURRENT TRANSFORMERS - application note
To precisely define the core balance current transformer you need, our engineers are available:
Installation
• Warning ! Never install a split-core CT on a live primary conductor. Unless you use the terminals to short
circuit the secondary (optional)
• Caution! Never leave the secondary circuit open while the primary conductor is energized. High voltages
might surge at secondary terminals, which might be hazardous to people and destroy the current
transformer. Unless you use a voltage limiter device (see datasheet M2MA index 17)
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2MZ/4
LOW VOLTAGE INSTRUMENT TRANSFORMERS
14
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV (1kV for W serie)
Primary voltage Upn 10 to 90 V
• Indoor Secondary voltage Usn 100: √3 - 110: √3 - 100 - 110 V
• Primary voltage up to 2000V Frequency 50 or 60 Hz
• Measurement and protection Rated output 5 VA to 25 kVA
Accuracy class 0.5 - 1 - 3 - Cl A
• Robust design, with
Thermal power Up to 25 kVA
unbreakable bushing insulators
Insulation class E
Terminal protection IP00
Ambient temperature -25 °C to +40 °C
Normes IEC - IEEE - CSA - AS - BS
Accessories / Options
Sealable terminal cover (IP20)
Primary/Secondary shield
Tropicalization
With flying leads on primary and secon-
dary side
Primary or secondary protection TP 150-W series
Primary switch TP 150-W series
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2JA/10
SINGLE PHASE VOLTAGE TRANSFORMERS - tp series
B A
Selection table TP84 … TP180
B A
Type Burden Thermal output C
maximum en VA maximum in VA
C
cl 3 cl 1 cl 0.5 cl 0.2 cl A
TP84-1 15 - - - 50
E ∅F D
TP84-2 30 5 - - 60
TP108-1 75 30 20 - 100
E ∅F D
TP108-2 150 50 30 - 150
TP126-1 250 80 50 5 250
TP126-2 300 100 60 5 300
TP150-1 400 120 70 10 400 TP232
TP150-2 600 240 150 15 600
TP150-3 700 300 200 40 700 B A
TP150-W4 - - - - 5000
TP150-W1 - TP150-W2 - TP150-W3
TP150-W5 - - - - 6000
TP150-W6 - - - - 7500
TP150-W7 - - - - 10000 Cosse
2
TP150-W8 - - - - 12500 Tôle du capot
TP150-W9 - - - - 15000 de protection du
C
1 Cosse
2 transformateur
TP150-W10 - - - - 20000 Borne Tôle du capot
de protection du
TP150-W11 - - - - 25000 isolante
1
transformateur
Borne B A
isolante
F
D
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2JA/10
SINGLE PHASE VOLTAGE TRANSFORMERS - tp series
Dimensions
Type Weight A B C D E F
kg mm mm mm mm mm mm
TP84-1 2.3 115 99 90 54 84 5.5
TP84-2 2.4 130 99 90 67 84 5.5
TP108-1 3.6 124 124 113 70 108 6
TP108-2 4.5 137 124 107 82 108 6
TP126-1 6.2 150 142 124 82 126 6
TP126-2 7.2 160 142 124 93 126 6
TP150-1 8 156 167 138 84 150 7
TP150-2 11 185 167 138 116 150 7 B A
E ∅F D
Installation
Cable lug
When tightening connections, it is essential to block nut 1 when nut 2 is tightened to 2
avoid breaking the winding wire underneath.
Max tightening torque for secondary terminal : 5 N.m 1
Transformer metal
body
Insulating
bushing
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2JA/10
SINGLE PHASE VOLTAGE TRANSFORMERS - tp series
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2JA/10
LOW VOLTAGE INSTRUMENT TRANSFORMERS
14
TPN96 - open terminal lid
TPN96
Technical data
Rated insulation 0.72/3 kV
Primary voltage 10 to 400 V
Secondary voltage 100 / √3 - 110 / √3 - 100 - 110 V
Frequency 50 or 60 Hz
• For indoor, outdoor and wet Rated output 5 VA to 80 VA
environments Accuracy class 0.2 - 0.5 - 1 - 3 - cl A
• Primary voltage up to 1200V Thermal power Up to 250 VA
• Measurement and protection Voltage factor 1.2 Un permanent
• Tropicalized Insulation class E
Live terminal Terminal blocks with screw connectors
Earth terminal Terminal block with screw connectors
Terminal protection IP40 with cover lid
Rated output -25°C to + 40°C
Norm IEC - IEEE - CSA - AS - BS
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2JB/3
SINGLE PHASE VOLTAGE TRANSFORMERS - tpN series
Selection table
cl 3 cl 1 cl 0.5 cl 0.2 cl A
TPN96 60 20 15 5 75 4kg
TPN120 200 100 50 15 250 6kg
TPN96 TPN120
24,25 64 31,5 85 8O
132
115
172
150
5,5 23,5
4,5
138 172,8
Terminal blocks with
Raccordements screwetconnection
primaire secondaire
par blocs de jonction à vis
89
109,5
Membrane
Passe fil àgrommet
membraneforpour
maxcâble
9mm
outside dia cable
O extérieur max 9mm
Installation Marking :
Connections to terminal blocks with screw connectors :
Primary : A-B Phase - Phase
• Solid conductor min 0.2 mm2 A-N Phase - Ground
2
• Solid conductor max 6 mm
• Stranded conductor min 0.2 mm2 Secondary : a-b Phase- Phase
2
a-n Phase - Ground
• Stranded conductor max: 6 mm da-dn Tertiary winding
• Conductor Stripping length : 8 mm
• Thread of the terminal blocks clamping screw: M3
• Torque: 0.6 to 0.8 Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2JB/3
LOW VOLTAGE INSTRUMENT TRANSFORMERS
15
OTC2
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Primary voltage Upn 100 to 660 V
• Indoor Secondary voltage Usn 100: √3 - 110: √3 - 100 - 110 V
• Primary voltage up to 2000V Frequency 50 or 60 Hz
• Air-type construction Rated output 3 x 2.5 VA to 3 x 150 VA
Accuracy class 0.5 - 1 - 3
Thermal power Up to 4 kVA
Insulation class E
Ambient temperature -25 °C to +40 °C
Standards IEC - IEEE - CSA - AS - BS
Accessories / Options
Shield
star
Vector group triangle,
neutral out
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2JN/6
THREE PHASE VOLTAGE TRANSFORMERS
Selection table
OTC 1 … OT 3
Dimensions
D ∅F E
Type Weight A B C D E F
kg mm mm mm mm mm mm
OTC1 3 135 157 130 80 85 6 OW1...OW7
OTC2 5.5 125 210 148 75 120 6
OTC3 9 133 245 178 80 145 7
OW1 41 121 240 215 86 210 10
OT1 10 132 245 185 90 175 7
OW2 41 131 240 215 96 210 10
OT2 15 152 245 185 100 175 7
C
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2JN/6
OTHER LOW VOLTAGE EQUIPMENT
S10 S100 16
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
• Indoor Frequency 50 or 60 Hz
• Capacitor banks up to 220 kVar Continuous thermal current 1.2 Ipn
under 380 V Short-time thermal current Ith 40 Ipn.1s
• Without magnetic core Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25 °C to + 40 °C
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2KN/9
SERIES REACTORS
Capacitor Us Type A B D E G H I K L M N
kVAr V mm mm mm mm mm mm mm mm mm mm mm mm
7.5 380 SS 7.5 104 60 56 86 17 M8 6.3 66 42 112 4
10 380 SS 10 104 60 56 86 17 M8 6.3 66 42 112 4
15 380 SS 15 104 60 56 86 17 M8 6.3 66 42 112 4
20 380 SS 20 104 60 56 86 17 M8 6.3 66 42 112 4
25 380 SS 25 104 60 56 86 17 M8 6.3 66 42 112 4
30 380 SS 30 104 60 56 86 17 M8 6.3 66 42 112 4
40 380 SS 40 104 60 56 86 17 M8 6.3 66 42 112 4
50 380 SS 50 104 60 56 86 17 M8 6.3 66 42 112 4
60 380 SS 60 104 70 66 86 17 M8 6.3 76 52 112 4
70 380 SS 70 104 88 76 86 25 M 12 6.3 86 62 112 4
75 380 SS 75 104 88 76 86 25 M 12 6.3 86 62 112 4
80 380 SS 80 155 93 81 137 25 M 12 6.3 91 69 155 5
90 380 SS 90 155 93 81 137 25 M 12 6.3 91 69 155 5
100 380 SS 100 155 93 81 137 25 M 12 6.3 91 69 155 5
120 380 SS 120 155 93 81 137 25 M 12 6.3 91 69 155 5
160 380 SS 160 155 105.5 93.5 137 25 M 12 6.3 103.5 81.5 155 5
200 380 SS 200 155 130.5 118.5 137 25 M 12 6.3 128.5 106.5 155 5
• Dimensions B,D,K,L can vary according to electrical performance (spacer)
Capacitor Us Type A B D E G H I K L M N
kVAr V mm mm mm mm mm mm mm mm mm mm mm mm
7,5 220 S 7.5 104 60 56 86 17 M8 6.3 66 42 112 4
10 220 S 10 104 60 56 86 17 M8 6.3 66 42 112 4
15 220 S 15 104 60 56 86 17 M8 6.3 66 42 112 4
20 220 S 20 104 60 56 86 17 M8 6.3 66 42 112 4
25 220 S 25 104 60 56 86 17 M8 6.3 66 42 112 4
30 220 S 30 104 78 66 86 25 M 12 6.3 76 52 112 4
40 220 S 40 104 78 66 86 25 M 12 6.3 76 52 112 4
50 220 S 50 104 78 66 86 25 M 12 6.3 76 52 112 4
60 220 S 60 104 93 81 86 25 M 12 6.3 91 67 112 4
70 220 S 70 104 93 81 86 25 M 12 6.3 91 67 112 4
75 220 S 75 104 103 91 86 25 M 12 6.3 101 77 112 4
80 220 S 80 104 103 91 86 25 M 12 6.3 101 77 112 4
90 220 S 90 155 105.5 93.5 137 25 M 12 6.3 103.5 81.5 155 5
100 220 S 100 155 105.5 93.5 137 25 M 12 6.3 103.5 81.5 155 5
120 220 S 120 155 130.5 118.5 137 25 M 12 6.3 128.5 106.5 155 5
• Dimensions B,D,K,L can vary according to electrical performance (spacer)
B
D
M E
N ∅I
L E
K A
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET: M2KN/9
LV EQUIPMENT
17
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2MA/7
VOLTAGE LIMITER - VFS SERIES
Type A B C
+/-2mm +/-3mm mm (mini)
VFS 90 25 40 50
VFS 200 25 40 50
VFS 450 30 65 70
VFS 600 40 75 80
VFS 1500 60 95 100
Installation
• The VFS limiter shall be directly connected to the secondary terminals of the current transformer.
• Suitable lead terminals have to be used
• No additional fixing device is required
• The VFS limiter can be connected in any direction
• Short-circuit the secondary terminals of the current transformer before replacing the VFS limiter.
• The limiter must be disconnected before applying dielectric tests above the nominal value.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2MA/7
LOW VOLTAGE INSTRUMENT TRANFORMER ON EXTRA HIGH VOLTAGE
ORFE 1000-80-1200
18
ORFE 275-75-440
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Rated primary current Ipn 50 to 10 000 A
• Indoor or outdoor
Rated secondary current Isn 5 or 1 A
•Inner Ø from 165 up to 1000 mm Rated frequency 50 Hz or 60 Hz
• Up to 4 cores Network nominal voltage 0.75 - 20 - 72.5 - 100 - 245 -... to 1000kV
•Any protection class Rated output Up to 500 VA
•Adaptability, modularity Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
Accuracy factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current 80 Ipn
Dynamic current Idyn 2.5 Ith
These ring type current transformers Inner diameter 165 to 1000 mm
are available for indoor or outdoor Ambient temperature -25°C to + 40°C
use. They have been designed to Insulation material Cast resin
meet the requirements for metering Insulation class E
and protection duties of :
Fixing clamps Galvanized steel
- power transformers and auto-trans-
formers Standards IEC - IEEE - CSA - AS - BS
- HV or MV wall bushings
Other characteristics on request
- GIS substation
- IPB Highest voltage for equipment 2 kV
- Homopolar detection in neutral Power-frequency withstand voltage 6 kV
connections Multi-ratio By secondary tapping
Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
The secondary terminals are acces- Ambient temperature - 40°C to + 70°C
sible either directly in the case of
indoor equipment (ORF) or through a Accessories / Options
watertight terminal box or a watertight Watertight terminal box with cable gland Supplied on outdoor ORFE serie
plastic cover (ORFE or ORF - - - W) IP43 Optional on indoor ORF
in the case of outdoor application. Watertight plastic cover IP54 As standard on outdoor ORFE ......W
Optional on indoor ORF
As per customer’s requirement, se-
Fixing clamps Stainless steel on request
condary windings can integrate time
Earth terminal On request
constant constraints.
Voltage limiter On request
Filtering capacitor On request
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2FP/5
CURRENT TRANSFORMER - ORF SERIES
Ø 11.5 à 18mm
Ø 11.5 à 18mm
Model ØA ØB C R ά Weight H
mm mm mm mm ° kg mm
ORF 165-75-330 165 330 350 195 30 20 75
ORF 165-75-360 165 360 380 210 30 20 75
ORF 210-75-400 210 400 420 230 45 20 75
ORF 240-75-400 240 400 420 230 45 20 75
ORF 240-75-440 240 440 460 250 45 30 75
ORF 260-75-440 260 440 460 250 45 30 75
ORF 260-75-490 260 490 510 275 45 40 75
ORF 275-75-440 275 440 460 250 45 20 75
ORF 275-75-490 275 490 510 275 45 30 75
ORF 300-75-490 300 490 510 275 45 30 75
ORF 300-75-520 300 520 540 290 45 40 75
ORF 350-75-520 350 520 540 290 45 30 75
ORFE ORF 390-75-610 390 610 630 335 45 40 75
Position of the fixing brackets along R axis ORF 450-75-610 450 610 630 335 45 40 75
ORF 450-75-690 450 690 710 375 45 50 75
ORF 505-75-690 505 690 710 375 45 40 75
ORF 550-75-730 550 730 750 395 45 50 75
ORF 550-75-800 550 800 820 430 45 70 75
ORF 258-80-360 258 360 380 420 30 15 80
ORF 258-120-360 258 360 380 420 30 25 120
ORF 165-120-330 165 330 350 195 30 30 120
ORF 165-120-360 165 360 380 210 30 30 120
ORF 210-120-400 210 400 420 230 45 40 120
ORF 240-120-400 240 400 420 230 45 30 120
ORF 240-120-440 240 440 460 250 45 50 120
ORF 260-120-440 260 440 460 250 45 40 120
ORF 260-120-490 260 490 510 275 45 60 120
ORF 275-120-440 275 440 460 250 45 40 120
ORF 275-120-490 275 490 510 275 45 50 120
ORF 300-120-490 300 490 510 275 45 50 120
ORF 300-120-520 300 520 540 290 45 60 120
ORF 350-120-520 350 520 540 290 45 50 120
ORF 390-120-610 390 610 630 335 45 70 120
ORF 450-120-610 450 610 630 335 45 60 120
ORF 450-120-690 450 690 710 335 45 80 120
ORF 505-120-690 505 690 710 375 45 60 120
ORF 550-120-730 550 730 750 395 45 80 120
ORF 550-120-800 550 800 820 430 45 110 120
ORF 165-180-330 165 330 350 195 30 40 180
ORF 165-180-360 165 360 380 210 30 50 180
ORF 210-180-400 210 400 420 230 45 60 180
ORF 240-180-400 240 400 420 230 45 50 180
ORF 240-180-440 240 440 460 250 45 70 180
ORF 260-180-440 260 440 460 250 45 60 180
ORF 260-180-490 260 490 510 275 45 90 180
ORF 275-180-440 275 440 460 250 45 60 180
Fixing brackets supplied on request ORF 275-180-490 275 490 510 275 45 80 180
ORF 300-180-490 300 490 510 275 45 70 180
ORF 300-180-520 300 520 540 290 45 90 180
ORF 350-180-520 350 520 540 290 45 80 180
ORF 390-180-610 390 610 630 335 45 110 180
ORF 450-180-610 450 610 630 335 45 90 180
ORF 450-180-690 450 690 710 375 45 130 180
ORF 505-180-690 505 690 710 375 45 100 180
ORF 550-180-730 550 730 750 395 45 120 180
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2FP/5
CURRENT TRANSFORMER - ORF SERIES
Breather
11.5 à 18mm
11.5 to 18mm
Model ØA ØB C R Weight H
mm mm mm mm kg mm
ORF 315-80-480 315 480 500 270 35 80
ORF 315-80-600 315 600 620 330 65 80
ORF 450-80-600 450 600 620 330 35 80 18
ORF 450-80-720 450 720 740 390 85 80
ORF 550-80-720 550 720 740 390 50 80
ORF 700-80-860 700 860 880 460 55 80
ORF 715-80-980 715 980 1000 520 120 80
ORF 1000-80-1300 1000 1300 1320 680 180 80
Position of the fixing brackets along R axis ORFE ORF 315-120-480 315 480 500 270 55 120
ORF 315-120-600 315 600 620 330 120 120
ORF 450-120-600 450 600 620 330 60 120
ORF 450-120-720 450 720 740 390 145 120
ORF 550-120-720 550 720 740 390 85 120
ORF 700-120-860 700 860 880 460 95 120
ORF 715-120-980 715 980 1000 520 200 120
ORF 1000-120-1300 1000 1300 1320 680 310 120
ORF 315-180-480 315 480 500 270 85 180
ORF 315-180-600 315 600 620 330 190 180
ORF 450-180-600 450 600 620 330 95 180
ORF 450-180-720 450 720 740 390 230 180
ORF 550-180-720 550 720 740 390 140 180
ORF 700-180-860 700 860 880 460 150 180
ORF 715-180-980 715 980 1000 520 320 180
ORF 1000-180-1300 1000 1300 1320 680 500 180
Presse-étoupe Pg21
câbleO11,5-18mm
100 Maxi
LV terminals M8
Joint Néoprène
Rubber seal
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2FP/5
Low voltage instrument transformers on EXTRA high voltage
18
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
Rated primary current Ipn 50 to 4000 A
Rated secondary current Isn 5 or 1 A
• Indoor or outdoor Rated frequency 50 Hz or 60 Hz
•Inner Ø from 53 up to 250 mm Network nominal voltage 0.75 - 20 - 72.5 - 100 - 245 - ... - 1000kV
• Up to 4 secondary cores Rated output Up to 500 VA
•Any protection class Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
• Modularity, wide range Accuracy limit factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current 80 Ipn
Dynamic current Idyn 2.5 Ith
Inner diameter 53 to 250 mm
Ambient temperature -25°C to + 40°C
Insulation material Cast resin
Insulation class E
These ring type current transformers are
available for indoor or outdoor use. They Base plate or fixing brackets U-shape brackets - galvanized steel
have been designed to meet the requi- Standards IEC - IEEE - CSA - AS - BS
rements for measuring:
Other characteristics on request
- line currents Highest voltage for equipment 2 kV
- zero-sequence currents in the neutral of Power-frequency withstand voltage 6 kV
power transformers
Multi-ratio by secondary tapping
- earth fault currents in power transfor-
Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
mers.
Ambient temperature - 40°C to + 70°C
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2GM/11
CURRENT TRAnsformerS - ORX series
Dimensions
ORX Weight ØH A B C D E F G I
kg mm mm mm mm mm mm mm mm mm
100 Maxi
175-180-450 135 175 505 450 180 250 110 14 265 20 LV terminals M8
175-230-450 175 175 505 450 230 250 150 14 265 20
175-260-450 200 175 505 450 260 250 180 14 265 20 Joint Néoprène
175-80-480 60 175 550 480 80 250 55 14 285 20 Rubber seal
175-105-480 80 175 550 480 105 250 55 14 285 20
175-130-480 105 175 550 480 130 250 80 14 285 20
175-180-480 155 175 550 480 180 250 110 14 285 20
175-230-480 205 175 550 480 230 250 150 14 285 20
175-260-480 235 175 550 480 260 250 180 14 285 20
210-80-380 30 210 435 380 80 250 55 14 225 20
210-105-380 40 210 435 380 105 250 55 14 225 20
210-130-380 55 210 435 380 130 250 80 14 225 20
210-180-380 75 210 435 380 180 250 110 14 225 20
210-230-380 100 210 435 380 230 250 150 14 225 20
210-260-380 115 210 435 380 260 250 180 14 225 20
210-80-450 45 210 505 450 80 250 55 14 265 20
210-105-450 65 210 505 450 105 250 55 14 265 20
210-130-450 85 210 505 450 130 250 80 14 265 20
210-180-450 120 210 505 450 180 250 110 14 265 20
Detailed drawings available on request:
210-230-450 160 210 505 450 230 250 150 14 265 20
- terminal box
210-260-450 180 210 505 450 260 250 180 14 265 20
- overall dimensions
210-80-480 55 210 550 480 80 250 55 14 285 20
- name plate
210-105-480 75 210 550 480 105 250 55 14 285 20
- wiring diagram
210-130-480 100 210 550 480 130 250 80 14 285 20
210-180-480 140 210 550 480 180 250 110 14 285 20
Installation
210-230-480 190 210 550 480 230 250 150 14 285 20
• These current transformers are designed to fit over :
210-260-480 215 210 550 480 260 250 180 14 285 20
– LV bare conductors
250-80-450 40 250 505 450 80 250 55 14 265 20
– LV, HV, EHV insulated cables
250-105-450 55 250 505 450 105 250 55 14 265 20
250-130-450 70 250 505 450 130 250 80 14 265 20 - • Cantilever installation of current
- transformers
- may require additionalDate:
Dess.: N.G.
fixing
01/08/2013
250-180-450 100 250 505 450 180 250 110 14 265 20 - supports on the existing equipment.
- -
MODIFICATIONS Date Ind. Vérif.: C.P. Ech: 2/1
250-230-450 135 250 505 450 230 250 150 14 265 20 • Tightening torque for secondary terminals M8
Désignation : Embout pour tige de contact : 7 Nm.
Matière: Alliage de Tungstène CUTENE 120WI
45, Aven
451
250-260-450 155 250 505 450 260 250 180 14 265 20 Format: A4 tél: +33.(0)2.38.85.6
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2GM/11
LOW VOLTAGE INSTRUMENT TRANFORMER ON EXTRA HIGH VOLTAGE
18
ORBE DAYA BAY
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
• Indoor or outdoor Rated primary current Ipn 50 to 10 000 A
•Inner diameter from 240 Rated secondary current Isn 5 or 1 A
up to 690 mm Rated frequency 50 Hz or 60 Hz
• Up to 4 cores Network nominal voltage 0.75 - 20 - 72.5 - 100 - 245 -... to 1000kV
Rated output Up to 500 VA
•Any protection class
Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
Accuracy factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
These ring type current transformers are Short-time thermal current 80 Ipn
available for indoor (ORB) or outdoor Dynamic current Idyn 2.5 Ith
use (ORBE). They have been designed Inner diameter 240 to 690 mm
to meet the requirements for metering
Ambient temperature -25°C to + 40°C
and protection duties of :
Insulation material Cast resin
- power transformers and auto-trans-
formers Insulation class E
- HV or MV wall bushings Standards IEC - IEEE - CSA - AS - BS
- GIS substation Other characteristics on request
- IPB
Highest voltage for equipment 2 kV
- Homopolar detection in neutral
Power-frequency withstand voltage 6 kV
connections
Multi-ratio By secondary tapping
The secondary terminals are accessible Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
either directly in the case of indoor Ambient temperature - 40°C to + 70°C
equipment (ORB) or through a water-
tight terminal box or cover in the case
Accessories / Options
of outdoor application (ORBE - ORBE Watertight terminal box or cover with cable Supplied on outdoor ORBE series
- - W). gland (IP43) Optional on indoor ORB
Watertight plastic cover (IP54) As standard on outdoor ORBE... W
Optional on indoor ORB
As per customer’s requirement, se-
condary windings can integrate time Fixing clamps On request
constant constraints. Earth terminal On request
Voltage limiter On request
Filtering capacitor On request
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FR/5
CURRENT TRANSFORMER - ORB SERIES
ORBE
Presse-étoupe
Borne BT M6 Cable gland
LV terminals M6 Boîte à bornes
LV terminals box Model ØA ØB C Weight H
Borne de mise à la terre M8 mm mm mm kg mm
Earthing terminal M8 ORB 240-80-410 240 410 445 25 80
ORB 372-80-550 372 550 625 35 80
OB -100
ORB 372-80-630 372 630 665 65 80
ORB 565-80-740 565 740 815 53 80
ORB 565-80-820 565 820 855 85 80
ORB 690-80-830 690 830 865 150 80
+10 +5 ORB 690-80-900 690 900 935 175 80
OA 0 C -10
ORB 240-110-410 240 410 445 40 110
ORB 372-110-550 372 550 625 55 110
ORB 372-110-630 372 630 665 100 110
ORB 565-110-740 565 740 815 80 110
ORB 565-110-820 565 820 855 135 110
ORB 530-130-720 530 720 805 90 130
ORB 240-140-410 240 410 445 50 140
ORB 372-140-550 372 550 625 75 140
ORB 372-140-630 372 630 665 135 140
H ±5 ORB 565-140-740 565 740 815 106 140
ORB 565-140-820 565 820 855 185 140
ORB 240-170-410 240 410 445 65 170
ORB 372-170-550 372 550 625 100 170
Option «Watertight plastic cover» (mounted instead of the watertight terminal box) ORB 372-170-630 372 630 665 175 170
orBE - - - W Presse-étoupe Pg21
câbleO11,5-18mm
ORB 565-170-740 565 740 815 133 170
ORB 565-170-820 565 820 855 235 170
Boîtier plastique Presse-étoupe Pg11 ORB 690-170-1010 690 1015 1050 350 170
Plastic cover câbleO6-10mm
Cable glands ORB 240-200-410 240 410 445 75 200
Borne BT M8 ORB 372-200-550 372 550 625 120 200
100 Maxi
LV terminals M8
ORB 372-200-630 372 630 665 210 200
•C
aution ! Never leave the secondary circuit open while the primary conductor is
energized. High voltages might surge at secondary terminals, which might be
hazardous for people and destroy the current transformer.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FR/5
- - -
LOW VOLTAGE INSTRUMENT TRANSFORMERS
CRE
19
Technical data
Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
•Split-core current transformers for Rated primary current Ipn 200 to 20 000 A
indoor or outdoor use Rated secondary current Isn 5 or 1 A
Rated frequency 50 or 60 Hz
•Large inner diameters up to Ø 690 mm
Rated output Up to 100 VA
•Until two cores
Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
•Any protection class Accuracy factor 5 - 10 - 15 - 20 - 30
•Easier to install Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 Ipn
Dynamic current Idyn 2.5 Ith
Insulation class E
The change to newer, faster and more Ambient temperature - 25°C to + 40°C
selective protective system makes it Insulation material Cast resin
necessary to replace existing current Standard IEC - IEEE - CSA - AS - BS
transformers with different output, class,
ratio, number of secondaries to suit the Other characteristics on request
needs of the new protection.
Highest voltage for equipment 2 kV
The best solution is to use split-core Power-frequency withstand voltage 6 kV
current transformers on insulated cables Multi-ratio By secondary tapping
or outside single phase metalclad units. Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
This solution is very economical because Ambient temperature - 40°C to + 70°C
- It is not necessary to dismantle and
remake the cable sealing ends on the Accessories / Options
metalclad units. Watertight secondary terminal box As standard on outdoor CRE
- There is no need to recommission and Optional on indoor CR
test the main equipment. Watertight plastic cover As standard on outdoor CRE...W
- It reduces the risk of damage and the Optional on indoor CR
length of outages at reduced costs. Earth terminal On request
Filtering capacitor On request
These current transformers are avalaible Voltage limitor On request
for indoor use (CR) or for outdoor use
(CRE - CRE - - W).
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET: M2GS/10
SPLIT-CORE Current transformer - cr SERIES
Dimensions
Model Weight Ø A B C D E ØF G H I
kg mm mm mm mm mm mm mm mm mm mm
CRE 372 - xxx - 750
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2GS/10
SPLIT-CORE Current transformer - cr SERIES
Option «Watertight plastic cover» (mounted instead of the watertight terminal box)
CrE - - - W Presse-étoupe Pg21
câbleO11,5-18mm
Cable glands
Boîtier plastique Presse-étoupe Pg11
Plastic cover câbleO6-10mm
Cable glands
Borne BT M8
100 Maxi
LV terminals M8
Joint Néoprène
Rubber seal
19
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2GS/10
SPLIT-CORE Current transformer - cr SERIES
©RS ISOLSEC PAGE 4/4 contact: [email protected] - information non contractuelle - DATASHEET : M2GS/10
LOW VOLTAGE INSTRUMENT TRANSFORMERS
19
CRFE 200-220-550
Technical data
•Split-core current transformers Highest voltage for equipment 0.72 kV
for indoor or outdoor use Power-frequency withstand voltage 3 kV
•Up to 2 cores Rated primary current Ipn 200 to 20000 A
Rated secondary current Isn 5 or 1 A
•Any protection class
Rated frequency 50 or 60 Hz
• Easier to install
Rated output Up to 100 VA
Accuracy class 0.2 - 0.2S - 0.5 - 0.5S - 1 - 5P - 10P
Accuracy limit factor 5 - 10 - 15 - 20 - 30
The change to newer, faster and more Continuous thermal current 1.2 Ipn
selective protective system makes it Short-time thermal current Ith 80 Ipn
necessary to replace existing current Dynamic current Idyn 2.5 Ith
transformers with different output, Insulation class E
class, ratio, number of secondaries to Ambient temperature - 25°C to + 40°C
suit the needs of the new protection. Insulation material Cast resin
Standard IEC - IEEE - CSA - AS - BS
The best solution is to use split-core
current transformers on insulated Other characteristics on request
cables or outside single phase
metalclad units. Highest voltage for equipment 2 kV
This solution is very economical Power-frequency withstand voltage 6 kV
because Multi-ratio By secondary tapping
- It is not necessary to dismantle and Accuracy class PX, PXR, PR, TPS, TPX, TPY, TPZ
remake the cable sealing ends on Ambient temperature - 40°C to + 70°C
the metalclad units.
- There is no need to recommission and Accessories / Options
test the main equipment. Watertight secondary terminal box (IP43) As standard on outdoor CRFE
- It reduces the risk of damage and the Optional on indoor CRF
length of outages at reduced costs. Watertight plastic cover (IP54) As standard on outdoor CRFE ...W
Optional on indoor CRF
Earth terminal On request
These current transformers are
Filtering capacitor On request
avalaible for indoor use (CRF) or
Voltage limitor On request
outdoor use (CRFE - CRFE - - W).
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2GU/8
SPLIT-CORE Current transformer - crF SERIES
Dimensions
Model Weight Ø A B C D E ØF G H I J K
kg mm mm mm mm mm mm mm mm mm mm mm mm
CRF 60-260-370 90 60 320 370 260 50 150 10 262 160 - 75 -
CRF 140-90-400 30 140 450 460 90 50 55 12 - 235 - 75 -
CRF 140-150-400 50 140 450 460 150 50 90 12 - 235 - 75 -
CRF 200-150-550 130 200 590 640 150 50 300 12 600 295 30 160 140
CRF 200-170-550 160 200 590 640 170 50 300 12 600 295 30 160 140
CRF 200-220-550 200 200 590 640 220 50 300 12 600 295 30 160 140
CRF 200-260-550 240 200 590 640 260 50 300 12 600 295 30 160 140
Note : CFRE 175-145-400 see Notice M1GS CRE 175-145-460
M8
75 maxi OF
O
J
A E
H
G C D
B
CRFE 60-260-370
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2GU/8
SPLIT-CORE Current transformer - crF SERIES
Option «Watertight plastic cover» (mounted instead of the watertight terminal box)
CrfE - - - W
Presse-étoupe Pg21
câbleO11,5-18mm
Cable glands
Boîtier plastique Presse-étoupe Pg11
Plastic cover câbleO6-10mm
Cable glands
Borne BT M8
100 Maxi
LV terminals M8
Joint Néoprène
Rubber seal
Installation
Page:
• Tightening torque for secondary terminals M8
Embout : 7 NmTige
pour . de Contact .010813. - 1/1
• Caution ! Never install a split-core CT while the primary conductor is energized.
• Caution ! Never leave the secondary circuit open while the primary conductor is energized. High voltages might surge at secondary
terminals, which might be hazardous for people and destroy the current transformer.
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2GU/8
SPLIT-CORE Current transformer - crF SERIES
©RS ISOLSEC PAGE 4/4 contact: [email protected] - information non contractuelle - DATASHEET : M2GU/8
LOW VOLTAGE INSTRUMENT TRANSFORMER ON EXTRA HIGH VOLTAGE
ABUH ABUM
20
Technical data
•RTE Specifications Highest voltage for equipement 0.72 kV
•Outdoor use Power-frequency withstand voltage 3 kV
•Thermoset resin Primary current Ipn 500 to 3000 A
•Measuring, differential protection, Secondary current Isn 5 or 1 A
Frequency 50 Hz
or HV outgoing protection.
Network nominal voltage 20 - 72.5 - 100 - 245 - 420kV
Accuracy class 0.5 - 5PR15 - 5PR20 - 5P15 - TPY
Ring core Toroidal
These Current Transformers have been Short time thermal current Ith 2 to 63 kA
designed and developed in close colla- Dynamic current Idyn 5 to 171 kA
boration with RTE, the French Electricity Idenner window diameter 280 à 1000 mm
Transmission Network, to match the most
Ambient Temperature -25°C to + 40°C
stringent requirements of outdoor subs-
Insulation material Cast resin
tations.
Weatherproof terminal cover (IP43) Vent, M8 earth terminal
- Their « window type » design makes Fixing tabs Galvanized steel
it possible to install them under Extra Reference standart RTE - CNER - DP - MHT - 13 - 00008
High Voltage (EHV) environment taking
advantage of the insulation of primary
(cable, GIS busducts, wall bushing...). Accessories / Options
Fixing tabs Stainless steel upon request
- They can also be equipped with a filter Filter capacitor By construction on ABUA-B-D-E-F-G-H-S-T-U
capacitor to limit the high frequency vol- Voltage limiter By construction ABUR- ABUS
tage peaks appearing during connect/
disconnect cycles, or in case of fault on
the network.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2FQ/10
current transformerS for BUSHINGs - ABU series
ABUZ - - Offshore wind connecting PDIF 4000/1 5VA CL5P10 ORFE 315-80-440 315 80 440 500 460 75 20
G maxi
D
18
30°
A
45°
C
B
Detailed drawings available upon request :
- terminal box
- overall dimensions
- name plate
- connections sketch
Installation
• Installing these CT’s may require implementing special supporting fixings
on existing structures.
• Thightening torque of secondary terminal M8 : 7 Nm.
• Never leave open the secondary cicuit of a current transformer when fed
on primary. High voltage may surge at the secondary circuit terminals and
might be dangerous for people, and lead to the destruction of the current
transformer. The voltage limiter device available as option for 1A secondary
CT’s enables users to avoid such risk.
©RS ISOLSEC
PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2FQ/10
LOW VOLTAGE INSTRUMENT TRANFORMER ON EXTRA HIGH VOLTAGE
ATOQ ATOY
20
Technical data
•O
utdoor use Highest voltage for equipment 0.72 kV
Power-frequency withstand voltage 3 kV
•T
oroidal or split-core type
Primary current Ipn 100 to 3000 A
• Specification RTE (French Electricity
Secondary current Isn 5 or 1 A
Transmission System Operator) Frequency 50 Hz
•C
ast in thermoset resin Network nominal voltage 20 - 72.5 - 100 - 245 - 420kV
•M
easuring, differential protection, Accuracy class 0.5 - 5PR10 - 5PR20 - 5P20 - 5P30 - 10P30
or HV outgoing protection TPY
Ring core Toroidal except for following split-core models
ATOY - ATOD - ATOZ - ATOX-O
Short time thermal current Ith 2 to 63 kA
Dynamic current Idyn 5 to 171 kA
These Current Transformers have been Inner window diameter 140 to 200 mm
designed and developed in close colla- Ambient Temperature -25°C to + 40°C
boration with RTE, the French Electricity Insulation material Cast resin
Network, to match the most stringent Weatherproof terminal cover (IP43) Vent, M8 earth terminal
requirements of outdoor substations. Reference standard RTE CNER - DP - MHT - 13 - 00008
CEI/ CdcT 61869-2
- Their «window type» design makes
it possible to install them under Extra Accessories / Options
High Voltage (EHV) environment taking Fixing brackets Advisable if cantilever installed
advantage of the insulation of primary
Filter capacitor By construction on ATOA - ATOY - ATOX - ATOX-O
(cable, GIS busducts, wall bushing, …)
Voltage limiter By construction on ATOA - ATOY - ATOX - ATOX-O
- CT’s with ref ATOA - ATOY - ATOX -
ATOX-O for outgoing differential protec-
tion are equipped with a filter capacitor
to limit the high frequency voltage peaks
showing during connect/disconnect
cycles, or in case of fault on the network,
and of a voltage limiter protecting CT
against overvoltage in case of secon-
dary open circuit.
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2GL/12
CURRENT TRANSFORMER for cables - ATO SERIES
ATOO Tank protection of TR 400/MT Transformer for thermal gen MAX I 1000/1 15VA cl 10P30
sets
ATOP Transformer Neutral protection for thermal gen sets MAX I 1500/1 15VA cl 5P20
ATOQ 554921 7030078 Transformer Neutral protection for TR 225 et 400 kV MAX I 1500/5 20VA cl 5P20
6455733
ATOR Cable shield earth fault protection for 225 and 400 kV MAX I 100/1 10VA cl 5P20
ATOS Cable shield earth fault protection 225 and 400 kV Neutre MV MAX I 100/5 15VA cl 5P20
Auxiliary
ATOT 554924 7030079 Outgoing 225 kV with underground cable of open type substation PD 1000/5 50VA cl 5PR20
or GIS substation ME21 500/5 50VA cl 5PR20
ATOU 554925 7030080 Outgoing 225 kV with underground cable of open type nearby PD 1500/5 50VA cl 5PR20
substation or GIS substation ME21 1000/5 50VA cl 5PR20
ATOW 554926 7030081 90 kV Neutral protection TR225/90 and 90/MT Transformer MAX I 250/5 30VA cl 5P 20
63 kV Neutral protection for 63 kV Neutral and 63/MT Transformer
Tank protection TPN 63 kV Neutral Point Transformer
63 and 90 kV Cable shield earth fault protection
Tank protection for 90/MT and 63/MT of distribution substations
ATOX 575810 Outgoing 400 kV with underground cable PDI 3000/1 5VA cl 5P 20 TPY
ATOX-0 554927 Outgoing 400 kV with underground cable PD TPY 3000/1 5VA cl 5P 20 TPY
ATOY 554928 7030082 Underground cable for outgoing 225 kV of open type distant PD TPY 1500/1 10VA cl 5P20 TPY
substation
ATOZ 565768 7030083 Underground cable for 225 kV outgoing of open type distant PD 1500/5 50VA cl 5PR 20
substation ME21 1000/5 50VA cl 5PR 20
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2GL/12
CURRENT TRANSFORMER for cables - ATO SERIES
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2GL/12
CURRENT TRANSFORMER for cables - ATO SERIES
G maxi
F
A
I
D E
4 4holes
trous J
C B
ATO Series
G maxi
4 anneaux
4 lifting ears
deM10
levage M10
44 holes
trous J
160
F E
A
140
H
D I
C B
F
OA
H 50 maxi
Installation
• Installing these CT’s may require implementing special supporting fixings on existing structures
• Tightening torque of secondary terminals M8 : 7 Nm.
• Attention ! Never install a split-core CT while primary conductor is with live voltage
• Never leave open the secondary circuit of a current transformer when fed on primary. High voltage may
surge at the secondary circuit terminals, and might be dangerous for people, and lead to the destruction of
the current transformer.
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2GL/12
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
CB131-A1
Technical data 21
Rated insulation level 7.2/20/60 kV to 36/70/170 kV
• Indoor Primary current Ipn Up to 3000 A
• 7.2 - 12 - 17.5 - 24 - 36 kV Secondary current Isn 5 or 1 A
• Primary current from 0 to 3000 A Frequency 50 or 60 Hz
• Ith up to 1000 Ipn or 100 kA.1s Rated output 1 to 100 VA
• Compact size Accuracy class 1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P - clPX
• Cast-resin insulated Security factor 5 to 10
• Low level of partial discharges Accuracy limit factor 5 - 10 - 15 - 20 - 30
• Up to 5 cores Continuous thermal current 1.2 Ipn
• Screw-in connectors Short-time thermal current Ith Up to 1000 Ipn or 100 kA.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25°C to + 40°C
Current transformers vacuum
moulded in self extinguishing Mounting Brackets
epoxy resin for the measu- Standards IEC - IEEE - CSA - AS - BS
rement of AC currents up to
3000A. This comprehensive and Other characteristics on request
compact range of current transfor- Power frequency withstand voltage Up to 75 kV
mers has been designed to meet the Secondary current Isn 0.005 to 10 A
requirements of MV switchgear Double ratio 5-10 to 600-1200A by primary change-over
manufacturers. Multiple cores Up to 5 cores
Ambient temperature - 40°C to + 70°C
It offers a very low level of partial
discharges. Accessories / Options
Mounting No bracket
It allows double-ratio up to 600- Strenghtened brackets
1200A via primary coupling and up ACEO base plate
to 5 independent secondary win- Sealable terminal cover (IP20)
dings.
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2PA/11
wound primary CURRENT TRANSFORMERS - CB SERIES
4 x
CB110 12/28/75 10 220 148 150 128 72
CB111 12/28/75 12 220 148 190 128 104
CB112 12/28/75 14 220 148 250 128 138
CB113 12/28/75 16 220 148 300 128 188
CB114 12/28/75 12 220 148 350 128 238
CB120 12/28/75 12 220 158 150 128 72 4x
CB131 17.5/38/95 16 220 178 190 128 104
CB132 17.5/38/95 21 220 178 250 128 138
CB133 17.5/38/95 24 220 178 300 128 188
CB134 17.5/38/95 29 220 178 350 128 238
CB220 24/50/125 14 250 158 150 128 72
CB231 24/50/125 19 250 178 190 128 104
CB232 24/50/125 23 250 178 250 128 138
CB233 24/50/125 28 250 178 300 128 188
CB234 24/50/125 30 250 178 350 128 238
CB241 24/50/125 19 250 198 190 128 104 Secondary terminals M6
CB242 24/50/125 24 250 198 250 128 138
CB243 24/50/125 29 250 198 300 128 188
Tetons blocking
CB244 24/50/125 34 250 198 350 128 238
CB252 24/50/125 26 250 228 250 128 138
CB253 24/50/125 32 250 228 300 128 188
CB254 24/50/125 36 250 228 350 128 238
CB430 36/70/170 19 360 178 150 128 72
CB431 36/70/170 24 360 178 190 128 104 CB xxx-A1
CB432 36/70/170 30 360 178 250 128 138
CB433 36/70/170 35 360 178 300 128 188
CB434 36/70/170 41 360 178 350 128 238 - - -
Dess : N.G.. Date : 02/2013
- - - RS ISOLSEC
CB441 36/70/170 26 360 198 190 128 104
MODIFICATIONS Date Ind. Vérif : C.P. Ech : 1:5
45 , Avenue des Acacias
Désignation : CB catalogue Matière : 45120 CEPOY
Diffusion : - Format : A3 tél : 33.(0)2.38.85.62.62 fax : 33.(0)2.38.85.62.05
CB443 36/70/170 37 360 198 300 128 188 Primary terminals: M12 with 23mm useful depth
CB444 36/70/170 43 360 198 350 128 238 Tightening torque for primary terminals: 50Nm
CB451 36/70/170 28 360 228 190 128 104 Tightening torque for secondary terminals: 2Nm
CB452 36/70/170 34 360 228 250 128 138
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2PA/11
wound primary CURRENT TRANSFORMERS - CB SERIES
40
32
C F
32
21
A1 A2 A4 B1 B2
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2PA/11
wound primary CURRENT TRANSFORMERS - CB SERIES
JBQ
JBD
JBP
JBR
21
Technical data
Rated insulation level 7.2/20/60 kV to 24/50/125 kV
Primary current Ipn Up to 2500 A
• Indoor
Secondary current Isn 5 or 1 A
• 7.2 - 12 - 17.5 - 24 kV Frequency 50 or 60 Hz
• Primary current from 0 to 2500 A Rated output 1 to 100 VA
• Ith up to 1000 Ipn or 100kA.1s Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P
• Compact size 10P - CLX - CLPX
Security factor From 5 to 10
• Dry insulation in epoxy resin
Accuracy limit factor 5 - 10 - 15 - 20 - 30
• Up to 4 independent cores
Continuous thermal current 1,2 Ipn
• Maintenance free Short-time thermal current Ith Up to 1000 Ipn or 100 kA.1s
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Current transformers vacuum moulded
in self-extinguishing epoxy resin for the Other characteristics on request
measure of AC currents from 0 up to Power-frequency withstand voltage Up to 75 kV
2500A. Double ratio 5-10 to 600-1200A by primary change-over
Secondary current Isn 0.005 to 10 A
This comprehensive and compact range Continuous thermal current 1.5 Ipn - 2 Ipn
of current transformers has been Multiple cores Up to 4
designed to meet the requirements of Ambient temperature -25°C to + 70°C
MV switchgear manufacturers.
Accessories / Options
It allows for double ratios up to 600-1200A,
and offers up to 4 independent cores. Fixing plate Standard
Surface finish Polyurethan or Silicone coating
Sealable cover for secondary terminal (IP31) Standard
Earth connector Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2PB/6
WOUND PRIMARY CURRENT TRANSFORMERS - J..B.. 24KV SERIES
JBD-JBM-JBP-JBR-JBQ
Selection table and dimensions Primary terminals
Type Un Weight A B C D E Ip Single ratio primary Double ratio primary
Up to (kV.) kg mm mm mm mm mm Type Up to Up to Up to Up to
0...600A 600...1250A 1250...2500A
300-600A 300-600A 600-1200A 600-1200A
J7BD 7.2/20/60 14 265 175 200 130 140
C F F F F F F F
J7BM 7.2/20/60 17 265 175 200 130 140 mm mm mm mm mm mm mm mm
J7BP 7.2/20/60 20 265 175 230 130 140 JBD 200 80 - - 80 - - -
JBP
JBD
JBM
JBQ
JBR
Installation
- This current transformer can be fixed in any position.
- Tightening torque for primary terminals 35 N.m
- Primary terminals M12x23 useful depth.
- Tightening torque for secondary terminals : M6 :4 N.m
- Never leave the secondary circuit of a current transformer open when voltage is applied to
the transformer. High voltages may appear at the secondary circuit terminals
which can be dangerous to personnel and may result in the destruction of the current
transformer.
- This current transformer is maintenance free.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2PB/6
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
JBY
JBT
JBX
Technical data 21
Rated insulation level 7.2/20/60 kV to 36/70/170 kV
Primary current Ipn Up to 2500 A
Secondary current Isn 5 or 1 A
• Indoor
Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 - 24 - 36kV Rated output 1 to 100 VA
• Primary current from 0 to 2500 A Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P
• Ith up to 1000 Ipn or 100kA.1s 10P - CLX - CLPX
• Compact size Security factor From 5 to 10
Accuracy limit factor 5 - 10 - 15 - 20 - 30
• Dry insulation in epoxy resin
Continuous thermal current 1.2 Ipn
• Up to 4 independent cores
Short-time thermal current Ith Up to 1000 Ipn or 100 kA.1s
• Maintenance free
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2PC/5
WOUND PRIMARY CURRENT TRANSFORMERS - J..B.. 36KV SERIES
JBT-JBX-JBY
Selection table and dimensions Primary terminals
Type Un Weight A B C D E Type Ip Single ration primary Double ratio primary
Up to (kV.) kg mm mm mm mm mm 0...600A 600...1250A 1250...2500A Up to Up to Up to Up to
300-600A 300-600A 600-1200A 600-1200A
J7BT 7.2/20/60 21 352 190 200 130 140
C F F F F F F F
J7BX 7.2/20/60 41 360 230 270 150 280 mm mm mm mm mm mm mm mm
J7BY 7.2/20/60 67 360 230 375 150 330 JBT 200 80 - - 80 - - -
J12BT 12/28/75 21 352 190 200 130 140 JBX 270 120 120 120 - 120 - 120
JBY 375 120 120 120 - 120 - 120
J12BX 12/28/75 41 360 230 270 150 280
A1 A2 A3 B1 B2 B3 B4
J12BY 12/28/75 67 360 230 375 150 330
J17BT 17.5/38/95 21 352 190 200 130 140
J17BX 17.5/38/95 41 360 230 270 150 280
J17BY 17.5/38/95 67 360 230 375 150 330
J24BT 24/50/125 21 352 190 200 130 140
J24BX 24/50/125 41 360 230 270 150 280
J24BY 24/50/125 67 360 230 375 150 330
J36BT 36/70/170 21 352 190 200 130 140
J36BX 36/70/170 41 360 230 270 150 280
J36BY 36/70/170 67 360 230 375 150 330
Installation
- This current transformer can be fixed in any position.
- Tightening torque for primary terminals 35 N.m
- Primary terminals M12x23 useful depth.
- Tightening torque for secondary terminals : M6 :4 N.m
- Never leave the secondary circuit of a current transformer
JBT open when voltage is applied to the transformer. High
voltages may appear at the secondary circuit terminals
which can be dangerous to personnel and may result in the
destruction of the current transformer.
- This current transformer is maintenance free.
JBY
JBX
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2PC/5
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
T30E
Technical data
Rated insulation level 7.2/20/60 kV to 36/70/170 kV
22
Primary current Ipn 0 to 600 A
Secondary current Isn 5 or 1 A
• Outdoor Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 - 24 - 36 kV Rated output 1 to 60 VA
• Primary current up to 600 A Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P - clX
Accuracy limit factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 to 200 Ipn
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25° C to + 40 °C
Standards IEC - IEEE - CSA - AS - BS
Outdoor current transformers
vacuum moulded in self extin-
guishing epoxy resin for the Other characteristics on request
measurement of AC currents
Secondary current Isn 0.005 to 10 A
up to 600A.
Double ratio Secondary tapping for T24E model
Primary change-over for T30E model
They are equipped with a
Multiple cores Up to 2 separate cores
weatherproof terminal box
Ambient temperature - 40° C to + 70 °C
fitted with 2 cable glands.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2QA/6
OUTDOOR CURRENT TRANSFORMERS SERIES T24E - T30E - RC15E - RC36E - RC306E
T24E - T30E
E B
G M12X20
M12X20
∅F
P1 P2
D
C
S1 S2
∅L
K H
A M6 secondary J
Sortiesterminals
secondaires
M6
∅A B
C
P1
∅F
S1 S2
G
∅L
K H
Sorties secondaires
M6 J
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2QA/6
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
JCD JCY
JCV
Technical data
22
Rated insulation level 7.2/20/60 kV to 52/95/250 kV
• Outdoor Primary current Ipn Up to 2500 A
• 7.2 - 12 - 17.5 - 24 - 36 - 52kV Secondary current Isn 5 or 1 A
• Primary current from 0 to 2500 A Frequency 50 or 60 Hz
Rated output 1 to 100 VA
• Ith up to 1000 Ipn or 100kA.1s
Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P
• Dry insulation in epoxy resin 10P - CLX - CLPX
• Up to 4 independent cores Security factor From 5 to 10
• Maintenance free Accuracy limit factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith Up to 1000 Ipn or 100 kA.1s
Dynamic current Idyn 2.5 Ith
Surface finish Polyurethan coating
Insulation class E
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
Current transformers vacuum moulded
in self extinguishing epoxy resin for the Other characteristics on request
measure of AC currents from 0 up to Power-frequency withstand voltage Up to 75 kV
2500A. Double ratio 5-10 to 600-1200A by primary change-over
Secondary current Isn 0.005 to 10 A
This comprehensive and compact
Accuracy class CL TPS
range of current transformers has been
Continuous thermal current 1.5 Ipn - 2 Ipn
designed to meet the requirements of
Multiple cores Up to 4
MV switchgear manufacturers.
Ambient temperature - 25°C to + 70°C
It allows for double ratios up to 600- Accessories / Options
1200 A, and offers up to 4 independent
cores. Fixing plate Standard
Surface finish Silicone coating
Sealable cover for secondary terminal (IP65) Standard
Earth connector Option
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2QC/6
OUTDOOR CURRENT TRANSFORMER - J..C.. SERIES
JCD
Selection table and dimensions
Type Un Weight A ØB C D E Creep.
Up to (kV.) kg mm mm mm mm mm mm
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2QC/6
OUTDOOR CURRENT TRANSFORMER - J..C.. SERIES
Primary terminals
22
Secondary tap
Installation
- This current transformer can be fixed in any position.
- Tightening torque for primary terminals 35 N.m
- Primary terminals M12x23 useful depth.
- Tightening torque for secondary terminals : M6 :4 N.m
- Never leave the secondary circuit of a current transformer open when voltage is applied to
the transformer. High voltages may appear at the secondary circuit terminals, which can be
dangerous to personnel and may result in the destruction of the current transformer.
- This current transformer is maintenance free.
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2QC/6
OUTDOOR CURRENT TRANSFORMER - J..C.. SERIES
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2QC/6
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
T36E
Technical data
Rated insulation level 7.2/20/60 kV to 36/70/170 kV
22
• Outdoor Primary current Ipn Up to 1200 A
• 7.2 - 12 - 17.5 - 24 - 36 kV Secondary current Isn 5 or 1 A
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2QB/3
OUTDOOR CURRENT TRANSFORMERS - T36E SERIES
Installation
Never leave open the secondary circuit when voltage is on.
Tightening torque for primary terminals : 30 Nm.
Tightening torque for secondary terminals : 5 Nm.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2QB/3
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
HT350
Technical data
Rated insulation level 7.2/20/60 kV to 24/50/125 kV
• Indoor 23
Primary current Ipn 100 to 30000 A
• 7.2 - 12 - 17.5 - 24 kV
Secondary current Isn 5 or 1 A
• Primary current from 100 to 30000 A
Frequency 50 or 60 Hz
• Cast resin insulated Rated output 1 to 1000 VA
• Inner diameter from 165 to 800 mm Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P -CLX
• Ith Up to 1000 Ipn Accuracy limit factor 5 - 10 - 15 - 20 - 30 - 50
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 to 1000 Ipn
Dynamic current Idyn 2.5 Ith
Current transformers vacuum moulded Insulation class E
in self extinguishing epoxy resin for the
HV primary screen (see installation) Standard on all transformers
measurement of AC currents from 100
Ambient temperature - 25°C to + 40°C
to 30000A.
Standards IEC - IEEE - CSA - AS - BS
This range of transformers is suitable
for power generation. They have Other characteristics on request
been designed to be installed in Rated insulation level 25/50/150 kV
bus ducts between generator and Secondary current 0.005 to 10 A
transformer. Multiple cores Up to 3 separate cores
Ambient temperature - 40°C to + 70°C
They allow very high performances.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2OC/7
BAR OR CABLE PRIMARY CURRENT TRANSFORMERS - HT SERIES
Type Un Weight A B C D E H φ°
kV Kg mm mm mm mm mm mm
HT 165 A 24/50/125 120 634 165 604 653 166 166 60°
HT 165 B 24/50/125 130 634 165 604 653 166 190 60°
HT 165 C 24/50/125 140 634 165 604 653 166 230 60°
HT 165 D 24/50/125 145 634 165 604 653 166 300 60°
HT 165.200 24/50/125 130 634 200 604 653 166 190 60°
HT 296.200A 24/50/125 80 596 200 476 610 135 135 45°
HT 296.200B 24/50/125 110 596 200 476 610 135 250 45°
HT 165.230 24/50/125 120 634 230 604 653 166 190 60°
HT 296.250 24/50/125 60 596 250 476 610 135 135 45°
HT 296 17.5/38/95 55 596 296 476 610 135 135 45°
HT 350A 24/50/125 53 733 350 640 750 110 110 45°
HT 350B 24/50/125 86 733 350 640 750 110 160 45°
HT 384 24/50/125 120 794 384 704 800 161 161 60°
HT 420 24/50/125 55 800 420 640 815 110 110 60°
HT 421 24/50/125 70 800 420 640 815 110 120 60°
HT 470 24/50/125 130 880 470 780 892 155 155 60°
HT 600 A 24/50/125 100 1007 600 840 1015 82 122 60°
HT 600 B 24/50/125 140 1007 600 1015 1026 122 207 60°
HT 800 24/50/125 120 1210 800 1062 1214 130 130 60°
M6 secondary terminals
øD
øB
Shield M8x4
Fixings M16x20
øC
H
E
E /2
Installation
• Useful depth of M16 inserts = 20mm
• The HV primary screen must be connected to the busbar by a flexible connection.
• The fixing fittings on the outer diameter must allow for transformer expansion.
• Tightening torque
terminal M6 : 2 N.m
terminal M8 : 4 N.m
terminal M16 : 18 N.m
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2OC/7
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
RC13 RC16
Technical data
Rated insulation level 7.2/20/60 kV to 24/50/125 kV
23
Primary current Ipn 50 to 12000 A
Secondary current Isn 5 or 1 A
Frequency 50 or 60 Hz
• Indoor
Rated output 1 to 100 VA
• 7.2 - 12 - 17.5 - 24 kV
Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P - clX
• Primary current from 50 to 12000 A
Accuracy limit factor 5 - 10 - 15 - 20 - 30
• Ith up to 1000 Ipn or 100 kA.1s
Continuous thermal current 1.2 Ipn
• Cast-resin insulated
Short-time thermal current Ith 80 to 1000 Ipn
• Up to 4 separate cores.
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25 °C to + 40 °C
Standards IEC - IEEE - CSA - AS - BS
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2OA/7
BAR OR CABLE PRIMARY CURRENT TRANSFORMERS - RC SERIES
Type Un Weight A B C D E F G H J K L
kV kg mm mm mm mm mm mm mm mm mm mm mm
RC5 12/28/75 17 230 190 140 185 300 106 35 25 135 115 155
RC12 17.5/38/95 27 304 210 140 225 377 180 35 30 160 115 155
RC13 17.5/38/95 36 304 210 140 225 377 130 35 30 160 115 155
RC13-100 17.5/38/95 36 304 210 140 225 377 100 35 30 160 115 155
RC14 17.5/38/95 33 304 210 140 225 377 140 35 30 160 115 155
RC15 17.5/38/95 18 230 210 140 265 380 106 45 40 135 115 155
RC16 24/50/125 22 254 210 140 293 420 130 40 25 135 115 160
RC17-106 24/50/125 66 346 240 160 335 508 105 40 30 160 120 160
RC17 24/50/125 60 346 240 160 335 508 130 50 30 160 120 160
RC20 24/50/125 85 425 240 180 395 610 200 40 25 165 180 220
RC21 24/50/125 75 425 240 180 395 610 250 40 25 165 180 220
OA B
C
P1
FilEquipotential
de l'écran de mise
au screen
potentiel wire
(option)
OF
J
M6 secondary
Sorties secondaires M6
terminals
S1 S2
G
H O 8
K 180
L 220
Installation
• At 24kV, it is advisable to use a round primary conductor, with a maximum diameter of
100 mm, and centered in the window. A bar may be used provided that its edges are rounded.
• When equipped with, the HV primary screen wire must be connected to the HV busbar.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2OA/7
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
TA3P-7 TA301-7
Technical data
Rated insulation level 7.2/20/60 kV to 17.5/38/95 kV
rimary current Ipn 40 to 8000 A
Secondary current Isn 5 or 1 A
23
• Indoor Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 kV Rated output 1 to 100 VA
• Primary current from 40 to 8000A Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P - clX
• Ith up to 600 Ipn Accuracy limit factor 5 - 10 - 15 - 20 - 30
• Low cost range Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 40 to 600 Ipn
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature -25 °C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
Dimensions Up to 500mm maximum.
Current transformers for the mea- Specific dimension indicated on the offer.
surement of AC currents from 40 to
Other characteristics on request
8000A.
Secondary current Isn 0.005 to 10 A
This low cost range combines a low Double ratio By secondary tapping
voltage current transformer and an Multiple cores Up to 2 separate cores
insulating epoxy tube. Ambient temperature -40 °C to +70 °C
Accessories / Options
Mounting brackets
Sealable terminal cover
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2OB/10
BAR OR CABLE PRIMARY CURRENT TRANSFORMERS TA301-7 ~ p80-17 series
Selection table
Ip Type Output Ip Type Output Ip Type Output
A maximum VA A
maximum VA A
maximum VA
7.2 kV 12 kV 17.5 kV cl 3 cl 1 cl 0.5 7.2 kV 12 kV 17.5 kV cl 3 cl 1 cl 0.5 7.2 kV 12 kV 17.5 kV cl 3 cl 1 cl 0.5
40 TA3P-7 TA3P-7 TA3P-17 5 - - 300 TA3P-7 TA3P-7 TA3P-17 60 60 45 1250 P80-7 P80-7 P80-17 60 60 45
P80-7 P80-7 P80-17 2.5 - - P80-7 P80-7 P80-17 45 30 15 TA301-7 TA301-7 TA301-17 60 60 45
50 TA3P-7 TA3P-7 TA3P-17 5 1.25 - TA301-7 TA301-7 TA301-17 30 20 15 TA321-7 TA321-7 TA321-17 60 60 45
P80-7 P80-7 P80-17 2.5 - - TA321-7 TA321-7 TA321-17 30 15 10 TA34-7 TA34-7 TA34-17 60 60 60
TA34-7 TA34-7 TA34-17 30 20 10 TA312-7 TA312-7 TA312-17 60 60 60
60 TA3P-7 TA3P-7 TA3P-17 10 2.5 - TA316-7 TA316-7 - 60 60 60
P80-7 P80-7 P80-17 5 1.25 - 400 TA3P-7 TA3P-7 TA3P-17 60 60 60
P80-7 P80-7 P80-17 60 45 20 1500 P80-7 P80-7 P80-17 60 60 45
75 TA3P-7 TA3P-7 TA3P-17 15 3.75 - TA301-7 TA301-7 TA301-17 60 60 45
P80-7 P80-7 P80-17 5 2.5 - TA301-7 TA301-7 TA301-17 60 30 20
TA321-7 TA321-7 TA321-17 45 30 20 TA321-7 TA321-7 TA321-17 60 45 45
100 TA3P-7 TA3P-7 TA3P-17 20 10 5 TA34-7 TA34-7 TA34-17 45 20 15 TA34-7 TA34-7 TA34-17 60 60 60
P80-7 P80-7 P80-17 15 3.75 1.25 TA316-7 TA316-7 60 30 30 TA312-7 TA312-7 TA312-17 60 60 60
TA301-7 TA301-7 TA301-17 10 1.25 - TA316-7 TA316-7 - 60 60 60
TA321-7 TA321-7 TA321-17 10 2.5 - 500 TA3P-7 TA3P-7 TA3P-17 60 60 60
P80-7 P80-7 P80-17 60 60 45 2000 P80-7 P80-7 P80-17 60 60 45
TA34-7 TA34-7 TA34-17 10 1.25 - TA34-7 TA34-7 TA34-17 60 60 60
TA301-7 TA301-7 TA301-17 60 45 30
125 TA3P-7 TA3P-7 TA3P-17 30 10 5 TA312-7 TA312-7 TA312-17 60 60 60
TA321-7 TA321-7 TA321-17 45 30 20 TA316-7 TA316-7 - 60 60 60
P80-7 P80-7 P80-17 20 5 2.5
TA34-7 TA34-7 TA34-17 60 45 30
TA301-7 TA301-7 TA301-17 15 5 - 2500 TA34-7 TA34-7 TA34-17 60 60 60
TA316-7 TA316-7 60 45 30
TA321-7 TA321-7 TA321-17 15 3.75 - TA312-7 TA312-7 TA312-17 60 60 60
TA34-7 TA34-7 TA34-17 10 3.75 1.25 600 TA3P-7 TA3P-7 TA3P-17 60 60 60 TA316-7 TA316-7 - 60 60 45
P80-7 P80-7 P80-17 60 60 45
150 TA3P-7 TA3P-7 TA3P-17 45 20 10 3000 TA312-7 TA312-7 TA312-17 60 60 60
P80-7 P80-7 P80-17 20 10 5 TA301-7 TA301-7 TA301-17 60 45 30
TA301-7 TA301-7 TA301-17 15 5 - TA321-7 TA321-7 TA321-17 60 45 30 4000 TA312-7 TA312-7 TA312-17 60 60 60
TA321-7 TA321-7 TA321-17 20 7.5 1.25 TA34-7 TA34-7 TA34-17 60 45 30
5000
TA34-7 TA34-7 TA34-17 15 5 2.5 TA316-7 TA316-7 60 45 30 to TA312-7 TA312-7 TA312-17 60 60 60
200 TA3P-7 TA3P-7 TA3P-17 45 30 20 750 P80-7 P80-7 P80-17 60 60 45 8000
P80-7 P80-7 P80-17 45 20 5 to TA301-7 TA301-7 TA301-17 60 60 45
TA301-7 TA301-7 TA301-17 20 10 5 800 TA321-7 TA321-7 TA321-17 60 45 30
TA321-7 TA321-7 TA321-17 20 10 5 TA34-7 TA34-7 TA34-17 60 45 30
TA34-7 TA34-7 TA34-17 20 10 5 TA316-7 TA316-7 60 60 45
250 TA3P-7 TA3P-7 TA3P-17 60 45 30 1000 P80-7 P80-7 P80-17 60 60 45
P80-7 P80-7 P80-17 45 20 10 TA301-7 TA301-7 TA301-17 60 60 45
TA301-7 TA301-7 TA301-17 30 20 10 TA321-7 TA321-7 TA321-17 60 45 45
TA321-7 TA321-7 TA321-17 30 20 7.5 TA34-7 TA34-7 TA34-17 60 60 60
TA34-7 TA34-7 TA34-17 30 10 5 TA316-7 TA316-7 60 60 45
Dimensions
Type A B C D E F G H* J* K L* M Primary conductor
mm mm mm mm mm mm mm mm mm mm mm mm bar or Ø
TA301-7 88 123 216 (1) 52 16 69 63 65 72 30 - 15 1 to 2 bars 50x5
TA316-7 155 155 280 (1) 52 52 84 65 80 100 30 - 15 1 to 3 bars 50x10
TA321-7 87 144 300 (1) 70 16 81 85 72 114 20 - 15 1 bar 60x15
TA34-7 137 190 300 (1) 85 20 101 103 80 110 30 - 15 1 to 2 bars 80x5
TA312-7 226 209 280 (1) 85 102 90.5 105 100 90 40 - 15 1 to 2 bars 100x20
TA3P-7 104 112 200 (1) 86 18 66 30 56 72 35 42 15 Ø 16
P80-S7 150 150 280 (2) 137 18 75 30 56 113 30 44 15 Ø 16
P80-7 150 150 310 (2) 137 60 75 80 56 128 30 44 15 Ø 50
TA301-17 88 123 500 44 8 69 63 65 214 30 - 15 1 bar 40x8
TA321-17 87 144 500 70 12 81 85 72 214 20 - 15 1 bar 60x8
TA34-17 137 190 500 85 20 101 103 80 210 30 - 15 1 to 2 bars 80x5
TA312-17 226 209 500 85 102 111 105 100 200 40 - 15 1 to 2 bars 100x20
TA 3P-17 104 112 430 86 18 66 40 56 192 35 42 15 Ø 18
P80-S17 150 150 430 137 18 75 40 56 193 30 44 15 Ø 18
P80-17 150 150 500 137 50 75 80 56 223 30 44 15 Ø 45
*Dimensions H, J, L can vary according to electrical performances (spacer) • Tightening torque terminal M5 : 2 N.m
(1) up to 500mm maximum. Specific size to be quoted on offer
(2) up to 430mm maximum. Specific size to be quoted on offer
TA… TA3P-7 - TA3P-17 - P80-7 - P80-17…
M5 K
M M5 K
M
S2 S1 S2
F S1
F OG
P1
G D B B
P1 OE
5
L O6,3
J H J E J H J D
C A C A
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2OB/10
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
RC15E
Technical data
Rated insulation level 7.2/20/60 kV to 36/70/170 kV
Primary current Ipn 0 to 10000 A
• Outdoor
Secondary current Isn 5 or 1 A
24
Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 - 24 - 36 kV
Rated output 1 to 60 VA
• Primary current up to 10000 A
Accuracy class 0.1 - 0.2 - 0.2S - 0.5 - 0.5S - 1 - 3 - 5P - 10P - clX
• Ith up to 1000 Ipn
Accuracy limit factor 5 - 10 - 15 - 20 - 30
Continuous thermal current 1.2 Ipn
Short-time thermal current Ith 80 to 1000 Ipn
Dynamic current Idyn 2.5 Ith
Insulation class E
Ambient temperature - 25° C to + 40 °C
Standards IEC - IEEE - CSA - AS - BS
Outdoor current transformers va-
cuum moulded in self extinguishing
epoxy resin for the measurement Other characteristics on request
of AC currents up to 10000A.
Secondary current Isn 0.005 to 10 A
Double ratio Secondary tapping
They are equipped with a wea-
Multiple cores Up to 2 separate cores
therproof terminal box fitted with 2
cable glands. Ambient temperature - 40° C to + 70 °C
Accessories / Options
HV primary screen (see installation) On RC series
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2QD/1
OUTDOOR CURRENT TRANSFORMERS SERIES RC15E - RC36E - RC306E
OA B
C
Fil deEquipotential
l'écran de mise
P1 screen wire
au potentiel (option)
Installation
• In 24kV, for the RC15E model, it is advisable that the
OF
conductor passing through the transformer should be
round, with a maximum diameter of 80 mm, centered in
the hole. A bar may be used provided that its edges are
rounded.
E
D
• When equipped with, the HV primary screen wire must
be connected to the HT.
SortiesM6secondaires
secondaryM6
terminals
S1 S2
• Tightening torque
OL G terminal M6 : 2 N.m
K H
terminal M12 : 25 N.m.
J
RC36E
Potential
Fil screen
de l'écran de mise
auwire
potentiel
M6
secondary terminals Fixings
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2QD/1
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
Technical data
Rated insulation level 3.6/16/45 kV to 52/95/250 kV
Primary voltage Upn Up to 50000 : √3 V
Secondary voltage Usn 100 : √3 - 110 : √3 V 25
Frequency 50 or 60 Hz
• Indoor Rated output Up to 200 VA CL0.2 - 500 VA CL0.5 -
• 7.2 - 12 - 17.5 - 24 - 36 - 52 kV 1000 VA CL1
• Primary voltage up to 50000 /√3 V Accuracy class 0.1 - 0.2 - 0.5 - 1 - 3 - 3P - 6P
Voltage factor 1.9 Upn 30s
Thermal limiting output Up to 5000 VA
Insulation class E
Ambient temperature - 25°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS
Single pole voltage transformer va-
cuum moulded in self extinguishing Other characteristics on request
epoxy resin for the measurement of Secondary voltage Usn 24/√3 to 380/√3 V
AC voltages between phase and Voltage factor 1.9 Upn 8h
earth up to 50000 : √3 V. Secondary windings Up to 3 secondary windings
Residual voltage winding 100/3 V 50VA cl3 - Delta connection
on a 68.1Ω or 150W resistor
This range is also suitable for the power
Ambient temperature - 40°C to + 70°C
supply of auxiliairies up to 5KVA CLA.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2RA/9
single phase 1-pole voltage transformerS - ru series
Model Un Up Max rated output VA Thermal output Model Weight kg A B C D F G H J K Q
mm mm mm mm mm mm mm mm mm mm
kV kV cl0,5 cl1 cl3 VA
RU7 7.2/20/60 Up to 6.6/√3 60 100 150 Up to 300 RU7 16 220 205 120 270 185 180 33 33 35 75
RU10M 12/28/75 Up to 11/√3 60 100 150 Up to 300 RU10M 16 220 246 159 276 185 180 50 50 40 67
RU12 24/50/125 Up to 22/√3 100 200 600 Up to 1000 RU12 27 220 285 186 300 190 180 50 50 40 67
RU15 24/50/125 Up to 22/√3 200 300 1000 Up to 1500 RU15 34 220 300 210 350 300 180 58 50 40 60
RU30 36/70/170 Up to 35/√3 150 300 1000 Up to 2500 RU30 49 220 370 260 378 280 180 50 50 40 75
RU26 36/70/170 Up to 35/√3 500 1000 2000 Up to 5000 RU26 90 236 415 265 417 305 196 50 50 40 108
RU27 36/70/170 Up to 35/√3 500 1000 2000 Up to 5000 RU27 95 236 435 310 420 305 196 58 50 40 108
RU45 52/95/250 Up to 50/√3 100 150 500 Up to 4000 RU45 90 220 535 300 450 325 180 80 50 40 40
RU7
RU10M M8
159
P1
15
231
P2 M8
1S1 1S2 2S1 2S2
50
40 40 40
90 90
185
220
276
RS ISOLSEC
- - - Dess : C.P. Date : 27/10/1998
- - -
Vérif : G.L. Ech : 1/2,5
RU26-RU27
MODIFICATIONS Date Ind.
45 , Avenue des Acacias
Désignation : Encombrement Matière : Isolite 45120 CEPOY
Format : A4 tél : 33.(0)2.38.85.62.62 fax : 33.(0)2.38.85.6 2.05
RU12-RU15-RU45
Installation:
Tightening torque terminal M8 : 13N.m
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2RA/9
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U26E
Technical data
Rated insulation level 3.6/16/45 kV to 24/50/125 kV
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2RB/5
SINGLE PHASE 1-POLE PLUG-IN VOLTAGE TRANSFORMERS - U26E
55
A
350
245
M8
N
30
50
20
35 O8 90 90
Secondary
Sorties 260 220
output M6
secondaires
Installation
Tightening torque
terminal M6 : 2 Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2RB/5
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
EBM
EBL
EBF
EBH
EBT
Technical data
Highest voltage for equipment 3.6/16/45 kV up to 36/70/170 kV
Primary voltage Upn Up to 36 000 /√3V 25
• Indoor Secondary voltage Usn 100/√3 - 110/√3 - 100/3 - 110/3 V
Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 - 24 - 36 kV
Rated output Up to 100 VA CL 0.2 - 300 VA CL 0.5
• Primary voltage up to 36 000/√3 V 450 VA CL 1
Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
Voltage factor 1.9 Upn 8 h
Thermal limiting output Up to 1500 VA
Single phase 1-pole voltage transformers Insulation class E
made of self extinguishing epoxy resin for Ambient temperature - 5°C to + 40°C
the measure of AC voltages between
Standards IEC - IEEE - CSA - AS - BS - UNE
phase and earth up to 36 000/√3 V.
This range is also suitable for the power Other characteristics on request
supply of auxiliaries up to 1500VA CLA. Secondary voltage Usn From 24/√3 up to 380/√3 V
Voltage factor 1.5 Un 30s - 1.2 Un
The anti-explosion system exclusively Secondary windings Up to 3
deals with secondary fault (short-
Ambient temperature - 25°C to + 70°C
circuit, maintained overload...). Under
Simultaneous loads Measure and/or protection
no circumstances it can handle a
primary fault (overvoltage, ferroreso- Accessories / Options
nance, lightning, switching...)
Fixing plate Standard
This system must be associated with a
Sealable cover for secondary terminal (IP31) Standard
cut-off relay. Maintaining feeding of VT
would result in its destruction. Surface finish Polyurethane or Silicone coating
Earth connector Option
Anti-explosion system Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2RE/9
SINGLE PHASE 1-POLE VOLTAGE TRANSFORMER - E36B SERIES
Selection table EBFA
Type Un Up Rated output Thermal output
Up to (kV.) Up to (kV.) Up to (VA) Up to (VA)
cl 0.2 cl 0.5 cl 1 cl 3
E7BFA 7.2/20/60 6.6:√3 15 30 60 120 250
E7BHA 7.2/20/60 6.6:√3 35 80 150 250 350
E7BMA 7.2/20/60 6.6:√3 60 125 225 400 500
E7BTA 7.2/20/60 6.6:√3 40 80 160 320 600
E7BLA 7.2/20/60 6.6:√3 100 200 400 800 1500
E12BFA 12/28/75 11:√3 15 30 60 120 250
E12BHA 12/28/75 11:√3 35 80 150 250 350
E12BMA 12/28/75 11:√3 60 125 225 400 500
E12BTA 12/28/75 11:√3 40 80 160 320 600
EBHA
E12BLA 12/28/75 11:√3 100 200 400 800 1500
E17BFA 17.5/38/95 16.5:√3 15 30 60 120 250
E17BHA 17.5/38/95 16.5:√3 35 80 150 250 350
E17BMA 17.5/38/95 16.5:√3 60 125 225 400 500
E17BTA 17.5/38/95 16.5:√3 100 200 400 800 1500
E17BLA 17.5/38/95 16.5:√3 40 80 160 320 600
E24BFA 24/50/125 22:√3 15 30 60 120 250
E24BHA 24/50/125 22:√3 35 80 150 250 350
E24BMA 24/50/125 22:√3 60 125 225 400 500
E24BTA 24/50/125 22:√3 40 80 160 320 600
E24BLA 24/50/125 22:√3 100 200 400 800 1500
E36BTA 36/70/170 33:√3 35 75 150 300 600
E36BLA 36/70/170 33:√3 75 150 300 600 1500
Dimensions EBMA
Type Weight A B C D F G J K
kg mm mm mm mm mm mm mm mm
E7BFA 23 180 282 148 310 290 150 47 24
E7BHA 25 180 280 186 310 290 150 47 24
E7BMA 41 178 284 240 411 290 150 35 24
E7BTA 37 230 407 232 447 350 200 35 24
E7BLA 61 228 410 232 410 350 200 51 24
E12BFA 23 180 282 148 310 290 150 47 24
E12BHA 25 180 280 186 310 290 150 47 24
E12BMA 41 178 284 240 411 290 150 35 24
E12BTA 37 230 407 232 447 350 200 35 24
E12BLA 61 228 410 232 410 350 200 51 24
EBTA
E17BFA 23 180 282 148 310 290 150 47 24
E17BHA 25 180 280 186 310 290 150 47 24
E17BMA 41 178 284 240 411 290 150 35 24
E17BTA 37 230 407 232 447 350 200 35 24
E17BLA 61 228 410 232 410 350 200 51 24
E24BFA 23 180 282 148 310 290 150 47 24
E24BHA 25 180 280 186 310 290 150 47 24
E24BMA 41 178 284 240 411 290 150 35 24
E24BTA 37 230 407 232 447 350 200 35 24
E24BLA 61 228 410 232 410 350 200 51 24
E36BTA 37 230 407 232 447 350 200 35 24
E36BLA 61 228 410 232 410 350 200 51 24
EBLA
Installation
- This voltage transformer can be fixed in any position.
- Tightening torque for primary terminals 35 N.m
- Primary terminals M12x23 useful depth.
- Tightening torque for secondary terminals : M6 :4 N.m
- This voltage transformer is maintenance free.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2RE/9
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
Dénomination example :
E 2 4 G 2 B
Primary terminal type
Mould type denomination
E24G2B
Technical data
Rated insulation level From 3.6/16/45 kV to 36/70/170 kV
• Indoor Primary voltage Upn Up to 36 000/√3 V
• 7.2 - 12 - 17.5 - 24 - 36 kV Secondary voltage Usn 100/√3 - 110/√3 - 100/3 - 110/3 V
• Primary voltage up to 36000/√3 V Frequency 50 or 60 Hz
Rated output Up to 25 VA CL 0.2 - 50 VA CL 0.5
• Touchproof finish
100 VA CL 1 - 200 VA CL 3 25
• For metering, protection or Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
auxiliary power Voltage factor 1,9 Upn 8h
Thermal limiting output Up to 10 kVA
Surface finish Metallic surface
1-pole voltage transformers vacuum moulded Insulation class E
in self extinguishing epoxy resin for the measure Ambient temperature - 5°C to + 40°C / 25°F to 100°F
of AC voltages between phase and earth up Standards IEC - IEEE - CSA - AS - BS - UNE
to 36 000/√3 V.
Other characteristics on request
The user connects an insulated cable equi- Secondary voltage Usn 24/√3 to 380/√3 V
ped with a standard female or male plug. Voltage factor 1.5 Un 30s - 1,2Un
Plug -in and plug-out have to be done with no Secondary windings Up to 3
voltage present. Ambient temperature - 25°C to + 70°C / -13°F to +160°F
Simultaneous loads Measure and/or protection
The transformer’s surface is coated with a Antiferroresonance Low induction
metallic compound that ensures a safe repar-
tition of the magnetic field and zero-potential Accessoires / Options
surface.
Fixing plate Standard - Several options available
Surface finish Silicone coating
The anti-explosion system exclusively deals
Secondary terminal Series waterproof terminal cover (IP31)
with secondary fault (short-circuit, maintained
overload...). Finish bornier secondary On cable
Under no circumstances it can handle a Earth connector Option
primary fault (overvoltage, ferroresonance, Anti-explosion device Option
lightning, switching...) Double primary ratio Option
This system must be associated with a cut-off Up to 3 secondaries Option
relay. Maintaining feeding of VT would result
in its destruction.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - NOTICE: M2RH/1
SINGLE PHASE 1 POLE PLUG-IN VOLTAGE TRANSFORMERS - indoor - E..G.. A/B/C/W SERIES
SINGLE PHASE 1-POLE PLUG-IN VOLTAGE TRANSFORMERS - INDOOR TYPE - E..G..A/B/C/W SERIE
ONE INSULATED POLE - PHASE TO GROUND INDOOR TYPE
E..G1.. E..G2.. E..G4.. E..G5.. E..G7.. E..G8..
Drawing type
Mod.01 Mod.01 Mod.02 Mod.02 Mod.01/02 Mod.02
General Dimensions. [mm].
A: 280 A: 340 A: 332 A: 382 A: 500 A: 560
B: 255 B: 307 B: 317 B: 350 B: 458 B: 561
C: 148 C: 186 C: 225 C: 270 C: 335 C: 410
D: 120 D: 120 D: 120 D: 146 D: 200 D: 270
M: 25 kg. M: 45 kg. M: 55 kg. M: 75 kg. M: 135 kg. M: 320 kg.
UNE-EN IEC 50181 H.V. PRIMARY TERMINAL TYPE
TYPE B - up to 36 kV.
TYPE C - up to 36 kV.
TYPE A - up to 24 kV.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - NOTICE: M2RH/1
medium voltage instrument transformers
RM5 RM7
Technical data
Rated insulation level 3.6/16/45 kV to 36/70/170 kV
Primary voltage Upn Up to 36000 V
• Indoor
Secondary voltage Usn 100 - 110 V
• 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV
Frequency 50 or 60 Hz 26
Rated output Up to 100 VA CL 0.2 - 150 VA CL 0.5 -
200 VA CL 1
Accuracy class 0.1 - 0.2 - 0.5 - 1 - 3 - 3P - 6P
Voltage factor 1.2 Upn permanent
Double pole voltage transfor- Thermal limiting output Up to 2500 VA
mers vacuum moulded in self Insulation class E
extinguishing epoxy resin for the Ambient temperature - 25°C to + 40°C
measurement of AC voltages Standards IEC - IEEE - CSA - AS - BS
between phases up to 36 kV, with
rated outputs up to 100 VA CL0.2 Other characteristics on request
or 150 VA CL0.5.
Secondary voltage Usn 10 to 600 V
Secondary windings Up to 3 secondary windings
This range is also suitable for the
Ambient temperature - 40°C to + 70°C
power supply of auxiliairies up to
2500VA CLA.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2SA/6
single phase 2-pole voltage transformer - rm series
Model Weight A B C D E F G H J K L M Q
kg mm mm mm mm mm mm mm mm mm mm mm mm mm
RM5 - RM10
RM7 - RM15
RM30
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2SA/6
medium voltage instrument transformers
RT13 RT12
Technical data
Rated insulation level 3.6/16/45 kV to 36/70/170 kV
Primary voltage Upn Up to 36.000 V
Secondary voltage Usn 100 - 110 V
• indoor Frequency 50 or 60 Hz
• 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV Rated output Up to 200 VA CL 0.2 - 300 VA CL 0.5 -
• High performance characteristics 500 VA CL1 26
Accuracy class 0.1 - 0.2 - 0.5 - 1 - 3 - 3P - 6P
Voltage factor 1.2 Upn continuously
Thermal limiting output Up to 5000 VA
Insulation class E
Ambient temperature - 25°C to + 45°C
Double pole voltage transformers va- Standards IEC - IEEE - CSA - AS - BS
cuum moulded in self extinguishing
epoxy resin for the measurement of Other characteristics on request
AC voltages between phases up to
36kV, with rated outputs up to 200VA Secondary voltage Usn 10 to 600 V
CL0.2 or 300VA CL0.5. Voltage factor 1.9 Upn 8h if used as single pole
Secondary windings Up to 3 secondary windings
This range is also suitable for the Ambient temperature - 40°C to + 70°C
power supply of auxiliairies up to
5000VA CLA.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2SB/7
single phase 2-pole voltage transformer - rT series
Model Weight kg A B C D E F G H J I Q
mm mm mm mm mm mm mm mm mm mm mm
RT26 - RT 27
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2SB/7
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
UBH
UBH
UBN
UBN
UBHC
UBHc
Technical data
Highest voltage for equipment 3.6/16/45 kV up to 36/70/170 kV
Primary voltage Upn Up to 36.000 V
Secondary voltage Usn 100 - 110 - 120 - 230 V
• Indoor Frequency 50 or 60 Hz
Rated output Up to 100 VA CL 0.2 - 150 VA CL 0.5
• 7.2 - 12 - 17.5 - 24 - 36 kV
200 VA CL 1
• Primary voltage up to 36.000 V Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P 26
Voltage factor 1.2 Un
Thermal limiting output Up to 5000 VA
Insulation class E
Single phase 2-pole voltage transformers Ambient temperature - 5°C to + 40°C
made of self extinguishing epoxy resin for Standards IEC - IEEE - CSA - AS - BS - UNE
the measure of AC voltages between
phases up to
Other characteristics on request
36 000 V.
Secondary voltage Usn 10 to 600 V
This range is also suitable for the power sup- Secondary windings Up to 3
ply of auxiliaries up to 5000VA clA. Ambient temperature - 25°C to + 70°C
Simultaneous loads Measure and/or protection
The anti-explosion system exclusively deals Voltage factor 1.2 Un - 1.5 Un 30s - 1.9 Un 8h
with secondary fault (short-circuit, maintai-
ned overload...). Under no circumstances
it can handle a primary fault (overvoltage, Accessories / Options
ferroresonance, lightning, switching...)
Fixing plate Standard
This system must be associated with a cut-
Sealable cover for secondary terminal (IP31) Standard
off relay. Maintaining feeding of VT would
result in its destruction. Surface finish Polyurethane or Silicone coating
Earth connector Option
Anti-explosion system Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2SC/9
SINGLE PHASE 2-POLE VOLTAGE TRANSFORMER - U..B.. SERIES
Selection table UBHA-UBMA
Type Un Up Rated output Thermal
output
Up to (kV.) Up to (kV.) Max (VA ) Up to (VA)
cl 0.5 cl 1 cl 3
U7BH 7.2/20/60 6.6 50 100 150 300
U7BM 7.2/20/60 6.6 100 200 350 400
U7DM 7.2/20/60 6.6 150 250 450 1000
U7BN 7.2/20/60 6.6 200 400 700 2500
U7CO 7.2/20/60 6.6 300 600 1000 3500
U12BH 12/28/75 11 50 100 150 300
U12BM 12/28/75 11 100 200 350 400
U12DM 12/28/75 11 150 250 450 1000
U12BN 12/28/75 11 200 400 700 2500
U12CO 12/28/75 11 300 600 1000 3500
U17BH 17.5/38/95 16.5 50 100 150 300
U17BM 17.5/38/95 16.5 100 200 350 400
U17DM 17.5/38/95 16.5 150 250 450 1000
U17BN 17.5/38/95 16.5 200 400 700 2500 UBNA
U17CO 17.5/38/95 16.5 300 600 1000 3500
U24BH 24/50/125 22 50 100 150 300
U24BM 24/50/125 22 100 200 350 400
U24DM 24/50/125 22 150 250 450 1000
U24BN 24/50/125 22 200 400 700 2500
U24CO 24/50/125 22 300 600 1000 3500
U36DM 36/70/170 35 150 250 450 1000
U36BN 36/70/170 35 200 400 700 2500
U36CO 36/70/170 35 300 600 1000 3500
Dimensions
Type Weight A B C D F G J K M N
kg mm mm mm mm mm mm mm mm mm mm
U7BH 30 180 280 190 310 290 150 47 24 165 130
U7BM 34 178 285 240 411 290 150 35 24 165 130
U7DM 40 178 290 220 349 240 150 21 60 251 - UCOA
U7BN 34 230 415 220 380 350 200 35 24 325 -
U7CO 60 230 341 370 441 350 200 26 23 320 100
U12BH 30 180 280 190 310 290 150 47 24 165 130
U12BM 34 178 285 240 411 290 150 35 24 165 130
U12DM 40 178 290 220 349 240 150 21 60 251 -
U12BN 34 230 415 220 380 350 200 35 24 325 -
U12CO 60 230 341 370 441 350 200 26 23 320 100
U17BH 30 180 280 190 310 290 150 47 24 165 130
U17BM 34 178 285 240 411 290 150 35 24 165 130
U17DM 40 178 290 220 349 240 150 21 60 251 -
U17BN 34 230 415 220 380 350 200 35 24 325 -
U17CO 60 230 341 370 441 350 200 26 23 320 100
U24BH 30 180 280 190 310 290 150 47 24 165 130
U24BM 34 178 285 240 411 290 150 35 24 165 130
U24DM 40 178 290 220 349 240 150 21 60 251 -
UDMA
U24BN 34 230 415 220 380 350 200 35 24 325 -
U24CO 60 230 341 370 441 350 200 26 23 320 100
U36DM 40 178 290 220 349 240 150 21 60 251 -
U36BN 34 230 415 220 380 350 200 35 24 325 -
U36CO 60 230 341 370 441 350 200 26 23 320 100
Installation
- This voltage transformer can be fixed in any position.
- Tightening torque for primary terminals 35 N.m
- Primary terminals M12x23 useful depth.
- Tightening torque for secondary terminals : M6 :4 N.m
- This voltage transformer is maintenance free.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2SC/9
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U 2 4 G 4 B
Primary terminal type
U24G4B
Technical data
Rated insulation level From 3,6/16/45 kV to 36/70/170 kV
• Indoor Primary voltage Upn Up to 36.000 V
• 7,2 - 12 - 17,5 - 24 - 36 kV Secondary voltage Usn 100 - 110 - 120 - 220 - 230 V
• Primary voltage up to 36kV Frequency 50 or 60 Hz
• Touchproof finish Rated output Up to 500 VA CL 0,2 - 1200 VA CL 0,5
- 2400 VA CL 1 - 1200 VA CL 3
• For metering, protection or Accuracy class 0,1 - 0,2 - 0,5 -1 - 3 - 3P - 6P 26
auxilary power. Voltage factor 1,9 Un 8h
Thermal limiting output Up to 10 kVA
Surface finish Metallic
Secondary terminal and fixing plate finish Indoor
2-pole voltage transformer vacuum Insulation class E
moulded in self extinguishing epoxy resin
Ambient temperature - 5°C to + 40°C / 25°F to 100°F
for the measure of AC voltages between
Standards IEC - IEEE - CSA - AS - BS - UNE
phases up to 36.000 V.
Other characteristics on request
This transformer is equipped with two stan-
dard plugs. The user connects two insu- Antiferroresonance Low induction
lated cables equipped with a standard Secondary voltage 10 to 600 V
mobile plug. Secondary windings Up to 3
Ambient temperature - 25°C to + 70°C / -13°F to +160°F
The transformer’s surface is coated with a Application Measure and/or protection
metallic compound that ensures a safe Voltage factor 1,2 Un - 1,5 Un 30s
and evenly distributed magnetic field and
zero-potential surface. Accessories / Options
Primary terminal Interface A, B, C, or W
The anti-explosion system exclusively deals
Surface coating finish Optional silicone Coating
with secondary fault (short-circuit, maintai-
Base plate Standard - Several options available
ned overload...). Under no circumstances
it can handle a primary fault (overvoltage, Secondary terminal On cable
ferroresonance, lightning, switching...) Earth connector Option
This system must be associated with a cut- Anti-explosion device Option
off relay. Maintaining feeding of VT would Double primary ratio Option
result in its destruction. Up to 3 secondaries Option
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information - NOTICE : M2SF/1
SINGLE PHASE 2-POLE PLUG-IN VOLTAGE TRANSFORMERS - INDOOR - U..G.. A/B/C/W
SINGLE PHASE 2-POLE PLUG-IN VOLTAGE TRANSFORMERS - INDOOR TYPE - E..G..A/B/C/W SERIE
TWO INSULATED POLES - PHASE TO PHASE INDOOR
TYPE
U..G4.. U..G5.. U..G7.. U..G8..
Dimensions. [mm].
A: 332 A: 382 A: 500 A: 560
B: 317 B: 350 B: 458 B: 561
C: 225 C: 270 C: 335 C: 410
D: 120 D: 146 D: 200 D: 270
M : 57kg M : 77kg M : 137kg M : 327kg
UNE-EN IEC 50181 H.V. PRIMARY TERMINAL TYPE
TYPE B - up to 36 kV.
TYPE C - up to 36 kV.
TYPE A - up to 24 kV.
CT15
UT20
Technical data
Rated insulation level 3.6/16/45 kV to 36/70/170 kV
• Indoor Primary voltage Upn Up to 33 000/√3 V
Secondary voltage Usn 100/√3 V - 110/√3 V
• 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV
Frequency 50 or 60 Hz
• With 1 or 2 HBC protection fuses
Rated output Up to 100 VA CL0.2 - 150 VA CL0.5
• Compact size 300 VA CL1
Accuracy class 0.1 - 0.2 - 0.5 - 1 - 3 - 3P - 6P 27
Voltage factor 1.2 Upn for double poles
1.9 Upn 30s for single pole
Thermal limiting output Up to 2500 VA
Insulation class E
1 or 2-pole voltage transfor-
Fuses 6.3 A
mers vacuum moulded in self
extinguishing epoxy resin for the Ambient temperature - 25°C to + 40°C
measurement of AC voltages Standards IEC- IEEE - CSA - AS - BS
between phases or between
phase and earth up to 36kV.
Other characteristics on request
These compact voltage trans-
formers are equipped with 1 or 2 Secondary voltage Usn 10 to 400 V
protection fuses of 6.3A rating. Voltage factor 1.9 Upn 8h for single pole
Ambient temperature - 40°C to + 70°C
They are also suitable for the Secondary windings Up to 3 separate secondary windings
power supply of auxiliaries up to Residual voltage windings 100/3 V - 50 VA CL3 - Delta connection on a
2500VA CLA. 68.1 Ω - 150 W resistor
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2TA/11
SINGLE PHASE 1 OR 2-POLE VOLTAGE TRANSFORMERS WITH FUSE - UT - CT SERIES
Model Weight A B C D E F H J K Q
kg mm mm mm mm mm mm mm mm mm mm
UT20 28 300 175 342 302 290 190 42 - 40 66
UT
CT
Installation
Maximum tightening torque
- M8 Primary terminals :5 Nm
- M8 Secondary terminals & fixing screws : 13 Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2TA/11
medium voltage instrument transformers
• Indoor
Technical data
• 12 - 24 - 36 kV
• 1 insulated pole Isolation level 12, 24, or 36kV
• 2 insulated poles Frequency 50 or 60 Hz
Insulation class F
Fuse type A 0.5A from 12 to 25.5kV
Kit for mounting fuse(s) on measuring voltage Fuse type B 2.5A from 12 to 36kV 28
transformers, 1 or 2 insulated poles. These Ambient temperature From - 5°C to + 40°C
parts are molded under vacuum, same as Standards IEC - IEEE - CSA - AS - BS
voltage transformers.
Accessories
Made in brown epoxy resin, having excellent Ambient temperature - 25°C to + 70°C
mechanical behavior, and good resistance
to corrosive atmosphere and fire.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M1TE/2
FUSE HOLDER FOR TRANSFORMER WITH 1 OR 2 INSULATED POLES
VT Fuse
LINE INSULATION A B C D E F G H I (*) J (*) K L M (*) N O
MODEL type
12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV 12,5 kV 24 kV 36 kV
1 EBFA 75 41 - 316 - 290 150 11 180 310 586 786 - 50 150 - 373 - 346 - 200 300 - M10 M6 A
2 EBHA 75 127 276 - 309 314 - 290 150 11 180 310 586 786 - 50 150 467 616 - 406 405 - 200 300 - M10 M6 B
3 75 41 - 321 - 290 150 11 178 400 760 840 - 110 150 - 419 - 351 - 260 300 - M10 M6 A
EBMA
4 75 127 276 - 313 318 - 290 150 11 178 400 760 840 - 110 150 - 490 639 - 410 409 - 260 300 - M10 M6 B
5 100 15 - 442 - 350 200 11 230 441 752 832 - 60 100 - 447 - 471 - 260 300 - M12 M6 A
EBLA
6 100 72 221 - 434 439 - 350 200 11 230 441 752 832 - 60 100 - 506 665 - 434 439 - 260 300 - M12 M6 B
24KV
7 60 118 - 378 - 350 200 11 230 441 1170 - 200 - 515 - 407 - 400 - M12 M6 A
ECOA
8 60 122 271 - 371 376 - 350 200 11 230 441 1176 - 200 - 550 699 - 468 467 - 400 - M12 M6 B
9 60 61 - 416 - 350 200 14 230 446 1170 - 200 - 446 - 445 - 400 - M12 M6 A
EFQA
10 60 147 296 - 408 413 - 350 200 14 230 446 1177 - 200 - 552 801 - 505 504 - 400 - M12 M6 B
11 100 11 - 444 - 350 200 13 228 410 752 832 - 60 100 - 410 - 473 - 260 300 - M12 M6 A
EBTA
12 100 97 246 - 432 441 - 350 200 13 228 410 752 832 - 60 100 - 502 651 - 533 532 - 260 300 - M12 M6 B
13 ECOA 33 310 378 350 200 11 230 441 - - 1170 - - 200 737 469 - - 400 M12 M6 B
14 EFQA 36KV 33 335 415 350 200 14 230 446 - - 1173 - - 200 740 506 - - 400 M12 M6 B
15 EBTA 73 185 443 350 200 13 228 410 - - 1032 - - 200 664 534 - - 400 M12 M6 B
16 50 41 - 316 - 290 150 11 180 310 541 - 100 - 373 - 345 - 250 - M10 M6 A
UBHA
17 39 33 180 - 310 - 290 150 11 180 310 518 - 78 - 446 592 - 403 - 229 - M10 M6 B
18 50 41 - 323 - 290 150 11 178 400 541 - 100 - 419 - 352 - 250 - M10 M6 A
UBMA
19 39 32 180 - 310 317 - 290 150 11 178 400 658 - 218 - 456 581 - 409 - 658 - M10 M6 B
24KV
20 110 15 - 381 - 350 200 11 230 441 881 - 220 - 441 - 410 - 420 - M12 M6 A
UCOA
21 109 20 168 - 376 - 350 200 11 230 441 899 - 218 - 441 596 - 465 - 418 - M12 M6 B
22 110 11 - 419 - 350 200 14 230 446 881 - 220 - 446 - 448 - 420 - M12 M6 A
UFQA
23 109 45 193 - 414 411 - 350 200 14 230 446 897 - 218 - 446 599 505 502 - 898 - M12 M6 B
24 UCOA 87 - - 210 - - 378 350 200 11 230 441 - - 856 - - 174 - - 662 - - 464 - - 374 M12 M6 B
36KV
25 UFQA 87 - - 235 - - 416 350 200 14 230 446 - - 856 - - 174 - - 662 - - 464 - - 374 M12 M6 B
Theoretical dimensions in mm Overall tolerance +/- 5mm (*) Recommanded
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information- DATASHEET : M1TE/2
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
Denomination example :
E 2 4 G 4 P
E24G4P E24G3R
E24G0G E52G7Y
Technical data
Rated insulation level From 3.6/16/45 kV to 52/95/250 kV
Primary voltage Upn Up to 52 000 /√3 V
• Outdoor
Secondary voltage Usn 100/√3 - 110/√3 - 100/3 - 110/3 V
• 7.2 - 12 - 17.5 - 24 - 36 - 52kV
Frequency 50 or 60 Hz
• Primary voltage up to 52/√3 kV Rated output Up to 200 VA CL 0.5 - 400 VA CL 1
800 VA CL 3
Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
Voltage factor 1.9 Upn 8h
1-pole voltage transformer vacuum Thermal limiting output Up to 10 000 VA
moulded in self extinguishing epoxy resin Surface finish Touch-proof (deadtank) or Polyurethane 29
for the measure of AC voltages between Fixing plate Standard
phase and earth up to 52 000/√3 V. Wheatherproof cover for secondary terminal Standard
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information- DATASHEET : M2TC/11
SINGLE PHASE 1-POLE OUTDOOR VOLTAGE TRANSFORMERS - E..G. r/p/g/m/v/y SERIES
MAXIMUM SECONDARY Nº
1 , 2 or 3 1 , 2 or 3 1 , 2 or 3 1 , 2 or 3 1 , 2 or 3 1 , 2 or 3
MAXIMUM TOTAL BURDEN [VA].
Up kV. cl0.2 cl0.5 cl1 cl3 Up kV. cl0.2 cl0.5 cl1 cl3 Up kV. cl0.2 cl0.5 cl1 cl3 Up kV. cl0.2 cl0.5 cl1 cl3 Up kV. cl0.2 cl0.5 cl1 cl3 Up kV. cl0.2 cl0.5 cl1 cl3
35 75 150 450 40 80 160 500 25 50 100 300 80 170 350 1100 400 900 1800 5500 500 1100 2200 6500
≤24 ≤24 ≤24 ≤24 ≤24 ≤24
Pth.[VA.]: 750 Pth.[VA.]: 800 Pth.[VA.]: 500 Pth.[VA.]: 1800 Pth.[VA.]: 8000 Pth.[VA.]: 10000
25 60 120 300 15 35 70 200 - - - - 55 130 260 750 350 850 1600 5000 500 1100 2200 6500
36 36 36 36 36 36
Pth.[VA.]: 450 Pth.[VA.]: 300 Pth.[VA.]: - Pth.[VA.]: 1100 Pth.[VA.]: 7500 Pth.[VA.]: 10000
- - - - - - - - - - - - 15 35 70 200 200 450 900 2500 300 600 1200 3500
52 52 52 52 52 52
Pth.[VA.]: - Pth.[VA.]: - Pth.[VA.]: - Pth.[VA.]: 300 Pth.[VA.]: 4000 Pth.[VA.]: 5000
A B C D A B C D A B C D A B C D A B C D A B C D
mm. mm. mm. mm. mm. mm.
288 392 232 124 340 308 186 120 332 317 225 120 382 350 270 146 500 458 335 200 560 561 410 270
M: 30 kg. M: 40 kg. M: 45 kg. M: 65 kg. M: 135 kg. M: 320 kg.
PRIMARY TERMINAL
R P G M V Y
SECONDARY TERMINALS
PLASTIC BOX METALLIC BOX CABLE
Taps: M6 Screws Taps: M6 Screws Taps: M6 Screws 2 / 3 / 4 / … copper wire cable.
Protection: White Sealable box Protection: Stainless Steel Protection: Stainless Steel Different cross section depending on maximal burden.
(Optional) IP65 (Optional) IP53 (Optional) IP54 With or without Ground wire.
PG11+PG21 tap 2x PG21 + 2x breathers + ground 2x PG16 + 1x breathers V0 capable.
©RS ISOLSEC PAGE 2/2 contact : [email protected] - non binding information - DATASHEET : M2TC/11
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
Denomination example :
E 2 4 G 2 B
Primary terminal type
E24G2B
Technical data
Rated insulation level From 3.6/16/45 kV to 36/70/170 kV
• Outdoor
Primary voltage Upn Up to 36 000/√3 V
• 7.2 - 12 - 17.5 - 24 - 36 kV
Secondary voltage Usn 100/√3 - 110/√3 - 100/3 - 110/3 V
• Primary voltage up to 36/√3 kV Frequency 50 or 60 Hz
• Touchproof finish Rated output Up to 25 VA CL 0.2 - 50 VA CL 0.5
• For metering, protection or 100 VA CL 1 - 200 VA CL 3
auxiliary power Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
Voltage factor 1,9 Upn 8h
Thermal limiting output Up to 10 kVA
Surface finish Metallic
1-pole voltage transformers vacuum Insulation class E 29
moulded in self extinguishing epoxy resin Ambient temperature - 5°C to + 40°C / 25°F to 100°F
for the measure of AC voltages between Standards IEC - IEEE - CSA - AS - BS - UNE
phase and earth up to 36 000/√3 V.
Other characteristics on request
The user connects an insulated cable equi-
Secondary voltage Usn 24/√3 to 380/√3 V
ped with a standard female or male plug.
Voltage factor 1.5 Un 30s - 1,2Un
Plug -in and plug-out have to be done with
Secondary windings Up to 3
no voltage present.
Ambient temperature - 25°C to + 70°C / -13°F to +160°F
Simultaneous loads Measure and/or protection
The transformer’s surface is coated with a
Antiferroresonance Low induction
metallic compound that ensures a safe
repartition of the magnetic field and zero- Accessoires / Options
potential surface.
Fixing plate Standard - Several options available
The anti-explosion system exclusively deals Surface finish Silicone coating
with secondary fault (short-circuit, maintai- Secondary terminal Series waterproof terminal cover (IP65)
ned overload...). Under no circumstances Finish bornier secondary Optional cable
it can handle a primary fault (overvoltage, Earth connector Option
ferroresonance, lightning, switching...)
Anti-explosion device Option
This system must be associated with a cut-
off relay. Maintaining feeding of VT would Double primary ratio Option
result in its destruction. Up to 3 secondaries Option
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - NOTICE: M2RG/1
SINGLE PHASE 1-POLE PLUG-IN VOLTAGE TRANSFORMERS - outdoor - E..G.. A/B/C/W SERIES
SINGLE PHASE 1-POLE PLUG-IN VOLTAGE TRANSFORMERS - OUTDOOR TYPE - E..G..A/B/C/W SERIE
ONE INSULATED POLE - PHASE TO GROUND OUTDOOR TYPE
E..G1.. E..G2.. E..G4.. E..G5.. E..G7.. E..G8..
Drawing type
Mod.01 Mod.01 Mod.02 Mod.02 Mod.01/02 Mod.02
Dimensions. [mm].
A: 280 A: 340 A: 332 A: 382 A: 500 A: 560
B: 255 B: 307 B: 317 B: 350 B: 458 B: 561
C: 148 C: 186 C: 225 C: 270 C: 335 C: 410
D: 120 D: 120 D: 120 D: 146 D: 200 D: 270
M: 25 kg. M: 45 kg. M: 55 kg. M: 75 kg. M: 135 kg. M: 320 kg.
UNE-EN IEC 50181 H.V. PRIMARY TERMINAL TYPE
TYPE A - up to 24 kV.
TYPE B - up to 36 kV.
TYPE C - up to 36 kV.
TM
IEEE Std. 386 H.V. PRIMARY TERMINAL TYPE
TYPE W - up to 21.1kV.
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - NOTICE: M2RG/1
medium voltage instrument transformers
RU12E
RM30E
Technical data
• Outdoor
Rated insulation level 3.6/16/45 kV to 36/70/170 kV
• Single or double pole
Primary voltage Upn Up to 36 000 V
• 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV Secondary voltage Usn 100 - 110 V
Frequency 50 or 60 Hz
Rated output Up to 50 VA CL 0.5 - 100 VA CL1 - 300 VA CL 3
Outdoor single or double pole voltage Accuracy class 0.1 - 0.2 - 0.5 - 1 - 3 - 3P - 6P 29
Voltage factor 1.9 Upn-30s for single pole
transformers vacuum moulded in self
1.2 Upn continuous
30
extinguishing epoxy resin for the mea-
Thermal limiting output Up to 2 500 VA
surement of AC voltages between
Insulation class E
phases or between phase and earth
Ambient temperature - 25°C to + 40°C
up to 36kV, with rated output up to 50
VA CL0.5 or 100 VA CL1. Standards IEC - IEEE - CSA - AS - BS
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2TB/8
outdoor single phase voltage transformer - RME - RUE SERIES
RM20E 805 890 34 390 270 380 290 190 180 220 20 40
RM25E 930 1590 37 570 220 500 470 190 180 220 20 60
RM30E 1030 1240 69 500 350 485 400 292 180 220 20 65
RM...
Secondary terminals
RU12E
Secondary terminals
Installation
Tightening torque
terminal M6 : 2 Nm
terminal M8 : 13 Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2TB/8
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U 2 4 G 4 P
Technical data
Rated insulation level From 3.6/16/45 kV to 52/95/250 kV
Primary voltage Upn Up to 52 000 V
Secondary voltage Usn 100 - 110 V
• Outdoor Frequency 50 or 60 Hz
• 7.2 - 12 - 17.5 - 24 - 36 - 52 kV Rated output Up to 200 VA CL 0.5 - 400 VA CL 1 -
• Primary voltage up to 52 kV 1000 VA CL 3
Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
Voltage factor 1.9 Upn 8h
Thermal limiting output Up to 10 000 VA
Surface finish Touch-proof (deadtank) or Polyurethane
Fixing plate Standard
Sealable cover for secondary terminal (IP65) Standard
30
Insulation class E
Ambient temperature - 5°C to + 40°C
Standards IEC - IEEE - CSA - AS - BS - UNE
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information - DATASHEET : M2TD/9
SINGLE PHASE 2-POLE OUTDOOR VOLTAGE TRANSFORMERS - U..G.. r/p/g/m/v SERIES
A B C D A B C D A B C D A B C D
mm. mm. mm. mm.
332 317 225 120 382 350 270 146 500 458 335 200 560 561 410 270
M: 45 kg. M: 65 kg. M: 135 kg. M: 320 kg.
PRIMARY TERMINALS
R P G M V
SECONDARY TERMINALS
PLASTIC BOX METALLIC BOX CABLE
Taps: M6 Screws Taps: M6 Screws Taps: M6 Screws
2 / 3 / 4 / … copper wire cable.
Protection: White Sealable box Protection: Stainless Steel Protection: Stainless Steel Different cross section depending on maximal burden.
(Optional) IP65 (Optional) IP53 (Optional) IP54 With or without Ground wire.
PG11+PG21 tap 2x PG21 + 2x breather + ground 2x PG16 + 1x breather V0 capable.
©RS ISOLSEC PAGE 2/2 contact : [email protected] - non binding information - DATASHEET : M2TD/9
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U 2 4 G 4 P
Technical data
Rated insulation level From 3.6/16/45 kV to 52/95/250 kV
Primary voltage Upn Up to 52 000 V
• Outdoor Secondary voltage Usn 100 - 110 V
• 7.2 - 12 - 17.5 - 24 - 36 - 52 kV Frequency 50 or 60 Hz
• Primary voltage up to 52 kV Rated output Up to 200 VA CL 0.5 - 400 VA CL 1 -
1000 VA CL 3
Accuracy class 0.1 - 0.2 - 0.5 -1 - 3 - 3P - 6P
Voltage factor 1.9 Upn 8h
2-pole voltage transformer vacuum Thermal limiting output Up to 10 000 VA
moulded in self extinguishing epoxy resin Surface finish Touch-proof (deadtank) or Polyurethane
for the measure of AC voltages between Fixing plate Standard
phases up to 52 000 V. Sealable cover for secondary terminal (IP65) Standard
30
Insulation class E
This series also allows for feeding auxiliaries up
Ambient temperature - 5°C to + 40°C
to 10 000 VA CLA.
Standards IEC - IEEE - CSA - AS - BS - UNE
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information - DATASHEET : M2TD/10
SINGLE PHASE 2-POLE OUTDOOR VOLTAGE TRANSFORMERS - U..G.. r/p/g/m/v SERIES
A B C D A B C D A B C D A B C D
mm. mm. mm. mm.
332 317 225 120 382 350 270 146 500 458 335 200 560 561 410 270
M: 45 kg. M: 65 kg. M: 135 kg. M: 320 kg.
PRIMARY TERMINALS
R P G M V
SECONDARY TERMINALS
PLASTIC BOX METALLIC BOX CABLE
Taps: M6 Screws Taps: M6 Screws Taps: M6 Screws
2 / 3 / 4 / … copper wire cable.
Protection: White Sealable box Protection: Stainless Steel Protection: Stainless Steel Different cross section depending on maximal burden.
(Optional) IP65 (Optional) IP53 (Optional) IP54 With or without Ground wire.
PG11+PG21 tap 2x PG21 + 2x breather + ground 2x PG16 + 1x breather V0 capable.
©RS ISOLSEC PAGE 2/2 contact : [email protected] - non binding information - DATASHEET : M2TD/10
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U 2 4 G 4 B
Primary terminal type
U24G4B
Technical data
Rated insulation level From 3,6/16/45 kV to 36/70/170 kV
Primary voltage Upn Up to 36.000 V
• Outdoor
Secondary voltage Usn 100 - 110 - 120 - 220 - 230 V
• 7,2 - 12 - 17,5 - 24 - 36 kV
Frequency 50 or 60 Hz
• Primary voltage up to 36kV Rated output Up to 500 VA CL 0,2 - 1200 VA CL 0,5
• Touchproof finish - 2400 VA CL 1 - 1200 VA CL 3
• For metering, protection or Accuracy class 0,1 - 0,2 - 0,5 -1 - 3 - 3P - 6P
auxilary power. Voltage factor 1,9 Un 8h
Thermal limiting output Up to 10 kVA
Surface finish Metallic
Secondary terminal and fixing plate finish Outdoor
2-pole voltage transformer vacuum moulded
in self extinguishing epoxy resin for the mea-
Insulation class E
30
Ambient temperature - 5°C to + 40°C / 25°F to 100°F
sure of AC voltages between phases up to Standards IEC - IEEE - CSA - AS - BS - UNE
36.000 V.
Other characteristics on request
This transformer is equipped with two stan-
dard plugs. The user connects two insulated Antiferroresonance Low induction
cables equipped with a standard mobile Secondary voltage 10 to 600 V
plug. Secondary windings Up to 3
Ambient temperature - 25°C to + 70°C / -13°F to +160°F
The transformer’s surface is coated with a Application Measure and/or protection
metallic compound that ensures a safe and Voltage factor 1,2 Un - 1,5 Un 30s
evenly distributed magnetic field and zero-
potential surface. Accessories / Options
Primary terminal Interface A, B, C, or W
The anti-explosion system exclusively deals Surface coating finish Optional Silicone Coating
with secondary fault (short-circuit, maintai-
Secondary terminal Optional cable
ned overload...). Under no circumstances
Base plate Standard - Several options available
it can handle a primary fault (overvoltage,
Earth connector Option
ferroresonance, lightning, switching...)
This system must be associated with a cut-off Anti-explosion device Option
relay. Maintaining feeding of VT would result Double primary ratio Option
in its destruction. Up to 3 secondaries Option
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information - NOTICE : M2SG/1
SINGLE PHASE 2-POLE PLUG-IN VOLTAGE TRANSFORMERS - U..G.. A/B/C/W SERIES
SINGLE PHASE 2-POLE PLUG-IN VOLTAGE TRANSFORMERS - OUTDOOR TYPE - U..G..A/B/C/W SERIE
TWO INSULATED POLES - PHASE TO PHASE OUTDOOR
TYPE
U..G4..
U..G5.. U..G7.. U..G8..
General Dimensions. [mm].
A: 332 A: 382 A: 500 A: 560
B: 317 B: 350 B: 458 B: 561
C: 225 C: 270 C: 335 C: 410
D: 120 D: 146 D: 200 D: 270
M: 57 kg. M: 77 kg. M: 137 kg. M: 327 kg.
UNE-EN IEC 50181 H.V. PRIMARY TERMINAL TYPE
TYPE B - up to 36 kV.
TYPE C - up to 36 kV.
TYPE A - up to 24 kV.
TM
IEEE Std. 386 H.V. PRIMARY TERMINAL TYPE
TYPE W - up to 21.1kV.
Technical data
• Outdoor use
• MV connection via plug-in socket Highest voltage for equipment 24 kV
• Metal enclosed anti- explosion safety design Power-frequency withstand voltage 50 kV
Lightening impulse test voltage 125 kV
• Separate neutral and ground circuit
Primary current Ipn 15 000/√3 ou 20 000/√3 V
• LV cabinet for disconnecting and switching
Secondary current Isn 100/√3 V
of LV side Frequency 50 Hz
• Fuse and switch operation display Rated output 30 VA
• Reliable system to isolate primary or secon- Accuracy class CL1 - CL0.5
dary faults that may occur in the installation. Ambient temperature - 25°C to + 40°C
Spare LV fuse set Delivered free with the VT set
Post insulators VT set / platorm Delivered free with the VT set
Protection Index IP2X Box - IP65 LVBox 32
These three-phase VT sets have been desig- Standards IEC - IEEE - CSA - AS - BS -
ned with ENEDIS to meet the voltage measu- CCTP ENEDIS HM-23/03/004/C Additif 1
rement needs of HV/MV primary substations,
as part of the implementation of the com-
pensated neutral HV system. Accessories / Options out of seope of contact
Set of 3 BIC collars for 50 mm2 cable Type CS44
A VT set consists of 3 plug-in voltage measu-
Set of 3 BIC collars for 95 mm2 cable Type CS44
ring transformers, in a galvanized steel enclo-
sure, and a LV cabinet for disconnecting, Primary voltage Upn 10 000/√3 V to 20 000/√3
interrupting LV circuits and signalling blown Assembly of the LV cabinet on the left
fuse, or interruption of LV circuits. Socomec fuse holder and auxiliary contact
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2RL/1
THREE-PHASE voltage TRANSFORMER SET FOR STEP DOWN SUBSTATION
Fuse &
connect
Neutral P2/S2 display
+ground STN
Rating
Plaqueplate
de firme
A B C
Ground connection
10mLiaison
2
cablecâble 10mm²
M12 ScrewM12
97
Fixations
PostSupport
insulator
isolant pour
1203
la protection masse
1164
1050
Platform M12
M12
BorneGround terminal
de neutre M12 sortie
sur sabot de terre STN isolé
de la rehausse à 2kV
4xM8 platform
Fixation au solfixing
de la
rehausse par
4 boulons M8
734 462
936 520
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2RL/1
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
MT20
Technical data
• Indoor Rated insulation level 3.6/16/45 kV to 24/50/125 kV
• 3.6 - 7.2 - 12 - 17.5 - 24 kV. Primary voltage Upn Up to 22000 V
• Output up to 17 kVA Secondary voltage Usn 10 to 600 V
• Compact size Frequency 50 or 60 Hz
Output Up to 17 kVA
Voltage factor 1.2Upn - 1.9Upn-30s 1.9Upn-8h
or 1.9Upn continuous
Voltage transformers vacuum Insulation class E
moulded in self extinguishing
Ambient temperature - 25°C to + 40°C
epoxy resin.
Standards IEC - IEEE - CSA - AS - BS
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2UA/9
SINGLE PHASE OR THREE PHASE VOLTAGE TRANSFORMERS - MA - MT SERIES
Selection table
Type Weight A B C D E F G H J K L M N
kg mm mm mm mm mm mm mm mm mm mm mm
MA10 175 460 490 420 465 290 240 385 250 125 430 335 - -
MA20 220 500 490 420 465 300 240 385 400 200 - - 70 35
MA25 285 570 570 420 545 315 240 385 400 - 493 320 - -
MA30 330 610 630 420 605 320 450 385 400 - 525 365 - -
MT3 86 397 300 220 275 177 310 200 220 110 240 188 - -
MT4 100 480 375 300 350 205 240 265 300 150 310 245 - -
MT5 135 490 405 300 380 195 240 265 340 170 - - 45 15
MT20 230 660 480 420 455 300 450 385 540 270 - - 150 45
MA35 - MA20 - MT5 - MT20 MA10 - MA25 - MA30 - MT4 - MT25 - MT3
A L
H E
J J M M8 terminals
N
D B
K
M12M8
terminals
terminals
F G
UPN 50x25 4 holes ø 12.5
C
Installation
Max tightening torques :
- M12 terminals : 13 N.m
- M 8 terminals : 10 N.m
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2UA/9
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
U24G4B
E36G2C
Technical data
Rated insulation level From 3.6/16/45 kV to 36/70/170 kV
• Auxiliary power Primary voltage Upn Up to 36 000V
• Indoor, Outdoor or Submersible Secondary voltage Usn 110 - 220 - 380 V
• 7.2 - 12 - 17.5 - 24 - 36 kV Frequency 50 or 60 Hz
Voltage factor 1,2 Un
• Touch proof finish
Thermal limiting output Up to 10 kVA
Surface finish Metallic surface (Touch proof)
Insulation class E
Ambient temperature - 5°C to + 40°C / 25°F to 100°F
1 or 2 pole voltage transformers vacuum Earth terminal On base plate
moulded in self extinguishing epoxy resin Standards IEC - IEEE - CSA - AS - BS - UNE
powered by voltages between phase and
earth up to 36 000/√3 V. Other characteristics on request
Secondary voltage Usn 24/√3 to 380/√3 V
The user connects an insulated cable equi- Setting taps +/- % +/-2.5 or 5 %
ped with a standard female or male plug. Secondary tapping 33
Plug -in and plug-out have to be done with
Ambient temperature - 25°C to + 70°C / -13°F to +160°F
no voltage present.
Earth connector On base plate
Antiferroresonance Low induction - Air gap
The transformer’s surface is coated with a
metallic compound that ensures a safe Accessoires / Options
repartition of the magnetic field and zero-
Fixing plate Standard
potential surface.
Surface finish Submersible
The anti-explosion system exclusively deals Secondary terminal Indoor : cover (IP31)
with secondary fault (short-circuit, maintai- Outdoor : waterproof cover (IP54)
ned overload...). or Submersible connector (IP67or IP68)
Under no circumstances it can handle a Anti-explosion device Option
primary fault (overvoltage, ferroresonance,
lightning, switching...)
This system must be associated with a cut-off
relay. Maintaining feeding of VT would result
in its destruction.
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET: M2RM/1
SINGLE PHASE auxiliary power TRANSFORMERS 1 OR 2 INSULATED POLE - E..G.. AND u..G.. a/b/c/W SERIES
Denomination example :
E 3 6 G 2 C
Primary terminal type
UNE-EN IEC 50181 H.V. PRIMARY TERMINAL TYPE IEEE Std. 386TM H.V. PRIMARY TERMINAL TYPE
TYPE W - up to 21.1kV.
TYPE B - up to 36 kV.
TYPE C - up to 36 kV.
TYPE A - up to 24 kV.
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2RM/1
SINGLE PHASE auxiliary power TRANSFORMERS 1 OR 2 INSULATED POLE - E..G.. AND u..G.. a/b/c/W SERIES
SINGLE PHASE PLUG-IN VOLTAGE TRANSFORMERS FOR AUXILIARY POWER
Use: Outdoor.
Plastic type: White - IP54 - Holes: 1xPG11 + 1xPG21 Metallic type: Inox - IP55 - Holes: 2xPG21
(consult for other options)
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2RM/1
SINGLE PHASE auxiliary power TRANSFORMERS 1 OR 2 INSULATED POLE - E..G.. AND u..G.. a/b/c/W SERIES
U24G71A
Technical data
• Indoor Rated insulation level From 3.6/16/45 kV to 24/50/125 kV
• 3.6 - 7.2 - 12 - 17.5 - 24 kV Primary voltage Upn Up to 24kV
• Primary voltage up to 24kV Secondary voltage Usn 100 - 110 - 120 - 220 - 230 V
• Auxilary power up to 10kVA Frequency 50 or 60 Hz
• Secondary setting Voltage factor 1.05 Upn
Thermal limiting output 4 - 5 - 8 - 10 kVA
Insulation class E
Ambient temperature - 5°C to + 40°C / 25°F to 100°F
2-pole voltage transformer isolated Standards CEI - IEEE - CSA - AS - BS - UNE
in self-extinguishing molded epoxy
33
resin to provide auxiliary power up to
Other characteristics on request
10kVA in closed installation, away from
Secondary voltage Usn From 100 to 600 V
people (cubicle, concrete/skid com-
Ambient temperature From - 25°C to + 70°C / -13°F to + 160°F
partment...)
Secondary setting +/-2.5% +/-5%
This transformer is equipped with two
type A 250A plug-in quick connectors.
The user connects with two insulated
cables equipped with a standardized
plug.
©RS ISOLSEC PAGE 1/2 contact : [email protected] - non binding information - DATASHEET : M2SH/1
SINGLE PHASE 2-POLE PLUG-IN VOLTAGE TRANSFORMERS - INDOOR - secondary voltage taps - U24G71A
A
B 600
350 420
D
O 110
200
166
A B
636
Name plate
450
35
30
15
20
100 60 60 60 60 60 60 20 40
420
6 secondary terminals M12
Temperature sensors (in option)
4 terminals M4
340
4 lifting lugs
40
Name plate
95 450 95 Connexion diagram
600 (With optional secondary
Connexion taps)
diagram
Schéma de branchement
21000V
A B
380
page :
2/2
©RS ISOLSEC PAGE 2/2 contact : [email protected] - non binding information - DATASHEET : M2SH/1
MEDIUM VOLTAGE INSTRUMENT TRANSFORMERS
CME III / I
Technical data
• Outdoor Highest voltage for equipment 7.2/20/60 kV up to 52/95/250 kV
• Combined CT and VT Primary current Ipn Up to 2 500A
Secondary current Isn 5 or 1 A
Primary voltage Upn Up to 52 000/√3 V
Single or three phase assembly made of Secondary voltage Usn 100/√3 - 110/√3 - 120/√3 - 220/√3 V
respectively 1 voltage transformer and 1 Continuous thermal current 1.2 Ipn
current transformer, or 3 voltage transfor- Short-time thermal current Ith 80 Ipn .1s
mers and 3 current transformers. Dynamic current Idyn 2.5 Ith
Surface finish Polyurethane coating
For measuring AC voltages between Insulation class F
phases or phase to earth, and for AC cur- Ambient temperature - 5°C to + 40°C
rents from 0 to 2 500 A, up to 52 000 /√3 V. Standards IEC - IEEE - CSA - AS - BS - UNE
34
Delivered mounted on a metal platform,
they are equipped with secondary wiring Other characteristics on request
for direct connexion to the switchboard
Resistor for antiferroresonnance Option
terminals.
Surface finish Silicone coating / metallized
Anti-explosion system Option
The anti-explosion system exclusively deals
Cables for secondary connexions According to customer requirement
with secondary fault (short-circuit, maintai-
Ambient temperature - 25°C to + 70°C
ned overload...). Under no circumstances
it can handle a primary fault (overvoltage, Fixing Any type of post
ferroresonance, lightning, switching...)
This system must be associated with a cut-
off relay. Maintaining feeding of VT would
result in its destruction.
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2XA/8
SINGLE OR THREE PHASE ASSEMBLY FOR OUTDOOR USE - CME SERIES
Installation
- Specification of customer requirements in terms of platform fixing (type of post, material, height, etc...)
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2XA/8
OTHER MEDIUM VOLTAGE EQUIPMENT
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2WA/10
CAPACITIVE VOLTAGE DIVIDERS
Diagram Installation
Tightening torque of M12-16 inserts : 25Nm
Un
C1
Us
C2
Neon
Lampelamp
néon
C1
Us= Un
C1+C2
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2WA/10
OTHER MEDIUM VOLTAGE EQUIPMENT
DAMPING REACTORS
SA
• Indoor or outdoor
• Cast resin Technical data
• From 3.6 to 36 kV.
Rated insulation level 3.6/16/45 kV to 36/70/170 kV
• Without magnetic core
Frequency 50 or 60 Hz
Impedance Up to 1000 μH
Series or damping reactors for me- Rated current Up to 650A
dium voltage are encapsulated in Main conductor Copper
epoxy resin. They are without ma-
Short-time thermal current Ith 43In-1s or 25In-3s
gnetic core.
Insulation class E
The damping reactors SA, SB and SC Ambient temperature -25°C to +40 °C
type limit current transients and surge Standards IEC - IEEE - CSA - AS - BS
currents to acceptable levels for the
capacitor units and corresponding
control systems.
Other characteristics on request
Short time thermal current Ith Up to 500In.1s
Damping reactors are necessary in Main conductor Aluminum
the following cases: Ambient temperature -40°C to +70°C
• Capacitor banks with several steps
• Several capacitor banks connec-
Accessories / Options
ted in the same busbar
• Very high network short-circuit Insulators ISO See datasheet M2VN 36
power in relation to the power of the
capacitor bank to be connected
• Frequent capacitor bank opera-
tions
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2VA/10
damping REACTORS
SELF - SA - SB - SC
G
5
F
F/2
D 6 M12 E
OA
OB
O8,5
25
50
15 30 C
Installation
Tightening torque M12 inserts: 20 Nm
M16 inserts: 25 Nm
G
5
F
SELF - SA - SB - SC WITH INSULATORS ISO OPTION
F/2
D 6 M12 E
OA
OB
O8,5
25
50
Height depending on the type of insulator.
15 30 C Please contact us
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2VA/10
OTHER MEDIUM VOLTAGE EQUIPMENT
POST INSULATORS
Technical data
• Indoor or outdoor Rated insulation level 2.4/10/20 kV to 36/70/170 kV
• Cast resin Insulation class E
• 2.4 to 36 kV. Type Indoor or outdoor
Fixing insert M6 to M20
• Good dielectric stength
Ambient temperature - 25°C to + 40°C
• Long creepage distance
37
©RS ISOLSEC PAGE 1/2 contact: [email protected] - non-binding information - DATASHEET : M2VN/9
post insulator
A A
A A
A
A
M2 M2
1
M2 M2 M2 M2
D D D D D D
Installation
Tightening torque: M6-9 inserts: 6Nm
M10-16 inserts: 20Nm
M12-16 inserts: 25Nm
M16-20 inserts: 76Nm
M20-40 inserts: 150Nm
©RS ISOLSEC PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2VN/9
OTHER MEDIUM VOLTAGE EQUIPMENT
BUSHING INSULATORS
Technical data
©RS ISOLSEC PAGE 1/4 contact: [email protected] - non-binding information - DATASHEET : M2WN/11
BUSHING INSULATORS
7
ISOTRA 24 B 800 24 20 160 130 90 280 235 25 680 12 425
1250 30 10
indoor only
800 20 5
ISOTRA 24 24 160 130 90 280 235 25 640 12 425
1250 30 9
indoor only
ISOTRA 37 800 30 14
36 140 120 110 360 401 34 945 60 1040
1250 30
180
630 20 18
800 25 19
TIRE 36 36 118 100 110 369 70 980 650
1250 32 20
2000 40 21
indoor only
©RS ISOLSEC PAGE 2/4 contact: [email protected] - non-binding information - DATASHEET : M2WN/11
BUSHING INSULATORS E F OA
20
110 110 OB
100
OC
ISOTRA371 B 4000
ISOTRA 4500 7.2
3 60 200 160 100 100 95 20 505 14 120-300 16
25
25 O14 4OI
indoor and outdoor G
Od
H
indoor only
TM 24 B
2000
2500 24 500 1000 800
80
100
40
50
4 x Ø15
4 x Ø15 375
39
42
38
3000 125 70 5 x Ø15 46
indoor only
©RS ISOLSEC PAGE 3/4 contact: [email protected] - non-binding information - DATASHEET : M2WN/11
BUSHING INSULATORS
Installation
Maximum tightening torque:
- terminals M6 : 2 N.m
- terminals M8 : 13 N.m
- terminals M10 : 20 N.m
- on hole resin Ø10 : 20 N.m
- on hole resin Ø12 : 40 N.m
©RS ISOLSEC PAGE 4/4 contact: [email protected] - non-binding information - DATASHEET : M2WN/11