2. Delivery and Completion Schedule
Tender No: TR212/2023/2024/G/522
The delivery or completion period shall commence from the date of contract signature and effectiveness. Refer to the
Incoterm in the GCC13 for the interpretation of the delivery period.
51
nest-document-section-data#02a523c6-067f-4194-af4a-8bab6fce1824#
3. Technical Specifications
52
Rated Frequency 50Hz
Rated Power Frequency 275kV
Withstand Voltage (1 min)
Impulse withstand BIL ±650 kvp
(1.2/50/micro-Sec) Line to earth
Screen insulation, Lightning 75kV
impulse voltage
Screen insulation, DC Voltage 20kV
(1min)
Pollution level 4 31 mm/kV
Rated short time withstand 31.5 kA (rms)
current (1 sec)
Size of the cable (cross section 1000 mm square
area)
Applicable standard IEC60815
Application Cables with PE, XLPE and EPR insulation with extruded semi-conductive
layers, with copper wire screen, lead sheath, corrugated AL-sheath or
combination of CU-screen/Pb -sheath
53
Permissible Pulling force 30KN
Permissible short circuit current 59.6kA
Earth fault current Same as short circuit current of metallic screen
Maximum Operating Voltage 145kV
Power-frequency withstand 650kV
voltage (1 min)
Rated voltage between conductor 76kV
and sheath
Maximum short-circuit current of 12.3/16.6/34.7kA
metallic screen for 1 s/0.5 s/0.1 s
(calculation is according to IEC
60949)
Earthing Condition - trefoil Without circulating current
formation
Permissible current rating buried 825A
20⁰C - trefoil formation
Permissible current rating buried 710A
30⁰C - trefoil formation
Permissible current rating in air 1135A
30⁰C - trefoil formation
Permissible current rating in air 905A
50⁰C - trefoil formation
Permissible current rating buried 905A
20⁰C - flat formation
Permissible current rating buried 780A
30⁰C - flat formation
Permissible current rating in air 1295A
30⁰C - flat formation
Permissible current rating in air 1040A
50⁰C - flat formation
Maximum DC resistance of the 0.029ohm/km
conductor at 20⁰C
Nominal phase capacitance 0.21µf/km
Operating voltage 132kV
System nominal frequency 50Hz
54
Rated Power Frequency 275
Withstand Voltage (1 min)
Impulse withstand BIL ±650 kVp
(1.2/50/micro-Sec) Line to earth
Grounding Effectively Earthed
Rated short time withstand 31.5 kA (rms)
current (1 sec)
Size of the cable (cross section 1000 mm²
area)
Creep age distance of cable 4495 mm
sealing end
Design (i) Silicone insulator with alluminium base plate and head ring filled with
polyisobuthylene insulation oil. (ii) The insulator should have alternating
sheds (extended creepage distance) or sheds according to DIN 48115 (iii) Pre-
moulded silicone rubber stress cone (iv) Bottom seal by silicone-rubber sleeve
(v) Aluminium funnel below the seal serves as connector for corrugated Al-
sheaths.
Application Shall be able to be used on cables with PE, XLPE and EPR insulation with
extruded semi-conductive layers, with copper wire screen, lead sheath,
corrugated AL-sheath or combination of CU-screen/Pb -sheath.
55
Size of the cable (cross section 1000 mm square
area)
Applicable standard IEC60815
Application Cables with PE, XLPE and EPR insulation with extruded semi-conductive
layers, with copper wire screen, lead sheath, corrugated AL-sheath or
combination of CU-screen/Pb -sheath
56
Earthing Condition - trefoil Without circulating current
formation
Permissible current rating buried 825A
20⁰C - trefoil formation
Permissible current rating buried 710A
30⁰C - trefoil formation
Permissible current rating in air 1135A
30⁰C - trefoil formation
Permissible current rating in air 905A
50⁰C - trefoil formation
Permissible current rating buried 905A
20⁰C - flat formation
Permissible current rating buried 780A
30⁰C - flat formation
Permissible current rating in air 1295A
30⁰C - flat formation
Permissible current rating in air 1040A
50⁰C - flat formation
Maximum DC resistance of the 0.029ohm/km
conductor at 20⁰C
Nominal phase capacitance 0.21µf/km
Operating voltage 132kV
System nominal frequency 50Hz
57