The FC-21 and FC-22 are multifunction flow computers that can be used for liquid, gas, steam, and heat flow applications. They contain multiple flow equations and can monitor values such as volume flow, corrected volume flow, mass flow, temperature, pressure, and density. They have isolated analog and pulse outputs and RS-232 communication for data logging and remote reading. Both models are programmable from the front panel and have display options, power supply options, and can operate from 0 to 50 degrees Celsius.

Uploaded by

Ct Hardiyanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

FC21 22

The FC-21 and FC-22 are multifunction flow computers that can be used for liquid, gas, steam, and heat flow applications. They contain multiple flow equations and can monitor values such as volume flow, corrected volume flow, mass flow, temperature, pressure, and density. They have isolated analog and pulse outputs and RS-232 communication for data logging and remote reading. Both models are programmable from the front panel and have display options, power supply options, and can operate from 0 to 50 degrees Celsius.

Uploaded by

Ct Hardiyanto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MultiFunction Flow Computers

FC-21

FC-21 shown smaller


than actual size.

68 x 138 mm (2.67 x 5.43") cutout

FC-22

FC-22-V shown
smaller than actual size.

U Custody Transfer with Audit Trail OMEGA’s FC-21 and FC-22 flow computers
U Liquid, Gas, Steam, are useful in a variety of flowmeter applications.
The FC-21 is suitable for liquid batching, volumetric
and Heat Flow Equations batching, and corrected-volume applications. The
U Menu-Selectable Inputs/Outputs FC-22 is designed for liquid, gas, steam, and heat
U Isolated Pulse and Analog Outputs applications. Both models can store multiple
flow equations.
U RS232 Communications with
These versatile instruments are programmable from
Windows Setup Software the front panel. During setup, the user can assign
inputs and outputs. For example, the isolated analog
output can monitor the volume flow, corrected-
volume flow, mass flow, temperature, pressure, or
density. The RS232 serial port allows for data logging,
transaction printing, or connection to a modem for
remote meter reading.
M-27
(inch) (inch)

FC-21/22 Front Dimensions FC-21/22 Side Dimensions

Specifications
SM

Environmental
Operating Temperature: 0 to 50°C
Extended Warranty
(32 to 122°F) Program
Storage Temperature: -40 to 85°C OMEGACARESM extended warranty
(-40 to 185°F) program is available for models shown on
Relative Humidity: 0 to 95%, this page. Ask your sales representative
non-condensing for full details when placing an order.
Display Type: Alphanumeric, 2 lines, OMEGACARESM covers parts, labor and
7.6 mm (0.3") characters, backlit LCD equivalent loaners.
or VFD (specify at time of order) FC-21/22 Panel Cutout
Mounting: Panel, wall mount
Power Supply:
FC-21: 110, 220 Vac standard;
12 or 24 Vdc optional
FC-22: 85 to 275 Vac standard; To Order
24 Vdc optional Model No. Description
Signal Inputs FC-21 Multifunction flow computer for liquid applications
Pulse:
High-Level Pulse: FC-22  Multifunction flow computer for liquid, gas, steam, and
heat applications
Low = 0 to 1 Vdc; high = 3 to 30 Vdc
Low-Level Pulse: FC-21-V Multifunction flow computer with VFD display
10 mV or 100 mV (magnetic pickup) FC-22-V Multifunction flow computer with VFD display
Frequency: Up to 20 kHz FC-21-NEMA Flow computer with NEMA 4 (IP65) wall mount
Analog
Voltage: 0 to 10 Vdc, 0 to 5 Vdc, FC-22-NEMA Flow computer with NEMA 4 (IP65) wall mount
1 to 5 Vdc (FC-21 only) FC-21-EXP Flow computer factory mounted inside explosion-proof box
Current: 4 to 20 mA, 0 to 20 mA (no button access)
Temperature Input FC-22-EXP Flow computer factory mounted in explosion-proof box
RTD: 100 Ω DIN RTD (no button access)
Auxiliary/Compensation:
FC-21: Temperature, density
FC-22: 2 temperature,
pressure, density
Excitation Voltage:
M
Options
FC-21: Programmable—5 Vdc,
12 Vdc or 24 Vdc @ 100 mA Suffix Description
FC-22: Fixed @ 24 Vdc -220VAC 220 Vac power option (optional for model FC-21, 85 to 275 Vac
Relays: Menu assignable for each power standard on model FC-22)
relay; 2 SPDT relays rated 5 A, 240 Vac -12VDC 12 Vdc power option (available for FC-21 only)
or 30 Vdc; Contact Flow Engineering -24VDC 24 Vdc power option
for additional information
Isolated Output: Menu assignable -RS485 RS485 serial connector
Analog: 4 to 20 mA; 1000 Ω Comes complete with operator’s manual.
maximum load Ordering Examples: FC-21, multifunction flow computer for liquid applications.
Pulse: Open collector; 24 Vdc OCW-3, OMEGACARESM extends standard 2-year warranty to a total of 5 years.
(FC-22 only) FC-22, multifunction flow computers for liquid, gas, steam and heat applications.