This user manual provides troubleshooting guidance for a KNX Universal Dimming Actuator. It lists several potential exceptions with dimming LED lamps, such as flickering, unstable output, or not functioning properly in certain brightness ranges. For each exception, it suggests possible causes such as incompatible dimming curves between the lamp and driver, voltage issues, or protection features being triggered. It recommends solutions like adjusting dimming parameters, using a user-defined dimming curve, reducing the load power, or replacing components if issues persist.

Uploaded by

muhammad zakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views78 pages

Universal Dimming KNX

This user manual provides troubleshooting guidance for a KNX Universal Dimming Actuator. It lists several potential exceptions with dimming LED lamps, such as flickering, unstable output, or not functioning properly in certain brightness ranges. For each exception, it suggests possible causes such as incompatible dimming curves between the lamp and driver, voltage issues, or protection features being triggered. It recommends solutions like adjusting dimming parameters, using a user-defined dimming curve, reducing the load power, or replacing components if issues persist.

Uploaded by

muhammad zakir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 78

User manual

KNX Universal Dimming Actuator,


1/2/4-Fold_V1.0

ADUD-01/02.3

ADUD-02/02.3

ADUD-04/02.3

KNX/EIB Home and Building Control System


Attentions
1.Please keep devices away from strong magnetic field, high temperature,

wet environment;

2.Do not fall the device to the ground or make them get hard impact;

3.Do not use wet cloth or volatile reagent to wipe the device;

4.Do not disassemble the devices.


When using this product, please pay attention to analysis of the following

troubleshooting.

NO. Exception Possible cause Solution Remark


Increase the min.
brightness appropriately
to debounce
Lamp flickers in the Lamp driver works Use the user defined
1
low brightness unstably at low voltage curve, and set the
output value when 1%
as the min. brightness
that can be stable
Decrease the max.
brightness appropriately
to avoid the invalid
There is no obvious The LED has reached control
2 differences for LED in the highest brightness Use the user defined
the high brightness after a certain voltage curve, and set the
output value when 100%
as the control value of
LED highest brightness
Enable the additional
Lamp driver needs an startup characteristic
Flicker or unstable
3 extra startup voltage for and set its parameter, to
when LED startup
stable output avoid the flicker when
startup
Enable the additional
The min. control value
Lamp driver needs an startup characteristic
when lamp off is
4 extra startup voltage for and set its parameter, to
higher than the value
lamp on normally improved dimming
when lamp on
effect
Check the lamp
Lamp dose not support
characteristic supports
dimming
dimming or not
Incompatible between Check the lamp is
lamp and driver power matched to the driver or
supply not
Adjust the ETS If there is no
Incompatible of load
parameter and check
type or dimming curve improvement, it is
Lamp flickers in again
5 suggested to
dimming Extend the dimming
Brightness changed in replace the lamp or
time and change the
dimming is too fast driver
dimming curve
Incompatible of
Use the user defined
dimming curve if only
curve to adjust the
flicker in a partial curve
flickering curve
in the middle
If only flicker in the high Decrease the max.
brightness brightness value
NO. Exception Possible cause Solution Remark

If there is no
Lamp driver is not good Test with an additional improvement, it is
Lamp flickers in enough, unstable incandescent lamp or
5 suggested to
dimming voltage, compatibility electronic dummy load
issue in parallel replace the lamp or
driver

Use the user defined


curve, and set the
The dimmable range is It is the limitation of the
output value when 1%
not 0-100%, not a good operation voltage range
6 as the min. brightness,
experience with user and effect of lamp
set the output value
operation driver
when 100% as the
control value of lamp
highest brightness
Change the curve to one
with a lower change
value, such as
Lamp is still brighter at Incompatible of
quadratic, cubic,
lower brightness, and dimming curve
7 exponential, logarithmic,
have a small even use the user
dimmable range defined curve
Possible the min. Check and decrease the
brightness is high min. brightness
Operation voltage
Check and reconnect Configure the
failure
The connected lamp monitoring the
has been overloaded group addresses of
and caused the Reduce the load power
abnormal status
protection of
over-temperature objects, re-check to
Reconnect the wiring confirm there is an
Output terminal is
Switch off abnormally and test that there are
8 short-circuit and trigger alarm telegram or
or can not turn on no problems before
the protection
power up again not, if still exist
The inrush current of Reduce the load power alarm and improve
lamp driver is too big Change to trailing edge again according the
and trigger the Change a better lamp or
protection of over-load alarm telegram
driver
Bus diagnostics and
Bus voltage failure confirm to connect
normally
Test with an additional
incandescent lamp or
electronic dummy load
in parallel If there is no
Connect an external improvement, it is
Incompatible between switch actuator channel
9 LED can not turn off suggested to
lamp driver and dimmer with output in
series,linking the switch replace the LED or
object together to work driver
simultaneously
Change a better LED or
driver
Contents

Chapter 1 Summary -----------------------------------------------------------------------------------------------------1


Chapter 2 Technical Data -----------------------------------------------------------------------------------------------3
2.1. Load type -------------------------------------------------------------------------------------------------------- 5
2.2. Operation mode ------------------------------------------------------------------------------------------------- 8
Chapter 3 Dimension and Connection Diagram ----------------------------------------------------------------------9
3.1. Dimension drawing --------------------------------------------------------------------------------------------- 9
3.2. Connection Diagram ------------------------------------------------------------------------------------------ 10
Chapter 4 Project Design and Programming ----------------------------------------------------------------------- 11
Chapter 5 Parameter setting description in the ETS ---------------------------------------------------------------13
5.1. KNX Secure ---------------------------------------------------------------------------------------------------- 13
5.2. Parameter window "General" --------------------------------------------------------------------------------- 17
5.3. Parameter window "Output setting" ------------------------------------------------------------------------- 20
5.3.1. Parameter window "Channel" --------------------------------------------------------------------------- 22
5.3.2. Parameter window "User defined dimming curve" --------------------------------------------------- 32
5.3.3. Parameter window "Extension function" -------------------------------------------------------------- 35
5.4. Parameter window "Logic" ------------------------------------------------------------------------------------49
5.4.1. Parameter window "AND/OR/XOR" ---------------------------------------------------------------------50
5.4.2. Parameter window "Gate forwarding" ------------------------------------------------------------------52
5.4.3. Parameter window "Threshold comparator" ---------------------------------------------------------- 54
5.4.4. Parameter window "Format convert" ------------------------------------------------------------------ 56
5.4.5. Parameter window "Gate function" ---------------------------------------------------------------------57
5.4.6. Parameter window "Delay function" --------------------------------------------------------------------59
5.4.7. Parameter window "Staircase lighting" ---------------------------------------------------------------- 59
Chapter 6 Description of Communication Object ------------------------------------------------------------------ 61
6.1. "General" Communication Object ---------------------------------------------------------------------------- 61
6.2. "Output setting" Communication Object -------------------------------------------------------------------- 62
6.3. "Logic" Communication Object -------------------------------------------------------------------------------67
6.3.1. "AND/OR/XOR" Communication Object ----------------------------------------------------------------67
6.3.2. "Gate forwarding" Communication Object -------------------------------------------------------------67
6.3.3. "Threshold comparator" Communication Object ----------------------------------------------------- 68
6.3.4. "Format convert" Communication Object --------------------------------------------------------------69
6.3.5. "Gate function" Communication Object ----------------------------------------------------------------71
6.3.6. "Delay function" Communication Object ---------------------------------------------------------------72
6.3.7. "Staircase lighting" Communication Object ----------------------------------------------------------- 73
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 1 Summary

KNX Universal Dimming Actuator,1/2/4-Fold (hereinafter referred to as Dimmer) has 1/2/ 4 output

channels, and it can connect with dimmable lamps (such as incandescent lamps, halogen lamps,

energy-saving lamps, LED, etc.), and you can dim, preset scene, switch these lamps or other operations

via the bus. In addition, as well as KNX Data Secure.

This dimmer is a modular installation device for fast installation in the distribution board on 35 mm

mounting rails to DIN EN 60 715, the output adopts screw terminal to realize electrical connection. Bus

connection is directly connected via KNX terminal, the additional power supply is not required except

KNX bus.

You can build the various scenes with the dimmer, such as watch movie, entertainment, dinner and

rest, and so on; its brightness value can be set as any value (1-100%); it is able to set the duration time

to dim up or down to the target brightness and the gradual speed to extend the luminaries life and save

energy.

The physical address assignment and parameter settings can be used with the engineering tool

software ETS (version ETS5 or above) with the .knxprod file.

In use you need to note the type of connected electrical load, thus reasonable select them and

note their technical performance. If the technical performance of the selected load is not consistent

with the technical performance of the dimmer, it is possible to affect the dimming effect.

The manual provides detailed technical information about the dimmer, including installation and

programming details, and explains how to use the dimmer in conjunction with examples in actual use.

1
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

The functions are summarized as followed:

Switch, Relative dimming/Absolute dimming

Status feedback of switch, brightness, as well as abnormal status (short-circuit, over-voltage,

over- temperature and operating voltage failure)

Reset behaviour after download/bus failure/bus recovery

6 dimming curves, including Linear, Exponential, Cubic, Quadratic, Logarithmic, Root and

User defined curves

Leading edge/Trailing edge phase cut dimming

Manual operation and Output indication function

Central control function (Only apply for 2/4-fold)

Individual or parallel output (Parallel can expand the load capacity, only apply for 2/4-fold)

Staircase lighting, Flashing switch and Delay switch, as well as Scene, Threshold, Forced

operation, Safety operation and Operation hours counter

Logic function, with AND, OR, XOR, Gate forwarding, Threshold comparator, Format convert,

Gate function, Delay function and Staircase lighting

Support the KNX Data Secure

2
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 2 Technical Data

Power Supply Bus voltage 21-30V DC,via the KNX bus

Bus current <6mA/24V, <5.5mA/30V (1 fold)

<7mA/24V, <6mA/30V (2 fold)

<7.5mA/24V, <6.5mA/30V (4 fold)

Bus consumption <165mW (1 fold)

<180mW (2 fold)

<195mW (4 fold)

Output Dimming channel 1/2/4 folds, separate phase connection

Max. output capacity 300W (per channel, Incandescent/ Halogen/ LED,

trailing edge)

Parallel: 2 channels 500W /3 channels 750W/

4 channel 1000W

Un rated voltage 110~230 V AC (50/60HZ)

Protection Short-circuit, Over-voltage, Over-temperature

Standby loss Approx. 0.7W

Power loss ≤2W / per channel

Connection KNX Bus connection terminals

Outputs Screw terminals

Wire Range 0.2—2.5mm2 (1 fold)

0.2—6.0mm2 (2/4 fold)

Operation and Programming button and Red LED For assigning the physical address

display

3
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Green LED flashing For displaying application layer running normally

Channel button For manual switching or dimming

Channel indication LED Indicates channel status of the load

Man./Auto. button Change the Man./Auto. mode

Man./Auto. LED Indicate the Man./Auto. mode status

Temperature Operation –5 °C ... + 45 °C

Storage –25 °C ... + 55 °C

Transport – 25 °C ... + 70 °C

Environment Humidity <93%, except dewing

Mounting On 35mm mounting rail

Dimension 36 x 90 x 64 mm (1 fold)

72 x 90 x 64 mm (2 fold)

144 x 90 x 64 mm (4 fold)

Weight 0.2kg (1 fold)

0.3kg (2 fold)

0.5kg (4 fold)

4
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

2.1.Load type

Max. Load capacity (110V) Max. Load capacity (230V)


Load type
Leading edge Trailing edge Leading edge Trailing edge

Incandescent lamp 10...150W 10...150W 10...300W 10...300W

HV Halogen lamp 10...150W 10...150W 10...300W 10...300W

LV Halogen lamp with Electronic 10...150W 10...150W 10...300W 10...300W

transformer

HV LED 2...30W 2...150W 2...60W 2...300W

LV LED with Electronic transformer 2...40W 2...150W 2...80W 2...300W

LV LED with Constant current driver 2...40W 2...150W 2...80W 2...300W

(Down light, Spotlight)

LV LED with Constant voltage driver 2...40W 2...150W 2...80W 2...300W


Resistive load

Capacitive load

Inductive load

LED load

5
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Individual or parallel outputs can be selected for 2/4-fold dimmer, and the parallel can expand the
load capacity. Load type as following:
Load type Max. Load capacity (110V)
Parallel with 2 channels Parallel with 3 channels Parallel with 4 channels

Leading edge Trailing edge Leading edge Trailing edge Leading edge Trailing edge

Incandescent lamp 300W 300W 400W 400W 500W 500W

HV Halogen lamp 300W 300W 400W 400W 500W 500W

LV Halogen lamp with Electronic 300W 300W 400W 400W 500W 500W

transformer

HV LED - 300W - 400W - 500W

LV LED with Electronic transformer - 300W - 400W - 500W

LV LED with Constant current driver - 300W - 400W - 500W

(Down light Spotlight)

LV LED with Constant voltage driver - 300W - 400W - 500W

Load type Max. Load capacity (230V)


Parallel with 2 channels Parallel with 3 channels Parallel with 4 channels

Leading edge Trailing edge Leading edge Trailing edge Leading edge Trailing edge

Incandescent lamp 500W 500W 750W 750W 1000W 1000W

HV Halogen lamp 500W 500W 750W 750W 1000W 1000W

LV Halogen lamp with Electronic 500W 500W 750W 750W 1000W 1000W

transformer

HV LED - 500W - 750W - 1000W

LV LED with Electronic transformer - 500W - 750W - 1000W

LV LED with Constant current driver - 500W - 750W - 1000W

(Down light,Spotlight)

LV LED with Constant voltage driver - 500W - 750W - 1000W

6
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Note:

It is not permitted to connect inductive and capacitive loads together at the same output.

However, mixing of loads such as capacitive + resistive loads or inductive + resistive loads is allowed

to connect, but power reduction needs to be considered. It is more advisable to connect the same type

of loads for an output.

The max. load capacity depends on the surge current and power loss of the lamp, these types of

lamp will cause large heating and high surge current in leading edge mode, especially LED lamp, so it

is not recommended to drive LED in leading edge mode, make sure the connected lamp do not trigger

over-load or over-heating protection.

7
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

2.2.Operation mode

Dimmer system is dimming in leading or trailing edge.

1.Dimming in leading edge:

Explanation of the dimming system: turn off dimmer in leading edge and turn on in trailing edge. As

shown in the following figure, no voltage input from zero point until dimmer is turned on. It is suitable

for inductive loads.

2.Dimming in trailing edge:

Explanation of the dimming system: turn on dimmer in leading edge and turn off in trailing edge. As

shown in the following figure, dimmer will be turned on the zero-crossing point, during this moment, the

voltage is very low and there is no inrush current to the load. In this way, there is no minimum load

requirement, so that allows for better performance of a single lighting or a very small load and extends

the life of the lamp, as well as reduce the interference to the power grid. It is suitable for resistive or

capacitive loads.

8
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 3 Dimension and Connection Diagram

3.1.Dimension drawing

1-Fold

2-Fold

4-Fold

9
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

3.2.Connection Diagram

Parallel with 2 channels

Parallel with 3 channels


Individual 4 channels

Individual 1 channel Individual 2 channels Parallel with 2 channels Parallel with 4 channels

①Programming button ②Programming LED

③KNX bus connection terminal ④Input, Output, load terminal

⑤ Channel indication LED: in normal mode, LED off is the lamp off, LED on is the lamp on; in manual

mode, flashing slowly is dimming manually. Flashing fast is channel abnormality (Short-circuit,

Over-voltage, Over-temperature, Operating voltage failure)

⑥Channel button: when no ETS configuration, press to switch on/off; in manual mode, short press to

switch on/off, long press for dimming up/down, long press then release to stop dimming

⑦⑧Man./Auto. operation switch button and status indicating LED:

Long press to switchover Man. and Auto. mode, LED on is Man. mode and off is Auto. mode.

Reset the device to the factory configuration: press the programming button and hold for 4 seconds

then release, repeat the operation for 4 times, and the interval between each operation is less than 3

seconds

10
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 4 Project Design and Programming

Maximum of Maximum Maximum


Secure group
Application communication number of group number of
addresses
objects addresses associations

KNX Universal Dimming Actuator,


237 280 280 160
1-Fold/1.0

KNX Universal Dimming Actuator,


237 280 280 200
2-Fold/1.0

KNX Universal Dimming Actuator,


237 280 280 280
4-Fold/1.0

General function

General function includes device In operation setting, central control (Switch, Dimming), safety

function, as well as manual operation and output indication function.

In addition, central control function only applies for 2/4-Fold Dimmers, and it is not supported by

1-Fold Dimmer.

Output channel

There are 1/2/4 output channels according the product type, support to switch, relative

dimming/absolute dimming, feed back the status of switch, brightness and the abnormal status

(short-circuit, over-voltage, over- temperature and operating voltage failure), as well as reset behaviour

after download/bus failure/bus recovery. Individual or parallel outputs can be selected, and the parallel

can expand the load capacity, which only applies for 2/4-fold.

Load types and dimming curves can be independently configured, as well as extension functions

including Staircase lighting, Flashing switch, Delay switch, Scene, Threshold, Forced operation, Safety

operation and Operation hours counter.

For output function, the definition of function priority: Manual > Forced > Safety > other functions,

after exiting higher priority, the next priority action needs to be executed.
11
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Logic function

Up to support 8 channels of logic, each channel up to support 8 inputs and 1 logic result.

Logic function support functions, including AND, OR, XOR, Gate forwarding, Threshold comparator,

Format convert, Gate function, Delay function and Staircase lighting.

12
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 5 Parameter setting description in the ETS

5.1.KNX Secure

Dimmer is a KNX device that complies with the KNX secure standard. That is, you can run the

device in data secure mode.

Fig.5.1 (1) "KNX Secure" parameter window

The device with KNX secure will be displayed notes on ETS, as shown as Fig.5.1(1).

If secure commissioning is actived in ETS project, the following information must be considered during

device debugging:

It is essential to assign a project password as soon as a KNX Secure device is imported into a

project. This will protect the project against unauthorized access.

The password must be kept in a safe place – access to the project is not possible without it (not

even the KNX Association or device manufacturer will be able to access it)!

Without the project password, the commissioning key will not be able to be imported.

A commissioning key is required when commissioning a KNX Secure device (first download). This

key (FDSK = Factory Default Setup Key) is included on a sticker on the side of the device, and it must be

imported into the ETS prior to the first download:

On the first download of the device, a window pops up in the ETS to prompt the user to enter the

key, as shown in Fig.5.1 (2) below.

The certificate can also be read from the device using a QR scanner (recommended).

13
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

1.1.8 KNX Universal Dimming Actuator,4-Fold

Fig.5.1(2) Add Device Certificate window

Alternatively, the certificates of all Secure devices can be entered in the ETS beforehand.

This is done on the "Security" tab on the project overview page, as shown in Fig.5.1(3) below.

The certificates can be also added to the selected device in the project, as shown in Fig.5.1(4).

Fig.5.1(3) Add Device Certificate

Fig.5.1(4) Add Device Certificate

There is a FDSK sticker on the device, which is used for viewing FDSK number.

Without the FDSK, it will no longer be possible to operate the device in KNX Secure mode

after a reset.

The FDSK is required only for initial commissioning. After entering the initial FDSK, the ETS will
14
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

assign a new key, as shown in Fig.5.1(5) below.

The FDSK will be required again only if the device was reset to its factory settings (e.g. If the device

is to be used in a different ETS project).

-.-.- KNX Universal Dimming Actuator,4-Fold

FDSK

Fig.5.1(5)

Example:

If this application in the project needs to be tried with another device, it is no longer the original

device. When the application is downloaded to a new device, the following prompt will appear on the

left of Fig.5.1(6), click yes, the Add Device Certificate window will appear, then enter the initial FDSK of

the new device, and you need to reset the device to the factory settings (it is not required if the device is

still factory default; If it has been used, it will be required to reset, otherwise the following error

message will appear on the right of Fig.5.1(6)), and then the device can be successfully downloaded

again.

1.1.8 KNX Universal Dimming Act...

1.1.8 KNX Universal Dimming Actuator,4-Fold

Fig.5.1(6) Example

Whether the device is replaced in the same project, or the device is replaced in a different project,

the processing is similar: Reset the device to the factory settings, then reassign the FDSK.

15
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

After the device is downloaded successfully, the label Add Device Certificate turns gray, indicating

that the key for this device has been assigned successfully, as shown in Fig.5.1(7) below.

Fig.5.1(7)

ETS generates and manages keys:

Keys and passwords can be exported as needed to the use of security keys outside of the

associated ETS projects. As shown in Fig.5.1(8) below, the file extension is .knxkeys.

Fig.5.1(8)

Note: Any USB interface used for programming a KNX Secure device must support "long frames".

Otherwise ETS will report a download failure information, as shown below.

16
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.2.Parameter window "General"

Fig.5.2 "General setting" parameter window

Parameter "Operation and Send delay after bus recovery [0..15]"

This parameter is for setting the delay time to send to bus after the device bus recovery.

Options: 0..15 s

The setting dose not contain the device initialization time, and bus telegrams received during delay

time will be recorded.

Parameter "Send cycle of "In operation" telegram [1..240,0=inactive]"

This parameter is for setting the time interval when cyclically send telegrams through the bus to

indicate this device in normal operation. When set to "0", the object "In operation" will not send a

telegram. If the setting is not "0", the object "In operation" will send a telegram according to the setting

period time with logic "1" to the bus. Options: 0…240 s, 0= inactive

As to reduce the bus load as much as possible, the maximum time interval should be selected

according to actual application requirement.

Parameter “Manual operation”

This parameter is for setting whether to enable manual operation, which is mainly convenient for

engineers to debug or check the lamps, when enabled, you can manually switch and dim each output

channel.
17
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

The definition of function priority: Manual > Forced > Safety > other functions, after exiting higher

priority, the next priority action needs to be executed. When during manual operation, the telegrams

from bus will be ignored and not executed, but the statuses of low priority (Forced/Safety) will be

recorded in the background, and they will be executed after exiting manual operation.

Manual operation is enabled by default in case of no database; after download, enable manual or

not depends on the parameter.

Theses two parameters as follow are visible when enabled:

Parameter “Manual to automatic by”

This parameter is for setting the behaviour when exit manual operation. Options:

Only long press

Both long press and automatic delay time

Parameter “Delay time [10...6000]”

This parameter is visible when ”Both long press and automatic delay time” is selected by previous

parameter. Set the delay time for exiting manual operation automatically, and timing from the last

button operation. Options: 10....6000 s

Parameter "Safety function"

This parameter is for setting the object value of safety status cancellation for whole device, while

receiving the reversed value is to enter safety status. Options:

Cancel via object value "0"

Cancel via object value "1"

When enter safety status, execute the configured behaviour of the channel if its safety function is

enabled, more details are defined in the channel.

Parameter "Monitoring period [0...1000, 0=monitoring deactive]"

This parameter is for setting the period to monitor the telegram of safety object.

Options: 0...1000 s

If the period is greater than 0, the telegram to cancel safety status was not received during the

monitoring period, enter the safety status. Exit this status and reset the monitoring period when a

18
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

cancellation telegram is received. It is also possible to enter the safety status directly by receiving the

reversed value defined by the previous parameter.

If the period is set as 0, enter the safety status directly by receiving the reversed value defined by

the previous parameter, and receiving cancellation value is to exit the status.

Parameter "Logic function"

Setting page of logic function interface is visible after this parameter enabled.

19
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.Parameter window "Output setting"

Fig.5.3 "Output setting" parameter window

Parameter "Device type"

This parameter is for displaying the device type, it is according to the product:

1-Fold

2-Fold

4-Fold

Display corresponding connection preview below the parameter.

Parameter “Dimming channels”

This parameter is visible when device type is 2-Fold or 4-Fold. Set the dimming channels. For the

dimmer with multiple channels, individual or parallel channels can be configure. Parallel channels can

expand the load capacity.

When 2-Fold, options:

Individual

Parallel (A+B)

When 4-Fold, options:

Individual

Parallel (A+B) and Parallel (C+D)

Parallel (A+B) and Individual (C, D)

20
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Individual (A, B) and Parallel (C+D)

Parallel (A+B+C) and Individual (D)

Individual (A) and Parallel (B+C+D)

Parallel (A+B+C+D)

Parameter "Channel A/B/C/D/A+B/..."

For the dimmer with multiple channels, these parameters are visible depends on the previous

parameter. Set whether to enable dimming channel, and corresponding window is visible when enabled.

For 1-Fold Dimmer, only display Channel A.

Configuration of individual channel is as same as the parallel channel, the following is an example

of Channel A.

21
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.1.Parameter window "Channel"

Fig.5.3.1(1) "Channel" parameter window

22
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Fig.5.3.1(2) "Channel" parameter window

Parameter "Description (max 30char.)"

This parameter is for setting the name description of the channel.

Parameter "Load type"

This parameter is for setting the load type of the channel. Options:

Resistive&Capacitive load (trailing edge)

Inductive load (leading edge)

LED (trailing edge)

LED (leading edge)

Parameter "Dimming curve"

This parameter is for setting dimming cure of the channel, display corresponding preview figure

below the parameter. Options:

23
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Logarithmic function Cubic function

Root function Exponential function

Linear function User defined

Quadratic function

When "User defined" is selected, user can custom a dimming curve, more detail please refer to

chapter 5.3.2.

Parameter "General dimming time (from min. to max.)"

This parameter is for setting the time for the whole dimming process, which refers to the time from

minimum to maximum value. Suppose the time is set as 6s, the min. Value is 0% and the max. is 100%,

if the brightness is only dimmed from 0% to 50%, then the dimming time only takes 3s.

Options: 2...255 s

If the channel function has not specified a dimming time, use the time set by this parameter,

functions such as switch on/off lamps, forced, safety, staircase lighting, threshold, etc.

24
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Minimum brightness value"

Parameter "Maximum brightness value"

These parameters are for setting minimum and maximum brightness values individually, to limit

the output range of dimming brightness, which is allow the lamps work in a better brightness range

depending on the environment or lamps compatibility.

This range is not allowed to be exceeded in any status of lamps on, including threshold, forced,

safety functions, etc. Output as min. value when the brightness is lower than the min., and output as

max. value when it is higher than the max.

Options of the min. value: 1...49 %; Options of the max. value: 50...100 %

Parameter "Switching on value"

This parameter is for setting the brightness when the lamp is switched on. Options:

Preset brightness value

Last brightness value

Parameter "Preset brightness value"

This parameter is visible when previous parameter is selected "Preset brightness value". Set the

preset brightness value. Options: 1...100 %

Parameter "Dimming mode selection for switching on"

This parameter is for setting the dimming mode when the lamp is switched on. Options:

Jumping

Dimming

Jumping: switch on immediately and directly to the target brightness.

Dimming: switch on with dimming to the target brightness and use the General dimming time.

Parameter "Dimming mode selection for switching off"

This parameter is for setting the dimming mode when the lamp is switched off. Options:

Jumping

Dimming

Jumping: switch off immediately.

Dimming: switch off with dimming and use the General dimming time.
25
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Dimming time for relative dimming"

This parameter is for setting the time for the whole relative dimming process. Options: 2...255 s

Parameter "Dimming time for absolute dimming"

This parameter is for setting the time for the whole absolute dimming process. Options: 2...255 s

Parameter "Allow switch off via relative dimming"

This parameter is for setting whether allow to switch lamp off via relative dimming. When disabled,

it can only be adjusted downward to the minimum brightness value; while enabled, switch the lamp off

directly when the brightness is dimming to the minimum brightness value.

Parameter "Absolute dimming value lower than the minimum value"

This parameter is for setting the behaviour when absolute dimming value lower than the minimum

value, it only affects the object "Absolute dimming". Options:

0%=0%,otherwise=Minimum brightness value

To be the minimum brightness value

To be 0%

0%=0%, otherwise=Minimum brightness value%: output as min. value when the value is lower than

the min., but the value is 0% is to switch the lamp off.

To be the minimum brightness value: output as min. value when the value is lower than the min.,

even if the value is 0%.

To be 0%: switch the lamp off directly when the value is lower than the min.

Parameter "Additional startup characteristic when the lamp is off"

This parameter is for setting whether the lamp needs the startup characteristic additionally when

the lamp is off. Some lamps require a higher voltage to start up when switched off.

Following four parameters are visible when parameter is enabled.


Parameter "Startup brightness value"
This parameter is for setting the brightness value of lamp startup. Options: 5..90 %

Note: the brightness must not exceed the max. and min. value, otherwise it cannot be set in the

ETS.

26
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Behavior for dimming up"


This parameter is for setting the behavior for dimming up when the lamp is off. Options:

Ignore the telegram

Like normal

Dim up based on the startup brightness

Ignore the telegram: feed back an off telegram immediately to synchronize the status with the

control device.

Like normal: dimming up and output normally.

Dim up based on the startup brightness: use the startup brightness as a based point, and dimming

up from this brightness.


Parameter "Behavior when the switch or dimming value is lower than startup value"
This parameter is for setting the behavior when the target brightness is lower than startup value,

and the lamp is off. Options:

Ignore the telegram

Like normal

Jump to startup brightness

Jump to startup then delay to target

Ignore the telegram: feed back a off telegram immediately to synchronize the status with the

control device.

Like normal: dimming and output normally.

Jump to startup brightness: jump to the startup brightness immediately and feed back the new

brightness to the bus.

Jump to startup then delay to target: jump to startup brightness firstly then dimming to the target

brightness after the delay has elapsed.

If the target brightness is higher than startup value, dimming from the startup value to the target

brightness directly, it is only applied to receive the telegrams of objects "Switching" and "Absolute

dimming".
Parameter "Delay time after reach startup"
This parameter is visible when previous parameter is selected "Jump to startup then delay to

27
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

target". Set the delay time for dimming to target brightness after reaching the startup value. Options:

50ms

80ms

100ms

...

2s

4s

5s

Reset behavior
Parameter "Behavior after download"

This parameter is for setting the behaviour of channel after download. Options:

Switching off

Preset brightness value

Brightness before bus failure

Preset brightness value: dimming to a setting brightness, defined by next parameter.

Brightness before bus failure: recover to the brightness value stored when the bus failure.

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

Parameter "Behavior after bus failure"

This parameter is for setting the behaviour of channel after bus failure. Options:

Switching off

Preset brightness value

No reaction

Preset brightness value: dimming to a setting brightness, defined by next parameter.

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
28
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

value. Options: 1...100 %

Parameter "Behavior after bus recovery"

This parameter is for setting the behaviour of channel after bus recovery.

Switching off

Preset brightness value

Brightness before bus failure

Preset brightness value: dimming to a setting brightness, defined by next parameter.

Brightness before bus failure: recover to the brightness value stored when the bus failure.

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

Parameter "Short-circuit detect for operating supply or device reset if output is off"

This parameter is for setting whether detect short-circuit for operating supply or device reset if

output is off.

When disabled, a short-circuit may be detected only when turn on the lamp until exceed the

threshold of short-circuit detection.

When enabled, every time a operating supply or device voltage recovery, it needs to detect a

short-circuit firstly if initially the lamp is off or the brightness is lower than the threshold of short-circuit

detection, but it is not required to detect if the brightness is higher than the threshold of short-circuit

detection. Download database and restart, if the detection has been normal before the download, there

is no need to repeat the detection, otherwise it is still necessary to perform a detection.

29
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Central control

Central control is used to control the switching and dimming of all channels, each channel can be

configured to support central control or not. When receive the telegram of central control from bus,

control the outputs centrally for the supported channels.

Note: central control function only applies for 2/4-Fold Dimmers, and it is not supported by 1-Fold

Dimmer.

Parameter “Switching”

This parameter is for setting whether control switch centrally.

Parameter “Relative dimming”

This parameter is for setting whether control relative dimming centrally.

Parameter “Absolute dimming”

This parameter is for setting whether control absolute dimming centrally.

Status feedback
Parameter "Switching/Brightness value/Short-circuit/Over-voltage/Over-temperature/Operating voltage

failure"

These parameters are for setting the way to feed back the status of switch, brightness and

abnormal status. The abnormal status including short-circuit, over-voltage, over-temperature, operating

voltage failure. Options:

Respond after read only

Respond after change

Handling of abnormal status:

Trigger hardware protection when channel load terminal is short-circuited, and feed back the

status to bus. It will disconnect the output when in protection. If it is the first time a short-circuit has

been detected since power on, disconnect the output first then wait a 1 minute to output the current

control value again; but if there is still a short-circuit, disconnect the output permanently, and cannot be

used unless the device is restarted.

Trigger hardware protection when the operated voltage is higher than the rated voltage, and feed
30
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

back the status to bus. It will disconnect the output when in protection.

When the measured internal temperature exceeds 90℃ for 10s, then will trigger over-temperature

protection and send the status to bus. The brightness will down to 20% or to the minimum value under

the protection status. After the temperature is reduced to below 70℃, output normally if a new control

telegram is received.

Operation voltage is failure when no valid over-zero signal is detected, and feed back the status to

bus. When in voltage failure, it can not feed back control status and no drive signal if receive the control

telegram, need to power supply normally and has actual output value can feed back the current status

of the lamp.

Extension function
Parameter "Scene function"

Setting page of scene function interface is visible after this parameter enabled.

Parameter "Time function"

Setting page of time function interface is visible after this parameter enabled.

Parameter "Threshold function"

Setting page of threshold function interface is visible after this parameter enabled.

Parameter "Forced function"

Setting page of forced function interface is visible after this parameter enabled.

Parameter "Safety function"

Setting page of safety function interface is visible after this parameter enabled.

Parameter “Operating hours counter”

Setting page of operating hours counter interface is visible after this parameter enabled.

31
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.2.Parameter window "User defined dimming curve"

Fig.5.3.2 "User defined dimming curve" parameter window

Parameter "Number of curve coordinate points"

This parameter is for setting the number of curve coordinate points. Options: 2...16

Coordinate point x (x=1~16)


Parameter "KNX dimming value"

This parameter is for setting KNX dimming value of the curve. Options: 1..100%

For user defined dimming curve, the first and the last one points are fixed to 1% and 100%.

Note: the previous KNX dimming value must be small than next one, otherwise it can not be set

on the ETS:

32
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Output value"

This parameter is for setting the output value corresponding to the KNX dimming value.

Options: 1..100%

Note: the previous output value must be small than next one, otherwise it can not be set on the

ETS:

Custom curves with different number of coordinate points, as shown as following:

Example 1 Example 2 Example 3 Example 4

(3 coordinate points) (4 coordinate points) (5 coordinate points) (6 coordinate points)

33
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Commissioning steps of User defined dimming curve:

Step 1: use the linear function curve at first to determine the adjustable range, then

obtain the minimum and maximum adjustable brightness values of the applied lamp with

absolute dimming;

Step 2: when testing in step 1, you can experience the brightness changes with

relative dimming, then checking the number of curve areas and coordinate points;

Step 3: the minimum brightness value is the point of knx value 1%, the maximum

brightness value is the point of knx value 100%;

Step 4: add the coordinate points of the middle section according to the planning

area;

Step 5: download and commission, according to the experience of dimming process,

there may also be slight adjustment of the coordinate points or increase the configuration

areas, and even need to adjust the dimming time, until achieve the best results for user

satisfaction.

34
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.3.Parameter window "Extension function"

Parameter windows are visible according to the enabling of the extension function parameters.

5.3.3.1.Parameter window "Scene function"

Fig.5.3.3.1 "Scene function" parameter window

Scene function can work with the control panel or other software to execute the setting scene and

output the specified brightness.

Parameter "Overwrite scene stored values during download"

This parameter is for setting whether to override the scene stored values during application

download. If select to overwrite, follow the parameter setting, otherwise for the brightness value

corresponding to the scene number that has saved the modified value has executed, the last saved

value will remain; for the modified brightness has not executed, still use the value set by parameter.

35
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Scene x (x=1~16)
Parameter "Description"

This parameter is for setting the name description of the corresponding scene, up to 30

characters.

Parameter "Scene NO."

This parameter is for setting the triggered scene number, up to 16 scenes. Options: 0...64

When scene number is 0, it is invalid, and the brightness and dimming time cannot be set, as

shown as following:

When scene numbers are greater than 0, if there are same scene numbers, display following error

message:

Parameter "Brightness"

This parameter is for setting the brightness of the corresponding scene. Options: 0...100 %

Parameter "Dimming"

This parameter is for setting the dimming time of the corresponding scene. Options: 2...255 s

36
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.3.2.Parameter window "Time function"

Delay switch

Flash switch

Staircase lighting
Fig.5.3.3.2 "Time function" parameter window

Different configurations of time function can be used for different application.

Parameter "Time function"

This parameter is for setting the time function, its brightness is depending on the value of switch

on/off. Options:

Delay switch
37
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Flashing switch

Staircase lighting

Delay switch: delay a period time to switch on/off, dimming mode is Jumping.

Flashing switch: flashing to switch on/off, dimming mode is Jumping.

Staircase lighting: dimming mode is Dimming, use the General dimming time.

Note: time function will be interrupted directly after entering safety or forced operation.

Parameter "Delay for switch on"

Parameter "Delay for switch off"

These two parameters are visible when "Delay switch" is selected. Set the delay time for switch

on/off, execute the on/off telegram received from bus after the delay has elapsed. During delay time,

receive the same telegram again, the delay time is reset.

Options: 00:00:00 ...23h:59min:59s

Parameter "On time for flashing"

Parameter "Off time for flashing"

These two parameters are visible when "Flashing switch" is selected. Set the duration time of

flashing for switch on/off.

Options: 00:00:05s ...23h:59min:59s

Parameter "Number of flashing cycles [0..10000,0=no limit]"

This parameter is visible when "Flashing switch" is selected. Set the number of flashing cycles, a

cycle includes an on and an off. 0 means the cycles is no limited. Options: 0...10000

Parameter "Status after flashing"

This parameter is visible when "Flashing switch" is selected. Set the status after flashing. Options:

Switching off

Switching on

Unchange

Note: there is a possibility of an extra half cycle of action when "Switching on" or "Unchange" is

selected.

38
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Control mode of flashing"

This parameter is visible when "Flashing switch" is selected. Set the control mode of flashing.

Options:

Start with"1", Stop with "0"

Start with"0", Stop with "1"

Start with"0/1", can not be stopped

Start with"1", Stop with "0": it will start flashing with value "1" and stop flashing with "0", action

to the end status when stopped, which is defined via previous parameter.

Start with"0", Stop with "1": it will start flashing with value "0" and stop flashing with "1", action

to the end status when stopped, which is defined via previous parameter.

Start with"0/1", can not be stopped: it will start flashing with value "0" or "1", and can not stop

until the number of the flashing cycles is exhausted, or stop via the interruption from other

operation.

Parameter "Duration time"

This parameter is visible when "Staircase lighting" is selected. Set the duration time of staircase

lighting switch on, and switch off automatically after the time has elapsed.

Options: 00:00:05s ...23h:59min:59s

Parameter "Time extension"

This parameter is visible when "Staircase lighting" is selected. Set whether to retrigger or extend

the duration time when receive an on telegram during the time. Options:

Not retriggerable

Retriggerable

Extend duration time

Not retriggerable: ignore the telegram, switch off automatically after the time has elapsed.

Retriggerable: retrigger the duration time when receive an on telegram during the time.

Extend duration time: add up a duration time to the remaining time when receive an on telegram

during the duration time. For example the duration time is set as 60s, but it is still has 40s left, and

receive an on telegram at the moment, then the new duration time is 40s+60s =100s, and the staircase
39
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

light will be turned off automatically after the 100s is elapsed. If receive multiple on telegrams

continuously, the duration time will continue to add up until the maximum time is reached.

Parameter "Control mode of staircase lighting"

This parameter is visible when "Staircase lighting" is selected. Set the control mode of staircase

lighting. Options:

Start with"1", Stop with "0"

Start with"1", no reaction with "0"

Start with"0/1", can not be stopped

Start with"1", Off with "0"

Start with "1", Stop with "0": it will switch on the staircase light with the value "1" and stop the

timing with "0", keep the current lamps status until it is changed by other operations.

Start with "1", no reaction with "0": it will switch on the staircase lights with the value "1" and no

reaction with "0".

Start with"0/1", can not be stopped: it will switch on the staircase lights with the value "1" or "0",

and can not stop until the duration time is exhausted, or stop via the interruption from other

operation.

Start with"1", Off with "0": it will switch on the staircase lights with the value "1" and switch off with

"0"

Parameter "Prewarning before staircase time end"

This parameter is visible when "Staircase lighting" is selected. Set whether to prewarn before

staircase light time end, and set the prewarning mode. User can be noticed before the staircase light

time is about to finish. Options:

No

No, but dim-down the dimming value after end

Via object

Via flashing switching on-off

Via flashing switching on-off and object

Dim-down the dimming value

40
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Dim-down the dimming value and via object

No: no prewarn, and switch off automatically after the time has elapsed.

No, but dim-down the dimming value after end: no prewarn, but dim down the brightness after the

time has elapsed.

Via object: prewarn via the object.

Via flashing switching on-off: prewarn via a short flashing, 1s to switch on and 1s to switch off,

dimming mode is Jumping.

Via flashing switching on-off and object: prewarn, refer to the explanation of the previous options.

Dim-down the dimming value: prewarn via dimming down the brightness.

Dim-down the dimming value and via object: prewarn, refer to the explanation of the previous

options.

Parameter "Warning time"

This parameter is visible when the selection does not contains "No...". Set the time of prewarning.

Options: 00:00:05s...00h:59min:59s

Note: the warning time must be less than the duration time, or it cannot set on the ETS.

Note: the warning time is contained in the startup time of staircase lighting. If switch off before

the warning time, there is no prewarning.

Parameter "Value of dimming down"

This parameter is visible when the selection contains "Dim-down the dimming value....". Set the

brightness value of dimming down at the end of the staircase lighting. Options: 1...100 %

Parameter "Duration time can be changed via bus"

This parameter is visible when "Staircase lighting" is selected. Set whether the duration time can be

changed via bus. Store the modified value when bus failure, recovery to the value set by parameter after

download.

41
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.3.3.3.Parameter window "Threshold function"

Fig.5.3.3.3 "Threshold function" parameter window

Switch on/off or dimming the brightness according to telegram from the bus and threshold set on

the ETS. Note: the brightness of threshold function is depending on the value of switch on/off.

Parameter "Threshold value datatype"

This parameter is for setting the threshold value datatype. Options:

1byte unsigned value (DPT5.010)

1byte percentage (DPT5.001)

Temperature (DPT9.001)

Illuminance (DPT9.004)

Parameter "Threshold value 1"

Parameter "Threshold value 2"

These two parameters are for setting the threshold value 1 and 2. Options are display according to

the threshold value datatype.

When 1byte unsigned value, options: 0...255

When 1byte percentage, options: 0...100 %

When Temperature, options: -20...95 °C

42
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

When Illuminance, options: 0...65535 lux

Note: the threshold 1 must be less than threshold 2, or they cannot be set on the ETS, as shown

as following:

Parameter "Threshold value can be changed via bus"

This parameter is for setting whether the threshold 1 and 2 can be changed via bus.

Store the modified value when bus failure, recovery to the value set by parameter after download.

Parameter "Threshold behavior"

This parameter is for setting whether the threshold 1 and 2 with hysteresis. Options:

Without hysteresis

With hysteresis

The hysteresis can avoid the unnecessary behaviour caused by the input value if the value is

between two threshold values.

Parameter "Output type"

This parameter is for setting the output type after threshold comparison. Options:

Switching

Brightness value

If input value<=threshold value 1

Set the output value when input value is less than or equal to the threshold 1. Following parameter

and its options are displayed according to the output type.

Parameter "Output is"

This parameter is visible when "Switching" is selected. Options:

Switching off

Switching on

Unchange

Parameter "Dimming value is"

This parameter is visible when "Brightness value" is selected. Options: 0...100 %


43
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

If threshold value 1<input value<threshold value 2

Set the output value when input value is between the threshold 1 and 2. Output parameter and its

options are displayed according to the output type, as above explanation.

Note: when with hysteresis, the output is only Unchange

If input value>=threshold value 2

Set the output value when input value is greater than the threshold 2. Output parameter and its

options are displayed according to the output type, as above explanation.

5.3.3.4.Parameter window "Forced function"

1bit

2bit

Fig.5.3.3.4 "Forced function" parameter window

The lamp can be forcibly fixed at a brightness in some special situations. Forced function has the

highest priority. Ignore the normal control telegram received from bus when during in forced or safety

operation.

Parameter "Forced operation datatype"

This parameter is for setting the datatype of forced operation. Options:


44
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

1bit

2bit

Parameter "Forced operation at object value"

This parameter is visible when 1bit. Set the object value for activating or canceling the forced.

Options:

0=Forced/1=Cancel

1=Forced/0=Cancel

Parameter "Behavior at forced operation"

This parameter is visible when 1bit. Set behavior at forced operation. Options:

Switching off

Preset brightness value

Unchange

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

Parameter "Behavior at forced operation "switch on""

This parameter is visible when 2bit. Set the behavior at forced operation "switch on" when receive

telegram value 3 from 2bit. Options:

Preset brightness value

Unchange

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

Parameter "Behavior at forced operation "switch off""

This parameter is visible when 2bit. Set the behavior at forced operation "switch off" when receive

telegram value 2 from 2bit. Option is only Switching off

Parameter "Behavior at end of forced operation"

This parameter is for setting the behavior at end of forced operation. Note: the telegram values
45
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

0/1 from 2bit are used to cancel forced operation. Options:

Switching off

Preset brightness value

Unchange

1.When receive a telegram to end forced operation, it is valid if the forced operation has been

activated before, otherwise ignore the telegram.

2.When a telegram to end forced operation is valid, if there is another priority (safety operation)

active in the device, execute this action of this priority; otherwise, ignore the end telegram and execute

the action of forced operation.

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

5.3.3.5.Parameter window "Safety function"

Fig.5.3.3.5 "Safety function" parameter window

Safety function can work with external sensor and perform dimming behaviour in some emergency

situations. Safety function has the second highest priority and only lower than forced function.

Parameter "Behavior at safety operation"

Parameter "Behavior at end of safety operation"

These two parameters are for setting the behavior for activating or canceling the safety operation.

Options:

Switching off

Preset brightness value

Unchange
46
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Preset brightness value"

This parameter is visible when "Preset brightness value" is selected. Set the preset brightness

value. Options: 1...100 %

1.When receive an end telegram, it is valid if the safety operation has been activated before,

otherwise ignore the telegram.

2.When the end telegram is valid, if there is another priority (forced operation) active in the device,

execute this action of this priority; otherwise, ignore the cancel telegram and execute the action of

safety operation.

5.3.3.6.Parameter window "Operating hours counter"

Fig.5.3.3.6 “Operating hours counter” parameter window

Parameter “Operating hours counter”

This parameter is for setting whether activate the function of operating hours counter, and setting

the datatype. It is used to count the time that the lamp has been switched on. If brightness is greater

than “0”, start timing. It can be used as a seconds counter or an hours counter. Options:

Inactive

Value in s (DPT 13.100)

Value in h (DPT 7.007)

These following parameters are visible when parameter is activated:

Parameter “Send counter value in second [0..65535]”

This parameter is visible when “Value in s (DPT 13.100)” is selected. Set the cycle for sending

47
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

counter value. If set to 3600s, that is send a counter value to the bus every 3600s.

Options: 60...65535 s

Parameter “Send counter value in hours [0..255]”

This parameter is visible when “Value in h (DPT 7.007)” is selected. Set the cycle for sending

counter value. If set to 1h, that is send a counter value to the bus every hours. Options: 1...255 h

Parameter “Monitoring operation hours”

This parameter is for setting whether to enable the monitoring of operating hours counter, which is

used to monitor the time that the lamp has been switched on. When the time is closed to the end of the

lamp's life, send a telegram to remind the user to change a new lamp.

Following parameters are visible when the monitoring is enabled:

Parameter “Threshold for operation hours”

This parameter is for setting the threshold for operation hours, usually refer to the lamp’s life. The

range of options depends on the datatype.

When “Value in s (DPT 13.100)”, options: 100...2147483647 s

When “Value in h (DPT 7.007)”, options: 1...65535 h

Parameter “Send status cyclical [0..255,0=inactive]”

This parameter is for setting the cycle of sending status, 0 is no send. Send on change is enabled

by default. Options: 0...255 min

48
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.4.Parameter window "Logic"

Fig.5.4 "Logic function setting" parameter window

Parameter "1st/2nd/3rd... Logic function"

This parameter is for setting the setting interface of logic function, display corresponding logic

function page when select. Up to enable 8 logic functions.

Parameter "Description for logic function"

This parameter is for setting the name description for logic function, up to input 30 characters.

Parameter "Function of channel"

This parameter is for setting function of the channel. Options:

AND

OR

XOR

Gate forwarding

Threshold comparator

Format convert

Gate function

Delay function

Staircase lighting

AND/OR/XOR: as the parameter is similar to the communication object (only the logic algorithm is

different), the following parameters taking one options for example.


49
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.4.1.Parameter window "AND/OR/XOR"

Fig.5.4.1 "AND/OR/XOR" parameter window

Parameter "Input a/b/c/d/e/f/g//h"

This parameter is for setting whether input x to calculate, whether to normally calculate or inverted

calculate.Options:

Disconnected

Normal

Inverted

50
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Disconnected: not to calculate;

Normal: to directly calculate the input value;

Inverted: invert the input value, then to calculate. Note: not to invert the initiate value.

Parameter "Default value"

This parameter is for setting the initial value of logic input x. Options:

Parameter "Result is inverted"

This parameter is for setting whether to invert the logic calculation result. Options:

No

Yes

No: output directly;

Yes: output after inverting.

Parameter "Read input object value after voltage recovery"

This parameter is for setting whether to send the read request to the logic input object after device

voltage recovery or finish programming. Options:

No

Yes

Parameter "Output send when"

This parameter is for setting the condition of sending logic result. Options:

Receiving a new telegram

Every change of output object

Receiving a new telegram:every time the object received a new input value will the logic result be
sent to the bus;
Every change of output object:only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic calculate, the logic result will be sent even if it has no change.

Parameter "Send delay time"

Base: None

0.1s

51
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

1s

...

10s

25s

Factor: 1..255

This parameter is for setting the delay time for sending the logic calculation result to the bus. Delay
time = Base × Factor, if option "None" of Base is selected, then there is no delay.

5.4.2.Parameter window "Gate forwarding"

Fig.5.4.2 "Gate forwarding" parameter window

Parameter "Object type of Input/Output"

This parameter is for setting the object type of input/output. Options:

1bit

4bit

1byte

52
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Default scene NO. of Gate after startup [1~64,0=inactive]"

This parameter is for setting the initial scene where logical gate forwarding can be performed by

default after device starts, which needs to be configured in the parameters. Options:1..64, 0=inactive

Note: gate scene is recommended to be selected before operating, or it will enable the initiate

scene by default.

Parameter "z->Gate trigger scene NO. is [1~64,0=inactive]"(z=1~8)

This parameter is for setting scene number of logic gate forwarding. Up to 8 trigger scene number

can be set for each logic. Options: 1..64, 0=inactive

——Parameter "Input A/B/C/D send on"

This parameter is for setting the output of input X (X=A/B/C/D) after gate forwarding. Options:

Disable

Output A

Output B

...

Output B,C,D

According to the options, one input can be forwarded into one or more outputs, the output value is

the same as the input value.

53
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.4.3.Parameter window "Threshold comparator"

Fig.5.4.3 "Threshold comparator" parameter window

Parameter "Threshold value data type"

This parameter is for setting the threshold value data type. Options:

4bit value (DPT3.007) 4byte unsigned value[0..4294967295]

1byte unsigned value (DPT5.010) Ext. temperature value (DPT 9.001)

2byte unsigned value (DPT7.001) Ext. humidity value (DPT 9.007)

2byte signed value (DPT8.x) Illuminance value (DPT 9.004)

2byte float value (DPT9.x)

Parameter "Threshold value "

This parameter is for setting threshold value, the range depends on the data type. Options:

4bit value (DPT3.007) 0..15 /1byte unsigned value (DPT5.010) 0..255 /

2byte unsigned value (DPT7.001) 0..65535 / 2byte signed value (DPT8.x) -32768..32767 /

2byte float value (DPT9.x) -670760...670760 / 4byte unsigned value[0..4294967295]

0..4294967295 /Ext. temperature value (DPT 9.001) -20..95℃ / Ext. humidity value (DPT 9.007)

0..100% / Illuminance value (DPT 9.004) 0..65535lux

54
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Hysteresis threshold value"

This parameter is visible when object datatype is selected "2byte float value (DPT9.x)", "Illuminance

value (DPT 9.004)". Set the hysteresis threshold value. Options: 0..500

Parameter "If Object value<Threshold value"

Parameter "If Object value=Threshold value"

Parameter "If Object value!=Threshold value"

Parameter "If Object value>Threshold value"

Parameter "If Object value<=Threshold value"

Parameter "If Object value>=Threshold value"

This parameter is for setting the logic result value that should be sent when threshold value Less

than, equal to, not equal to, greater than, less than or equal to the setting valve. When object datatype is

selected "2byte float value (DPT9.x)", can only set the object value less than or greater than threshold

value. Options:

Do not send telegram

Send value "0"

Send value "1"

Do not send telegram: not consider to select this option;

Send value "0"/"1": when condition is satisfied, send telegram 0 or1.

If there is a conflict between the setting options between parameters, the base on the value that

should be sent when reach the final parameter condition. For example: parameter "If Object

value=Threshold value" is set to be "Send value "0" ";parameter "If Object value<=Threshold value" is

set to be "Send value "1" ";when object value is equal to the threshold value, then the logic result will

send "1".

Parameter "Output send when"

This parameter is for setting the condition of sending logic result. Options:

Receiving a new telegram

Every change of output object

Receiving a new telegram: every time the object received a new input value will the logic result be

sent to the bus;


55
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Every change of output object: only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.

Parameter "Send delay time"

Base: None

0.1s

1s

...

10s

25s

Factor: 1..255

This parameter is for setting the delay time for sending the logic algorithm result to the bus. Delay

time = Base x Factor, if option "None" of Base is selected, then there is no delay.

5.4.4.Parameter window "Format convert"

Fig.5.4.4 "Format convert" parameter window

Parameter "Function"

This parameter is for setting the format convert type. Options:

2x1bit-->1x2bit

8x1bit-->1x1byte

1x1byte-->1x2byte

2x1byte-->1x2byte

2x2byte-->1x4byte

1x1byte-->8x1bit

1x2byte-->2x1byte
56
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

1x4byte-->2x2byte

1x3byte-->3x1byte

3x1byte-->1x3byte

Parameter "Output send when"

This parameter is for setting the condition of sending logic result. Options:

Receiving a new telegram

Every change of output object

Receiving a new telegram: every time the object received a new input value will the logic result be

sent to the bus;

Every change of output object: only when logic result has changed will it be sent to the bus.

Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.

5.4.5.Parameter window "Gate function"

Fig.5.4.5 "Gate function" parameter window

Parameter "Object type of Input/Output"

This parameter is for setting the object type of input/output. Options:

1bit[On/Off]

1byte[0..100%]

1byte[0..255]

2byte[Float]

2byte[0..65535]

57
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

——Parameter "Filter function"

This parameter is visible when "1bit[On/Off]" is selected. Set whether to filter On or Off telegram,

only pass one of them or pass all. Options:

Deactivate

On filter out

Off filter out

Deactivate: Do not filter the On or Off telegrams;

On filter out: Off can pass, On cannot pass;

Off filter out: On can pass, Off cannot pass.

——Parameter "Value output"

This parameter is visible when "1bit[On/Off]" is selected. Set whether to invert the value then output

it. Options:

Normal

Inverted

Parameter "Gate object value"

This parameter is for setting whether to invert the gate object value then output it. Options:

Normal

Inverted

Parameter "Gate status after voltage recovery"

This parameter is for setting the gate status after power on. Options:

Disable

Enable

Parameter "Save input signal when gate close"

This parameter is for setting whether to save input signal on gate close. Options:

No

Yes

No: disable to save the input, the input values received during the gate closing period are ignored;

Yes: enable to save the input, the input values received during the gate closing period are output

when gate is open (whether the input value is changed or not).

58
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

5.4.6.Parameter window "Delay function"

Fig.5.4.6 "Delay function" parameter window

Parameter "Object type of Input/Output"

This parameter is for setting the object type of input/output. Options:

1bit[On/Off]

1byte[0..100%]

1byte[0..255]

2byte[Float]

2byte[0..65535]

——Parameter "Delay time [0..6500]"

This parameter is for setting the delay time that output object forwards the value when the input

object receives the telegram. Options: 0..6500 s

Note: Receive telegram again in delay time, re-timing.

5.4.7.Parameter window "Staircase lighting"

Fig.5.4.7 "Staircase lighting" parameter window

59
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Parameter "Trigger value"

This parameter is for setting the telegram value of the object "Trigger value". Options:

0 or 1

Parameter "Object type of output"

This parameter is for setting the object type of output. Options:

1bit

1byte

Parameter "Duration time of staircase lighting[10..6500]"

This parameter is for setting duration time of staircase lighting after the stair light power on.

Options: 10..6500 s

——Parameter "Send value 1 when trigger"

——Parameter "Send value 2 after duration time"

These parameters are for setting the value to send. Send value 1 when trigger, and then send value

2 after duration time. Options display according to the output object datatype.

When 1 bit, options:

OFF

ON

When 1 byte , options: 0..255

Parameter "Retriggering"

This parameter is for setting whether to trigger re-timing when received trigger value in delay time.

Options:

Disable

Enable

60
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Chapter 6 Description of Communication Object

The communication object is the medium to communicate other device on the bus, namely only

the communication object can communicate with the bus.

NOTE: "C" in "Flag" column in the below table means enable the communication function of the

object; "W" means value of object can be written from the bus; "R" means the value of the object can

be read by the other devices; "T" means the object has the transmission function; "U" means the value

of the object can be updated.

6.1."General" Communication Object

Fig.6.1 "General" communication object


Data
NO. Object Function Name Flag DPT
Type
1 In operation General 1bit C,R,T 1.001 switch

The communication object is used to periodically send a telegram "1" to the bus to indicate that
the device is working properly.
2 Central: Switching General 1bit C,W 1.001 switch

The communication object is used to receive a command of switching on/off lamps for central
control, it only applies to the channel that the central control is enabled.
3 Central: Relative dimming General 4bit C,W 3.007 dimming

The communication object is used to receive a command of relative dimming for central control,
to dim up or dim down. It only applies to the channel that the central control is enabled.
4 Central: Absolute dimming General 1byte C,W 5.001 percentage

The communication object is used to receive a command of absolute dimming for central control,
it only applies to the channel that the central control is enabled.
5 Central: Safety General 1bit C,W 1.005 alarm

The communication object is used to receive the 1bit telegram that is sent from other device
(such as sensor, controller, etc.), the cancel telegram value is decided by the parameter.

61
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

If no corresponding telegram is received within the monitoring time, it is assumed that other
devices are failure, and the channel with a safety function activates the safety operation. With a
monitoring time of 0, it is also possible to activate and exit the safety operation by receiving the
corresponding value with this object.
In the case that the safety operation is not active, the cancel telegram is meaningless and it will be
ignored.
Table 6.1 "General" communication object table

6.2."Output setting" Communication Object

Fig.6.2 "Output setting" communication object


Data
NO. Object Function Name Flag DPT
Type
78 Switching Channel A-{{...}} 1bit C,W 1.001 switch

The communication object is used to receive a command of switching on/off lamps. Telegrams:
1——Switch on
0——Switch off
The name in parentheses changes with the parameter "Description (max 30char.)". If description
is empty, display "Channel A - ..." by default. The same below.
79 Relative dimming Channel A-{{...}} 4bit C,W 3.007 dimming

The communication object is used to receive a command of relative dimming, to dim up or dim
down.
Dimming down when telegram is 1~7, and the larger this range the adjust step is smaller. That is,
the maximum step of dimming down when is 1, and the minimum step of dimming down when is 7,
stop dimming when is 0;

62
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

Dimming up when telegram is 9~15, and the larger this range the adjust step is smaller. That is,
the maximum step of dimming up when is 9, and the minimum step of dimming up when is 15, stop
dimming when is 8.
80 Absolute dimming Channel A-{{...}} 1byte C,W 5.001 percentage

The communication object is used to receive a command of absolute dimming.


Telegrams: 0...100%
81 Switching, status Channel A-{{...}} 1bit C,R,T 1.001 switch

The communication object is used to report the status of the current switch to the bus. Send "1" to
the bus when the value of the brightness is larger than 0, send "0" to the bus with value of "0". Send the
status when voltage recovery.
82 Brightness value, status Channel A-{{...}} 1byte C,R,T 5.001 percentage

The communication object is used to report the status of the current brightness value to the bus.
Send the status at power-up when voltage recovery.
83 Short-circuit, status Channel A-{{...}} 1bit C,R,T 1.005 alarm

The communication object is used to report the status of short circuit to the bus. Send the status
at power-up when voltage recovery. Telegrams:
1——Short circuit
0——Normal
84 Over-voltage, status Channel A-{{...}} 1bit C,R,T 1.005 alarm

The communication object is used to report the status of over-voltage to the bus. Send the status
when voltage recovery. Telegrams:
1——Over voltage
0——Normal
85 Over-temperature, status Channel A-{{...}} 1bit C,R,T 1.005 alarm

The communication object is used to report the status of over-temperature to the bus. Send the
status when voltage recovery. Telegrams:
1——Over temperature
0——Normal
87 Operation voltage failure Channel A-{{...}} 1bit C,R,T 1.005 alarm

The communication object is used to report the status of operation voltage failure to the bus.
Operation voltage is failure when no valid over-zero signal is detected. Send the status when voltage
recovery. Telegrams:
1——Operation voltage failure
0——Normal

63
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

88 Scene Channel A-{{...}} 1byte C,W 18.001 scene control

The communication object is used to receive a 8 bit command to recall or storage scene.
Detailed 8bit the meaning of the directive.
Set up a 8bit Orders for the (Binary code): FXNNNNNN
F: '0' recall scene; '1' for storage scene;
X:0;
NNNNNN: Scene number( 0... 63).
As follows:
Object message Description
value
0 Recall scene 1
1 Recall scene 2
2 Recall scene 3
… ...
63 Recall scene 64
128 Store scene 1
129 Store scene 2
130 Store scene 3
… ...
191 Store scene 64
Parameter setting Options are 1~64, actually communication object "Scene" corresponds to the
telegram received is 0~63. Such as parameter settings is the scene 1, communication
object "Scene" sends the scene for 0.

89 Delay switch Channel A-{{...}} 1bit C,W 1.001 switch

The communication object is visible when "Delay Switch" is selected for time function, used to
turn on the function of delay switch.
89 Flashing switch Channel A-{{...}} 1bit C,W 1.010 start/stop

The communication object is visible when "Flashing Switch" is selected for time function, used to
turn on the function of flashing switch.
89 Staircase lighting Channel A-{{...}} 1bit C,W 1.010 start/stop

The communication object is visible when "Staircase lighting" is selected for time function, used
to turn on the function of staircase lighting.
Duration of staircase lighting
90 Channel A-{{...}} 2byte C,W,R 7.005time(s)
(5..65535s)

The communication object is visible when "Staircase lighting" is selected for time function and
duration time can be changed via bus. Used to modify the time, and save it after voltage failure. If the
duration has not been modified, the value read from the object is the setting value of ETS parameter.
91 Staircase lighting Prewarning Channel A-{{...}} 1bit C,R,T 1.005 alarm
64
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

The communication object is visible when "Staircase lighting" is selected for time function and
prewarn via bus. Used to send the telegram of prewarning before staircase lighting end. Telegram:
1——Warning
0——End of warning
5.010 counter pulses(0..255)

1byte 5.001 percentage


92 Threshold input Channel A-{{...}} C,W
2byte 9.001 temperature

9.004 brightness (lux)

The communication object is receive the input value of threshold function. Telegram value is
determined by the datatype, and the datatype is determined by the parameter setting.
5.010 counter pulses(0..255)

1byte 5.001 percentage


93 Threshold value 1 Channel A-{{...}} C,W,R
2byte 9.001 temperature

9.004 brightness (lux)

5.010 counter pulses(0..255)

1byte 5.001 percentage


94 Threshold value 2 Channel A-{{...}} C,W,R
2byte 9.001 temperature

9.004 brightness (lux)

These two communication objects are visible when the threshold value 1/2 can be changed via
bus. Used to modify the values, and save them after voltage failure. If the thresholds have not been
modified, the value read from the object is the setting value of ETS parameter. Note: threshold value 1
must be less than threshold value 2, or ignore the telegram.
1bit 1.003 enable
95 Forced operation Channel A-{{...}} C,W
2bit 2.001 DPT_Switch control

The communication object is used to trigger a forced operation. Save the trigger status when
voltage failure, and keep the status at voltage recovery.
When 1bit, activate the forced operation when receive telegram 1, at this time, ignore all the other
actions; End the forced operation when receive telegram 0, and the behaviour in forced operation is
defined by parameter.
When 2bit, force to switch off when receive telegram 3; force to switch on when receive telegram
2; End the forced operation when receive telegram 1 or 0.
The end telegram is invalid when the forced operation is not active, and ignore it directly.
2byte 7.007 time (h)
103 Operating hours counter Channel A-{{...}} C,R,W,T
4byte 13.100 time lag (s)

65
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

The communication object is used to send the accumulated operating time that the lamp has
been switched on to the bus, begin to count when brightness is greater than “0”, and the accumulated
time can also be modified via the bus, and send it after the device is restarted.
104 Reset operating hours counter Channel A-{{...}} 1bit C,W 1.015 reset

The communication object is used to reset the accumulated operating time to 0. Telegrams:

1——Reset

0——NA

105 Exceedance of operating hours Channel A-{{...}} 1bit C,R,T 1.005 alarm

The communication object is used to send the status to the bus when the accumulated operating
time exceeds the threshold, remind user the exceedance. Send the status when voltage recovery.
Telegrams:

1——Exceed

0——Normal

Table 6.2 "Output setting" communication object table

66
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

6.3."Logic" Communication Object

6.3.1."AND/OR/XOR" Communication Object

Fig.6.3.1 "AND/OR/XOR" communication object


Data
NO. Object Function Name Flag DPT
Type
6/.../13 Input a/b/../h {{1st Logic}} 1bit C,W,T,U 1.002 boolean

The communication object is used to receive the value of logical input Input a/b/../h.
The name in parentheses changes with the parameter "Description for logic function". If
description is empty, display "1st Logic" by default. The same below.

14 Logic result {{1st Logic}} 1bit C,T 1.002 boolean

The communication object is used to send the results of logical operation.


Table 6.3.1 "AND/OR/XOR" communication object table

6.3.2."Gate forwarding" Communication Object

Fig.6.3.2 "Gate forwarding" communication object


Data
NO. Object Function Name Flag DPT
Type
6 Gate value select {{1st Logic}} 1byte C,W 17.001 scene number

The communication object is used to select the scene of logical gate forwarding.
1bit 1.001 switch

7/.../10 Input x {{1st Logic}} 4bit C,W 3.007 dimming control

1byte 5.010 counter pulses(0..255)

67
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

The communication object is used to receive the value of the logic gate input Input x.
1bit 1.001 switch

11/../14 Output x {{1st Logic}} 4bit C,T 3.007 dimming control

1byte 5.010 counter pulses(0..255)

The communication object is used to output the value forwarded by the logic gate. The output
value is the same as the input value, but one input can be forwarded into one or more outputs, set by
parameters.

Table 6.3.2 "Gate forwarding" communication object table

6.3.3."Threshold comparator" Communication Object

Fig.6.3.3 "Threshold comparator" communication object


Data
NO. Object Function Name Flag DPT
Type
4bit 3.007 dimming

1byte 5.010 counter pulses


6 Threshold value input {{1st Logic}} C,W, U
2byte 7.001 pulses

4byte 12.001 counter pulses

The communication object is used to input threshold value.

14 Logic result {{1st Logic}} 1bit C,T 1.002 boolean

The communication object is used to send the results of logical operation. That is, the value that
should be sent after the object input threshold is compared with the setting threshold value.
Table 6.3.3 "Threshold comparator" communication object table

68
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

6.3.4."Format convert" Communication Object

"2x1bit --> 1x2bit"function: converts two 1bit values to a 2bit value, such as Input bit1=1, bit0=0-->
Output 2bit=2

"8x1bit --> 1x1byte"function: converts eight 1bit values to a 1byte value, such as Input bit2=1, bit1=1,
bit0=1,other bits are 0--> Output 1byte=7

"1x1byte --> 1x2byte"function: converts one 1byte values to a 2byte value, such as Input 1byte=125-->
Output 2byte=125.Although the value remains the same, the data type of the value is different.

"2x1byte --> 1x2byte"function: converts two 1byte values to a 2byte value, such as Input 1byte-low
= 255 ($FF), Input 1byte-high = 100 ($64) --> Output 2byte = 25855 ($64 FF)

"2x2byte --> 1x4byte"function: converts two 2 byte values to a 4byte value, such as Input 2byte-low =
65530 ($FF FA), Input 2byte-high = 32768 ($80 00)--> Output 2byte = 2147549178 ($80 00 FF FA)

"1x1byte --> 8x1bit" function: converts one 1byte values to eight 1but value, such as Input 1byte=200 -->
Output bit0=0, bit1=0, bit2=0, bit3=1, bit4=0, bit5=0, bit6=1, bit7=1
69
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

"1x2byte --> 2x1byte"function: converts one 2byte values to two 2byte value, such as Input 2byte =
55500 ($D8 CC) --> Output 1byte-low = 204 ($CC), Output 1byte-high =216 ($D8)

"1x4byte --> 2x2byte"function: converts one 4byte values to two 2byte value, such as Input 4byte =
78009500 ($04 A6 54 9C) --> Output 2byte-low = 21660 ($54 9C), Output 2byte-high =1190 ($04 A6)

"1x3byte --> 3x1byte"function: converts one 3byte values to three 1byte value, such as Input 3byte = $78
64 C8--> Output 1byte-low = 200 ($C8) , Output 1byte-middle = 100 ($64) , Output 1byte-high =120 ($78)

"3x1byte --> 1x3byte"function: converts three 1byte values to a 3byte value, such as Input 1byte-low =
150 ($96), Input 1byte-middle = 100 ($64), Input 1byte-high = 50 ($32)--> Output 3byte = $32 64 96
Fig.6.3.4 "Format convert" communication object
Object Data
NO. Name Flag DPT
Function Type
1bit 1.001 switch

1byte 5.010 counter pulses(0..255)

6 Input ... {{1st Logic}} 2byte C,W,U 7.001 pulses

3byte 232.600 RGB value 3x(0..255)

4byte 12.001 counter pulses

The communication object is used to input a value that needs to be converted.


1bit 1.001 switch

2bit 2.001 switch control

1byte 5.010 counter pulses(0..255)


14 Output ... {{1st Logic}} C,T
2byte 7.001 pulses

3byte 232.600 RGB value 3x(0..255)

4byte 12.001 counter pulses

The communication object is used to output the converted value.


Table 6.3.4 "Format convert" communication object table

70
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

6.3.5."Gate function" Communication Object

Input/Output - 1bit[On/Off]

Input/Output - 1byte[0..100%]

Input/Output - 1byte[0..255]

Input/Output - 2byte[Float]

Input/Output - 2byte[0..65535]
Fig.6.3.5 "Gate function" communication object
Data
NO. Object Function Name Flag DPT
Type
1.001 switch

1bit 5.001 percentage

6 Input {{1st Logic}} 1byte C,W 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to input a value that needs to gate filter.

7 Gate input {{1st Logic}} 1bit C,W 1.002 boolean

The communication object is used to control the switch status of gate input. Input signal is
allowed to pass when gate open, then output, and the current input status is still sent if there is a
change; Can not pass when gate close.
1.001 switch

bit 5.001 percentage

14 Output {{1st Logic}} 1byte C,T 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to output the value after gate filtering. Only when gate input
status is open, output is available, defined by the object "Gate input".
Table 6.3.5 "Gate function" communication object table

71
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

6.3.6."Delay function" Communication Object

1bit[On/Off]

1byte[0..100%]

1byte[0..255]

2byte[Float]

2byte[0..65535]
Fig.6.3.6 "Delay function" communication object
Data
NO. Object Function Name Flag DPT
Type
1.001 switch

1bit 5.001 percentage

6 Input {{1st Logic}} 1byte C,W 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to input a value that needs to delay.


1.001 switch

1bit 5.001 percentage

14 Output {{1st Logic}} 1byte C,T 5.010 counter pulses

2byte 9.001 temperature

7.001 pulses

The communication object is used to output that needs to delay converted value, delay time is
defined by the parameter.
Table 6.3.6 "Delay function" communication object table

72
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold

6.3.7."Staircase lighting" Communication Object

Fig.6.3.7 "Staircase lighting" communication object


Data
NO. Object Function Name Flag DPT
Type
6 Trigger value {{1st Logic}} 1bit C,W 1.017 trigger

The communication object is used to receive the value to trigger staircase lighting.

7 Light-on duration time {{1st Logic}} 2byte C,W 7.005 time(s)

The communication object is used to modify the staircase light-on duration time, the modified
range is referenced from the range defined by the parameter, take the limit value if exceeded.
1bit 1.001 switch
14 Output {{1st Logic}} C,T
1byte 5.010 counter pulses

The communication object is used to output value 1 when trigger, and send value 2 after duration
time. Telegram value is determined by the parameter setting datatype.
Table 6.3.7 "Staircase lighting" communication object table

73