Universal Dimming KNX
Universal Dimming KNX
ADUD-01/02.3
ADUD-02/02.3
ADUD-04/02.3
wet environment;
2.Do not fall the device to the ground or make them get hard impact;
3.Do not use wet cloth or volatile reagent to wipe the device;
troubleshooting.
If there is no
Lamp driver is not good Test with an additional improvement, it is
Lamp flickers in enough, unstable incandescent lamp or
5 suggested to
dimming voltage, compatibility electronic dummy load
issue in parallel replace the lamp or
driver
Chapter 1 Summary
KNX Universal Dimming Actuator,1/2/4-Fold (hereinafter referred to as Dimmer) has 1/2/ 4 output
channels, and it can connect with dimmable lamps (such as incandescent lamps, halogen lamps,
energy-saving lamps, LED, etc.), and you can dim, preset scene, switch these lamps or other operations
This dimmer is a modular installation device for fast installation in the distribution board on 35 mm
mounting rails to DIN EN 60 715, the output adopts screw terminal to realize electrical connection. Bus
connection is directly connected via KNX terminal, the additional power supply is not required except
KNX bus.
You can build the various scenes with the dimmer, such as watch movie, entertainment, dinner and
rest, and so on; its brightness value can be set as any value (1-100%); it is able to set the duration time
to dim up or down to the target brightness and the gradual speed to extend the luminaries life and save
energy.
The physical address assignment and parameter settings can be used with the engineering tool
In use you need to note the type of connected electrical load, thus reasonable select them and
note their technical performance. If the technical performance of the selected load is not consistent
with the technical performance of the dimmer, it is possible to affect the dimming effect.
The manual provides detailed technical information about the dimmer, including installation and
programming details, and explains how to use the dimmer in conjunction with examples in actual use.
1
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
6 dimming curves, including Linear, Exponential, Cubic, Quadratic, Logarithmic, Root and
Individual or parallel output (Parallel can expand the load capacity, only apply for 2/4-fold)
Staircase lighting, Flashing switch and Delay switch, as well as Scene, Threshold, Forced
Logic function, with AND, OR, XOR, Gate forwarding, Threshold comparator, Format convert,
2
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
<180mW (2 fold)
<195mW (4 fold)
trailing edge)
4 channel 1000W
Operation and Programming button and Red LED For assigning the physical address
display
3
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Transport – 25 °C ... + 70 °C
Dimension 36 x 90 x 64 mm (1 fold)
72 x 90 x 64 mm (2 fold)
144 x 90 x 64 mm (4 fold)
0.3kg (2 fold)
0.5kg (4 fold)
4
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
2.1.Load type
transformer
Capacitive load
Inductive load
LED load
5
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Individual or parallel outputs can be selected for 2/4-fold dimmer, and the parallel can expand the
load capacity. Load type as following:
Load type Max. Load capacity (110V)
Parallel with 2 channels Parallel with 3 channels Parallel with 4 channels
Leading edge Trailing edge Leading edge Trailing edge Leading edge Trailing edge
LV Halogen lamp with Electronic 300W 300W 400W 400W 500W 500W
transformer
Leading edge Trailing edge Leading edge Trailing edge Leading edge Trailing edge
LV Halogen lamp with Electronic 500W 500W 750W 750W 1000W 1000W
transformer
(Down light,Spotlight)
6
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Note:
It is not permitted to connect inductive and capacitive loads together at the same output.
However, mixing of loads such as capacitive + resistive loads or inductive + resistive loads is allowed
to connect, but power reduction needs to be considered. It is more advisable to connect the same type
The max. load capacity depends on the surge current and power loss of the lamp, these types of
lamp will cause large heating and high surge current in leading edge mode, especially LED lamp, so it
is not recommended to drive LED in leading edge mode, make sure the connected lamp do not trigger
7
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
2.2.Operation mode
Explanation of the dimming system: turn off dimmer in leading edge and turn on in trailing edge. As
shown in the following figure, no voltage input from zero point until dimmer is turned on. It is suitable
Explanation of the dimming system: turn on dimmer in leading edge and turn off in trailing edge. As
shown in the following figure, dimmer will be turned on the zero-crossing point, during this moment, the
voltage is very low and there is no inrush current to the load. In this way, there is no minimum load
requirement, so that allows for better performance of a single lighting or a very small load and extends
the life of the lamp, as well as reduce the interference to the power grid. It is suitable for resistive or
capacitive loads.
8
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
3.1.Dimension drawing
1-Fold
2-Fold
4-Fold
9
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
3.2.Connection Diagram
Individual 1 channel Individual 2 channels Parallel with 2 channels Parallel with 4 channels
⑤ Channel indication LED: in normal mode, LED off is the lamp off, LED on is the lamp on; in manual
mode, flashing slowly is dimming manually. Flashing fast is channel abnormality (Short-circuit,
⑥Channel button: when no ETS configuration, press to switch on/off; in manual mode, short press to
switch on/off, long press for dimming up/down, long press then release to stop dimming
Long press to switchover Man. and Auto. mode, LED on is Man. mode and off is Auto. mode.
Reset the device to the factory configuration: press the programming button and hold for 4 seconds
then release, repeat the operation for 4 times, and the interval between each operation is less than 3
seconds
10
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
General function
General function includes device In operation setting, central control (Switch, Dimming), safety
In addition, central control function only applies for 2/4-Fold Dimmers, and it is not supported by
1-Fold Dimmer.
Output channel
There are 1/2/4 output channels according the product type, support to switch, relative
dimming/absolute dimming, feed back the status of switch, brightness and the abnormal status
(short-circuit, over-voltage, over- temperature and operating voltage failure), as well as reset behaviour
after download/bus failure/bus recovery. Individual or parallel outputs can be selected, and the parallel
can expand the load capacity, which only applies for 2/4-fold.
Load types and dimming curves can be independently configured, as well as extension functions
including Staircase lighting, Flashing switch, Delay switch, Scene, Threshold, Forced operation, Safety
For output function, the definition of function priority: Manual > Forced > Safety > other functions,
after exiting higher priority, the next priority action needs to be executed.
11
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Logic function
Up to support 8 channels of logic, each channel up to support 8 inputs and 1 logic result.
Logic function support functions, including AND, OR, XOR, Gate forwarding, Threshold comparator,
12
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
5.1.KNX Secure
Dimmer is a KNX device that complies with the KNX secure standard. That is, you can run the
The device with KNX secure will be displayed notes on ETS, as shown as Fig.5.1(1).
If secure commissioning is actived in ETS project, the following information must be considered during
device debugging:
It is essential to assign a project password as soon as a KNX Secure device is imported into a
The password must be kept in a safe place – access to the project is not possible without it (not
even the KNX Association or device manufacturer will be able to access it)!
Without the project password, the commissioning key will not be able to be imported.
A commissioning key is required when commissioning a KNX Secure device (first download). This
key (FDSK = Factory Default Setup Key) is included on a sticker on the side of the device, and it must be
On the first download of the device, a window pops up in the ETS to prompt the user to enter the
The certificate can also be read from the device using a QR scanner (recommended).
13
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Alternatively, the certificates of all Secure devices can be entered in the ETS beforehand.
This is done on the "Security" tab on the project overview page, as shown in Fig.5.1(3) below.
The certificates can be also added to the selected device in the project, as shown in Fig.5.1(4).
There is a FDSK sticker on the device, which is used for viewing FDSK number.
Without the FDSK, it will no longer be possible to operate the device in KNX Secure mode
after a reset.
The FDSK is required only for initial commissioning. After entering the initial FDSK, the ETS will
14
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The FDSK will be required again only if the device was reset to its factory settings (e.g. If the device
FDSK
Fig.5.1(5)
Example:
If this application in the project needs to be tried with another device, it is no longer the original
device. When the application is downloaded to a new device, the following prompt will appear on the
left of Fig.5.1(6), click yes, the Add Device Certificate window will appear, then enter the initial FDSK of
the new device, and you need to reset the device to the factory settings (it is not required if the device is
still factory default; If it has been used, it will be required to reset, otherwise the following error
message will appear on the right of Fig.5.1(6)), and then the device can be successfully downloaded
again.
Fig.5.1(6) Example
Whether the device is replaced in the same project, or the device is replaced in a different project,
the processing is similar: Reset the device to the factory settings, then reassign the FDSK.
15
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
After the device is downloaded successfully, the label Add Device Certificate turns gray, indicating
that the key for this device has been assigned successfully, as shown in Fig.5.1(7) below.
Fig.5.1(7)
Keys and passwords can be exported as needed to the use of security keys outside of the
associated ETS projects. As shown in Fig.5.1(8) below, the file extension is .knxkeys.
Fig.5.1(8)
Note: Any USB interface used for programming a KNX Secure device must support "long frames".
16
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the delay time to send to bus after the device bus recovery.
Options: 0..15 s
The setting dose not contain the device initialization time, and bus telegrams received during delay
This parameter is for setting the time interval when cyclically send telegrams through the bus to
indicate this device in normal operation. When set to "0", the object "In operation" will not send a
telegram. If the setting is not "0", the object "In operation" will send a telegram according to the setting
period time with logic "1" to the bus. Options: 0…240 s, 0= inactive
As to reduce the bus load as much as possible, the maximum time interval should be selected
This parameter is for setting whether to enable manual operation, which is mainly convenient for
engineers to debug or check the lamps, when enabled, you can manually switch and dim each output
channel.
17
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The definition of function priority: Manual > Forced > Safety > other functions, after exiting higher
priority, the next priority action needs to be executed. When during manual operation, the telegrams
from bus will be ignored and not executed, but the statuses of low priority (Forced/Safety) will be
recorded in the background, and they will be executed after exiting manual operation.
Manual operation is enabled by default in case of no database; after download, enable manual or
This parameter is for setting the behaviour when exit manual operation. Options:
This parameter is visible when ”Both long press and automatic delay time” is selected by previous
parameter. Set the delay time for exiting manual operation automatically, and timing from the last
This parameter is for setting the object value of safety status cancellation for whole device, while
When enter safety status, execute the configured behaviour of the channel if its safety function is
This parameter is for setting the period to monitor the telegram of safety object.
Options: 0...1000 s
If the period is greater than 0, the telegram to cancel safety status was not received during the
monitoring period, enter the safety status. Exit this status and reset the monitoring period when a
18
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
cancellation telegram is received. It is also possible to enter the safety status directly by receiving the
If the period is set as 0, enter the safety status directly by receiving the reversed value defined by
the previous parameter, and receiving cancellation value is to exit the status.
Setting page of logic function interface is visible after this parameter enabled.
19
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for displaying the device type, it is according to the product:
1-Fold
2-Fold
4-Fold
This parameter is visible when device type is 2-Fold or 4-Fold. Set the dimming channels. For the
dimmer with multiple channels, individual or parallel channels can be configure. Parallel channels can
Individual
Parallel (A+B)
Individual
20
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Parallel (A+B+C+D)
For the dimmer with multiple channels, these parameters are visible depends on the previous
parameter. Set whether to enable dimming channel, and corresponding window is visible when enabled.
Configuration of individual channel is as same as the parallel channel, the following is an example
of Channel A.
21
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
22
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the load type of the channel. Options:
This parameter is for setting dimming cure of the channel, display corresponding preview figure
23
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Quadratic function
When "User defined" is selected, user can custom a dimming curve, more detail please refer to
chapter 5.3.2.
This parameter is for setting the time for the whole dimming process, which refers to the time from
minimum to maximum value. Suppose the time is set as 6s, the min. Value is 0% and the max. is 100%,
if the brightness is only dimmed from 0% to 50%, then the dimming time only takes 3s.
Options: 2...255 s
If the channel function has not specified a dimming time, use the time set by this parameter,
functions such as switch on/off lamps, forced, safety, staircase lighting, threshold, etc.
24
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
These parameters are for setting minimum and maximum brightness values individually, to limit
the output range of dimming brightness, which is allow the lamps work in a better brightness range
This range is not allowed to be exceeded in any status of lamps on, including threshold, forced,
safety functions, etc. Output as min. value when the brightness is lower than the min., and output as
Options of the min. value: 1...49 %; Options of the max. value: 50...100 %
This parameter is for setting the brightness when the lamp is switched on. Options:
This parameter is visible when previous parameter is selected "Preset brightness value". Set the
This parameter is for setting the dimming mode when the lamp is switched on. Options:
Jumping
Dimming
Dimming: switch on with dimming to the target brightness and use the General dimming time.
This parameter is for setting the dimming mode when the lamp is switched off. Options:
Jumping
Dimming
Dimming: switch off with dimming and use the General dimming time.
25
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the time for the whole relative dimming process. Options: 2...255 s
This parameter is for setting the time for the whole absolute dimming process. Options: 2...255 s
This parameter is for setting whether allow to switch lamp off via relative dimming. When disabled,
it can only be adjusted downward to the minimum brightness value; while enabled, switch the lamp off
This parameter is for setting the behaviour when absolute dimming value lower than the minimum
To be 0%
0%=0%, otherwise=Minimum brightness value%: output as min. value when the value is lower than
To be the minimum brightness value: output as min. value when the value is lower than the min.,
To be 0%: switch the lamp off directly when the value is lower than the min.
This parameter is for setting whether the lamp needs the startup characteristic additionally when
the lamp is off. Some lamps require a higher voltage to start up when switched off.
Note: the brightness must not exceed the max. and min. value, otherwise it cannot be set in the
ETS.
26
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Like normal
Ignore the telegram: feed back an off telegram immediately to synchronize the status with the
control device.
Dim up based on the startup brightness: use the startup brightness as a based point, and dimming
Like normal
Ignore the telegram: feed back a off telegram immediately to synchronize the status with the
control device.
Jump to startup brightness: jump to the startup brightness immediately and feed back the new
Jump to startup then delay to target: jump to startup brightness firstly then dimming to the target
If the target brightness is higher than startup value, dimming from the startup value to the target
brightness directly, it is only applied to receive the telegrams of objects "Switching" and "Absolute
dimming".
Parameter "Delay time after reach startup"
This parameter is visible when previous parameter is selected "Jump to startup then delay to
27
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
target". Set the delay time for dimming to target brightness after reaching the startup value. Options:
50ms
80ms
100ms
...
2s
4s
5s
Reset behavior
Parameter "Behavior after download"
This parameter is for setting the behaviour of channel after download. Options:
Switching off
Brightness before bus failure: recover to the brightness value stored when the bus failure.
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
This parameter is for setting the behaviour of channel after bus failure. Options:
Switching off
No reaction
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
28
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the behaviour of channel after bus recovery.
Switching off
Brightness before bus failure: recover to the brightness value stored when the bus failure.
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
Parameter "Short-circuit detect for operating supply or device reset if output is off"
This parameter is for setting whether detect short-circuit for operating supply or device reset if
output is off.
When disabled, a short-circuit may be detected only when turn on the lamp until exceed the
When enabled, every time a operating supply or device voltage recovery, it needs to detect a
short-circuit firstly if initially the lamp is off or the brightness is lower than the threshold of short-circuit
detection, but it is not required to detect if the brightness is higher than the threshold of short-circuit
detection. Download database and restart, if the detection has been normal before the download, there
29
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Central control
Central control is used to control the switching and dimming of all channels, each channel can be
configured to support central control or not. When receive the telegram of central control from bus,
Note: central control function only applies for 2/4-Fold Dimmers, and it is not supported by 1-Fold
Dimmer.
Parameter “Switching”
Status feedback
Parameter "Switching/Brightness value/Short-circuit/Over-voltage/Over-temperature/Operating voltage
failure"
These parameters are for setting the way to feed back the status of switch, brightness and
abnormal status. The abnormal status including short-circuit, over-voltage, over-temperature, operating
Trigger hardware protection when channel load terminal is short-circuited, and feed back the
status to bus. It will disconnect the output when in protection. If it is the first time a short-circuit has
been detected since power on, disconnect the output first then wait a 1 minute to output the current
control value again; but if there is still a short-circuit, disconnect the output permanently, and cannot be
Trigger hardware protection when the operated voltage is higher than the rated voltage, and feed
30
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
back the status to bus. It will disconnect the output when in protection.
When the measured internal temperature exceeds 90℃ for 10s, then will trigger over-temperature
protection and send the status to bus. The brightness will down to 20% or to the minimum value under
the protection status. After the temperature is reduced to below 70℃, output normally if a new control
telegram is received.
Operation voltage is failure when no valid over-zero signal is detected, and feed back the status to
bus. When in voltage failure, it can not feed back control status and no drive signal if receive the control
telegram, need to power supply normally and has actual output value can feed back the current status
of the lamp.
Extension function
Parameter "Scene function"
Setting page of scene function interface is visible after this parameter enabled.
Setting page of time function interface is visible after this parameter enabled.
Setting page of threshold function interface is visible after this parameter enabled.
Setting page of forced function interface is visible after this parameter enabled.
Setting page of safety function interface is visible after this parameter enabled.
Setting page of operating hours counter interface is visible after this parameter enabled.
31
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the number of curve coordinate points. Options: 2...16
This parameter is for setting KNX dimming value of the curve. Options: 1..100%
For user defined dimming curve, the first and the last one points are fixed to 1% and 100%.
Note: the previous KNX dimming value must be small than next one, otherwise it can not be set
on the ETS:
32
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the output value corresponding to the KNX dimming value.
Options: 1..100%
Note: the previous output value must be small than next one, otherwise it can not be set on the
ETS:
33
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Step 1: use the linear function curve at first to determine the adjustable range, then
obtain the minimum and maximum adjustable brightness values of the applied lamp with
absolute dimming;
Step 2: when testing in step 1, you can experience the brightness changes with
relative dimming, then checking the number of curve areas and coordinate points;
Step 3: the minimum brightness value is the point of knx value 1%, the maximum
Step 4: add the coordinate points of the middle section according to the planning
area;
there may also be slight adjustment of the coordinate points or increase the configuration
areas, and even need to adjust the dimming time, until achieve the best results for user
satisfaction.
34
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Parameter windows are visible according to the enabling of the extension function parameters.
Scene function can work with the control panel or other software to execute the setting scene and
This parameter is for setting whether to override the scene stored values during application
download. If select to overwrite, follow the parameter setting, otherwise for the brightness value
corresponding to the scene number that has saved the modified value has executed, the last saved
value will remain; for the modified brightness has not executed, still use the value set by parameter.
35
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Scene x (x=1~16)
Parameter "Description"
This parameter is for setting the name description of the corresponding scene, up to 30
characters.
This parameter is for setting the triggered scene number, up to 16 scenes. Options: 0...64
When scene number is 0, it is invalid, and the brightness and dimming time cannot be set, as
shown as following:
When scene numbers are greater than 0, if there are same scene numbers, display following error
message:
Parameter "Brightness"
This parameter is for setting the brightness of the corresponding scene. Options: 0...100 %
Parameter "Dimming"
This parameter is for setting the dimming time of the corresponding scene. Options: 2...255 s
36
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Delay switch
Flash switch
Staircase lighting
Fig.5.3.3.2 "Time function" parameter window
This parameter is for setting the time function, its brightness is depending on the value of switch
on/off. Options:
Delay switch
37
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Flashing switch
Staircase lighting
Delay switch: delay a period time to switch on/off, dimming mode is Jumping.
Staircase lighting: dimming mode is Dimming, use the General dimming time.
Note: time function will be interrupted directly after entering safety or forced operation.
These two parameters are visible when "Delay switch" is selected. Set the delay time for switch
on/off, execute the on/off telegram received from bus after the delay has elapsed. During delay time,
These two parameters are visible when "Flashing switch" is selected. Set the duration time of
This parameter is visible when "Flashing switch" is selected. Set the number of flashing cycles, a
cycle includes an on and an off. 0 means the cycles is no limited. Options: 0...10000
This parameter is visible when "Flashing switch" is selected. Set the status after flashing. Options:
Switching off
Switching on
Unchange
Note: there is a possibility of an extra half cycle of action when "Switching on" or "Unchange" is
selected.
38
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is visible when "Flashing switch" is selected. Set the control mode of flashing.
Options:
Start with"1", Stop with "0": it will start flashing with value "1" and stop flashing with "0", action
to the end status when stopped, which is defined via previous parameter.
Start with"0", Stop with "1": it will start flashing with value "0" and stop flashing with "1", action
to the end status when stopped, which is defined via previous parameter.
Start with"0/1", can not be stopped: it will start flashing with value "0" or "1", and can not stop
until the number of the flashing cycles is exhausted, or stop via the interruption from other
operation.
This parameter is visible when "Staircase lighting" is selected. Set the duration time of staircase
lighting switch on, and switch off automatically after the time has elapsed.
This parameter is visible when "Staircase lighting" is selected. Set whether to retrigger or extend
the duration time when receive an on telegram during the time. Options:
Not retriggerable
Retriggerable
Not retriggerable: ignore the telegram, switch off automatically after the time has elapsed.
Retriggerable: retrigger the duration time when receive an on telegram during the time.
Extend duration time: add up a duration time to the remaining time when receive an on telegram
during the duration time. For example the duration time is set as 60s, but it is still has 40s left, and
receive an on telegram at the moment, then the new duration time is 40s+60s =100s, and the staircase
39
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
light will be turned off automatically after the 100s is elapsed. If receive multiple on telegrams
continuously, the duration time will continue to add up until the maximum time is reached.
This parameter is visible when "Staircase lighting" is selected. Set the control mode of staircase
lighting. Options:
Start with "1", Stop with "0": it will switch on the staircase light with the value "1" and stop the
timing with "0", keep the current lamps status until it is changed by other operations.
Start with "1", no reaction with "0": it will switch on the staircase lights with the value "1" and no
Start with"0/1", can not be stopped: it will switch on the staircase lights with the value "1" or "0",
and can not stop until the duration time is exhausted, or stop via the interruption from other
operation.
Start with"1", Off with "0": it will switch on the staircase lights with the value "1" and switch off with
"0"
This parameter is visible when "Staircase lighting" is selected. Set whether to prewarn before
staircase light time end, and set the prewarning mode. User can be noticed before the staircase light
No
Via object
40
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
No: no prewarn, and switch off automatically after the time has elapsed.
No, but dim-down the dimming value after end: no prewarn, but dim down the brightness after the
Via flashing switching on-off: prewarn via a short flashing, 1s to switch on and 1s to switch off,
Via flashing switching on-off and object: prewarn, refer to the explanation of the previous options.
Dim-down the dimming value: prewarn via dimming down the brightness.
Dim-down the dimming value and via object: prewarn, refer to the explanation of the previous
options.
This parameter is visible when the selection does not contains "No...". Set the time of prewarning.
Options: 00:00:05s...00h:59min:59s
Note: the warning time must be less than the duration time, or it cannot set on the ETS.
Note: the warning time is contained in the startup time of staircase lighting. If switch off before
This parameter is visible when the selection contains "Dim-down the dimming value....". Set the
brightness value of dimming down at the end of the staircase lighting. Options: 1...100 %
This parameter is visible when "Staircase lighting" is selected. Set whether the duration time can be
changed via bus. Store the modified value when bus failure, recovery to the value set by parameter after
download.
41
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Switch on/off or dimming the brightness according to telegram from the bus and threshold set on
the ETS. Note: the brightness of threshold function is depending on the value of switch on/off.
Temperature (DPT9.001)
Illuminance (DPT9.004)
These two parameters are for setting the threshold value 1 and 2. Options are display according to
42
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Note: the threshold 1 must be less than threshold 2, or they cannot be set on the ETS, as shown
as following:
This parameter is for setting whether the threshold 1 and 2 can be changed via bus.
Store the modified value when bus failure, recovery to the value set by parameter after download.
This parameter is for setting whether the threshold 1 and 2 with hysteresis. Options:
Without hysteresis
With hysteresis
The hysteresis can avoid the unnecessary behaviour caused by the input value if the value is
This parameter is for setting the output type after threshold comparison. Options:
Switching
Brightness value
Set the output value when input value is less than or equal to the threshold 1. Following parameter
Switching off
Switching on
Unchange
Set the output value when input value is between the threshold 1 and 2. Output parameter and its
Set the output value when input value is greater than the threshold 2. Output parameter and its
1bit
2bit
The lamp can be forcibly fixed at a brightness in some special situations. Forced function has the
highest priority. Ignore the normal control telegram received from bus when during in forced or safety
operation.
1bit
2bit
This parameter is visible when 1bit. Set the object value for activating or canceling the forced.
Options:
0=Forced/1=Cancel
1=Forced/0=Cancel
This parameter is visible when 1bit. Set behavior at forced operation. Options:
Switching off
Unchange
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
This parameter is visible when 2bit. Set the behavior at forced operation "switch on" when receive
Unchange
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
This parameter is visible when 2bit. Set the behavior at forced operation "switch off" when receive
This parameter is for setting the behavior at end of forced operation. Note: the telegram values
45
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Switching off
Unchange
1.When receive a telegram to end forced operation, it is valid if the forced operation has been
2.When a telegram to end forced operation is valid, if there is another priority (safety operation)
active in the device, execute this action of this priority; otherwise, ignore the end telegram and execute
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
Safety function can work with external sensor and perform dimming behaviour in some emergency
situations. Safety function has the second highest priority and only lower than forced function.
These two parameters are for setting the behavior for activating or canceling the safety operation.
Options:
Switching off
Unchange
46
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is visible when "Preset brightness value" is selected. Set the preset brightness
1.When receive an end telegram, it is valid if the safety operation has been activated before,
2.When the end telegram is valid, if there is another priority (forced operation) active in the device,
execute this action of this priority; otherwise, ignore the cancel telegram and execute the action of
safety operation.
This parameter is for setting whether activate the function of operating hours counter, and setting
the datatype. It is used to count the time that the lamp has been switched on. If brightness is greater
than “0”, start timing. It can be used as a seconds counter or an hours counter. Options:
Inactive
This parameter is visible when “Value in s (DPT 13.100)” is selected. Set the cycle for sending
47
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
counter value. If set to 3600s, that is send a counter value to the bus every 3600s.
Options: 60...65535 s
This parameter is visible when “Value in h (DPT 7.007)” is selected. Set the cycle for sending
counter value. If set to 1h, that is send a counter value to the bus every hours. Options: 1...255 h
This parameter is for setting whether to enable the monitoring of operating hours counter, which is
used to monitor the time that the lamp has been switched on. When the time is closed to the end of the
lamp's life, send a telegram to remind the user to change a new lamp.
This parameter is for setting the threshold for operation hours, usually refer to the lamp’s life. The
This parameter is for setting the cycle of sending status, 0 is no send. Send on change is enabled
48
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the setting interface of logic function, display corresponding logic
This parameter is for setting the name description for logic function, up to input 30 characters.
AND
OR
XOR
Gate forwarding
Threshold comparator
Format convert
Gate function
Delay function
Staircase lighting
AND/OR/XOR: as the parameter is similar to the communication object (only the logic algorithm is
This parameter is for setting whether input x to calculate, whether to normally calculate or inverted
calculate.Options:
Disconnected
Normal
Inverted
50
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Inverted: invert the input value, then to calculate. Note: not to invert the initiate value.
This parameter is for setting the initial value of logic input x. Options:
This parameter is for setting whether to invert the logic calculation result. Options:
No
Yes
This parameter is for setting whether to send the read request to the logic input object after device
No
Yes
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram:every time the object received a new input value will the logic result be
sent to the bus;
Every change of output object:only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic calculate, the logic result will be sent even if it has no change.
Base: None
0.1s
51
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
1s
...
10s
25s
Factor: 1..255
This parameter is for setting the delay time for sending the logic calculation result to the bus. Delay
time = Base × Factor, if option "None" of Base is selected, then there is no delay.
1bit
4bit
1byte
52
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the initial scene where logical gate forwarding can be performed by
default after device starts, which needs to be configured in the parameters. Options:1..64, 0=inactive
Note: gate scene is recommended to be selected before operating, or it will enable the initiate
scene by default.
This parameter is for setting scene number of logic gate forwarding. Up to 8 trigger scene number
This parameter is for setting the output of input X (X=A/B/C/D) after gate forwarding. Options:
Disable
Output A
Output B
...
Output B,C,D
According to the options, one input can be forwarded into one or more outputs, the output value is
53
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the threshold value data type. Options:
This parameter is for setting threshold value, the range depends on the data type. Options:
2byte unsigned value (DPT7.001) 0..65535 / 2byte signed value (DPT8.x) -32768..32767 /
0..4294967295 /Ext. temperature value (DPT 9.001) -20..95℃ / Ext. humidity value (DPT 9.007)
54
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is visible when object datatype is selected "2byte float value (DPT9.x)", "Illuminance
value (DPT 9.004)". Set the hysteresis threshold value. Options: 0..500
This parameter is for setting the logic result value that should be sent when threshold value Less
than, equal to, not equal to, greater than, less than or equal to the setting valve. When object datatype is
selected "2byte float value (DPT9.x)", can only set the object value less than or greater than threshold
value. Options:
If there is a conflict between the setting options between parameters, the base on the value that
should be sent when reach the final parameter condition. For example: parameter "If Object
value=Threshold value" is set to be "Send value "0" ";parameter "If Object value<=Threshold value" is
set to be "Send value "1" ";when object value is equal to the threshold value, then the logic result will
send "1".
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram: every time the object received a new input value will the logic result be
Every change of output object: only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.
Base: None
0.1s
1s
...
10s
25s
Factor: 1..255
This parameter is for setting the delay time for sending the logic algorithm result to the bus. Delay
time = Base x Factor, if option "None" of Base is selected, then there is no delay.
Parameter "Function"
2x1bit-->1x2bit
8x1bit-->1x1byte
1x1byte-->1x2byte
2x1byte-->1x2byte
2x2byte-->1x4byte
1x1byte-->8x1bit
1x2byte-->2x1byte
56
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
1x4byte-->2x2byte
1x3byte-->3x1byte
3x1byte-->1x3byte
This parameter is for setting the condition of sending logic result. Options:
Receiving a new telegram: every time the object received a new input value will the logic result be
Every change of output object: only when logic result has changed will it be sent to the bus.
Tip: when in the first time to logic algorithm, the logic result will be sent even if it has no change.
1bit[On/Off]
1byte[0..100%]
1byte[0..255]
2byte[Float]
2byte[0..65535]
57
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is visible when "1bit[On/Off]" is selected. Set whether to filter On or Off telegram,
Deactivate
On filter out
This parameter is visible when "1bit[On/Off]" is selected. Set whether to invert the value then output
it. Options:
Normal
Inverted
This parameter is for setting whether to invert the gate object value then output it. Options:
Normal
Inverted
This parameter is for setting the gate status after power on. Options:
Disable
Enable
This parameter is for setting whether to save input signal on gate close. Options:
No
Yes
No: disable to save the input, the input values received during the gate closing period are ignored;
Yes: enable to save the input, the input values received during the gate closing period are output
58
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
1bit[On/Off]
1byte[0..100%]
1byte[0..255]
2byte[Float]
2byte[0..65535]
This parameter is for setting the delay time that output object forwards the value when the input
59
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
This parameter is for setting the telegram value of the object "Trigger value". Options:
0 or 1
1bit
1byte
This parameter is for setting duration time of staircase lighting after the stair light power on.
Options: 10..6500 s
These parameters are for setting the value to send. Send value 1 when trigger, and then send value
2 after duration time. Options display according to the output object datatype.
OFF
ON
Parameter "Retriggering"
This parameter is for setting whether to trigger re-timing when received trigger value in delay time.
Options:
Disable
Enable
60
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is the medium to communicate other device on the bus, namely only
NOTE: "C" in "Flag" column in the below table means enable the communication function of the
object; "W" means value of object can be written from the bus; "R" means the value of the object can
be read by the other devices; "T" means the object has the transmission function; "U" means the value
The communication object is used to periodically send a telegram "1" to the bus to indicate that
the device is working properly.
2 Central: Switching General 1bit C,W 1.001 switch
The communication object is used to receive a command of switching on/off lamps for central
control, it only applies to the channel that the central control is enabled.
3 Central: Relative dimming General 4bit C,W 3.007 dimming
The communication object is used to receive a command of relative dimming for central control,
to dim up or dim down. It only applies to the channel that the central control is enabled.
4 Central: Absolute dimming General 1byte C,W 5.001 percentage
The communication object is used to receive a command of absolute dimming for central control,
it only applies to the channel that the central control is enabled.
5 Central: Safety General 1bit C,W 1.005 alarm
The communication object is used to receive the 1bit telegram that is sent from other device
(such as sensor, controller, etc.), the cancel telegram value is decided by the parameter.
61
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
If no corresponding telegram is received within the monitoring time, it is assumed that other
devices are failure, and the channel with a safety function activates the safety operation. With a
monitoring time of 0, it is also possible to activate and exit the safety operation by receiving the
corresponding value with this object.
In the case that the safety operation is not active, the cancel telegram is meaningless and it will be
ignored.
Table 6.1 "General" communication object table
The communication object is used to receive a command of switching on/off lamps. Telegrams:
1——Switch on
0——Switch off
The name in parentheses changes with the parameter "Description (max 30char.)". If description
is empty, display "Channel A - ..." by default. The same below.
79 Relative dimming Channel A-{{...}} 4bit C,W 3.007 dimming
The communication object is used to receive a command of relative dimming, to dim up or dim
down.
Dimming down when telegram is 1~7, and the larger this range the adjust step is smaller. That is,
the maximum step of dimming down when is 1, and the minimum step of dimming down when is 7,
stop dimming when is 0;
62
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Dimming up when telegram is 9~15, and the larger this range the adjust step is smaller. That is,
the maximum step of dimming up when is 9, and the minimum step of dimming up when is 15, stop
dimming when is 8.
80 Absolute dimming Channel A-{{...}} 1byte C,W 5.001 percentage
The communication object is used to report the status of the current switch to the bus. Send "1" to
the bus when the value of the brightness is larger than 0, send "0" to the bus with value of "0". Send the
status when voltage recovery.
82 Brightness value, status Channel A-{{...}} 1byte C,R,T 5.001 percentage
The communication object is used to report the status of the current brightness value to the bus.
Send the status at power-up when voltage recovery.
83 Short-circuit, status Channel A-{{...}} 1bit C,R,T 1.005 alarm
The communication object is used to report the status of short circuit to the bus. Send the status
at power-up when voltage recovery. Telegrams:
1——Short circuit
0——Normal
84 Over-voltage, status Channel A-{{...}} 1bit C,R,T 1.005 alarm
The communication object is used to report the status of over-voltage to the bus. Send the status
when voltage recovery. Telegrams:
1——Over voltage
0——Normal
85 Over-temperature, status Channel A-{{...}} 1bit C,R,T 1.005 alarm
The communication object is used to report the status of over-temperature to the bus. Send the
status when voltage recovery. Telegrams:
1——Over temperature
0——Normal
87 Operation voltage failure Channel A-{{...}} 1bit C,R,T 1.005 alarm
The communication object is used to report the status of operation voltage failure to the bus.
Operation voltage is failure when no valid over-zero signal is detected. Send the status when voltage
recovery. Telegrams:
1——Operation voltage failure
0——Normal
63
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is used to receive a 8 bit command to recall or storage scene.
Detailed 8bit the meaning of the directive.
Set up a 8bit Orders for the (Binary code): FXNNNNNN
F: '0' recall scene; '1' for storage scene;
X:0;
NNNNNN: Scene number( 0... 63).
As follows:
Object message Description
value
0 Recall scene 1
1 Recall scene 2
2 Recall scene 3
… ...
63 Recall scene 64
128 Store scene 1
129 Store scene 2
130 Store scene 3
… ...
191 Store scene 64
Parameter setting Options are 1~64, actually communication object "Scene" corresponds to the
telegram received is 0~63. Such as parameter settings is the scene 1, communication
object "Scene" sends the scene for 0.
The communication object is visible when "Delay Switch" is selected for time function, used to
turn on the function of delay switch.
89 Flashing switch Channel A-{{...}} 1bit C,W 1.010 start/stop
The communication object is visible when "Flashing Switch" is selected for time function, used to
turn on the function of flashing switch.
89 Staircase lighting Channel A-{{...}} 1bit C,W 1.010 start/stop
The communication object is visible when "Staircase lighting" is selected for time function, used
to turn on the function of staircase lighting.
Duration of staircase lighting
90 Channel A-{{...}} 2byte C,W,R 7.005time(s)
(5..65535s)
The communication object is visible when "Staircase lighting" is selected for time function and
duration time can be changed via bus. Used to modify the time, and save it after voltage failure. If the
duration has not been modified, the value read from the object is the setting value of ETS parameter.
91 Staircase lighting Prewarning Channel A-{{...}} 1bit C,R,T 1.005 alarm
64
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is visible when "Staircase lighting" is selected for time function and
prewarn via bus. Used to send the telegram of prewarning before staircase lighting end. Telegram:
1——Warning
0——End of warning
5.010 counter pulses(0..255)
The communication object is receive the input value of threshold function. Telegram value is
determined by the datatype, and the datatype is determined by the parameter setting.
5.010 counter pulses(0..255)
These two communication objects are visible when the threshold value 1/2 can be changed via
bus. Used to modify the values, and save them after voltage failure. If the thresholds have not been
modified, the value read from the object is the setting value of ETS parameter. Note: threshold value 1
must be less than threshold value 2, or ignore the telegram.
1bit 1.003 enable
95 Forced operation Channel A-{{...}} C,W
2bit 2.001 DPT_Switch control
The communication object is used to trigger a forced operation. Save the trigger status when
voltage failure, and keep the status at voltage recovery.
When 1bit, activate the forced operation when receive telegram 1, at this time, ignore all the other
actions; End the forced operation when receive telegram 0, and the behaviour in forced operation is
defined by parameter.
When 2bit, force to switch off when receive telegram 3; force to switch on when receive telegram
2; End the forced operation when receive telegram 1 or 0.
The end telegram is invalid when the forced operation is not active, and ignore it directly.
2byte 7.007 time (h)
103 Operating hours counter Channel A-{{...}} C,R,W,T
4byte 13.100 time lag (s)
65
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is used to send the accumulated operating time that the lamp has
been switched on to the bus, begin to count when brightness is greater than “0”, and the accumulated
time can also be modified via the bus, and send it after the device is restarted.
104 Reset operating hours counter Channel A-{{...}} 1bit C,W 1.015 reset
The communication object is used to reset the accumulated operating time to 0. Telegrams:
1——Reset
0——NA
105 Exceedance of operating hours Channel A-{{...}} 1bit C,R,T 1.005 alarm
The communication object is used to send the status to the bus when the accumulated operating
time exceeds the threshold, remind user the exceedance. Send the status when voltage recovery.
Telegrams:
1——Exceed
0——Normal
66
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is used to receive the value of logical input Input a/b/../h.
The name in parentheses changes with the parameter "Description for logic function". If
description is empty, display "1st Logic" by default. The same below.
The communication object is used to select the scene of logical gate forwarding.
1bit 1.001 switch
67
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is used to receive the value of the logic gate input Input x.
1bit 1.001 switch
The communication object is used to output the value forwarded by the logic gate. The output
value is the same as the input value, but one input can be forwarded into one or more outputs, set by
parameters.
The communication object is used to send the results of logical operation. That is, the value that
should be sent after the object input threshold is compared with the setting threshold value.
Table 6.3.3 "Threshold comparator" communication object table
68
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
"2x1bit --> 1x2bit"function: converts two 1bit values to a 2bit value, such as Input bit1=1, bit0=0-->
Output 2bit=2
"8x1bit --> 1x1byte"function: converts eight 1bit values to a 1byte value, such as Input bit2=1, bit1=1,
bit0=1,other bits are 0--> Output 1byte=7
"1x1byte --> 1x2byte"function: converts one 1byte values to a 2byte value, such as Input 1byte=125-->
Output 2byte=125.Although the value remains the same, the data type of the value is different.
"2x1byte --> 1x2byte"function: converts two 1byte values to a 2byte value, such as Input 1byte-low
= 255 ($FF), Input 1byte-high = 100 ($64) --> Output 2byte = 25855 ($64 FF)
"2x2byte --> 1x4byte"function: converts two 2 byte values to a 4byte value, such as Input 2byte-low =
65530 ($FF FA), Input 2byte-high = 32768 ($80 00)--> Output 2byte = 2147549178 ($80 00 FF FA)
"1x1byte --> 8x1bit" function: converts one 1byte values to eight 1but value, such as Input 1byte=200 -->
Output bit0=0, bit1=0, bit2=0, bit3=1, bit4=0, bit5=0, bit6=1, bit7=1
69
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
"1x2byte --> 2x1byte"function: converts one 2byte values to two 2byte value, such as Input 2byte =
55500 ($D8 CC) --> Output 1byte-low = 204 ($CC), Output 1byte-high =216 ($D8)
"1x4byte --> 2x2byte"function: converts one 4byte values to two 2byte value, such as Input 4byte =
78009500 ($04 A6 54 9C) --> Output 2byte-low = 21660 ($54 9C), Output 2byte-high =1190 ($04 A6)
"1x3byte --> 3x1byte"function: converts one 3byte values to three 1byte value, such as Input 3byte = $78
64 C8--> Output 1byte-low = 200 ($C8) , Output 1byte-middle = 100 ($64) , Output 1byte-high =120 ($78)
"3x1byte --> 1x3byte"function: converts three 1byte values to a 3byte value, such as Input 1byte-low =
150 ($96), Input 1byte-middle = 100 ($64), Input 1byte-high = 50 ($32)--> Output 3byte = $32 64 96
Fig.6.3.4 "Format convert" communication object
Object Data
NO. Name Flag DPT
Function Type
1bit 1.001 switch
70
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
Input/Output - 1bit[On/Off]
Input/Output - 1byte[0..100%]
Input/Output - 1byte[0..255]
Input/Output - 2byte[Float]
Input/Output - 2byte[0..65535]
Fig.6.3.5 "Gate function" communication object
Data
NO. Object Function Name Flag DPT
Type
1.001 switch
7.001 pulses
The communication object is used to input a value that needs to gate filter.
The communication object is used to control the switch status of gate input. Input signal is
allowed to pass when gate open, then output, and the current input status is still sent if there is a
change; Can not pass when gate close.
1.001 switch
7.001 pulses
The communication object is used to output the value after gate filtering. Only when gate input
status is open, output is available, defined by the object "Gate input".
Table 6.3.5 "Gate function" communication object table
71
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
1bit[On/Off]
1byte[0..100%]
1byte[0..255]
2byte[Float]
2byte[0..65535]
Fig.6.3.6 "Delay function" communication object
Data
NO. Object Function Name Flag DPT
Type
1.001 switch
7.001 pulses
7.001 pulses
The communication object is used to output that needs to delay converted value, delay time is
defined by the parameter.
Table 6.3.6 "Delay function" communication object table
72
KNX/EIB KNX Universal Dimming Actuator,1/2/4-Fold
The communication object is used to receive the value to trigger staircase lighting.
The communication object is used to modify the staircase light-on duration time, the modified
range is referenced from the range defined by the parameter, take the limit value if exceeded.
1bit 1.001 switch
14 Output {{1st Logic}} C,T
1byte 5.010 counter pulses
The communication object is used to output value 1 when trigger, and send value 2 after duration
time. Telegram value is determined by the parameter setting datatype.
Table 6.3.7 "Staircase lighting" communication object table
73