AC01-Series network inverter manual General
Chapter 1 General
1.1 Safety Precautions
Please fully understand the safety precautions described in this manual before using to ensure safety of both persons and products.
Warning signs and their meanings
The following marks are used in this manual to indicate that this part is of great safety importance. Failure to follow these precautions may
result in personal injury, damage or even death to the product and associated systems.
DANGER: death or major safety accidents may occur due to wrong operations.
Table 1- 1
Operating qualification
This product must be operated by trained professionals. In addition, operators must go through professional skills training, familiar with the
installation, wiring, operation and maintenance of the equipment, and correctly respond to various emergency situations in use.
Safety rules
Safety rules are put forward for your safety and are measures taken to prevent injury to operators and damage to the product and associated
systems; Read this manual carefully before use and strictly follow the safety rules and warning signs in this manual.
● Correct transportation, storage, installation, as well as careful operation and maintenance, is very important for the safe operation of the
frequency inverter. During transportation and storage, the inverter must be protected from shock and shake. It must also be stored in places which
are dry and free from non-corrosive gas, non-conductive dust and where ambient temperature is lower than 60℃.
● This product has dangerous voltage, and it is controlled by a potentially dangerous movement mechanism. Any operations against the
regulations or the requirements of this manual may lead to personal injury or damage of the product and related system.
● Do not wire when power is on otherwise there is a risk of death by electric shock; When connecting cables, checking, or maintaining cables,
power off all related devices and ensure that the DC voltage of the main loop is reduced to a safe level. Wait five minutes before performing related
operations.
● Power cables, motor cables and control cables must be connected tight and all of the ground terminals must be grounded, and the grounding
resistance is less than 10Ω.
● The static electricity of human body will seriously damage the internal sensitive devices. Before performing related operations, please follow
the instructions specified in ESD prevention measures (ESD), otherwise the frequency inverter may be damaged.
● Output voltage of the inverter is a kind of pulse waveform, if the output side is equipped with capacitors or lightning protection varistor
devices to improve the power factor, be sure to remove or refit the input side of the inverter.
● Switch devices such as circuit breakers and contactors shall not be added on the output side of the inverter (if the switch device must be
connected on the output side, the output current of the inverter must be zero when the switch is operated in the control).
● No matter where the fault occurs in the control equipment, it may cause production suspension and major accidents. Therefore, take
necessary external protection measures or backup devices.
● Please use this product only for the purposes prescribed by the manufacturer, usage for special occasions of emergency and rescue like
marine, medical, aviation and nuclear facilities without permission are seriously forbidden.
● Maintenance of this product can only carry out by Veichi or professionals who have been licensed by Veichi, unauthorized modification or
use of accessories without Veichi’s authorization may lead to product failure. Any defective components must be replaced in time for product
maintenance.
1.2 Pre-use
Upon receipt of your ordered products, please check whether the outer package is damaged, open the outer package after confirming that it is
intact, and confirm whether the frequency inverter is damaged, scratched or contaminated (Damage caused during transportation does not fall within
the scope of Veichi’s “three guarantees”). If you receive a product with transportation damage, please contact the company or transportation
1
General AC01-Series network inverter manual
company immediately. After confirming that the received product is intact, please confirm again whether you received what you have ordered.
Figure 1- 1
Table 1- 2
T/S2: -10% ~ 10%; T3: -15% ~ 10%; Voltage unbalance rate: <3%; Frequency: ±5%;
Allowable fluctuation
distortion rate conforming to IEC61800-2
Output frequency
±0.5% of the maximum frequency value
accuracy
T3 model: 150% of rated current for 89 s, 180% of rated current for 10 seconds, 200% rated current for 3 s
Overload capacity
S2 model: 150% of rated current for 24 seconds, 180% of rated current for 3.4 seconds
Motor control mode No PG V/F control, no PG vector control
Modulation mode Optimized space vector PWM modulation
Primary control performance
Motor type Three-phase asynchronous motor & permanent magnet synchronous motor supported
Carrier frequency 2.0kHz ~ 12.0kHz
Speed control range No PG vector control, rated load 1:100;
Steady-state speed
No PG vector control: ≤2% of rated synchronous speed;
accuracy
Starting torque No PG vector control: 150% of rated torque at 0.5Hz;
Torque ripple No PG vector control: ≤0.1% of rated torque
2
AC01-Series network inverter manual General
Four methods: linear torque characteristic curve, self-setting V/F curve, reduced torque characteristic curve (power
V/F curve
1.1 ~ 2.0), square V/F curve
Acceleration & Two methods: linear acceleration and deceleration, S-curve acceleration and deceleration
Deceleration curves Four settings of acceleration and deceleration time, time unit 0.01s, 65000s max.
Power supply voltage compensation enables setting within the range of 50% ~ 100% (the output cannot exceed the
Rated output voltage
Product basic functions
Automatic
The V/F control mode automatically optimizes the output voltage according to the load to realize energy saving.
energy-saving operation
Automatic current
Automatic current limit during operation to prevent frequent overcurrent failure trip
limiting
Instantaneous power
Uninterrupted running during instantaneous power failure through the bus voltage control
failure treatment
PID control, speed tracking and power-off restart, jump frequency, frequency upper and minimum control, program
Standard functions operation, multi-speed, RS485 communication port, analog output, parameter access level setting, common
parameter setting, monitoring parameter comparator output, counting and timing, and swing frequency
Frequency setting Analog voltage/current terminals AS (VS), communication and multi-channel terminals setting, combination of
channel primary and secondary channels, and external keyboard settings can be switched in various ways
Communication setting via upper computer
Producct 品基本功能
Command running
Terminal setting via the X terminal
channel
The number entering via the external keyboard
Start, stop, positive and negative rotation, point, multi-speed, free stop, reset, acceleration and deceleration time
Input command signal
selection, frequency and channel setting and external fault alarm
External output signal 1-way relay output, 1-way collector open output
Overvoltage, undervoltage, current limiting, overcurrent, overload, electronic thermal relay, overheat, overvoltage
Protections stall, data protection, rapid protection, input and output phase loss protection
Function code information of the inverter can be uploaded and downloaded to realize fast parameter replication (only
Parameter copy external keyboard)
1. External keyboard input all parameters of monitoring parameter group including output frequency, given
frequency, output current, input voltage, output voltage, motor speed, PID feedback, PID setting, module
temperature, given torque and output torque.
Condition monitoring 2. The relevant status of the inverter can be indicated through the three LED lights on the product.
POWER indicates the power and it’s red when power is normal.
RUN indicates running status and it’s green when running is normal.
FAULT indicates warning or fault and it’s red when something is abnormal.
Overvoltage, undervoltage, overcurrent, short circuit, phase loss, overload, overheating, overvoltage stall, current
Fault warning limiting, data protection, current fault conditions and historical faults
If the altitude is higher than 1000 meters, reduce 1% for each elevation of 100 meters;
Installation site No condensation, icing, rain, snow, hail, etc., solar radiation lower than 700W/m2, air pressure between 70kPa ~
106kPa
Environment
Temperature & -20℃ ~ +50℃, reduce 5% for each increase of 1℃ when it’s above 40 ℃, 50℃ max (no-load running)
Humidity ≤95%RH (20℃; relative humidity change rate shall not exceed 5% per hour, and no condensation)
Vibration 5.9m/s2(0.6G) when during 9Hz~200Hz
Storage temperature -30℃~+60℃
Installation method wall-mounted
3
General AC01-Series network inverter manual
Table 1- 3
4
AC01-Series network inverter manual Installation
Chapter 2 Installation
Please use the product in strict accordance with the requirements of the environment, wiring, and ventilation described in this chapter.
in order to ensure safety of the users and best performance of the inverter.
AC01-S2-R75G-B
65 150 130 5 5.5 54 139.5 Φ5.2
AC01-T3-R75G-B
AC01-T3-1R5G-B
5
Installation AC01-Series network inverter manual
AC01-S2-2R2G-B
75 205 145 4.7 55 207.9 193.25 Φ5.2
AC01-T3-2R2G-B
AC01-T3-004G-B
Table 2- 2 Installation dimensions of V2 model
Note:
1. Select the appropriate brake resistance according to the field conditions and Brake Resistance Specifications;
2. Multifunctional input terminals (X1 ~ X3) can be used as input for NPN transistor signals;
3. The digital and analog grounding terminals are combined into the COM terminal in the control circuit;
6
AC01-Series network inverter manual Installation
7
Installation AC01-Series network inverter manual
It’s the top view above and the specific network interpretations are as follows:
2 NC Reserved
4 5V 5V power
5 5V 5V power
8
AC01-Series network inverter manual Installation
The braking resistance and resistance power in the following table are verified by ordinary inertia load and intermittent braking mode. If it
needs to be used in the occasion of large inertia and frequent braking for a long time, please adjust the braking resistance and resistance power
appropriately according to the specifications of the selected inverter and the rated parameters of the braking unit. If you have any questions, please
consult the service hotline of technical service department of Suzhou Veichi Electric Technology Co., LTD.
Three-phase 380V
Recommended resistance
Motor (on 100% braking torque and 10% Minimum
Model Brake unit braking rate)
power (kW) resistance(Ω)
Resistance model Resistors qty.
AC01-T3-R75G-B 0.75 kW Built-in, standard 750 Ω 150W 1 100Ω
AC01-T3-1R5G-B 1.5 kW Built-in, standard 400 Ω 300W 1 100Ω
AC01-T3-2R2G-B 2.2 kW Built-in, standard 250 Ω 400W 1 100Ω
AC01-T3-004G-B 4.0 kW Built-in, standard 150 Ω 500W 1 40Ω
AC01-T3-5R5G-B 5.5 kW Built-in, standard 100 Ω 600W 1 40Ω
AC01-T3-7R5G-B 7.5 kW Built-in, standard 75 Ω 780W 1 40Ω
Single-phase 220V
Recommended resistance
Motor (on 100% braking torque and 10% Minimum
Model Brake unit braking rate)
power (kW) resistance(Ω)
Resistance model Resistors qty.
AC01-S2-R40G-B 0.4 kW Built-in, standard 400Ω 100W 1 50Ω
AC01-S2-R75G-B 0.75 kW Built-in, standard 200Ω 120W 1 50Ω
AC01-S2-1R5G-B 1.5 kW Built-in, standard 100Ω 300W 1 50Ω
AC01-S2-2R2G-B 2.2 kW Built-in, standard 75.0Ω 300W 1 20Ω
AC01-S2-004G-B 4kW Built-in, standard 50.0Ω 500W 1 20Ω
9
AC01-Series network inverter manual Indicators, Keyboard Layout and Operation Instructions
States ofAC01 Series inverters can be told via the three indicating lights on its interface:
Note: Refer to PAGE 54 of this manual for main FAULT/WARNING codes 1~163.
Keyboard layout
Note: The current version of AC01 series inverter does not have its own keyboard, and KBD300-25 or KBD10-15 keyboard can be
10
Indicators, Keyboard Layout and Operation Instructions AC01-Series network inverter manual
Digital potentiometer: press the up key to increase the operating value for clockwise
rotation and press down key to reduce the operating value for counterclockwise rotation.
G Confirm key: Press this key to confirm after modifying the value
Move left/ right
Move left or right
Multifunction key
H Select the function of the key via F11.02[multi-function key selection via keyboard]
Take F0.122 [acceleration time] setting as an example to illustrate the basic operations of the external LED keyboard.
Note: The keyboard shift key on the external keyboard can be used to quickly select the tens, hundreds and thousands of parameter values.
Note: When using the external keyboard, use the left shift key to cycle switch the first row of monitoring parameters, and use the right shift key to
12
AC01-Series network inverter manual Function List
staff of Veichi.
Table 4- 3 Note
13
Function List AC01-Series network inverter manual
Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
Set parameter access level according to parameter access
limits
F00.00 Parameter access 0
0: standard parameters (Fxx.yy,Cxx.yy) RUN
(0x0000) level (0 ~3)
1: common parameters (F00.00,Pxx.yy)
2: monitered parameters (F00.00,Cxx.yy)
3: changed pa (F00.00,Hxx.yy)
V/F SVC
Set the inverter initialization mode.
0: No initialization
F00.03 0
Initialization 11: Choose the set value according to purposes (excluding STOP
(0x0003) (0~33)
motor parameters)
22:All parameters initialized
33: Clear the failure records
V/F SVC
0: No function
F00.04 Keyboard 11: Upload parameters to keyboard 0
STOP
(0x0004) parameters copy 22: Download parameters to the inverter (0~30)
Note: The built-in keyboard does not support parameter
copying.
V/F SVC
F00.07 0
Free parameter 1 machine number when using multiple machines; RUN
(0x0007) (0~65535)
mode number for purposes when using multiple machines
14
AC01-Series network inverter manual Function List
V/F SVC
F00.08 0
Free parameter 2 machine number when using multiple machines; RUN
(0x0008) (0~65535)
mode number for purposes when using multiple machines
V/F SVC
Reference
Change this parameter to select reference source for frequency
F01.06 frequency 0
setting channel B RUN
(0x0106) source for (0~1)
0: refer to the maximum output frequency
channel B
1: refer to the frequency of channelA
V/F SVC
Used for setting combination method of frequency channelA and
B for the inverter.
Selection of
0: channelA
F01.07 frequency 0
1: channel B RUN
(0x0107) source (0~5)
2: channelA + channel B
channel
3: channelA- channel B
4: the higher frequency between channelA and channel B
: the lower frequency between channelA and channel B
V/F SVC
3: via current analog AS
When this parameter is valid, it is
4: via voltage analog VS
used to set the source channel for
5: reserved
each command running channel of
6: reserved
bundled frequencies
7: via RS485
Ones-place: bundled command from
Command of communication port
keyboard 0x0000
F01.08 running 8: via UP/DW terminal
Tens-place: bundled command from (0x0000~0x RUN
(0x0108) bundled 9: via PID control
terminals DDDD)
frequencies A: via program control
Hundreds-place: bundled command
(PLC)
from communication port
B: reserved
Thousands-place: reserved
C: via multi-speed
0:no bundling
setting
1: via keyboard number entering
D: reserved
2: via keyboard analog potentiometer
Frequency 50.00Hz
V/F SVC
F01.09 setting via (0.00Hz~
Used to set and modify the frequency set via input keyboard RUN
(0x0109) keyboard upper limit
numbers
numbers frequency)
16
AC01-Series network inverter manual Function List
V/F SVC
F01.14 Resolution of 0
Set the resolution of the frequency command. STOP
(0x010E) frequency command (0~4)
0:0.01Hz; 1:0. 1Hz; 2:0.1 rpm; 3:1 rpm; 4:10 rpm
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Acceleration &
Set benchmark frequency to calculate acceleration &
F01.20 deceleration time 0
deceleration time STOP
(0x0114) benchmark (0~2)
0: Maximum frequency; 1: fixed frequency of 50Hz;
frequency
2: set frequency
V/F SVC
F01.21 Acceleration time 2
The unit of the set acceleration time STOP
(0x0115) unit (0~2)
0:1s; 1:0.1s; 2:0.00s
V/F SVC
Time required to accelerate the output frequency from Model
F01.22
Acceleration time 1 0.00Hz to the benchmark frequency setting(0.01s~650. RUN
(0x0116)
1s~65000s (F01.21 = 0); 0.1s~6500.0s (F01.21 = 1); 00s)
0.01s~650.00s (F01.21 = 2)
V/F SVC Model
F01.23
Deceleration time 1 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x0117)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.24
Acceleration time 2 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x0118)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.25
Deceleration time 2 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x0119)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.26
Acceleration time 3 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x011A)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.27
Deceleration time 3 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x011B)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.28
Acceleration time 4 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x011C)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.29
Deceleration time 4 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x011D)
from benchmark frequency to 0.00Hz 00s)
V/F SVC
S-curve acceleration
F01.30 Whether the S-curve acceleration & deceleration 1
& deceleration STOP
(0x011E) selection is valid (0~2)
selection
0:invalid; 1:valid; 2:flexible S-curve
F01.31 S-curve acceleration V/F SVC 0.20s
STOP
(0x011F) start time Set start time of acceleration for S-curve (0.00s~10.00s)
F01.32 S-curve acceleration V/F SVC 0.20s
STOP
(0x0120) end time Set end time of acceleration for S-curve (0.00s~10.00s)
F01.33 S-curve deceleration V/F SVC 0.20s
STOP
(0x0121) start time Set start time of deceleration for S-curve (0.00s~10.00s)
F01.34 S-curve deceleration V/F SVC 0.20s
STOP
(0x0122) end time Set end time of deceleration for S-curve (0.00s~10.00s)
17
Function List AC01-Series network inverter manual
0.00Hz
Switch frequency
F01.35 V/F SVC (0.00Hz~
between acceleration RUN
(0x0123) Set frequency switch between acceleration time 1 & 2 Upper limit
time 1 & 2
frequency)
LED hundreds-place:
random PWM enable
V/F SVC 0: forbidden
LED ones-place: 1: valid under V/F
relationship between carrier mode
and temperature 2: valid under vector
0: irrelevant mode
F01.41 1111
PWM control mode 1: relevant RUN
(0x0129) (0000~1211)
LED tens-place: LED thousands-palce:
relationship between carrier PWM modulation
and output frequency mode
0: irrelevant 0: three-phase only
1: relevant 1: automatic switching
between two-phase
&three-phase
18
AC01-Series network inverter manual Function List
V/F SVC
[F02.07] will automatically be set to "0"
Parameters after the parameter self-tuning is finished.
F02.07 0
self-learning 0: no operation STOP
(0x0207) (0~3)
selection 1: rotational self-learning
2: static self-learning
3: stator resistance self-learning
Note: When F02.00 [motor type] is a synchronous motor, F2.04 [motor rated speed] is calculated from F2.01 [motor pole number] and
F2.03 [motor rated frequency], please set the corresponding parameters correctly. The calculation formula is: F2.04 [rated speed of
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F02.10 V/F SVC Model setting
No-load current STOP
(0x020A) Set no-load current of asynchronous motor (0.1A~3000.0A)
Model setting
F02.11 V/F SVC
Stator resistance (0.01 mΩ~ STOP
(0x020B) Set stator resistance of asynchronous motor
60000.00 mΩ)
Model setting
F02.12 V/F SVC
Rotor resistance (0.01 mΩ~ STOP
(0x020C) Set rotor resistance of asynchronous motor
60000.00 mΩ)
Model setting
F02.13 Stator leakage V/F SVC
(0.01 mH ~ STOP
(0x020D) inductance Set stator leakage inductance of asynchronous motor
65535.00 mH)
Model setting
F02.14 V/F SVC
Stator inductance (0.01 mH ~ STOP
(0x020E) Set stator inductance of asynchronous motor
65535.00 mH)
F02.15 Stator resistance V/F SVC Model setting
READ
(0x020F) per-unit value Set stator resistance per-unit value (0.01% ~ 50.00%)
Stator leakage
F02.17 V/F SVC Model setting
inductance per-unit READ
(0x0211) Set stator leakage inductance per-unit value (0.01% ~ 50.00%)
value
F02.18 Stator inductance V/F SVC Model setting
READ
(0x0212) per-unit value Set stator inductance per-unit value (0.1% ~ 999.0%)
F02.11~F02.14 V/F SVC
F02.19 0x0000
decimal point Set the decimal point of the four parameters from READ
(0x0213) F02.11 to F02.14. This parameter is read-only. (0x0000 ~ 0x2222)
selection
19
Function List AC01-Series network inverter manual
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F02.50 Stator resistor 0
0: invalid; 1: only learn without update; value greater STOP
(0x0232) learning selection (0 ~ 3)
than 1: learn and update;
Stator resistance
F02.51 V/F SVC 0
learning starting RUN
(0x0233) Set stator resistance learning starting factor 1. (0 ~ 1000)
factor 1
Stator resistance
F02.52 V/F SVC 0
learning starting RUN
(0x0234) Set stator resistance learning starting factor 2. (-20.00% ~ 20.00%)
factor 2
Stator resistance
F02.53 V/F SVC 0
learning starting RUN
(0x0235) Set stator resistance learning starting factor 3. (0 ~ 65535)
factor 3
20
AC01-Series network inverter manual Function List
V/F SVC
Magnetic pole Ones-place: reserved
F02.60 search of Tens-place: open loop vector 0010
STOP
(0x023C) synchronous 0: off ; 1: on; 2: on but only the first power-on start (0000 ~ 3223)
motor The hundreds-place: V/F
0: off; 1: on; 2: on, but only the first power-on start
Current for
F02.61 V/F SVC 0.0%
magnetic pole STOP
(0x023D) Set the current value of magnetic pole search (0.0% ~ 6553.5%)
search
21
Function List AC01-Series network inverter manual
(0x030C) gain Set q-axis proportional gain of current loop (0.001 ~ 4.000)
F03.13 SVC 1.000
Q-axis integral gain RUN
(0x030D) Set q-axis integral gain of current loop (0.001 ~ 4.000)
F03.15 Torque limit of SVC 250.0%
RUN
(0x030F) motoring Set torque limit of motoring (0.0% ~ 400.0%)
F03.16 Torque limit of SVC 250.0%
RUN
(0x0310) power generation Set torque limit of power generation (0.0% ~ 400.0%)
F03.17 Regenerative torque SVC 0.0%
RUN
(0x0311) limit at low speed Set regenerative torque limit at low speed (0.0% ~ 400.0%)
Amplitude-frequenc SVC
F03.18 6.00Hz
y of torque limit at Set amplitude & frequency of torque limit at low RUN
(0x0312) (0.00Hz ~ 30.00Hz)
low speed speed
SVC
Ones-place: torque limit channel of motoring
decided
0: via keyboard number entering;
1: via keyboard potentiometer;
2: via AS setting; 3: via VS setting
4: reserved; 5: reserved;
6: via RS485 communication port (0x3014)
7: reserved;
Tens-place: torque limit channel of power generation
F03.19 Torque limit 0x0000
decided RUN
(0x0313) selection (0x0000~0x0177)
0: via keyboard number entering;
1: via keyboard potentiometer;
2: via AS setting; 3: via VS setting
4: reserved; 5: reserved;
6: via RS485 communication port (0x3014);
7: reserved;
Hundreds-place
0:C00.06 displays torque limit of motoring
1:C00.06 displays torque limit of power generation
Thousands-place: reserved
22
AC01-Series network inverter manual Function List
SVC
F03.37 Energy-saving 0
0: off; RUN
(0x0325) running (0~1)
1: on
Lower limit
F03.38 excitation of SVC 50.0%
RUN
(0x0326) energy-saving Set lower limit excitation of energy-saving running (0.0%~80.0%)
running
Filter coefficient of
F03.39 SVC 0.010s
energy-saving RUN
(0x0327) Set filter coefficient of energy-saving running (0.000s~6.000s)
running
23
Function List AC01-Series network inverter manual
(0x032A) keyboard number Set torque via keyboard number entering. (0.0%~100.0%)
entering
F03.43 Lower limit SVC 0.00%
RUN
(0x032B) torque input Set the lower limit value of torque input. (0.00%~100.00%)
F03.44 Corresponding SVC 0.00%
RUN
(0x032C) Lower limit value Set corresponding Lower limit value. (-250.00%~300.00%)
F03.45 Upper limit SVC 100.00%
RUN
(0x032D) torque input Set upper limit torque input. (0.00%~100.00%)
24
AC01-Series network inverter manual Function List
Oscillation
F04.07 V/F 1.0s
suppression filter RUN
(0x0407) Set oscillation suppression filter time (0.0s~100.0s)
time
F04.08 Output voltage V/F 100.0%
STOP
(0x0408) percentage Set output voltage percentage (25.0%~120.0%)
25
Function List AC01-Series network inverter manual
25.00Hz
F04.15 V/F
Self-set frequency F3 (0.00Hz~ STOP
(0x040F) Set the value of self-set frequency F3
maximum frequency)
F04.16 V/F 78.0%
Self-set voltage V4 STOP
(0x0410) Set the value of self-set voltage V4 (0.0%~100.0%)
37.50Hz
F04.17 V/F
Self-set frequency F4 (0.00Hz~ STOP
(0x0411) Set the value of self-set frequency F4
maximum frequency)
F04.18 V/F 100.0%
Self-set voltage V5 STOP
(0x0412) Set the value of self-set voltage V5 (0.0%~100.0%)
50.00Hz
F04.19 V/F
Self-set frequency F5 (0.00Hz~ STOP
(0x0413) Set the value of self-set frequency F5
maximum frequency)
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F05.00 Terminal X1 V/F SVC 1
STOP
(0x0500) function selection See the functions of terminal X for details (0~95)
F05.01 Terminal X2 V/F SVC 2
STOP
(0x0501) function selection See the functions of terminal X for details (0~95)
F05.02 Terminal X3 V/F SVC 4
STOP
(0x0502) function selection See the functions of terminal X for details (0~95)
26
AC01-Series network inverter manual Function List
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F05.10 X1 detected effective 0.010s
The delay time of transition of terminal X1 from RUN
(0x050A) delay (0.000s~6.000s)
the invalid state to the valid state
27
Function List AC01-Series network inverter manual
LED ones-place: AS
V/F SVC
LED tens-place: VS
0: straight line
F05.43 Analog input curve LED hundreds- place: 0000
(default) RUN
(0x052B) selection reserved (0000~2222)
1: curve-1
LED thousands-place:
2: curve 2
reserved
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F05.50 Define the signal received by the AS terminal, 0.0%
Lower limitAS RUN
(0x0532) and the voltage signal below this value is (0.0%~100.0%)
processed as the lower limit.
Setting R
F05.51 V/F SVC++ 0.00%
corresponding to
(0x0533) Set percentage for the setAS lower limit value. (-100.00%~100.00%)
lower limitAS
V/F SVC
F05.52 Define the signal received by the AS terminal, 100.0% UN
Upper limit AS RUN
(0x0534) and the voltage signal above this value is (0.0%~100.0%)
processed as the upper limit.
Setting
F05.53 V/F SVC 100.00%
corresponding to RUN
(0x0535) Set percentage for the setAS upper limit value. (0.00%~100.00%)
upper limitAS
F05.54 V/F SVC 0.100s
AS filter time Define the size of the AS circuit analog signal RUN
(0x0536) (0.000s~6.000s)
filtering to eliminate interference signals.
V/F SVC
F05.55 Define the signal received by the VS terminal, 0.0%
Lower limit VS RUN
(0x0537) and the voltage signal below this value is (0.0%~100.0%)
processed as the lower limit.
Setting
F05.56 V/F SVC 0.00%
corresponding to RUN
(0x0538) Set percentage for the set VS lower limit value. (-100.00%~100.00%)
lower limit VS
V/F SVC
F05.57 Define the signal received by the VS terminal, 100.0%
Upper limit VS RUN
(0x0539) and the voltage signal above this value is (0.0%~100.0%)
processed as the upper limit.
Setting
F05.58 V/F SVC 100.00%
corresponding to RUN
(0x053A) Set percentage for the setAS upper limit value. (0.00%~100.00%)
upper limit VS
V/F SVC
F05.59 0.100s
VS filter time Define the size of the VS circuit analog signal RUN
(0x053B) (0.000s~6.000s)
filtering to eliminate interference signals.
28
AC01-Series network inverter manual Function List
Parameter Adjustab
Factory default
code Designation Content le
(setting range)
(Address) attribute
F05.60 V/F SVC 0.0%
Curve-1 lower limit RUN
(0x053C) Set lower limit value for curve-1. (0.0%~100.0%)
Setting
F05.61 V/F SVC 0.00%
corresponding to RUN
(0x053D) Set percentage of lower limit value for curve-1. (-100.00%~100.00%)
curve-1 lower limit
Input voltage on
F05.62 V/F SVC 30.0%
inflection point-1 of RUN
(0x053E) Set input voltage on inflection point-1 of curve-1. (0.0%~100.0%)
curve-1
Setting V/F SVC
F05.63 30.00%
corresponding to Set percentage of input voltage on inflection point-1 of RUN
(0x053F) (-100.00%~100.00%)
F05.62 curve-1.
Input voltage on
F05.64 V/F SVC 60.0%
inflection point 2 of RUN
(0x0540) Set input voltage on inflection point 2 of curve-1. (0.0%~100.0%)
curve-1
Setting V/F SVC
F05.65 60.00%
corresponding to Set percentage of input voltage on inflection point 2 of RUN
(0x0541) (-100.00%~100.00%)
F05.64 curve-1.
F05.66 V/F SVC 100.0%
Curve-1 upper limit RUN
(0x0542) Set upper value for curve-1. (0.0%~100.0%)
Setting
F05.67 V/F SVC 100.00%
corresponding to RUN
(0x0543) Set percentage of upper limit value for curve-1. (-100.00%~100.00%)
curve-1 upper limit
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F05.70 V/F SVC 0.0%
Curve-2 lower limit RUN
(0x0546) Set lower limit value for curve-2. (0.0%~100.0%)
Setting
F05.71 V/F SVC 0.00%
corresponding to RUN
(0x0547) Set percentage of lower limit value for curve-2. (-100.00%~100.00%)
curve-2 lower limit
Input voltage on V/F SVC
F05.72 30.0%
inflection point-1 of Set input voltage on inflection point-1 of RUN
(0x0548) (0.0%~100.0%)
curve-2 curve-2.
Setting V/F SVC
F05.73 30.00%
corresponding to Set percentage of input voltage on inflection RUN
(0x0549) (-100.00%~100.00%)
F05.72 point-1 of curve-2.
Input voltage on V/F SVC
F05.74 60.0%
inflection point-2 of Set input voltage on inflection point-2 of RUN
(0x054A) (0.0%~100.0%)
curve-2 curve-2.
Setting V/F SVC
F05.75 60.00%
corresponding to Set percentage of input voltage on inflection RUN
(0x054B) (-100.00%~100.00%)
F05.74 point-2 of curve-2.
F05.76 V/F SVC 100.0%
Curve-2 upper limit RUN
(0x054C) Set upper value for curve-2. (0.0%~100.0%)
Setting
F05.77 V/F SVC 100.00%
corresponding to RUN
(0x054D) Set percentage of upper limit value for curve-2. (-100.00%~100.00%)
curve-2 upper limit
V/F SVC
F05.82 70.00%
AS high-level setting It’s high level when AS input setting is greater than the RUN
(0x0552) (0.00%~100.00%)
high-level setting.
V/F SVC
F05.83 30.00%
AS low-level setting It’s low level when AS input setting is smaller than the RUN
(0x0553) (0.00%~100.00%)
low-level setting.
F05.84 VS terminal function V/F SVC 0
RUN
(0x0554) selection (used as X) See X terminal functions for details. (0~95)
V/F SVC
F05.85 70.00%
VS high-level setting It’s high level when VS input setting is greater than the RUN
(0x0555) (0.00%~100.00%)
high-level setting.
V/F SVC
F05.86 30.00%
VS low-level setting It’s low level when VS input setting is smaller than the RUN
(0x0556) (0.00%~100.00%)
low-level setting.
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
Tens-place: relay output
V/F SVC
terminal
0: positive
F06.20 Output terminal Hundreds-place: 0000
1: negative RUN
(0x0614) polarity selection reserved (0000~1111)
LED ones-place: Y
Thousands-place:
terminal
reserved
F06.21 V/F SVC 1
Output terminal Y RUN
(0x0615) SeeY terminal functions for details. (0~63)
F06.22 Relay output V/F SVC 4
RUN
(0x0616) (TA-TB-TC) SeeY terminal functions for details. (0~63)
F06.25 Y output delayed V/F SVC 0.010s
RUN
(0x0619) start time Set delay time when Y terminal starts output. (0.000s~60.000s)
F06.26 Relay output delayed V/F SVC 0.010s
RUN
(0x061A) start time Set delay time when relay starts output. (0.000s~60.000s)
F06.29 Y output delayed V/F SVC 0.010s
RUN
(0x061D) stop time Set delay time when Y terminal stops output. (0.000s~60.000s)
30
AC01-Series network inverter manual Function List
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
LED ones-& tens-place: set “yy” between 00~63
F06.50 Comparator 1 0001
among monitoring parameter “Cxx.yy”; RUN
(0x0632) monitoring selection (0000~0763)
LED hundreds-&thousands-place: set “xx” between
00~07 among monitoring parameter “Cxx.yy”;
F06.51 Upper limit of V/F SVC
(up to F06.50) RUN
(0x0633) comparator 1 Set upper limit value of comparator 1.
F06.52 Lower limit of V/F SVC
(up to F06.50) RUN
(0x0634) comparator 1 Set lower limit value of comparator 1.
F06.53 V/F SVC
Comparator 1 bias (up to F06.50) RUN
(0x0635) Set comparator 1 bias.
V/F SVC
Action selection of 0: go on running (digital terminal output only)
F06.54 0
sending comparator 1: display warning and stop freely RUN
(0x0636) (0~3)
1 2: display warning and go on running
3: forced stop
V/F SVC
LED ones-& tens-place: set “yy” between 00~63
F06.55 Comparator 2 0002
among monitoring parameter “Cxx.yy”; RUN
(0x0637) monitoring selection (0000~0763)
LED hundreds-&thousands-place: set “xx” between
00~07 among monitoring parameter “Cxx.yy”;
F06.56 Upper limit of V/F SVC
(up to F06.55) RUN
(0x0638) comparator 2 Set upper limit value of comparator 2.
F06.57 Lower limit of V/F SVC
(up to F06.55) RUN
(0x0639) comparator 2 Set lower limit value of comparator 2.
F06.58 V/F SVC
Comparator 2 bias (up to F06.55) RUN
(0x063A) Set comparator 2 bias.
V/F SVC
Action selection of 0: go on running (digital terminal output only)
F06.59 0
sending comparator 1: display warning and stop freely RUN
(0x063B) (0~3)
2 2: display warning and go on running
3: forced stop
31
Function List AC01-Series network inverter manual
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F06.60
(0x063C) Function selection of
V/F SVC 0
~ virtual vX1~vX3 STOP
See X terminal functions for details. (0~95)
F06.63 terminals
(0x063F)
V/F SVC
0: interconnect with the Ones-place: vX1
virtual vYn terminal; Tens-place: vX2
F06.64 State source of vX 0000
1: connect to the physical Hundreds-place: vX3 RUN
(0x0640) terminal (0000~0222)
terminal Xn Thousands-place:
2: function code valid or reserved
not
V/F SVC Tens-place: vX2
Virtual vX terminal
F06.65 0: invalid; Hundreds-place: vX3 0000
function code status RUN
(0x0641) 1: valid; Thousands-place: (0000~0111)
setting
Ones-place: vX1 reserved
F06.66
(0x0642)
Output selection of
~ V/F SVC 0
virtual vY1~vY3 RUN
F06.69 SeeY terminal functions for details. (0~63)
terminals
(0x0645)
F06.69
(0x0645)
F06.70
(0x0646)
vY1~ vY3 output V/F SVC 0.010s
~ RUN
delayed start time Set delay time when vY1~ vY3 starts output. (0.000s~60.000s)
F06.73
(0x0649)
F06.74
(0x064A)
vY1~ vY3 output V/F SVC 0.010s
~ RUN
delayed stop time Set delay time when vY1~ vY3 stops output. (0.000s~60.000s)
F06.77
(0x064D)
Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
F07.00 0: started by the starting frequency 0
Start method STOP
(0x0700) 1: DC braking before started by the starting frequency (0~2)
2: speed tracking & direction judgment and then start
V/F SVC
F07.01 Start pre-excitation Only asynchronous motor vector control without PG 0.00s
STOP
(0x0701) time supports pre-excitation, so ignore this code on other (0.00s~60.00s)
motors.
32
AC01-Series network inverter manual Function List
0.50Hz
V/F SVC (0.00Hz~upper
F07.02
Start frequency Remain stop and standby when set frequency is lower limit frequency STOP
(0x0702)
than start frequency. via number
entering)
V/F SVC
0: off
1: on
LED ones-place: terminal protection activated on exit
exception
Tens-place: jogging terminal protection activated exit
F07.03 Start protection 0111
exception STOP
(0x0703) selection (0000~1111)
Hundreds-place: terminal protection activated when the
command channel switches to the terminal
Thousands-place: reserved
Note: When the free stop, emergency stop and forced
stop commands are valid, the terminal protection is
enabled by default.
1:forward command only
V/F SVC
2: reverse command only
LED ones-place:
Hundreds-place: frequency
rotation direction
controlling command
0: remain;
direction:
1: reverse the direction;
0: controlling command
F07.05 Rotation direction Tens-place: rotation 0000
direction invalid STOP
(0x0705) selection direction permission: (0000~1121)
1: controlling command
0: forward and reverse
direction valid
commands allowed
Thousands-place: reserved
Note: Initialization will not restore this value.
Parameter downloading will not change the ones digit
value.
V/F SVC
F07.06 Restart after power 0: invalid 0
STOP
(0x0706) failure selection 1: speed tracking and restart (0~2)
2: restart as the start mode.
F07.07 Restart waiting time V/F SVC 0.50s
STOP
(0x0707) after power cut. Set the waiting time to restart after power cut. (0.00s~60.00s)
33
Function List AC01-Series network inverter manual
(0x0710) current at zero speed Set torque holding current at zero speed, 100.0% of (0.0%~150.0%)
rated current of the inverter.
F07.17 Torque holding time V/F SVC 0.0s
RUN
(0x0711) at zero speed Set Torque holding time at zero speed. (0.0s~6000.0s)
V/F SVC
F07.18 Forward & reverse 0.0s
Zero frequency holding time during forward & reverse STOP
(0x0712) rotation dead time (0.0s~120.0s)
switching.
34
AC01-Series network inverter manual Function List
V/F SVC
F07.34 0
Jogging stop mode 0: stop as F7.10 setting; RUN
(0x0722) (0~1)
1: decelerate and stop
F07.4x group: start & stop holding frequency and hopping frequency
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC 0.50Hz
F07.40 Start holding Start holding frequency is higher than the start (0.00Hz~upper limit
STOP
(0x0728) frequency frequency and lower than the upper limit frequency frequency via number
via number entering. entering)
V/F SVC
F07.41 Start holding This shall be higher than the starting frequency, and 0.00s
STOP
(0x0729) frequency time the starting frequency should be taken when it is (0.00s~60.00s)
lower than it.
0.50Hz
F07.42 Stop holding V/F SVC (0.00Hz~ upper limit
STOP
(0x072A) frequency Set stop holding frequency. frequency via number
entering))
V/F SVC
Stop holding frequency time is invalid when
terminal DC braking and jogging;
stop DC braking is effective while the stop
F07.43 Stop holding 0.00s
holding frequency is lower than stop DC STOP
(0x072B) frequency time (0.00s~60.00s)
braking frequency;
no stop DC braking and the stop holding
frequency is lower than the stop detection
frequency
0.00Hz
F07.44 V/F SVC
Hopping frequency 1 (0.00 Hz ~ RUN
(0x072C) Set hopping frequency 1.
maximum frequency)
0.00Hz
F07.45 Hopping frequency V/F SVC
(0.00Hz~ RUN
(0x072D) amplitude Set hopping frequency1 amplitude.
maximum frequency)
0.00Hz
F07.46 V/F SVC
Hopping frequency 2 (0.00Hz~ RUN
(0x072E) Set hopping frequency 2.
maximum frequency)
0.00Hz
F07.47 Hopping frequency V/F SVC
(0.00Hz~ RUN
(0x072F) amplitude Set hopping frequency 2 amplitude.
maximum frequency
率)
Table 4-39 F07.4x group
35
Function List AC01-Series network inverter manual
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
36
AC01-Series network inverter manual Function List
V/F SVC
Ones-place: cooling fan
0: invalid; 1: valid
F09.02 Device maintenance 0x0000
Tens-place: main relay RUN
(0x0902) warning selection (0x0000~0x1111)
0: invalid; 1: valid
Hundreds-place: reserved
Thousands-place: reserved
F09.03 Cooling fan V/F SVC 0
Set this parameter in hours and set it to 0 after replacing STOP
(0x0903) maintenance (0~65535)
with a new one.
F09.04 Main relay V/F SVC 0.0%
STOP
(0x0904) maintenance Set this parameter to 0.0% after replacing with a new relay. (0.0%~150.0%)
V/F SVC
F10.01 Overcurrent 160.0%
Set the load current limiting level, 100% of rated RUN
(0x0A01) suppression point (0.0%~300.0%)
motor current.
37
Function List AC01-Series network inverter manual
V/F SVC
F10.06 Current imbalance 2.0
Increase this parameter on occasions with great current STOP
(0x0A06) filtering coefficient (0.0~60.0)
fluctuation.
T3:430
V/F SVC
S2:240
Set the bus voltage value to trigger the undervoltage
F10.17 Bus undervoltage (T3:350V~450V
suppression function. STOP
(0x0A11) suppression point S2:180V~260V)
Note: T3 overpressure point :820V(750V~840V)
Also limited by
S2 overpressure point :400V(360V~410V)
overvoltage point
38
AC01-Series network inverter manual Function List
T3:320V
V/F SVC
S2:190V
Set the allowable lower limit of busbar voltage, below
F10.19 Busbar undervoltage (T3:300V~400V
which inverter will report undervoltage fault. STOP
(0x0A13) protection point S2:160V~240V)
Note :T3 overpressure point :820V(750V~840V)
Also limited by
S2 overpressure point :400V(360V~410V)
overvoltage point
39
Function List AC01-Series network inverter manual
V/F SVC
F10.36 Load warning Set the duration of load detection warning 2. If the 5.0s
STOP
(0x0A24) detection time 2 load is greater than the load warning detection level, (0.0s~60.0s)
load detection warning 2 functions.
40
AC01-Series network inverter manual Function List
V/F SVC
Excessive speed Set the duration of detecting speed deviation. If the
F10.42 2.0s
deviation detection given speed & feedback speed deviation is greater STOP
(0x0A2A) (0.0s~60.0s)
time than F10.41 and lasts for this setting, report
excessive speed deviation warning.
V/F SVC
Set detection mode and warning mode of motor
stall.
Ones-place: detection mode selection
F10.43 0: detection off; 02
Stall protection STOP
(0x0A2B) 1: on at constant speed only; (00~12)
2: on;
Tens-place: warning mode
0: stop freely and report warning;
1: report warning and go on running
Stall protection V/F SVC
F10.44 110.0%
detection threshold Set the detectable value of stall warning, which STOP
(0x0A2C) (0.0%~150.0%)
value corresponds 100% of F01.10[maximum frequency]
V/F SVC
F10.45 Stall protection Set the duration of stall detection. If feedback speed 0.100s
STOP
(0x0A2D) detection time deviation is greater than F10.44 and lasts for this (0.000s~2.000s)
setting, report stall warning.
41
Function List AC01-Series network inverter manual
V/F SVC
F10.56 0: insulation levelA; 1: insulation level E 3
Motor insulation level STOP
(0x0A38) 2: Insulation level B; 3: insulation level F (0~5)
4: Insulation class H; 5: special level S
V/F SVC
F10.57 Motor working 0-1: S1 working system (continuous working) 0
STOP
(0x0A39) system 2: S2 working system (0~9)
3-9: corresponds to S3-S9
V/F SVC
F10.59 Motor overload 100.0%
Motor overload calculated current = actual current * STOP
(0x0A3B) current coefficient (0.0%~250.0%)
motor overload current coefficient.
V/F SVC
F11.01 Function together with the key lock; Remember the 0
Key lock password RUN
(0x0B01) password after setting, otherwise, the operation (0~65535)
cannot be performed if it is locked.
V/F SVC
0: invalid;
1: reverse running;
2: forward jogging;
3: backward jogging;
4: switch between the keyboard command channel
F11.02 Multi-function key 0
and the terminal command channel; STOP
(0x0B02) selection (0~7)
5: switch between the keyboard command channel
and the communication command channel;
6: switch between the terminal command channel
and the communication command channel;
7: switch between the keyboard, terminal, and
communication command channel;
V/F SVC
F11.03 Keyboard STOP key 0: non-keyboard control invalid; 0
setting STOP
(0x0B03) 1: non-keyboard control stops as stop mode; (0~2)
2: non-keyboard control stops as free mode;
V/F SVC
Ones-place; keyboard up & down function selection
Up/down button on 0: invalid;
F11.04 the status interface 1: used to change the frequency of F01.09; 0011
STOP
(0x0B04) (knob) function 2: used to adjust PID keyboard of F13.01; (0000~0213)
selection 3: keyboard up & down keys to change the
parameters;
Tens-place: power failure storage
42
AC01-Series network inverter manual Function List
0: off;
1: on;
Hundreds-place: action limit
0: adjustable both during running & shutdown;
1: adjustable during running and keeping during
shutdown;
2: adjustable during running and clearing all after
shutdown;
Thousands-place: reserved
V/F SVC
Ones-place: set yy value from 00 to 99 among code
F11.05 Up & down key quick 0109
“Fxx.yy”; RUN
(0x0B05) change parameter (0000~2999)
Tens-place: set xxvalue from 00 to 15 among code
“Fxx.yy”
43
Function List AC01-Series network inverter manual
V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.17 0010
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B11) (0000~0763)
parameter 3 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.18 0012
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B12) (0000~0763)
parameter 4 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
F11.21 100.0%
Speed factor display Set keyboard monitoring speed parameter RUN
(0x0B15) (0.0%~500.0%)
factor ratio display.
V/F SVC
F11.22 100.0%
Power factor display Set keyboard monitoring power parameter RUN
(0x0B16) (0.0%~500.0%)
factor ratio display.
V/F SVC
Ones-place: reserved
0: invalid;
1: valid;
Tens-place: C05 display selection
Monitoring parameter 0: Automatically switches with control modes
F11.23 0x0000
group display 1: V/F mode related parameters; RUN
(0x0B17) (0x0000~0xFFFF)
selection 2: V/C mode related parameters;
Hundreds-place: C00.40~C00.63 display
selection
0: off;
1: on;
Thousands-place: reserved
V/F SVC
F11.24 Monitoring parameter Ones- place: output current filtering displayed 0x0002
RUN
(0x0B18) filtering selection 0 to F: The larger the value, the deeper the (0x0000~0x000F)
filtering
V/F SVC
0: status of the self-learning process displayed
F11.25 Motor self - learning 1: status of the self-learning process not 0
RUN
(0x0B19) display selection displayed (0~1)
Note: T/S2 models do not support this
parameter.
44
AC01-Series network inverter manual Function List
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F12.00 Master/slave 0
0: slave STOP
(0x0C00) selection (0~1)
1: master
Modbus V/F SVC
F12.01 1
communication Set the communication address of the Modbus slave STOP
(0x0C01) (1~247)
address computer.
45
Function List AC01-Series network inverter manual
V/F SVC
Communication 0: timeout fault undetected;
F12.07 0
disconnection 1: report fault and stop freely; RUN
(0x0C07) (0~3)
processing 2: report warning and go on running;
3: forced stop
Received data V/F SVC
F12.08 0.00
(address 0x3000) Set the bias value of the set frequency of RUN
(0x0C08) (-100.00~100.00)
with zero bias communication (100.00 corresponding to 100.00Hz)
V/F SVC
F12.09 Receive data (address Set the gain of communication at the set frequency 100.0%
RUN
(0x0C09) 0x3000) gain Set frequency = actual communication × gain + bias (0.0%~500.0%)
value
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Ones-, tens-, hundreds-, 6: output torque;
thousands-place 7: reserved
0: invalid; 8: reserved
F12.10 Master loop-sending 9: PID setting 0x0031
1: running command; RUN
(0x0C0A) parameters selection A: PID feedback; (0x0000~0xCCCC)
2: set frequency;
3: output frequency; B: reserved;
C: Active current
4: upper limit frequency;
component;
5: set torque ;
46
AC01-Series network inverter manual Function List
V/F SVC
F12.11 Self-defined Set this parameter to non-0 in place of frequency 0x0000
RUN
(0x0C0B) frequency address address of 0x3000 or 0x2000 set via (0x0000~0xFFFF)
communication port.
V/F SVC
F12.12 Self-defined Set this parameter to non-0 in place of command 0x0000
RUN
(0x0C0C) command address address of 0x3001 or 0x2001 set via (0x0000~0xFFFF)
communication port.
Forward running V/F SVC
F12.13 0x0001
command value Set this parameter in place of 0001H forward RUN
(0x0C0D) setting (0x0000~0xFFFF)
running set via communication port.
Backward running V/F SVC
F12.14 0x0002
command value Set this parameter in place of 0002H backward RUN
(0x0C0E) (0x0000~0xFFFF)
setting running set via communication port.
V/F SVC
F12.15 Stop command value 0x0005
Set this parameter in place of 0005H deceleration RUN
(0x0C0F) (0x0000~0xFFFF)
stop set via communication port.
V/F SVC
F12.16 Reset command 0x0007
Set this parameter in place of 0007H fault recovery RUN
(0x0C10) value (0x0000~0xFFFF)
set via communication port.
V/F SVC
F12.19 Master sending Master sending command selection 0
RUN
(0x0C13) command selection 0: sending the running command (0~1)
1: sends the running status
Table 4-54 F12.1x group
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
PID setting/feedback
F13.01 The parameter is valid when [F13.00]or [F13.03] is 50.0%
via keyboard number RUN
(0x0D01) selected with “PID setting/feedback via keyboard (0.0%~100.0%)
entering
number entering”.
47
Function List AC01-Series network inverter manual
V/F SVC
F13.06 Feedback signal 100.0
PID feedback signal range is a dimensionless unit used RUN
(0x0D06) range (0.0~100.0)
to adjust PID feedback.
F13.07~F13.24:PID modulation
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Ones- place: feedback characteristic selection
0: positive characteristic;
1: negative characteristic
F13.07 0100
PID control selection Tens-place: reserved RUN
(0x0D07) (0000~1111)
Hundreds-place: reserved
Thousands-place: differential regulation characteristics
0: differentiates the deviation
1: differentiate the feedback
F13.08 V/F SVC 100.0%
PID preset output RUN
(0x0D08) Output as PID preset value after PID starts. (0.0%~100.0%)
V/F SVC
F13.09 PID preset output 0.0s
Set PID preset output time and set output starts after RUN
(0x0D09) time (0.0s~6500.0s)
countdown.
V/F SVC
F13.10 0.0%
PID deviation limit Set maximum deviation between PID feedback and RUN
(0x0D0A) (0.0%~100.0%)
PID set
F13.11 V/F SVC 0.100
Proportional gain P1 RUN
(0x0D0B) Set PID parameter group 1 proportional gain. (0.000~4.000)
F13.12 V/F SVC 1.0s
Integral time I1 RUN
(0x0D0C) Set PID parameter group 1 integral time. (0.0s~600.0s)
F13.13 V/F SVC 0.000s
Rate time D1 RUN
(0x0D0D) Set PID parameter group 1 rate time. (0.000s~6.000s)
F13.14 V/F SVC 0.100
Proportional gain P1 RUN
(0x0D0E) Set PID parameter group 2 proportional gain. (0.000~4.000)
F13.15 V/F SVC 1.0s
Integral time I2 RUN
(0x0D0F) Set PID parameter group 2 integral time. (0.0s~600.0s)
F13.16 V/F SVC 0.000s
Rate time D2 RUN
(0x0D10) Set PID parameter group 2 rate time. (0.000s~6.000s)
V/F SVC
F13.17 PID parameter 0: off; 0
switching condition RUN
(0x0D11) 1: switch via DI terminal; (0~2)
2: switch according to deviation;
V/F SVC
F13.18 Set lower deviation 20.0%
Apply the gain 1 parameter when the PID deviation is RUN
(0x0D12) value (0.0%~100.0%)
smaller than this value.
48
AC01-Series network inverter manual Function List
V/F SVC
F13.19 Set higher deviation 80.0%
Apply the gain 1 parameter when the PID deviation is RUN
(0x0D13) value (0.0%~100.0%)
larger than this value.
V/F SVC
F13.21 5.0%
Differential limit Differential limit is used to set the range of PID RUN
(0x0D15) (0.0%~100.0%)
differential output.
F13.22 PID upper limit V/F SVC 100.0%
RUN
(0x0D16) output Set the upper limit of PID output. (0.0%~100.0%)
49
Function List AC01-Series network inverter manual
50
AC01-Series network inverter manual Function List
51
Function List AC01-Series network inverter manual
C02.02 (0x2302) PID output C02.16 (0x2310) inverter overload timing factor
C02.17 (0x2311) ~
C02.03 (0x2303) PID control status reserved
C02.18 (0x2312)
C02.05 (0x2305) PLC running stage C02.19 (0x2313) number of current limiting per wave
C02.20 (0x2314) ~
C02.06 (0x2306) PLC stage frequency reserved
C02.31 (0x231F)
C02.32 (0x2320) ~ power-off storage parameter 1~
C02.07 (0x2307) PLC stage run time
C02.47 (0x232F) power-off storage parameter 16
forward & reverse command C02.48 (0x2330) ~
C02.08 (0x2308) reserved
setting C02.49 (0x2331)
C02.50 (0x2332) ~
C02.09 (0x2309) jogging command setting cache register 0 to cache register 9
C02.59 (0x233B)
C02.60 (0x233C) ~
C02.10 (0x230A) AS current before correction reserved
C02.61 (0x233D)
C02.11 (0x230B) VS voltage before correction C02.62 (0x233E) external keyboard version
52
AC01-Series network inverter manual Function List
53
Function List AC01-Series network inverter manual
10 output frequency level detection 2 (FDT 2) 23 counter set value arrival 39~63 reserved
54
AC01-Series network inverter manual Function List
operation
E. oL1(14) motor overload fault E. FA4(113) external extension reserved 4 fault
E. oL2(15) inverter overload 1 fault E. FA5(114) external extension reserved 5 fault
E. oL3(16) inverter overload 2 fault E. FA6(115) external extension reserved 6 fault
E. oL4(17) inverter overload 3 fault E. FA7(116) external extension reserved 7 fault
E. iLF (18) input phase loss fault E. FA8(117) external extension reserved 8 fault
three-phase output phase
E. oLF (19) fault
loss
U-phase output phase
E. oLF1(20) fault Here are the warnings
loss
V-phase output phase
E. oLF2(21) fault A. Lu1(128) undervoltage shutdown warning
loss
W-phase output phase
E. oLF3(22) fault A. ou (129) overvoltage shutdown warning
loss
Reserved (23-29) reserved fault A. iLF (130) input phase loss warning
E. oH1(30) rectifier overheat fault A. PID (131) PID feedback disconnection warning
E. oH2(31) inverter overheat fault A. EEP (132) parameter storage warning warning
Reserved (32) reserved fault A. dEF (133) excessive speed deviation
E. EF (33) external fault fault A. SPd (134) Stall warning warning
Modbus communication
E. CE (34) fault A. GPS1(135) GPS lock warning
fault
U-phase excessive zero
E. HAL1(35) fault A. GPS2(136) GPS disconnection warning
drift
V-phase excessive zero Modbus disconnection
E. HAL2(36) fault A. CE (137) warning
drift warning
non-zero sum of three
E. HAL (37) fault A. Ld1(138) load protection 1 warning
phase currents
W-phase excessive zero
E. HAL3(38) fault A. Ld2(139) load protection 2 warning
drift
Reserved (39) reserved fault Reserved (140) reserved warning
E. SGxx (40) ground short circuit fault A. oH1(141) Module overheat warning warning
E. FSG (41) fan short circuit fault Reserved (142) reserved warning
PID feedback
E. PID (42) fault A. run1(143) warning 1 in motion warning
disconnection
external keyboard
E. CoP (43) parameter copy failure fault A. PA2(144) warning
disconnection warning
Reserved (44) reserved fault A. CoP (145) parameter copy warning warning
monitor comparison output 1
Reserved (45-49) reserved fault A. CP1(146) warning
warning
monitor comparison output 2
E. bru (50) brake unit failure fault A. CP2(147) warning
warning
Reserved (51) reserved fault A. run2(148) warning 2 in motion warning
self-learning output
E. TExx (52) fault A. run3(149) warning 3 in motion warning
current over limit
reserved
reserved fault A. FA1(150) external extension reserved 1 warning
(53~70)
motor angle learning
E. iAE1(71) fault A. FA2(151) external extension reserved 2 warning
fault 1
motor angle learning
E. iAE2(72) fault A. FA3(152) external extension reserved 3 warning
fault 2
motor angle learning
E. iAE3(73) fault A. FA4(153) external extension reserved 4 warning
fault 3
synchronous motor step
E. PST1(74) fault A. FA5(154) external extension reserved 5 warning
out fault 1
synchronous motor step
E. PST2(75) fault A. FA6(155) external extension reserved 6 warning
out fault 2
synchronous motor step
E. PST3(76) fault A. FrA(157) reserved warning
out fault 3
55
Function List AC01-Series network inverter manual
56
AC01-Series network inverter manual Regular Inspection and Maintenance
58
AC01-Series network inverter manual Appendix I: Modbus Communication Protocol
● Error code meaning from the slave's response to the exception message
Error code Description Error Description Error code Description
code
1 Wrong command code 3 CRC check error 4 Illegal address
Unchangeable
5 Illegal data 6 8 Converter busy (EEPROM in storage)
parameters in motion
60
AC01-Series network inverter manual Appendix II: External Keyboard Size and Model
AC01 series external two-row display keyboard shape and hole size
66 26. 6
5
42 35. 6
60. 6
38. 3
参考开孔尺寸: 61x36mm
61