AC01 Series Network Type Inverter Speed Controller Operating Instructions-20.06.2023

This document is a manual for the AC01-Series network inverter. It contains 17 chapters covering general safety precautions, technical specifications, installation, operation instructions, function groups, parameter settings, regular inspection and maintenance procedures, and appendices on communication protocols and external keyboards. The manual provides guidance on safely using the inverter and configuring its various functions and parameters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
203 views

AC01 Series Network Type Inverter Speed Controller Operating Instructions-20.06.2023

This document is a manual for the AC01-Series network inverter. It contains 17 chapters covering general safety precautions, technical specifications, installation, operation instructions, function groups, parameter settings, regular inspection and maintenance procedures, and appendices on communication protocols and external keyboards. The manual provides guidance on safely using the inverter and configuring its various functions and parameters.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 63

AC01-Series network inverter manual Catalog

Catalog
Chapter 1 General........................................................................................................... 1

1.1 Safety Precautions....................................................................................................1


1.2 Pre-use.................................................................................................................... 1
1.3 Technical Specifications........................................................................................... 2

Chapter 2 Installation...................................................................................................... 5

Chapter 3 Indicators, Keyboard and Operation Instructions....................................... 10

Chapter 4 Function List.................................................................................................13

4.1 Safety Precautions..................................................................................................13


4.2 Reading Method of the Parameter List.................................................................... 13
4.3 Function Group......................................................................................................13
4.4 F00 Group: Environmental Applications................................................................. 14
4.5 F01 Group: Basic Setting........................................................................................15
4.6 F02 Group: Parameter Of Motor 1 .......................................................................... 18
4.7 F03 Group: Vector Control..................................................................................... 21
4.8 F04 Group: V/F Control......................................................................................... 25
4.9 F05 Group: Input Terminal..................................................................................... 26
4.10 F06 Group: Output Terminal.................................................................................30
4.11 F07 Group: Running Control................................................................................ 32
4.12 F08 Group: Auxiliary Control 1 ............................................................................ 35
4.13 F09 Group: Auxiliary Control 2 ............................................................................ 36
4.14 F10 Group: Protection Parameter.......................................................................... 37
4.15 F11 Group: Keyboard Parameter...........................................................................42
4.16 F12 Group: Communication Parameter.................................................................45
4.17 F13 Group: PID Control....................................................................................... 47
4.18 F14 Group: Multi-Speed and Simple PLC.............................................................50
4.19 F15 Group: Reserved........................................................................................... 51
4.20 F25 Group: AS/VS Correction.............................................................................. 51
4.21 C0x Group: Monitoring Parameter........................................................................51
4.22 Input & Output Terminal Functions Selection........................................................53
4.23 Fault Code Table.................................................................................................. 54

Chapter 5 Regular Inspection and Maintenance...........................................................57


I
Catalog AC01-Series network inverter manual

5.1 Inspection.............................................................................................................. 57
5.2 Maintenance.......................................................................................................... 57
5.3 Product Guarantee..................................................................................................58

Appendix I: Modbus Communication Protocol............................................................ 59

Appendix Ii: External Keyboard Size and Model......................................................... 61

II
AC01-Series network inverter manual General

Chapter 1 General
1.1 Safety Precautions
Please fully understand the safety precautions described in this manual before using to ensure safety of both persons and products.
Warning signs and their meanings
The following marks are used in this manual to indicate that this part is of great safety importance. Failure to follow these precautions may
result in personal injury, damage or even death to the product and associated systems.

DANGER: death or major safety accidents may occur due to wrong operations.

Caution: minor injuries may occur due to wrong operations.

Table 1- 1
Operating qualification
This product must be operated by trained professionals. In addition, operators must go through professional skills training, familiar with the
installation, wiring, operation and maintenance of the equipment, and correctly respond to various emergency situations in use.
Safety rules
Safety rules are put forward for your safety and are measures taken to prevent injury to operators and damage to the product and associated
systems; Read this manual carefully before use and strictly follow the safety rules and warning signs in this manual.
● Correct transportation, storage, installation, as well as careful operation and maintenance, is very important for the safe operation of the
frequency inverter. During transportation and storage, the inverter must be protected from shock and shake. It must also be stored in places which
are dry and free from non-corrosive gas, non-conductive dust and where ambient temperature is lower than 60℃.
● This product has dangerous voltage, and it is controlled by a potentially dangerous movement mechanism. Any operations against the
regulations or the requirements of this manual may lead to personal injury or damage of the product and related system.
● Do not wire when power is on otherwise there is a risk of death by electric shock; When connecting cables, checking, or maintaining cables,
power off all related devices and ensure that the DC voltage of the main loop is reduced to a safe level. Wait five minutes before performing related
operations.
● Power cables, motor cables and control cables must be connected tight and all of the ground terminals must be grounded, and the grounding
resistance is less than 10Ω.
● The static electricity of human body will seriously damage the internal sensitive devices. Before performing related operations, please follow
the instructions specified in ESD prevention measures (ESD), otherwise the frequency inverter may be damaged.
● Output voltage of the inverter is a kind of pulse waveform, if the output side is equipped with capacitors or lightning protection varistor
devices to improve the power factor, be sure to remove or refit the input side of the inverter.
● Switch devices such as circuit breakers and contactors shall not be added on the output side of the inverter (if the switch device must be
connected on the output side, the output current of the inverter must be zero when the switch is operated in the control).
● No matter where the fault occurs in the control equipment, it may cause production suspension and major accidents. Therefore, take
necessary external protection measures or backup devices.
● Please use this product only for the purposes prescribed by the manufacturer, usage for special occasions of emergency and rescue like
marine, medical, aviation and nuclear facilities without permission are seriously forbidden.
● Maintenance of this product can only carry out by Veichi or professionals who have been licensed by Veichi, unauthorized modification or
use of accessories without Veichi’s authorization may lead to product failure. Any defective components must be replaced in time for product
maintenance.

1.2 Pre-use
Upon receipt of your ordered products, please check whether the outer package is damaged, open the outer package after confirming that it is
intact, and confirm whether the frequency inverter is damaged, scratched or contaminated (Damage caused during transportation does not fall within
the scope of Veichi’s “three guarantees”). If you receive a product with transportation damage, please contact the company or transportation

1
General AC01-Series network inverter manual

company immediately. After confirming that the received product is intact, please confirm again whether you received what you have ordered.

Figure 1- 1

Voltage 220V 380V


Power(kW) Rated output current(A)
0.4 3.0 ——
0.75 4.0 2.5
1.5 7.0 3.7
2.2 10.0 5.0
4 16.0 9.5
5.5 —— 13.0
7.5 —— 17.0

Table 1- 2

1.3 Technical Specifications


Item Specification
S2: single-phase 200V ~ 240V 50Hz/60Hz;
Voltage & Frequency
T3: Three-phase 380V ~ 480V 50Hz/60Hz.
Power input

T/S2: -10% ~ 10%; T3: -15% ~ 10%; Voltage unbalance rate: <3%; Frequency: ±5%;
Allowable fluctuation
distortion rate conforming to IEC61800-2

Closing striking current Lower than rated current


Output voltage Rated output: 3 phase, 0V ~ input voltage, error lower than 5%
Output frequency range 0Hz ~ 600Hz
Output

Output frequency
±0.5% of the maximum frequency value
accuracy
T3 model: 150% of rated current for 89 s, 180% of rated current for 10 seconds, 200% rated current for 3 s
Overload capacity
S2 model: 150% of rated current for 24 seconds, 180% of rated current for 3.4 seconds
Motor control mode No PG V/F control, no PG vector control
Modulation mode Optimized space vector PWM modulation
Primary control performance

Motor type Three-phase asynchronous motor & permanent magnet synchronous motor supported
Carrier frequency 2.0kHz ~ 12.0kHz
Speed control range No PG vector control, rated load 1:100;
Steady-state speed
No PG vector control: ≤2% of rated synchronous speed;
accuracy
Starting torque No PG vector control: 150% of rated torque at 0.5Hz;
Torque ripple No PG vector control: ≤0.1% of rated torque

2
AC01-Series network inverter manual General

Torque response No PG vector control: < 20ms;


Frequency accuracy Digital setting: maximum frequency ×±0.01%; Simulation setting: maximum frequency ×±0.2%
Frequency resolution Digital setting: 0.01Hz; Simulation setting: maximum frequency ×0.05%
Torque control Torque setting calculation, torque mode speed limit
DC braking capability Starting frequency: 0.00Hz ~ 50.00Hz; Braking time: 0.0s ~ 60.0s; Braking current: 0.0% ~ 150.0% of rated current
Torque boost Automatic torque increased by 0.0% ~ 100.0%; Manual torque increased by 0.0% ~ 30.0%

Four methods: linear torque characteristic curve, self-setting V/F curve, reduced torque characteristic curve (power
V/F curve
1.1 ~ 2.0), square V/F curve

Acceleration & Two methods: linear acceleration and deceleration, S-curve acceleration and deceleration
Deceleration curves Four settings of acceleration and deceleration time, time unit 0.01s, 65000s max.
Power supply voltage compensation enables setting within the range of 50% ~ 100% (the output cannot exceed the
Rated output voltage
Product basic functions

input voltage) when rated motor voltage is 100%.


Automatic voltage
The output voltage can be kept constant automatically during grid voltage fluctuation.
regulation

Automatic
The V/F control mode automatically optimizes the output voltage according to the load to realize energy saving.
energy-saving operation
Automatic current
Automatic current limit during operation to prevent frequent overcurrent failure trip
limiting
Instantaneous power
Uninterrupted running during instantaneous power failure through the bus voltage control
failure treatment
PID control, speed tracking and power-off restart, jump frequency, frequency upper and minimum control, program
Standard functions operation, multi-speed, RS485 communication port, analog output, parameter access level setting, common
parameter setting, monitoring parameter comparator output, counting and timing, and swing frequency
Frequency setting Analog voltage/current terminals AS (VS), communication and multi-channel terminals setting, combination of
channel primary and secondary channels, and external keyboard settings can be switched in various ways
Communication setting via upper computer
Producct 品基本功能

Command running
Terminal setting via the X terminal
channel
The number entering via the external keyboard
Start, stop, positive and negative rotation, point, multi-speed, free stop, reset, acceleration and deceleration time
Input command signal
selection, frequency and channel setting and external fault alarm

External output signal 1-way relay output, 1-way collector open output
Overvoltage, undervoltage, current limiting, overcurrent, overload, electronic thermal relay, overheat, overvoltage
Protections stall, data protection, rapid protection, input and output phase loss protection
Function code information of the inverter can be uploaded and downloaded to realize fast parameter replication (only
Parameter copy external keyboard)
1. External keyboard input all parameters of monitoring parameter group including output frequency, given
frequency, output current, input voltage, output voltage, motor speed, PID feedback, PID setting, module
temperature, given torque and output torque.
Condition monitoring 2. The relevant status of the inverter can be indicated through the three LED lights on the product.
POWER indicates the power and it’s red when power is normal.
RUN indicates running status and it’s green when running is normal.
FAULT indicates warning or fault and it’s red when something is abnormal.
Overvoltage, undervoltage, overcurrent, short circuit, phase loss, overload, overheating, overvoltage stall, current
Fault warning limiting, data protection, current fault conditions and historical faults
If the altitude is higher than 1000 meters, reduce 1% for each elevation of 100 meters;
Installation site No condensation, icing, rain, snow, hail, etc., solar radiation lower than 700W/m2, air pressure between 70kPa ~
106kPa
Environment

Temperature & -20℃ ~ +50℃, reduce 5% for each increase of 1℃ when it’s above 40 ℃, 50℃ max (no-load running)
Humidity ≤95%RH (20℃; relative humidity change rate shall not exceed 5% per hour, and no condensation)
Vibration 5.9m/s2(0.6G) when during 9Hz~200Hz
Storage temperature -30℃~+60℃
Installation method wall-mounted

3
General AC01-Series network inverter manual

Protection level IP20


Pollution level Level 2
Natural cooling for models with V1 cases
Cooling method
Forced air cooling for models with V2 and V3 cases

Table 1- 3

4
AC01-Series network inverter manual Installation

Chapter 2 Installation
Please use the product in strict accordance with the requirements of the environment, wiring, and ventilation described in this chapter.

in order to ensure safety of the users and best performance of the inverter.

 Dimensions of the inverter and keyboard

Figure 2- 1 Installation dimensions of V1 model

Boundary dimension (mm) Mounting dimension (mm) Mounting


Model aperture(
W H D A B W1 H1
mm)
AC01-S2-R40G-B

AC01-S2-R75G-B
65 150 130 5 5.5 54 139.5 Φ5.2
AC01-T3-R75G-B

AC01-T3-1R5G-B

Table 2- 2 Installation dimensions of V1 model

5
Installation AC01-Series network inverter manual

Figure 2- 2 Installation dimensions of V2 model

Boundary dimension (mm) Mounting dimension (mm) Mounting


Model aperture(
W H D A W1 H1 H2 mm)
AC01-S2-1R5G-B

AC01-S2-2R2G-B
75 205 145 4.7 55 207.9 193.25 Φ5.2
AC01-T3-2R2G-B

AC01-T3-004G-B
Table 2- 2 Installation dimensions of V2 model

 Standard connection diagram

Note:

1. Select the appropriate brake resistance according to the field conditions and Brake Resistance Specifications;

2. Multifunctional input terminals (X1 ~ X3) can be used as input for NPN transistor signals;

3. The digital and analog grounding terminals are combined into the COM terminal in the control circuit;

6
AC01-Series network inverter manual Installation

Figure 2- 3 Standard connection diagram

 Auxiliary terminals and output capacity


Terminal Function Maximum output
a loop formed with a 10V auxiliary analog power
+10V output and COM 50mA
a loop formed with a 24V auxiliary digital power
+24V output and COM 100mA

COM digital and analog power supply


X1 、X2、X3 digit input terminal NPN-type, impedance 15 k Ω

Y Collector open output & programmable action object. DC24V/50mA


TATC: normally on; TB TC: normally off 3A/240VAC
TA/TB/TC Passive contact output & programmable action object.
5A/30VDC
AS Current analog input 0-20mA/ 4-20mA
VS Voltage analog input 0-10V
A+ B- RS485 communication terminal

Table 2- 3 Auxiliary terminals and output capacity

7
Installation AC01-Series network inverter manual

 Main loop terminal


Symbol Designation Function
T3: three-phase power input R phase
R/L
S2: single-phase power input L line
T3: three-phase power input S phase
S main loop input terminal
S2: reserved
T3: three-phase power input T phase
T/N
S2: single-phase power input N wire
U U-phase output
V main loop output terminal V-phase output
W W-phase output
﹢ DC bus power terminal +
Used on external brake resistance to realize quick stop
PB brake resistance terminal
ground terminal Used to ground the inverter

Table 2- 4 Main loop terminal

 RJ45 interface pin definition

Figure 2- 4 RJ45 interface

It’s the top view above and the specific network interpretations are as follows:

Pin label Pin definition Description

1 COM 5V power supply ground terminal

2 NC Reserved

3 COM 5V power supply ground terminal

4 5V 5V power

5 5V 5V power

6 LOAD software programming to select pin

7 B- RS485 communication B-, shared with terminal B-

8 A+ RS485 communicationA+, shared with terminalA+

Table 2-5 Network interpretations

8
AC01-Series network inverter manual Installation

 Recommended brake resistance specifications

The braking resistance and resistance power in the following table are verified by ordinary inertia load and intermittent braking mode. If it

needs to be used in the occasion of large inertia and frequent braking for a long time, please adjust the braking resistance and resistance power

appropriately according to the specifications of the selected inverter and the rated parameters of the braking unit. If you have any questions, please

consult the service hotline of technical service department of Suzhou Veichi Electric Technology Co., LTD.
Three-phase 380V

Recommended resistance
Motor (on 100% braking torque and 10% Minimum
Model Brake unit braking rate)
power (kW) resistance(Ω)
Resistance model Resistors qty.
AC01-T3-R75G-B 0.75 kW Built-in, standard 750 Ω 150W 1 100Ω
AC01-T3-1R5G-B 1.5 kW Built-in, standard 400 Ω 300W 1 100Ω
AC01-T3-2R2G-B 2.2 kW Built-in, standard 250 Ω 400W 1 100Ω
AC01-T3-004G-B 4.0 kW Built-in, standard 150 Ω 500W 1 40Ω
AC01-T3-5R5G-B 5.5 kW Built-in, standard 100 Ω 600W 1 40Ω
AC01-T3-7R5G-B 7.5 kW Built-in, standard 75 Ω 780W 1 40Ω
Single-phase 220V

Recommended resistance
Motor (on 100% braking torque and 10% Minimum
Model Brake unit braking rate)
power (kW) resistance(Ω)
Resistance model Resistors qty.
AC01-S2-R40G-B 0.4 kW Built-in, standard 400Ω 100W 1 50Ω
AC01-S2-R75G-B 0.75 kW Built-in, standard 200Ω 120W 1 50Ω
AC01-S2-1R5G-B 1.5 kW Built-in, standard 100Ω 300W 1 50Ω
AC01-S2-2R2G-B 2.2 kW Built-in, standard 75.0Ω 300W 1 20Ω
AC01-S2-004G-B 4kW Built-in, standard 50.0Ω 500W 1 20Ω

Table 2-6 Recommended brake resistance specifications

9
AC01-Series network inverter manual Indicators, Keyboard Layout and Operation Instructions

Chapter 3 Indicators, Keyboard and Operation Instructions


 Indicators

Figure 3- 1 AC01 series main interface

States ofAC01 Series inverters can be told via the three indicating lights on its interface:

Symbol Indicator Status Description


on Power on, and ready for operation
POWER RED
off Abnormal power supply
on The inverter runs in positive rotation
RUN GREEN Flash (500ms on and then 500ms off,and cycle starts again) Inverter runs in reverse
off Inverter is not running
on Faults of main codes 1~11 occur
Flash (100ms on and then 100ms off,and cycle starts again) Faults of main codes 12~117 occur
FAULT RED Flash slowly (100ms on and then 100ms off +100ms on and
warning
then 1700ms off,
,and cycle starts again)
off fault-free

Table 3-1 Indicators

Note: Refer to PAGE 54 of this manual for main FAULT/WARNING codes 1~163.

 Keyboard layout

Note: The current version of AC01 series inverter does not have its own keyboard, and KBD300-25 or KBD10-15 keyboard can be

extended via RJ45 network port.

10
Indicators, Keyboard Layout and Operation Instructions AC01-Series network inverter manual

Figure 3- 2 KBD300-25 dual-line display keyboard

 External keyboard functions

Symbol Dual-line display keyboard Functions

Hz: Frequency;A: current; V: voltage; V/A: voltage or current; RPM: speed;


A Unit indicator
%: percentage.
B Status indicator On: forward running; flash: reverse running; Off: shutdown.
Menu Enter the menu interface when standby or running. Press the key to exit the modification
C after parameters are modified and long press the key for 1 second to directly enter the
status interface.
Run
When run/stop is controlled by the keyboard, press the key to make inverter rotate
forward. The status indicator is on for forward rotating and flashing for reverse rotating.
F Stop/Reset
When the command is given via keyboard, press the key to stop the inverter.
F11.03[keyboard stop key setting] can be used to define whether other command
channels are valid or not; Press the key to reset the inverter in the fault state.

Digital potentiometer: press the up key to increase the operating value for clockwise
rotation and press down key to reduce the operating value for counterclockwise rotation.

G Confirm key: Press this key to confirm after modifying the value
Move left/ right
Move left or right

Multifunction key
H Select the function of the key via F11.02[multi-function key selection via keyboard]

Table 3-2 External keyboard meanings

 Meaning of external keyboard indicators

Designation Status Meaning


Hz flash/on frequency unit
External A on current unit
keyboard V on voltage unit
unit indicator RPM on speed unit
% flash/on Percentage unit

Table 3-3 Meaning of external keyboard indicators


11
AC01-Series network inverter manual Indicators, Keyboard Layout and Operation Instructions

 Basic parameter group setting

Take F0.122 [acceleration time] setting as an example to illustrate the basic operations of the external LED keyboard.

Figure 3- 3 Setting steps

Note: The keyboard shift key on the external keyboard can be used to quickly select the tens, hundreds and thousands of parameter values.

 Operation monitoring status checking

Figure 3- 4 Checking steps

Note: When using the external keyboard, use the left shift key to cycle switch the first row of monitoring parameters, and use the right shift key to

cycle switch the second row of monitoring parameters.

 Monitoring parameters checking


Take C02.05[PLC operation phase] parameter checking as an example to explain the basic operation of the external LED keyboard.

Figure 3- 5 Checking steps

12
AC01-Series network inverter manual Function List

Chapter 4 Function List


This section only provides a brief list of functions. For details please refer to the technical manual of AC01 series inverter or consult relevant

staff of Veichi.

4.1 Safety Precautions


Danger
Note all the information about safety in this book.
Please note that failure to follow these warnings may result in serious injury or even death. We shall not be liable for any personal injury or
equipment damage resulting from failure to comply with this manual by users.

Table 4-1 Safety precautions

4.2 Reading Method of the Parameter List


 Icons and terms under control mode

Mark Meaning Mark Meaning


Valid parameters in V/F control Changeable parameters during running
V/F RUN
mode
Valid parameters in open-loop vector Unchangeable parameters during running
SVC STOP
control mode
READ Read-only parameters, unchangeable

Table 4- 2 Icons and terms

4.3 Function Group


Note
Setting parameter [F11.30] to choose RS485 or foreign keyboard and this parameter will not be reset with [F00.03] parameter. It is strongly
recommended that the user disconnects the hardware of the other channel when using one of them.

Table 4- 3 Note

Parameters of the Inverter

Parameter Designation Parameter Designation


F00.0x Environment settings F07.0x Start
F00.1x Common parameter setting F07.1x Stop
F01.0x Basic command F07.2x DC braking & speed tracking
F01.1x Frequency command F07.3x Jog
F01.2x-F01.3x Acceleration & deceleration time F07.4x Start/stop frequency keeping& frequency jump
F01.4x PWM control F08.0x Counting and timing
F02.0x Motor basic parameters & self-learning F08.1x Reserved
setting
F02.1x Advanced parameters of asynchronous F08.2x Reserved
motor
F02.2x Advanced parameters of synchronous F08.3x Swing frequency control
motor
F02.3x-F02.4x Reserved F10.0x Current protection
F02.5x Motor application parameters F10.1x Voltage protection
F03.0x Speed ring F10.2x Auxiliary protection
F03.1x Current loop and torque limit F10.3x Load protection
F03.2x Torque optimization F10.4x Stall protection
F03.3x Magnetic flow optimization F10.5x Fault recovery & motor overload protection

13
Function List AC01-Series network inverter manual

F03.4x-F03.5x Torque control F11.0x keys operation


F04.0x V/F control F11.1x Cyclic state monitoring
F04.1x User-defined V/F curve F11.2x Monitoring parameter control
F04.2x Reserved F11.3x Keyboard special characteristics
F04.3x V/F energy saving control F12.0x Modbus slave parameters
F05.0x Digital input terminal F12.1x Modbus master parameters
F05.1x Delay X1-X3 detection F13.00-F13.06 PID setting and feedback
F05.2x Digital input terminal operation selection F13.07-F13.24 PID adjustment
F05.3x Reserved F13.25-F13.28 PID feedback of disconnection
F05.4x Analog type processing F13.29-F13.33 Sleep mode
F05.5x Analog linear processing F14.00-F14.14 Multi- speed frequency setting
F05.6x AS/VS curve-1 processing F14.15 PLC operation mode selection
F05.7x AS/VS curve 2 processing F14.16-F14.30 PLC operation time selection
PLC direction & acceleration/deceleration time
F05.8x AS/VS as digital input terminal F14.31-F14.45
selection
F06.0x Reserved F16 group Reserved
F06.1x Reserved C00.xx Basic monitoring
F06.2x-F06.3x Digital & relay output C01.xx Fault monitoring
F06.4x Frequency detection C02.xx Application monitoring
F06.5x Monitoring parameter comparator output C03.xx Reserved
F06.6x-F06.7x Virtual input and output terminals

Table 4- 4 Parameters of the inverter

4.4 F00 Group: Environmental Applications


F00.0x group: environment setting

Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
Set parameter access level according to parameter access
limits
F00.00 Parameter access 0
0: standard parameters (Fxx.yy,Cxx.yy) RUN
(0x0000) level (0 ~3)
1: common parameters (F00.00,Pxx.yy)
2: monitered parameters (F00.00,Cxx.yy)
3: changed pa (F00.00,Hxx.yy)
V/F SVC
Set the inverter initialization mode.
0: No initialization
F00.03 0
Initialization 11: Choose the set value according to purposes (excluding STOP
(0x0003) (0~33)
motor parameters)
22:All parameters initialized
33: Clear the failure records
V/F SVC
0: No function
F00.04 Keyboard 11: Upload parameters to keyboard 0
STOP
(0x0004) parameters copy 22: Download parameters to the inverter (0~30)
Note: The built-in keyboard does not support parameter
copying.
V/F SVC
F00.07 0
Free parameter 1 machine number when using multiple machines; RUN
(0x0007) (0~65535)
mode number for purposes when using multiple machines

14
AC01-Series network inverter manual Function List

V/F SVC
F00.08 0
Free parameter 2 machine number when using multiple machines; RUN
(0x0008) (0~65535)
mode number for purposes when using multiple machines

Table 4- 5 F00.0x group

F00.10~F00.39 group: common parameters setting


Parameter Factory default Adjustable
Designation Content
code (setting range) attribute
(Address) V/F SVC
F00.1~ Common LED ones & tens-place: set “yy” between 00~ 99 among
Generic default
F00.39 parameter the parameter code Fxx.yy
parameters RUN
(0x000A~ addresses 00~99
(0000~2999)
0x0027) setting LED hundreds & thousands-place: set “xx” between 00~
31 among the parameter code Fxx.yy

Table 4- 6 F00.10~F00.39 group

4.5 F01 Group: Basic Setting


F01.0x group: basic setting
Factory
Parameter
default Adjustable
code Designation Content
(setting attribute
(Address)
range)
V/F SVC
Controlling method of the motor
0:AM-V/F: V/F control mode
F01.00 Motor 1 0
1:AM-SVC: open loop vector control, current closed loop control STOP
(0x0100) control mode (0~11)
PM:
10:PM-V/F: V/F control
11:PM-SVC:open loop vector control, current closed loop control
V/F SVC
The channel set for the inverter to receive command of operation,
Command stop and direction.
F01.01 1
running 0: keyboard control (external keyboard preferred) RUN
(0x0101) (0~3)
channel 1: terminal control
2: RS485 communication control
3: reserved
5: reserved
V/F SVC 6: via RS485
Setting frequency source channel for communication port
the inverter: 7: via UP/DW terminal
Source
F01.02 0: via keyboard number entering 8: via PID control 2
channelA of RUN
(0x0102) 1: via keyboard analog potentiometer 9: via program control (0~11)
set frequency
2: via current analog AS (PLC)
3: via voltage analog VS 10: reserved
4: reserved 11: via multi-speed
setting
Gain of
100.0
F01.03 frequency V/F SVC
(0.0 %~500. STOP
(0x0103) source Gain of the frequency source channelA
0%)
channelA
Source V/F SVC
F01.04 0
channel B of Source channel of frequency setting for the inverter, the same as RUN
(0x0104) (0~11)
set frequency [F01.02]
Gain of
100.0
F01.05 frequency V/F SVC
(0.0 %~500. STOP
(0x0105) source Gain of the frequency source channel B
0%)
channel B
15
Function List AC01-Series network inverter manual

V/F SVC
Reference
Change this parameter to select reference source for frequency
F01.06 frequency 0
setting channel B RUN
(0x0106) source for (0~1)
0: refer to the maximum output frequency
channel B
1: refer to the frequency of channelA

V/F SVC
Used for setting combination method of frequency channelA and
B for the inverter.
Selection of
0: channelA
F01.07 frequency 0
1: channel B RUN
(0x0107) source (0~5)
2: channelA + channel B
channel
3: channelA- channel B
4: the higher frequency between channelA and channel B
: the lower frequency between channelA and channel B
V/F SVC
3: via current analog AS
When this parameter is valid, it is
4: via voltage analog VS
used to set the source channel for
5: reserved
each command running channel of
6: reserved
bundled frequencies
7: via RS485
Ones-place: bundled command from
Command of communication port
keyboard 0x0000
F01.08 running 8: via UP/DW terminal
Tens-place: bundled command from (0x0000~0x RUN
(0x0108) bundled 9: via PID control
terminals DDDD)
frequencies A: via program control
Hundreds-place: bundled command
(PLC)
from communication port
B: reserved
Thousands-place: reserved
C: via multi-speed
0:no bundling
setting
1: via keyboard number entering
D: reserved
2: via keyboard analog potentiometer
Frequency 50.00Hz
V/F SVC
F01.09 setting via (0.00Hz~
Used to set and modify the frequency set via input keyboard RUN
(0x0109) keyboard upper limit
numbers
numbers frequency)

Table 4- 7 F01.0x group

F01.1x group: command about frequency


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
50.00Hz
F01.10 Maximum V/F SVC (upper limit
STOP
(0x010A) frequency The maximum frequency can be set for the inverter. frequency
~500.00Hz)
V/F SVC
3: via current analogAS
Select the source channel of
4: reserved
Upper limit upper limit frequency for
F01.11 5: reserved 0
frequency source the inverter RUN
(0x010B) 6: via RS485 (0~7)
selection 0: via keyboard number
communication port
entering
7: reserved
1: via keyboard analog
potentiometer 0.00Hz
Upper limit 2:电流模拟量
F01.12 V/F SVC AS 给定 (lower limit ~
frequency setting via RUN
(0x010C) Set upper limit frequency value when F01.11 is set 0 upper limit
number entering
frequency)
0.00Hz
F01.13 Lower limit V/F SVC
(0.00Hz~ upper RUN
(0x010D) frequency Set lower limit value of frequency.
limit frequency)

16
AC01-Series network inverter manual Function List

V/F SVC
F01.14 Resolution of 0
Set the resolution of the frequency command. STOP
(0x010E) frequency command (0~4)
0:0.01Hz; 1:0. 1Hz; 2:0.1 rpm; 3:1 rpm; 4:10 rpm

Table 4-8 F01.1x group

F01.2x~F01.3x group: acceleration & deceleration time

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Acceleration &
Set benchmark frequency to calculate acceleration &
F01.20 deceleration time 0
deceleration time STOP
(0x0114) benchmark (0~2)
0: Maximum frequency; 1: fixed frequency of 50Hz;
frequency
2: set frequency
V/F SVC
F01.21 Acceleration time 2
The unit of the set acceleration time STOP
(0x0115) unit (0~2)
0:1s; 1:0.1s; 2:0.00s
V/F SVC
Time required to accelerate the output frequency from Model
F01.22
Acceleration time 1 0.00Hz to the benchmark frequency setting(0.01s~650. RUN
(0x0116)
1s~65000s (F01.21 = 0); 0.1s~6500.0s (F01.21 = 1); 00s)
0.01s~650.00s (F01.21 = 2)
V/F SVC Model
F01.23
Deceleration time 1 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x0117)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.24
Acceleration time 2 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x0118)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.25
Deceleration time 2 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x0119)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.26
Acceleration time 3 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x011A)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.27
Deceleration time 3 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x011B)
from benchmark frequency to 0.00Hz 00s)
V/F SVC Model
F01.28
Acceleration time 4 Time required to accelerate the output frequency from setting(0.01s~650. RUN
(0x011C)
0.00Hz to the benchmark frequency 00s)
V/F SVC Model
F01.29
Deceleration time 4 Time required for the output frequency to decelerate setting(0.01s~650. RUN
(0x011D)
from benchmark frequency to 0.00Hz 00s)
V/F SVC
S-curve acceleration
F01.30 Whether the S-curve acceleration & deceleration 1
& deceleration STOP
(0x011E) selection is valid (0~2)
selection
0:invalid; 1:valid; 2:flexible S-curve
F01.31 S-curve acceleration V/F SVC 0.20s
STOP
(0x011F) start time Set start time of acceleration for S-curve (0.00s~10.00s)
F01.32 S-curve acceleration V/F SVC 0.20s
STOP
(0x0120) end time Set end time of acceleration for S-curve (0.00s~10.00s)
F01.33 S-curve deceleration V/F SVC 0.20s
STOP
(0x0121) start time Set start time of deceleration for S-curve (0.00s~10.00s)
F01.34 S-curve deceleration V/F SVC 0.20s
STOP
(0x0122) end time Set end time of deceleration for S-curve (0.00s~10.00s)

17
Function List AC01-Series network inverter manual

0.00Hz
Switch frequency
F01.35 V/F SVC (0.00Hz~
between acceleration RUN
(0x0123) Set frequency switch between acceleration time 1 & 2 Upper limit
time 1 & 2
frequency)

Table 4-9 F01.2x~F01.3x group

F01.4x group: PWM control


Parameter Factory default Adjustable
Designation Content
code (setting range) attribute
(Address) Model setting
F01.40 V/F SVC
Carrier frequency (2.0 kHz~12.0 RUN
(0x0128) Used to set the switching frequency of inverter IGBT.
kHz)

LED hundreds-place:
random PWM enable
V/F SVC 0: forbidden
LED ones-place: 1: valid under V/F
relationship between carrier mode
and temperature 2: valid under vector
0: irrelevant mode
F01.41 1111
PWM control mode 1: relevant RUN
(0x0129) (0000~1211)
LED tens-place: LED thousands-palce:
relationship between carrier PWM modulation
and output frequency mode
0: irrelevant 0: three-phase only
1: relevant 1: automatic switching
between two-phase
&three-phase

F01.43 Compensated gain V/F SVC 306


RUN
(0x012B) of dead zone Compensated gain of dead zone (0~512)
V/F SVC
F01.46 0
PWM random depth When the PWM random depth is effective, the larger it RUN
(0x012E) (0~20)
is set, the larger the carrier fluctuation will be.

Table 4-10 F01.4x group

4.6 F02 Group: Parameter of Motor 1


F02.0x group: basic parameters and self-learning type selection of the motor
Parameter Factory default Adjustable
Designation Content
code (setting range) attribute
(Address) V/F SVC
F02.00 Set the type of motor. 0
Motor type READ
(0x0200) 0:Asynchronous motor (AM) (0~1)
1: Synchronous motor (PM)
F02.01 V/F SVC 4
Pole number STOP
(0x0201) Set the motor pole number. (2~98)
F02.02 V/F SVC Model setting
Rated power STOP
(0x0202) Set the rated power of motor (0.1 kW~22.0 kW)
Model setting
F02.03 V/F SVC
Rated frequency (0.01 Hz~ STOP
(0x0203) Set the rated frequency of motor
maximum frequency)
F02.04 V/F SVC Model setting
Rated speed STOP
(0x0204) Set the rated speed of motor (0 rpm~65000 rpm)
F02.05 V/F SVC Model setting
Rated voltage STOP
(0x0205) Set the rated voltage of motor (0 V~2000 V)

18
AC01-Series network inverter manual Function List

F02.06 V/F SVC Model setting


Rated current STOP
(0x0206) Set the rated current of motor (0.1A~3000.0A)

V/F SVC
[F02.07] will automatically be set to "0"
Parameters after the parameter self-tuning is finished.
F02.07 0
self-learning 0: no operation STOP
(0x0207) (0~3)
selection 1: rotational self-learning
2: static self-learning
3: stator resistance self-learning

Table 4-11 F02.0x group

Note: When F02.00 [motor type] is a synchronous motor, F2.04 [motor rated speed] is calculated from F2.01 [motor pole number] and

F2.03 [motor rated frequency], please set the corresponding parameters correctly. The calculation formula is: F2.04 [rated speed of

motor] = 60* F2.03 [rated frequency of motor] / (F2.01[number of poles of motor] / 2)

F02.1x group: advanced parameters of asynchronous motor

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F02.10 V/F SVC Model setting
No-load current STOP
(0x020A) Set no-load current of asynchronous motor (0.1A~3000.0A)

Model setting
F02.11 V/F SVC
Stator resistance (0.01 mΩ~ STOP
(0x020B) Set stator resistance of asynchronous motor
60000.00 mΩ)

Model setting
F02.12 V/F SVC
Rotor resistance (0.01 mΩ~ STOP
(0x020C) Set rotor resistance of asynchronous motor
60000.00 mΩ)

Model setting
F02.13 Stator leakage V/F SVC
(0.01 mH ~ STOP
(0x020D) inductance Set stator leakage inductance of asynchronous motor
65535.00 mH)
Model setting
F02.14 V/F SVC
Stator inductance (0.01 mH ~ STOP
(0x020E) Set stator inductance of asynchronous motor
65535.00 mH)
F02.15 Stator resistance V/F SVC Model setting
READ
(0x020F) per-unit value Set stator resistance per-unit value (0.01% ~ 50.00%)

F02.16 Rotor resistance V/F SVC Model setting


READ
(0x0210) per-unit value Set rotor resistance per-unit value (0.01% ~ 50.00%)

Stator leakage
F02.17 V/F SVC Model setting
inductance per-unit READ
(0x0211) Set stator leakage inductance per-unit value (0.01% ~ 50.00%)
value
F02.18 Stator inductance V/F SVC Model setting
READ
(0x0212) per-unit value Set stator inductance per-unit value (0.1% ~ 999.0%)
F02.11~F02.14 V/F SVC
F02.19 0x0000
decimal point Set the decimal point of the four parameters from READ
(0x0213) F02.11 to F02.14. This parameter is read-only. (0x0000 ~ 0x2222)
selection

Table 4-12 F02.1x group

F02.2x group: advanced parameters of synchronous motor

19
Function List AC01-Series network inverter manual

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

F02.20 V/F SVC Model setting


Stator resistance STOP
(0x0214) Set stator resistance of synchronous motor. (0.01 mΩ ~ 60000.00 mΩ)
F02.21 V/F SVC Model setting
D-axis inductance STOP
(0x0215) Set d-axis inductance of synchronous motor. (0.001 mH ~ 6553.500 mH)

F02.22 V/F SVC Model setting


Q-axis inductance STOP
(0x0216) Set q-axis inductance of synchronous motor. (0.001 mH ~ 6553.500 mH)
V/F SVC
Counter
F02.23 Set counter electromotive force of synchronous Model setting
electromotive STOP
(0x0217) motor. Only recognized during rotation (0 V ~ 500 V)
force
self-tuning.
V/F SVC
F02.24 Encoder mounting Model setting
Set encoder mounting angle of synchronous RUN
(0x0218) angle (0.0° ~ 360.0°)
motor
V/F SVC
F02.25 Stator resistance Model setting
Set stator resistance per-unit value of READ
(0x0219) per-unit value (monitored value)
synchronous motor
V/F SVC
F02.26 D-axis inductance Model setting
Set d-axis inductance per-unit value of READ
(0x021A) per-unit value (monitored value)
synchronous motor
V/F SVC
F02.27 Q-axis inductance Model setting
Set q-axis inductance per-unit value of READ
(0x021B) per-unit value (monitored value)
synchronous motor
V/F SVC
F02.28 Pulse width Model setting
Set pulse width coefficient of synchronous STOP
(0x021C) coefficient (00.00 ~ 99.99)
motor
V/F SVC
F02.20~F02.22
F02.29 Set the decimal point of the three parameters 0x0000
decimal point READ
(0x021D) from F02.20 to F02.22. This parameter is (0x0000 ~ 0x2222)
selection
read-only.

Table 4-13 F02.2x group

F02.3x~F02.4x group: reserved

F02.5x~F02.6x group: motor application parameters

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F02.50 Stator resistor 0
0: invalid; 1: only learn without update; value greater STOP
(0x0232) learning selection (0 ~ 3)
than 1: learn and update;
Stator resistance
F02.51 V/F SVC 0
learning starting RUN
(0x0233) Set stator resistance learning starting factor 1. (0 ~ 1000)
factor 1
Stator resistance
F02.52 V/F SVC 0
learning starting RUN
(0x0234) Set stator resistance learning starting factor 2. (-20.00% ~ 20.00%)
factor 2
Stator resistance
F02.53 V/F SVC 0
learning starting RUN
(0x0235) Set stator resistance learning starting factor 3. (0 ~ 65535)
factor 3

20
AC01-Series network inverter manual Function List

V/F SVC
Magnetic pole Ones-place: reserved
F02.60 search of Tens-place: open loop vector 0010
STOP
(0x023C) synchronous 0: off ; 1: on; 2: on but only the first power-on start (0000 ~ 3223)
motor The hundreds-place: V/F
0: off; 1: on; 2: on, but only the first power-on start
Current for
F02.61 V/F SVC 0.0%
magnetic pole STOP
(0x023D) Set the current value of magnetic pole search (0.0% ~ 6553.5%)
search

Table 4-14 F02.5x ~ F02.6x group

4.7 F03 Group: Vector Control


F03.0x group: speed ring
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
SVC
F03.00 ASR speed stiffness 32
Set speed stiffness level. The higher the level, the better RUN
(0x0300) level (1 ~ 128)
the speed stiffness.

F03.01 ASR speed stiffness SVC 0x0000


RUN
(0x0301) mode SetASR speed stiffness mode. (0x0000 ~ 0x1111)

F03.02 ASR (speed ring) SVC 10.00


RUN
(0x0302) proportional gain 1 SetASR (speed ring) proportional gain 1 (0.01 ~ 100.00)
F03.03 ASR (speed ring) SVC 0.100s
RUN
(0x0303) integral time1 SetASR (speed ring) integral time1 (0.000 s ~ 6.000 s)
0.0ms
F03.04 SVC
ASR filter time 1 (0.0 ms ~ 100.0 RUN
(0x0304) SetASR filter time 1.
ms)
0.00Hz
F03.05 ASR switching SVC
(0.00Hz ~ RUN
(0x0305) frequency 1 SetASR switching frequency 1.
max frequency)

F03.06 ASR (speed ring) SVC 10.00


RUN
(0x0306) proportional gain 2 SetASR (speed ring) proportional gain 2. (0.01 ~ 100.00)

F03.07 ASR (speed ring) SVC 0.100s


RUN
(0x0307) integral time 2 SetASR (speed ring) integral time 2. (0.000s ~ 6.000s)

F03.08 SVC 0.0ms


ASR filter time 2 RUN
(0x0308) SetASR filter time 2. (0.0ms ~ 100.0ms)
0.00Hz
F03.09 ASR switching SVC
(0.00Hz ~ RUN
(0x0309) frequency 2 SetASR switching frequency 2.
max frequency)

Table 4-15 F03.0x group

F03.1x group: current loop & torque limit


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F03.10 D-axis proportional SVC 1.000
RUN
(0x030A) gain Set d-axis proportional gain of current loop (0.001 ~ 4.000)

F03.11 SVC 1.000


D-axis integral gain RUN
(0x030B) Set d-axis integral gain of current loop (0.001 ~ 4.000)

F03.12 Q-axis proportional SVC 1.000 RUN

21
Function List AC01-Series network inverter manual

(0x030C) gain Set q-axis proportional gain of current loop (0.001 ~ 4.000)
F03.13 SVC 1.000
Q-axis integral gain RUN
(0x030D) Set q-axis integral gain of current loop (0.001 ~ 4.000)
F03.15 Torque limit of SVC 250.0%
RUN
(0x030F) motoring Set torque limit of motoring (0.0% ~ 400.0%)
F03.16 Torque limit of SVC 250.0%
RUN
(0x0310) power generation Set torque limit of power generation (0.0% ~ 400.0%)
F03.17 Regenerative torque SVC 0.0%
RUN
(0x0311) limit at low speed Set regenerative torque limit at low speed (0.0% ~ 400.0%)
Amplitude-frequenc SVC
F03.18 6.00Hz
y of torque limit at Set amplitude & frequency of torque limit at low RUN
(0x0312) (0.00Hz ~ 30.00Hz)
low speed speed
SVC
Ones-place: torque limit channel of motoring
decided
0: via keyboard number entering;
1: via keyboard potentiometer;
2: via AS setting; 3: via VS setting
4: reserved; 5: reserved;
6: via RS485 communication port (0x3014)
7: reserved;
Tens-place: torque limit channel of power generation
F03.19 Torque limit 0x0000
decided RUN
(0x0313) selection (0x0000~0x0177)
0: via keyboard number entering;
1: via keyboard potentiometer;
2: via AS setting; 3: via VS setting
4: reserved; 5: reserved;
6: via RS485 communication port (0x3014);
7: reserved;
Hundreds-place
0:C00.06 displays torque limit of motoring
1:C00.06 displays torque limit of power generation
Thousands-place: reserved

Table 4-16 F03.1x group

F03.2x group: torque optimization


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
SVC
LF sourcing current
F03.20 When the open-loop control of PM motor is valid, 20.0%
of synchronous RUN
(0x0314) and the greater sourcing current, the greater the (0.0%~50.0%)
motor
torque output.
SVC
HF sourcing current
F03.21 When the open-loop control of PM motor is valid, 10.0%
of synchronous RUN
(0x0315) and the greater sourcing current, the greater the (0.0%~50.0%)
motor
torque output.
Sourcing current SVC
F03.22 10.0%
frequency of 100.0% of the set sourcing current frequency RUN
(0x0316) (0.0%~100.0%)
synchronous motor corresponds to F01.10[Upper limit frequency].
Slip compensation
F03.23 SVC 100.0%
of asynchronous RUN
(0x0317) Set slip compensation of asynchronous motor. (0.0%~250.0%)
motor

F03.24 Initial Starting SVC 0.0%


RUN
(0x0318) torque Set initial starting torque. (0.0%~250.0%)

Table 4-17 F03.2x group

22
AC01-Series network inverter manual Function List

F03.3x group: magnetic flow optimization


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
Feedforward
F03.30 SVC 10.0%
coefficient of weak RUN
(0x031E) Set feedforward coefficient of weak magnetism. (0.0% ~ 500.0%)
magnetism
Magnetic
F03.31 SVC 10.0%
weakening control RUN
(0x031F) Set magnetic weakening control gain (0.0% ~ 500.0%)
gain
Upper limit
F03.32 SVC 60.0%
magnetic weakening RUN
(0x0320) Set upper limit magnetic weakening current. (0.0% ~ 250.0%)
current
Magnetic
F03.33 SVC 90.0%
weakening voltage RUN
(0x0321) Set magnetic weakening voltage coefficient (0.0% ~ 120.0%)
coefficient
F03.34 SVC 250.0%
Output power limit RUN
(0x0322) Set output power limit. (0.0% ~ 400.0%)

F03.35 Over-excitation SVC 100.0%


RUN
(0x0323) braking gain Set over-excitation braking gain (0.0% ~ 500.0%)

F03.36 Over-excitation SVC 100.0%


RUN
(0x0324) brake clipping Set over-excitation brake clipping (0.0% ~ 250.0%)

SVC
F03.37 Energy-saving 0
0: off; RUN
(0x0325) running (0~1)
1: on
Lower limit
F03.38 excitation of SVC 50.0%
RUN
(0x0326) energy-saving Set lower limit excitation of energy-saving running (0.0%~80.0%)
running
Filter coefficient of
F03.39 SVC 0.010s
energy-saving RUN
(0x0327) Set filter coefficient of energy-saving running (0.000s~6.000s)
running

Table 4-18 F03.3x group

F03.4x~F03.5x group: torque control


Paramete
Factory default Adjustable
r code Designation Content
(setting range) attribute
(Address)
SVC
F03.40 Torque control 0
0: speed control mode to limit torque RUN
(0x0328) selection (0~1)
1: torque control mode to limit speed
SVC Tens-place:
Ones-place: channelA: channel B:
0: torque setting via keyboard Setting methods
number entering the same
1: via keyboard potentiometer; with
2: viaAS channelA
F03.41 Torque command 3: via VS Hundreds-place: 0000
RUN
(0x0329) setting 4: reserved combinatio (0000~0599)
5: reserved ns:
6: via RS485 communication 0:A channel
port 1: B channel
7: reserved 2: A+B
8: reserved 3: A-B
9: reserved 4:MIN(A,B)
F03.42 Torque setting via SVC 5:MAX(A,B) 0.0% RUN

23
Function List AC01-Series network inverter manual

(0x032A) keyboard number Set torque via keyboard number entering. (0.0%~100.0%)
entering
F03.43 Lower limit SVC 0.00%
RUN
(0x032B) torque input Set the lower limit value of torque input. (0.00%~100.00%)
F03.44 Corresponding SVC 0.00%
RUN
(0x032C) Lower limit value Set corresponding Lower limit value. (-250.00%~300.00%)
F03.45 Upper limit SVC 100.00%
RUN
(0x032D) torque input Set upper limit torque input. (0.00%~100.00%)

F03.46 Corresponding SVC 100.00%


RUN
(0x032E) upper limit value Set corresponding upper limit value. (-250.00%~300.00%)

F03.47 Filter time of SVC 0.100s


RUN
(0x032F) torque Set filter time of torque. (0.000s~6.000s)

F03.52 Upper limit SVC 150.0%


RUN
(0x0334) torque command Set upper limit output torque. (0.0%~300.0%)
F03.53 Lower limit SVC 0.0%
RUN
(0x0335) torque command Set lower limit output torque. (0.0%~300.0%)
SVC
0: set via code F03.56;
1: value from external keyboard potentiometer ×
F03.56;
Torque
2:AS×F03.56;
F03.54 controlling 0
3:VS×F03.56; RUN
(0x0336) forward speed (0~8)
4: reserved;
limit selection
5:reserved;
6: value from RS485 communication port×F03.56;
7:reserved;
8: reserved;
SVC
0: set via code F03.57;;
1: value from external keyboard potentiometer ×
F03.57;
Torque
2:AS×F03.57;
F03.55 controlling 0
3:VS×F03.57; RUN
(0x0337) reverse speed (0~8)
4: reserved;
limit selection
5: reserved;
6: value from RS485 communication port×F03.57;
7: reserved;
8: reserved;
Torque
F03.56 controlling SVC 100.0%
RUN
(0x0338) maximum Set torque controlling maximum forward speed (0.0%~100.0%)
forward speed
Torque
F03.57 controlling SVC 100.0%
RUN
(0x0339) maximum reverse Set torque controlling maximum reverse speed (0.0%~100.0%)
speed
Torque gain
F03.58 SVC 1.00Hz
switching RUN
(0x033A) Set torque gain switching frequency. (0.00Hz~50.00Hz)
frequency
F03.59 SVC 100.0%
Torque gain RUN
(0x033B) Set torque gain (0.0%~500.0%)

Table 4-19 F03.4x~F03.5x group

24
AC01-Series network inverter manual Function List

4.8 F04 Group: V/F Control


F04.0x group: V/F control
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F
Used to select the type of V/F curve to meet the
requirements of different load characteristics.
F04.00 Linear V/F curve 0: straight V/F curve; 0
STOP
(0x0400) selection 1-9: V/F curves to the powers of 1.1 to 1.9; (0~11)
10: V/F curve squared;
11: self-defined V/F curve;
V/F
F04.01 机型确定
Torque boost 0.0%: automatic torque boost RUN
(0x0401) (0.0%~30.0%)
0.1%~30.0%: manual torque boost
V/F
F04.02 Torque boost cut-off Set the effective range of the torque boost so when 100.0%
RUN
(0x0402) frequency the output frequency exceeds this value, the torque (0.0%~100.0%)
boost will be cut off.
F04.03 Slip compensation V/F 0.0%
RUN
(0x0403) gain Set slip compensation gain (0.0%~200.0%)
F04.04 Slip compensation V/F 100.0%
RUN
(0x0404) limit Set slip compensation limit (0.0%~300.0%)
V/F
The slip compensation function requires correct
F04.05 Slip compensation 0.200s
input of parameters on the motor nameplate to start RUN
(0x0405) filter time (0.000s~6.000s)
parameter learning and then deliver the best
performance.
V/F
F04.06 Oscillation By adjusting this value, the low frequency 100.0%
RUN
(0x0406) suppression gain resonance can be suppressed, but if it’s too large, (0.0%~900.0%)
additional stability problems will further occur.

Oscillation
F04.07 V/F 1.0s
suppression filter RUN
(0x0407) Set oscillation suppression filter time (0.0s~100.0s)
time
F04.08 Output voltage V/F 100.0%
STOP
(0x0408) percentage Set output voltage percentage (25.0%~120.0%)

Table 4-20 F04.0x group

F04.1x group: self-defined V/F curve


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F04.10 V/F 3.0%
Self-set voltage V1 STOP
(0x040A) Set the value of self-set voltage V1 (0.0%~100.0%)
1.00Hz
F04.11 V/F
Self-set frequency F1 (0.00Hz ~ STOP
(0x040B) Set the value of self-set frequency F1
maximum frequency)
F04.12 V/F 28.0%
Self-set voltage V2 STOP
(0x040C) Set the value of self-set voltage V2 (0.0% ~100.0%)
10.00Hz
F04.13 V/F
Self-set frequency F2 (0.00Hz~ STOP
(0x040D) Set the value of self-set frequency F2
maximum frequency)
55.0%
F04.14 V/F
Self-set voltage V3 (0.0%~ STOP
(0x040E) Set the value of self-set voltage V3
100.0%)

25
Function List AC01-Series network inverter manual

25.00Hz
F04.15 V/F
Self-set frequency F3 (0.00Hz~ STOP
(0x040F) Set the value of self-set frequency F3
maximum frequency)
F04.16 V/F 78.0%
Self-set voltage V4 STOP
(0x0410) Set the value of self-set voltage V4 (0.0%~100.0%)
37.50Hz
F04.17 V/F
Self-set frequency F4 (0.00Hz~ STOP
(0x0411) Set the value of self-set frequency F4
maximum frequency)
F04.18 V/F 100.0%
Self-set voltage V5 STOP
(0x0412) Set the value of self-set voltage V5 (0.0%~100.0%)
50.00Hz
F04.19 V/F
Self-set frequency F5 (0.00Hz~ STOP
(0x0413) Set the value of self-set frequency F5
maximum frequency)

Table 4-21 F04.1x group

F04.2x group: reserved

F04.3x group: V/F energy-saving control


Parameter Factory default Adjustable
code Designation Content
(setting range) attribute
(Address) V/F
F04.30 Automatic energy 0
0: off STOP
(0x041E) saving control (0~1)
1: on
V/F
F04.31 Lower limit 15.0Hz
Set lower limit step-down frequency STOP
(0x041F) step-down frequency (0.0Hz~50.0Hz)
of energy-saving
V/F
F04.32 Lower limit 50.0%
Set lower limit step-down voltage of STOP
(0x0420) step-down voltage (20.0%~100.0%)
energy-saving
V/F
F04.33 Regulation rate of 0.010 V/ms
Set regulation rate of step-down RUN
(0x0421) step-down voltage (0.000 V/ms ~ 0.200 V/ms)
voltage of energy-saving
V/F 0.200 V/ms
F04.34 Recovery rate of
Set recovery rate of step-down (0.000 V/ms~ RUN
(0x0422) step-down voltage
voltage of energy-saving 2.000 V/ms)

Table 4-22 F04.3x group

4.9 F05 Group: Input Terminal


F05.0x group: setting terminal function via number entering

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F05.00 Terminal X1 V/F SVC 1
STOP
(0x0500) function selection See the functions of terminal X for details (0~95)
F05.01 Terminal X2 V/F SVC 2
STOP
(0x0501) function selection See the functions of terminal X for details (0~95)
F05.02 Terminal X3 V/F SVC 4
STOP
(0x0502) function selection See the functions of terminal X for details (0~95)

Table 4-23 F05.0x group

26
AC01-Series network inverter manual Function List

F05.1x group:X1~X3 delay detection

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F05.10 X1 detected effective 0.010s
The delay time of transition of terminal X1 from RUN
(0x050A) delay (0.000s~6.000s)
the invalid state to the valid state

F05.11 X1 detected V/F SVC 0.010s


The delay time of the transition of terminal X1 RUN
(0x050B) ineffective delay (0.000s~6.000s)
from a valid state to an invalid state
V/F SVC
F05.12 X2 detected effective 0.010s
The delay time of transition of terminal X2 from RUN
(0x050C) delay (0.000s~6.000s)
the invalid state to the valid state
V/F SVC
F05.13 X2 detected 0.010s
The delay time of the transition of terminal X2 RUN
(0x050D) ineffective delay (0.000s~6.000s)
from a valid state to an invalid state
V/F SVC
F05.14 X3 detected effective 0.010s
The delay time of transition of terminal X1 from RUN
(0x050E) delay (0.000s~6.000s)
the invalid state to the valid state
V/F SVC
F05.15 X3 detected 0.010s
The delay time of the transition of terminal X3from RUN
(0x050F) ineffective delay (0.000s~6.000s)
a valid state to an invalid state
Table 4-24 F05.1x group

F05.2x group: Terminal action selection via number entering


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
0: two-wire system 1
F05.20 Terminal controlling 0
1: two-wire system 2 STOP
(0x0514) running mode (0~3)
2: three-wire system 1
3: three-wire system 2
V/F SVC
0: valid when connected
X1~X3 terminal 1: valid when disconnected
F05.22 0000
characteristic LED ones-place: X1 terminal RUN
(0x0516) (0000~1111)
selection LED tens-place: X2 terminal
LED hundreds -place: X3 terminal
LED thousands-place: reserved
V/F SVC
F05.25 UP/DW terminal 0: power-off frequency storage 0
STOP
(0x0519) control selection 1: no power-off frequency storage (0~2)
2: adjustable in operation and clear all at stop
UP/DW terminal
V/F SVC
F05.26 controlling increase 0.50Hz/s
Set UP/DW terminal controlling increase & RUN
(0x051A) & decrease rate of (0.01Hz/s~50.00Hz/s)
decrease rate of frequency
frequency
Terminal emergency V/F SVC
F05.27 1.00s
stop deceleration Set emergency stop deceleration time g for the RUN
(0x051B) (0.01s~650.00s)
time terminal

Table 4-25 F05.2x group

27
Function List AC01-Series network inverter manual

F05.3x group: reserved

F05.4x group: analog type processing


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

LED ones-place: AS
V/F SVC
LED tens-place: VS
0: straight line
F05.43 Analog input curve LED hundreds- place: 0000
(default) RUN
(0x052B) selection reserved (0000~2222)
1: curve-1
LED thousands-place:
2: curve 2
reserved

Table 4-26 F05.4x group

F05.5x group: analog linear processing

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

V/F SVC
F05.50 Define the signal received by the AS terminal, 0.0%
Lower limitAS RUN
(0x0532) and the voltage signal below this value is (0.0%~100.0%)
processed as the lower limit.
Setting R
F05.51 V/F SVC++ 0.00%
corresponding to
(0x0533) Set percentage for the setAS lower limit value. (-100.00%~100.00%)
lower limitAS
V/F SVC
F05.52 Define the signal received by the AS terminal, 100.0% UN
Upper limit AS RUN
(0x0534) and the voltage signal above this value is (0.0%~100.0%)
processed as the upper limit.
Setting
F05.53 V/F SVC 100.00%
corresponding to RUN
(0x0535) Set percentage for the setAS upper limit value. (0.00%~100.00%)
upper limitAS
F05.54 V/F SVC 0.100s
AS filter time Define the size of the AS circuit analog signal RUN
(0x0536) (0.000s~6.000s)
filtering to eliminate interference signals.
V/F SVC
F05.55 Define the signal received by the VS terminal, 0.0%
Lower limit VS RUN
(0x0537) and the voltage signal below this value is (0.0%~100.0%)
processed as the lower limit.
Setting
F05.56 V/F SVC 0.00%
corresponding to RUN
(0x0538) Set percentage for the set VS lower limit value. (-100.00%~100.00%)
lower limit VS
V/F SVC
F05.57 Define the signal received by the VS terminal, 100.0%
Upper limit VS RUN
(0x0539) and the voltage signal above this value is (0.0%~100.0%)
processed as the upper limit.
Setting
F05.58 V/F SVC 100.00%
corresponding to RUN
(0x053A) Set percentage for the setAS upper limit value. (0.00%~100.00%)
upper limit VS
V/F SVC
F05.59 0.100s
VS filter time Define the size of the VS circuit analog signal RUN
(0x053B) (0.000s~6.000s)
filtering to eliminate interference signals.

Table 4-27 F05.5x group

28
AC01-Series network inverter manual Function List

F05.6x group: analog quantity curve-1

Parameter Adjustab
Factory default
code Designation Content le
(setting range)
(Address) attribute
F05.60 V/F SVC 0.0%
Curve-1 lower limit RUN
(0x053C) Set lower limit value for curve-1. (0.0%~100.0%)
Setting
F05.61 V/F SVC 0.00%
corresponding to RUN
(0x053D) Set percentage of lower limit value for curve-1. (-100.00%~100.00%)
curve-1 lower limit
Input voltage on
F05.62 V/F SVC 30.0%
inflection point-1 of RUN
(0x053E) Set input voltage on inflection point-1 of curve-1. (0.0%~100.0%)
curve-1
Setting V/F SVC
F05.63 30.00%
corresponding to Set percentage of input voltage on inflection point-1 of RUN
(0x053F) (-100.00%~100.00%)
F05.62 curve-1.
Input voltage on
F05.64 V/F SVC 60.0%
inflection point 2 of RUN
(0x0540) Set input voltage on inflection point 2 of curve-1. (0.0%~100.0%)
curve-1
Setting V/F SVC
F05.65 60.00%
corresponding to Set percentage of input voltage on inflection point 2 of RUN
(0x0541) (-100.00%~100.00%)
F05.64 curve-1.
F05.66 V/F SVC 100.0%
Curve-1 upper limit RUN
(0x0542) Set upper value for curve-1. (0.0%~100.0%)

Setting
F05.67 V/F SVC 100.00%
corresponding to RUN
(0x0543) Set percentage of upper limit value for curve-1. (-100.00%~100.00%)
curve-1 upper limit

Table 4-28 F05.6x group

F05.7x group: analog quantity curve 2

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F05.70 V/F SVC 0.0%
Curve-2 lower limit RUN
(0x0546) Set lower limit value for curve-2. (0.0%~100.0%)
Setting
F05.71 V/F SVC 0.00%
corresponding to RUN
(0x0547) Set percentage of lower limit value for curve-2. (-100.00%~100.00%)
curve-2 lower limit
Input voltage on V/F SVC
F05.72 30.0%
inflection point-1 of Set input voltage on inflection point-1 of RUN
(0x0548) (0.0%~100.0%)
curve-2 curve-2.
Setting V/F SVC
F05.73 30.00%
corresponding to Set percentage of input voltage on inflection RUN
(0x0549) (-100.00%~100.00%)
F05.72 point-1 of curve-2.
Input voltage on V/F SVC
F05.74 60.0%
inflection point-2 of Set input voltage on inflection point-2 of RUN
(0x054A) (0.0%~100.0%)
curve-2 curve-2.
Setting V/F SVC
F05.75 60.00%
corresponding to Set percentage of input voltage on inflection RUN
(0x054B) (-100.00%~100.00%)
F05.74 point-2 of curve-2.
F05.76 V/F SVC 100.0%
Curve-2 upper limit RUN
(0x054C) Set upper value for curve-2. (0.0%~100.0%)
Setting
F05.77 V/F SVC 100.00%
corresponding to RUN
(0x054D) Set percentage of upper limit value for curve-2. (-100.00%~100.00%)
curve-2 upper limit

Table 4-29 F05.7x group


29
Function List AC01-Series network inverter manual

F05.8x group: AS/VS as digital signal input terminal


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC LED tens-place: VS
Characteristic
0: effective for low level LED hundreds-place:
F05.80 selection ofAS/VS 0000
1: effective for high reserved RUN
(0x0550) as digital signal input (0000~1111)
level LED thousands-place:
terminal
LED ones-place: AS reserved
F05.81 AS terminal function V/F SVC 0
RUN
(0x0551) selection (used as X) See X terminal functions for details. (0~95)

V/F SVC
F05.82 70.00%
AS high-level setting It’s high level when AS input setting is greater than the RUN
(0x0552) (0.00%~100.00%)
high-level setting.

V/F SVC
F05.83 30.00%
AS low-level setting It’s low level when AS input setting is smaller than the RUN
(0x0553) (0.00%~100.00%)
low-level setting.
F05.84 VS terminal function V/F SVC 0
RUN
(0x0554) selection (used as X) See X terminal functions for details. (0~95)
V/F SVC
F05.85 70.00%
VS high-level setting It’s high level when VS input setting is greater than the RUN
(0x0555) (0.00%~100.00%)
high-level setting.
V/F SVC
F05.86 30.00%
VS low-level setting It’s low level when VS input setting is smaller than the RUN
(0x0556) (0.00%~100.00%)
low-level setting.

Table 4-30 F05.8x group

4.10 F06 Group: Output Terminal


F06.0x group: reserved

F06.1x group: reserved

F06.2x~F06.3x group: digital & relay output

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
Tens-place: relay output
V/F SVC
terminal
0: positive
F06.20 Output terminal Hundreds-place: 0000
1: negative RUN
(0x0614) polarity selection reserved (0000~1111)
LED ones-place: Y
Thousands-place:
terminal
reserved
F06.21 V/F SVC 1
Output terminal Y RUN
(0x0615) SeeY terminal functions for details. (0~63)
F06.22 Relay output V/F SVC 4
RUN
(0x0616) (TA-TB-TC) SeeY terminal functions for details. (0~63)
F06.25 Y output delayed V/F SVC 0.010s
RUN
(0x0619) start time Set delay time when Y terminal starts output. (0.000s~60.000s)
F06.26 Relay output delayed V/F SVC 0.010s
RUN
(0x061A) start time Set delay time when relay starts output. (0.000s~60.000s)
F06.29 Y output delayed V/F SVC 0.010s
RUN
(0x061D) stop time Set delay time when Y terminal stops output. (0.000s~60.000s)

F06.30 Relay output delayed V/F SVC 0.010s


RUN
(0x061E) stop time Set delay time when relay stops output. (0.000s~60.000s)

30
AC01-Series network inverter manual Function List

Table 4-31 F06.2x~F06.3x group

F06.4x group: frequency detection


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F06.40 Frequency detection V/F SVC 2.00Hz
RUN
(0x0628) value 1 Set frequency detection value 1. (0.00Hz ~ maximum)

F06.41 Frequency detection V/F SVC 1.00Hz


RUN
(0x0629) amplitude 1 Set frequency detection amplitude 1. (0.00Hz ~ maximum

F06.42 Frequency detection V/F SVC 2.00Hz


RUN
(0x062A) value 2 Set frequency detection value 2. (0.00Hz ~ maximum)
F06.43 Frequency detection V/F SVC 1.00Hz
RUN
(0x062B) amplitude 2 Set frequency detection amplitude 2. (0.00Hz ~ maximum)
F06.44 Detection amplitude V/F SVC 2.00Hz
RUN
(0x062C) of set frequency Set detection amplitude for set frequency. (0.00Hz ~ maximum)

Table 4-32 F06.4x group

F06.5x group: comparator output of monitored parameter

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

V/F SVC
LED ones-& tens-place: set “yy” between 00~63
F06.50 Comparator 1 0001
among monitoring parameter “Cxx.yy”; RUN
(0x0632) monitoring selection (0000~0763)
LED hundreds-&thousands-place: set “xx” between
00~07 among monitoring parameter “Cxx.yy”;
F06.51 Upper limit of V/F SVC
(up to F06.50) RUN
(0x0633) comparator 1 Set upper limit value of comparator 1.
F06.52 Lower limit of V/F SVC
(up to F06.50) RUN
(0x0634) comparator 1 Set lower limit value of comparator 1.
F06.53 V/F SVC
Comparator 1 bias (up to F06.50) RUN
(0x0635) Set comparator 1 bias.
V/F SVC
Action selection of 0: go on running (digital terminal output only)
F06.54 0
sending comparator 1: display warning and stop freely RUN
(0x0636) (0~3)
1 2: display warning and go on running
3: forced stop
V/F SVC
LED ones-& tens-place: set “yy” between 00~63
F06.55 Comparator 2 0002
among monitoring parameter “Cxx.yy”; RUN
(0x0637) monitoring selection (0000~0763)
LED hundreds-&thousands-place: set “xx” between
00~07 among monitoring parameter “Cxx.yy”;
F06.56 Upper limit of V/F SVC
(up to F06.55) RUN
(0x0638) comparator 2 Set upper limit value of comparator 2.
F06.57 Lower limit of V/F SVC
(up to F06.55) RUN
(0x0639) comparator 2 Set lower limit value of comparator 2.
F06.58 V/F SVC
Comparator 2 bias (up to F06.55) RUN
(0x063A) Set comparator 2 bias.
V/F SVC
Action selection of 0: go on running (digital terminal output only)
F06.59 0
sending comparator 1: display warning and stop freely RUN
(0x063B) (0~3)
2 2: display warning and go on running
3: forced stop

31
Function List AC01-Series network inverter manual

Table 4-33 F06.5x group

F06.6x ~ F06.7x group: virtual input & output terminals

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

F06.60
(0x063C) Function selection of
V/F SVC 0
~ virtual vX1~vX3 STOP
See X terminal functions for details. (0~95)
F06.63 terminals
(0x063F)
V/F SVC
0: interconnect with the Ones-place: vX1
virtual vYn terminal; Tens-place: vX2
F06.64 State source of vX 0000
1: connect to the physical Hundreds-place: vX3 RUN
(0x0640) terminal (0000~0222)
terminal Xn Thousands-place:
2: function code valid or reserved
not
V/F SVC Tens-place: vX2
Virtual vX terminal
F06.65 0: invalid; Hundreds-place: vX3 0000
function code status RUN
(0x0641) 1: valid; Thousands-place: (0000~0111)
setting
Ones-place: vX1 reserved
F06.66
(0x0642)
Output selection of
~ V/F SVC 0
virtual vY1~vY3 RUN
F06.69 SeeY terminal functions for details. (0~63)
terminals
(0x0645)
F06.69
(0x0645)
F06.70
(0x0646)
vY1~ vY3 output V/F SVC 0.010s
~ RUN
delayed start time Set delay time when vY1~ vY3 starts output. (0.000s~60.000s)
F06.73
(0x0649)
F06.74
(0x064A)
vY1~ vY3 output V/F SVC 0.010s
~ RUN
delayed stop time Set delay time when vY1~ vY3 stops output. (0.000s~60.000s)
F06.77
(0x064D)

Table 4-34 F06.6x ~F06.7x group

4.11 F07 Group: Running Control


F07.0x group: start control

Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
F07.00 0: started by the starting frequency 0
Start method STOP
(0x0700) 1: DC braking before started by the starting frequency (0~2)
2: speed tracking & direction judgment and then start

V/F SVC
F07.01 Start pre-excitation Only asynchronous motor vector control without PG 0.00s
STOP
(0x0701) time supports pre-excitation, so ignore this code on other (0.00s~60.00s)
motors.

32
AC01-Series network inverter manual Function List

0.50Hz
V/F SVC (0.00Hz~upper
F07.02
Start frequency Remain stop and standby when set frequency is lower limit frequency STOP
(0x0702)
than start frequency. via number
entering)
V/F SVC
0: off
1: on
LED ones-place: terminal protection activated on exit
exception
Tens-place: jogging terminal protection activated exit
F07.03 Start protection 0111
exception STOP
(0x0703) selection (0000~1111)
Hundreds-place: terminal protection activated when the
command channel switches to the terminal
Thousands-place: reserved
Note: When the free stop, emergency stop and forced
stop commands are valid, the terminal protection is
enabled by default.
1:forward command only
V/F SVC
2: reverse command only
LED ones-place:
Hundreds-place: frequency
rotation direction
controlling command
0: remain;
direction:
1: reverse the direction;
0: controlling command
F07.05 Rotation direction Tens-place: rotation 0000
direction invalid STOP
(0x0705) selection direction permission: (0000~1121)
1: controlling command
0: forward and reverse
direction valid
commands allowed
Thousands-place: reserved
Note: Initialization will not restore this value.
Parameter downloading will not change the ones digit
value.
V/F SVC
F07.06 Restart after power 0: invalid 0
STOP
(0x0706) failure selection 1: speed tracking and restart (0~2)
2: restart as the start mode.
F07.07 Restart waiting time V/F SVC 0.50s
STOP
(0x0707) after power cut. Set the waiting time to restart after power cut. (0.00s~60.00s)

Table 4-35 F07.0x group

F07.1x group: stop control


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F07.10 0
Stop method 0: deceleration stop RUN
(0x070A) (0~1)
1: free stop
0.50Hz
V/F SVC
F07.11 Stop detection (0.00Hz~
Stop when inverter output frequency is lower than this RUN
(0x070B) frequency upper limit via
value under deceleration stop.
number entering)
F07.12 Limit time to restart V/F SVC 0.000s
STOP
(0x070C) after stop Set waiting time to restart after stop. (0.000s~60.000s)
V/F SVC
action selection 0: run by frequency command
F07.15 2
when lower than 1: stop freely and remains pause RUN
(0x070F) (0~3)
minimum frequency 2: run at the minimum frequency
3: run at zero speed
F07.16 Torque holding V/F SVC 60.0% RUN

33
Function List AC01-Series network inverter manual

(0x0710) current at zero speed Set torque holding current at zero speed, 100.0% of (0.0%~150.0%)
rated current of the inverter.
F07.17 Torque holding time V/F SVC 0.0s
RUN
(0x0711) at zero speed Set Torque holding time at zero speed. (0.0s~6000.0s)
V/F SVC
F07.18 Forward & reverse 0.0s
Zero frequency holding time during forward & reverse STOP
(0x0712) rotation dead time (0.0s~120.0s)
switching.

Table 4-36 F07.1x group

F07.2x group: DC braking and speed tracking


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F07.20 Braking current 100.0% of the motor rated current, and the upper limit 60.0%
STOP
(0x0714) before starting of the braking current is the rated current of the (0.0%~150.0%)
inverter.
F07.21 Braking time before V/F SVC 0.0s
STOP
(0x0715) starting Set braking time before starting (0.0s~60.0s)
F07.22 DC braking start V/F SVC 1.00Hz
STOP
(0x0716) frequency Set DC braking start frequency (0.00Hz~50.00Hz)
V/F SVC
F07.23 The reference is the rated current of the inverter, and 60.0%
DC braking current STOP
(0x0717) the internal limit shall not exceed the rated current of (0.0%~150.0%)
the motor.
F07.24 DC braking time of V/F SVC 0.0s
STOP
(0x0718) stop Set DC braking time in stop state. (0.0s~60.0s)
V/F SVC
1: on
Ones-place: tracking mode
Hundreds-place:
0: tracking from the
tracking source
F07.25 maximum frequency; 0000
Speed tracking 0: software tracking; STOP
(0x0719) 1: tracking from stop (0000~1111)
1: hardware tracking;
frequency;
Thousands-place:
Tens-place: reverse tracking
reserved
0: off
F07.26 V/F SVC 0.50s
Speed tracking time STOP
(0x071A) Set speed tracking time (0.00s~60.00s)
F07.27 Speed tracking stop V/F SVC 1.00s
STOP
(0x071B) delay time Set delay time when speed tracking stops. (0.00s~60.00s)
F07.28 Speed tracking V/F SVC 120.0%
STOP
(0x071C) current Set speed tracking current. (0.0%~400.0%)

Table 4-37 F07.2x group

F07.3x group: jogging


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
F07.30 V/F SVC 5.00Hz
Jogging frequency RUN
(0x071E) Set running frequency of jogging. (0.00Hz~maximum frequency)
F07.31 Jogging acceleration V/F SVC 10.00s
RUN
(0x071F) time Set jogging acceleration time. (0.00s~650.00s)
F07.32 Jogging deceleration V/F SVC 10.00s
RUN
(0x0720) time Set jogging deceleration time. (0.00s~650.00s)
V/F SVC
F07.33 Jogging S-curve 1
0: invalid RUN
(0x0721) selection (0~1)
1: valid

34
AC01-Series network inverter manual Function List

V/F SVC
F07.34 0
Jogging stop mode 0: stop as F7.10 setting; RUN
(0x0722) (0~1)
1: decelerate and stop

Table 4-38 F07.3x group

F07.4x group: start & stop holding frequency and hopping frequency
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC 0.50Hz
F07.40 Start holding Start holding frequency is higher than the start (0.00Hz~upper limit
STOP
(0x0728) frequency frequency and lower than the upper limit frequency frequency via number
via number entering. entering)
V/F SVC
F07.41 Start holding This shall be higher than the starting frequency, and 0.00s
STOP
(0x0729) frequency time the starting frequency should be taken when it is (0.00s~60.00s)
lower than it.
0.50Hz
F07.42 Stop holding V/F SVC (0.00Hz~ upper limit
STOP
(0x072A) frequency Set stop holding frequency. frequency via number
entering))
V/F SVC
Stop holding frequency time is invalid when
 terminal DC braking and jogging;
 stop DC braking is effective while the stop
F07.43 Stop holding 0.00s
holding frequency is lower than stop DC STOP
(0x072B) frequency time (0.00s~60.00s)
braking frequency;
 no stop DC braking and the stop holding
frequency is lower than the stop detection
frequency
0.00Hz
F07.44 V/F SVC
Hopping frequency 1 (0.00 Hz ~ RUN
(0x072C) Set hopping frequency 1.
maximum frequency)
0.00Hz
F07.45 Hopping frequency V/F SVC
(0.00Hz~ RUN
(0x072D) amplitude Set hopping frequency1 amplitude.
maximum frequency)
0.00Hz
F07.46 V/F SVC
Hopping frequency 2 (0.00Hz~ RUN
(0x072E) Set hopping frequency 2.
maximum frequency)
0.00Hz
F07.47 Hopping frequency V/F SVC
(0.00Hz~ RUN
(0x072F) amplitude Set hopping frequency 2 amplitude.
maximum frequency
率)
Table 4-39 F07.4x group

4.12 F08 Group: Auxiliary Control 1


F08.0x group: counting and timing
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F08.00 1: reserved 0
Counter input source 0: from common X RUN
(0x0800) 2: reserved (0~2)
terminal
F08.01 Counter input V/F SVC 0
RUN
(0x0801) frequency division Set counter input frequency division (0~6000)

35
Function List AC01-Series network inverter manual

F08.02 V/F SVC 1000


Counter maximum RUN
(0x0802) Set counter maximum value. (0~65000)
F08.03 V/F SVC 500
Counter value RUN
(0x0803) Set counter value. (0~65000)
F08.04 V/F SVC 10.0
Pulses per meter RUN
(0x0804) Set pulses per meter. (0.1~6553.5)
V/F SVC
F08.05 Set a length, when the actual length is greater than 1000m
Length STOP
(0x0805) or equal to setting length, the terminal will output a (0m~65535m)
valid signal, then reset after the output
F08.06 V/F SVC 0m
Actual length STOP
(0x0806) No power-off saving. (0m~65535m)
F08.07 V/F SVC 1: minute (m) 0
Timer time unit STOP
(0x0807) 0: second (s) 2: hour (h) (0~2)
F08.08 V/F SVC 0
Timer value STOP
(0x0808) Set timer value. (0~65000)

Table 4-40 F08.0x group

F08.1x ~ F08.2x group: reserved

F08.3x group: swing frequency


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F08.30 0
Swing frequency 0: swing frequency invalid STOP
(0x081E) (0~1)
1: swing frequency valid
V/F SVC 1: refer to maximum
Ones-place: start mode frequency
0: auto; Hundreds-place: preset
F08.31 Swing frequency 0000
1: manual terminal setting frequency STOP
(0x081F) amplitude (0000~0111)
Tens-place: amplitude 0: unenabled
control 1: enabled
0: refer to center frequency Thousands-place: reserved
0.00Hz
F08.32 Preset swing V/F SVC (0.00Hz ~
STOP
(0x0820) frequency Set preset swing frequency. maximum
frequency)
Preset swing
F08.33 V/F SVC 0.0s
frequency waiting STOP
(0x0821) Set preset swing frequency waiting time. (0.0s~3600.0s)
time
F08.34 Swing frequency V/F SVC 10.0%
STOP
(0x0822) amplitude value Set swing frequency amplitude value. (0.0%~50.0%)
F08.35 V/F SVC 10.0%
Hopping frequency STOP
(0x0823) Set hopping frequency. (0.0%~50.0%)
F08.36 Triangular wave rise V/F SVC 5.00s
STOP
(0x0824) time Set triangular wave rise time. (0.00s~650.00s)
F08.37 Triangular wave fall V/F SVC 5.00s
STOP
(0x0825) time Set triangular wave fall time. (0.00s~650.00s)

Table 4-41 F08.3x group

4.13 F09 Group: Auxiliary Control 2


F09.0x group: maintenance

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

36
AC01-Series network inverter manual Function List

V/F SVC
Ones-place: cooling fan
0: invalid; 1: valid
F09.02 Device maintenance 0x0000
Tens-place: main relay RUN
(0x0902) warning selection (0x0000~0x1111)
0: invalid; 1: valid
Hundreds-place: reserved
Thousands-place: reserved
F09.03 Cooling fan V/F SVC 0
Set this parameter in hours and set it to 0 after replacing STOP
(0x0903) maintenance (0~65535)
with a new one.
F09.04 Main relay V/F SVC 0.0%
STOP
(0x0904) maintenance Set this parameter to 0.0% after replacing with a new relay. (0.0%~150.0%)

Table 4-42 F09.0x group

4.14 F10 Group: Protection Parameter


F10.0x group: current protection
Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Automatically limited output current shall not exceed
the set overcurrent suppression point to prevent
F10.00 Overcurrent 0
overcurrent fault triggered by excessive current. RUN
(0x0A00) suppression (0~1)
0: suppression always valid;
1: valid during acceleration & deceleration, while
invalid during constant speed

V/F SVC
F10.01 Overcurrent 160.0%
Set the load current limiting level, 100% of rated RUN
(0x0A01) suppression point (0.0%~300.0%)
motor current.

F10.02 Overcurrent V/F SVC 100.0%


RUN
(0x0A02) suppression gain Set the response effect of overcurrent suppression. (0.0%~500.0%)
V/F SVC
Set whether the current-related protection is activated:
Ones-place: current limiting by wave (CBC)
0: off
1: on
Tens-place: OC protection interference suppression
0: normal
F10.03 Current protection 0001
1: primary interference suppression STOP
(0x0A03) setting 1 (0000~F221)
2: secondary interference suppression
Hundreds-place: SC protection interference
suppression
0: normal
1: primary interference suppression
2: secondary interference suppression
LED thousands-place: reserved
V/F SVC
Ones-place: three-phase current and protection
selection
F10.04 Current protection 0001
0: off ; 1: on STOP
(0x0A04) setting 2 (0000~0011)
Tens-place: three-phase current unbalance protection,
fault code E. oLF4.
0: off; 1: on
V/F SVC
F10.05 Current imbalance The ratio of the maximum to the minimum phase in 160%
STOP
(0x0A05) threshold the three phases of the current, and the set value is (0%~500%)
compared to tell if it’s current imbalance fault.

37
Function List AC01-Series network inverter manual

V/F SVC
F10.06 Current imbalance 2.0
Increase this parameter on occasions with great current STOP
(0x0A06) filtering coefficient (0.0~60.0)
fluctuation.

Table 4-43 F10.0x group

F10.1x group: voltage protection


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
When the bus voltage is greater than the overvoltage
suppression point, the acceleration and deceleration
will be slowed down or stopped to prevent the
F10.11 Bus overvoltage overvoltage fault. 0011
STOP
(0x0A0B) suppression Ones-place: overvoltage suppression (0000~0021)
0: off; 1: on
Tens-place: overexcitation
0: off; 1: enabled during deceleration; 2: enabled
during running;
T3:750V
V/F SVC
S2:370V
Set the bus voltage value for triggering the overvoltage
F10.12 Bus overvoltage (T3:650V~800V
suppression function STOP
(0x0A0C) suppression point S2:340V~380V)
Note: T3 overpressure point :820V(750V~840V)
Also limited by
S2 overpressure point :400V(360V~410V)
overvoltage point
F10.13 Bus overvoltage V/F SVC 100.0%
RUN
(0x0A0D) suppression gain Set the response effect of overvoltage suppression。 (0.0%~500.0%)
V/F SVC
Set dynamic braking on or off;
F10.14 2
Dynamic braking 0: off; RUN
(0x0A0E) (0~2)
1: on with the overvoltage suppression off;
2: on wth the overvoltage suppression on;
V/F SVC T3:740V
Set the dynamic braking action voltage. When the bus S2:360V
F10.15 Dynamic braking voltage is greater than this value, this function starts to (T3:650V~800V
RUN
(0x0A0F) action voltage act. S2:350V~390V)
Note: T3 overpressure point :820V(750V~840V) Also limited by
S2 overpressure point :400V(360V~410V) overvoltage point
V/F SVC
When the bus voltage is lower than the undervoltage
F10.16 Bus undervoltage suppression point, the operating frequency will be 0
STOP
(0x0A10) suppression automatically adjusted to stop the bus voltage reduction (0~1)
to prevent undervoltage fault reporting
0: off; 1: on

T3:430
V/F SVC
S2:240
Set the bus voltage value to trigger the undervoltage
F10.17 Bus undervoltage (T3:350V~450V
suppression function. STOP
(0x0A11) suppression point S2:180V~260V)
Note: T3 overpressure point :820V(750V~840V)
Also limited by
S2 overpressure point :400V(360V~410V)
overvoltage point

F10.18 Busbar undervoltage V/F SVC 100.0%


RUN
(0x0A12) suppression gain Set the response effect of undervoltage suppression. (0.0%~500.0%)

38
AC01-Series network inverter manual Function List

T3:320V
V/F SVC
S2:190V
Set the allowable lower limit of busbar voltage, below
F10.19 Busbar undervoltage (T3:300V~400V
which inverter will report undervoltage fault. STOP
(0x0A13) protection point S2:160V~240V)
Note :T3 overpressure point :820V(750V~840V)
Also limited by
S2 overpressure point :400V(360V~410V)
overvoltage point

Table 4-44 F10.1x group

F10.2x group: auxiliary protection


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
Set input & output phase loss protection on or off.
Ones-place: output phase loss protection
0: off;
1: on;
Tens-place: input phase loss protection
F10.20 Input & output phase 0021
0: off; STOP
(0x0A14) loss protection (0000~1121)
1:on , report A. iLF warning when phase loss
detected but go on running;
2:on , report A. iLF warning when phase loss
detected and stop freely.
Hundreds-place; reserved;
Thousands-place: reserved;
V/F SVC
F10.21 Input phase loss 10.0%
Set percentage of the input phase loss detected STOP
(0x0A15) threshold value (0.0%~30.0%)
voltage, 100% of the rated bus voltage.
V/F SVC
Set inverter output & cooling fan grounding short
circuit protection on or off;
Ones-place: Output grounding short circuit
protection:
F10.22 Grounding short 0: off; 1: on; 11
STOP
(0x0A16) circuit protection Tens-place: Cooling fan grounding short circuit (00~12)
protection:
0: off; 1: on;
Hundreds-place; reserved;
Thousands-place: reserved;
Set the operation mode of the cooling fan
0: fan runs after the inverter is powered on
F10.23 1
Cooling fan 1: fan runs or not up to temperature after shutdown; RUN
(0x0A17) (0~2)
2: fan stops after the set time of F10.24 during
shutdown, and runs or not up to temperature then.
V/F SVC
F10.24 Delay time of cooling 30.00s
Set the time from release of the running command STOP
(0x0A18) fan (0.00s~600.00s)
to the cooling fan stops running
V/F SVC
Inverter overheating 80.0℃
F10.25 Set the temperature of overheat warning of the
oH1 warning (0.0℃ RUN
(0x0A19) inverter, any value detected larger will cause
detection level ~100.0℃)
overheating warning.

Table 4-45 F10.2x group

39
Function List AC01-Series network inverter manual

F10.3x group: load protection


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
Set load detection mode and the corresponding
warning mode
Ones-place: load detection warning 1 setting
0: detection off;
1: excessive load;
2: excessive load only at constant speed;
3: insufficient load;
4: insufficient load only at constant speed;
Tens-place: warning mode of load detection
warning 1
F10.32 Load detection 0000
0: go on running,reportA. Ld1 STOP
(0x0A20) warning (0000~1414)
1: stop freely,report E. Ld1
Hundreds-place: load detection warning 2 setting
0: detection off;
1: excessive load;
2: excessive load only at constant speed;
3: insufficient load;
4: insufficient load only at constant speed;
Thousands-place: warning mode of load detection
warning 2
0: go on running,reportA. Ld2
1: stop freely,report E. Ld2
V/F SVC
Set the detectable value of load warning 1;
F10.33 Load warning For V/F control, the value equals to 100% of the 130.0%
STOP
(0x0A21) detection level 1 rated current of the motor; (0.0%~200.0%)
For vector control, the value equals to 100% of the
rated output torque of the motor
V/F SVC
F10.34 Load warning Set the duration of load detection warning 1. If the 5.0s
STOP
(0x0A22) detection time 1 load is greater than the load warning detection level, (0.0s~60.0s)
load detection warning 1 functions.
V/F SVC
Set the detectable value of load warning 2;
F10.35 Load warning For V/F control, the value equals to 100% of the 30.0%
STOP
(0x0A23) detection level 2 rated current of the motor; (0.0%~200.0%)
For vector control, the value equals to 100% of the
rated output torque of the motor

V/F SVC
F10.36 Load warning Set the duration of load detection warning 2. If the 5.0s
STOP
(0x0A24) detection time 2 load is greater than the load warning detection level, (0.0s~60.0s)
load detection warning 2 functions.

Table 4-46 F10.3x group

F10.4x group: stall protection


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
F10.40 Excessive speed 00
Set the detection mode and warning mode when the STOP
(0x0A28) deviation protection (00~12)
deviation between the given motor speed and the

40
AC01-Series network inverter manual Function List

feedback speed is too large


Ones-place: detection mode selection
0: detection off;
1: on at constant speed only;
2: on;
Tens-place: warning mode
0: stop freely and report warning;
1: report warning and go on running

Excessive speed V/F SVC


F10.41 10.0%
deviation detection Set the detectable value with excessive speed STOP
(0x0A29) (0.0%~60.0%)
threshold value deviation, 100% of F01.10[maximum frequency]

V/F SVC
Excessive speed Set the duration of detecting speed deviation. If the
F10.42 2.0s
deviation detection given speed & feedback speed deviation is greater STOP
(0x0A2A) (0.0s~60.0s)
time than F10.41 and lasts for this setting, report
excessive speed deviation warning.
V/F SVC
Set detection mode and warning mode of motor
stall.
Ones-place: detection mode selection
F10.43 0: detection off; 02
Stall protection STOP
(0x0A2B) 1: on at constant speed only; (00~12)
2: on;
Tens-place: warning mode
0: stop freely and report warning;
1: report warning and go on running
Stall protection V/F SVC
F10.44 110.0%
detection threshold Set the detectable value of stall warning, which STOP
(0x0A2C) (0.0%~150.0%)
value corresponds 100% of F01.10[maximum frequency]
V/F SVC
F10.45 Stall protection Set the duration of stall detection. If feedback speed 0.100s
STOP
(0x0A2D) detection time deviation is greater than F10.44 and lasts for this (0.000s~2.000s)
setting, report stall warning.

Table 4-47 F10.4x group

F10.5x group: fault recovery protection and motor overload


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
F10.50 Times of Set the allowable times of self-recovery. 0
STOP
(0x0A32) self-recovery Note: 0 indicates that the fault self-recovery function (0~10)
is off. Otherwise, it’s on.
V/F SVC
F10.51 Interval between fault 1.0s
Set the waiting time between each inverter failure STOP
(0x0A33) self-recoveries (0.0s~100.0s)
and recovery.
V/F SVC
F10.52 Times of recovered
The times of self-recoveries that have been 0 STOP
(0x0A34) faults
performed. This parameter is read-only.
V/F SVC
0: common motor
F10.55 Motor overload 0
1: inverter motor (50Hz) RUN
(0x0A37) model (0~3)
2: inverter motor (60Hz)
3: motor without cooling fan

41
Function List AC01-Series network inverter manual

V/F SVC
F10.56 0: insulation levelA; 1: insulation level E 3
Motor insulation level STOP
(0x0A38) 2: Insulation level B; 3: insulation level F (0~5)
4: Insulation class H; 5: special level S
V/F SVC
F10.57 Motor working 0-1: S1 working system (continuous working) 0
STOP
(0x0A39) system 2: S2 working system (0~9)
3-9: corresponds to S3-S9

F10.58 Motor overload V/F SVC 105.0%


Set motor overload threshold. The actual current is STOP
(0x0A3A) threshold greater than accumulated excess load. (0.0%~130.0%)

V/F SVC
F10.59 Motor overload 100.0%
Motor overload calculated current = actual current * STOP
(0x0A3B) current coefficient (0.0%~250.0%)
motor overload current coefficient.

Table 4-48 F10.5x group

4.15 F11 Group: Keyboard Parameter


F11.0x group: keyboard operation (external keyboard required)
Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
0: lock off;
F11.00 1: keyboard parameters changing function locked; 0
Key lock RUN
(0x0B00) 2: function parameters and the non-start & stop key (0~3)
locked;
3: all function parameters and keys are locked;

V/F SVC
F11.01 Function together with the key lock; Remember the 0
Key lock password RUN
(0x0B01) password after setting, otherwise, the operation (0~65535)
cannot be performed if it is locked.

V/F SVC
0: invalid;
1: reverse running;
2: forward jogging;
3: backward jogging;
4: switch between the keyboard command channel
F11.02 Multi-function key 0
and the terminal command channel; STOP
(0x0B02) selection (0~7)
5: switch between the keyboard command channel
and the communication command channel;
6: switch between the terminal command channel
and the communication command channel;
7: switch between the keyboard, terminal, and
communication command channel;
V/F SVC
F11.03 Keyboard STOP key 0: non-keyboard control invalid; 0
setting STOP
(0x0B03) 1: non-keyboard control stops as stop mode; (0~2)
2: non-keyboard control stops as free mode;
V/F SVC
Ones-place; keyboard up & down function selection
Up/down button on 0: invalid;
F11.04 the status interface 1: used to change the frequency of F01.09; 0011
STOP
(0x0B04) (knob) function 2: used to adjust PID keyboard of F13.01; (0000~0213)
selection 3: keyboard up & down keys to change the
parameters;
Tens-place: power failure storage

42
AC01-Series network inverter manual Function List

0: off;
1: on;
Hundreds-place: action limit
0: adjustable both during running & shutdown;
1: adjustable during running and keeping during
shutdown;
2: adjustable during running and clearing all after
shutdown;
Thousands-place: reserved
V/F SVC
Ones-place: set yy value from 00 to 99 among code
F11.05 Up & down key quick 0109
“Fxx.yy”; RUN
(0x0B05) change parameter (0000~2999)
Tens-place: set xxvalue from 00 to 15 among code
“Fxx.yy”

Table 4-49 F11.0x group

F11.1x group: status interface cycle monitoring


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
Left & right key on Ones-place: left key to adjust the first row;
F11.10 0011
the status screen 0: invalid; 1: valid STOP
(0x0B0A) (0000~0011)
function selection Tens-place: right key to adjust the second row;
0: invalid; 1: valid
V/F SVC
Keyboard first line Ones- & tens-place: set yy from 00 to 63 among
F11.11 0000
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B0B) (0000~0763)
parameter 1 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard first line Ones- & tens-place: set yy from 00 to 63 among
F11.12 0001
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B0C) (0000~0763)
parameter 2 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard first line Ones- & tens-place: set yy from 00 to 63 among
F11.13 0002
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B0D) (0000~0763)
parameter 3 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard first line Ones- & tens-place: set yy from 00 to 63 among
F11.14 0011
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B0E) (0000~0763)
parameter 4 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.15 0002
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B0F) (0000~0763)
parameter 1 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.16 0004
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B10) (0000~0763)
parameter 2 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;

43
Function List AC01-Series network inverter manual

V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.17 0010
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B11) (0000~0763)
parameter 3 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;
V/F SVC
Keyboard second line Ones- & tens-place: set yy from 00 to 63 among
F11.18 0012
cycle- display monitoring parameter Cxx.yy; RUN
(0x0B12) (0000~0763)
parameter 4 Hundreds-& Thousands-plac: set xx from 00 to 07
among monitoring parameter Cxx.yy;

Table 4-50 F11.1x group

F11.2x group: monitoring parameter control


Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
Ones-place: input frequency display selection
0: target frequency
1: running frequency
>=2: running frequency, filtering depth
increases with this value.
Tens-place: reserved
F11.20 Keyboard item 0x0002
0: invalid RUN
(0x0B14) display selection (0x0000~0x111F)
1: remove the active power of stator resistance
loss
Hundreds-place: power display dimension
0: display percentage (%)
1: display kW (kW)
Thousands-place: reserved

V/F SVC
F11.21 100.0%
Speed factor display Set keyboard monitoring speed parameter RUN
(0x0B15) (0.0%~500.0%)
factor ratio display.

V/F SVC
F11.22 100.0%
Power factor display Set keyboard monitoring power parameter RUN
(0x0B16) (0.0%~500.0%)
factor ratio display.
V/F SVC
Ones-place: reserved
0: invalid;
1: valid;
Tens-place: C05 display selection
Monitoring parameter 0: Automatically switches with control modes
F11.23 0x0000
group display 1: V/F mode related parameters; RUN
(0x0B17) (0x0000~0xFFFF)
selection 2: V/C mode related parameters;
Hundreds-place: C00.40~C00.63 display
selection
0: off;
1: on;
Thousands-place: reserved
V/F SVC
F11.24 Monitoring parameter Ones- place: output current filtering displayed 0x0002
RUN
(0x0B18) filtering selection 0 to F: The larger the value, the deeper the (0x0000~0x000F)
filtering
V/F SVC
0: status of the self-learning process displayed
F11.25 Motor self - learning 1: status of the self-learning process not 0
RUN
(0x0B19) display selection displayed (0~1)
Note: T/S2 models do not support this
parameter.

44
AC01-Series network inverter manual Function List

Ones-place: The fault display during


F11.27 self-recovery: 0x0001
Fault display selection RUN
(0x0B1B) 0: off (0x0000~0x0001)
1: on

Table 4-51 F11.2x group

F11.3x group: keyboard special functions


Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting
V/F SVC range)
0: RS485 communication port;
F11.30 AC01 Serial port 1: external keyboard; 0
STOP
(0x0B1E) function select Choose one of the two functions of the 485 bus and the (0~1)
external keyboard. If the external keyboard is valid and
connected, the 485 bus (master/slave) remains invalid.
Keyboard V/F SVC
F11.31 0.50V
potentiometer Define the keyboard potentiometer voltage lower limit, any RUN
(0x0B1F) (0.00V~3.00V)
lower limit voltage value smaller than this value will still be taken as this one.
Keyboard
potentiometer V/F SVC
F11.32 0.00%
lower limit Set the input percentage of lower voltage limit of the RUN
(0x0B20) (0.00%~100.00%)
corresponding keyboard potentiometer.
value
V/F SVC
Keyboard
F11.33 Define the keyboard potentiometer upper voltage limit, 2.80V
potentiometer RUN
(0x0B21) any value bigger than this value will still be taken as this (0.00V~3.00V)
upper limit voltage
one.
Keyboard
potentiometer V/F SVC
F11.34 100.0%
upper limit Set the input percentage of upper voltage limit of the RUN
(0x0B22) (0.0%~100.0%)
corresponding keyboard potentiometer.
value
V/F SVC
Keyboard Set the keyboard potentiometer channel
F11.35 0
potentiometer 0: built-in keyboard potentiometer effective; STOP
(0x0B23) (0~1)
selection 1: external single-line display keyboard potentiometer
effective

Table 4-52 F11.3x group

4.16 F12 Group: Communication Parameter


(Note: The Modbus bus (master/slave) cannot be used when the external keyboard selected for F11.30 is valid and connected.)

F12.0x group : Modbus slave parameters

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
F12.00 Master/slave 0
0: slave STOP
(0x0C00) selection (0~1)
1: master
Modbus V/F SVC
F12.01 1
communication Set the communication address of the Modbus slave STOP
(0x0C01) (1~247)
address computer.

45
Function List AC01-Series network inverter manual

V/F SVC 3:9600 bps


F12.02 Communication baud 0:1200 bps 4:19200 bps 3
STOP
(0x0C02) rate selection 1:2400 bps 5:38400 bps (0~6)
2:4800 bps 6:57600 bps
V/F SVC
0:(N, 8,1) No check, 3:(N, 8,2) No check,
Data bit :8, Data bit :8,
Stop bit :1 Stop bit :2
Modbus 1:(E, 8,1) Parity 4:(E, 8,2) Parity check,
F12.03 0
communication data check, Data bit :8, STOP
(0x0C03) (0~5)
format Data bit :8, Stop bit :2
Stop bit :1 5:(O, 8,2) odd check,
2:(O, 8,1) odd check, Data bit :8,
Data bit :8, Stop bit :2
Stop bit :1
Modbus
V/F SVC
F12.04 communication 0
0: write operation valid; RUN
(0x0C04) transmission response (0~1)
1: write operation invalid;
processing
Modbus V/F SVC
F12.05 0ms
communication The time interval between receiving the data and RUN
(0x0C05) (0ms~5000ms)
response delay replying to the master.

Modbus V/F SVC


F12.06 1.0s
communication interval time between two communication to tell RUN
(0x0C06) (0.1s~100.0s)
timeout failure time communication disconnection.

V/F SVC
Communication 0: timeout fault undetected;
F12.07 0
disconnection 1: report fault and stop freely; RUN
(0x0C07) (0~3)
processing 2: report warning and go on running;
3: forced stop
Received data V/F SVC
F12.08 0.00
(address 0x3000) Set the bias value of the set frequency of RUN
(0x0C08) (-100.00~100.00)
with zero bias communication (100.00 corresponding to 100.00Hz)
V/F SVC
F12.09 Receive data (address Set the gain of communication at the set frequency 100.0%
RUN
(0x0C09) 0x3000) gain Set frequency = actual communication × gain + bias (0.0%~500.0%)
value

Table 4-53 F12.0x group

F12.1x group : Modbus master parameters

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Ones-, tens-, hundreds-, 6: output torque;
thousands-place 7: reserved
0: invalid; 8: reserved
F12.10 Master loop-sending 9: PID setting 0x0031
1: running command; RUN
(0x0C0A) parameters selection A: PID feedback; (0x0000~0xCCCC)
2: set frequency;
3: output frequency; B: reserved;
C: Active current
4: upper limit frequency;
component;
5: set torque ;

46
AC01-Series network inverter manual Function List

V/F SVC
F12.11 Self-defined Set this parameter to non-0 in place of frequency 0x0000
RUN
(0x0C0B) frequency address address of 0x3000 or 0x2000 set via (0x0000~0xFFFF)
communication port.

V/F SVC
F12.12 Self-defined Set this parameter to non-0 in place of command 0x0000
RUN
(0x0C0C) command address address of 0x3001 or 0x2001 set via (0x0000~0xFFFF)
communication port.
Forward running V/F SVC
F12.13 0x0001
command value Set this parameter in place of 0001H forward RUN
(0x0C0D) setting (0x0000~0xFFFF)
running set via communication port.
Backward running V/F SVC
F12.14 0x0002
command value Set this parameter in place of 0002H backward RUN
(0x0C0E) (0x0000~0xFFFF)
setting running set via communication port.
V/F SVC
F12.15 Stop command value 0x0005
Set this parameter in place of 0005H deceleration RUN
(0x0C0F) (0x0000~0xFFFF)
stop set via communication port.
V/F SVC
F12.16 Reset command 0x0007
Set this parameter in place of 0007H fault recovery RUN
(0x0C10) value (0x0000~0xFFFF)
set via communication port.
V/F SVC
F12.19 Master sending Master sending command selection 0
RUN
(0x0C13) command selection 0: sending the running command (0~1)
1: sends the running status
Table 4-54 F12.1x group

4.17 F13 Group: PID Control


F13.00~F13.06:PID setting and feedback

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)

V/F SVC 4: reserved


0: via keyboard number 5: reserved
setting; 6: via RS485
1: via keyboard communication port;
F13.00 PID controller signal 0
potentiometer; 7: reserved RUN
(0x0D00) source setting (0~9)
2: via current analog 8: via terminal
quantityAS; selection;
3: via voltage analog 9: via active current of
quantity VS; communication

V/F SVC
PID setting/feedback
F13.01 The parameter is valid when [F13.00]or [F13.03] is 50.0%
via keyboard number RUN
(0x0D01) selected with “PID setting/feedback via keyboard (0.0%~100.0%)
entering
number entering”.

F13.02 V/F SVC 1.00s


PID time RUN
(0x0D02) Set PID time needed from 0.0% to 100%. (0.00s~60.00s)
V/F SVC 5: reserved
PID controller 0: via keyboard number 6: via RS485
F13.03 2
feedback signal setting; communication port; RUN
(0x0D03) (0~9)
source setting 1: via keyboard 7: reserved
potentiometer; 8: via terminal

47
Function List AC01-Series network inverter manual

2: via current analog selection;


quantityAS; 9: via local active
3: via voltage analog current;
quantity VS;
4: reserved
V/F SVC
F13.04 Feedback signal 0.010s
The longer the filter time, the stronger the RUN
(0x0D04) low-pass filter time (0.000s~6.000s)
anti-interference, and the slower the reaction.
V/F SVC
F13.05 1.00
Feedback signal gain Used for linear proportional modulation of feedback RUN
(0x0D05) (0.00~10.00)
input signal.

V/F SVC
F13.06 Feedback signal 100.0
PID feedback signal range is a dimensionless unit used RUN
(0x0D06) range (0.0~100.0)
to adjust PID feedback.

Table 4-55 F13.00~F13.06

F13.07~F13.24:PID modulation

Parameter
Factory default Adjustable
code Designation Content
(setting range) attribute
(Address)
V/F SVC
Ones- place: feedback characteristic selection
0: positive characteristic;
1: negative characteristic
F13.07 0100
PID control selection Tens-place: reserved RUN
(0x0D07) (0000~1111)
Hundreds-place: reserved
Thousands-place: differential regulation characteristics
0: differentiates the deviation
1: differentiate the feedback
F13.08 V/F SVC 100.0%
PID preset output RUN
(0x0D08) Output as PID preset value after PID starts. (0.0%~100.0%)
V/F SVC
F13.09 PID preset output 0.0s
Set PID preset output time and set output starts after RUN
(0x0D09) time (0.0s~6500.0s)
countdown.
V/F SVC
F13.10 0.0%
PID deviation limit Set maximum deviation between PID feedback and RUN
(0x0D0A) (0.0%~100.0%)
PID set
F13.11 V/F SVC 0.100
Proportional gain P1 RUN
(0x0D0B) Set PID parameter group 1 proportional gain. (0.000~4.000)
F13.12 V/F SVC 1.0s
Integral time I1 RUN
(0x0D0C) Set PID parameter group 1 integral time. (0.0s~600.0s)
F13.13 V/F SVC 0.000s
Rate time D1 RUN
(0x0D0D) Set PID parameter group 1 rate time. (0.000s~6.000s)
F13.14 V/F SVC 0.100
Proportional gain P1 RUN
(0x0D0E) Set PID parameter group 2 proportional gain. (0.000~4.000)
F13.15 V/F SVC 1.0s
Integral time I2 RUN
(0x0D0F) Set PID parameter group 2 integral time. (0.0s~600.0s)
F13.16 V/F SVC 0.000s
Rate time D2 RUN
(0x0D10) Set PID parameter group 2 rate time. (0.000s~6.000s)
V/F SVC
F13.17 PID parameter 0: off; 0
switching condition RUN
(0x0D11) 1: switch via DI terminal; (0~2)
2: switch according to deviation;
V/F SVC
F13.18 Set lower deviation 20.0%
Apply the gain 1 parameter when the PID deviation is RUN
(0x0D12) value (0.0%~100.0%)
smaller than this value.

48
AC01-Series network inverter manual Function List

V/F SVC
F13.19 Set higher deviation 80.0%
Apply the gain 1 parameter when the PID deviation is RUN
(0x0D13) value (0.0%~100.0%)
larger than this value.
V/F SVC
F13.21 5.0%
Differential limit Differential limit is used to set the range of PID RUN
(0x0D15) (0.0%~100.0%)
differential output.
F13.22 PID upper limit V/F SVC 100.0%
RUN
(0x0D16) output Set the upper limit of PID output. (0.0%~100.0%)

F13.23 PID lower limit V/F SVC 0.0%


RUN
(0x0D17) output Set the lower limit of PID output. (-100.0%~F13.22)
F13.24 V/F SVC 0.000s
PID output filter time RUN
(0x0D18) Set the filter time for PID output. (0.000s~6.000s)

Table 4-56 F13.07~F13.24

F13.25~F13.28:PID Feedback disconnection


Parameter Factory default Adjustable
Designation Content
code (setting range) attribute
(Address) V/F SVC
0: PID continues running and no fault is reported;
1: PID stops running and fault is reported;
F13.25 Action selection of 0
2: PID continues running and sends output warning STOP
(0x0D19) PID disconnection (0~3)
signal;
3: PID continues running at the current frequency and
sends output warning signal;
F13.26 Detection time of V/F SVC 1.0s
RUN
(0x0D1A) PID disconnection Set detection time of PID disconnection diagnosis. (0.0s~120.0s)
Upper limit of V/F SVC
F13.27 100.0%
disconnection If the feedback signal exceeds this value and persists RUN
(0x0D1B) (0.0%~100.0%)
warning for [F13.26], the sensor is considered disconnected
V/F SVC
Lower limit of
F13.28 If the feedback signal is lower than this value and 0.0%
disconnection RUN
(0x0D1C) persists for [F13.26], the sensor is considered (0.0%~100.0%)
warning
disconnected

Table 4-57 F13.25~F13.28

F13.29~F13.33:PID sleep mode


Parameter Factory default Adjustable
Designation Content
code (setting range) attribute
(Address) V/F SVC
F13.29 0
Sleep selection 0: off; RUN
(0x0D1D) (0~1)
1: on
10.00Hz
F13.30 V/F SVC
Sleep frequency (0.00Hz ~ max. RUN
(0x0D1E) When the sleep function is effective, PID output
frequency)
frequency is lower than [F13.30] and last for sleep
F13.31 60.0s
Sleep delay delay of [F13.31], then starts the sleep mode. RUN
(0x0D1F) (0.0s~3600.0s)
F13.32 V/F SVC 5.0%
Wakeup deviation RUN
(0x0D20) PID feedback is lower than/greater than (positive (0.0%~50.0%)
characteristic/negative characteristic) PID minus/plus
F13.33 (positive characteristic/negative characteristic) wakeup 1.0s
Wakeup delay RUN
(0x0D21) deviation [F13.32] and lasts for wakeup delay (0.0s~60.0s)
[F13.33], sleep mode ends and running is resumed.

Table 4-58 F13.29~F13.33

49
Function List AC01-Series network inverter manual

4.18 F14 Group: Multi-speed and Simple PLC


F14.00~F14.14: multi-speed frequency setting
Parameter Factory
Adjustable
code Designation Content default
attribute
(Address) (setting range)
V/F SVC
[F01.02] frequency source channel is 9: program control (PLC)
setting. Frequency and running direction of inverter is controlled by
PLC with up to 15 stages speed; See Setting [F14.15] for running
mode. If one stage of speed time is set to "0", the program will skip
that speed.

[F01.02] frequency source channel is 11: multi-speed setting.


Frequency is set via“multi-speed terminal”. Running direction,
F14.00 acceleration & deceleration time are [F14.31~ F14.45] respectively. See description
(0x0E00) If multi-speed terminals are invalid , multi-speed is set to on the left
PLC
0.“multi-speed terminal” parameters see [F5.00~F5.03]. (0.00Hz~
~ multi-speed RUN
F14.14 1~15 setting maximum
(0x0E0E) Default values are set as follows: frequency)
F14.00 multi-speed1 = 10.00Hz; F14.08 multi-speed9 = 10.00Hz
F14.01 multi-speed2 = 20.00Hz; F14.09 multi-speed10 = 20.00Hz
F14.02 multi-speed3 = 30.00Hz; F14.10 multi-speed11 = 30.00Hz
F14.03 multi-speed4 = 40.00Hz; F14.11 multi-speed12= 40.00Hz
F14.04 multi-speed5 = 50.00Hz; F14.12 multi-speed13= 50.00Hz
F14.05 multi-speed6 = 40.00Hz; F14.13 multi-speed14= 40.00Hz
F14.06 multi-speed7 = 30.00Hz; F14.14 multi-speed15= 30.00Hz
F14.07 multi-speed8 = 20.00Hz;

Table 4-59 F14.00~F14.14

F14.15:PLC running mode selection


Parameter Factory default Adjust
Designation Content
code (setting range) able
(Address) V/F SVC Hundreds-place: power failure attribu
Ones-place: cycle mode storage mode te
0: stops after a single cycle; 0: off;
1: continues with cycles; 1: on;
F14.15 PLC running 2: keep the final value after Thousands-place: start mode 0000
RUN
(0x0E0F) mode selection a single cycle; 0: restart from stage 1; (0000~2122)
Tens-place: timing unit 1: restart the interrupted stage
0: second (s); all over again;
1: minute (m); 2: restart the interrupted stage
2: hour (h); for the remaining time;

Table 4-60 F14.15

F14.16~F14.30:PLC running time selection


Parameter Factory default Adjust
code Designation Content able
(setting range)
(Address)
F14.16 attribu
(0x0E10) 10.0(s/m/h) te
PLC 1st ~ 15th stage V/F SVC
~ (0.0(s/m/h) RUN
speed running time Set PLC running time for 1st ~ 15th stage speed
F14.30 ~6500.0(s/m/h))
(0x0E1E)

Table 4-61 F14.16 ~ F14.30

F14.31~F14.45:PLC running direction and time selection

50
AC01-Series network inverter manual Function List

Parameter Factory default Adjust


Designation Content
code (setting range) able
(Address) V/F SVC attribu
Ones-place: running direction of this stage (compared with te
running command)
0: in the same direction;
F14.31 PLC 1st ~ 15th stage
1: in the opposite direction
(0x0E1F) speed running
Tens-place: acceleration and deceleration time of this stage 0000
~ directions and RUN
0: acceleration and deceleration time 1; (0000~0031)
F14.45 acceleration &
1: acceleration and deceleration time 2;
(0x0E2D) deceleration time
2: acceleration and deceleration time 3;
3: acceleration and deceleration time 4;
Hundreds-place: reserved
Thousands-place: reserved

Table 4-62 F14.31~F14.45

4.19 F15 Group: Reserved


4.20 F25 Group: AS/VS Correction
Please refer to the corresponding technical manual for detailed introduction of the function codes and description of this group.

4.21 C0x Group: Monitoring Parameter


C00.xx group : basic monitoring
Parameter code Factory default Adjustable Parameter code
Designation Content
(Address) (setting range) attribute (Address)
input terminal X
C00.00 (0x2100) set frequency C00.14 (0x210E) C00.28 (0x211C) software version
connection status
output input terminal Y
C00.01 (0x2101) C00.15 (0x210F) C00.29 (0x211D) reserved
frequency connection status
C00.02 simulated quantity
output current C00.16(0x2110) C00.30 (0x211E) timer timing
(0x2102) AS input value
simulated quantity
C00.03 (0x2103) input voltage C00.17 (0x2111) C00.31 (0x211F) PID output value
VS input value
keyboard
inverter software
C00.04 (0x2104) output voltage C00.18 (0x2112) potentiometer C00.32 (0x2120)
sub-version
input value
machinery
C00.05 (0x2105) C00.19 (0x2113) reserved C00.33(0x2121) reserved
speed
C00.06 (0x2106) set torque C00.20 (0x2114) reserved C00.34 (0x2122) reserved
C00.07 (0x2107) output torque C00.21 (0x2115) reserved C00.35 (0x2123) reserved
C00.08 (0x2108) PID set quantity C00.22 (0x2116) counter value C00.36 (0x2124) fault warning code
PID feedback cumulative electricity
C00.09 (0x2109) C00.23 (0x2117) run time C00.37 (0x2125)
qty. consumption (low)
accumulative run cumulative electricity
C00.10 (0x210A) output power C00.24 (0x2118) C00.38 (0x2126)
time consumption (high)
inverter power
C00.11 (0x210B) busbar voltage C00.25 (0x2119) C00.39 (0x2127) power factor angle
level
module inverter rated
C00.12 (0x210C) C00.26 (0x211A)
temperature 1 voltage
module inverter rated
C00.13 (0x210D) C00.27 (0x211B)
temperature 2 current

Table 4-63 C00.xx group

C01.xx group: fault monitoring

51
Function List AC01-Series network inverter manual

Parameter code Parameter code Parameter code


Designation Designation Designation
(Address) (Address) (Address)
fault type diagnosis fault input terminal module temperature of
C01.00 (0x2200) C01.08 (0x2208) C01.16 (0x2210)
information status last fault
fault diagnosis fault output terminal
C01.01 (0x2201) C01.09 (0x2209) C01.17 (0x2211) inverter status of last fault
information status
fault running input terminal status of
C01.02 (0x2202) C01.10 (0x220A) last fault type C01.18 (0x2212)
frequency last fault
diagnosis information
C01.03 (0x2203) fault output voltage C01.11 (0x220B) C01.19 (0x2213) fault type of last 2 faults
of last fault
running frequency of diagnosis information of
C01.04 (0x2204) fault output current C01.12 (0x220C) C01.20 (0x2214)
last fault last 2 faults
output voltage of last diagnosis information of
C01.05 (0x2205) fault bus voltage C01.13 (0x220D) C01.21 (0x2215)
fault last 2 faults
fault module output current of last
C01.06 (0x2206) C01.14 (0x220E) C01.22 (0x2216) fault type of last 3 faults
temperature fault
bus voltage of last diagnosis information of
C01.07 (0x2207) fault inverter status C01.15 (0x220F) C01.23 (0x2217)
fault last 3 faults

Table 4-64 C01.xx group

Note: fault inverter status means:


 ones-place: running direction 0: forward; 1: backward
 tens-place: running state 0: stop; 1: at steady speed; 2: acceleration; 3: deceleration
 hundreds-place: overvoltage and overcurrent 0: normal; 1: overvoltage ; 2: overcurrent; 3: overvoltage and overcurrent
 thousands-place: reserved
C02.xx group: application monitoring

Parameter code Parameter code


Designation Designation
(Address) (Address)
C02.13 (0x230D) ~
C02.00 (0x2300) PID setting reserved
C02.14 (0x230E)
C02.01 (0x2301) PID feedback C02.15 (0x230F) inverter overload timing factor

C02.02 (0x2302) PID output C02.16 (0x2310) inverter overload timing factor
C02.17 (0x2311) ~
C02.03 (0x2303) PID control status reserved
C02.18 (0x2312)
C02.05 (0x2305) PLC running stage C02.19 (0x2313) number of current limiting per wave
C02.20 (0x2314) ~
C02.06 (0x2306) PLC stage frequency reserved
C02.31 (0x231F)
C02.32 (0x2320) ~ power-off storage parameter 1~
C02.07 (0x2307) PLC stage run time
C02.47 (0x232F) power-off storage parameter 16
forward & reverse command C02.48 (0x2330) ~
C02.08 (0x2308) reserved
setting C02.49 (0x2331)
C02.50 (0x2332) ~
C02.09 (0x2309) jogging command setting cache register 0 to cache register 9
C02.59 (0x233B)
C02.60 (0x233C) ~
C02.10 (0x230A) AS current before correction reserved
C02.61 (0x233D)

C02.11 (0x230B) VS voltage before correction C02.62 (0x233E) external keyboard version

C02.12 (0x230C) reserved

Table 4-65 C02.xx group

C03.xx: maintenance parameter monitoring

Parameter code Parameter code


Designation Designation
(Address) (Address)

52
AC01-Series network inverter manual Function List

C03.00 (0x2400) run time C03.23 (0x2417) reserved

C03.01 (0x2401) accumulative run time(h) C03.24 (0x2418) reserved


accumulative power-on
C03.02 (0x2402) C03.25 (0x2419) reserved
time(h)
accumulative power-on
C03.03 (0x2403) C03.26 (0x241A) reserved
time(m)
C03.04 (0x2404) cooling fan run time C03.27 (0x241B) reserved
C03.05 (0x2405) cooling fan maintenance C03.28 (0x241C) reserved
C03.06 (0x2406) reserved C03.29 (0x241D) reserved
C03.07 (0x2407) Main relay maintenance C03.30 (0x241E) reserved

C03.08 (0x2408) ~ C03.31 (0x241F) ~


reserved reserved
C03.19 (0x2413) C03.39 (0x2427)

C03.20 (0x2414) reserved C03.50 (0x2432) machine code 1


C03.21 (0x2415) reserved C03.51 (0x2433) machine code 2
C03.22 (0x2416) reserved C03.52 (0x2434) machine code 3

Table 4-66 C03.xx group

4.22 Input & Output Terminal Functions Selection


X Functional definition X Functional definition X Functional definition
command channel switched
0 null 24 PID switch 1 48
to keyboard
command channel switched
1 forward running 25 PID switch 2 49
to terminal
command channel switched
2 backward running 26 PID switch 3 50
to communication
3 three-wire system control (xi) 27 PID feedback switch 1 51 reserved
4 forward jogging 28 PID feedback switch 2 52 operation prohibited
5 backward jogging 29 PID feedback switch 3 53 forward prohibited
6 free stop 30 program operation (PLC) 54 backward prohibited
paused (PLC)
program operation
7 emergency stop 31 55 reserved
terminal 1restart
acceleration &
8 fault recovery 32 56 reserved
deceleration time selection
external fault input terminal 2 acceleration &
9 33 57 reserved
deceleration time selection
10 frequency progressive increase (up) 34 acceleration & deceleration 58 reserved
pause
11 frequency progressive decrease (dw) 35 swing frequency input 59 reserved
frequency increasing & decreasing
12 36 swing frequency pause 60 speed torque control switch
clearance (up/dw zero clearing)
jogging frequency as upper
13 channel a switched to channel b 37 swing frequency reset 62 limit frequency of torque
mode
frequency channel combination switches to keys & self - inspection display
14 38 63~87 reserved
a selection
frequency channel combination switches to
15 39 reserved 88 reserved
b
16 multi-speed terminal 1 40 timer triggered terminal 89 reserved
17 multi-speed terminal 2 41 timer clearing terminal 90 reserved
18 multi-speed terminal 3 42 counter clock input terminal 91 reserved
19 multi-speed terminal 4 43 counter clearing terminal 92 reserved
20 PID control off 44 DC brake command 93 reserved

53
Function List AC01-Series network inverter manual

21 PID control pause 45 pre-excitation command 94 reserved


22 PID characteristic switch 46 terminal
reserved 95 reserved
23 PID parameter switch 47 reserved
Y Functional definition Y Functional definition Y Functional definition
N
0 null 13 upper frequency arrival 26 emergency stop now
o.
1 inverter in motion 14 lower frequency arrival 27 overload warning output 1
2 inverter backward running 15 program run cycle completed 28 underload warning output 2
3 inverter forward running 16 program run stage completed 29 inverter warning
fault trip warning 1(warning during fault 0x3018
4 17 PID feedback over limit 30
self-recovery) control output
fault trip warning 2 (no warning during inverter overheating
5 18 PID feedback below limit 31
fault self-recovery) warning
PID feedback sensor
6 external failure shutdown 19 32 reserved
disconnected
7 inverter undervoltage 20 reserved 33~36 reserved
8 inverter ready for operation 21 timer time out 37 comparator 1 detection
counter maximum value
9 output frequency level detection 1(FDT1) 22 38 comparator 2 detection
arrival

10 output frequency level detection 2 (FDT 2) 23 counter set value arrival 39~63 reserved

11 set frequency arrival 24 energy consumption braking —— ——


12 running at zero speed 25 reserved —— ——

Table 4-67 Input & output terminal functions selection

4.23 Fault Code Table


Note:
1. Refer to the relevant instructions on page 9 of this manual for inverter fault/operation status information.
2.The numbers in the code column in brackets are fault codes OR warning codes (Dec means decimal), the following codes need to be
obtained from the external keyboard OR by reading the inverter address 0x3003/0x3010 information through communication.
Display (DEC.) Fault Type Display (DEC.) Fault Type
system fault during
E. SC1(1) fault E. Ld2(80) load protection 2 fault
acceleration
system fault during
E. SC2(2) fault E. CPu (81) CPU timeout failure fault
deceleration
system fault during Reserved
E. SC3(3) fault reserved fault
constant speed (82-84)
E. SC4(4) shutdown system fault fault E. LoC (85) chip lock fault
overcurrent during
E. oC1(5) fault E. EEP (86) parameter storage failure fault
acceleration
overcurrent during Reserved
E. oC2(6) fault reserved fault
deceleration (87-96)
overcurrent during monitor comparison output 1
E. oC3(7) fault E. CP1(97) fault
constant speed failure
AC01 software monitor comparison output 2
E. oC4(8) fault E. CP2(98) fault
overcurrent failure
overvoltage during
E. ou1(9) fault E. dAT (99) parameter setting failure fault
acceleration
overvoltage during reserved
E. ou2(10) fault reserved fault
deceleration (100~109)
overvoltage during
E. ou3(11) fault E. FA1(110) external extension reserved 1 fault
constant speed
Reserved (12) reserved fault E. FA2(111) external extension reserved 2 fault
E. Lu (13) undervoltage during fault E. FA3(112) external extension reserved 3 fault

54
AC01-Series network inverter manual Function List

operation
E. oL1(14) motor overload fault E. FA4(113) external extension reserved 4 fault
E. oL2(15) inverter overload 1 fault E. FA5(114) external extension reserved 5 fault
E. oL3(16) inverter overload 2 fault E. FA6(115) external extension reserved 6 fault
E. oL4(17) inverter overload 3 fault E. FA7(116) external extension reserved 7 fault
E. iLF (18) input phase loss fault E. FA8(117) external extension reserved 8 fault
three-phase output phase
E. oLF (19) fault
loss
U-phase output phase
E. oLF1(20) fault Here are the warnings
loss
V-phase output phase
E. oLF2(21) fault A. Lu1(128) undervoltage shutdown warning
loss
W-phase output phase
E. oLF3(22) fault A. ou (129) overvoltage shutdown warning
loss
Reserved (23-29) reserved fault A. iLF (130) input phase loss warning
E. oH1(30) rectifier overheat fault A. PID (131) PID feedback disconnection warning
E. oH2(31) inverter overheat fault A. EEP (132) parameter storage warning warning
Reserved (32) reserved fault A. dEF (133) excessive speed deviation
E. EF (33) external fault fault A. SPd (134) Stall warning warning
Modbus communication
E. CE (34) fault A. GPS1(135) GPS lock warning
fault
U-phase excessive zero
E. HAL1(35) fault A. GPS2(136) GPS disconnection warning
drift
V-phase excessive zero Modbus disconnection
E. HAL2(36) fault A. CE (137) warning
drift warning
non-zero sum of three
E. HAL (37) fault A. Ld1(138) load protection 1 warning
phase currents
W-phase excessive zero
E. HAL3(38) fault A. Ld2(139) load protection 2 warning
drift
Reserved (39) reserved fault Reserved (140) reserved warning
E. SGxx (40) ground short circuit fault A. oH1(141) Module overheat warning warning
E. FSG (41) fan short circuit fault Reserved (142) reserved warning
PID feedback
E. PID (42) fault A. run1(143) warning 1 in motion warning
disconnection
external keyboard
E. CoP (43) parameter copy failure fault A. PA2(144) warning
disconnection warning
Reserved (44) reserved fault A. CoP (145) parameter copy warning warning
monitor comparison output 1
Reserved (45-49) reserved fault A. CP1(146) warning
warning
monitor comparison output 2
E. bru (50) brake unit failure fault A. CP2(147) warning
warning
Reserved (51) reserved fault A. run2(148) warning 2 in motion warning
self-learning output
E. TExx (52) fault A. run3(149) warning 3 in motion warning
current over limit
reserved
reserved fault A. FA1(150) external extension reserved 1 warning
(53~70)
motor angle learning
E. iAE1(71) fault A. FA2(151) external extension reserved 2 warning
fault 1
motor angle learning
E. iAE2(72) fault A. FA3(152) external extension reserved 3 warning
fault 2
motor angle learning
E. iAE3(73) fault A. FA4(153) external extension reserved 4 warning
fault 3
synchronous motor step
E. PST1(74) fault A. FA5(154) external extension reserved 5 warning
out fault 1
synchronous motor step
E. PST2(75) fault A. FA6(155) external extension reserved 6 warning
out fault 2
synchronous motor step
E. PST3(76) fault A. FrA(157) reserved warning
out fault 3

55
Function List AC01-Series network inverter manual

excessive speed cooling fan service life


E. dEF (77) fault A. 161(161) warning
deviation warning
E. SPd (78) stall protection fault A. 163(163) Main relay service life warning warning
E. Ld1(79) load protection 1 fault

Table 4-68 Fault code

56
AC01-Series network inverter manual Regular Inspection and Maintenance

Chapter 5 Regular Inspection and Maintenance


5.1 Inspection
Inverters are composed of semiconductor devices, passive electronic devices and motion devices, and these devices have a service life. Even
under normal working conditions, some of the devices may have characteristics change or failures if the service life is exceeded, thus preventive
maintenance such as routine check, periodic check, and component replacement must be performed. It is recommended to check the machine every
3 to 4 months after installation.
● Daily inspection: in order to avoid damage to inverters and shortened service life, please check the following items daily.
Item Content Method
Check whether the power supply voltage meets requirements and
Power supply. Address by requirements of the nameplate.
any phase loss.
Surroundings Check whether the installation environment meets requirements. Identify the source and address it properly.
Check whether it is overloaded, the heat sink of the
Whether there is abnormal heating and discoloration of inverter and
Cooling system converter is dirty or not, whether the fan is blocked,
motor, and the working condition of cooling fan.
tighten the screws.
Check whether the motor has abnormal vibration and abnormal Tighten mechanical and electrical connections and
Motor
sound. lubricate mechanical parts.
Check whether the inverter output current is higher than the motor Confirm whether overload occurs and whether the
Load status
or inverter rated values for a certain period of time. selection of inverter is correct.
Table 5- 1 Daily inspection
● Regular inspection: Generally, it is appropriate to carry out regular inspection every 3 to 4 months, please determine the actual inspection period
based on the use of each machine and working environment.
Item Content Method
●Tighten and replace defective parts; Clean and
Overall ●Insulation resistance & environment check.
improve the working environment.
● Replace the damaged wire;
● Whether there is discoloration on wires and connected parts; whether
there is discoloration, damage, cracking, aging traces on insulation layer; ● Tighten the loose terminals and replace damaged
Electrical
connection ● Whether terminal are worn, damaged or loose; terminals;
● Measure the grounding resistance and tighten the
● Grounding check;
corresponding grounding terminals;
Mechanical ● Whether there is any abnormal vibration and sound, and connected
● Tighten, lubricate and replace defective parts.
connection parts loose;
Semiconduct ● Whether there is garbage and dust; ● Clean and improve the working environment;
or device ● Whether there is a significant change in appearance; ● Replace the damaged parts;
Electrolytic ● Whether there is liquid leakage, discoloration, cracking, and exposure,
● Replace the damaged parts;
capacitance expansion, rupture or leakage on safety valves;
Peripheral ● Clean and improve the working environment;
● Peripheral equipment appearance and insulation inspection;
device ● Replace the damaged parts;
● Fasten connectors;
Printed ● Whether there is abnormal odor, discoloration, serious rust, and
● Clean the printed circuit board;
circuit board connectors are correct and tight;
● Replace the damaged printed circuit board;
● Whether cooling fan is damaged and blocked
Cooling ● Whether heat sink is stained with garbage and dust; ● Clean and improve the working environment;
system ● Whether the air inlet and exhaust outlet are blocked or stained with ● Replace the damaged parts;
foreign matters;
Keyboard ● Whether keyboard is damaged and display complete or not; ● Replace the damaged parts;
● Tighten the mechanical and electrical
Motor ● Whether the motor has abnormal vibration and abnormal sound.
connection, and lubricate the motor shaft.
Table 5- 2 Regular inspection
: Do not perform any operations when the power supply is on, otherwise there is a risk of death by electric shock. When performing
operations, cut off the power supply and ensure that the DC voltage of the main loop has been decreased to a safe level and then wait 5
minutes.
5.2 Maintenance
All devices and components have service life. Proper maintenance can prolong the service life, but will not make up for the damage of devices
and components. Please replace the components as required.
Part Service life Part Service life Part Service life
Fan 2~3 year Electrolytic capacitance 4~5 year Printed circuit board 8~10 year

Table 5- 3 Parts and service life


The replacement of other components requires high maintenance technology and product familiarity, and they must pass strict testing before
being put into use. Therefore, please don’t replace other internal components by yourself. If you do need a replacement, please contact the purchasing
57
Regular Inspection and Maintenance AC01-Series network inverter manual

agent or our sales department.

5.3 Product Guarantee


1. If the product fails within the warranty period, please refer to the clauses and scope in the warranty card.
2. Primary fault diagnosis is performed by customers in principle, but if required, we or our service network stations can provide according
service. On the result of negotiation between us, if the fault is on the product or caused behavior of Veichi ,it’s free, otherwise it will be charged;
3. Exemption from liability: any inconvenience caused to our customers or secondary customers, any damage caused to non-Veichi products
due to the failure of our products, whether within the warranty period or not, shall not be within the scope of our company's liability

58
AC01-Series network inverter manual Appendix I: Modbus Communication Protocol

Appendix I: Modbus Communication Protocol


● Communication frame structure
The communication data format is as follows:
Byte composition: includes the start bit, 8 data bits, check bit and stop bit.
start bit Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8 check bit stop bit

TableAppendix I-1 Communication frame structure


The information of a frame must be transmitted as a continuous data stream. If the interval of more than 1.5 bytes is longer before the end of the
frame transmission, the receiving device will clear the incomplete information and mistakenly assume that the next byte is the address domain part of
the new frame. Similarly, if the interval between the start of a new frame and the previous frame is less than 3.5 bytes, the receiving device will
consider it as a continuation of the previous frame. Due to the misalignment of the frame, the CRC check value will eventually be incorrect, resulting
in a communication error.
● Communication control parameter group address description
R/W
Function description Address definition Data description
characteristics
Frequency from communication 0x3000 or 0x2000 0~50000 corresponding to 0.00Hz~500.00Hz W/R
0005H: decelerate and
stop;
0000H: null 0006H: free stop;
0001H: forward running; 0007H: fault reset
Communication command setting 0x3001or 0x2001 0002H: backward running; 0008H: Operation W/R
0003H:forward jogging; prohibited command
0004H: backward jogging; 0009H: Operation
allowed command

Bit0 0: stopped 1: running


Bit1 0: non-accelerating state 1: accelerating
Bit2 0: non-decelerating state 1: decelerating
Inverter status 0x3002 or 0x2002 Bit3 0:forward 1: backward R
Bit4 0: no faults 1: inverter failure

Bit5 0: GPRS unlocking 1: GPRS locked


Bit6 0: no warning 1: inverter warning
Inverter fault code 0x3003 or 0x2003 Current inverter fault code (see fault code table) R
Upper limit frequency from
0x3004 or 0x2004 0~32000 corresponding to0.00Hz~320.00Hz W/R
communication
Torque setting from
0x3005 or 0x2005 0~1000 corresponding to0.0%~100.0% W/R
communication
Forward maximum frequency
0x3006 or 0x2006 0~1000 corresponding to0.0%~100.0% W/R
limited by torque
Backward maximum frequency
0x3007 or 0x2007 0~1000 corresponding to0.0%~100.0% W/R
limited by torque
PID value setting from
0x3008 or 0x2008 0~1000 corresponding to0.0%~100.0% W/R
communication
PID feedback value setting from
0x3009 or 0x2009 0~1000 corresponding to0.0%~100.0% W/R
communication
Failure and warning code reading 0x3010 or 0x2010 0~63 are fault codes and 64~are warning codes R
BIT1--TA1-TB1-TC
External inverter output terminal,, 1;
Output terminal status 0x3018 or 0x2018 W
BII0--Y BIT2--TA2-TB2-TC
2
AO output 0x3019 or 0x2019 0~10000corresponding to output 0V~10V,0mA~20mA W

TableAppendix I-2 Communication control parameter group address description


Note: For other function code addresses, see the "CommunicationAddress" column in the function code table.
When the F00 to F15 parameter group parameters are written with write command (06H), if the highest bit in the address field of the
function code parameter is 0, the parameters are only written into the RAM of the inverter and are not stored after power failure. If the
address field height of the function code parameter is 1, the parameter is written into the EEPROM. For example, F00 group :0x00XX
(write RAM)0x10XX(store in EEPROM).
When using the write command (06H) to write parameters of F16 to F29, if the highest bit in the address field of the function code
parameter is 5, it is only written into the RAM of the inverter, and is not stored after power failure. If the address field height of the
function code parameter is D, the parameter is written into the EEPROM, which is power-off storage. For example, F16
group :0x50XX(write RAM)0xD0XX(store in EEPROM); Group F17 :0x51XX(write to RAM)0xD1XX(save to EEPROM).
59
Appendix I: Modbus Communication Protocol AC01-Series network inverter manual

● Error code meaning from the slave's response to the exception message
Error code Description Error Description Error code Description
code
1 Wrong command code 3 CRC check error 4 Illegal address

Unchangeable
5 Illegal data 6 8 Converter busy (EEPROM in storage)
parameters in motion

Unchangeable saved The number of bytes in the parameter


9 Parameters out of range 10 11
parameters read incorrectly

Table Appendix I-3 Error code meaning

60
AC01-Series network inverter manual Appendix II: External Keyboard Size and Model

Appendix II: External Keyboard Size and Model


 External double-row display keyboard shape and hole size
Model: KBD300-25(Note: LCD is fully compatible with LED keyboard dimensions and hole sizes (unit: mm)).

AC01 series external two-row display keyboard size

AC01 series external two-row display keyboard shape and hole size

 External single-row keyboard shape and hole size


Model: KBD10-15 (Note: hole size of mounting plate :61mmx36mm. (Unit in the figure: mm))

66 26. 6
5

42 35. 6

60. 6
38. 3
参考开孔尺寸: 61x36mm

61