TON-0001, TON-0011
Cut off power and mount the wall plate as shown below:
Mount the monitor on the wall and the height from the ground is 1.2m-1.3m, please see the mounting dimension and fixing hole
in fig. 3. Connect wires to terminal strips, (see fig. 4) Make sure wiring connection correct and secure.
After finishing the mounting, follows the step 4-5 in the fig. 2 to close the cover.
Fig.4 Wiring Diagram Fig.3
85.00 36.50
TONGDY
L
220VAC OFF
9.50
N PPm
4.20
Co2
L1
Outlet
N1 130.00 84.00
sumer temperature
o
0 22 28 50 C
winter temperature
o
0 18 24 50 C
AC/DC
Switch
Power Input TON-0001: 100-240VAC (screw terminals) @ 3.5 W Max, 2.5 W Avg.
Power Input TON-0011: 24VAC (screw terminals) @ 3.5 W Max, 2.5 W Avg.
Operation
Turn on the power, a red light at middle bottom of the cover is flickering. The
measured temperature and the relative humidity displays on the upper line of the
OFF
LCD and the number on the below line displaying count down from 120 seconds
PPm
to 0. Finish the count down, the below line starts displaying measured CO2 level.
Please note: for the first using or using again after power off for a long time (more
than one month), the warm up time should be 24 hours, then the measurement
will be steadily. In normal operation, the warm up time is 10 minutes.
Touch button: (With relay ) the touch button is used to operate the monitor as shown in table below:
TONGDY
OFF
PPm
sumer temperature
winter temperature
o
0 18 24 50 C
Switch
4 setting values of CO2 measurement available as shown in table below. Choose one of them to control the output. Default
setting is 1000ppm, which means when CO2 measurement reaches 800ppm, the output of the controller will turn on the
controlled device, like say a ventilation fan.
Turn off the power and find the two DIP switches on the circle board through the notch on the back plate.
DIP1-1: ON – Change defaults (not for end users) DIP2-1 DIP2-2 CO2 measurement
OFF - Normal Using OFF OFF 800ppm
DIP1-2: ON – Temperature display in Fahrenheit degree OFF ON 1000ppm (default)
OFF- Temperature display in Celsius degree ON OFF 1200ppm
Put the DIP2 up for ON, down for OFF. ON ON 1400ppm
2
L1
N1