Megger Testing
Megger Testing
Case (I): If the resistance has a higher value then the pointer on the
device coil will move towards infinity.
Case(II): If the resistance value is low then the pointer will indicate
zero resistance.
Construction of Megger
The circuit consists of two coils Coil-A and Coil-B. Both the coils
are connected to the DC generator
Types of Megger
Manual megger
Electronic megger
Mechanism of Megger
The leads that are used to connect the megger to the circuit
need to be free of any faults, and the two leads that are used
to connect the megger need to have electrical continuity.
For Wires
When all of the devices are connected, both ends of the conductors
are shorted, and all of the switches are turned on, the reading that
is displayed on the megger must be zero. If the reading indicates
that there is no limit, then the circuit is open. It is necessary to
identify the source of the problem and correct it.
For Cables
In the case of cables, the outermost ends of any two phases should
be shorted, and the reading should be zero when the test is carried
out; if the meter reads infinity or some number of mega ohms, this
For Cables
The Megger range for cables needs to be 1000V, & both ends of the
cable must be left open during testing between the phases and
neutrals.
Between Phase-to-Phase
R-to-Y
R-to-B
Y-to-B
Between Phase-to-Neutral
R-to-N
Y-to-N
B-to-N
All of these readings supposed to be infinity; if they are not, the
cable’s conductors and phases are defective and need to be fixed.
With the use of a ground (E) cable, the cables need to be checked
against one another (phase to phase). Formula for determining
minimum insulation resistance values is provided by the Insulated
Power Cable Engineers Association (UPCEA).
R=K X Log10(D/d)
Where,
Advantages of Megger
Disadvantages
Applications