MCB DB
MCB DB
L&T Electrical & Automation is India s largest switchgear company that manufactures and
markets low and medium voltage switchgear products, electrical systems, energy meters and
automation solutions.
Its products and solutions address the power distribution and control needs of industry, utility,
infrastructure, buildings & homes and agriculture segments.
L&T promotes a culture of innovation and creation of intellectual property. Its products and
solutions have been in use at many landmark installations of the country and continue to
prove their high performance and reliability.
EN
L&T
L&T offers its new range of Modular Devices EXORA to
ensure a safe environment around you. Protection and
Control devices offered in this range provide safety at your
home and at your workplace. Salient features of this range
Quick Break Mechanism, True Contact Position Indicator,
Energy Limitation Class 3 enhance safety of human lives
and precious belongings.
11
3. Isolators
16
Technical Index
MCB (10kA)
Miniature Circuit Breaker
The MCB is a vital protection device. It is essential in every electrical installation to safeguar d both your life and
valuable property against short-circuit and overload.
Unique patented design gives both label holder and true contact indication facility for individual poles
Low watt loss almost 50% of the values prescribed by IEC 60898-1 saves energy
Design based on advanced current limiting hammer trip mechanism ensures quick breaking
No line load bias gives flexibility for incomer supply termination on either sides
Accessories wide range of accessories like aux contact, trip alarm contact and shunt r elease
DC MCB as per IEC 60947-2 : Rated Voltage: 130 V DC (for SP), 250 V DC (for DP)*
conformity
Dual Termination
True Contact
Indication
enhanced safety
Label Holder
2
Technical Specifications MCB
Dimensions
36.5
ON
20.5
87.3
45
85
67
47°
OFF
30.5
39.5
31 5.5
36.5 17.5 35 52.5 70
41
43
59.6 1 - POLE 2 - POLE 3 - POLE 4 - POLE
69
3
Modules
Current B-Curve C-Curve D-Curve DC MCBs
1 Mod=
Rating (In) Cat. Nos. Cat. Nos. Cat. Nos. Cat. Nos.
Single-Pole (SP) 17.5mm
Modules
Current B-Curve C-Curve D-Curve DC MCBs
1 Mod=
Rating (In) Cat. Nos. Cat. Nos. Cat. Nos. Cat. Nos.
17.5mm
Double-Pole (DP)
0.5A 2 - BB20E50C BB20E50D BB20E5DC
4
Current Modules B-Curve C-Curve D-Curve
Rating (In) 1 Mod= Cat. Nos. Cat. Nos. Cat. Nos.
Three-Pole (TP) 17.5mm
1A 3 - BB30010C BB30010D
2A 3 - BB30020C BB30020D
3A 3 - BB30030C BB30030D
4A 3 - BB30040C BB30040D
1A 4 - BB40010C BB40010D
2A 4 - BB40020C BB40020D
3A 4 - BB40030C BB40030D
4A 4 - BB40040C BB40040D
5
Auxiliaries and Accessories
10 kA MCBs
L&T MCBs can be fitted with a wide range of accessories like the auxiliary contact, shunt release and trip alarm
contact.
6
RCCB
Residual Current Circuit Breaker
Residual Current Circuit Breakers provide protection against earth leakage fault. They ensure safety of human
life in case of earth leakage fault and protection against electric shock.
L&T RCCBs are available in DP and FP versions from 25A to 100A ratings with 30mA, 100mA and
300mA sensitivity
7
Protection Devices RCCB
8
Technical Specifications RCCB
RCCB Type AC
Degree of Protection IP 20
50 mm2 (Rigid)
Termination Capacity
35 mm2 (Flexible)
Operating Temperature -5°C to + 55°C
Mechanical Life
20,000
(operating cycles)
* For back-up short circuit protection device, please refer to page no. 27
Dimensions
71.6 52.5
17.5 71.53
17.5
45
36
83
35.5
45
83
3.3
5.5
50 71
5.5 66
3.3
50 35
66
9
Current Sensitivity Modules 1 Mod= Cat Nos.
Rating 17.5mm Double-Pole (DP)
(In)
100mA 2 BG202510
300mA 2 BG202530
100mA 2 BG204010
300mA 2 BG204030
100mA 2 BG206310
300mA 2 BG206330
100mA 2 BG210010
300mA 2 BG210030
100mA 4 BG402510
300mA 4 BG402530
100mA 4 BG404010
300mA 4 BG404030
100mA 4 BG406310
300mA 4 BG406330
100mA 4 BG410010
300mA 4 BG410030
10
ISOLATORS
Isolators are used in electrical installations to make, carry and break circuit current. The Isolator ensures that
the circuit remains completely isolated i.e. there will be no current at the load side even if the impulse voltage
appears when the isolator is OFF.
Available in DP, TP and FP versions in 40A, 63A, 80A and 100A ratings
and certified
11
Terminals suitable up to 35 sq mm
cable and dual termination
True Contact
Indication
enhanced safety
12
Technical Specifications ISOLATORS
Rated Frequency 50 Hz
Degree of Protection IP 20
35 mm2 (Rigid)
Termination Capacity
25 mm2 (Flexible)
Dimensions
36.5
ON
20.5
470
67.0
87.3
85
45
OFF
30.5
39.5
31 5.5
35 52.5 70
36.5
41
43
2 - POLE 3 - POLE 4 - POLE
59.6
69
13
Current Modules
Modules 1 Cat. Nos
Double Pole (DP) Current
Rating (In) Mod= 17.5mm Cat. Nos
Rating (In) 1Mod = 17.5mm
40 2 BF204000
63 2 BF206300
80 2 BF208000
100 2 BF210000
Current Modules
Three Pole (TP)
Cat. Nos.
Rating (In) 1Mod = 17.5mm
40 3 BF304000
63 3 BF306300
80 3 BF308000
100 3 BF310000
Current Modules
Four Pole (FP) Rating (In) 1Mod = 17.5mm
Cat. Nos.
40 4 BF404000
63 4 BF406300
80 4 BF408000
100 4 BF410000
14
Ingress Protection (IP)
The protection of enclosures against ingress of dirt or against the ingress of water is defined in IEC529 (BSEN60529:1991).
Conversely, an enclosure which protects equipment against ingress of particles will also protect a person from potential
hazards within that enclosure, and this degree of protection is also defined as a standard.
The degrees of protection are most commonly expressed as 'IP' followed by two numbers, e.g. IP65, where the numbers
define the degree of protection.
With tools and wires etc. with a Water jets from a nozzle in all directions
thickness >1mm / granular
foreign bodies, diam. >1mm
High pressure jets
Complete protection / dust
protected Temporary immersion
15
TECHNICAL INDEX
1. Basics of Electrical System and General
Electrical Practices
1.1 Types of faults
2. Earthing Systems
2.1 Types of Earthing systems
16
Basics of Electrical System and General Electrical Practices
An incipient fault is a fault that starts from very small g. The metallic body of the fan regulator if any, shall be
beginnings, say some partial discharge (excessive electronic earthed effectively.
activity often referred to as corona) in a void in the h. Earth leakage circuit-breaker at the intake of power
insulation, increasing and developing over an extended supply at the consumer's premises shall be provided.
period, until such time as it burns away adjacent insulation,
eventually running away and developing into a "solid"
fault.
2. Passive Fault
Passive faults are not real faults in the true sense of the
word, but are conditions that stress the system beyond its
design capacity, so that ultimately active faults will occur.
Examples of passive faults Overloading leading to
overheating of insulation (deteriorating quality, reduced life
and ultimate failure).
17
Earthing 1. TT system If the neutral of the source & protective
earth (PE) conductor at the consumer end are earthed
According to BS 7671 five types of earthing are specified. separately, the system is called TT system. The system is as
TT- Earthing system shown in the figure.
TN-S Earthing system With TT, the consumer must provide their own connection
to earth, i.e. by installing a suitable earth electrode local to
TN-C system
the installation. The circumstances in which a distributor
TN-C-S system may not provide a means of earthing for the consumer
IT-system where the distributor cannot guarantee the earth
connection back to the source, e.g. a low voltage overhead
In the above systems,
supply or where there is the likelihood of the earth wire
T = Earth (from the French word Terre) either becoming somehow disconnected or even stolen.
N = Neutral
S = Separate TT System
L
C = Combined
Installation
I = Isolated N Equipment
2. TN- S system
In this system, the N and PE neutral
conductors are separate. PE and N
TN-S system conductors are mandatory for the circuits of
cross-section less than 10 sq.mm.
Source of supply Installation
A TN-S system has the neutral of the source
L
of energy connected with earth at one point
Installation
Equipment only, at or as near as is reasonably practicable
N
to the source. The consumer s earthing
terminal is typically connected to the metallic
T Exposed-conductive-part
sheath or armour of the distributor s service
N-S
cable into the
Source Earth premises or to a separate protective
conductor of, for instance, an overhead
supply. Large consumers may have one or
more HV/LV transformers dedicated to their
installation and installed adjacent to or
within their premises. In such situations, the
usual form of system earthing is TN-S.
18
3. TN-C-S system
A TN-C-S system has the supply neutral conductor of a
TN-C-S system
distribution main connected with earth at source and at
L
intervals along its run. This is usually referred to as Protective
Installation
Equipment Multiple Earthing (PME). With this arrangement the
PEN N
PE distributor s neutral conductor is also used to return earth
Link
fault currents arising in the consumer s installation safely to
Additional the source. To achieve this, the distributor will provide a
Source
Earth T Source Electrode
N-C S consumer s earthing terminal which is linked to the
[combined neutral and (separate neutral (N) and incoming neutral conductor.
protective conductor (PEN) Protective conductors (PE)
in source of supply, within installation)
with PME applied]
4.TN-C system
If the N and PE neutral conductors are one and the same
TN-C System
(PEN) in the system than such a system is called a TN-C
Source of Installation
system. In this system RCD will trip in case of leakage only supply
L
through human body. So this system is most the dangerous Installation
Equipment
from the safety point of view.
PE N
T Exposed-
N-C conductive-part
Source
Earth
5. IT system
In an IT network, the distribution system has no connection
IT System
to the earth at all, or it has only a high impedance
L connection. In such systems, an insulation monitoring
Installation device is used to monitor the impedance. Only the IT system
N Equipment
guarantees risk-free continuity of supply in the presence of
an insulation fault.
IT
Consumer’s Earth
19
Comparison of earthing systems
High loop
Safety risks Double fault, Overvoltage Broken PE Broken neutral Broken Neutral
impedance
Continunity of operation,
Advantages Safe and reliable Safest Cost Safety and cost
cost
Choice of earthing
Choice of earthing system for an installation depends on harmonics in the system
parameters: 4. Environment (risk of lightning strike)
1. Safety of person 5. Quality, maintenance and cost
2. Continuity of supply 6. Network size
3. Sensitivity of the equipment to the presence of 7. Requirement of skilled operator and designer
20
Application of Different Types of Curves
Temperature Derating
As per IS/IEC 60898, thermal calibration of an MCB is to be done at 30°C and if the manufacturer decides to do it at any
other temperatures, the data has to be furnished on the breaker. When used at ambient temperatures exceeding the
calibrated temperatures, MCBs tend to trip faster while carrying the rated current. This calls for de-rating the MCBs when
used in ambiences, with temperatures higher than the design ambient temperature. At temperature higher than 30°C, the
MCB require progressively less time to trip on the same level of overload.
6 6 5.4 4.8
10 10 9 8
16 16 14.4 12.8
20 20 18 16
25 25 22.5 20
32 32 28.8 25.6
40 40 36 32
50 50 45 40
63 63 56.7 50.4
21
Current-limiting and Energy-limiting class Let thru energy is the amount of fault energy which passes
through a circuit breaker to downstream network
Current limitation is the technique used in circuit breakers
measured from the instant fault occurs in a system to the
to limit the short circuit current to reach its prospective
instant the circuit breaker clears the fault.
value.
IEC classify MCBs into three classes depending upon their
Current limitation can be achieved by following methods:
"Quality of current limiting" and let thru energy of a circuit
1. By Limiting the Fault breaker on short circuit class.
By series inductors coil lot of heat loss combined with Class 3 110 kA²S
bulky size of inductor coils.
As per EN-60898-1 -2003, for 10kA C-curve MCB
(Greater than 16A up to and including 32A)
2. By Current Limiting Technology
A current limiting circuit breaker cuts off the fault
Ip.14.1 kA peak
current much before it attains its peak value and hence
greatly reduces the thermodynamic stresses on an electrical
network.
A current limiting circuit breaker interrupts the fault current Let thru energy
within 5 msec and clears the fault within 10 msec to limit
the fault current and minimize let thru energy for maximum
3-5 ms 10 ms
protection of electrical network.
MCB
Some Important Definitions and Symbols the temperature rise test
Icm = rated short circuit making capacity 1.45 In Less than 1 hour
Icn = rated short circuit capacity
2.55 In 1 to 120 seconds
Ics = rated service short circuit breaking capacity
22
The inverse time delay characteristics of all MCBs complying with IEC 60898 must operate within these limits.
The difference between three types of characteristic curve B, C and D concer ns only the magnetic instantaneous trip
which provides short circuit protection.
100 100
Tripping Time T (s)
10 10
1 1
0.1 0.1
0.01 0.01
1 1.13 1.45 2 3 5 10 20 1 1.13 1.45 2 3 4 5 10 20
Multiple of Rated Current In (A) Multiple of Rated Current In (A)
100
Tripping Time T (s)
10
0.1
0.01
1 1.13 1.45 2 3 4 5 10 20
Multiple of Rated Current In (A)
Watt Loss
Current (A) In 6 10 16 20 25 32 40 50 63
Loss (Watt) 1.36 1.8 1.8 2.49 3.52 3.4 3.75 5.17 5.93
23
RCCB
Danger of Human Electrocution
2000
1000
500
1 2 3 4
200
100
50
20
10
0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 1000 2000 5000 10000 mA
Duration of current flow in the body as a function of current strength: In this graph, the effect
of AC current (15 to 100 Hz) has been divide into four zones (as per IEC60479-1).
24
Critical Current Thresholds conductor. If these do not sum to zero, there is a
leakage of current to somewhere else (to
According to the medical study, effect of various earth/ground, or to another circuit), and the
current levels on human bodies is as shown device will open its contacts.
below.
RCCBs have different current sensitivities which
can be used for various applications.
mA
Working Principle of RCCB To ensure safety, the RCCB switches turn off the protected
circuit immediately. If there is an insulation fault causing a
short-circuit to an exposed part (frame etc.) of machinery
and equipment (protection against indirect contact), the
L N
maximum permissible touch voltage U must occur at a
residual current greater than or equal to the rated residual
operating current I that triggers the In RCCB. This condition
is met by earthing the exposed part with a sufficiently low
1 resistance to earth RE.
Earth Resistance (RE) < Touch Voltage (U)
P
Faults existing downstream of the RCD
N
Indirect contact. An RCD may be used to provide
protection against electric shock due to indirect
contact in an installation.
Main Switch 30 mA RCD
Direct contact. An RCD may be used to provide
supplementary protection against direct contact.
In the above diagram, the external lighting circuit has been
Incorrect application. An RCD must be correctly incorrectly connected. The MCB supplying the circuit is
selected and erected for the particular application. For connected to the non-RCD-protected side of the split load
example, protecting an entire installation using a single board but the neutral conductor for the circuit has been
high sensitivity RCD can, in many cases, lead to inadvertently connected downstream of the RCD.
unwanted tripping, particularly in industrial
As soon as the outside light is energized, the RCD will see a
environments where inductive loads will cause greater
large imbalance and will operate. The neutral must be taken
transient overvoltages and where longer cable runs will
from the same final circuit, never from another circuit, as
result in larger values of capacitance to earth.
has happened in this example. Circuits must be kept
No discrimination between series connected RCDs. separate; in this example a borrowed neutral situation
A fault downstream of two series-connected RCDs may exists presenting a potential shock risk for an electrician
result in operation of either device. A fault downstream attempting to troubleshoot the problem.
of the second device will be seen by both devices.
Neutral-to-Earth fault. A neutral-to earth fault or
Inconvenience may result if the upstream device
in advertent connection of neutral to earth downstream
operates. Discrimination, where required, must be
of an RCD will probably result in the device operating as
ensured by means such as selecting a time delayed
part of the neutral current will flow in the circuit
device for the upstream device.
protective conductor resulting in the RCD seeing an
Loose connections. A loose connection downstream imbalance (refer fig below). A neutral-to-earth fault
of an RCD may cause it to operate due to transient can be caused by:
voltages or capacitive effects. Every connection must be
A neutral conductor touching an earthed mounting box
properly constructed of durable electrical continuity and
or earthed metal conduit
adequate mechanical strength correctly selected
enclosed and accessible, where required. Reversed neutral and earth connections at an accessory
or item of current-using equipment
Crossed neutral on split load distribution board or
consumer unit. Withdrawal of a fuse or switching off a circuit-breaker in
a final circuit resulting in an RCD tripping as the neutral
is normally not interrupted.
26
Mineral insulated cables. Mineral insulated cables can mains borne interference. Motors such as lift motors,
absorb moisture if not correctly terminated resulting in control gear for discharge lighting and transformer inrush
reduced insulation which may cause an RCD to trip as a currents can cause unwanted RCD operation. Although
certain amount of outgoing phase current will return significant transients can arise within an installation they
through the MI cable sheath causing the RCD to detect would normally only occur under fault conditions. They
an imbalance. Insulation testing should identify the might, however, travel to other installations where they
problem. could cause unwanted tripping of a RCD.
Moisture ingress can cause reduced insulation resulting Overhead lines: Unwanted tripping may occur more
in RCD operation. Reduced insulation can result from frequently in an installation supplied by overhead lines
wet plaster, condensation or water entry into compared to one supplied by an underground concentric
accessories. Similarly, some appliances may exhibit cable. An underground concentric cable is, by its very
reduced insulation causing RCD operation. Certain nature, a good attenuator of transient overvoltages.
installed services, such as heating elements in cookers Spurious tripping may be avoided by installing a filter
can have reduced insulation when cold; the insulation upstream of the RCD at the origin of the installation.
increasing when hot. The manufacturer s instructions
should be consulted. Domestic Installation (RCCBs)
Double-pole switching. Double pole switching within RCCBs can be installed mainly in two ways:
the fixed wiring is known to trip an RCD when switching
1.Whole house protection: In this type of protection the
off or on due to capacitive effects. Changing over from
RCCBs serve as the main switch. This type of protection is
double pole to single pole switching can overcome the
very popular but has a major disadvantage that all the
problem, where such replacement is permissible and
circuits are disconnected in the event of a fault.
safe.
2.Selective protection: This type of protection can be
divided into two types.
RCD detects A. Split busbar consumer unit: In this case all circuits
Imbalance and Operates are fed through an overall isolator and selected
circuits additionally through RCCBs. The examples of
P
selected circuits are socket outlets, garage circuits,
etc. So this reduces the inconvenience in the event of
fault.
N B. Per Phase Isolation (PPI): A RCCB is used as sub-
incomer for each individual phase. In case of a fault,
Neutral-earth
Some Current Returns Through only faulty phase will be disconnected and remaining
fault
E Circuit Protective Conductor phases will not be affected.
27
SPDs
a. IEC Standards
As per international standards, SPDs are classified as SPDs offer a lower surge capacity and provide a lower clamp
lightning current arresters (Class I), surge protection devices level than the primary suppressor. These SPDs also suppress
(Class II) or device protection (Class III). Each Class is defined any surge currents generated by induced lightning currents
by performance testing methods for surge current handling / partial lightning and operational switching action in the
capability. electrical network. These SPDs are tested with a 8/20s
Type 1 / Class I SPDs (Lightning Arresters) are mainly medium-energy or low-energy surge currents, and typically
installed in the electrical entry panel or the Main offer a VPL of around 1.5 kV. It is important to note that this
Distribution Panel. This is the first-stage protection in the voltage level can still potentially allow damage to sensitive
electrical network, and the surge arrester is designed to equipment. It is also interesting to note that some SPDs
divert lightning energy caused by over-voltage comparable offer combined Type 1 and 2 protection of loads against
to that of a direct lightning strike to the power lines or both direct and indirect lightning strokes.
28
Installation and Wiring
1 Install only in a restricted access power distribution cabinet that requires a key or tool to open.
4 Keep wires as short as possible (maximum length 0.5 m) and free of sharp bends.
5 Before installation, shut off power to prevent accidental electrical shock or injury.
6 The ground conductor should be insulated stranded copper greater than 10 mm2 (#6 AWG) diameter.
The power conductors should be copper stranded insulated gr eater than 6 mm2 (#10 AWG) diameter.
SPD selection
IEC 61643-1 Class I test Class II test (8/20 s) Class III test
EN/IEC 61643-11 Type 1 : (10/350 s) Type 2 : (8/20 s) Type 3 : (8/20 s)
29
CBMC/031018
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA CIN: L99999MH1946PLC004768