SIL Verification Sample Report

This document provides a SIL verification report for two Safety Instrumented Functions (SIFs) in a refinery expansion project. It includes details of the SIF design such as the logic solver, sensors and actuators used. It also contains calculations of Probability of Failure on Demand (PFDavg), Safety Integrity Level (SIL), Mean Time To Failure Safe (MTTFS), and other metrics to demonstrate that the required SIL is achieved.

Uploaded by

Ayman Fawzy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
74 views

SIL Verification Sample Report

This document provides a SIL verification report for two Safety Instrumented Functions (SIFs) in a refinery expansion project. It includes details of the SIF design such as the logic solver, sensors and actuators used. It also contains calculations of Probability of Failure on Demand (PFDavg), Safety Integrity Level (SIL), Mean Time To Failure Safe (MTTFS), and other metrics to demonstrate that the required SIL is achieved.

Uploaded by

Ayman Fawzy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

Sample: Detailed Report

Refinery Expansion

SIL verification Report

Annex I

2
1
0 27/01/2020 First review AHT AHT JB
Rev. Date Description Prepared Reviewed Approved

1
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M4-LT-1111-01
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-1 SIL SIL-1 PFDavg SIL-1 sensor SIL-1 5,77E-04 836
20 RRF 56 Arch. C. SIL-1 logic solver SIL-3 1,65E-04 209
Route 1H PFDavg 1,79E-02 SC SIL-2 actuator SIL-1 1,72E-02 125
10 MTTFS (y) 71 other -- -- --

On High High Level (LT-1) [1oo1] in Tank 100-1111 close valve XV-1 [1oo1] Used Tables of IEC61508 for all SIFs (Route 1H)

Factors for Maintenance Capability:


Cpt=1 TI=1
Out of range diagnostic: ON Sensor Fault: U.R. Channel Trip: No

LOGIC SOLVER
ESD-1
1oo1 1oo1
LT-1 1oo2D XV-1
Input Input Output Output
voting Safety PLC voting
group Model: Generic group

2
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M4-LT-1111-01

Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor LT-1 1oo1 5,77E-04 3 0 2 1 836
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --
sen_part interface -- -- 2 -- --
logicsolver ESD-1 1oo2D 1,65E-04 3 1 3 3 209

actuator XV-1 1oo1 1,72E-02 1 0 3 1 125


act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part isolator -- -- 3 -- --

Subsystem Tags Logic Cpt TI (y) LT (y) Beta MTTRdd Startup(h)


sensor LT-1 1oo1 95% 1,0 15 48 24
sen_part transmitter --
sen_part process --
sen_part interface --
logicsolver ESD-1 1oo2D 99% 4,0 15 2% 48 24

actuator XV-1 1oo1 73% 1,0 15 0 24


act_part valve --
act_part actuator --
act_part solenoid --
act_part isolator --

Subsystem Tags Logic SD SU DD DU Type SFF


sensor LT-1 1oo1 53 84 377 77 B 87,0%
sen_part transmitter -- 24 84 234 32 B 91,4%
sen_part process -- 0 0 0 0 A 0,0%
sen_part interface -- 29 0 143 45 A 79,4%
logicsolver ESD-1 1oo2D 11617 129 3815 241 B 98,5%

actuator XV-1 1oo1 0 916 0 829 A 52,5%


act_part valve -- 0 0 0 442 A 0,0%
act_part actuator -- 0 286 0 199 A 59,0%
act_part solenoid -- 0 516 0 188 A 73,3%
act_part isolator -- 0 114 0 0 A 100,0%

3
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M4-PT-2312-06
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-2 5,25E-05 3866
200 RRF 459 Arch. C. SIL-2 logic solver SIL-3 1,73E-04 201
Route 1H PFDavg 2,18E-03 SC SIL-3 actuator SIL-2 1,95E-03 66
10 MTTFS (y) 49 other -- -- --

On High High Pressure (PT-6A/B/C) [2oo3] in Vessel 100-2312 close valves Used Tables of IEC61508 for all SIFs (Route 1H)
XV-6A/B [1oo2]

Factors for Maintenance Capability:


Cpt=1 TI=1
Out of range diagnostic: ON Sensor Fault: -- Channel Trip: Yes

PT-6A
Input LOGIC SOLVER
ESD-1 XV-6A
2oo3 1oo2 Output
PT-6B 1oo2D
Input Input Output
voting Safety PLC voting XV-6B
group Model: Generic group Output
PT-6C
Input

4
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M4-PT-2312-06

Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor PT-6 2oo3 5,25E-05 4 1 3 2 3.866
sen_part transmitter -- -- 3 -- --
sen_part seal -- -- 3 -- --

logicsolver ESD-1 1oo2D 1,73E-04 3 1 3 3 201

actuator XV-6 1oo2 1,95E-03 2 1 3 2 66


act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part isolator -- -- 3 -- --

Subsystem Tags Logic Cpt TI (y) LT (y) Beta MTTRdd Startup(h)


sensor PT-6 2oo3 94% 1,0 15 5% 48 24
sen_part transmitter --
sen_part seal --

logicsolver ESD-1 1oo2D 99% 4,0 15 2% 48 24

actuator XV-6 1oo2 73% 1,0 15 10% 48 24


act_part valve --
act_part actuator --
act_part solenoid --
act_part isolator --

Subsystem Tags Logic SD SU DD DU Type SFF


sensor PT-6 2oo3 279 94 0 87 B 81,1%
sen_part transmitter -- 279 94 0 41 B 90,1%
sen_part seal -- 0 0 0 46 A 0,0%

logicsolver ESD-1 1oo2D 11852 136 3968 250 B 98,5%

actuator XV-6 1oo2 0 916 0 829 A 52,5%


act_part valve -- 0 0 0 442 A 0,0%
act_part actuator -- 0 286 0 199 A 59,0%
act_part solenoid -- 0 516 0 188 A 73,3%
act_part isolator -- 0 114 0 0 A 100,0%

5
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M5-FT-2312-30
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-3 2,54E-05 4176
200 RRF 244 Arch. C. SIL-2 logic solver SIL-3 1,78E-04 197
Route 1H PFDavg 4,11E-03 SC SIL-3 actuator SIL-2 3,90E-03 33
10 MTTFS (y) 28 other -- -- --

On Low Low Air Combustion Flow (FT-30A/B/C) [2oo3] in Incinerator 100- Used Tables of IEC61508 for all SIFs (Route 1H)
2312 closes Fuel Gas Valves (1oo2 XV-30/31) & Natural Gas Valves (1oo2
XV-32/33) [2oo2 of FG & NG]
Factors for Maintenance Capability:
Cpt=1 TI=1
Out of range diagnostic: ON Sensor Fault: -- Channel Trip: Yes

[FG] XV-30
1oo2 Output
FT-30A
Input LOGIC SOLVER Output
ESD-1 voting [FG] XV-31
2oo3 2oo2 group Output
FT-30B 1oo2D
Input Input Output
voting Safety PLC Group [NG] XV-32
group Model: Generic 1oo2 Output
FT-30C
Input Output
voting [NG] XV-33
group Output

6
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

SIF: M5-FT-2312-30

Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor FT-30 2oo3 2,54E-05 4 1 3 3 4.176
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --

logicsolver ESD-1 1oo2D 1,78E-04 3 1 3 3 197

actuator [FG] XV-30/31 1oo2 1,95E-03 2 1 3 2 66


actuator [NG] XV-32/33 1oo2 1,95E-03 2 1 3 2 66

Subsystem Tags Logic Cpt TI (y) LT (y) Beta MTTRdd Startup(h)


sensor FT-30 2oo3 90% 1,0 15 5% 48 24
sen_part transmitter --
sen_part process --

logicsolver ESD-1 1oo2D 99% 4,0 15 2% 48 24

actuator [FG] XV-30/31 1oo2 73% 1,0 15 10% 48 24


actuator [NG] XV-32/33 1oo2 73% 1,0 15 10% 48 24

Subsystem Tags Logic SD SU DD DU Type SFF


sensor FT-30 2oo3 258 84 0 32 B 91,4%
sen_part transmitter -- 258 84 0 32 B 91,4%
sen_part process -- 0 0 0 0 A 0,0%

logicsolver ESD-1 1oo2D 12130 138 4082 256 B 98,5%

actuator [FG] XV-30/31 1oo2 0 916 0 829 A 52,5%


actuator [NG] XV-32/33 1oo2 0 916 0 829 A 52,5%

7
Client name

Project: Refinery Expansion Rev.1 by JB

SIL verification of Safety Instrumented Functions

Groups: [Fuel-Gas] XV-30/31 & [N.Gas] XV-32/33

Subsystem Tags Logic SD SU DD DU Type SFF


actuator [FG] XV-30/31 1oo2 0 916 0 829 A 52,5%
act_part valve -- 0 0 0 442 A 0,0%
act_part actuator -- 0 286 0 199 A 59,0%
act_part solenoid -- 0 516 0 188 A 73,3%
act_part driver -- 0 114 0 0 A 100,0%

actuator [NG] XV-32/33 1oo2 0 916 0 829 A 52,5%


act_part valve -- 0 0 0 442 A 0,0%
act_part actuator -- 0 286 0 199 A 59,0%
act_part solenoid -- 0 516 0 188 A 73,3%
act_part driver -- 0 114 0 0 A 100,0%

Subsystem Tags Logic Cpt TI (y) LT (y) Beta MTTRdd Startup(h)


actuator [FG] XV-30/31 1oo2 73% 1,0 15 10% 48 24
act_part valve --
act_part actuator --
act_part solenoid --
act_part driver --

actuator [NG] XV-32/33 1oo2 73% 1,0 15 10% 48 24


act_part valve --
act_part actuator --
act_part solenoid --
act_part driver --

Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
actuator [FG] XV-30/31 1oo2 1,95E-03 2 1 3 2 66
act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part driver -- -- 3 -- --

actuator [NG] XV-32/33 1oo2 1,95E-03 2 1 3 2 66


act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part driver -- -- 3 -- --