SIL Verification Sample Report
SIL Verification Sample Report
Refinery Expansion
Annex I
2
1
0 27/01/2020 First review AHT AHT JB
Rev. Date Description Prepared Reviewed Approved
1
Client name
SIF: M4-LT-1111-01
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-1 SIL SIL-1 PFDavg SIL-1 sensor SIL-1 5,77E-04 836
20 RRF 56 Arch. C. SIL-1 logic solver SIL-3 1,65E-04 209
Route 1H PFDavg 1,79E-02 SC SIL-2 actuator SIL-1 1,72E-02 125
10 MTTFS (y) 71 other -- -- --
On High High Level (LT-1) [1oo1] in Tank 100-1111 close valve XV-1 [1oo1] Used Tables of IEC61508 for all SIFs (Route 1H)
LOGIC SOLVER
ESD-1
1oo1 1oo1
LT-1 1oo2D XV-1
Input Input Output Output
voting Safety PLC voting
group Model: Generic group
2
Client name
SIF: M4-LT-1111-01
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor LT-1 1oo1 5,77E-04 3 0 2 1 836
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --
sen_part interface -- -- 2 -- --
logicsolver ESD-1 1oo2D 1,65E-04 3 1 3 3 209
3
Client name
SIF: M4-PT-2312-06
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-2 5,25E-05 3866
200 RRF 459 Arch. C. SIL-2 logic solver SIL-3 1,73E-04 201
Route 1H PFDavg 2,18E-03 SC SIL-3 actuator SIL-2 1,95E-03 66
10 MTTFS (y) 49 other -- -- --
On High High Pressure (PT-6A/B/C) [2oo3] in Vessel 100-2312 close valves Used Tables of IEC61508 for all SIFs (Route 1H)
XV-6A/B [1oo2]
PT-6A
Input LOGIC SOLVER
ESD-1 XV-6A
2oo3 1oo2 Output
PT-6B 1oo2D
Input Input Output
voting Safety PLC voting XV-6B
group Model: Generic group Output
PT-6C
Input
4
Client name
SIF: M4-PT-2312-06
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor PT-6 2oo3 5,25E-05 4 1 3 2 3.866
sen_part transmitter -- -- 3 -- --
sen_part seal -- -- 3 -- --
5
Client name
SIF: M5-FT-2312-30
Required Achieved Achieved Achieved PFDavg MTTFS (years)
SIL-2 SIL SIL-2 PFDavg SIL-2 sensor SIL-3 2,54E-05 4176
200 RRF 244 Arch. C. SIL-2 logic solver SIL-3 1,78E-04 197
Route 1H PFDavg 4,11E-03 SC SIL-3 actuator SIL-2 3,90E-03 33
10 MTTFS (y) 28 other -- -- --
On Low Low Air Combustion Flow (FT-30A/B/C) [2oo3] in Incinerator 100- Used Tables of IEC61508 for all SIFs (Route 1H)
2312 closes Fuel Gas Valves (1oo2 XV-30/31) & Natural Gas Valves (1oo2
XV-32/33) [2oo2 of FG & NG]
Factors for Maintenance Capability:
Cpt=1 TI=1
Out of range diagnostic: ON Sensor Fault: -- Channel Trip: Yes
[FG] XV-30
1oo2 Output
FT-30A
Input LOGIC SOLVER Output
ESD-1 voting [FG] XV-31
2oo3 2oo2 group Output
FT-30B 1oo2D
Input Input Output
voting Safety PLC Group [NG] XV-32
group Model: Generic 1oo2 Output
FT-30C
Input Output
voting [NG] XV-33
group Output
6
Client name
SIF: M5-FT-2312-30
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
sensor FT-30 2oo3 2,54E-05 4 1 3 3 4.176
sen_part transmitter -- -- 3 -- --
sen_part process -- -- -- --
7
Client name
Subsystem Tags Logic PFDavg SIL (pfd) HFT SC SIL (arch) MTTFS (y)
actuator [FG] XV-30/31 1oo2 1,95E-03 2 1 3 2 66
act_part valve -- -- 3 -- --
act_part actuator -- -- 3 -- --
act_part solenoid -- -- 3 -- --
act_part driver -- -- 3 -- --