06-326 CyberCat
06-326 CyberCat
Fike copyrights this manual and products it describes. You may not reproduce,
transmit, transcribe, or any part of this manual without express, written
permission from Fike.
QUALITY Fike has maintained ISO 9001 certification since 1996. Prior to shipment, we
thoroughly test our products and review our documentation to assure the highest
quality in all respects.
WARRANTY Fike provides a one-year limited manufacturer’s warranty on this product. All
warranty returns must be returned from an authorized Fike Distributor. Contact
Fike’s Marketing department for further warranty information.
Fike maintains a repair department that is available to repair and return existing
electronic components or exchange/purchase previously repaired inventory
component (advance replacement). All returns must be approved prior to return.
A Material Return Authorization (MRA) number must be indicated on the box of
the item being returned. Contact the appropriate Regional Sales Manager for
further information regarding product return procedures.
LIMITATIONS OF LIABILITY Installation in accordance with this manual, applicable codes, and the
instructions of the Authority Having Jurisdiction is mandatory. Fike can not be
held liable for any incidental or consequential damages arising from the loss of
property or other damages or losses resulting from the use or misuse of Fike
products beyond the cost of repair or replacement of any defective components.
Fike reserves the right to make product improvements and change product
specifications at any time.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its content, Fike assumes no responsibility for errors or
omissions.
CONTENT
TABLE OF CONTENTS
SECTION DESCRIPTION PAGE
Revision History......................................................................................................................ix
About This Manual ...................................................................................................................x
Product Support.......................................................................................................................x
Safety Information....................................................................................................................x
Terms Used In This Manual ....................................................................................................x
1.0 Product Overview................................................................................................................. 1-1
1.1 System Description ................................................................................................................ 1-1
1.2 Listings and Approvals........................................................................................................... 1-2
1.3 Agency Standards and Compliance....................................................................................... 1-2
1.4 Related Documentation ......................................................................................................... 1-3
1.5 CyberCat Features................................................................................................................. 1-4
2.0 System Components ........................................................................................................... 2-1
2.1 System Modules..................................................................................................................... 2-1
2.2 Addressable Devices ............................................................................................................. 2-2
2.3 Programming/Configuration Equipment................................................................................. 2-3
2.4 Notification Appliances........................................................................................................... 2-3
2.5 Factory Mutual Approved Solenoids ...................................................................................... 2-3
2.6 Batteries and Battery Enclosures........................................................................................... 2-3
2.7 Spare Parts ............................................................................................................................ 2-4
2.8 System Component Specifications ........................................................................................ 2-5
2.8.1 Basic Equipment Packages ................................................................................................... 2-5
2.8.2 Enclosures ............................................................................................................................. 2-5
2.8.2.1 Standard Enclosure................................................................................................................ 2-6
2.8.2.2 Standard Enclosure with Solid Deadfront Option .................................................................. 2-6
2.8.2.3 Deadfront Enclosure with Three Module Option.................................................................... 2-7
2.8.2.4 Deadfront Enclosure Thirteen Module Option ....................................................................... 2-7
2.8.3 CyberCat Controller ............................................................................................................... 2-8
2.8.4 DACT ................................................................................................................................... 2-16
2.8.5 DACT Programmer .............................................................................................................. 2-16
2.8.6 Supplemental Power Supply (SPS) ..................................................................................... 2-17
2.8.7 Supplemental Loop Module (SLM) ...................................................................................... 2-18
2.8.8 Relay Module (CRM4) ......................................................................................................... 2-19
2.8.9 Reverse Polarity Module (RPM) .......................................................................................... 2-19
2.8.10 Network Module ................................................................................................................... 2-20
2.8.11 Fiber Optic Network Module ................................................................................................ 2-20
2.8.12 Remote LCD Display............................................................................................................ 2-20
2.8.13 14 Button Remote Display ................................................................................................... 2-21
2.8.14 10 Button Remote Display ................................................................................................... 2-21
2.8.15 2 Button Remote Display ..................................................................................................... 2-21
2.8.16 Zone Annunciator................................................................................................................. 2-21
2.8.17 VESDA HLI Interface ........................................................................................................... 2-22
2.8.18 Ethernet Module................................................................................................................... 2-22
2.8.19 Multi-Interface Module ......................................................................................................... 2-22
2.8.20 Addressable LED Graphic ................................................................................................... 2-23
2.8.21 Firefighter’s Smoke Control Graphic.................................................................................... 2-23
2.8.22 6 Zone, Smoke Control Switch Module................................................................................ 2-23
2.8.23 20 Zone, Input/Output Switch Module.................................................................................. 2-24
2.8.24 20 Zone, Annunciator Module.............................................................................................. 2-24
2.9 Addressable Device Specifications...................................................................................... 2-24
2.9.1 Photoelectric Smoke Sensor................................................................................................ 2-25
2.9.2 Ionization Smoke Sensor ..................................................................................................... 2-25
2.9.3 Photoelectric/Heat Sensor ................................................................................................... 2-26
LIST OF EXHIBITS
EXHIBIT DESCRIPTION PAGE
1-1 CyberCat Block Diagram ....................................................................................................... 1-1
2-1 CyberCat System Package.................................................................................................... 2-5
2-2 Standard Enclosure................................................................................................................ 2-6
2-3 Standard Enclosure (Solid Deadfront Option) ....................................................................... 2-6
2-4 Deadfront Enclosure (Three Module Option)......................................................................... 2-7
2-5 Deadfront Enclosure (Thirteen Module Option) ..................................................................... 2-7
2-6 CyberCat Controller ............................................................................................................... 2-8
2-7 CyberCat Controller (-exd)..................................................................................................... 2-8
2-8 CyberCat Terminal Block Locations....................................................................................... 2-9
2-9 DACT ................................................................................................................................... 2-16
2-10 DACT Programmer .............................................................................................................. 2-16
2-11 SPS ...................................................................................................................................... 2-17
2-12 SLM ...................................................................................................................................... 2-18
2-13 CRM4 ................................................................................................................................... 2-19
2-14 CRPM................................................................................................................................... 2-19
2-15 Network Module ................................................................................................................... 2-20
2-16 Fiber Optic Network Module ................................................................................................ 2-20
2-17 Remote LCD Display............................................................................................................ 2-20
2-18 14 Button Remote Display ................................................................................................... 2-21
2-19 10 Button Remote Display ................................................................................................... 2-21
2-20 2 Button Remote Display ..................................................................................................... 2-21
2-21 Zone Annunciator................................................................................................................. 2-21
2-22 VESDA Open Protocol HLI .................................................................................................. 2-22
2-23 Ethernet Module................................................................................................................... 2-22
2-24 Multi-Interface Module ......................................................................................................... 2-22
2-25 LED Graphic......................................................................................................................... 2-23
2-26 Firefighter’s Smoke Control Station ..................................................................................... 2-23
2-27 Remote Twenty Zone Annunciator ...................................................................................... 2-23
2-28 Smoke Control Module ........................................................................................................ 2-24
2-29 I/O Switch Module ................................................................................................................ 2-24
2-30 Twenty Zone Annunciator Module ....................................................................................... 2-24
2-31 Photo Sensor ....................................................................................................................... 2-25
2-32 Ion Sensor............................................................................................................................ 2-25
2-33 Photo/Heat Sensor............................................................................................................... 2-26
2-34 Heat Sensor ......................................................................................................................... 2-26
2-35 6 inch Base .......................................................................................................................... 2-27
2-36 4 inch Base .......................................................................................................................... 2-27
2-37 Sounder Base ...................................................................................................................... 2-27
2-38 Relay Base........................................................................................................................... 2-27
2-39 Mini Monitor Module............................................................................................................. 2-28
2-40 4 inch Monitor Module.......................................................................................................... 2-28
2-41 Dual Monitor Module ............................................................................................................ 2-29
LIST OF TABLES
TABLE DESCRIPTION PAGE
1-1 Related Documentation ......................................................................................................... 1-3
2-1 Compatible System Modules ................................................................................................. 2-1
2-2 Standard Devices (Style 4 or 6 wiring)................................................................................... 2-2
2-3 Isolator Devices (Style 7 wiring)............................................................................................. 2-2
2-4 Configuration, Testing, and/or Diagnostics Equipment.......................................................... 2-3
2-5 Battery and Battery Enclosures ............................................................................................. 2-3
2-6 Spare Parts ............................................................................................................................ 2-4
2-7 System Ordering Formats...................................................................................................... 2-5
2-8 Enclosure Ordering Formats.................................................................................................. 2-5
2-9 P1 Power Input Specifications ............................................................................................. 2-11
2-10 P2 P2 Relay Specifications.................................................................................................. 2-12
2-11 P3-P5 RS232 Specifications................................................................................................ 2-12
2-12 P6 RS485 Specifications ..................................................................................................... 2-13
2-13 P7 Auxiliary Power Specifications........................................................................................ 2-13
2-14 P8-P9 SLC Specifications.................................................................................................... 2-14
2-15 P10-P11 NAC Specifications ............................................................................................... 2-15
2-16 NAC Circuit Field Wiring Resistance ................................................................................... 2-15
2-17 Compatible DACT Receivers ............................................................................................... 2-17
2-18 SPS Specifications............................................................................................................... 2-18
2-19 SLM Specifications............................................................................................................... 2-19
2-20 CRM4 Specifications............................................................................................................ 2-20
2-21 RPM Specifications .............................................................................................................. 2-20
2-22 Network Module Specifications............................................................................................ 2-21
4-1 General Wiring Specifications................................................................................................ 4-7
4-2 SLC Performance................................................................................................................. 4-16
6-1 Event Description/History Messages ..................................................................................... 6-6
REVISION HISTORY
Document Title: CyberCat Addressable Fire Alarm System Product Manual
Document Reorder Number: 06-326
Revision Section Date Reason for Change
0 All Sections 09/2004 Initial Release
Added CyberCat 254 and programming
1 All Sections 12/2004
menu’s
Added Networking, Isolator devices,
2 All Sections 05/2005
sounder bases
3 All Sections 08/2007 Upgraded Firmware to Version 3.0
Normal State - (“Trouble” Yellow LED OFF) The Power-Limited - A circuit designation given for
system is in the normal state when the power wiring purposes. The amount of current flowing
supply and all circuits are configured properly, through the circuit is limited (typically by fuse) vs.
connected, and responding properly. The system being unlimited, or non-power-limited. The
remains in normal state until a trouble condition CyberCat addressable loops and output circuits are
occurs. power-limited. The circuit has a maximum power
that flows through it or it current limits and opens
Notification Appliance - A fire alarm system
the circuit.
component such as a bell, horn, speaker, light, or
textual display that provides audible, tactile, or Supervisory State - (“Supervisory” Yellow LED
visible output, or any combination thereof. The ON, Piezo Warble) The supervisory state occurs
device notifies building occupants of system status. upon activation of a supervisory input circuit. The
This manual interchanges the terms notification supervisory state is non-latching and will follow the
and audible appliance. status of the supervisory input contact.
Notification Appliance Circuit - A circuit or path Trouble State - (“Trouble” Yellow LED ON, Piezo
directly connected to a notification appliance(s). Constant) The trouble state occurs upon any
This manual interchanges the terms notification detectable condition which could impair system
appliance circuit and audible circuit. operation including connection problems, ground
faults, hardware problems, power problems, or
Non Power-Limited - A circuit designation given
configuration problems. Certain trouble conditions
for wiring purposes. The amount of current flowing
are latching; others allow the system to reset upon
through the circuit is unlimited vs. being limited, or
trouble condition removal. Depending upon the
power-limited. AC power and Battery wiring is Non
type of trouble condition, the system may or may
Power-limited.
not remain operational. When the system is in
trouble state, it is not in the normal state.
COMPATIBLE DETECTORS
EXTERNAL
BATTERIES
SUPERVISED NAC CIRCUIT
SUPERVISED NAC CIRCUIT
COMPATIBLE
CONVENTIONAL
DETECTORS
The installer should also be familiar with the following documents and standards:
National Fire Protection Association (NFPA) Codes:
NFPA 13 – Sprinkler Systems
NFPA 15 – Water Spray Fixed Systems
NFPA 16 – Deluge, Foam-water and Foam-water Spray Systems
NFPA 70 – National Electrical Code (NEC)
NFPA 70, Article 300 – Wiring Methods
NFPA 70, Article 760 – Fire Protective Signaling Systems
NFPA 72 – National Fire Alarm Code
NFPA 101 – Life Safety Code
NFPA 110 – Emergency Standby Power Systems
Underwriters Laboratories (UL) Standards:
UL 38 – Manually Actuated Signaling Boxes
UL 217 – Smoke Detectors, Single and Multiple Station
UL 228 – Door Closers – Holders for Fire Protective Signaling Systems
UL 268 – Smoke Detectors for Fire Protective Signaling Systems
UL 268A – Smoke Detectors for Duct Applications
UL 346 – Waterflow Indicators for Fire Protective Signaling Systems
UL 464 – Audible Signaling Appliances
UL 521 – Heat Detectors for Fire Protective Signaling Systems
UL 1481 – Power Supplies for Fire Protective Signaling Systems
UL 1638 – Visual Signaling Appliances
UL 1971 – Visual Signaling Appliances
Factory Mutual (FM) Standards:
FMRC 1011 and 1012 – Deluge and Pre-action Sprinkler Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
♦ Removable terminal blocks for field wiring ♦ Devices contain multi-color LED for quick
reference of device status
♦ Local piezo with distinct event tones
♦ Sensors provide early warning pre-alarm
♦ 10 Status LED’s to easily identify system status detection and can also provide a summing
♦ Available with and without integral SERIAL, feature (up to 8 sensors), non-listed.
Point ID DACT interface ♦ Sounder or Relay Bases fully programmable
♦ Supports up to 31 peripheral devices such as ♦ Optional Remote LED can be added to a sensor
Remote Display, LED Graphics, and Smoke base, programmable for any device, zone/state
Control Switch Cards
♦ Compatible with internal or external Firefighter’s ENCLOSURE
Smoke Control Station Modules
♦ Three steel enclosures are available to suite
♦ Supports ability to network up to 128 nodes system requirements.
(each could be CyberCat 254 or 1016)
♦ Enclosures are equipped with a 0.50” wide lip to
facilitate flush mounting
POWER
♦ Removable door and deadfront panel for ease of
♦ 6 amps useable alarm power, 2A standby- installation
CyberCat 1016 expandable to 12 amps alarm
power, 4 A standby ♦ Two door options available: with or without lexan
cover on oval opening
♦ Operation from 120VAC/ 60 Hz or 240VAC 50
/60Hz ♦ Available in Red or Black
Remote Supervising
Protected Premises
Station (PPU/SSU)
Releasing Service
Y = Yes
N = No
FM Approved
Station (PPU)
O = Optional
ULC Listed
(Sprinkler)
UL Listed
(Local)
(PPU)
Part Number
(isolator version) Description
10-2620 CyberCat 50 Controller Y Y Y Y Y Y Y Y Y
10-2621 Enclosure Y Y Y Y Y Y Y Y Y
10-2628 Dead front Panel Y Y Y Y Y Y Y Y Y
02-10881 (Note 1) 120VAC Primary Transformer Y Y Y Y Y Y Y Y Y
02-10882 (Note 1) 240VAC Primary Transformer O O O O O O Y Y Y
10-2528 (Note 2) 5-Zone DACT (Bosch Model D9068), internal O Y Y O O O Y Y Y
10-2476 (Note 2) 5-Zone DACT (Bosch Model D9602), external O O O O O O Y Y Y
10-2321 Remote Display O O O O O O Y Y Y
10-2373 Zone Annunciator O O O O O O Y Y Y
10-2627 Ethernet Module O O O Y O O Y Y Y
10-2583 Multi-Interface Module O O O Y O O Y Y Y
68-023 VESDA Open Protocol High Level Interface (HLI) O O O O O O Y Y Y
10-1XX Intelligent Graphic Panel O O O O O O Y Y Y
10-2667 20-Zone Remote Annunciator O O O O O O Y Y Y
63-1052 (63-1058) Photoelectric Sensor O O O O O O Y Y Y
67-033 (67-034) Ionization Sensor O O O O O O Y Y Y
63-1053 (63-1059) Combination Photo/135°F Heat Sensor O O O O O O Y Y Y
60-1039 (60-1040) Heat Detector, 135°F-190°F (57-88°C) FT/RR O O O O O O Y Y Y
63-1054 (63-1060) Sensor Base, 6-inch O O O O O O Y Y Y
63-1055 (63-1061) Sensor Base, 4-inch O O O O O O Y Y Y
63-1064 Sounder Base, 6-inch O O O O O O Y Y Y
63-1063 Relay Base, 6-inch O O O O O O Y Y Y
55-045 (55-050) MMM – Mini Monitor Module (Note 3) O O O O O Y Y Y Y
55-041 (55-046) MM – Monitor Module 4-inch (Note 3) O O O O O Y Y Y Y
20-1063 (20-1064) APS – Addressable Pull Station O O O O O O Y Y Y
55-042 (55-047) SCM – Supervised Control Module O O O O Y Y Y Y Y
10-2360 Series Solenoid Diode/Resistor O O O O O Y Y Y Y
10-2413 Masterbox Module O O O O Y O Y Y Y
55-043 RM – Relay Module O O O O O O Y Y Y
63-1057 (63-1062) Photo Duct Sensor O O O O O O Y Y Y
63-1056 Duct Detector Housing with relays (isolator base) O O O O O O Y Y Y
55-055 (55-060) Conventional Zone Monitor Module O O O O O O Y Y Y
55-056 (55-061) Dual Monitor Module O O O O O O Y Y Y
10-2658 Six Zone Smoke Control Module
10-2659 Input/Output Control Module
10-2660 Twenty Zone Annunciator Module
10-2663/10-2665 Smoke Control Module / Switch-LED Driver Module
10-2667 Twenty Zone Remote Annunciator Module
Notes: 1. Only one transformer (120VAC or 240VAC) can be used.
2. DACT may be mounted internal or external to control panel enclosure.
3. Module is required to monitor sprinkler system components (e.g., Waterflow, Tamper, Low Air, etc.).
Permitted
in UL Settings
Circuit or 864? Possible Settings permitted
Component Program Feature or Option (Y/N) (Defaults shown bold) in UL 864 Notes
Main Board Configuration Options
MISC. AC Trouble Delay Y 0-12 hours
Walktest Y Enabled / Disabled
Transformer Y 120VAC / 240VAC
Loop Wiring Style (SLC) Y 4, 6, or 7
Main Battery Y Supervised / Unsupervised
Unsilence Time Y 0-24 hours
Silence Reminder Y Enabled / Disabled
Silence Inhibit Y Enabled / Disabled
Positive Alarm Sequence Y Enabled / Disabled
Daytime Sensitivities start/stop Y 12am – 12am
time
Days that use daytime sensitivity Y Sunday – Saturday
Use Daylight Savings Option Y Enabled / Disabled
Holidays for Night time sensitivity Y 20 days total
DACT Auto test start hour Y 0 – 23 (2 default)
DACT Auto test period (hrs.) Y 0 - 24
NAC 1 & 2 Sync Protocol Y NO / Gentex / System Sensor / Note 1
Wheelock
State (Activation) Y Alarm / Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process
Silenceable Y Silenceable / Non silenceable
Zone Assignment Y 1 – 255
Circuit Enable/Disable Y Enabled / Disabled
Drill Y Enabled / Disabled
Walktest Y Enabled / Disabled
Relay 1 & 2 State (Activation) Y Alarm / Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Zone
Disable
Silenceable Y Non-Silenceable /
Silenceable
Circuit Enable/Disable Y Enabled / Disabled
Zone Assignment Y 1 – 255
Drill Y Enabled / Disabled
Zones Zones Y 1 – 254
Zone Type Y Alarm
Zone Enable/Disable Y Enabled / Disabled
Custom Message Y 20 character user defined
(CUSTOM MESS ZONE ZZZ)
where ZZZ = zone number
Notes:
1. If synchronization is selected, both circuits will sync.
2. Device must be added to the Peripherals list before the following configuration options are available.
3. Not used for CyberCat 50 panel.
4. EVAX is not available on the CyberCat 50; Leave set to OFF.
5. This command contains status for Alarm, Supervisory, Trouble and all other states. Peripheral devices that have
firmware version before 3.00 should set this variable to STD, which is the original CyberCat format. The EXP
selection refers to an ‘Expanded’ format of the 1.2 command. Peripheral devices with new 3.00 firmware will use this
command. The EXP speeds up operation of the peripheral bus and is the factory default setting.
6. The selection VERBOSE will transmit all history messages. With the selection COMPACT a message filter with in
the panel is used to prevent transmission of certain history record events, including the NEW DEVICE history
messages. This is done so that the peripherals do not display messages that are not required.
7. The variable HISTORY PACKING refers to how many history records are transmitted back-to-back with minimum
time in between. The selection UNPACKED means that history messages are sent one at a time. The selection
PACKED means that up to 50 history events are sent back-to-back. This technique will speed up the transmission of
large amounts of history data.
8. The variable HISTORY MESSAGE refers to what kind of data is packed into the history command. The STD
(Standard) selection means data is packed as with previous versions. The EXP (Expanded) selection means that
both lines 1 and 2 of the history data as shown on the LCS of the panel is packed into the history command.
9. Networking with the CyberCat 50 panel can only be accomplished by using the 10-2627 Ethernet Module.
10. Defines the location of the panel with respect to others on the network. Not used with CyberCat 50.
11. Defines if the respective panel will react to Reset, Silence, Acknowledge, and Drill commands received from other
networked panels.
12. Defines which network zones will participate in the local panel zone(s).
13. Defines which network panel(s) the selected panel should supervise.
14. Defines the unique Internet Protocol (IP) address for the selected panel.
15. Defines the unique Internet Protocol (IP) address for the panel that is to receive history events from the selected
panel.
16. Defines the unique Internet Protocol (IP) address for the panel that is to supervision responses from the selected
panel.
17. Used to synchronize panel time over the network.
18. Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
19. Pre-Alarm 2 setting must always be set equal or higher than Pre-Alarm 1 setting.
20. High setting must be equal or lower obscuration setting than Low setting.
21. Can be set in 1% increments. Trouble must be higher % than Warning.
22. If Independent operation, Sounder Base, or Relay Base is selected, an 8-row priority table will be displayed. Select
activation state, activation type, and output pattern for each priority row (row 1 has higher priority).
23. Rate of Rise temperature range is 135°F - 174°F. Fixed temperature operation will be used for detection above this
range.
24. Either = PA1, PA2, Supervisory, Trouble, Process, PAS Inhibit; Non-Latch = Reset, Silence, Acknowledge, Zone
Disable, Fan Restart; Latching = ManAlarm, Detection, Waterflow, Drill.
25. NO Contacts = Detection, Manual Alarm, Reset, Supervisory; NO/NC Contacts = Process, Waterflow, PA1, PA2,
Trouble, Drill, Silence, Acknowledge, Zone Disable, PAS Inhibit, Fan Restart.
26. Modifies control module configuration for use with Pre-Action solenoid.
27. Can be assigned to Any of 3 Zones, All of 3 Zones, Specific Device or Multiple Conditions (Priority Table).
28. Process and Zone Disable will require a zone number be assigned (1 – 253).
29. Point ID used only for reporting device information to DACT.
30. LED assignment is tied to LED function selected.
L*Note: The 10-2474-p Supplemental Power Supply (SPS) and 10-2473, Supplemental Loop
Module (SLM) are only compatible with the CyberCat 1016 product.
Table 2-3: Isolator Devices (required for Style 7 wiring – base and head if applicable)
Part Number Description
63-1058 Photo Sensor with Isolator)
67-034 Ionization Sensor with Isolator
63-1059 Photo/135° F Heat Combination Sensor with Isolator
60-1040 Intelligent Heat Det., 135°-190° F (57°-88° C) Fixed Temp./ Rate of Rise with Isolator
63-1060 Sensor Base, 6 inch with Isolator
63-1061 Sensor Base, 4 inch with Isolator
55-050 MMM – Mini Monitor Module with Isolator
55-046 MM – Monitor Module, 4 inch with Isolator
20-1064 PSMM – Pull Station Monitor Module with Isolator
55-047 SCM – Supervised Control Module with Isolator
55-048 RM – Relay Module with Isolator
63-1062 Photo DUCT sensor with Isolator (for replacement)
55-060 Conventional Zone Monitor Module with Isolator
55-061 Dual Monitor Module with Isolator
02-4035 Hardware Kit, #6 lock washers and hex nuts (30 each)
02-10788 Standoff kit, 5/8” M/F, 5 each required (10 each supplied)
02-4009 Standoff, 2” M/F, for 10-2528 DACT, 4 each required (1 each supplied)
02-10998 Terminal Block, 5 position for P8-P11, P31-P32 SLC or NAC circuits
02-11151 14KΩ Series Resistor, for Monitor Module Short Circuit detection
10-2570 End of Line Resistor, 1.2 K (for NAC 1 & 2)
02-4174 Fuse, 15 Amp, Mini-Auto, Fast Acting (For F1 & F2) (Littelfuse p/n 297015)
02-11412 Fuse, 4 Amp, Mini-Auto, Fast Acting (For F3-5) (Littelfuse p/n 297004)
The following pages indicate the specifications for the 10-2472 / 10-2525 controllers listed in order of terminal
block designation (P) as shown in Exhibit 2-8:
P2 P6 P7
P3 P4 P5
P13 P20
P8
P12
P9
P10
P11
I Caution
It is critical that AC is applied to the left terminals of P1 and NOT the right terminals (battery) 3 and 4. Damage
to the controller could occur if not followed. See Section 4.7
LNote: System AC line power MUST originate from a dedicated circuit at the main building power
distribution center. The circuit breaker shall be equipped with a lockout mechanism and be clearly
labeled as a “Fire Protection Control Circuit.”
P2 – Relays:
Table 2-10: P2 Relay Specifications
LNote: *May be connected to power-limited or non power-limited sources. All connections to terminal block
shall be either power limited or non-power limited, not both.
P7 – Auxiliary Power:
LNote: The standard CyberCat Control Panel has a total power capability of 6A. The CyberCat 1016 is
expandable to 12A with the addition of Supplemental Power Supply p/n 10-2474-p. Use Battery Calculation
software in C-Linx Software or the form in Appendix 1 to determine proper system design.
Addressable
Loop 2
P9 Power Limited Same as noted in Loop 1 above
(Available on
+ - SHLD ++ -- CyberCat 1016 Supervised
ONLY)
L*Note: SLC voltage will range from 24 VDC nominal to 0-5 VDC level during data communication pulse.
During normal operation, with a meter connected, the voltage should measure between 0-24 VDC. It
should never measure a constant 0 VDC.
Power Limited
P11 Notification
Appliance Supervised Same as noted in NAC1 above
+ - SHLD ++ -- Circuit 2
No t-tapping
The NAC circuit field wiring resistance is limited by the amount of anticipated load. Many local authorities
require a voltage drop calculation be performed to demonstrate the lowest voltage present at the last device.
The designer shall determine the resistance of the wire specified and distance for the installation needs. From
this information, they can determine the total resistance for the circuit. Table 2-16 provides the maximum field
wiring resistance for total device current that can also be used as a tool:
Max Current
.1 .2 .3 .4 .5 .6 .8 1.0 1.5 2.0
(Amps)
Refer to Fike document 06-186, “Compatible Notification Appliances and Releasing Devices Manual” for more
details.
P20 – Optional Module, 10-2482 Network or 10-2624 Fiber Optic Network Module
Connects 10-2482 Network module and provides capability to network/communicate 128 total network devices
(panels) at distances up to 4000 feet (1219m) between devices (panels).
Connects 10-2624 Multi-Mode Fiber Optic module and provides capability to network/communicate 128 total
network devices (panels) at distances up to 3 Km (9,842.5 feet) between devices (panels).
Contact ID √ √ √ √ √
SIA 300 √ √ √
SIA 110 √ √ √
4/2 √ √ √ √ √ √
The 10-2474-p (Exhibit 2-11) includes the power supply circuit board and
transformer (-1 for 120VAC primary; -2 for 240VAC primary). It is
compatible with the CyberCat 1016 only. This module adds 2.0A
external standby power and 6.0A alarm power, which increases the total
system power to 4A standby / 12A alarm total. The module supports
charging up to 75 Ah of additional standby battery. AC power and
standby batteries are supervised. Supervision may be turned off in
configuration if batteries are not required on SPS.
The SPS interfaces to P16 on the Control Panel behind the LCD using
the four standoffs and hardware supplied with SPS.
System AC line power to the SPS must originate from a dedicated circuit
at the main building power distribution center. This wiring is non power
limited. The circuit breaker shall be equipped with a lockout mechanism
and be clearly labeled as a “Fire Protection Control Circuit.”
Technical Specifications:
Dimensions (HxWxD): 5.5 in. x 4.5 in. x 2 in. Exhibit 2-11: SPS
(13.97 cm x 11.4 cm x 5.08 cm)
Weight: 0.66 lbs. (1.68 cm)
Power Input: 120 VAC, 60 Hertz, 2.22 Amps 225 VA
(Transformer 02-10881)
240 VAC, 50/60 Hertz, 1.45 Amps, 348 VA
(Transformer 02-10882)
Table 2-18: SPS Specification
LNote: The SPS expands the power capability of the CyberCat 1016 Controller to a total of 12 amps
of useable current and 150 Ah of standby batteries. It also adds three additional 2 Amp auxiliary
circuits.
The SLM (Exhibit 2-12) adds two more SLC loops to the CyberCat 1016.
Loop specifications and wiring for P31 and P32 are same as P8 and P9
from the main controller. It interfaces to P15 on the Control Panel using
four standoffs supplied with the SLM.
Technical Specifications:
Dimensions (HxWxD): 6.5 in. x 2 in. x 1 in.
(16.5 cm x 5 cm x 2.54 cm)
Weight: 0.12 lb. (0.30 cm)
Power Consumption: 100 mA (standby/alarm)
.
Exhibit 2-12: SLM
P32
Addressable Power Limited Same as noted in Loop 3 above
Loop 4
+ - SHLD ++ -- Supervised
2.8.16 ZONE ANNUNCIATOR, 10-2373 Exhibit 2-20: Two Button Remote Display
YOU ARE
HERE
LEGEND:
RED L.E.D. INDICATES LOCATION OF
ACTIVATED CEILING SMOKE DETECTOR.
GREEN L.E.D. INDICATES LOCATION OF
ACTIVATED SUB FLOOR SMOKE DETECTOR.
YELLOW L.E.D. INDICATES LOCATION OF
ACTIVATED ABOVE CEILING SMOKE DETECTOR.
RED L.E.D. W/ SQUARE BEZEL INDICATES
LOCATION OF MANUAL PULL STATION.
GREEN L.E.D. W/ SQUARE BEZEL INDICATES
LOCATION OF ABORT SWITCHES.
YELLOW L.E.D. W/ SQUARE BEZEL INDICATES
LOCATION OF LOW PRESSURE SWITCHES.
MICROCOMPUTER O.K. FCP INDICATES LOCATION OF
FIRE CONTROL PANEL.
COMMUNICATIONS O.K. INDICATES LOCATION OF
GAP
GRAPHIC ANNUNCIATOR PANEL.
OPEN CLOSE
RETURN AIR
DAMPER
SUPPLY AIR
DAMPER
OPEN CLOSE
EXHAUST SUPPLY
FAN FAN
until confirmation that the desired state of the air handling EXHAUST DAMPER SUPPLY DAMPER
LED will transition from flashing to continuously on. Connection ON AUTO OFF FAULT ON AUTO OFF FAULT
between the CyberCat and FSCS is made via the panel’s RS485 EXHAUST DAMPER
peripheral bus. Refer to Fike document 06-447, “Firefighters EXHAUST DAMPER SUPPLY DAMPER
ACCESS
LOCK
EXHAUST AIR SUPPLY AIR PRESSURIZATION LAMP TEST
SYSTEMS SYSTEMS SYSTEMS
MANUAL
OVERRIDE
POWER O.K.
ENGAGE
Exhibit 2-29:
2.8.25 TWENTY ZONE ANNUNCIATOR MODULE, 10-2660
I/O Switch Module
The Zone Annunciator Module (Exhibit 2-30) is a tabular based
display with a dedicated red (for Alarm) and yellow (for
Supervisory and Trouble) LED per assigned zone. Connection
between the FACP and Zone Annunciator is made via the
panel’s RS485 peripheral bus. Refer to Fike document 06-445,
“Twenty Zone Annunciator Module manual” for more details.
LNote: All electronics are rated 32° - 120°F (0° - 49°C), 10- 93% relative humidity, unless otherwise noted.
Each addressable device requires a normal operating voltage 15 to 30VDC (supplied by the SLC).
Exhibit 2-55:
USB Communication Cable
Batteries are required for alarm systems for maintaining emergency back-up power. Two each 12V batteries are
required and are to be wired in series for maintaining a 24VDC back-up. Most systems require at least a 24 hour
standby current with 5 minutes alarm current for determining minimum battery size. Refer to Appendix 1 for
Battery Calculation form for determining required battery size for system. The 10-2190-2 consists of 2 each 18
A-H, 12VDC batteries with a wiring harness.
2.11.2 BATTERIES
This section defines the system operation pertaining to the front panel controls, display, defining the operational
states, test modes and general panel operation.
3.1 DISPLAY
C Y B ER CA T v 4 . 0 0
F I K E COR PORA T I O N
08 : 0 0 : 0 0 A 0 8 / 0 1 / 2 0 0 7
AL : 0 0 0 SU : 0 0 0 T R : 0 0 0
Exhibit 3-2: System Status Display
A L ARM : DE V I CE T Y P E
CU S T OM ME S S AG E L - ADR
H H : MM : S S A MM / D D / Y Y YY
E V EN T X X X X OF Y Y Y Y
Exhibit 3-3: System Event Display
T OP L E V E L MENU
F 1 - C ON F I G F 4 - P A S SWR D
F 2 - H I S T RY F 5 - MA I N T
F 3 - D I AG F 6 - I R C OMM
Exhibit 3-4: Top Level Menu
3.3 KEYPAD
The CyberCat has a 3,200 event history buffer. This The four red buttons below the oval display on the
buffer continuously cycles in new information, keypad may be accessed with the enclosure front door
replacing the oldest information. A 1,600 event alarm opened.
history is held storing just the alarm events within that
3.3.5 DRILL
same 3,200 event buffer. There is a maximum of
1,600 alarms between reset in order to keep the first Press to activate outputs assigned for
alarm events (prealarms are not recorded once an Drill Function in the configuration.
alarm is recorded from an address). An 800 event Press RESET to clear the Drill
supervisory buffer is held storing just the supervisory activation.
events within that same 3,200 event buffer. The three 3.3.6 ACKNOWLEDGE
oval STEP buttons just to the left of the LCD are
accessible with the enclosure door closed on the Press to acknowledge an Alarm,
version with no door cover. These buttons are Trouble or Supervisory State.
accessible with the enclosure door opened only with Deactivates local piezo without
silencing active outputs. Creates
the lexan-covered opening door. These buttons
provide the capability to step through these current ‘Acknowledge’ event in the history.
events. 3.3.7 SILENCE
Press to Silence any notification
LNote: Each history or diagnostic screen has a 100 appliance circuits that are sounding
second time-out. When a specific menu or screen and programmed as silenceable
is selected, a timer will begin. Each button press outputs. Also deactivates local piezo.
restarts the timer. After 100 seconds of no user Creates ‘Silence Function’ event for all
interaction, the display will revert back to the loops. NFPA requires a panel that has
System Event Menu or System Status Display. been silenced for 24 hours to resound
The switches have a 5 minute timeout. Pressing a (which UL requires that it also re-send
switch changes the display to the switch function to the DACT). Some local authorities
pressed and keeps that display for up to 5 require this sooner. The CyberCat has
minutes, followed by the 100 second timeout. a configurable option for resound from
3.3.1 STEP ALARM 0-24 hours with 24 hours programmed
as the default.
Press to step through the current
ALARM events on the display. 3.3.8 RESET
Press to restore system to Normal.
3.3.2 STEP SUPER Deactivates control functions, flashes
Press to step through the current LEDs and momentarily interrupts
SUPERvisory events on the display. resettable auxiliary power. Clears any
latching event. If events are still
3.3.3 STEP ALL present, they will immediately restore.
Press to step through all current 3.3.9 NAVIGATION (+, >, -, <)
events on the display. Press F5 to
These buttons are used for data entry
toggle between current events and
during maintenance and configuration.
the entire 3200 event history display.
The <> arrows are used to move about
3.3.4 STEP TROUBLE in the configuration displays. The +/-
Press to step through the current buttons will increment or decrement
TROUBLE events on the display. the value at the cursor when in a
configuration display. They can also
be used when cycling through the
event history. The Step Alarm button
only cycles forward in events. These
buttons allow you to go forward and
backward through the events.
3.3.11.2 F2 (HISTRY)
3.3.10 ESCAPE
Toggles from System Event display History: Pressing this button will display the
(if events are present) to System HISTORY MENU screen. Events will be displayed
Status (time/date) to Top Level ONLY if there are events present in that respective
Menu. If in a menu, this button state. From this screen you can select Alarm,
EXITS the current menu and returns Supervisory, Trouble, Events, Zone, and Erase
to the previous menu screen. If in functions. If one of these are selected, the history
the System Status Menu, pressing messages are displayed in the sequential order
ESCAPE takes you back to event they occurred. Other states, such as Drill and
#1. Walktest, are available only in the Event History. If
in the SYSTEM EVENTS mode, pressing F2
3.3.11 FUNCTION BUTTONS displays extra 40 characters of the custom
message.
The function buttons F1, F2 ,F3, F4, F5 and F6 are
used to navigate the menu system during 3.3.11.3 F3 (DIAG)
maintenance and configuration of the system.
Diagnostics: Press this button to cycle through
two diagnostic displays. See the Troubleshooting
section of this manual for more details. (Requires
level 2 or higher password).
3.3.11.4 F4 (PASSWRD)
Password: Press this button to enter the
Password selection menu. A password has to be
entered to be able to configure the panel. Each
CyberCat is shipped with a default Level 3
Password (PW). This password it obtained from
Function Buttons Fike.
If an event is present and the display is in the
SYSTEM EVENTS mode, pressing F1 button will 3.3.11.5 F5 (MAINT)
display the EVENT SOURCE information for an Maintenance: Press this button to enter the
addressable device type event. Event source Maintenance screen. This allows you to do
consists of ‘PNLxxx LOOPxxx ADDRxxx’ information. Walktest, Device Read, Device Address, Device
This will show the panel number, SLC loop number Replace and Buzzer functions.
and the specific address that caused the event.
Pressing F2 will show the extra 40 characters of 3.3.11.6 F6 (IR COMM)
custom message for the device (toggles on each
press of the key). If the ESCAPE button is pressed, IR Communication: The IR tool (non-listed) is
the display will toggle to the TOP LEVEL MENU recommended for use in system set-up and service.
display (Exhibit 3-6). It is recommended that the IR communication be
enabled only during these times and disabled
T OP L E VE L MENU during normal operation. The system devices will
F 1 - C ON F I G F 4 - P A S SWR D pull 50% more power with the IR communication
enabled. Level 3 - Distributor password required.
F 2 - H I S T RY F 5 - MA I N T
F 3 - D I AG F 6 - I R C OMM
3.3.12 ENTER
Exhibit 3-6: TOP LEVEL MENU Display
Saves and enters the current
configuration settings. Use
3.3.11.1 F1 (CONFIG)
Navigation buttons to change
Configuration: Press this button to enter the variables at the blinking cursor
Configuration menus in the CyberCat. (or displays position.
EVENT SOURCE if in the SYSTEM EVENTS mode).
Events are displayed ONLY if there are current event
states present.
3.4 SYSTEM OPERATIONAL OVERVIEW Output devices are then configured to activate when
their associated zone(s) enter into the configured
The CyberCat is an Addressable Fire Alarm system.
State(s).
Most connections are made to an addressable smoke
sensor, input or output module. Each CyberCat Example: MMM configured for Supervisory Input for
addressable loop can contain up to 254 devices, any Zone 3. When activated will cause any Output
combination. Each device is supervised by a unique configured for Supervisory Zone 3 to turn ON.
address, 1-254. The device address as shipped from
Fike is Loop 0, Address 0 and is 3.5 PASSWORDS
changed/programmed into the device using the IR The CyberCat provides 4 different levels of security:
Tool or Hand-Held Programmer (non-listed). The
panel will also auto-address a new device (default Level Type Created Function
loop 0, address 0) when wired to the loop. It will 1 CUSTOMER Keylock Button access
recognize the new device by recording a DEVICE Date/time
NOT IN CONFIG trouble and address it to the first 2 MAINTENANCE C-Linx View Config
available empty address on the loop (if one exists). Diagnostics
Configuration
The operation of the CyberCat Control System is 3 DISTRIBUTOR CyberCat
Change lev 3
based upon a Zone and State Relationship. All Factory Init.
4 FACTORY CyberCat
devices, Input or Output, must be assigned to at least Create level 3
one Zone and State. A zone is defined as a specific
area of protection or hazard to protect. There are Each CyberCat is shipped with a default Level 3
253 software zones available on the CyberCat. A Password (PW). This password is announced at the
state is defined as ‘a status which describes a Fike CyberCat training class. Once a successful
specific operation of the fire alarm system.’ Input password is entered on the control panel, the user
devices can be assigned to up to four individual has the ability to perform the functions noted.
zones, two individual zones and a range of zones, or The Password Menu (Exhibit 3-7) can be accessed
two zone ranges (only one zone is typical). The from the Top Level Menu. The levels are also noted
panel zone is 254 (for troubles such as AC Power, on the Appendix 3 Menu Structure. They can be
Battery, NAC Supervision, or any other main panel changed only by a certified technician with a proper
trouble). Zone 254 is also an ANY ZONE selection password.
that CAN be disabled. Zone 255 is an ANY ZONE
selection that CAN NOT be disabled. Output devices Press F4 from the Top level Menu to access the
may be configured for any zone (Z255) or maximum password menu (once a successful password is
zones in action table (3 x 32 = 96 different zones). entered, press ESCAPE to access other menus):
Panel events report in zone 254. EN T ER P A S SWO R D
Each one of the addressable devices is intelligent _ _ _ _ < - - - X X XX
and maintains its own operating configuration. The ACCE S S : DEN I ED
devices use the Cyber-loop to transmit and receive CODE : X X X X
status information with one another and the control Exhibit 3-7: Password Menu
panel (the control panel appends zone information to
the event and also holds the custom message Line 2 4 digit password. Use the <> buttons to move
information). The control panel sends this the cursor and the +/- buttons (cycles through 0-
9) to enter a password.
information from Cyber-loop to Cyber-loop and
transmits data to on-board and peripheral devices. Note: Successful Level 3 - Distributor password
The control panel also performs supervision of provides the ability to change the default
password (by changing the right-handed 4 digit
devices and user communication/interface. number, XXXX then pressing ENTER). If this is
When an input is activated, it is configured to cause changed and then unknown, call Fike with the 4-
its associated zone(s) to enter an operational State. digit CODE displayed on line 4.
Any Detection device will cause their associated Line 3 Displays the access level (Denied, Level 2(A-H),
Zone(s) to enter the Alarm State (or Supervisory if Sys Admin, Factory) allowed with the password
programmed). All other input devices must be that has been entered.
configured for a specific type of input State, which will Line 4 Random 4 digit-code that changes periodically.
cause its associated Zone(s) to enter that Operational
State.
3.9 SUMMING ALARM STATE (NON-LISTED) The Trouble state is generally non-latching,
excluding ‘LOOP CLASS A OPEN’, ‘LOOP
The Summing Alarm State may be activated by
SHORT’, and ‘DRIFT TROUBLE’ troubles which are
Sensors. When a sensor is active with a summing
latching. Once the trouble is restored, the panel will
alarm, it will turn on its RED LED steady to indicate
return to normal if no other events are present. The
the activated status. It will light its REMOTE LED as
latching troubles noted require reset of the panel to
programmed, if connected.
clear the fault once it is corrected. When a trouble
The ALARM LED flashes and panel piezo pulses. event occurs it will display similar to Exhibit 3-11 for
The Alarm LED illuminates steady and piezo turns off 100 seconds then switches to the System Status
after ACKNOWLEDGE or SILENCE buttons are Display if no buttons are pressed.
pressed. Any output circuit/module programmed for
the Summing Alarm State will be ON until Silenced (if GENER A L T ROUB L E
programmed as Silenceable). The Z255 Alarm will CU S T OM ME S SAGE L - ADR
also be active. H H : MM : S S A MM / D D / Y Y YY
The Summing Alarm State is a latching event and will EV EN T X X X X OF Y Y Y Y
require panel reset to clear the event and return the
Exhibit 3-11: Trouble Display
panel to the Normal State. The display is similar to
Alarm state, except noted as Alarm Type #2.
Line 1 Trouble Event
3.10 ALARM VERIFICATION STATE Line 2 Device Custom Message
When a sensor programmed for alarm verification Line 3 Time and Date of Event
exceeds its alarm threshold, it broadcasts the Alarm
Line 4 This event is number XXXX for the
Verification state. Any output device programmed for
total YYYY current events
alarm verification in that same zone would operate. If
the sensor is still above the alarm threshold at the
3.12 SUPERVISORY STATE
end of the verification period, it will broadcast the
alarm (alarm verification state will then be OFF). The Supervisory State may be activated by any
Panel LED’s or piezo does not operate during this input configured for Supervisory. These inputs are
state. An event is recorded in the event buffer. typically connected to Sprinkler system Tamper, or
Low Air Pressure input contacts.
3.11 TROUBLE STATE
SUPERV LED flashes and panel piezo warbles (on
The Trouble State may be caused by a system, & off pattern). LED illuminates steady and piezo off
circuit or device supervision trouble. It can also be after ACKNOWLEDGE or SILENCE buttons are
activated by an input module programmed for pressed. When an input device is active, it will turn
Trouble, a PreAlarm input(s), or Walk-Test activation. on its RED LED steady to indicate the activated
Upon entering the Trouble State the following occurs: status. Any output circuit/module programmed for
the Supervisory State in the zone that is in
The TROUBLE LED flashes and panel piezo is
Supervisory will be ON until Silenced (if
steady. The Trouble LED illuminates steady and
programmed as Silenceable).
piezo off after ACKNOWLEDGE or SILENCE buttons
are pressed. If the trouble is caused by an Supervisory inputs may be configured for latching
addressable device, the device LED will blink or non-latching. If configured for latching, the panel
YELLOW approximately every second. Any output will require reset to restore the system to normal. If
circuit/module programmed for the Trouble State in configured for non-latching, once the Supervisory is
the zone that is in Trouble will be ON until Silenced (if restored, the panel will return to normal if no other
programmed as Silenceable). The P2 System events are present. When a supervisory event
Trouble Relay will activate (this relay is normally occurs it will display similar to Exhibit 3-12.
energized and will de-energize).
3.15 ZONE DISABLE STATE Only Output devices, which are enabled for Walk-
Test, will respond during this mode. By default, here
The Zone Disable State may be activated by any
is how those devices come configured:
input configured for Zone Disable. Disabling a zone
from the C-Linx Software or by the main panel CM: Configured to respond to walk-test
menu’s will operate in the same manner. RM: Configured to NOT respond to walk-test
NAC1/NAC2: Configured to respond to walk-test
When a Zone Disable event occurs the panel will
RELAYS: Trouble activated, otherwise not
enter the Trouble and Supervisory states (as
responsive.
previously described). With the zone disabled, inputs
in the disabled zone do not operate, therefore output Entry to walk-test can be accomplished in two ways:
in that same zone will not receive a command to
IR tool- initiated at the device/by device (IR
operate (unless from a different zone that is not
Communication must be enabled at panel). If Test
disabled).
Modes-Test Alarm is entered on the device, it is in a
The Zone Disable event is non-latching. Once the test mode status. If configured for Walk-test with IR,
Zone Disable contact is restored or the zone is re- it will present a Walk-Test state to the outputs. If
enabled, the panel will return to normal if no other configured for Walk-Test with Smoke, it will be ready
events are present. When a zone disable event to test with smoke to create the Walk-Test state for
occurs it will display similar to Exhibit 3-15. the outputs.
Z ON E D I S A B L ED : 0 0 1 Panel Menu System (via panel) – All input devices
C U ST OM ME S S ZONE 0 0 1 are put in a test alarm status and can then be tested
H H : MM : S S A MM / DD / Y Y YY with smoke. Each input programmed for Walktest
E V EN T X X X X O F Y Y Y Y with IR will immediately show a Walktest Alarm event
when Walktest mode is entered from the panel menu.
Exhibit 3-15: Zone Disable Display
1. Press ESCAPE to access TOP LEVEL menu.
Line 1 Zone Disabled State with Zone # 2. Press F4 to access PASSWORD menu. Enter
password then press ESCAPE.
Line 2 Device Custom Message
3. Press F5 to access MAINTENANCE menu.
Line 3 Time and Date of Event
4. Press F4 to access WALKTEST menu (Exhibit 3-16).
Line 4 This event is number XXXX for the total
5. Press ENTER to begin Walk-test mode 1 – Buzzer ON
YYYY current events (the local piezo will also sound with the activation of
the alarm events).
If all events are restored, it will display for 100
seconds then switch to the System Status Display if 6. Press ENTER again to begin Walk-test mode 2 –
Buzzer OFF (the local piezo will be silent with the
no buttons are pressed. activation of the alarm events).
The walk-test functions as a toggle mode, it is either LNote: A Device may only be activated once
On or Off. While On, the system goes into trouble during a walk-test mode. Walk-test timeout is 60
and accepts normal sensor alarm events and minutes. This timer restarts upon any event or
responds by recording the events (‘Walk-test active’) press of button. If no events or buttons are
in history and activating chosen output devices for 4 pressed for 60 minutes, the system will reset
second duration (continuous). itself back to normal operation.
3.18 AC TROUBLE DELAY The two Addressable Loops, Input Monitor Modules,
Supervised Control Module and the two on-board
Central and Remote Supervising Station Systems Audible Loops (A1 & A2) can all be configured for
require the use of a Digital Alarm Communicator Class B, two wire, or Class A, four wire wiring. The
Transmitter (DACT), 10-2528 or 10-2254 Reverse redundant wiring provided with Class A wiring
Polarity Module. These modules transmit all provides added security that events can still be
information from the panel output, to the Supervising recognized with a single wire break. When Class A
Station. Since Loss of AC is non-critical and wiring is utilized, Configure the circuit for Class A
secondary power is available, Supervising Stations wiring, no ‘t-tap’ wiring is allowed, the return leg from
typically need not see immediate AC power low the last device must be located in a separate conduit
troubles. AC power loss trouble will not immediately as the main leg. The control panel is constantly
be sent to the dialer for AC power low or loss supervising all wiring. Once an Open Fault is
Trouble, if it is the only fault. The communication will recorded on one of the inside legs of wiring, the panel
wait the programmed amount of time. The CyberCat immediately transfers communication to the
controller is programmable for a 0-30 hour (in 1 hour redundant leg of Class A wiring.
increments) AC trouble delay. The piezo and the
display of the event do not follow the delay of the 3.22 DAYLIGHT SAVINGS
relay and are immediately annunciated if the AC
The control panel will automatically change the time
trouble is the only trouble.
forward/backward at the appropriate times if daylight
savings is selected, YES. The control panel will not
3.19 ALARM VERIFICATION change the time if the daylight savings is selected
NO. Daylight Saving Time (for the U.S. and its
Sensors can be individually configured for an alarm
territories) is NOT observed in Hawaii, American
verification delay. The delay consists of extra time to
Samoa, Guam, Puerto Rico, the Virgin Islands, the
confirm that the device is still in alarm. When a
Eastern Time Zone portion of the State of Indiana,
sensor is configured for Alarm Verification, it will first
and by most of Arizona (with the exception of the
report ‘Alarm Verification ON’ at the first sense of the
Navajo Indian Reservation in Arizona).
alarm level being exceeded. The actual alarm event
is not broadcast until the Alarm verification time has Control panels with firmware Version 3.00 and
expired AND the sensitivity level is still above the higher operate as follows: Daylight Saving Time
alarm threshold. will start on the second Sunday in March, and change
back to standard time on the first Sunday in
November.
Control panels with firmware older than 3.00
operate as follows: Daylight Saving Time begins for
most of the United States at 2 a.m. on the first
Sunday of April. Time reverts to standard time at 2
a.m. on the last Sunday of October.
+/- Use the + and – on the Keypad to LNote: Pre-discharge state is not shared across
scroll through all Zone events in the network.
the history buffer.
Network nodes can be configured to either share
common zone numbers on the network (e.g., Zone 1
3.29.6 F6 – ERASE
spanning multiple panels operates as one zone for all
This menu requires prior entry of a successful Level 3 inputs and outputs), or leave the panel zones
(Distributor) password. independent from each other (e.g., Zone 1 on panel 1
is independent from zone 1 on panel 2). If the panel
is NOT configured to respond to the zone event that
P R E S S E N T ER is transmitted, it will respond by logging the event in
TO E R A SE H I S T O RY the panels history buffer and displaying it on the
panels display.
Exhibit 3-24: Erase History Menu Three types of network interface modules are
available:
Enter If you Press Enter on the Keypad a
screen will appear to the one below. • 10-2482 for connecting panels (nodes) with
This will erase current history as twisted-pair wire (Refer to Fike Document 06-
well as All History for the panel. 349, “Network Module” for more details).
• 10-2642 for connecting panels (nodes) with fiber-
optic cable (Refer to Fike Document 06-387,
* * ERAS I NG * *
“Fiber Optic Network Module” for more details).
* * H I ST O R Y * *
• 10-2627 for connecting panels (nodes) via IP
network (Refer to Fike Document 06-388,
Exhibit 3-25: Erase History Status
“Ethernet Module” for more details).
4.1 INSTALLATION
System installation is independent of whether the The back-boxes as shown in Exhibits 4-1 and 4-2
modules were ordered separately or as part of a can be surface or flush mounted as desired. For
complete CyberCat system. For optional modules surface mounting, utilize the four ‘tear-drop’
not used, skip the instructions detailing their openings in the back of the box. For flush mounting,
installation. Proper system installation requires cut the opening in the wall to fit the back-box and
following steps 1-9 in order: secure the box in place by utilizing the through holes
located on the sides of the box.
1. Install Enclosure(s)
2. Pull Field wiring. LNote: The CyberCat System enclosure is NOT
fire rated.
3. Install transformer and Wire AC to transformer.
Determine the maximum number of conductors
4. Install Optional Electronics onto main controller.
needed from the design. Wire is to be routed into
5. Install Controller and electronics into Back-box. the enclosure via knock-out openings. Conduit
knock-outs are provided for two distinct conduit
6. Connect AC and batteries.
sizes. Removing just the inside hole creates a one-
7. Connect Field wiring. half inch (1/2”) opening. Removing the entire
opening provides a three-quarter inch (3/4”)
8. Power up with devices connected.
opening.
9. Configure System – Auto-program or
Unless otherwise detailed in this manual, or in other
Engineered configuration
documents relating to this control panel, the
technician shall utilize published standards and
4.2 INSTALL ENCLOSURE(S) references such as NFPA 70 National Electrical
The mounting location for the control panel Code, NFPA 72 National Fire Alarm Code, and
enclosure is very important. Vibration, dust, others, which may be relevant to the Local Authority
moisture, electromagnetic interference, and radio Having Jurisdiction.
frequency interference are all types of problems that The enclosure accommodates the CyberCat
could adversely effect the successful operation and controller, Optional modules and either a 7 AH or 18
useful life of the equipment. Fike recommends that AH battery pack.
the fire alarm panel be installed in an environment
with a nominal room temperature of 15°-27°C / 60°-
80°F, with a relative humidity of 85 percent. Do not
install in an environment that exceeds these
temperature and humidity ranges.
BACK BOX
TOP VIEW
CONDUIT
OUTER DOOR
KNOCKOUT
OUTER DOOR
BACK BOX
BACK BOX
BACK BOX
MOUNTING HOLE
OUTER DOOR
BACK BOX
BOTTOM VIEW
Enclosure Dimensions
A 23.41 in [59.46 cm] N 14.22 in [36.12 cm]
B 21.70 in [55.12 cm] O 11.97 in [30.40 cm]
C 1.48 in [3.76 cm] P 9.72 in [24.69 cm]
D 14.25 in [36.21 cm] Q 3.95 in [10.03 cm]
E 12.58 in [31.95 cm] R 1.13 in [2.86 cm]
F 1.34 in [3.40 cm] S 14.35 in [36.44 cm]
G 0.50 in [1.27 cm] T 2.25 in [5.72 cm]
H 24.60 in [62.48 cm] U 3.25 in [8.26 cm]
I 23.50 in [59.69 cm] V 3.38 in [8.59 cm]
J 5.68 in [14.43 cm] W 1.00 in [2.54 cm]
K 1.73 in [4.40 cm] X 15.34 in [38.97 cm]
L 18.72 in [47.55 cm] Y 9.88 in [25.10 cm]
M 16.47 in [41.83 cm] Z -
BACK BOX
TOP VIEW
CONDUIT
OUTER DOOR
KNOCKOUT
OUTER DOOR
BACK BOX
BACK BOX
BACK BOX
MOUNTING HOLE
OUTER DOOR
BACK BOX
BOTTOM VIEW
Exhibit 4-2: 13 Module Deadfront Enclosure Dimensions
Enclosure Dimensions
A 23.41 in [59.46 cm] N 14.22 in [36.12 cm]
B 21.70 in [55.12 cm] O 11.97 in [30.40 cm]
C 1.48 in [3.76 cm] P 9.72 in [24.69 cm]
D 23.41 in [59.46 cm] Q 3.95 in [10.03 cm]
E 16.00 in [40.64 cm] R 1.13 in [2.86 cm]
F 4.21 in [10.69 cm] S 23.50 in [59.69 cm]
G 0.50 in [1.27 cm] T 6.81 in [17.30 cm]
H 24.60 in [62.48 cm] U 3.25 in [8.26 cm]
I 23.50 in [59.69 cm] V 3.38 in [8.59 cm]
J 5.68 in [14.43 cm] W 1.00 in [2.54 cm]
K 1.73 in [4.40 cm] X 24.54 in [62.34 cm]
L 18.72 in [47.55 cm] Y 9.88 in [25.10 cm]
M 16.47 in [41.83 cm] Z -
20" [50.8cm]
11" [27.9cm]
15" [38cm]
10" [25.4cm]
11" [27.9cm] 5"
[12.7cm]
5"
[12.7cm]
21" [53.3cm]
20" [50.8cm]
16.5" [41.9cm]
1.375 [3.5cm]
10" [25.4cm]
Back View
Tear Drop Locations for Mounting
Back View
Mounting Hole Locations
4.4 INSTALL TRANSFORMER AND WIRE AC TO To install the transformer into the back-box, follow
TRANSFORMER these steps:
System AC line power (120 VAC or 240 VAC, 50/60 1. Install the transformer(s) into the back-box
Hz) must originate from a dedicated circuit at the main onto the four press-studs. Secure in place
building power distribution center. The circuit breaker with four 6-32 hex nuts and washers.
shall be equipped with a lockout mechanism and be
2. Route the AC ground (chassis) wire to the
clearly labeled as a "Fire Protection Control Circuit".
open press stud in the enclosure back-box
Route the power to the system through the dedicated
and secure with a hex-nut and washer.
grounded metallic conduit.
3. Route the AC hot and neutral wires to the
I Caution transformer Primary as shown in Exhibits 4-5
or 4-6. DO NOT ENERGIZE THE AC
Ensure the power supplied is compatible with the
transformer assembly (120VAC or 240VAC) prior to POWER SOURCE AT THIS TIME!
applying power.
I Caution
Never swap transformer Primary (H1 and H2) and
Secondary (X1 and X2) by connecting AC feed to
secondary terminals. Doing so will cause the
transformer to step-up the power resulting in
certain damage to the controller.
SPS
LINE 2
OPTIONAL
DACT
P7
P2 P6
C NC NO C NC NO C NC NO
Alarm Supervisory Trouble
OPTIONAL
SUPPLEMENTAL
LOOP MODULE P10
OPTIONAL
SUPPLEMENTAL P11
POWER SUPPLY
I Caution
Do not install the electronic assemblies into the back-
box until the environment is free from construction
dust.
1. Thread the five 5/8” hex male-female standoffs
onto the back box pre-threaded press studs. C YBER C AT C AB IN ET
C O N TR O LLER STA N D O FF
CABINET
STANDOFF
DACT
STANDOFF
6-32 SCREWS THROUGH
(QTY. 4) BOARD
CYBERCAT
CONTROLLER
SPS
P5 is dedicated for connection to the Fike Guard voice - OUT LAST DEVICE
TOP
TOP
P8
TOP
P8
TOP
BLACK
RED
RED
The Mini Monitor Module can monitor dry contacts
(wired Class B, Style B initiating) for input to the
control system. It can be wired to Normally Open
(NO) contact as shown in Exhibit 4-25. To monitor
VIOLET
YELLOW
the wiring for a short circuit condition, the installation
requires a 14KΩ (10-2530) resistor in series with
each NO contact. Refer to modules installation
instructions for a complete description of wiring.
LNote: If monitoring a NC contact (Process Exhibit 4-25: Mini Monitor Module Wiring
Management only), the contact is wired in series
with the 39KΩ EOL (02-11259).
TOP
I Caution
Do not short SLC and 24VDC power wiring or
damage to the controller could occur.
I Caution
Do not short SLC and 24VDC power wiring or
damage to the controller could occur.
P50 P50
P3 P3
NETWORK MODULE NETWORK MODULE
P/N 10-2482 P/N 10-2482
P20 P20
PANEL #1 PANEL #2
(CONFIGURED AS FIRST) (CONFIGURED AS MIDDLE)
P50 P50
P3 P3
NETWORK MODULE NETWORK MODULE
P/N 10-2482 P/N 10-2482
P20 P20
PANEL #3 PANEL #4
(CONFIGURED AS MIDDLE) (CONFIGURED AS MIDDLE)
P50 P50
P3 P3
NETWORK MODULE NETWORK MODULE
P/N 10-2482 P/N 10-2482
P20 P20
PANEL #1 PANEL #2
(CONFIGURED AS FIRST) (CONFIGURED AS MIDDLE)
P50 P50
P3 P3
NETWORK MODULE NETWORK MODULE
P/N 10-2482 P/N 10-2482
P20 P20
PANEL #3 PANEL #4
(CONFIGURED AS MIDDLE) (CONFIGURED AS LAST)
P1 P1
PANEL #1 PANEL #2
(CONFIGURED AS FIRST) (CONFIGURED AS MIDDLE)
P1 P1
PANEL #4 PANEL #3
(CONFIGURED AS MIDDLE) (CONFIGURED AS MIDDLE)
P1 P1
PANEL #1 PANEL #2
(CONFIGURED AS FIRST) (CONFIGURED AS MIDDLE)
P1 P1
PANEL #3 PANEL #4
(CONFIGURED AS LAST) (CONFIGURED AS LAST)
F5
F4
F3
F2 F1
Exhibit 5-1: Controller Fuse Locations
P21
F1
Exhibit 5-2: SPS Fuse Locations
Required Standby Required Alarm Total Required Optional Factor of Adjusted Battery
Capacity (Amp-hr) Capacity (Amp-hr) Capacity (Amp-hr) Safety Capacity (Amp-hr)
+ = x =
Note 6 Note 7
Notes:
1. Auxiliary Power cannot exceed 2.0 A or 4.0 A with SPS in normal standby condition.
2. Auxiliary Power plus Notification Power cannot exceed 6.0 A or 12.0 A with SPS.
3. Auxiliary Power does not include current delivered to SCM during alarm conditions. This current is totaled
in Section 4.0 Notification Appliances.
4. NFPA 72 requires a secondary power supply of sufficient capacity to operate the fire alarm system under
nonalarm condition for a minimum of 24 hours. Alternate standby times may be required by the local
authority or approval agency.
5. NFPA 72 requires that at the end of the 24 hour period, the secondary power supply shall be capable of
operating all notification appliances used for evacuation for 5 minutes (0.083 hr) or 15 minutes for
emergency voice/alarm communication service.
6. 1.2 represents a battery derating factor of 20 percent.
7. CyberCat 254 and 1016 control panels can support charging up to 75 AH standby batteries. The
CyberCat 1016 panel with the SPS installed can support charging up to an additional 75 AH set of
batteries for a system total of 150 AH.
8. Add 0.010 A per relay used.
Total SLC Standby (mA): /1000 = A Total SLC Alarm (mA): /1000 = A
Total Total
Insert totals in Section 1 – Line Item 7.
Notes:
1. Current for sounder base activation is supplied by the auxiliary power circuit, not the SLC loop. Current
for associated detector head must be included in SLC calculations.
2. Current for solenoid activation is supplied by the auxiliary power circuit, not the SLC loop.
3. Current shown is the maximum value available to power conventional detectors connected to CZM
module.
4. Auxiliary power includes current supplied by the controller (6.0 A) and the supplemental power supply
(6.0 A), if installed.
OPERATIONAL CONDITIONS
To Silence Panel: Press SILENCE button Silences audibles & piezo. Changes flashing LED’s to steady.
Press F1 for top line to show source of event.
To Reset Panel: Press RESET button Resets system including turning off outputs, interrupting re-
settable power. Momentarily activates piezo, all LED’s, and
trouble relay. Restores system to normal state.
CAUTION: Remove AC and battery power before servicing equipment. The lithium battery used in
this device may present a risk of fire or chemical burn if mistreated. Do not recharge, disassemble, heat
above 100°C (212°F) or incinerate. Replace battery with Fike part 02-4040 only. Use of another battery
may present a risk of fire or explosion.
Periodic testing and inspection shall be conducted in accordance with NFPA 72 and NFPA 16.
AC and Battery fuses must be replaced with 15A Mini Automotive, Fast Acting Fuses.
Terminals P3, P4, P5, P6, P7, P8, P9, P10, and P11 are Power Limited Circuits.
This control unit is intended for installation in a controlled indoor environment, in a dry location.
OR