Current Transducer LF 305-S I 300 A
Current Transducer LF 305-S I 300 A
Preliminary
Electrical data
IPN Primary nominal r.m.s. current 300 A Features
IP Primary current, measuring range 0 .. ± 500 A
RM Measuring resistance RM min RM max • Closed loop (compensated) current
with ± 12 V @ ± 300 A max 0 39 Ω transducer using the Hall effect
@ ± 500 A max 0 12 Ω • Insulated plastic case recognized
with ± 15 V @ ± 300 A max 0 58 Ω according to UL 94-V0.
@ ± 500 A max 0 22 Ω
with ± 20 V @ ± 300 A max 15 93 Ω Advantages
@ ± 500 A max 15 45 Ω
• Excellent accuracy
ISN Secondary nominal r.m.s. current 150 mA • Very good linearity
KN Conversion ratio 1 : 2000 • Low temperature drift
VC Supply voltage (± 5 %) ± 12 .. 20 V • Optimized response time
IC Current consumption 16 (@ ± 20 V) + IS mA • Wide frequency bandwidth
Vd R.m.s. voltage for AC isolation test, 50 Hz, 1 mn 3 kV
• No insertion losses
• High immunity to external
Accuracy - Dynamic performance data interference
XG Overall accuracy @ IPN , TA = 25°C ± 0.4 % • Current overload capability.
ε L
Linearity < 0.1 %
Typ Max
Applications
IO Offset current @ IP = 0, TA = 25°C ± 0.20 mA
IOM Residual current 1) @ IP = 0, after an overload of 3 x IPN ± 0.08 mA
• AC variable speed drives and servo
motor drives
IOT Thermal drift of IO - 10°C .. + 70°C ± 0.1 ± 0.30 mA
• Static converters for DC motor drives
tra Reaction time @ 10 % of IPN < 500 ns • Battery supplied applications
tr Response time 2) @ 90 % of IPN <1 µs • Uninterruptible Power Supplies
di/dt di/dt accurately followed > 100 A/µs (UPS)
f Frequency bandwidth (- 1 dB) DC .. 100 kHz • Switched Mode Power Supplies
(SMPS)
General data • Power supplies for welding
TA Ambient operating temperature - 10 .. + 70 °C applications.
TS Ambient storage temperature - 25 .. + 85 °C
RS Secondary coil resistance @ TA = 70°C 28 Ω
m Mass 95 g
Standards 3) EN 50178
Notes : 1)
The result of the coercive field of the magnetic circuit
2)
With a di/dt of 100 A/µs
3)
A list of corresponding tests is available
991125/1
Bottom view
Secondary terminals
Connection
Top view
• General tolerance ± 0.5 mm • IS is positive when IP flows in the direction of the arrow.
• Fastening see drawing • Temperature of the primary conductor should not exceed
• Primary through-hole ∅ 20 mm 100°C.
• Connection of secondary Molex 5045-03/AG • Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.