Grid Code Requirements For WTG Interconnection
Grid Code Requirements For WTG Interconnection
interconnections
CNY Engineering Expo
Syracuse, NY
November 13, 2017
Purposes of grid codes
Voltage swells
– Tripping not allowed when the disturbance will subside normally
– Tripping permitted when expected limits are exceeded
– Typically within the range of the various types of swells
Not generally an issue with stiff systems unless large scale changes
occur in the grid.
With increased penetration of renewable energy, reduced inertia of
synchronous generators in system may lead to frequency instability.
Islanding: Frequency depends on ratio of load to generation.
– Frequency droop is used to control frequency versus power.
“Each Transmission Operator shall specify a voltage or Reactive Power schedule (which is
either a range or a target value with an associated tolerance band)…”
NERC VAR-001-4.2 — Voltage and Reactive Control
However, in some cases (in Canada and Europe) both voltage and reactive
power must be met at once, while maintaining acceptable frequency. This can
be difficult.
Reduced power output may be required due to
contingencies
Curtailment commands sent to wind farm control system
Minimum up/down ramp rates may be required (MW/min)
Power quality - harmonics.
In this example, the wind turbine harmonics peak at the 27th harmonic = 1620Hz
Line Load