0% found this document useful (0 votes)
42 views2 pages

Data Sheet - Make Ducab

Ducab flexible panel wires are intended for use in wiring switchgear panels and equipment operating at voltages up to 600V AC and 1000V DC. The wires have plain annealed copper conductors insulated with heat-resistant PVC and are available in various conductor sizes from 0.5 to 240 mm2. They can operate at temperatures from -15°C to 90°C and meet flame test standards.

Uploaded by

Rafeek Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views2 pages

Data Sheet - Make Ducab

Ducab flexible panel wires are intended for use in wiring switchgear panels and equipment operating at voltages up to 600V AC and 1000V DC. The wires have plain annealed copper conductors insulated with heat-resistant PVC and are available in various conductor sizes from 0.5 to 240 mm2. They can operate at temperatures from -15°C to 90°C and meet flame test standards.

Uploaded by

Rafeek Ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

INTRODUCTION:

Ducab flexible panel wires made as per BS 6231 Type CK are intended for use in the wiring
of switch, control, metering, relay and instrumentation panels of power switchgear. It is also
used for such purposes as internal connections in rectifier equipment and its motor starters
and controllers. They are intended for use at AC voltage not exceeding 600 V to earth and DC
voltage not exceeding 1000 V to earth. When installed in equipment they are suitable for wiring
circuits for which the prescribed AC test voltage does not exceed 4 kV R.M.S. for 1 minute.

Salient features of Ducab panel wires are as mentioned below.

Standard: BS 6231, Type CK

Plain annealed circular class 5 flexible copper conductor as per BS


Conductor:
EN 60228. Tinned conductor can be offered for special requests.

Heat Resistant PVC type TI3 as per BS EN 50363-3, suitable for


Insulation: continuous operating temperature of 90°C. Special PVC for 105°C
operating temperature is also available upon request.

Voltage rating : 600/1000 V

-15°C to 90°C operating temperature


Temperature range:
Cable installation temperature shall be above 0°C

Flame test: BS EN / IEC 60332-1

3 x O.D. for cable diameter up to 10 mm,


Minimum Bending
4 x O.D. for cable diameter above 10 mm up to 25 mm and
radius:
6 x O.D. for cable diameter greater than 25 mm

Green/Yellow (bi-colour combination), Red, Black, Blue, Brown,


Colours:
Grey, Orange, Pink, Turquoise, Violet and White
TECHNICAL DATA:

Nominal Approx. Current


Conductor Approx. cable DC resistance
Insulation Cable rating*
Size weight @ 20°C
thickness diameter (1 phase)
(sqmm) (mm) (mm) (kg/km) (ohm/km) (Amp)
1 x 0.5 0.8 2.7 11 39 11.5
1 x 0.75 0.8 2.9 14 26 16
1x1 0.8 3.1 17 19.5 19
1 x 1.5 0.8 3.4 22 13.3 24
1 x 2.5 0.8 3.9 33 7.98 32
1x4 0.8 4.4 47 4.95 43
1x6 0.8 4.9 66 3.30 56
1 x 10 1.0 6.3 111 1.91 79
1 x 16 1.0 7.4 169 1.21 105
1 x 25 1.2 9.0 264 0.780 141
1 x 35 1.2 10.4 350 0.554 178
1 x 50 1.4 12.3 491 0.386 217
1 x 70 1.4 14.0 688 0.272 276
1 x 95 1.6 16.0 931 0.206 337
1 x 120 1.6 17.7 1154 0.161 400
1 x 150 1.8 19.8 1421 0.129 457
1 x 185 2.0 21.8 1779 0.106 526
1 x 240 2.2 24.8 2346 0.0801 634
*: Current rating at 30°C ambient temperature

DERATING FACTORS FOR CHANGE IN AMBIENT TEMPERATURE:


Ambient
25°C 30°C 35°C 40°C 45°C 50°C
temperature
Factor 1.02 1.00 0.96 0.91 0.87 0.82