DCL10
DCL10
Valve Type
Part-Turn
Damper
0~90°
Torque/Time
100Nm/30S
Optional
50Nm/15S
100Nm/60S
Duty Type
Open-Close
Modulating
Supply Voltage
DC24V
AC24V
AC110V
AC220V
AC380V
Input/Output Signal
4~20mA
0~10V
Contact
Modbus-RTU | CAN | Ethernet
Options
Over torque protection
Failure Safe
Dehumidification
Diagnosis
Parameters
Power Supply DC24V, AC24V, AC110V, AC220V, AC380V
Standard Torque/Time 100Nm/30S
Optional Torque/Time 50Nm/15S, 100Nm/60S
Rotation angle range 0~90° Configurable
Motor Power/Current DC24V:25W/2.03A
AC24V:25W/2.12A
AC110V:25W/0.57A
AC220V:25W/0.35A
AC380V:15W/0.10A
Control Circuit A/B/C/D/E/F/G/H
Weight 4.5Kg
Insulation Resistance DC24V/AC24V: 100MΩ/250VDC
AC110V/AC220V/AC380V: 100MΩ/500VDC
Withstand Voltage DC24V/AC24V: 500VAC 1 Minite
AC110V/AC220V:1500VAC 1 Minite
AC380V:1800VAC 1 Minite
Water Proof Level IP67
Installation At any angle position
Electrical Interface G1/2 waterproof cable connect: one for power and one for signal
Working Temperature -25℃ ~ +55℃
Optional Function Over Torque Protect, Dehumidification Heater, Convex Indicator, Manual Wheel
Servo Parameters
Input Signal 4~20mA, 0~10V Configurable
Output Signal 4~20mA, 0~10V Configurable
Bus 485/Modbus/CAN
IOT WIFI/LoRA/4G
Basic Error ≤±1%
Return Error ≤1%
Hysteresis 0.5% to 5.0% Configurable
Repositioning Times 0 Times
Repeatability Error ≤1%
Control Circuit
Modulating
E-type: with Servo Module (Positioning)
Wiring instructions:
• P1 connect to N
• When P2 connected to L, Actuator
move to Shut
• When P3 connected to L, Actuator
move to Open
• P4 drives shut LED on, when actuator
arrived at shut position while P2
connected to L
• P5 drives shut LED on, when actuator
arrived at open position while P3
connected to L
• P7 connect to earth
Wiring instructions:
• P1 connect to + while P2 connect to -,
actuator move to shut
• P2 connect to + while P1 connect to -,
actuator move to open
• P3 is common pin for signal output
• P4 connect to com when actuator arrived at
open position
• P5 connect to com when actuator arrived at
shut position
• P7 connect to earth
Wiring instructions:
• P1/P2/P3 connect to power L1/L2/L3
• P4 is common pin for external control
• P5 controls shut operation
• P6 controls open operation
• P7 is common pin for signal output
• P8 connect to com when actuator arrived
at open position
• P9 connect to com when actuator arrived
at shut position
• P12 connect to earth
Position Transmitter
Type C: with 1K Ω (or 500 Ω) potentiometer
Implement "on" and "off" operations through switch
circuits, and output resistance signals corresponding to
the opening position.
Wiring instructions:
• P1 connect to N
• When P2 connected to L, Actuator move to Shut
• When P3 connected to L, Actuator move to Open
• P4 is the negtive of the potentiometer. When
actuator move to open, the resistance between
P4 and P5 increases along with position change
• P5 is output signal of potentiometer
• P6 is the positive of the potentiometer. When
actuator move to open, the resistance between
P6 and P5 decreases along with position change
• P7 connect to earth
Wiring instructions:
• P1 connect to N
• When P2 connected to L, Actuator move to Shut
• When P3 connected to L, Actuator move to Open
• P4 is common pin for signal output
• P5 connect to com when actuator arrived at open
position
• P6 connect to com when actuator arrived at shut
position
• P7 is the negtive of the potentiometer. When actuator
move to open, the resistance between P7 and P8
increases along with position change
• P8 is output signal of potentiometer
• P9 is the negtive of the potentiometer. When actuator
move to open, the resistance between P9 and P8
decreases along with position change
• P12 connect to earth
Type F: with position transmitter
Wiring instructions:
• Connect to power N line
• Connect to power L line
• Connect shut to L, actuator move to shut
• Connect open to L, actuator move to open
• Signal output 4-20mA, which is propotional
with actuator position