0% found this document useful (0 votes)
36 views

CA3KN22MD - Contator Aux

1) This document provides product specifications for a TeSys K control relay with 2 NO + 2 NC contacts rated for voltages up to 690V AC/DC and a standard coil voltage of 220V DC. 2) Key features include 10A thermal current, 110A making capacity, 690V insulation rating, and operating times of 10-40ms. 3) The relay measures 58x45x57mm and has screw clamp terminals that can accommodate wire sizes from 0.34-4mm^2. It is rated for industrial environments from -25°C to 50°C.

Uploaded by

Camila Cossenzo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views

CA3KN22MD - Contator Aux

1) This document provides product specifications for a TeSys K control relay with 2 NO + 2 NC contacts rated for voltages up to 690V AC/DC and a standard coil voltage of 220V DC. 2) Key features include 10A thermal current, 110A making capacity, 690V insulation rating, and operating times of 10-40ms. 3) The relay measures 58x45x57mm and has screw clamp terminals that can accommodate wire sizes from 0.34-4mm^2. It is rated for industrial environments from -25°C to 50°C.

Uploaded by

Camila Cossenzo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product datasheet CA3KN22MD

Characteristics TeSys K control relay - 2 NO + 2 NC - <= 690 V -


220 V DC standard coil

Main
Range TeSys
Product name TeSys CAK
Product or component type Control relay
Device short name CA3K
Contactor application Control circuit
Utilisation category AC-15
DC-13
Pole contact composition 2 NO + 2 NC
[Ue] rated operational voltage <= 690 V <= 400 Hz
Control circuit type DC standard

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Control circuit voltage 220 V DC

Complementary
[Ith] conventional free air thermal current 10 A at <= 50 °C
Irms rated making capacity 110 A conforming to IEC 60947
Associated fuse rating 10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
[Ui] rated insulation voltage 690 V conforming to BS 5424

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
690 V conforming to IEC 60947
750 V conforming to VDE 0110 group C
600 V conforming to CSA C22.2 No 14
Mounting support Plate
Rail
Connections - terminals Screw clamp terminals 1 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 2 cable(s) 1.5...4 mm² - cable stiffness: solid
Screw clamp terminals 2 cable(s) 0.75...4 mm² - cable stiffness: flexible - without
cable end
Screw clamp terminals 1 cable(s) 0.75...4 mm² - cable stiffness: flexible - with cable
end
Screw clamp terminals 1 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - with
cable end
Screw clamp terminals 2 cable(s) 0.34...1.5 mm² - cable stiffness: flexible - without
cable end
Tightening torque 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 6 mm
1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit voltage limits 0.8...1.15 Uc at 50 °C operational
0.1...0.75 Uc at 50 °C drop-out
Operating time 10 ms coil de-energisation and NO opening
15 ms coil de-energisation and NC closing
25...35 ms coil energisation and NC opening
30...40 ms coil energisation and NO closing
Mechanical durability 20 Mcycles
Operating rate 10000 cyc/h
Immunity to microbreaks 2 ms
Inrush power in W 3 W at 20 °C
Hold-in power consumption in W 3 W at 20 °C
Heat dissipation 3W
Minimum switching voltage 17 V
Minimum switching current 5 mA
Non overlap distance 0.5 mm
Insulation resistance > 10 MOhm

1/2
Height 58 mm
Width 45 mm
Depth 57 mm
Product weight 0.225 kg

Environment
standards BS 5424
IEC 60947
NF C 63-140
VDE 0660
product certifications CSA
UL
IP degree of protection IP2x
protective treatment TC conforming to IEC 60068
ambient air temperature for operation -25...50 °C
ambient air temperature for storage -50...80 °C
operating altitude 2000 m without derating in temperature
flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
mechanical robustness Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor open 2 Gn, 5...300 Hz IEC 60068-2-6
Shocks contactor open 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed 15 Gn for 11 ms IEC 60068-2-27

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0640 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months