CCR Control System Interface Handbook
CCR Control System Interface Handbook
AE
airfield engineering
design guides
ADB Safegate
977 Gahanna Parkway
Columbus, Ohio 43230 Document No: 110A0481
1-800-545-4157
ADB Airfield Solutions : ADB Ferro [Blue Skins] 4-30kW, 6.6A, Ferro, Air-cooled
Control System Interface Guide
Manufacturer:
ADB Airfield Solutions
Model:
ADB Ferro (Blue Skins)
4-30kW, 6.6A, Ferro, Air-cooled
Sample Picture
S1(PPF)
Pin 16
S2 (PPC) Primary Power Feedback
(48VDC) Primary Power Common
*Note 2
Primary Power feedback must be active
high (24VDC or 120VAC) when primary
power is present at the CCR
Remote/Local Feedback
Remote/Local Common
Pin 32
(-48VDC Remote / Local feedback must be active
/GND) high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
*Note 1
Notes:
1. See drawing 43A2304 for more details of wiring Remote/Local feedback in card cage
2. Internal wiring must be added, wired to spare terminal blocks and should be relabeled
ADB Airfield Solutions : ADB LC [Blue Skins] 4-30kW, 6.6A, Ferro, Air-cooled
Control System Interface Guide
Manufacturer:
ADB Airfield Solutions
Model:
ADB LC (Blue Skins)
4-30kW, 6.6A, Ferro, Air-cooled
Sample Picture
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. A KS2 Relay may exist if CCR was formally monitored by Scanning Monitor. Else a Relay Kit will have to
be added. K1 relay must be 12VDC Coil, .5A contact rating.
2. Internal wiring must be added, wired to spare terminal blocks and should be relabeled
Model:
CCF Signature Series
4-30kW, 6.6A, Ferro, Air-cooled
Sample Picture
CCR S1
S2
Control System
CCI CCI
CC CC
B1 B1
B2 B2
B3 B3
B4 B4
B5 B5
N
120VAC
Primary Power Feedback
FUSE Primary Power Common
F5 Primary Power feedback must be active
high (24VDC or 120VAC) when primary
power is present at the CCR
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. A KS2 Relay may exist if CCR was formally monitored by Scanning Monitor. Else a Relay Kit will have to
be added. K1 relay must be 12VDC Coil, .5A contact rating.
Model:
CCT Signature Series
4-30kW, 6.6A, LC, Air-cooled
Sample Picture
Notes:
1. A KS2 Relay may exist if CCR was formally monitored by Scanning Monitor. Else a Relay Kit will have to
be added. K1 relay must be 12VDC Coil, .5A contact rating.
2. Internal wiring must be added, wired to spare terminal blocks and relabeled
Model:
30000 Series [SEPCO]
10-70kW, 6.6A/20A, Ferro, Oil-cooled
Sample Picture
CCR N
120VAC
71
72
Control System
73 CCI
74 CC
*NOTE 1 B1 B1
B2 B2
B3 B3
B4 B4
B5 B5
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. Older Crouse-Hinds and SEPCO Series should always be field verified for interface accuracy. If new
variations of CCR’s are determined, information should be forwarded to Project Engineering Group for
addition to CCR Interface Handbook
Model:
31000 Series
4-30kW, 6.6A, Ferro, Air-cooled
Sample Picture
CCR (CC)
120VAC
XCP
N
Control System
CCI CCI
CC
B1(B10) B1
B2(B30) B2
12VGND B3(B100) B3
B4 B4
B5 B5
Remote/Local Feedback
Remote/Local Common
*Note 1 Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. Limited information is available regarding the S446 Kit required to create the Remote/Local feedback
signal. This information should always be field verified for interface accuracy. If interface information
becomes available, this data should be forwarded to Project Engineering Group for addition to CCR
Interface Handbook
2. Internal wiring must be added, wired to spare terminal blocks and should be relabeled
Model:
31060 Series
10-70kW, 6.6A/20A, Ferro, Oil-cooled
Sample Picture
CCR N
Control System
120VAC CCI CCI
CC CC
B1(B10) B1
B2(B30) B2
B3(B100) B3
B4 B4
B5 B5
Option XCP
S446 Kit XOS
(Optional)
Primary Power Feedback
? Primary Power Common
? Primary Power feedback must be active
high (24VDC or 120VAC) when primary
power is present at the CCR
Remote/Local Feedback
Remote/Local Common
*Note 1 Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. Some older models may require the S446 Kit. Limited information is available regarding the S446 Kit
required to create the Remote/Local feedback signal. This information should always be field verified
for interface accuracy. If interface information becomes available, this data should be forwarded to
Project Engineering Group for addition to CCR Interface Handbook
Model:
82860 Series, Small & Large
4-30kW, 6.6A, Ferro, Air-cooled
20-70kW, 20A, Ferro, Oil-cooled
Sample Picture
Remote/Local Feedback
PCB 31716 Remote/Local Common
Notes:
1. An Option 23 Kit may exist if CCR was formally monitored by Crouse-Hinds system. Else, the
Contractor must include in their pricing the purchase and installation of these kits. Card must be
added and configured in the CCR card cage
2. Internal wiring must be added, wired to spare terminal blocks and should be relabeled
3. Refer to manual to adjust S1 switch settings to assure proper configuration and enable OPT23 options
Doc no. 110A0481 9
Crouse-Hinds : 31360 Series, Small, 4-10kW, 6.6A, Ferro, Air-cooled
Constant Current Regulator
Control System Interface Guide
Manufacturer:
Crouse-Hinds
Model:
31360 Series, Small
4-10kW, 6.6A, Ferro, Air-cooled
Sample Picture
Notes:
1. An Option 23 Kit may exist if CCR was formally monitored by Crouse-Hinds system. Else, the
Contractor must include in their pricing the purchase and installation of these kits. Card must be
added and configured in the CCR card cage
2. Internal wiring must be added, wired to spare terminal blocks and should be relabeled
Model:
644 Series
10-70kW, 6.6A/20A, SCR Saturable Reactor
Ferro, Oil-cooled
Sample Picture
FU2
Notes:
1. Jumper needs wired from 3A on CCR Control PCB to spare terminal block and relabeled (N).
2. Jumper needs wired from FU2 to spare terminal and relabeled PPF (Primary Power feedback)
3. CCR may require both CC and B1 signals to turn on to Brightness step 1. Field verify by applying
jumper from CCI to CC and see if CCR turns on to Step 1. If so, B1 signal not required for control.
Doc no. 110A0481 11
Hevi-Duty 57990 Series, 10-70kW, 6.6A/20A, SCR, Oil-cooled
Constant Current Regulator
Control System Interface Guide
Manufacturer:
Hevi-Duty Electric
Model:
57990 Series
10-70kW, 6.6A/20A, SCR Saturable Reactor
Oil-cooled
Sample Picture
CCR 120VAC
71 (N)
72 (PPF)
Control System
*Note 2 73 (CCI) CCI
74 (CC) CC *Note 3
B1(B10) B1
B2(B30) B2
B3(B100) B3
B4 B4
B5 B5
SP1
SP2
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
*Note 1
Notes:
1. The Neutral and the Primary Power terminal blocks may not be pre-wired and require field
modifications to the internal wiring to wire these signals.
2. Some older series of Hevi-Duty CCR’s have different terminal block labels. Always field verify the
interface connections during site visit
3. CCR may require both CC and B1 signals to turn on to Brightness step 1. Field verify by applying
jumper from CCI to CC and see if CCR turns on to Step 1. If so, B1 signal not required for control.
Doc no. 110A0481 12
Manairco: MR/MSR Series 2-50kW, 6.6A/20A, Ferromagnetic, Air-cooled
Constant Current Regulator
Control System Interface Guide
Manufacturer:
Manairo
Model:
MR & MSR Series
2-50kW, 6.6A/20A, Ferromagnetic
Air-cooled
Sample Picture
CCR TB1
Control System
CCI CCI
CC CC
B1 B1
B2 B2
B3 B3
B4 B4
B5 B5
N
TB2
1
GRD Primary Power Feedback
Primary Power Common
*Note 1
Primary Power feedback must be active
high (24VDC or 120VAC) when primary
power is present at the CCR
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. Depending on Manairco model, Spare terminal block may not exist and require field modifications of
internal wiring to locate Primary Power feedbaclk signal (120VAC). If TB2 does not exist, PPF should be
field verified and documented and forwarded to Project Engineering to create new interface diagram
Sample Picture
FU2
Wire to spares TB’s and relabel
Notes:
1. Jumper needs wired from 3A on CCR Control PCB to spare terminal block and relabeled (N).
2. Jumper needs wired from FU2 and butt spliced /labeled to PPF wire (Primary Power feedback)
Manufacturer:
Honeywell
Model:
Stackable CCR (Old Style)
4-30kW, 6.6A, Thyristor Controlled
Air-cooled
Sample Picture
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
any local step including OFF
Notes:
1. Jumper needs wired from CC to B1 for CCR to turn on at Step 1 by only energizing CC
2. Jumper needs wired from Door switch P14 (position 14) and butt spliced /labeled to RLF wire
(Remote / Local feedback)
Notes:
1. Jumper needs wired from CC to B1 for CCR to turn on at Step 1 by only energizing CC
2. Jumper needs wired from J22 terminal 1 to terminal 18. Primary Power feedback (PPF=24VDC when
active) is wired to terminal 1, Remote/Local feedback (RLF=24VDC when active) is wired to terminal 15
Programming Distributed Control Device to provide feedback signals:
1. Program password: 0000 2. Remote reset: Yes
3. Option 1=0 4. Indication of faults: contact closed
5. Single lamp ctrl/mtrng: No 6. Serial Interface: Not used
7. PIO command: ON-input 8. Strobe: Not used
Remote/Local Feedback
Remote/Local Common
Remote / Local feedback must be active
high (24VDC or 120VAC) when CCR is in
Remote and low ( 0 V) when CCR is in
*Note 1 any local step including OFF
Notes:
1. No details for Primary Power and Remote/Local Feedback available at this time