LT 6749 MGC 4000 BR DIN Rail Template
LT 6749 MGC 4000 BR DIN Rail Template
Contents of kit: 3 DIN rails, 12 screws (#8 type AB 1/4” length), 12 flat washers, 6 brackets, 6 nuts for the brackets
Use this template to properly space the DIN rails in the enclosure.
Drill hole drill diameter: 9/64”
See page 2 for cable routing
274
10 13 "
16
250
9 13 "
16
6
1"
4
12
For 1 or 2 modules: 1"
2 Bracket Installation
• UL or equivalent listed enclosure with 1 DIN rail
• Minimum dimensions 9” (229 mm) x 12.75” (324 mm) x 3.15” (80 mm) Enclosure
18
• Minimum of 10 conduit knockouts
11 "
• Minimum distance from the DIN rail to top of enclosure: 3" (76 mm) (measured from the center of the rail) 16
• Minimum distance from the DIN rail to bottom of enclosure: 3" (76 mm) (measured from the center of the rail) DIN rail
Bracket Bracket
For 3 to 6 modules:
• UL or equivalent listed enclosure with 3 DIN rails Nut Nut
• Minimum dimensions 23” (584 mm) x 12.5” (318 mm) x 4.2” (107 mm)
• Minimum of 13 conduit knockouts
• Minimum distance from the top DIN rail to top of enclosure: 3" (76 mm) (measured from the center of the rail)
165 • Minimum distance from first rail to second rail: 6" (152 mm) (measured from the center of the rails)
6.5" • If using a third DIN rail, minimum distance from second rail to third rail: 6" (152 mm) (measured from the center of the rails) FRONT VIEW
• Minimum distance from the bottom DIN rail to bottom of enclosure: 3" (76 mm) (measured from the center of the rail)
Enclosure
LT-6749 rev 3
June 2023
Page 1
Cable Routing Examples Maintain a separation of 1/4” (6.4 mm) Gray area (solid Green area (dotted Right side of box is
minimum between power-limited and outline) marks the outline) marks the reserved for all power
non-power-limited wiring at all times. location for all location for all limited wiring.
non-power-limited power-limited wiring.
wiring.
1 or 2 Modules 3 to 6 Modules
Minimum 1/4”
Min.
1/4”
Min. 1/4”
Minimum 1/4”
Minimum 1/4”
Minimum 1/4”
Min.
1/4”
Min. 1/4”
Minimum
1/4”
Minimum 1/4” Minimum 1/4”
Min. 1/4” to third DIN rail wiring to third DIN rail wiring
Minimum
1/4”
LT-6749 rev 3
June 2023
Page 2