Electronic Motor Protection Relays - G - EMPR-DMPR

1) EMPR is a digital motor protection relay that uses a microprocessor control unit (MCU) to provide reliable protection through real-time data processing and precision. 2) EMPR can protect low voltage motors from overcurrent, phase loss, phase reversal, imbalance, stall, lock, and ground faults depending on the model. 3) EMPR is highly reliable, tested for EMC compliance, and many models are CE and UL certified to operate safely without issues from electromagnetic waves or surges.

Uploaded by

Truong Hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
400 views44 pages

Electronic Motor Protection Relays - G - EMPR-DMPR

1) EMPR is a digital motor protection relay that uses a microprocessor control unit (MCU) to provide reliable protection through real-time data processing and precision. 2) EMPR can protect low voltage motors from overcurrent, phase loss, phase reversal, imbalance, stall, lock, and ground faults depending on the model. 3) EMPR is highly reliable, tested for EMC compliance, and many models are CE and UL certified to operate safely without issues from electromagnetic waves or surges.

Uploaded by

Truong Hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

EMPR

Electronic motor protection relays

EMPR is digital motor protection relay where the MCU


(Microprocessor Control Unit) is built-in and features
excellent reliability by achieving real-time data processing
and high precision.

GMP Series

DMP Series

IMP Series
G
Features G-6

Ordering G-9

Specification G-10

Characteristics G-14

Setting method G-24

Contents
Dimensions G-33

Wiring method G-39

Accessories G-42

Direct mounting EMPR new/old comparative table G-44


EMPR replacing thermal overload relay Compact and stylish appearance can be
is electronic motor protect relay which is used combined with the magnetic contactor and
to protect the low voltage motor and also various installation methods make easy
called as Electronic Overcurrent Relay or an design features and manufacture motor
Electronic Overload Relay. control panel.

As a digital motor protection relay with MCU Especially, EMPR is EMC tested and approved
EMPR is highly reliable by realization of to operate safely without any malfunction
real-time data processing and, retention caused by electromagnetic wave and surge.
confidentiality and also can secure motor Most of the models have received CE Mark
safely with various functions such as phase and UL certification.
loss, phase reverse, unbalanced, stall, lock,
ground fault, short circuit protection
depending on the model .
General Motor Protection Relay
GMP Series
�Various connection & mount
�Inverse or definite time mode
�Ground fault type
�Display the causes of the falut by LED

Digital Motor Protection Relay


DMP Series
�Ampere meter, Load rate and the causes of fault Display
�Standard, Ground fault and short circuit protection type
�Select the Inverse or definite time modes
�Unit or Extension in one body by cable option
G
�Option function type (DMP-a)

EMPR/DMPR
Intelligent Motor Protection Relay
IMP Series
�Wide current setting range (0.125~100A)
�Communication support type
�Zero current and residual current sensing
�Save the fault events and operating time setup
�Select the Inverse, thermal inverse or definite time modes
�Unit or Extension in one body by option cable
Electronic motor protection relays
Features
GMP Series

● Combination with Metasol contactors for compact motor starters


EMPR model Contactor model

GMP22-2P/3P/3PR MC-9b, MC-12b, MC-18b, MC-22b


GMP40-2P/3P/3PR MC-32a, MC-40a

● Broad range of current setting


● Inverse time or definite time characteristics
● Simple operation and trip cause indication via LED
● Various Connection

Test /
Current Reset button
setting

Direct mount Screw connection & Passing through CT holes &


LED indicator Trip time setting
on a contactor Separate mount Separate mount

Certification of CE, UL, CCC and S mark

● Various protection functions


Types (GMP-�) 2P, 2T, 2S 3P, 3T, 3S 3PR, 3TR, 3SR 3TN, 3TZ 3TNR, 3TZR
Number of sensors 2CT 3CT
Overcurrent � � � � �
Phase failure � � � � �
Lock/Stall � � � � �
Phase unbalance � � � �
Reverse phase � �
Ground fault � �

● Large current can be applied through additional current transformers


● MCU (Microprocessor Control Unit) built-in
- excellent reliability by achieving real-time data processing and high precision.
● Store of the last failure cause
- can be checked by Test/Reset button 2 times.
● Products for ground fault protection
- detecting of zero phase currents (ZCT used: GMP60-3TZ)
- detecting of residual currents (ZCT unused: GMP60-3TN)

G-6
Features
DMP Series

● Digital measuring and displaying


- Display digital ampere-meter
- Save the causes of the fault and the value
- Display motor load rate by graph

Digital display
R phase Bar graph

S phase

T phase Display button

Test/Reset button

FUNC button Sel button


R R R
Current knob
S S S
Time knob T T T

R phase current value S phase current value T phase current value

G
● Convenient structure

EMPR/DMPR
- Install the Unit / Extension type in one body
The display part may be separated from the body
You can check the values and the causes of the
fault without opening the distribution panel door
- removable terminal block

● Various protection functions


Protection �-S/Sa
DMP� �-SZ/SZa
DMP� �-SI
DMP� �-T/Ta
DMP� �-TZ/TZa
DMP� �-TI
DMP�
Wiring Screw type Tunnel type
Over current � � � � � �
Under current � � � � � �
Stall � � � � � �
Lock � � � � � �
Phase failure � � � � � �
Reverse phase � � � � � �
Phase unbalance � � � � � �
Ground fault � �
Short circuit � �

● Trip curve selectable (Inverse/Definite) ● Applicable to inverter control circuit


LS DMPR has high performance under the harmonic noise and can be
used in the Inverter control circuit (20~200Hz)
● Optional functions (DMP-a type)

- Storing up the last fault cause


- Storing up motor operation hours

Inverse time characteristics Definite time characteristics

G-7
Electronic motor protection relays
Features
IMP Series

The EMPR IMP series are optimal solutions for protecting and monitoring motors in
complex industrial fields and provide high safety and productivity.

~100A Wide Current Setting Range: Total Digital Motor Protection Relay with
0.125~100A for One Model the MCU (Microprocessor Control Unit)
MCU
With the slide S/W, the current setting range Real-time processing and high precision
can be decided 0.5~10A or 5~100A. According
to the CT penetration number, even 0.125A
One-Body Type and Separate Body Type
current can be protected. (Wire penetration
The display can be attached to the panel front
hole).
so that current, operation time and settings can
be checked without fetching the unit. With the
Communication support type display separated, the motor can be protected.
RS-485 MODBUS communication with various
systems.The model with analogue signals
Applicable to Inverter Circuits
(4~20mA) is compatible with transducer
Thanks to its good high harmonic noise
systems. INV
characteristics, it can be applied to the of
inverter control circuits. The available
Thermal Inverse Time, frequency range is 20~200Hz. When the
Inverse Time and Definite Time Modes relative harmonic factor is over 30%, a
According to user’s needs, the motor can be harmonic filter should be installed (However,
protected in the inverse time mode or definite the ground fault function should be off).
time mode.

Various Reset Functions


Wide Ground Fault Sensitivity Manual, automatic and electric reset functions
Return
30mA 25A 30mA~25A are provided for customer convenience.
zero current sensing by zero sequence CT.
zero current sensing by Residual circuit.
Password
Settings are protected with a password.
Date and Total Operating Time Setup
When a fault occurs, its date and time are
stored for easy checkup. When the total
Storage of Fault Events
Up to five fault events can be stored for easy
operation time is over, it is displayed for
Save fault history management.
changing motor bearings or supplying oil.

3-Phase Digital Ampere-Meter


Quick Setup
3-phase current is displayed every two
All settings can be decided quickly on the
seconds for motor monitoring.
display.

G-8
Ordering

GMP Series

GMP 22 2 P R a 1.5A 220 1a1b Sol

Frame Nominal Current Type CT Type Reverse Phase Nominal Current Current Setup Range (A) Operation Current Aux. contactor Model Type
1.5A 2 2CT Reverse Protection 1.5A 0.3~1.5 110/220 AC 100~260V 1c Terminal
Direct - (Screw)
22 5A Coupling, 3 3CT No Protection 5A 1~5 24 AC 24V 1a1b - Penetration
22A Terminal Reverse Protection 22A 4.4~22 48 AC 48V Note) When the (Tunnel)
Connection, Type R power is
20A Protection Available 20A 4~20 110 AC 110V
Penetration applied, the Metasol
40 P Direct Coupling(Pin)
40A Automatic 40A 8~40 220 AC 220V system is in Direct
A the contacting Sol Coupling
80 80A Terminal Connection Terminal Recovery 80A 16~80 380 AC 380 (440)V
S status. (Pin)
06A Connection(Screw) 06A 0.5~6 Note) AC 24V, AC48V and
Penetration AC380 (440)V are for
60 30A Penetration 30A 3~30
T GMP60T.
60A (Tunnel) 60A 0.5~60 Note)
TE Economic Note) For GMP60-TD, GMP60-TDa 6/60A,
GMP60-3TZ (R), 3TN (R), 3T (R)
PD
Direct Coupling
(Definite Time)
G
Current Display
TD

EMPR/DMPR
(Definite Time)
Ground Fault Protection Classification
TZ (Zero-Phase- Sequence
Current Detection) - Existing Model
Ground Fault Protection Operation Time
TN (Residual Current a
Detection) Function

DMP Series

DMP 06 S Z a 220 1a1b

Current Control Range Wiring OPTION Classification Control Voltage Aux. contactor
06 0.5~6A Terminal - Standard Model - Existing Model 220 AC 220V 1a1b
S
36 3~36A (Screw) Ground Fault 110 AC 110V 2a
a Operation Time
Z
60 5~60A Penetration Protection Function 2b
T
(Tunnel) Short circuit 2a1b
I
Protection
Note) 1. Even the same model has different contact specifications.
2. When the power is applied, the system is in the contacting status.

IMP Series

IMP C A420

Items to be Protected Communication


C Current NO None
A420 4~20mA Output
M485 MODBUS/RS-485

G-9
Electronic motor protection relays
Specification
GMP Series

Ratings

GMP22- GMP22- GMP22- GMP22-


Model GMP22-2P/PD (1c) GMP22-2S GMP22-2T
2P(1a1b) 3P/3PR 3S/3SR 3T/3TR
Type Pin type Screw type Tunnel type
No. of CT 2CT 2CT 3CT 2CT 3CT 2CT 3CT
Protection Overcurrent ● ● ● ● ● ● ●
Phase failure Note1) ● ● ● ● ● ● ●
Lock/Stall ● ● ● ● ● ● ●
Phase unbalance — — ● — ● — ●
Reverse phase — — ●(3PR) — ●(3SR) — ●(3TR)
Current setting range (A) 0.3~1.5, 1~5, 4.4~22
Operating time characteristics Inverse time (GMP22-2PD: Definite time)
Time setting Inverse time 0~30 sec
(sec) Definite D-time 0.2~60 sec for GMP22-2PD
O-time 5sec (Fixed) for GMP22-2PD
Reset-time Manual reset
Tolerance Current ±5%
Time ±5%(or±0.5sec)
Control power Voltage AC 110V/220V(±10%) AC 100~260V
Frequency 50/60Hz
Aux. contact Contact Note 3) 1SPDT (1c) 2SPST (1a1b)
Ratings 5A/250VAC Resistive load 3A/250VAC Resistive load
Operate (95 96 Close) (95 96 Close) (97 98 Open)
Insulation resistance Min 100㏁ at 500Vdc
Surge endurance (IEC 61000-4-5) 5kV Apply the standard wave
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -30~80℃
Relative humidity 30~90%RH(No freezing)
Trip indicator Red LED Red/Green LED Red LED Red/Green LED Red LED Red/Green LED
Dimension (mm) ×H×
W× ×D 44×71×78 53×78×87.5 53×68×87.5 53×38×87.5
Mounting type Direct mount onto a Metasol MC (MC-9b-22b) Separate mount (Screw or Din-rail) Note2)
Certification UL, cUL, CE
Note) 1. When it is 2CT modle, only two-phase protection is available
2. The bracket for Din-rail mount is optional
3. When power applied Aux. contact operate

G-10
Specification
GMP Series

Ratings

GMP40- GMP40- GMP40- GMP40- GMP80- GMP80-


Model GMP40-2S GMP40-2T
2P/PD/PA 3P/3PR 3S/3SR 3T/3TR 2S/SA 3S/3SR
Type Pin type * Screw type Tunnel type Screw type
No. of CT 2CT 3CT 2CT 3CT 2CT 3CT 2CT 3CT
Protection Overcurrent ● ● ● ● ● ● ● ●
Phase failure Note1) ● ● ● ● ● ● ● ●
Lock/Stall ● ● ● ● ● ● ● ●
G
Phase unbalance — ● — ● — ● — ●
— ●(3PR) — ●(3SR) — ●(3TR) — ●(3SR)

EMPR/DMPR
Reverse phase
Current setting range(A) 4~20, 8~40 16~80
Operating time characteristics Inverse time characteristics
Time setting Inverse time 0~30 sec
(sec) Definite D-time 0.2~60 sec (GMP40-2PD)
O-time 5sec (Fixed) (GMP40-2PD)
Reset time Manual reset (Auto Reset type : GMP□-A)
Tolerance Current ±5%
Time ±5% (or±0.5 sec)
Control power Voltage AC 100~260V, 50/60Hz
Aux. contact Contact Note2) 2SPST (1a1b)
Ratings 3A/250VAC Resistive load
Operate (95 96 Close) (97 98 Open)
Insulation resistance Min 100㏁ at 500Vdc
Surge endurance (IEC 61000-4-5) 5kV Apply the standard wave
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -30~80℃
Relative humidity 30~90%RH (No freezing)
Trip indicator Red LED Red/Green LED Red LED Red/Green LED Red LED Red/Green LED Red LED 2Red LEDs
Dimension(mm) ×H×
W× ×D 53×78×87.5 53×68×87.5 53×38×87.5 89×77.5×97.4
Mounting type Direct mount onto a
Separate mount (Screw or Din-rail)
Metasol MC (MC-32a, 40a)
Certification UL, cUL, CE

Note) 1. When it is 2CT modle, only two-phase protection is available


2. When power applied Aux. Contact operate

G-11
Electronic motor protection relays
Specification
GMP Series

Ratings

GMP60TE GMP60-3TZ(R)
Model GMP60T GMP60-TD GMP60-TDa GMP60-3T(R)
GMP60TA GMP60-3TN(R)
Type Tunnel type Tunnel type Tunnel type Tunnel type
No. of CT 2CT 2CT 3CT 3CT
Protection Overcurrent ● ● ● ●
Phase failure ● ● ● ●
Lock/Stall ● ● ● ●
Phase unbalance — — ● ●
Reverse phase — — ●(R Type) ●(R Type)
Note1)
Ground fault — — — ●
Current setting range (A) 0.5~6, 3~30, 5~60 0.5~60 0.5~60 0.5~60
Operating time characteristics Definite Definite Definite Definite
Time setting D time 0.2~30 sec 1~60 sec 0.2~60 sec 0.2~60 sec
(sec) O time 0.2~30 sec 5 sec (Fixed) 0.5~30 sec 0.2~15 sec 3 sec (Fixed)
A time (Reset) — 0.2~120 Note4) — 1~20 min — —
Tolerance Current ±5% Time ±5% (or±5 sec)
Control power Voltage Note3) AC 110V/220 (±10%) Note3) AC 110V or 220V AC 100V~260V
Frequency 50/60Hz
Aux. contact Contact Note2) 1SPDT (1c) 2SPST (1a1b)
Ratings 1A/250VAC Resistive load 3A/250VAC Resistive load
Insulation resistance Min 100㏁ at 500Vdc
Surge endurance (IEC 61000-4-5) 5kV Apply the standard wave
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -30~80℃
Relative humidity 30~90% RH (No freezing)
Trip indicator Red LED 7 Segment Red/Green×2-Color LED Red/Green×2-Color LED, Red LED
Dimension(mm) ×H×
W× ×D 72×67×69 75×72.8×47 94.6×95×97 94.6×95×97
Mounting type Separate mount (Screw or Din-rail)
Certification UL, cUL, CE
Note) 1. 3TZ(R): Zero sequence CT type, 3TN(R): Residual curcuit
2. When power applied the Aux. contact operate
3. GMP60T/TE: AC24V, 48V or 380V, 50/60Hz types a option
4. GMP60TA: Auto Reset type

G-12
Specification
DMP/IMP Series

Ratings

Model �-S/SZ/SI
DMP� �-Sa/SZa
DMP� �-T/TZ/TI
DMP� �-Ta/TZa
DMP� IMP-C-NO IMP-C-A420 IMP-C-M485

Wiring Screw type Tunnel type Tunnel type


Panel mount Unit or Extension Note1) Unit or Extension
Operation time Inverse/Definite Thermal Inverse/Inverse/Definite
Protection Over current According to the setting time According to the setting time
Phase failure 3 sec 1.5 sec
G
Reverse phase Within 0.1 sec Within 0.1 sec
Within 0.5 sec Within 0.5 sec

EMPR/DMPR
Lock/Stall
Phase unbalance 5 sec 5 sec
Under current 3 sec 3 sec
Ground fault Within 0.05~1 sec. (DMP�-Z/Za Model) Within 0.05~1 sec Note2)
Short circuit Within 50ms (DMP�-I Model) Within 50ms
Alarm Variable (60~110% of the setting current) Variable (60~110% of the setting current)
Current setting range (A) 6: 0.5~6A, 36: 3~36A, 60: 5~60A 0.5~100
Time setting Definite D time 0~60 sec 1~200 sec
(sec) O time 0~30 sec 1~60 sec
Inverse time 0~60 sec 1~60 sec
A time (Reset) Manual reset Manual reset/Autometic
Tolerance Current ±5% ±5%
Time ±5% (or±0.5 sec) ±5% (or±0.5 sec)
Operating power Voltage AC 110V or 220V, 50/60Hz AC/DC 85~245V, 50/60Hz
Aux. contact 2a, 2b, 1a1b OL: 1a1b, AL: 1a
Insulation resistance Over DC 500V 100㏁ Over DC 500V 100㏁
Surge impulse voltage (IEC 61000-4-5) 5kV 5kV
Fast transient burst (IEC 61000-4-4) 2kV 2kV
Environment Operation -25~70℃ -25~70℃
Temperature Storage -30~80℃ -30~80℃
Relative humidity 30~90% RH (No freezing) 30~90% RH (No freezing)
Display 7-Segment 3 phase current, cause of a fault 3 phase current, cause of a fault
Bar-Graph 60~110% of real load current 60~110% of real load current
Mounting type 35mm Din-rail/Panel 35mm Din-rail/Panel
Certification UL, cUL, CE
Note) 1. In extension type, the digital EMPR is calibrated with combining the display past and main body so, please cautious not to combine the display part and main body with different part No.
2. Zero current sensing by zero sequencee CT and Residual circuit.

G-13
Electronic motor protection relays
Inverse time characteristics
GMP22/40 Type

Description
- Wide and adjustable current range
- Adjustable trip time (trip class 5-30)
- Designed suitable for use with contactors
Directly mountable on the Metasol contactors (Pin type)
Separate mount versions are also available
Separately mountable on 35mm DIN rail or with screws
- 1NO+1NC trip contacts
- Manual reset as standard (Automatic reset optional)

Front face configuration

Current setting LED indicator Test/Reset button Trip time setting


GMP22 type Operation status indication - 0 to 30 sec
0.3 ~ 1.5A - Normal operating - Set time is the trip time
1 ~ 5A - Overload at 6 x set current
1.1 ~ 22A - Phase unbalance
GMP40 type Trip cause indication
4 ~ 20A - Overcurrent
8 ~ 40A - Phase loss
- Reverse phase

Extended protective functions


�)
Types (GMP22/40-� -2P, -2T, -2S -3P, -3T, -3S -3PR, -3TR, -3SR
Number of sensors 2CT 3CT 3CT
Overcurrent
Phase failure
Functions Locked rotor
Phase unbalance
Reverse phase

Technical information
Relay control voltage 100 to 260V AC 50/60Hz
3A/250VAC at resistive load
Auxiliary contact
1NO (97-98) + 1NC (95-96)
Current ± 5%
Setting tolerance
Time ± 5% (or ± 0.5sec)
Insulation resistance Min 100㏁ at 500V DC
Impulse withstand voltage 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
Certificate -25 to 70℃ for operation
CE, ULcUL Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH

G-14
Inverse time characteristics
GMP22/40 Type

Selection (GMP22 Type)


Mount/Connection Sensor Setting range Catalog No.
Directly on a contactor 2-sensor 0.3 - 1.5A GMP22 - 2P∙1.5
(2 CT) 1 - 5A GMP22 - 2P∙5
4.4 - 22A GMP22 - 2P∙22
3-sensor 0.3 - 1.5A GMP22 - 3P∙1.5
(3 CT) 1 - 5A GMP22 - 3P∙5
4.4 - 22A GMP22 - 3P∙22
To mount on 35mm DIN rail 3-sensor 0.3 - 1.5A GMP22 - 3PR∙1.5
Reverse phase 1 - 5A GMP22 - 3PR∙5
detection 4.4 - 22A GMP22 - 3PR∙22
Separate mount 2-sensor 0.3 - 1.5A GMP22 - 2S∙1.5
(2 CT) 1 - 5A GMP22 - 2S∙5
Cable connection 4.4 - 22A GMP22 - 2S∙22
with a screw 3-sensor 0.3 - 1.5A GMP22 - 3S∙1.5
(3 CT) 1 - 5A GMP22 - 3S∙5
4.4 - 22A GMP22 - 3S∙22
3-sensor 0.3 - 1.5A GMP22 - 3SR∙1.5
Cable connection part can be modified Reverse phase 1 - 5A GMP22 - 3SR∙5 G
between screw connection and detection 4.4 - 22A GMP22 - 3SR∙22
passing CT hole

EMPR/DMPR
Separate mount 2-sensor 0.3 - 1.5A GMP22 - 2T∙1.5
(2 CT) 1 - 5A GMP22 - 2T∙5
Connection 4.4 - 22A GMP22 - 2T∙22
without a screw 3-sensor 0.3 - 1.5A GMP22 - 3T∙1.5
- cables pass (3 CT) 1 - 5A GMP22 - 3T∙5
through CT holes 4.4 - 22A GMP22 - 3T∙22
3-sensor 0.3 - 1.5A GMP22 - 3TR∙1.5
Reverse phase 1 - 5A GMP22 - 3TR∙5
detection 4.4 - 22A GMP22 - 3TR ∙22

Selection (GMP40 Type)


Mount/Connection Sensor Setting range Catalog No.
Directly on a contactor 2-sensor 4 - 20A GMP40-2P∙20
(2 CT) 8 - 40A GMP40-2P∙40
3-sensor 4 - 20A GMP40-3P∙20
(3 CT) 8 - 40A GMP40-3P∙40
3-sensor 4 - 20A GMP40-3PR∙20
Reverse phase 8 - 40A GMP40-3PR∙40
detection
Separate mount 2-sensor 4 - 20A GMP40-2S∙20
(2 CT) 8 - 40A GMP40-2S∙40
Cable connection 3-sensor 4 - 20A GMP40-3S∙20
with a screw (3 CT) 8 - 40A GMP40-3S∙40
3-sensor 4 - 20A GMP40-3SR∙20
Reverse phase 8 - 40A GMP40-3SR∙40
detection
Separate mount 2-sensor 4 - 20A GMP40-2T∙20
(2 CT) 8 - 40A GMP40-2T∙40
Connection 3-sensor 4 - 20A GMP40-3T∙20
without a screw (3 CT) 8 - 40A GMP40-3T∙40
- cables pass 3-sensor 4 - 20A GMP40-3TR∙20
through CT holes Reverse phase 8 - 40A GMP40-3TR∙40
detection

G-15
Electronic motor protection relays
Definite time characteristics
GMP60-T(E) Type

Description
- Small size, economical
- Delay time setting in starting and operation
- Over current, phase failure protection
- Definite time characteristics
- Wide current setting range
- Screw or Din-rail mounting

Extended protective functions


Types GMP60-T GMP60-TE GMP60-TA
Number of sensors 2CT 2CT 2CT
Overcurrent
Note1)
Phase failure
Functions
Locked rotor
Auto reset

Ratings (Tunnel type)


Model GMP-60T GMP-60TE GMP-60TA
Type Tunnel type
No. of CT 2
Current setting range (A) 0.5~6, 3~30, 5~60
Operating time characteristics Definite time characteristics
Starting time 0.2~30
Time setting
Operating time 0.2~15 5 5
(sec)
Reset time Manual reset 0.2~120
Large current over 60A can be applied Allowable Current ±5%
through additional current transformers
error Time ±5% (or ±0.5 sec)
Voltage 180~260V (AC 24V, 48V, 110V / 440V) Note2)
Control power
Frequency 50 / 60Hz
Contact Note3) 1SPDT (1c)
Aux. s/w Ratings 5A 250Vac, resistive load
Operation 95 96close
Insulation resistance Min. 50㏁ at 500Vdc
Surge insurance (IEC 61000-4-5) 5kV
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -50~80℃
Relative humidity 46~85 RH (No freezing)
Trip indicator LED
×H×
Dimension (mm) W× ×D 72×63×69
Mounting type Separate mount (Screw & Din-rail)
Certification UL, cUL, CE
Note) 1. Under phase failure condition over current flows. The EMPR tripped if it is over the setting over current
2. ( ) are optional specifications
3. When power applied the Aux. contact operate

Tunnel type EMPR protects the current under 0.1A


If we increase the number of times of a wire pass through the CT (Tunnel), the EMPR can detect the lower current
No. of times to pass through Current setting range
1 0.5~6
2 0.25~3
3 0.17~2
4 0.12~1.5

G-16
Ampere meter function
GMP60-TD(a) Type

Description
- Definte time characteristics
- Delay time setting in starting and operation
- Over current, phase failure protection
- Definite time characteristics
- Wide current setting range
- Screw or Din-rail mounting
- Display the causes of the fault and the values

Extended protective functions


Types GMP60-TD GMP60-TDa
Number of sensors 2CT 2CT
Overcurrent
Note1)
Phase failure
Functions Locked rotor
Under current
Auto reset
* Only two-phase oretectuib is available.
G
Ratings (Tunnel type)

EMPR/DMPR
Model GMP60-TD GMP60-TDa
Type Tunnel type
No. of CT 2
Current setting range (A) 0.5~60
Operating time characteristics Definite time characteristics
Delay time 1~60
Time setting
Operating time 0.5~30
(sec)
Reset time Manual reset 1~20min
Allowable Current ±5%
error Time ±5% (or ±0.5 sec)
Voltage AC 110/220V
Control power
Frequency 50 / 60Hz
Contact Note2) 2SPST (1a1b)
Aux. s/w Ratings 5A 250Vac, resistive load
Operation 95 96close 97 98open
Insulation resistance Min. 50㏁ at 500Vdc
Surge insurance (IEC 61000-4-5) 5kV
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -50~80℃
Relative humidity 46~85 RH (No freezing)
Trip indicator 7-Segment
×H×
Dimension (mm) W× ×D 72×63×69
Mounting type Separate mount (Screw & Din-rail)
Certification UL, cUL, CE
Note) 1. Under phase failure condition over current flows. The EMPR tripped if it is over the setting over current
2. When power applied the Aux. contact operate

Tunnel type EMPR protects the current under 0.1A


If we increase the number of times of a wire pass through the CT (Tunnel), the EMPR can detect the lower current
No. of times to pass through Current setting range Current Ratio
1 0.5~6 1
2 0.25~3 0.5
4 0.12~1.5 0.25

G-17
Electronic motor protection relays
Definite time characteristics with 3CT
GMP60-3T(R) Type

Description
- Cable connecting through CT holes (option: with screw)
- Auxiliary contact: 2SPST (1a1b at energization)
- Wide and adjustable current range (0.5~60A)
- D-time: 0.2~60 sec. / O-time: 0.2~15 sec.
- Control voltage: AC100~245V 50/60Hz
- Manual(electrical) reset as standard
- Applicable to inverter at the secondary circuit (except GMP60-3TR)

GMP60-3T
GMP60-3TR

Extended protective functions


Types GMP60-3T GMP60-3TR
Number of sensors 3CT 3CT
Overcurrent
Phase failure
Protective
Locked rotor
functions
Phase unbalance
Reverse phase

Terminal Lug
Storing the last fault cause

Selection
Mount/Connection Optional function Setting range Catalog No.

∙Separate mount None 0.5 - 60A GMP60-3T


∙Cable Connection
through CT holes Reverse phase 0.5 - 60A GMP60-3TR

Large current over 60A can be


applied through additional current
transformers

Technical information
Mounting On 35mm rail or panel with screws
Current ± 5%
Setting tolerance
Time ± 5% (or ±0.5sec)
Frequency 50/60Hz
Auxiliary contact rating 5A/250VAC at resistive load
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
-25 to 70℃ for operation
Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH
Operating indication Red/Green 2-color LED, Red LED
Standard UL508, IEC60947-1

G-18
For ground fault current protection
GMP60-3TZ(R), 3TN(R) Type

Description
- Cable connecting through CT holes
- Auxiliary contact: 2SPST (1a1b at energization)
- Wide and adjustable current range (0.5~60A)
- Definite time characteristics
D-time: 0.2~60sec. / O-time: 3sec.
- With 3 sensors (CT)
- Control voltage: AC100~245V (50/60Hz)

GMP60-3TZ, 3TZR
GMP60-3TN, 3TNR

Extended protective functions


Types GMP60-3TZ, 3TN GMP60-3TZR, 3TNR
Number of sensors 3CT 3CT
Overcurrent
Phase failure
Protective Ground fault G
functions Locked rotor
Phase unbalance

EMPR/DMPR
Reverse phase
Terminal Lug
Storing the last fault cause

Selection
Mount/Connection Ground fault current Optional function Setting range Catalog No.
Zero phase current
∙Separate mount (0.1~2.5A) None 0.5 - 60A GMP60-3TZ
∙Cable Connection *ZCT required
through CT holes Reverse phase 0.5 - 60A GMP60-3TZR
Residual current
(0.5~6A) None 0.5 - 60A GMP60-3TN

Reverse phase 0.5 - 60A GMP60-3TNR


Note) Use ZCT for EMPR, 100mA/40 ~ 55mV

Technical information
Mounting On 35mm rail or panel with screws
Current ± 5%
Setting tolerance
Time ± 5% (or ±0.5sec)
Frequency 50/60Hz
Auxiliary contact rating 5A/250VAC at resistive load
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
-25 to 70℃ for operation
Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH
Operating indication Red/Green 2-color LED, Red LED
Standard IEC 61000, KEMC 1120

G-19
Electronic motor protection relays
Inverse time characteristics
GMP80 Type

Description
- Wide and adjustable current range
- Adjustable trip time (trip class 5-30)
- Separately mountable on 35mm DIN rail or with screws
- 1NO+1NC trip contacts
- Manual reset as standard (Automatic reset optional: GMP80-2SA)

Front face configuration

Test/Reset button LED indicator Current setting Trip time setting


Operation status indication 16 ~ 80A - 0 to 30 sec
- Normal operating - Set time is the trip time
- Phase unbalance at 6 x set current
- Overcurrent
- Phase loss
- Reverse phase (R-type)

Extended protective functions


�)
Types (GMP80-� 2S 2SA 3S 3SR
Number of sensors 2CT 2CT 3CT 3CT
Overcurrent
Phase loss
Functions Locked rotor
Phase unbalance
Reverse phase
Auto reset

Selection
Mount/Connection Sensor Setting range Catalog No.
Separate mount 2-sensor 16 - 80A GMP80-2S
(2 CT)
Cable connection 3-sensor 16 - 80A GMP80-3S
with a screw (3 CT)
3-sensor 16 - 80A GMP80-3SR
Reverse phase detection

Technical information
Relay control voltage 100 to 260V AC 50/60Hz
Auxiliary contact 3A/250VAC at resistive load
1NO (97-98) + 1NC (95-96) (When power applied)
Setting tolerance Current ± 5%
Time ± 5% (or ±0.5sec)
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
Certificate Ambient temperature -25 to 70℃ for operation
-30 to 80℃ for storage
CE, ULcUL
Humidity 30 to 90% RH

G-20
Characteristics DMP Series
DMP-S(a)/SZ(a)/SI Type

�Unit type or extension type is available


- Extension type: Remotely mounts the display unit on the panel surface
�Ampere meter function: current and setting value by press the display button
�Select the inverse time or definite time
�Display the causes of the fault and the values
�Load ratio is displayed up to setting current

Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 3seconds Over 70% of the rate of unbalance
Phase unbalance Within 5seconds Over 50% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 5seconds Over 180% of the setting current
Lock Within 0.5seconds Setting 200~900% of rated current
Under current Within 3seconds Setting 30~70% of rated current
Note) Lock protection is operated after setting D-time in case of definite time type
G
Function selection

EMPR/DMPR
FUNC Sel Description
1. CHA Inv/dEF Operating characteristics setting (Inverse/definite time type)
Extention type (with cable) 2. dEF Note1)
0~30 (S) Setting the operating time (In definite type)
3. r.P oFF/on Reverse phase enable
4. Und oFF/30~70 (%) Under current enable and setting
5. Alt oFF/60~110 (%) Alerting enable and setting
6. Stl oFF/on Stall enable
7. Loc oFF/200~900 (%) Lock enable and setting
8. Ct 1~120 CT ratio setting
9. P.F on/oFF Phase fault enable
b. StA Note2)
0~120 Operating time setting by month
c. StH 10~730 Operating time setting by hour
d. tAH A000,000.0 Displaying total operating time (month, hour)
E. rAH A000,000.0 Displaying operating time (month, hour)
Sto Sto Store
Note) 1. 2.dEF is only displayed when dEF is selected in a 1.CHA mode
2. Functions for b to e are available for only Sa & SZa type.

Ratings
Model �-S/Sa
DMP� DMP� �-SZ/SZa/SI
Type Wiring method Screw
Panel mount Unit or Extension
Operating characteristics Inverse/definite type
Alerting function Variable between 60 and 110%
Current range (A) 06: 0.5~6, 36: 3~36, 60: 5~60
Setting time Definite Delay (D-T) 0~60seconds
Operating (O-T) 0~30seconds
Inverse 0~60seconds
Reset type Manual reset
Operating Voltage AC 110V or AC 220V
voltage Frequency 50/60Hz
Aux. contacts OL 2-SPST (95~98) 3A/250Vac resistive load
AL SPST (07-08) 3A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel
Certification UL, cUL, CE

G-21
Electronic motor protection relays
Characteristics DMP Series
DMP-T(a)/TZ(a)/TI Type

�Unit type or extension type is available


- Extension type:Remotely mounts the display unit on the panel surface
�Ampere meter function: current and setting value by press the display button
�Select the inverse time or definite time
�Display the causes of the fault and the values
�Ground fault protect function is added

Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 3seconds Over 70% of the rate of unbalance
Phase unbalance Within 5seconds Over 50% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 5seconds Over 180% of the setting current
Lock Within 0.5seconds Setting 200~900% of rated current
Under current Within 3seconds Setting 30~70% of rated current
Selectable Grounded current setting by dip s/w
Ground fault Note)

0.05~1.0seconds (100~2500mA)
Note) Lock protection is operated after setting D-time in case of definite time type

Function selection
FUNC Sel Description
1. CHA Inv/dEF Operating characteristics setting (Inverse/definite time type)
2. dEF Note1)
0~30 (S) Setting the operating time (In definite type)
3. r.P oFF/on Reverse phase enable
Extention type (with cable) 4. Und oFF/30~70 (%) Under current enable and setting
5. g-F oFF/0.05~1.0 (S) Ground fault enable and setting
6. Stl oFF/on Stall enable
7. Loc oFF/200~900 (%) Lock enable and setting
8. Ct 1~120 CT ratio setting
9. P.F on/oFF Phase fault enable
A. gFd Note2)
oFF/on Setting delay of ground fault
b. StA 0~120 Operating time setting by month
c. StH 10~730 Operating time setting by hour
d. tAH A000,000.0 Displaying total operating time (month, hour)
E. rAH A000,000.0 Displaying operating time (month, hour)
Sto Sto Store
Note) 1. 2.dEF is only displayed when dEF s selected in a 1.CHA mode
2. Functions for b to e are available for only SZa & TZa type.
3. Ground fault sensitive current selection: TZa type

Ratings
Model �-T/Ta
DMP� DMP� �-TZ/TZa/TI
Type Wiring method Tunnel
Panel mount Unit or Extension
Operating characteristics Inverse/definite type
Alerting function Variable between 60 and 110%
Current range (A) 06: 0.5~6, 36: 3~36, 60: 5~60
Setting time Definite Delay (D-T) 0~60seconds
Operating (O-T) 0~30seconds
Inverse 0~60seconds
Reset type Manual reset
Operating voltage AC 110V or AC 220V
voltage Frequency 50/60Hz
ZCT input (07-08) 200mA/110mV (ZCT)[30∅, 50∅, 65∅, 80∅]
Aux. contacts (2a, 2b, 1a1b) OL, GR 2-SPST (95~98) 3A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel

G-22
Characteristics IMP Series
IMP-C Type

�MODBUS RS-485 Communication or 4~20mA analogue output


�3 phase ampere meter function: Check the 3 phase current and setting value by press the
display button
�Select the Thermal inverse/inverse time or definite time
�Easy to operate: Set the most function by the operation button and knob
�Display the causes of the fault and the values
�Adjustable wide current range (0.5~100A)

Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 1.5seconds Over 70% of the rate of unbalance
Phase unbalance Within 3seconds 10~70% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 3seconds setting 150~500% of rated current
Lock Note1)
Within 0.5seconds Setting 200~800% of rated current
Under current Within 3seconds Setting 30~90% of rated current
Selectable 0.05, gF: 0.03/0.05/0.1~3A
Ground fault Note2)

0.1~1.0seconds gn: 20~500% of the FLC min


Note) 1. Lock protection is operated after setting D-time in case of definite time selected.
2. 12. gF Zero sequence CT, 13. gn Residual circuit sensing.
G
Setting Menu (A Group) Setting Menu (B Group)

EMPR/DMPR
Menu Setting Value Item Default Value Menu Setting Value Item Default Value
Operation Characteristics (Definite Time / 1.E-r On/OFF Electric Recovery On
1.CHA dEF/th/n-th Heat Accumulation Inverse Time /Inverse Time) n-th
2.A-r OFF, 1~20 min Automatic Recovery (Minute) OFF
2.O-t 1~60s Operation Time (sec) 60
3.r-t Hour/Minute Operation Time Time Check
3.d-t 1~200s Operation Delay (sec) In chase of dEF
Extention type (with cable) 4.r-C 0.5~10A/5~100A Rated Current Max.
4.Srt OFF, 1~8760Hour Operation Time Setup (Hour) -
5.s-d 2009/01.01/00:00 YY/MM/DD/ HH:MM -
5.Ctr 0.25, 0.5, 1~200 CT Ratio (4 times, twice, once) 1
6.Trt Day/hour:minute Total Operation Time Time Check
6.Loc OFF, 200~800% Lock Protection (sec) OFF
A.t-d 0.5~10/5~100A 20mA Output Setup A420
7.StL OFF, 150~500% Stall Protection (sec) OFF
A.Adr 1~247 Communication Address
8.P-F OFF/On Open Phase OFF
b.bps 96/192/384 Communication Speed M485 Model
9.P-U OFF, 10~70% Unbalance Protection (%) OFF
c.S-P On/OFF SWAP
10.rP OFF/On Reverse Phase OFF
11.UC OFF, 30~90% Low Current Protection (%) OFF Note) 1. When the power is supplied first or is resupplied after a power
Ground Fault Operation Current failure, must set up the date (5.S-d).
12.gF 0FF, 0.03, 0.05/0.1~3A (Zero-Phase-Sequence Current) (A) OFF
2. Automatic recovery is only possible in case of an excess
Ground Fault Operation Current current trip.
13.gn OFF, 20~500% (FLCmin) OFF
(Post-Arc Current) (FLCmin)
14.gt 0.05, 0.1~1.0s Ground Fault Operation Time (Current) -
15.gd On/OFF Ground Fault Delay During Start ON
16.IC OFF, 500~1000% Instantaneous Protection (%) OFF
17.Io ALt/TriP Instantaneous Warning/Operation TriP
Note) 1. When the rated current S/W is 100A, the CT ratio is not displayed.
2. Some menus are not displayed if relevant functions are not available.

Ratings
Model IMP-C-NO, M485, A420
Type Wiring method Tunnel
Panel mount Unit or Extension
Operating characteristics defin/TH-Inv./n-TH
Alerting function Variable between 60 and 110%
Current range (A) 0.5~100
Setting time Definite Delay (D-T) 1~200seconds
Operating (O-T) 0~30seconds
Inverse/TH-Inverse time 0~60seconds
Reset type Manual reset
Operating voltage AC 85~245V, 50/60Hz
ZCT input (07-08) 200mA/110mV (ZCT)[30∅, 50∅, 65∅, 80∅]
Aux. contacts (2a, 2b, 1a1b) OL, GR 2-SPST (95~98) 5A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause 5point
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel
Communication A420: Analog, M485: Modbus
Certification CE

G-23
Electronic motor protection relays
Setting method
GMP Series Inverse time

1. Check the rated voltage and apply the control power to A1 and A2 terminal
2. Check the TEST/RESET button
1) When you press the ‘Test/Reset’ button, the O.L LED is turned on and the EMPR is tripped
2) When you press the ‘Test/Reset’ button under the EMPR is tripped, the O.L LED is turned
off and the EMPR is reset
3) Auto reset function: When it is tripped by the over current, it is reset after 1 Min.(Optional)

3. Set the operating time


The operating time is set on the base of 600% of the rated current in the characteristic curve
1) Set the operating time by considering the operating time and start current according to the
types of the load
2) If the time knob is set to 10sec, the EMPR is tripped when the start current (600% of the
rated current) is applied for 10sec
Caution) The EMPR with inverse time characteristics can be tripped to protect the motor when the motor is started a few times continuously
When a motor is frequently changing the rotating direction (forward and reverse), set the operating time longer For the crane and hoist
use, select the EMPR with definite time characteristics

4. Set the operating current


Set the current by considering the rated current of a motor to protect from the over current
1) Check the rated current of a motor is within the current setting range of an EMPR
2) Set the ‘RC’ (Rated current) knob to the maximum value and then start a motor
3) Under normal motor operation, rotate the‘RC’knob to the counterclockwise until the
‘O.L’LED flickers The current at this point in the 100% current rating under real load
4) At this point, rotate the‘RC’knob to the clockwise until the‘O.L’LED turned off.
Ex) When the ‘O.L’ LED flickering at 20A, the setting current will be 22A(=20x1.1)
Note) The brackets for connection is offered standard

5. Check status of operation by LED


1) In case of overcurrent
If there will be an overcurrent during motor operation, the red color of LED will flicker at 0.4
second intervals. After tripping because of overcurrent, the red color of LED will light up.
2) In case of phase failure
If there will be a phase failure in three phase load, it will be tripped within 3 seconds.
Note) 2CT EMPR can protect motor from R or T phase failure.
3) In case of phase unbalance
If phase unbalance rate is over 50%, FAULT LED will flicker 0.4 second intervals.
4) In case of Reverse phase
Red & green color LED will flicker alternately.

Condition LED Status LED Diagram Remark

Normal LED OFF


Operating status

0.4 Second
Over current
intervals

Phase unbalance 0.4 Second GMP 80-3S/3SR model, only


(30~50%) intervals red color LED will flicker.

O.L LED
Over current
light up

1 time for 3
Phase failure (3CT)

R
seconds
GMP 80-3S/3SR model,
Tripped status

2 time for 3
S O.L LED will light up and
seconds
also FAULT LED will flicker.
2 time for 3
T
seconds

Red LED light up for 0.9 sec


Phase failure (2CT)
LED goes off for 0.1 sec

Red & Green color LED GMP 80-3S/3SR model,


Reverse phase (3CT)
flicker alternately Red/Green LED will flicker.
Note) There are two red color LEDs for O.L (Overload) & Fault in the model of GMP80-3S/SR

G-24
Setting method
GMP Series Definite time

Test/Reset button
Tunnel type mounting
O.L LED

1. Check the Test/Reset button operation


1) Check if the wiring is correct (Refer to the wiring diagram) D-Time knob O-Time knob

2) Set the 'D-Time' and 'O-Time'' knob to the min. ratings


3) When the 'Test' button is pressed under tripped condition,
the 'O.L' LED is turned off RC(A) knob

Note) In operation, even though you press the 'Test/Reset' button, the EMPR do not trip

2. Set the operating time


● D-time (Delay time): 0.2~30 sec
Time(sec)
The motor starting current, which flows when the motor is starting, is
generally 600% of the rated current. It is the time during which the
EMPR do not operated by over-current during the starting time
1) Set the delay time by use of the 'D-time' knob
2) In case you do not know the delay time, start the motor by setting the 'D-
time' knob to the max. position and after checking the time during which the
staring current become stable, set the D-time (In general , the setting time is
3~5 seconds)
G

EMPR/DMPR
● The operating time is the time during which the EMPR tripped by the Current (%)
over-current. The EMPR is tripped after the selected operation time
1) Set the operation time by the 'O-time' knob Definite time characteristics curve
2) If you set the 'O-time' to the min value, the EMPR is tripped at once
Note) Generally set it to 4~6 seconds

3. Set the operating current


1) Start the motor by setting the 'RC' knob to the maximum position
2) Under operating condition, rotate the 'RC' knob to the
counterclockwise until the 'O.L' LED turned on & off. The current at
this point is the value (100%) under real load condition
3) Rotate the 'RC' knob to the clock-wise until the 'O.L' LED turned off.
Ex) When the ‘O.L’ LED flickering at 20A, the setting current will
be 22A(=20x1.1) (ex: When the 'O.L' LED settings at 21A, the setting current will be 23A (=21*1.1))

4. Check the LED condition when operation Condition Red O.L LED Note
1) Over-current Operation normal Off
‐The EMPR is not tripped during the D-time under over-current but
the O.L LED turned on and off to indicate that the over-current flows Overcurrent Flicker
‐If the EMPR is tripped after D-time the O.L LED turned on
Trip over-current On The EMPR is tripped

G-25
Electronic motor protection relays
Setting method
GMP60-TD(a) Type

● Function & Setting menu


1) Automatic reset setting will work in the event of overcurrent trip
2) Func. A and b are to check the elapse time, not for setting
3) Undercurrent protection function will work at the current flow more than 0.4A
4) In case of changing the rating DIP S/W FUNC #1 should be changed accordingly
5) Function setting is allowable at TEST mode
- Turn off the power before changing a current type switch,
and then be sure to adjust the current in the menu

●Setting Menu
FUNC SEL Description Remarks
Current type selection Set the same with rated current S/W
Trip time setting -
Time delay setting -
Rated current setting -
Current ratio setting -
Phase loss enable -
Undercurrent setting For TDa model only
Automatic reset setting For TDa model only
Operation hour setting For TDa model only
Total running hour check For TDa model only
Running hour check For TDa model only
Store -
Note) 1. If operation hour set at is elapsed is displayed and the relay operates normally. (There is no additional relay output)
2. How to check and
Display How to check
Press SEL Day displayed Press SEL Hour, Min displayed
Press SEL Operation hour displayed Press SEL Day displayed
Press SEL Min displayed
3. When power is OFF the data in unit of minute is deleted at
4. Operation hour at is the total running hour before the motor is oFF and displayed in Day, Hour and Min.
When motor is OFF the data is deleted.

●Fault status configuration

Protection FND Description Remarks


Over current O-L More than set current : Within the set time

Undercurrent U-C Lower than the undercurrent set ratio : Within 3S GMP60TDa

PF - r Over 70% of the rate of unbalance : Within 3S R Phase Loss


Phase Loss
PF - t Over 70% of the rate of unbalance : Within 3S T Phase Loss

LOCK Loc More than lock set current ratio : Within 1S


Approaching
OrH When Running time approaches at setting time GMP60TDa
Running Time
Note) When the ‘FUN’ Key and ‘SEL’ Key are pushed simultaneously, a last trip cause appears on the disply window.

G-26
Setting method
GMP60-3TZ(R) / 3TN(R) Type

● Trip curve: definite time characteristics


● Protective function: overcurrent, locked rotor, phase loss, phaseun ② ③ ④
balance, ground fault (and phase reverse)
1) Overcurrent: trip within 3 sec. after D-time at 105% or more
2) Locked rotor: trip within 1 sec. after D-time at 300% or more
① ⑧
3) Phase loss: trip within 3 sec. (phases unbalance rate over 70%)
4) Phase unbalance: trip within 5 sec. (phases unbalance rate over 50%)
5) Ground fault: trip within 0.5 sec. after D-time at over 110% or under
90% of set value
6) phase reverse: trip within 1 sec. when any two phases out of three
⑤ ⑥ ⑦
● Overcurrent trip time
Note) 1.Make power off before changing the rated current with S/W ①
1) Time delay(D-time) setting: between 0.2-60 sec. 2.The setting range of RC (A) KNOB ⑥ is recognized as 0.5 ~ 6A or 5 ~
2) Trip time(O-time) setting: fixed at 3 sec. 60According to the setting value of S/W ①. The value of the scale for
RC (A) KNOB ⑥ is 0.5, 1, 2, 3, 4, 5, 6 or 5, 10, 20, 30, 40, 50,
60(A)from the left.
● Last fault cause data stored 3.Last fault cause function indicates the LED status for the last TRIP.
- to display it press TEST/RESET button 2 times within 0.5 sec.
- PWR LED flicking in case of no fault
Note) In case of load less than minimum rating of EMPR make the number of penetrating through CT more than 2 times.
If not, error may happen to phase loss .
G
● Status of LED configuration

EMPR/DMPR
NO Function Setting Description Remark

① 6A/60A Slide switch Maximum rated current (6A/60A) setting -

② PWR. Red LED Lights up when power is ON Blinking in the failure mode

Overcurrent / unbalance in progress:

Overcurrent TRIP:

Phase loss (unbalance) TRIP


Red LED
③ FAULT Red / Green LED ∙R-phase: Green LED

∙S-phase:

∙T-phase:

Reverse phase:

④ GF Red LED Lights up after blinking in the event of ground fault -

⑤ D-TIME (S) KNOB Delay time (0.2 to 60 sec.) -

⑥ RC (A) KNOB Rated current setting: 0.5~6A/5~60A -

Sensitivity current setting (0.1~2.5A) Zero phase current detection type


⑦ GR (A) KNOB
Sensitivity current setting (0.5~6A) Residual current detection type

TRIP / RESET alternately perform Pressing 2 times within 0.5 sec.

⑧ TEST/RESET BUTTON 1. Check relay contacts - displays fault cause the final failure

2. RESET cause is displayed

G-27
Electronic motor protection relays
Setting method
DMP Series

1. Check the operation of the Test/Reset button Digital display


1) Check the wiring method R phase Bar graph
2) Press the Test/Reset button and then test is displayed on S phase
the LED and the DMPR is tripped Display button
T phase
3) Press the Test/Reset button again and then it is reset
Test/Reset button
Note) The Test/Reset is not available when a motor is rotating.
FUNC button Sel button

Current knob
Time knob

2. Shift the mode by pressing the FUNC key and then select the values by the Sel key
1) First shift to the test mode by press the ”
Test/Reset”button and then set the functions by press the ”
FUNC”button
2) Each time you press the” FUNC”button, the function mode switches from 1.CHA mode to Sto mode.
When the mode that you want to change is displayed, push the ” Sel”button to select the value you want.
After you select the value, press the ”
FUNC”button to finish the settings and it displays the next mode
3) If no button is pressed in the selection mode, it remains in that mode
Alarm signal (Alert function)
4) If you select the inverse time characteristics it skips the mode 2
5.ALt AL(07-08) contact operation
(Definite O-time) and go to the mode 3 (Reverse phase)
5) Alt is the alert setting mode. It displays the load rate of the current 1
On
setting value by the bar LED (60~110%) 0
- If the current is higher than the setting value, the bar LED is switched
on and off and the AL relay (07-08) 1
make close and open in 1sec interval unit the EMPR is tripped (Pre- 0
alarm function)
Off
- If the 5. Alt mode is set to off, the AL relay make close after the EMPR Normal Alarm Trip
is tripped (Normal open contact) Alert setting Trip setting
value value
6) To finish the settings you have to press the ”
Sel”button in the Sto
mode

Setting Menu
FUNC Sel Functions Note
Inverse or definite time characteristics Default is inverse time characteristics
Set the O-time (Definite time only) For D-time setting, use the time knob
Reverse phases protection Default is“Off”
Under current protection Default is“Off”Note1)
Alarm function (With pre-alarm function) Default is“Off”
Ground fault and Setting the operating time Default is “Off”(Z type)
Stall function Default is“Off”
Lock function Default is“Off”
CT ratio Default is 1:1 Note2) (DMP06 Modle)
Phase failure Default is“On”to store
Setting delay of Ground Fault Available for SZa/TZa
Operating time setting (Month)
Operating time setting (Hour)
DMP�-Sa/Ta/SZa/TZa model
Displaying total operating time (Month, Hour)
Displaying operating time (Month, Hour)
Store Push the SEL button to store
Note) 1. Set the under current value from above 350mA
2. Do not change the CT ratio in 36, 60 type

G-28
Setting method
DMP Series

3. Adjust the operating time by the time knob


● Inverse time characteristics
1) Select the inverse time in the 1. CHA mode, the default operating time is 600% of the setting
current
2) The setting range of the operating time is 0~60sec. Set the time by considering the motor
start time
3) When it is over the setting time, the EMPR operate in accord with the hot characteristics curve

● Definite time characteristics


1) Select the definite in the 1. CHA mode, it is operated by the definite time characteristics
2) D-time means the time that delays the operating time when the motor is starting
3) The setting range of the operating time is 0~60sec. Set the time by considering the motor
start time
4) Set the O-time at the setting mode 2. dEF and the range is 0~30sec

4. Adjust the operating current by the current knob


1) Set the operating current based on the rated current that is described in the name plate.
Generally set the 110~115% of the real load current in the normal load condition
2) There are 3 types according to the current range (6 / 36 / 60). When you use the external CT G
you can see the real current by setting the CT ratio
3) You can easily set the current value by refer to the load rate which is displayed on the bar-

EMPR/DMPR
graph (Approx. 90% load rate)
R phase current

5. Check the setting state by the display key


Set the O-time S phase current
1) In normal condition it display the maximum current among the three phase current
to 10sec
(Display only in 2) Each time you press the“Display”button you can see the current and values
definite time) Normal condition
3) If no button is pressed for 3~4 seconds. It returned to the normal condition
Set the D-time T phase current
to 10sec
(Set the motor
6. Check the causes of the fault by look at the display unit
starting time)
The causes of the fault is switched on and off for 0.5sec interval. If you press the“Display”
5A setting
button at this time, you can see the values and the causes of the fault

ex) R
S
Turn on R R

S S

T T T

Overload Under current Reverse phase


R R
Turn
R R S S
on & off
S S T T
T T
Phase fail Ground fault
R R

S S

T T

R R Stall Short circuit


S S R
T T
S

R Lock
S
T

Zero current sensitivity setting


Sensitivity DIP S/W
(mA) 1 2 3 4
100 � � � �
200 1 � � �
500 � 1 � �
1000 � � 1 �
1500 � � � 1
2000 � � 1 1
2500 1 1 1 1
Note) 1. Please use ZCT for LS EMPR.

G-29
Electronic motor protection relays
Operation and Setting
IMP Series

1. Test/Reset
1) Check wires.
2) Press the Test/Reset key once. Then“TEST”is displayed and the EMPR is tripped.
3) Press again the Test/Reset key to reset the EMPR.
Note) While the motor is running, the Test/Reset key does not work.

2. Setting
1) Press the Test/Reset key once. Then“TEST”is displayed and the EMPR is tripped.
2) Press the Enter key. Then“P-99”is displayed. Use the Up/Down keys to change the password.
3) Press the Enter key to enter A-gr setup mode.
Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
4) In the A-Grp mode, Press the Enter key. Then“1.CHA”is displayed.
Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
Press the Test/Reset key to move back to the previous mode.
5) Use the Up/Down keys to set up the value and Press the Enter key to save it.
Note) When the power is supplied first or is resupplied after a power failure, must set up the date in b-gr, 5.S-d.
Set up the rated current S/W while the power is off.

3. Quick Setup
1) Press the“Up and Enter”keys at the same time.“UPLD”is displayed and settings are uploaded
to the display.
2) Insert the display to the body without settings, and then press the Test key to enter the test mode.
3) Press the“Down and Enter”keys at the same time.“TEST”is displayed and downloading is
completed.
4) Press the Test key to return to the normal mode.
Note) Communication settings cannot be uploaded or downloaded.

4. Setting Checkup
1) Press the Enter key.
2) Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
3) Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
4) Press the Enter key again to check settings.

5. Failure Event Checkup


1) Press the Up and Down keys at the same time to display“1.O-C”(recent failure events).
Note) When no failure events are stored,“1.non3”is displayed.

2) Use the Up/Down keys to select an event and press the Enter key to go to the selected event.
3) The R-phased failure current is displayed. Every time the Down key is pressed, S-phased failure
current, Tphased failure current, overload rate and date are displayed one after the other.
4) Press the Test/Reset key to move back to the previous mode.
5) Press the Up and Down keys at the same time to get out of the failure event checkup mode.

6. Forced Thermal Reset


When the system is tripped while it is in the thermal inverse time mode, if you want to turn the
EMPR into the cold mode by resetting the motor’ s heat amount, Press the Enter and Test/Rest
keys at the same time.
* When a trip occurs due to the thermal excess current, if the motor is started right after it is reset, as the motor is
hot, it is highly likely that the motor is tripped again.

G-30
Operation and Setting
IMP Series

Setting Menu (A Group)


Group Menu Setting Value Description Default Value

A Operation Characteristics
1.CHA dEF/th/n-th n-th (Inverse)
(Definite/Thermal Inverse/Inverse)

2.O-t 1~60s Operation Time (sec) 60

3.d-t 1~200s Delay Time (sec) 200

4.r-C 0.5~10A/5~100A Rated Current (10/100A) 10/100A

5.Ctr 0.25, 0.5, 1~200 CT Ratio (4 times, twice, once) 1 Note)

6.Loc OFF, 200~800% Lock Protection (sec) OFF

7.StL OFF, 150~500% Stall Protection (sec) OFF

8.P-F OFF/On Open Phase OFF

9.P-U OFF, 10~70% Unbalance Protection (%) OFF

10.rP OFF/On Reverse Phase OFF


G
11.UC OFF, 30~90% Under Current Protection (%) OFF

EMPR/DMPR
Ground Fault Operation Current
12.gF 0FF, 0.03, 0.05/0.1~3A OFF
(Zero sequence CT)

Ground Fault Operation Current


13.gn OFF, 20~500% (FLCmin) OFF
(Residual circuit)

14.gt 0.05, 0.1~1.0s Ground Fault Operation Time -

15.gd On/OFF Ground Fault Delay During Start ON

16.IC OFF, 500~1000% Instantaneous Protection (%) OFF

17.Io ALt/TriP Instantaneous Warning/Operation TriP

Note) 1. When the rated current S/W is 100A, the CT ratio is not displayed.
2. Some menus are not displayed if relevant functions are not available.

Setting Menu (B Group)


Group Menu Setting Value Description Default Value

B 1.E-r On/OFF Electric Reset On

2.A-r OFF, 1~20 min Automatic Reset OFF

3.r-t Hour/Minute Run Time Time Check

4.Srt OFF, 1~8760Hour Run Time Setup (Hour) -

5.s-d 2009/01.01/00:00 YY/MM/DD/ HH:MM (View/Setup) -

6.Trt Day/hour:minute Total Run Time Time Check

A.t-d 0.5~10/5~100A Analog output A420 Model

A.Adr 1~247 Communication Address

b.bps 96/192/384 Communication Speed M485 Model

c.S-P On/OFF SWAP

Note) 1. When the power is supplied first or is resupplied after a power failure, must set up the date (5.S-d).
2. Automatic reset is only possible in case of an excess current trip.

G-31
Electronic motor protection relays
Operation and Setting
IMP Series

Reverse Phase Current Unbalance Rate Current Unit

R Phase
S Phase

T Phase
Ground Fault Current

Load Rate Unit Load Rate Display


Communication Status

Note) kW, kVar, and V indicate the specification of the voltage models (under development).

Operation Display
Display Description Remark
Over Current Trip Operate within predefined time.
Under Current Trip Operate within 3 seconds.
Open Phase Trip Operate within 1.5 seconds when the unbalance rate is over 70%.
Unbalance Trip Operate within 3 seconds.
Lock Trip Operate within 0.5 seconds.
Stall Trip Operate within 3 seconds.
Reverse Phase Trip Operate within 0.1 second.
Ground Fault Trip Operate within predefined time.
Instantaneous Trip Operate within 0.05 seconds.
Elapsed Time (No Trip) The operation time is reset when the Reset key is pressed.
Communication Fault between Body and Display (Press the ENTER/RESET key to return to the normal mode)

IMP Specifications for Low Voltage 3-Phase Induction Motors (Reference)


Full Load Current IMP Settings Motor Output (Less than kW)
External CT
for the Motor Current Selection S/W Wire Tunnel CT ratio 220V 380V 440V
0.7A or less 4 times 0.25 - 0.1 0.18 0.2
0.7~1.6A 0.5~10A Twice 0.5 - 0.25 0.55 0.6
1.6~8A Once 1 - 1.5 3 3.7
7~100A 5~100A Once 1 - 25 45 55
90~120A Once 30 SCT-150 30 55 55
120A~160A Once 40 SCT-200 45 75 90
160~240A Once 60 SCT-300 55 110 132
240~320A 0.5~10A Once 80 SCT-400 90 160 160
320~400A Once 100 500 : 5 110 200 200
400~480A Once 120 600 : 5 132 250 250
480~640A Once 160 800 : 5 160 320 320
Note) 1. This table is written based on the full load current.
2. The CT is selected as a reference for the EMPR’s current setting range.

Analog (DC 4~20mA) Output / Communication 20mA


20mA
16.8mA
1) The biggest current out of measured 3-phase currents is converted into DC 4mA~20mA 16mA
13.6mA
and the current measured remotely by digital meter can be displayed. 12mA

2) When there is no current, 4mA is sent. If the current goes beyond the predefined value, 8mA

20mA is sent. 4mA


16mA
�Output Current = × Load Current + 4mA (Settings are changed in A.t-d of b-gr) 0A 0.1A 0.2A 0.3A 0.4A 0.5A(0.5A~10A)
Setting 0A 1A 2A 3A 4A 5A(5A~100A)

< Analogue output when the output is set to be 0.5A (5A) >
3) When the system is the 0.5A~10A setting mode, measurement starts from 0.3A. When
the system is the 5A~100A setting mode, measurement starts from 3A. Thus, when the
20mA
20mA
current is under 0.3A (3A), 0A is measured and output is 4mA. (To measure the load 16.8mA
16mA
current correctly, an appropriate CT should be used). 13.6mA
Note) The allowable burden is less than 500Ϊ . 12mA
10.4mA
Considering the receiver resistance (usually 250Ϊ ) and track resistance), the shielding cable should be used. 8mA
7.2mA

4mA
Communication Spec. :
Refer to G-41 page and LSIS Homepage (www.lsis.biz) 0A
0A
1A
10A
2A
20A
3A
30A
4A
40A
5A(0.5A~10A)
50A(5A~100A)

< Analogue output when the output is set to be 5A (50A) >

G-32
Dimensions
GMP Series

GMP22-2P (1c) Sol


GMP22-2PD (1c) Sol

Screw

Screw

0.15kg

GMP22-2P (1a1b) Sol


GMP22-3P Sol
GMP22-2PA (1a1b) Sol
GMP22-3PR Sol G
Screw

EMPR/DMPR
Screw

0.18kg

GMP40-2P Sol
GMP40-2PD Sol
GMP40-2PA Sol
GMP40-3P Sol
Screw
GMP40-3PR Sol

Screw

0.20kg/0.22kg

GMP80-2S
GMP80-3S
Screw
GMP80-3SR

Mounting hole

Screw

0.42kg/0.46kg

G-33
Electronic motor protection relays
Dimensions
GMP Series

GMP22-2S
GMP22-3S
GMP22-3SR
GMP40-2S
GMP40-3S
GMP40-3SR Screw

Screw

0.19kg/0.21kg

GMP22-2T
GMP22-3T
GMP22-3TR
Screw
GMP40-2T
GMP40-3T
GMP40-3TR

0.14kg/0.16kg

GMP60T
GMP60TE
GMP60TA

Screw

Screw

0.14kg

G-34
Dimensions
DMP Series

GMP60-TD
26.8 62.25 7.2 8.2
GMP60-TDa

.5
R2
.5

12.5
R2
74

74

75
61
10
22±0.5

55.4 55.4 47

5.8
72.8

0.25kg

GMP60-3TZ, TZR Tunnel type Screw type - Terminal lug sticking


GMP60-3TN, TNR
GMP60-3T, TR

EMPR/DMPR
Terminal arrangement

GMP22-2P (1c) GMP22-2P (1a1b) GMP22-2/3S


GMP22-2PD (1c) GMP22-3P GMP40-3/3S
GMP22-2PA (1c) GMP40-2P/3P GMP80-2/3S

Note)

GMP22-2/3T GMP60-T/TE/TA GMP60-TD GMP60-3TZ, TZR


GMP40-2/3T GMP60-TDa GMP60-3TN, TNR
GMP60-3T/3TR
Note) 1. Only for the GMP60-TZR modle.
2. Aux. Contacts are operate when power applied.

G-35
Electronic motor protection relays
Dimensions
DMP Series

DMP�-S
DMP�-SZ
※Aux. contact wire size
: below 8[mm2]
Mounting dimensions
※Torque : 0.5N
DMP�-Sa
DMP�-SZa

0.7kg

DMP�-S
DMP�-SZ Mounting dimensions
DMP�-Sa
DMP�-SZa

0.64kg
Panel mounting

Panel cutting size

Note) 1. In extension type, the digital EMPR is calibrated with combining the display unit and mainbody
so, please cautious not to combine the display unit and mainbody with different part No.
2. The 07-08 contacts are the ZCT input terminal (Digital EMPR with ground fault function)
G-36
Dimensions
DMP Series

DMP�-T
DMP�-TZ
※Wire size to penetrate a CT
:below 22[mm2]
Mounting dimensions
DMP�-Ta
DMP�-TZa

EMPR/DMPR
0.56kg

DMP�-T
DMP�-TZ Mounting dimensions
DMP�-Ta
DMP�-TZa

0.5kg
Panel mounting

Panel cutting size

Note) 1. In extension type, the digital EMPR is calibrated with combining the display unit and mainbody
so, please cautious not to combine the display unit and mainbody with different part No.
2. The 07-08 contacts are the ZCT input terminal (Digital EMPR with ground fault function)
G-37
Electronic motor protection relays
Dimensions
IMP Series

One-Body Type

68
90 64

7.3 82

135.5
109.3

4.2

25
U/2/T1 V/4/T2 W/6/T3

∅17
21
5

53.5

Separate BOdy Type

68
90 64
12

82
121.3
109.3

4.2

25

U/2/T1 V/4/T2 W/6/T3

∅17
21
5

53.5

Panel mounting
26 44
17 56 17
22

64
20

M4
22

90

Note) The cable should be purchased separately (1m/1.5m/2m/3m).

G-38
Wiring method
GMP Series

GMP22-2P (1c)
GMP60T (1c)

GMP�-� (1a1b)
G

EMPR/DMPR
With the External CT

GMP60-3TZ, TZR
GMP60-3TN, TNR
GMP60-3T, 3TR

주)

Note) 1. The Z1, Z2 are the ZCT input terminal (GPM60-3TZ/TZ type)
2. Aux. contacts are operate when power applied.

G-39
Electronic motor protection relays
Wiring method
DMP Series

DMP-S/Sa
DMP-T/Ta

With the External CT

Single phase

Note) When the single-phase motor is used, reverse phases protection should be set off.

DMP-SZ/SZa
DMP-TZ/TZa

DMP-SZ/SZa
DMP-TZ/TZa

주1)

With the External CT

G-40
Wiring method
IMP Series

OFF OL
(RESET) TRIP
MCCB
Y AUX

MC
SHT MCCB
RS485 VR VS VT TRX(+) TRX(-) 05 06
MC (4~20mA) 10A

VR VS VT TRX(+) TRX(-) 05 06 100A

A1(+) A2(-) 95 96 97 98 07 08 Z1 ZCT Z2


10A

100A A1 A2 95 97 07 TRX (+, -)


A1(+) A2(-) 95 96 97 98 07 08 Z1 ZCT Z2

EMPR OL SR

96 98 08 Z1 Z2

ZCT Note 1) With the External CT


G

EMPR/DMPR
Note) 1. When the zero-phase-sequence current transformer is used to detect ground faults, connect the ZCT.
2. When the single-phase motor is used, all phases are connected except the S phase, and open-phase, unbalance and ground fault should be set OFF.

Terminal layout Communication specification

- Operation mode: Differential


- Distance: Max. 1.2km
VR VS VT TRX(+) TRX(-) 05 06 - General RS-485 shielded twist 2-pair cable
10A - Baud rate: 9600/19200/38400bps
- Transmission method: half-Duplex
100A
- Max. In/Output voltage: -7V~+12V
A1(+) A2(-) 95 96 97 98 07 08 Z1 ZCT Z2

Terminal Configuration
Engrave Description Remark
A1(+), A2(-) Input terminal for operation power AC/DC85~245V
95-96 When the power is ON (NC contact output) In case of an instantaneous trip, if 17.lo is ALT, it is NC, and if 17.lo is Trip, it is NO.
97-98 When the power is ON (NC contact output) In case of an instantaneous trip, regardless of 17 .1o setup, it is NC.
07-08 Converted to the NC mode only when an instantaneous trip occurs.
Z1, Z2 Output terminal for the zero-phase sequence current transformer Specific ZCT (for the EMPR)
TRX(+) RS485 terminal (TRX+) Or 4~20mA (+) output
M485, A420 Type
TRX(-) RS485 terminal (TRX-) Or 4~20mA (-) output
10A/100A Max. rated current change S/W 10A : 0.5~10A, 100A : 5~100A
VR/VS/VT 3-phase voltage input terminal
N/A
05-06 Output terminal for voltage protection
Note) 1. The 3-phase voltage input terminal and 05-06 output terminal should be connected only for voltage protection models, which will be released in the future.
2. For RS485 connection, the terminal resistance should be 120Ϊ .
3. For 4~20mA current, the maximum burden should be less than 500Ϊ .

G-41
Electronic motor protection relays
Accessories
CT, ZCT, Cable and Terminal

● CT (Current Transformer)
Ratings
Type 2CT
DCT (Current Transformer) DCT-100 100 : 5A
DCT-150 150 : 5A
CT ratio DCT-200 200 : 5A
DCT-300 300 : 5A
DCT-400 400 : 5A
Class 1.0
2CT Burden 5VA
Insulation voltage 600VAC

Dimension Insulated impulse voltage 2kV


Insulation resistance 10㏁(DC 500V Megger)
Mounting Panel
● 외형치수 Note) Please use DCT for LS Electronic Motor Protection Relay only.
65

33.5

With GMP60T
28.5
55 60
120 80
69.6

2-
5

Ratings
Type 3CT
SCT(Current Transformer) SCT-100 100 : 5A
SCT-150 150 : 5A
CT ratio SCT-200 200 : 5A
SCT-300 300 : 5A
SCT-400 400 : 5A
Class 1.0
Burden 5VA
1CT 3CT (1CT×3)
Insulation voltage 600VAC
Insulated impulse voltage 2kV
Dimension Insulation resistance 10㏁(DC 500V Megger)
Mounting Panel
Note) Please use SCT for LS Electronic Motor Protection Relay only.
65

65

With GMP60-3T/DMP/IMP
64 82

82 82 82
64
53

5

27.5
65
32.5

82 82
256

G-42
Accessories
CT, ZCT, Cable and Terminal

● ZCT (Zero Sequence CT)


Ratings
Type Diameter (A) Ratio Weight (kg) Model
ZCT, D30 30 0.5 LZT-030
ZCT, D50 50 100mA/40~55mV 0.7 LZT-050
ZCT, D65 65 200mA/100mV 0.9 LZT-065
ZCT, D80 80 1.5 LZT-080

Dimension

ZCT 30 ZCT 50, 65, 80

EMPR/DMPR
Unit (mm) Unit (mm)

Model A B C D E F G H I ∅ Model A B C D E F G H I ∅
LZT-030 30 25 108 100 114 7 32 32 110 6 LZT-050 50 25 131 100 122 7 32 36 114 6
LZT-065 65 26 143 114 133 7 39 37 126 6
LZT-080 80 34 174 160 180 7 40 40 151 6

● Other Options
Cable Terminal Block

Applicable Type DMP, IMP Series Applicable Type DMP Series, GMP60-3T, 3TZ, 3TN
Spec. 1m, 1.5m, 2m, 3m, 4m Spec. 60A blelow
* Panel mount: Extension cable

G-43
Electronic motor protection relays
Direct mounting EMPR new/old comparative table

GMP22-2P (1c) GMP22-2P GMP22-3P GMP40-2P GMP40-3P


Type GMP22-2PD (1c) GMP22-2PA GMP22-3PR GMP40-2PD GMP40-3PR
GMP40-2PA
Number of sensors 2 2 3 2 3
Over current
Phase failure
Protective
Locked rotor
function
Phase unbalance
Reverse phase (PR) (PR)
Aux. contact (at Energization) 1SPDT (1c) 2SPST (1a1b) 2SPST (1a1b)
Rating Current 0.3~1.5, 1~5, 4.4~22A 0.3~1.5, 1~5, 4.4~22A 4~20, 8~40A

Metasol EMPR
(New) Demension

Type of contactors MC-9b, 12b, 18b, 22b MC-9b, 12b, 18b, 22b MC-32a, 40a

Meta-MEC EMPR
(Old) Demension

Type of contactors GMC-9, 12, 18, 22 GMC-9, 12, 18, 22 GMC-32, 40


Wiring/Mounting Compatibity Note) NO NO NO
GMP60T (1c) GMP22-2T GMP22-3T GMP40-2T GMP40-3T
Retrofit Type (Tunnel) GMP22-2T GMP60TA (1c) GMP22-3TR GMP60T (1c) GMP40-3TR
GMP60TA (1c)
Note) If you want to use Metasol EMPR with GMC Contactors, only tunnel type EMPR is avaliable.