Electronic Motor Protection Relays - G - EMPR-DMPR
Electronic Motor Protection Relays - G - EMPR-DMPR
GMP Series
DMP Series
IMP Series
G
Features G-6
Ordering G-9
Specification G-10
Characteristics G-14
Contents
Dimensions G-33
Accessories G-42
As a digital motor protection relay with MCU Especially, EMPR is EMC tested and approved
EMPR is highly reliable by realization of to operate safely without any malfunction
real-time data processing and, retention caused by electromagnetic wave and surge.
confidentiality and also can secure motor Most of the models have received CE Mark
safely with various functions such as phase and UL certification.
loss, phase reverse, unbalanced, stall, lock,
ground fault, short circuit protection
depending on the model .
General Motor Protection Relay
GMP Series
�Various connection & mount
�Inverse or definite time mode
�Ground fault type
�Display the causes of the falut by LED
EMPR/DMPR
Intelligent Motor Protection Relay
IMP Series
�Wide current setting range (0.125~100A)
�Communication support type
�Zero current and residual current sensing
�Save the fault events and operating time setup
�Select the Inverse, thermal inverse or definite time modes
�Unit or Extension in one body by option cable
Electronic motor protection relays
Features
GMP Series
Test /
Current Reset button
setting
G-6
Features
DMP Series
Digital display
R phase Bar graph
S phase
Test/Reset button
G
● Convenient structure
EMPR/DMPR
- Install the Unit / Extension type in one body
The display part may be separated from the body
You can check the values and the causes of the
fault without opening the distribution panel door
- removable terminal block
G-7
Electronic motor protection relays
Features
IMP Series
The EMPR IMP series are optimal solutions for protecting and monitoring motors in
complex industrial fields and provide high safety and productivity.
~100A Wide Current Setting Range: Total Digital Motor Protection Relay with
0.125~100A for One Model the MCU (Microprocessor Control Unit)
MCU
With the slide S/W, the current setting range Real-time processing and high precision
can be decided 0.5~10A or 5~100A. According
to the CT penetration number, even 0.125A
One-Body Type and Separate Body Type
current can be protected. (Wire penetration
The display can be attached to the panel front
hole).
so that current, operation time and settings can
be checked without fetching the unit. With the
Communication support type display separated, the motor can be protected.
RS-485 MODBUS communication with various
systems.The model with analogue signals
Applicable to Inverter Circuits
(4~20mA) is compatible with transducer
Thanks to its good high harmonic noise
systems. INV
characteristics, it can be applied to the of
inverter control circuits. The available
Thermal Inverse Time, frequency range is 20~200Hz. When the
Inverse Time and Definite Time Modes relative harmonic factor is over 30%, a
According to user’s needs, the motor can be harmonic filter should be installed (However,
protected in the inverse time mode or definite the ground fault function should be off).
time mode.
G-8
Ordering
GMP Series
Frame Nominal Current Type CT Type Reverse Phase Nominal Current Current Setup Range (A) Operation Current Aux. contactor Model Type
1.5A 2 2CT Reverse Protection 1.5A 0.3~1.5 110/220 AC 100~260V 1c Terminal
Direct - (Screw)
22 5A Coupling, 3 3CT No Protection 5A 1~5 24 AC 24V 1a1b - Penetration
22A Terminal Reverse Protection 22A 4.4~22 48 AC 48V Note) When the (Tunnel)
Connection, Type R power is
20A Protection Available 20A 4~20 110 AC 110V
Penetration applied, the Metasol
40 P Direct Coupling(Pin)
40A Automatic 40A 8~40 220 AC 220V system is in Direct
A the contacting Sol Coupling
80 80A Terminal Connection Terminal Recovery 80A 16~80 380 AC 380 (440)V
S status. (Pin)
06A Connection(Screw) 06A 0.5~6 Note) AC 24V, AC48V and
Penetration AC380 (440)V are for
60 30A Penetration 30A 3~30
T GMP60T.
60A (Tunnel) 60A 0.5~60 Note)
TE Economic Note) For GMP60-TD, GMP60-TDa 6/60A,
GMP60-3TZ (R), 3TN (R), 3T (R)
PD
Direct Coupling
(Definite Time)
G
Current Display
TD
EMPR/DMPR
(Definite Time)
Ground Fault Protection Classification
TZ (Zero-Phase- Sequence
Current Detection) - Existing Model
Ground Fault Protection Operation Time
TN (Residual Current a
Detection) Function
DMP Series
Current Control Range Wiring OPTION Classification Control Voltage Aux. contactor
06 0.5~6A Terminal - Standard Model - Existing Model 220 AC 220V 1a1b
S
36 3~36A (Screw) Ground Fault 110 AC 110V 2a
a Operation Time
Z
60 5~60A Penetration Protection Function 2b
T
(Tunnel) Short circuit 2a1b
I
Protection
Note) 1. Even the same model has different contact specifications.
2. When the power is applied, the system is in the contacting status.
IMP Series
IMP C A420
G-9
Electronic motor protection relays
Specification
GMP Series
Ratings
G-10
Specification
GMP Series
Ratings
EMPR/DMPR
Reverse phase
Current setting range(A) 4~20, 8~40 16~80
Operating time characteristics Inverse time characteristics
Time setting Inverse time 0~30 sec
(sec) Definite D-time 0.2~60 sec (GMP40-2PD)
O-time 5sec (Fixed) (GMP40-2PD)
Reset time Manual reset (Auto Reset type : GMP□-A)
Tolerance Current ±5%
Time ±5% (or±0.5 sec)
Control power Voltage AC 100~260V, 50/60Hz
Aux. contact Contact Note2) 2SPST (1a1b)
Ratings 3A/250VAC Resistive load
Operate (95 96 Close) (97 98 Open)
Insulation resistance Min 100㏁ at 500Vdc
Surge endurance (IEC 61000-4-5) 5kV Apply the standard wave
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -30~80℃
Relative humidity 30~90%RH (No freezing)
Trip indicator Red LED Red/Green LED Red LED Red/Green LED Red LED Red/Green LED Red LED 2Red LEDs
Dimension(mm) ×H×
W× ×D 53×78×87.5 53×68×87.5 53×38×87.5 89×77.5×97.4
Mounting type Direct mount onto a
Separate mount (Screw or Din-rail)
Metasol MC (MC-32a, 40a)
Certification UL, cUL, CE
G-11
Electronic motor protection relays
Specification
GMP Series
Ratings
GMP60TE GMP60-3TZ(R)
Model GMP60T GMP60-TD GMP60-TDa GMP60-3T(R)
GMP60TA GMP60-3TN(R)
Type Tunnel type Tunnel type Tunnel type Tunnel type
No. of CT 2CT 2CT 3CT 3CT
Protection Overcurrent ● ● ● ●
Phase failure ● ● ● ●
Lock/Stall ● ● ● ●
Phase unbalance — — ● ●
Reverse phase — — ●(R Type) ●(R Type)
Note1)
Ground fault — — — ●
Current setting range (A) 0.5~6, 3~30, 5~60 0.5~60 0.5~60 0.5~60
Operating time characteristics Definite Definite Definite Definite
Time setting D time 0.2~30 sec 1~60 sec 0.2~60 sec 0.2~60 sec
(sec) O time 0.2~30 sec 5 sec (Fixed) 0.5~30 sec 0.2~15 sec 3 sec (Fixed)
A time (Reset) — 0.2~120 Note4) — 1~20 min — —
Tolerance Current ±5% Time ±5% (or±5 sec)
Control power Voltage Note3) AC 110V/220 (±10%) Note3) AC 110V or 220V AC 100V~260V
Frequency 50/60Hz
Aux. contact Contact Note2) 1SPDT (1c) 2SPST (1a1b)
Ratings 1A/250VAC Resistive load 3A/250VAC Resistive load
Insulation resistance Min 100㏁ at 500Vdc
Surge endurance (IEC 61000-4-5) 5kV Apply the standard wave
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -30~80℃
Relative humidity 30~90% RH (No freezing)
Trip indicator Red LED 7 Segment Red/Green×2-Color LED Red/Green×2-Color LED, Red LED
Dimension(mm) ×H×
W× ×D 72×67×69 75×72.8×47 94.6×95×97 94.6×95×97
Mounting type Separate mount (Screw or Din-rail)
Certification UL, cUL, CE
Note) 1. 3TZ(R): Zero sequence CT type, 3TN(R): Residual curcuit
2. When power applied the Aux. contact operate
3. GMP60T/TE: AC24V, 48V or 380V, 50/60Hz types a option
4. GMP60TA: Auto Reset type
G-12
Specification
DMP/IMP Series
Ratings
Model �-S/SZ/SI
DMP� �-Sa/SZa
DMP� �-T/TZ/TI
DMP� �-Ta/TZa
DMP� IMP-C-NO IMP-C-A420 IMP-C-M485
EMPR/DMPR
Lock/Stall
Phase unbalance 5 sec 5 sec
Under current 3 sec 3 sec
Ground fault Within 0.05~1 sec. (DMP�-Z/Za Model) Within 0.05~1 sec Note2)
Short circuit Within 50ms (DMP�-I Model) Within 50ms
Alarm Variable (60~110% of the setting current) Variable (60~110% of the setting current)
Current setting range (A) 6: 0.5~6A, 36: 3~36A, 60: 5~60A 0.5~100
Time setting Definite D time 0~60 sec 1~200 sec
(sec) O time 0~30 sec 1~60 sec
Inverse time 0~60 sec 1~60 sec
A time (Reset) Manual reset Manual reset/Autometic
Tolerance Current ±5% ±5%
Time ±5% (or±0.5 sec) ±5% (or±0.5 sec)
Operating power Voltage AC 110V or 220V, 50/60Hz AC/DC 85~245V, 50/60Hz
Aux. contact 2a, 2b, 1a1b OL: 1a1b, AL: 1a
Insulation resistance Over DC 500V 100㏁ Over DC 500V 100㏁
Surge impulse voltage (IEC 61000-4-5) 5kV 5kV
Fast transient burst (IEC 61000-4-4) 2kV 2kV
Environment Operation -25~70℃ -25~70℃
Temperature Storage -30~80℃ -30~80℃
Relative humidity 30~90% RH (No freezing) 30~90% RH (No freezing)
Display 7-Segment 3 phase current, cause of a fault 3 phase current, cause of a fault
Bar-Graph 60~110% of real load current 60~110% of real load current
Mounting type 35mm Din-rail/Panel 35mm Din-rail/Panel
Certification UL, cUL, CE
Note) 1. In extension type, the digital EMPR is calibrated with combining the display past and main body so, please cautious not to combine the display part and main body with different part No.
2. Zero current sensing by zero sequencee CT and Residual circuit.
G-13
Electronic motor protection relays
Inverse time characteristics
GMP22/40 Type
Description
- Wide and adjustable current range
- Adjustable trip time (trip class 5-30)
- Designed suitable for use with contactors
Directly mountable on the Metasol contactors (Pin type)
Separate mount versions are also available
Separately mountable on 35mm DIN rail or with screws
- 1NO+1NC trip contacts
- Manual reset as standard (Automatic reset optional)
Technical information
Relay control voltage 100 to 260V AC 50/60Hz
3A/250VAC at resistive load
Auxiliary contact
1NO (97-98) + 1NC (95-96)
Current ± 5%
Setting tolerance
Time ± 5% (or ± 0.5sec)
Insulation resistance Min 100㏁ at 500V DC
Impulse withstand voltage 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
Certificate -25 to 70℃ for operation
CE, ULcUL Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH
G-14
Inverse time characteristics
GMP22/40 Type
EMPR/DMPR
Separate mount 2-sensor 0.3 - 1.5A GMP22 - 2T∙1.5
(2 CT) 1 - 5A GMP22 - 2T∙5
Connection 4.4 - 22A GMP22 - 2T∙22
without a screw 3-sensor 0.3 - 1.5A GMP22 - 3T∙1.5
- cables pass (3 CT) 1 - 5A GMP22 - 3T∙5
through CT holes 4.4 - 22A GMP22 - 3T∙22
3-sensor 0.3 - 1.5A GMP22 - 3TR∙1.5
Reverse phase 1 - 5A GMP22 - 3TR∙5
detection 4.4 - 22A GMP22 - 3TR ∙22
G-15
Electronic motor protection relays
Definite time characteristics
GMP60-T(E) Type
Description
- Small size, economical
- Delay time setting in starting and operation
- Over current, phase failure protection
- Definite time characteristics
- Wide current setting range
- Screw or Din-rail mounting
G-16
Ampere meter function
GMP60-TD(a) Type
Description
- Definte time characteristics
- Delay time setting in starting and operation
- Over current, phase failure protection
- Definite time characteristics
- Wide current setting range
- Screw or Din-rail mounting
- Display the causes of the fault and the values
EMPR/DMPR
Model GMP60-TD GMP60-TDa
Type Tunnel type
No. of CT 2
Current setting range (A) 0.5~60
Operating time characteristics Definite time characteristics
Delay time 1~60
Time setting
Operating time 0.5~30
(sec)
Reset time Manual reset 1~20min
Allowable Current ±5%
error Time ±5% (or ±0.5 sec)
Voltage AC 110/220V
Control power
Frequency 50 / 60Hz
Contact Note2) 2SPST (1a1b)
Aux. s/w Ratings 5A 250Vac, resistive load
Operation 95 96close 97 98open
Insulation resistance Min. 50㏁ at 500Vdc
Surge insurance (IEC 61000-4-5) 5kV
Fast transient burst (IEC 61000-4-4) 2kV
Environment Operation -25~70℃
Temperature Storage -50~80℃
Relative humidity 46~85 RH (No freezing)
Trip indicator 7-Segment
×H×
Dimension (mm) W× ×D 72×63×69
Mounting type Separate mount (Screw & Din-rail)
Certification UL, cUL, CE
Note) 1. Under phase failure condition over current flows. The EMPR tripped if it is over the setting over current
2. When power applied the Aux. contact operate
G-17
Electronic motor protection relays
Definite time characteristics with 3CT
GMP60-3T(R) Type
Description
- Cable connecting through CT holes (option: with screw)
- Auxiliary contact: 2SPST (1a1b at energization)
- Wide and adjustable current range (0.5~60A)
- D-time: 0.2~60 sec. / O-time: 0.2~15 sec.
- Control voltage: AC100~245V 50/60Hz
- Manual(electrical) reset as standard
- Applicable to inverter at the secondary circuit (except GMP60-3TR)
GMP60-3T
GMP60-3TR
Terminal Lug
Storing the last fault cause
Selection
Mount/Connection Optional function Setting range Catalog No.
Technical information
Mounting On 35mm rail or panel with screws
Current ± 5%
Setting tolerance
Time ± 5% (or ±0.5sec)
Frequency 50/60Hz
Auxiliary contact rating 5A/250VAC at resistive load
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
-25 to 70℃ for operation
Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH
Operating indication Red/Green 2-color LED, Red LED
Standard UL508, IEC60947-1
G-18
For ground fault current protection
GMP60-3TZ(R), 3TN(R) Type
Description
- Cable connecting through CT holes
- Auxiliary contact: 2SPST (1a1b at energization)
- Wide and adjustable current range (0.5~60A)
- Definite time characteristics
D-time: 0.2~60sec. / O-time: 3sec.
- With 3 sensors (CT)
- Control voltage: AC100~245V (50/60Hz)
GMP60-3TZ, 3TZR
GMP60-3TN, 3TNR
EMPR/DMPR
Reverse phase
Terminal Lug
Storing the last fault cause
Selection
Mount/Connection Ground fault current Optional function Setting range Catalog No.
Zero phase current
∙Separate mount (0.1~2.5A) None 0.5 - 60A GMP60-3TZ
∙Cable Connection *ZCT required
through CT holes Reverse phase 0.5 - 60A GMP60-3TZR
Residual current
(0.5~6A) None 0.5 - 60A GMP60-3TN
Technical information
Mounting On 35mm rail or panel with screws
Current ± 5%
Setting tolerance
Time ± 5% (or ±0.5sec)
Frequency 50/60Hz
Auxiliary contact rating 5A/250VAC at resistive load
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
-25 to 70℃ for operation
Ambient temperature
-30 to 80℃ for storage
Humidity 30 to 90% RH
Operating indication Red/Green 2-color LED, Red LED
Standard IEC 61000, KEMC 1120
G-19
Electronic motor protection relays
Inverse time characteristics
GMP80 Type
Description
- Wide and adjustable current range
- Adjustable trip time (trip class 5-30)
- Separately mountable on 35mm DIN rail or with screws
- 1NO+1NC trip contacts
- Manual reset as standard (Automatic reset optional: GMP80-2SA)
Selection
Mount/Connection Sensor Setting range Catalog No.
Separate mount 2-sensor 16 - 80A GMP80-2S
(2 CT)
Cable connection 3-sensor 16 - 80A GMP80-3S
with a screw (3 CT)
3-sensor 16 - 80A GMP80-3SR
Reverse phase detection
Technical information
Relay control voltage 100 to 260V AC 50/60Hz
Auxiliary contact 3A/250VAC at resistive load
1NO (97-98) + 1NC (95-96) (When power applied)
Setting tolerance Current ± 5%
Time ± 5% (or ±0.5sec)
Insulation resistance Min 100㏁ at 500V DC
Surge insurance 5kV (IEC 61000-4-5)
Fast transient burst 2kV (IEC 61000-4-4)
Certificate Ambient temperature -25 to 70℃ for operation
-30 to 80℃ for storage
CE, ULcUL
Humidity 30 to 90% RH
G-20
Characteristics DMP Series
DMP-S(a)/SZ(a)/SI Type
Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 3seconds Over 70% of the rate of unbalance
Phase unbalance Within 5seconds Over 50% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 5seconds Over 180% of the setting current
Lock Within 0.5seconds Setting 200~900% of rated current
Under current Within 3seconds Setting 30~70% of rated current
Note) Lock protection is operated after setting D-time in case of definite time type
G
Function selection
EMPR/DMPR
FUNC Sel Description
1. CHA Inv/dEF Operating characteristics setting (Inverse/definite time type)
Extention type (with cable) 2. dEF Note1)
0~30 (S) Setting the operating time (In definite type)
3. r.P oFF/on Reverse phase enable
4. Und oFF/30~70 (%) Under current enable and setting
5. Alt oFF/60~110 (%) Alerting enable and setting
6. Stl oFF/on Stall enable
7. Loc oFF/200~900 (%) Lock enable and setting
8. Ct 1~120 CT ratio setting
9. P.F on/oFF Phase fault enable
b. StA Note2)
0~120 Operating time setting by month
c. StH 10~730 Operating time setting by hour
d. tAH A000,000.0 Displaying total operating time (month, hour)
E. rAH A000,000.0 Displaying operating time (month, hour)
Sto Sto Store
Note) 1. 2.dEF is only displayed when dEF is selected in a 1.CHA mode
2. Functions for b to e are available for only Sa & SZa type.
Ratings
Model �-S/Sa
DMP� DMP� �-SZ/SZa/SI
Type Wiring method Screw
Panel mount Unit or Extension
Operating characteristics Inverse/definite type
Alerting function Variable between 60 and 110%
Current range (A) 06: 0.5~6, 36: 3~36, 60: 5~60
Setting time Definite Delay (D-T) 0~60seconds
Operating (O-T) 0~30seconds
Inverse 0~60seconds
Reset type Manual reset
Operating Voltage AC 110V or AC 220V
voltage Frequency 50/60Hz
Aux. contacts OL 2-SPST (95~98) 3A/250Vac resistive load
AL SPST (07-08) 3A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel
Certification UL, cUL, CE
G-21
Electronic motor protection relays
Characteristics DMP Series
DMP-T(a)/TZ(a)/TI Type
Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 3seconds Over 70% of the rate of unbalance
Phase unbalance Within 5seconds Over 50% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 5seconds Over 180% of the setting current
Lock Within 0.5seconds Setting 200~900% of rated current
Under current Within 3seconds Setting 30~70% of rated current
Selectable Grounded current setting by dip s/w
Ground fault Note)
0.05~1.0seconds (100~2500mA)
Note) Lock protection is operated after setting D-time in case of definite time type
Function selection
FUNC Sel Description
1. CHA Inv/dEF Operating characteristics setting (Inverse/definite time type)
2. dEF Note1)
0~30 (S) Setting the operating time (In definite type)
3. r.P oFF/on Reverse phase enable
Extention type (with cable) 4. Und oFF/30~70 (%) Under current enable and setting
5. g-F oFF/0.05~1.0 (S) Ground fault enable and setting
6. Stl oFF/on Stall enable
7. Loc oFF/200~900 (%) Lock enable and setting
8. Ct 1~120 CT ratio setting
9. P.F on/oFF Phase fault enable
A. gFd Note2)
oFF/on Setting delay of ground fault
b. StA 0~120 Operating time setting by month
c. StH 10~730 Operating time setting by hour
d. tAH A000,000.0 Displaying total operating time (month, hour)
E. rAH A000,000.0 Displaying operating time (month, hour)
Sto Sto Store
Note) 1. 2.dEF is only displayed when dEF s selected in a 1.CHA mode
2. Functions for b to e are available for only SZa & TZa type.
3. Ground fault sensitive current selection: TZa type
Ratings
Model �-T/Ta
DMP� DMP� �-TZ/TZa/TI
Type Wiring method Tunnel
Panel mount Unit or Extension
Operating characteristics Inverse/definite type
Alerting function Variable between 60 and 110%
Current range (A) 06: 0.5~6, 36: 3~36, 60: 5~60
Setting time Definite Delay (D-T) 0~60seconds
Operating (O-T) 0~30seconds
Inverse 0~60seconds
Reset type Manual reset
Operating voltage AC 110V or AC 220V
voltage Frequency 50/60Hz
ZCT input (07-08) 200mA/110mV (ZCT)[30∅, 50∅, 65∅, 80∅]
Aux. contacts (2a, 2b, 1a1b) OL, GR 2-SPST (95~98) 3A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel
G-22
Characteristics IMP Series
IMP-C Type
Protect function
Over current Depend on setting time Selectable the inverse/definite
Phase failure Within 1.5seconds Over 70% of the rate of unbalance
Phase unbalance Within 3seconds 10~70% of the rate of unbalance
Reverse phase Within 0.1seconds Function enable
Stall Within 3seconds setting 150~500% of rated current
Lock Note1)
Within 0.5seconds Setting 200~800% of rated current
Under current Within 3seconds Setting 30~90% of rated current
Selectable 0.05, gF: 0.03/0.05/0.1~3A
Ground fault Note2)
EMPR/DMPR
Menu Setting Value Item Default Value Menu Setting Value Item Default Value
Operation Characteristics (Definite Time / 1.E-r On/OFF Electric Recovery On
1.CHA dEF/th/n-th Heat Accumulation Inverse Time /Inverse Time) n-th
2.A-r OFF, 1~20 min Automatic Recovery (Minute) OFF
2.O-t 1~60s Operation Time (sec) 60
3.r-t Hour/Minute Operation Time Time Check
3.d-t 1~200s Operation Delay (sec) In chase of dEF
Extention type (with cable) 4.r-C 0.5~10A/5~100A Rated Current Max.
4.Srt OFF, 1~8760Hour Operation Time Setup (Hour) -
5.s-d 2009/01.01/00:00 YY/MM/DD/ HH:MM -
5.Ctr 0.25, 0.5, 1~200 CT Ratio (4 times, twice, once) 1
6.Trt Day/hour:minute Total Operation Time Time Check
6.Loc OFF, 200~800% Lock Protection (sec) OFF
A.t-d 0.5~10/5~100A 20mA Output Setup A420
7.StL OFF, 150~500% Stall Protection (sec) OFF
A.Adr 1~247 Communication Address
8.P-F OFF/On Open Phase OFF
b.bps 96/192/384 Communication Speed M485 Model
9.P-U OFF, 10~70% Unbalance Protection (%) OFF
c.S-P On/OFF SWAP
10.rP OFF/On Reverse Phase OFF
11.UC OFF, 30~90% Low Current Protection (%) OFF Note) 1. When the power is supplied first or is resupplied after a power
Ground Fault Operation Current failure, must set up the date (5.S-d).
12.gF 0FF, 0.03, 0.05/0.1~3A (Zero-Phase-Sequence Current) (A) OFF
2. Automatic recovery is only possible in case of an excess
Ground Fault Operation Current current trip.
13.gn OFF, 20~500% (FLCmin) OFF
(Post-Arc Current) (FLCmin)
14.gt 0.05, 0.1~1.0s Ground Fault Operation Time (Current) -
15.gd On/OFF Ground Fault Delay During Start ON
16.IC OFF, 500~1000% Instantaneous Protection (%) OFF
17.Io ALt/TriP Instantaneous Warning/Operation TriP
Note) 1. When the rated current S/W is 100A, the CT ratio is not displayed.
2. Some menus are not displayed if relevant functions are not available.
Ratings
Model IMP-C-NO, M485, A420
Type Wiring method Tunnel
Panel mount Unit or Extension
Operating characteristics defin/TH-Inv./n-TH
Alerting function Variable between 60 and 110%
Current range (A) 0.5~100
Setting time Definite Delay (D-T) 1~200seconds
Operating (O-T) 0~30seconds
Inverse/TH-Inverse time 0~60seconds
Reset type Manual reset
Operating voltage AC 85~245V, 50/60Hz
ZCT input (07-08) 200mA/110mV (ZCT)[30∅, 50∅, 65∅, 80∅]
Aux. contacts (2a, 2b, 1a1b) OL, GR 2-SPST (95~98) 5A/250Vac resistive load
Indicate 7-segment 3-phase current value, fault cause 5point
Bar-LED arrays Load ratio (60~110%)
Mounting 35mm Din-rail/Panel
Communication A420: Analog, M485: Modbus
Certification CE
G-23
Electronic motor protection relays
Setting method
GMP Series Inverse time
1. Check the rated voltage and apply the control power to A1 and A2 terminal
2. Check the TEST/RESET button
1) When you press the ‘Test/Reset’ button, the O.L LED is turned on and the EMPR is tripped
2) When you press the ‘Test/Reset’ button under the EMPR is tripped, the O.L LED is turned
off and the EMPR is reset
3) Auto reset function: When it is tripped by the over current, it is reset after 1 Min.(Optional)
0.4 Second
Over current
intervals
O.L LED
Over current
light up
1 time for 3
Phase failure (3CT)
R
seconds
GMP 80-3S/3SR model,
Tripped status
2 time for 3
S O.L LED will light up and
seconds
also FAULT LED will flicker.
2 time for 3
T
seconds
G-24
Setting method
GMP Series Definite time
Test/Reset button
Tunnel type mounting
O.L LED
Note) In operation, even though you press the 'Test/Reset' button, the EMPR do not trip
EMPR/DMPR
● The operating time is the time during which the EMPR tripped by the Current (%)
over-current. The EMPR is tripped after the selected operation time
1) Set the operation time by the 'O-time' knob Definite time characteristics curve
2) If you set the 'O-time' to the min value, the EMPR is tripped at once
Note) Generally set it to 4~6 seconds
4. Check the LED condition when operation Condition Red O.L LED Note
1) Over-current Operation normal Off
‐The EMPR is not tripped during the D-time under over-current but
the O.L LED turned on and off to indicate that the over-current flows Overcurrent Flicker
‐If the EMPR is tripped after D-time the O.L LED turned on
Trip over-current On The EMPR is tripped
G-25
Electronic motor protection relays
Setting method
GMP60-TD(a) Type
●Setting Menu
FUNC SEL Description Remarks
Current type selection Set the same with rated current S/W
Trip time setting -
Time delay setting -
Rated current setting -
Current ratio setting -
Phase loss enable -
Undercurrent setting For TDa model only
Automatic reset setting For TDa model only
Operation hour setting For TDa model only
Total running hour check For TDa model only
Running hour check For TDa model only
Store -
Note) 1. If operation hour set at is elapsed is displayed and the relay operates normally. (There is no additional relay output)
2. How to check and
Display How to check
Press SEL Day displayed Press SEL Hour, Min displayed
Press SEL Operation hour displayed Press SEL Day displayed
Press SEL Min displayed
3. When power is OFF the data in unit of minute is deleted at
4. Operation hour at is the total running hour before the motor is oFF and displayed in Day, Hour and Min.
When motor is OFF the data is deleted.
Undercurrent U-C Lower than the undercurrent set ratio : Within 3S GMP60TDa
G-26
Setting method
GMP60-3TZ(R) / 3TN(R) Type
EMPR/DMPR
NO Function Setting Description Remark
② PWR. Red LED Lights up when power is ON Blinking in the failure mode
Overcurrent TRIP:
∙S-phase:
∙T-phase:
Reverse phase:
⑧ TEST/RESET BUTTON 1. Check relay contacts - displays fault cause the final failure
G-27
Electronic motor protection relays
Setting method
DMP Series
Current knob
Time knob
2. Shift the mode by pressing the FUNC key and then select the values by the Sel key
1) First shift to the test mode by press the ”
Test/Reset”button and then set the functions by press the ”
FUNC”button
2) Each time you press the” FUNC”button, the function mode switches from 1.CHA mode to Sto mode.
When the mode that you want to change is displayed, push the ” Sel”button to select the value you want.
After you select the value, press the ”
FUNC”button to finish the settings and it displays the next mode
3) If no button is pressed in the selection mode, it remains in that mode
Alarm signal (Alert function)
4) If you select the inverse time characteristics it skips the mode 2
5.ALt AL(07-08) contact operation
(Definite O-time) and go to the mode 3 (Reverse phase)
5) Alt is the alert setting mode. It displays the load rate of the current 1
On
setting value by the bar LED (60~110%) 0
- If the current is higher than the setting value, the bar LED is switched
on and off and the AL relay (07-08) 1
make close and open in 1sec interval unit the EMPR is tripped (Pre- 0
alarm function)
Off
- If the 5. Alt mode is set to off, the AL relay make close after the EMPR Normal Alarm Trip
is tripped (Normal open contact) Alert setting Trip setting
value value
6) To finish the settings you have to press the ”
Sel”button in the Sto
mode
Setting Menu
FUNC Sel Functions Note
Inverse or definite time characteristics Default is inverse time characteristics
Set the O-time (Definite time only) For D-time setting, use the time knob
Reverse phases protection Default is“Off”
Under current protection Default is“Off”Note1)
Alarm function (With pre-alarm function) Default is“Off”
Ground fault and Setting the operating time Default is “Off”(Z type)
Stall function Default is“Off”
Lock function Default is“Off”
CT ratio Default is 1:1 Note2) (DMP06 Modle)
Phase failure Default is“On”to store
Setting delay of Ground Fault Available for SZa/TZa
Operating time setting (Month)
Operating time setting (Hour)
DMP�-Sa/Ta/SZa/TZa model
Displaying total operating time (Month, Hour)
Displaying operating time (Month, Hour)
Store Push the SEL button to store
Note) 1. Set the under current value from above 350mA
2. Do not change the CT ratio in 36, 60 type
G-28
Setting method
DMP Series
EMPR/DMPR
graph (Approx. 90% load rate)
R phase current
ex) R
S
Turn on R R
S S
T T T
S S
T T
R Lock
S
T
G-29
Electronic motor protection relays
Operation and Setting
IMP Series
1. Test/Reset
1) Check wires.
2) Press the Test/Reset key once. Then“TEST”is displayed and the EMPR is tripped.
3) Press again the Test/Reset key to reset the EMPR.
Note) While the motor is running, the Test/Reset key does not work.
2. Setting
1) Press the Test/Reset key once. Then“TEST”is displayed and the EMPR is tripped.
2) Press the Enter key. Then“P-99”is displayed. Use the Up/Down keys to change the password.
3) Press the Enter key to enter A-gr setup mode.
Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
4) In the A-Grp mode, Press the Enter key. Then“1.CHA”is displayed.
Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
Press the Test/Reset key to move back to the previous mode.
5) Use the Up/Down keys to set up the value and Press the Enter key to save it.
Note) When the power is supplied first or is resupplied after a power failure, must set up the date in b-gr, 5.S-d.
Set up the rated current S/W while the power is off.
3. Quick Setup
1) Press the“Up and Enter”keys at the same time.“UPLD”is displayed and settings are uploaded
to the display.
2) Insert the display to the body without settings, and then press the Test key to enter the test mode.
3) Press the“Down and Enter”keys at the same time.“TEST”is displayed and downloading is
completed.
4) Press the Test key to return to the normal mode.
Note) Communication settings cannot be uploaded or downloaded.
4. Setting Checkup
1) Press the Enter key.
2) Use the Up/Down keys to select a group and Press the Enter key to enter the selected group.
Press the Test/Reset key to move back to the previous mode.
3) Use the Up/Down keys to select an item and Press the Enter key to enter the selected item.
4) Press the Enter key again to check settings.
2) Use the Up/Down keys to select an event and press the Enter key to go to the selected event.
3) The R-phased failure current is displayed. Every time the Down key is pressed, S-phased failure
current, Tphased failure current, overload rate and date are displayed one after the other.
4) Press the Test/Reset key to move back to the previous mode.
5) Press the Up and Down keys at the same time to get out of the failure event checkup mode.
G-30
Operation and Setting
IMP Series
A Operation Characteristics
1.CHA dEF/th/n-th n-th (Inverse)
(Definite/Thermal Inverse/Inverse)
EMPR/DMPR
Ground Fault Operation Current
12.gF 0FF, 0.03, 0.05/0.1~3A OFF
(Zero sequence CT)
Note) 1. When the rated current S/W is 100A, the CT ratio is not displayed.
2. Some menus are not displayed if relevant functions are not available.
Note) 1. When the power is supplied first or is resupplied after a power failure, must set up the date (5.S-d).
2. Automatic reset is only possible in case of an excess current trip.
G-31
Electronic motor protection relays
Operation and Setting
IMP Series
R Phase
S Phase
T Phase
Ground Fault Current
Note) kW, kVar, and V indicate the specification of the voltage models (under development).
Operation Display
Display Description Remark
Over Current Trip Operate within predefined time.
Under Current Trip Operate within 3 seconds.
Open Phase Trip Operate within 1.5 seconds when the unbalance rate is over 70%.
Unbalance Trip Operate within 3 seconds.
Lock Trip Operate within 0.5 seconds.
Stall Trip Operate within 3 seconds.
Reverse Phase Trip Operate within 0.1 second.
Ground Fault Trip Operate within predefined time.
Instantaneous Trip Operate within 0.05 seconds.
Elapsed Time (No Trip) The operation time is reset when the Reset key is pressed.
Communication Fault between Body and Display (Press the ENTER/RESET key to return to the normal mode)
2) When there is no current, 4mA is sent. If the current goes beyond the predefined value, 8mA
< Analogue output when the output is set to be 0.5A (5A) >
3) When the system is the 0.5A~10A setting mode, measurement starts from 0.3A. When
the system is the 5A~100A setting mode, measurement starts from 3A. Thus, when the
20mA
20mA
current is under 0.3A (3A), 0A is measured and output is 4mA. (To measure the load 16.8mA
16mA
current correctly, an appropriate CT should be used). 13.6mA
Note) The allowable burden is less than 500Ϊ . 12mA
10.4mA
Considering the receiver resistance (usually 250Ϊ ) and track resistance), the shielding cable should be used. 8mA
7.2mA
4mA
Communication Spec. :
Refer to G-41 page and LSIS Homepage (www.lsis.biz) 0A
0A
1A
10A
2A
20A
3A
30A
4A
40A
5A(0.5A~10A)
50A(5A~100A)
G-32
Dimensions
GMP Series
Screw
Screw
0.15kg
EMPR/DMPR
Screw
0.18kg
GMP40-2P Sol
GMP40-2PD Sol
GMP40-2PA Sol
GMP40-3P Sol
Screw
GMP40-3PR Sol
Screw
0.20kg/0.22kg
GMP80-2S
GMP80-3S
Screw
GMP80-3SR
Mounting hole
Screw
0.42kg/0.46kg
G-33
Electronic motor protection relays
Dimensions
GMP Series
GMP22-2S
GMP22-3S
GMP22-3SR
GMP40-2S
GMP40-3S
GMP40-3SR Screw
Screw
0.19kg/0.21kg
GMP22-2T
GMP22-3T
GMP22-3TR
Screw
GMP40-2T
GMP40-3T
GMP40-3TR
0.14kg/0.16kg
GMP60T
GMP60TE
GMP60TA
Screw
Screw
0.14kg
G-34
Dimensions
DMP Series
GMP60-TD
26.8 62.25 7.2 8.2
GMP60-TDa
.5
R2
.5
12.5
R2
74
74
75
61
10
22±0.5
55.4 55.4 47
5.8
72.8
0.25kg
EMPR/DMPR
Terminal arrangement
Note)
G-35
Electronic motor protection relays
Dimensions
DMP Series
DMP�-S
DMP�-SZ
※Aux. contact wire size
: below 8[mm2]
Mounting dimensions
※Torque : 0.5N
DMP�-Sa
DMP�-SZa
0.7kg
DMP�-S
DMP�-SZ Mounting dimensions
DMP�-Sa
DMP�-SZa
0.64kg
Panel mounting
Note) 1. In extension type, the digital EMPR is calibrated with combining the display unit and mainbody
so, please cautious not to combine the display unit and mainbody with different part No.
2. The 07-08 contacts are the ZCT input terminal (Digital EMPR with ground fault function)
G-36
Dimensions
DMP Series
DMP�-T
DMP�-TZ
※Wire size to penetrate a CT
:below 22[mm2]
Mounting dimensions
DMP�-Ta
DMP�-TZa
EMPR/DMPR
0.56kg
DMP�-T
DMP�-TZ Mounting dimensions
DMP�-Ta
DMP�-TZa
0.5kg
Panel mounting
Note) 1. In extension type, the digital EMPR is calibrated with combining the display unit and mainbody
so, please cautious not to combine the display unit and mainbody with different part No.
2. The 07-08 contacts are the ZCT input terminal (Digital EMPR with ground fault function)
G-37
Electronic motor protection relays
Dimensions
IMP Series
One-Body Type
68
90 64
7.3 82
135.5
109.3
4.2
25
U/2/T1 V/4/T2 W/6/T3
∅17
21
5
53.5
68
90 64
12
82
121.3
109.3
4.2
25
∅17
21
5
53.5
Panel mounting
26 44
17 56 17
22
64
20
M4
22
90
G-38
Wiring method
GMP Series
GMP22-2P (1c)
GMP60T (1c)
GMP�-� (1a1b)
G
EMPR/DMPR
With the External CT
GMP60-3TZ, TZR
GMP60-3TN, TNR
GMP60-3T, 3TR
주)
Note) 1. The Z1, Z2 are the ZCT input terminal (GPM60-3TZ/TZ type)
2. Aux. contacts are operate when power applied.
G-39
Electronic motor protection relays
Wiring method
DMP Series
DMP-S/Sa
DMP-T/Ta
Single phase
Note) When the single-phase motor is used, reverse phases protection should be set off.
DMP-SZ/SZa
DMP-TZ/TZa
DMP-SZ/SZa
DMP-TZ/TZa
주1)
G-40
Wiring method
IMP Series
OFF OL
(RESET) TRIP
MCCB
Y AUX
MC
SHT MCCB
RS485 VR VS VT TRX(+) TRX(-) 05 06
MC (4~20mA) 10A
EMPR OL SR
96 98 08 Z1 Z2
EMPR/DMPR
Note) 1. When the zero-phase-sequence current transformer is used to detect ground faults, connect the ZCT.
2. When the single-phase motor is used, all phases are connected except the S phase, and open-phase, unbalance and ground fault should be set OFF.
Terminal Configuration
Engrave Description Remark
A1(+), A2(-) Input terminal for operation power AC/DC85~245V
95-96 When the power is ON (NC contact output) In case of an instantaneous trip, if 17.lo is ALT, it is NC, and if 17.lo is Trip, it is NO.
97-98 When the power is ON (NC contact output) In case of an instantaneous trip, regardless of 17 .1o setup, it is NC.
07-08 Converted to the NC mode only when an instantaneous trip occurs.
Z1, Z2 Output terminal for the zero-phase sequence current transformer Specific ZCT (for the EMPR)
TRX(+) RS485 terminal (TRX+) Or 4~20mA (+) output
M485, A420 Type
TRX(-) RS485 terminal (TRX-) Or 4~20mA (-) output
10A/100A Max. rated current change S/W 10A : 0.5~10A, 100A : 5~100A
VR/VS/VT 3-phase voltage input terminal
N/A
05-06 Output terminal for voltage protection
Note) 1. The 3-phase voltage input terminal and 05-06 output terminal should be connected only for voltage protection models, which will be released in the future.
2. For RS485 connection, the terminal resistance should be 120Ϊ .
3. For 4~20mA current, the maximum burden should be less than 500Ϊ .
G-41
Electronic motor protection relays
Accessories
CT, ZCT, Cable and Terminal
● CT (Current Transformer)
Ratings
Type 2CT
DCT (Current Transformer) DCT-100 100 : 5A
DCT-150 150 : 5A
CT ratio DCT-200 200 : 5A
DCT-300 300 : 5A
DCT-400 400 : 5A
Class 1.0
2CT Burden 5VA
Insulation voltage 600VAC
33.5
With GMP60T
28.5
55 60
120 80
69.6
2-
5
Ratings
Type 3CT
SCT(Current Transformer) SCT-100 100 : 5A
SCT-150 150 : 5A
CT ratio SCT-200 200 : 5A
SCT-300 300 : 5A
SCT-400 400 : 5A
Class 1.0
Burden 5VA
1CT 3CT (1CT×3)
Insulation voltage 600VAC
Insulated impulse voltage 2kV
Dimension Insulation resistance 10㏁(DC 500V Megger)
Mounting Panel
Note) Please use SCT for LS Electronic Motor Protection Relay only.
65
65
With GMP60-3T/DMP/IMP
64 82
82 82 82
64
53
∅
5
27.5
65
32.5
82 82
256
G-42
Accessories
CT, ZCT, Cable and Terminal
Dimension
EMPR/DMPR
Unit (mm) Unit (mm)
Model A B C D E F G H I ∅ Model A B C D E F G H I ∅
LZT-030 30 25 108 100 114 7 32 32 110 6 LZT-050 50 25 131 100 122 7 32 36 114 6
LZT-065 65 26 143 114 133 7 39 37 126 6
LZT-080 80 34 174 160 180 7 40 40 151 6
● Other Options
Cable Terminal Block
Applicable Type DMP, IMP Series Applicable Type DMP Series, GMP60-3T, 3TZ, 3TN
Spec. 1m, 1.5m, 2m, 3m, 4m Spec. 60A blelow
* Panel mount: Extension cable
G-43
Electronic motor protection relays
Direct mounting EMPR new/old comparative table
Metasol EMPR
(New) Demension
Type of contactors MC-9b, 12b, 18b, 22b MC-9b, 12b, 18b, 22b MC-32a, 40a
Meta-MEC EMPR
(Old) Demension
G-44