Pressure Transmitter

The Cerabar S pressure transmitter uses ceramic and metal sensors to measure process pressure with high accuracy and reliability. It can measure pressures up to 700 bar and temperatures up to 400°C with appropriate seals. Communication options include HART, PROFIBUS PA or FOUNDATION Fieldbus. It provides high accuracy pressure measurement for applications in process engineering and manufacturing.

Uploaded by

ramy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views

Pressure Transmitter

The Cerabar S pressure transmitter uses ceramic and metal sensors to measure process pressure with high accuracy and reliability. It can measure pressures up to 700 bar and temperatures up to 400°C with appropriate seals. Communication options include HART, PROFIBUS PA or FOUNDATION Fieldbus. It provides high accuracy pressure measurement for applications in process engineering and manufacturing.

Uploaded by

ramy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 92

Technical Information

Cerabar S PMC71, PMP71, PMP75


Process pressure measurement
Pressure transmitter with ceramic and metal sensors
Overload-resistant and function-monitored; Communication via
HART, PROFIBUS PA or FOUNDATION Fieldbus

Application Your benefits


The Cerabar S pressure transmitter is used for the • Very good reproducibility and long-term stability
following measuring tasks: • High reference accuracy: up to ±0.075%,
• Absolute pressure and gauge pressure in gases, steams as PLATINUM version: ±0.05%
or liquids in all areas of process engineering and • Turn down 100:1, higher on request
process measurement technology • Used for process pressure monitoring up to SIL3,
• Level, volume or mass measurement in liquids certified according to IEC 61508 by TÜV SÜD
• High process temperature • HistoROM®/M-DAT memory module
– without diaphragm seals up to 150°C (302°F) • Function-monitored from the measuring cell to the
– with typical diaphragm seals up to 400°C (752°F) electronics
• High pressure up to 700 bar (10,150 psi) • Continuous modularity for differential pressure,
• International usage thanks to a wide range of approvals hydrostatic and pressure (Deltabar S – Deltapilot S –
Cerabar S), e.g.
– replaceable display
– universal electronics
• Quick commissioning thanks to quick setup menu
• Easy and safe menu-guided operation on-site,
via 4 to 20 mA with HART, via PROFIBUS PA or
via FOUNDATION Fieldbus
• Extensive diagnostic functions
• Device versions in conformity with ASME-BPE

TI383P/24/ae/12.09
Cerabar S

Table of contents

Function and system design. . . . . . . . . . . . . . . . . . . . . 4 Operating conditions (installation) . . . . . . . . . . . . . . 24


Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . 24
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation instructions for devices without diaphragm seal – PMC71
Level measurement (level, volume and mass) . . . . . . . . . . . . . . . . 6 and PMP71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Heat insulation – PMC71 high temperature version and PMP75 . 24
Mounting with temperature isolator . . . . . . . . . . . . . . . . . . . . . . 25
Wall and pipe-mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
"Remote housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Turn the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Silicone-free applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Ultra pure gas applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Applications with hydrogen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Signal range – 4...20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . 10 Operating conditions (environment) . . . . . . . . . . . . . 28
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ambient temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Load – 4...20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Dynamic behavior current output . . . . . . . . . . . . . . . . . . . . . . . . 11
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Dynamic behavior HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dynamic behavior PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . 12
Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dynamic behavior FOUNDATION Fieldbus . . . . . . . . . . . . . . . . 12
Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Data of the FOUNDATION
Fieldbus interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Operating conditions (Process) . . . . . . . . . . . . . . . . . 30
Process temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Process temperature range, seals . . . . . . . . . . . . . . . . . . . . . . . . 31
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 32
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Housing dimensions T14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Housing dimensions T17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Process connections PMC71 (with ceramic process isolating
Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 diaphragm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Process connections PMP71 (with metallic process isolating
diaphragm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Performance characteristics – general . . . . . . . . . . . . 19
PMP75 Basic unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Process connections PMP75 (with metallic process isolating
Uncertainty of measurement for small absolute pressure ranges . . 19
diaphragm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
"Remote housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Influence of the installation position . . . . . . . . . . . . . . . . . . . . . . 19
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Performance characteristics – ceramic process isolating
diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Reference accuracy – PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Total performance – PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Total Error - PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Warm-up period – PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Thermal change of the zero output and the output span – Hard- and Software for local and remote operation . . . . . . . . . . . 66
PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Planning instructions, diaphragm seal systems . . . . . 68


Performance characteristics – metallic process isolating
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Planning instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Reference accuracy – PMP71, PMP75 . . . . . . . . . . . . . . . . . . . . 22 Diaphragm seal filling oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Total performance – PMP71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Influence of the temperature on the zero point . . . . . . . . . . . . . . 69
Total Error - PMP71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Warm-up period – PMP71, PMP75 . . . . . . . . . . . . . . . . . . . . . . 23 Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Thermal change of the zero output and the output span –
PMP71 and PMP75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

2 Endress+Hauser
Cerabar S

Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 75


CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Suitability for hygenic processes . . . . . . . . . . . . . . . . . . . . . . . . 75
Marine certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Functional Safety SIL / IEC 61508 Declaration of conformity
(optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Overspill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
CRN approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . 75
Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Block and bleed valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 77
PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
PMP71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
PMP75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

Additional documentation . . . . . . . . . . . . . . . . . . . . . 89
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Brief operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Manual for Functional Safety (SIL) . . . . . . . . . . . . . . . . . . . . . . . 89
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Overspill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

3 Endress+Hauser
Cerabar S

Function and system design


Device selection

Cerabar S – PMC71 PMP71 PMP75


Product family

P01-PMC71xxx-16-xx-xx-xx-000 P01-PMP71xxx-16-xx-xx-xx-000 P01-PMP75xxx-16-xx-xx-xx-000

With capacitive measuring cell and With piezoresistive measuring cell With diaphragm seal
ceramic measuring process isolating and metallic welded process isolating
diaphragm (Ceraphire®) diaphragm

Field of application – Gauge pressure and absolute pressure


– Level

Process connections – Diverse thread – Diverse thread – Wide range of diaphragm seals, → see
– DN 32 – DN 80 – DN 25 – DN 80 the following section "Overview of
– ANSI 1 1/2" – 4" – ANSI 1 1/2" – 4" diaphragm seal for PMP 75"
– JIS 50 A – 100 A – JIS 25 A – 100 A
– Oval flange adapter
– Prepared for diaphragm seal mount

Measuring ranges from -100/0 to 100 mbar from -100/0 to 100 mbar from -400/0 to 400 mbar
(-1.5/0 to 1.5 psi) (-1.5 to 1.5 psi) (-6/0 to 6 psi)
to -1/0 to 40 bar to -1/0 to 700 bar to -1/0 to 400 bar
(-14.5/0 to 600 psi) (-14.5/0 to 10,150 psi) (-14.5/0 to 6000 psi)

OPL 1 max. 60 bar (870 psi) max. 1050 bar (15,200 psi) max. 600 bar (8700 psi)
2
Process temperature range –25 to +125°C/–20 to +150°C –40 to +125°C -70 to 400°C (-94 to +752°F)
(–13 to +257°F/–4 to +302°F) (–40 to +257°F)

Ambient temperature range –40 to +85°C (–40 to +185°F) –40 to +85°C (–40 to +185°F) 3 –40 to +85°C (–40 to +185°F)

Ambient temperature range –40 to +60°C (–40 to +140°F)


separate housing

Reference accuracy – Up to ±0.075% of the set span Up to ±0.075% of the set span
– PLATINUM version: up to ±0.05% of the set span

Supply voltage – For non-hazardous areas: 10.5 to 45 V DC


– Ex ia (intrinsically safe): 10.5 to 30 V DC

Output 4 to 20 mA with superimposed HART protocol, PROFIBUS PA, FOUNDATION Fieldbus

Options – PMP71, PMP75: Gold-Rhodium-coated process isolating diaphragm


– PMP71, PMP75: NACE-compliant materials
– PMC71, PMP71, PMP75: inspection certificate 3.1
– HistoROM®/M-DAT memory module
– Separate housing

Specialities – Metal-free measurement with PVDF – Oil volume-minimized process – Wide range of diaphragm seals
connection connections – For high media temperatures
– Cleaning of the transmitter for the use – gas-tight, elastomer-free – Oil volume-minimized process
in paint shops connections
– Completely welded versions

1) OPL = Over pressure limit; dependent on the lowest-rated element, with regard to pressure, of the selected components
2) High temperature version "T" for feature 100 "Additional option 1" or for feature 110 "Additional option 2"
3) lower temperature on request

4 Endress+Hauser
Cerabar S

Measuring principle

Ceramic process isolating diaphragm used for PMC71 (Ceraphire®) Metallic process isolating diaphragm used for PMP71 and PMP75

1 2 3
1
2

4 3
4

p p

P01-PMC71xxx-03-xx-xx-xx-000 P01-PMP7xxxx-03-xx-xx-xx-000

Ceramic sensor Metal sensor


1 Atmospheric vent (gauge pressure only) 1 Measuring element
2 Ceramic substrate 2 Wheatstone bridge
3 Electrodes 3 Channel with fill fluid
4 Ceramic process isolating diaphragm 4 Metal process isolating diaphragm

Ceramic process isolating diaphragm used for PMC71 (Ceraphire®)


The ceramic sensor is a dry sensor, i.e. the process pressure acts directly on the robust ceramic process isolating
diaphragm and deflects it. A pressure-dependent change in capacitance is measured at the electrodes of the
ceramic carrier and the process isolating diaphragm. The measuring range is determined by the thickness of the
ceramic process isolating diaphragm.
Advantages:
• Guaranteed overload resistance up to 40 times the nominal pressure
• Thanks to highly-pure 99.9% ceramic (Ceraphire®, see also "www.endress.com/ceraphire")
– extremely high chemical resistance compared to Alloy
– less relaxation
– high mechanical stability
• Suitable for vacuums
• Second process barrier (Secondary Containment) for enhanced integrity
• Process temperature up to 150°C (302°F)

Metallic process isolating diaphragm used for PMP71 and PMP75

PMP71
The operating pressure deflects the process isolating diaphragm and a fill fluid transfers the pressure to a
resistance measuring bridge (semi-conductor technology). The pressure-dependent change of the bridge output
voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 700 bar (10,150 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Second process barrier (Secondary Containment) for enhanced integrity
• Significantly less thermal effect compared to diaphragm seal systems

PMP75
The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is transferred to the
process isloating diaphragm of the sensor by a diaphragm seal fill fluid. The process isolating diaphragm is
deflected and a fill fluid transfers the pressure to a resistance measuring bridge. The pressure-dependent change
of the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 400 bar (5800 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Second process barrier (Secondary Containment) for enhanced integrity

Endress+Hauser 5
Cerabar S

Level measurement (level, Design and operation mode


volume and mass)

p
h= ρ g

P01-PMx7xxxx-15-xx-xx-xx-000

Level measurement with Cerabar S


h Height (level)
p Pressure
ρ Density of the medium
g Gravitation constant

Your benefits
• Choice of three level operating modes in the device software
• Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve
• Choice of diverse level units with automatic unit conversion
• A customised unit can be specified
• Has a wide range of uses, as well
– in the event of foam formation
– in tanks with agitators of screen fittings
– in the event of liquid gases

Communication protocol • 4 to 20 mA with HART communication protocol


• PROFIBUS PA
– The Endress+Hauser devices meet the requirements as per the FISCO model.
– Due to the low current consumption of 13 mA ± 1 mA
– up to 7 Cerabar S for Ex ia, CSA IS and FM IS applications
– up to 27 Cerabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
can be operated at one bus segment with installation as per FISCO.
Further information on PROFIBUS PA, such as requirements for bus system components, can be found in
the Operating Instructions BA034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and in
the PNO guideline.
• FOUNDATION Fieldbus
– The Endress+Hauser devices meet the requirements as per the FISCO model.
– Due to the low current consumption of 15 mA ± 1 mA
– up to 6 Cerabar S for Ex ia, CSA IS and FM IS applications
– up to 24 Cerabar S for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
can be operated at one bus segment with installation as per FISCO.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components can be
found in the Operating Instructions BA013S "FOUNDATION Fieldbus Overview".

6 Endress+Hauser
Cerabar S

Input
Measured variable Absolute pressure and gauge pressure, from which level (level, volume or mass) is derived

Measuring range PMC71 – with ceramic process measuring diaphragm (Ceraphire®) for gauge pressure

Nominal value Measurement limit Smallest MWP 1 OPL 2 Vacuum Order


calibratable resistance code 3
Span 4

lower (LRL) upper (URL)

bar (psi) bar (psi) bar (psi) bar (psi) bar (psi) barabs (psia)

100 mbar –0.1 (-1.5) +0.1 (+1.5) 0.005 (0.07) 2.7 (39) 4 (60) 0.7 (10.1) 1C

250 mbar –0.25 (-3.75) +0.25 (+3.75) 0.005 (0.07) 3.3 (48) 5 (80) 0.5 (7.3) 1E

400 mbar (6 psi) –0.4 (-6) +0.4 (+6) 0.005 (0.07) 5.3 (77) 8 (120) 0 1F

1 bar –1 (-15) +1 (+14) 0.01 (0.15) 6.7 (97) 10 (150) 0 1H

2 bar –1 (-15) +2 (+30) 0.02 (0.30) 12 (174) 18 (260) 0 1K

4 bar –1 (-15) +4 (+60) 0.04 (0.60) 16.7 (242) 25 (360) 0 1M

10 bar –1 (-15) +10 (+150) 0.1 (1.5) 26.7 (387) 40 (600) 0 1P

40 bar (600 psi) –1 (-15) +40 (+600) 0.4 (6) 40 (600) 60 (900) 0 1S

PMC71 – with ceramic process measuring diaphragm (Ceraphire®) for absolute pressure

Nominal value Measurement limit Smallest MWP 1 OPL 2 Order


calibratable code 3
Span 4

lower (LRL) upper (URL)

barabs (psia) barabs (psia) bar (psi) barabs (psia) barabs (psia)

100 mbar(1.5 psi) 0 +0.1 (+1.5) 0.005 (0.07) 2.7 (39) 4 (60) 2C

250 mbar (4 psi) 0 +0.25 (+3.75) 0.005 (0.07) 3.3 (48) 5 (80) 2E

400 mbar (6 psi) 0 +0.4 (+6) 0.005 (0.07) 5.3 (77) 8 (120) 2F

1 bar (15 psi) 0 +1 (+14) 0.01 (0.15) 6.7 (97) 10 (150) 2H

2 bar (30 psi) 0 +2 (+30) 0.02 (0.30) 12 (174) 18 (260) 2K

4 bar (60 psi) 0 +4 (+60) 0.04 (0.60) 16.7 (242) 25 (360) 2M

10 bar (150 psi) 0 +10 (+150) 0.1 (1.5) 26.7 (387) 40 (600) 2P

40 bar (600 psi) 0 +40 (+600) 0.4 (6) 40 (600) 60 (900) 2S

1) The MWP (maximum working pressure) for the measuring device depends on the weakest element of the
components selected with regard to pressure, i.e. the process connection (→ 32 ff) has to taken into consideration
in addition to the sensor (→ see Table above). Pay attention to the pressure-temperature dependence also. For the
appropriate standards and further information, see → 31, "Pressure specification".
2) OPL: Over Pressure Limit; depends on the weakest link in terms of pressure of the selected components.
3) Versions in the order code → 77 ff, feature 40 "Sensor range; Sensor overload limit (= OPL)"
4) Turn down > 100:1 on request or can be set at the device

Endress+Hauser 7
Cerabar S

PMP71 and PMP75 – with metallic process isolating diaphragm for gauge pressure

Nominal value Measurement Smallest MWP 1 OPL 2 Vacuum Order


limits calibratable resistance 3 code 4
Span 5
lower upper Silicone oil/Inert oil
(LRL) (URL)

bar (psi) bar (psi) bar (psi) barrel (psi) barrel (psi) barabs (psia)

400 mbar (6 psi) –0.4 (-6) +0.4 (6) 0.005 (0.07) 4 (60) 6 (90) 0.01/0.04 (0.14/0.58) 1F

1 bar (15 psi) –1 (-15) +1 (15) 0.01 (0.15) 6.7 (100) 10 (150) 0.01/0.04 (0.14/0.58) 1H

2 bar (30 psi) –1 (-15) +2 (30) 0.02 (0.30) 13.3 (200) 20 (300) 0.01/0.04 (0.14/0.58) 1K

4 bar (60 psi) –1 (-15) +4 (60) 0.04 (0.6) 18.7 (270) 28 (400) 0.01/0.04 (0.14/0.58) 1M

10 bar (150 psi) –1 (-15) +10 (150) 0.1 (1.5) 26.7 (400) 40 (600) 0.01/0.04 (0.14/0.58) 1P

40 bar (600 psi) –1 (-15) +40 (600) 0.4 (6) 100 (1500) 160 (2320) 0.01/0.04 (0.14/0.58) 1S

100 bar –1 (-15) +10 1.0 100 400 0.01/0.04 (0.14/0.58) 1U


(1500 psi) (1500) (15) (1500) (6000)

400 bar –1 (-15) +400 4.0 400 600 0.01/0.04 (0.14/0.58) 1W


(6000 psi) (6000) (60) (6000) (8700)

700 bar 6 –1 (-15) +700 7.0 700 1050 0.01/0.04 (0.14/0.58) 1X


(10,150 psi) (10,150) (101) (10,150) (15,230)

PMP71 and PMP75 – with metallic process isolating diaphragm for absolute pressure

Nominal value Measurement Smallest MWP 1 OPL 2 Vacuum Order


limits calibratable resistance 3 code 4
Span 5
lower upper Silicone oil/Inert oil
(LRL) (URL)

barabs barabs bar (psi) barabs barabs barabs (psia)


(psia) (psia) (psia) (psia)

400 mbar (6 psi) 0 +0.4 (6) 0.005 (0.07) 4 (60) 6 (90) 0.01/0.04 (0.14/0.58) 2F

1 bar (15 psi) 0 +1 (15) 0.01 (0.15) 6.7 (100) 10 (150) 0.01/0.04 (0.14/0.58) 2H

2 bar (30 psi) 0 +2 (30) 0.02 (0.30) 13.3 (200) 20 (300) 0.01/0.04 (0.14/0.58) 2K

4 bar (60 psi) 0 +4 (60) 0.04 (0.6) 18.7 (270) 28 (400) 0.01/0.04 (0.14/0.58) 2M

10 bar (150 psi) 0 +10 (150) 0.1 (1.5) 26.7 (400) 40 (600) 0.01/0.04 (0.14/0.58) 2P

40 bar (600 psi) 0 +40 (600) 0.4 (6) 100 (1500) 160 (2320) 0.01/0.04 (0.14/0.58) 2S

100 bar 0 +10 1.0 100 400 0.01/0.04 (0.14/0.58) 2U


(1500 psi) (1500) (15) (1500) (6000)

400 bar 0 +400 4.0 400 600 0.01/0.04 (0.14/0.58) 2W


(6000 psi) (6000) (60) (6000) (8700)

700 bar 6 0 +700 7.0 700 1050 0.01/0.04 (0.14/0.58) 2X


(10,150 psi) (10,150) (101) (10,150) (15,230)

1) The MWP (maximum working pressure) for the measuring device depends on the weakest element of the
components selected with regard to pressure, i.e. the process connection (→ 32 ff) has to taken into consideration
in addition to the sensor (→ see Table above). Pay attention to the pressure-temperature dependence. For the
appropriate standards and further information, → 31, "Pressure specifications".
2) OPL: Over pressure limit (= Sensor overload limit)
3) The vacuum resistance applies to the measuring cell at a reference conditions. The pressure and temperature
application limits of the selected filling oil must also be observed for the PMP75. → 69, section "Diaphragm seal
filling oils".
4) Versions in the order code → 77 ff, feature 40 "Sensor range; Sensor Overload limit (= OPL)"
5) Turn down > 100:1 on request or can be set at the device
6) PMP71 only, PMP75 on request

8 Endress+Hauser
Cerabar S

Explanation of terms Explanation of terms: Turn down (TD),


set span and on zero based span

Case 1:
• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value (URV)⏐ 1 = 2

Example: LRL = LRV URV URL


• Lower range value (LRV) = 0 bar
• Upper range value (URV) = 0.5 bar (7 psi) 0 bar 7 psi +14.5 psi
(0.5 bar) (+1 bar)
• Nominal value (URL) = 1 bar (14.5 psi)
Turn down:
3
• TD = URL / ⏐URV⏐ = 2:1
set span: 4 = 5
• URV – LRV = 0.5 bar (7 psi)
P01-PMx7xxxx-05-xx-xx-xx-012
This span is based on the zero point.
Example: 1 bar (15 psi) measuring cell

Case 2:
• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value (URV)⏐ 1 = 2
Example: LRL LRV URV URL
• Lower range value (LRV) = 0 bar
• Upper range value (URV) = 0.5 bar (7 psi) –14.5 psi 0 7 psi +14.5 psi
(–1 bar) (0.5 bar) (+1 bar)
• Nominal value (URL) = 1 bar (14.5 psi)
Turn down:
3
• TD = URL / ⏐URV⏐ = 2:1
set span: 4
• URV – LRV = 0.5 bar (7 psi)
This span is based on the zero point.
5
P01-PMx7xxxx-05-xx-xx-xx-007

Example: 1 bar (15 psi) measuring cell

Case 3:
• ⏐Lower range value⏐ ≥ ⏐Upper range value⏐ 1 = 2
Example: LRL LRV URV URL
• Lower range value (LRV) = –0.6 bar (-8 psi)
• Upper range value (URV) = 0 bar -14.5 psi -8 psi 0 +14.5 psi
• Nominal value (URL) = 1 bar (14.5 psi) (-1 bar) (-0.6 bar) (+1 bar)

Turn down:
• TD = URL / ⏐LRV⏐ = 1.67:1 3
set span:
4
• URV – LRV = 0.6 bar (8 psi)
This span is based on the zero point.
5
P01-PMx7xxxx-05-xx-xx-xx-008

Example: 1 bar (15 psi) measuring cell


1 Set span
2 Zero based span
3 Nominal value i Upper range limit (URL)
4 Nominal measuring range
5 Sensor measuring range
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value

Endress+Hauser 9
Cerabar S

Output
Output signal • 4...20 mA with superimposed digital communication protocol HART 5.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0)
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
• Digital communication signal FOUNDATION Fieldbus, 2-wire
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode

Signal range – 4 to 3.8 mA to 20.5 mA


20 mA HART

Signal on alarm As per NAMUR NE 43


• 4...20 mA HART
Options:
– Max. alarm*: can be set from 21 to 23 mA
– Keep measured value: last measured value is kept
– Min. alarm: 3.6 mA
* Factory setting: 22 mA
• PROFIBUS PA: can be set in the Analog Input block,
options: Last Valid Out Value, Fsafe Value (factory setting), Status bad
• FOUNDATION Fieldbus: can be set in the Analog Input Block,
options: Last good Value, Fail Safe Value (factory setting), Wrong Value

Load – 4 to 20 mA HART

1 R Lmax R Lmax £
U – 10.5 V 2 R Lmax R Lmax £
U – 11.5 V
23 mA 23 mA
[W] [W]
Test 1500 Test
1456
1282 1239

847 804
4
413 4
369
3 3

10.5 20 30 40 45 U 11.5 20 30 40 45 U
[V] [V]

U – 11 V U – 12 V
R Lmax R Lmax £ R Lmax R Lmax £
23 mA 23 mA
[W] [W]
1478 1434
1260 1217

826 782
5 5
391 347

11 20 30 40 45 U 12 20 30 40 45 U
[V] [V]
P01-PMx7xxxx-05-xx-xx-xx-003

Load diagram, observe the position of the jumper and the explosion protection. (→ 17, section "Measuring the 4 to 20
mA test signal" .)
1 Jumper for the 4 to 20 mA test signal inserted in "Non-test" position
2 Jumper for the 4 to 20 mA test signal inserted in "Test" position
3 Supply voltage 10.5 (11.5) to 30 V DC for 1/2 G, 1 GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia
4 Supply voltage10.5 (11.5) to 45 V DC for devices for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA,
FM XP, FM DIP, FM NI, CSA XP, CSA Dust-Ex, NEPSI Ex d
5 Supply voltage 11 (12) to 45 V DC for PMC71, Ex d[ia], NEPSI Ex d[ia]
RLmax Maximum load resistance
U Supply voltage

Note!
When operating via a handheld terminal or via PC with an operating program, a minimum communication
resistance of 250 Ω must exist within the loop.

10 Endress+Hauser
Cerabar S

Resolution • Current output: 1 μA


• Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)

Dynamic behavior Dead time, Time constant (T63)


current output

I
100 %
90 %

63 %

t1 t2 t

P01-xxxxxxxx-05-xx-xx-xx-007

Presentation of the dead time and the time constant

Type Dead time t1 Time constant (T63), t2

PMC71 90 ms 120 ms

PMP71 45 ms • 400 mbar (6 psi) measuring cell: 70 ms


• measuring cells ≥ 1 bar (15 psi): 35 ms

PMP75 PMP71 + influence from the diaphragm seal

Dynamic behavior HART Dead time, Time constant (T63)


A typical parametrization for the PLC of 3 to 4 values per second results in the following total dead time:

Type Dead time t1 Time constant (T63), t2

PMC71 90 ms 120 ms

PMP71 45 ms • 400 mbar (6 psi) measuring cell: 70 ms


• measuring cells ≥ 1 bar (15 psi): 35 ms

PMP75 PMP71 + influence from the diaphragm seal

Reading cycle
• HART commands: on average 3 to 4 per second on average.
The Cerabar S commands the BURST MODE functionfor cyclic value transmission via the HART
communication protocol.

Response time
≤ 250 ms

Cycle time (Update time)


On average 250 to 330 ms.

Endress+Hauser 11
Cerabar S

Dynamic behavior Dead time, Time constant (T63)


PROFIBUS PA
A typical cyclic parametrization for the PLC of 20 values per second results in the following total dead time:

Type Dead time t1 Time constant (T63), t2

PMC71 340 ms 120 ms

PMP71 295 ms • 400 mbar (6 psi) measuring cell: 70 ms


• measuring cells ≥ 1 bar (15 psi): 35 ms

PMP75 PMP71 + influence from the diaphragm seal

Response time
• cyclic: approx. 10 ms per request
• acyclic: < 50 ms
All values are typical values.

Cycle time (Update time)


The cycle time in a bus segment in cyclic data communication depends on the number of devices, on the
segment coupler used and on the internal PLC cycle time.

Dynamic behavior Dead time, Time constant (T63)


FOUNDATION Fieldbus
If the macro cycle time (Hostsystem) is set to a typical value of 250 ms, the following total dead time results:

Type Dead time t1 Time constant (T63), t2

PMC71 340 ms 120 ms

PMP71 295 ms • 400 mbar (6 psi) measuring cell: 70 ms


• measuring cells ≥ 1 bar (15 psi): 35 ms

PMP75 PMP71 + influence from the diaphragm seal

Reading cycle
• cyclic: up to 5/s, dependent on the number and type of function blocks used in a closed-control loop
• acyclic: 10/s

Response time
• cyclic: < 80 ms
• acyclic: < 40 ms
All values are typical values.

Cycle time (Update time)


250 ms

Damping A damping affects all outputs (output signal, display).


• Via on-site display, handheld terminal or PC with operating program, continuous from 0 to 999 s
• Additionally for HART and PROFIBUS PA: via DIP-switch on the electronic insert, switch position
"on" = set value and "off"
• Factory setting: 2 s

12 Endress+Hauser
Cerabar S

Data of the FOUNDATION Basic Data


Fieldbus interface
Device Type 1007F (hex)

Device Revision 06 (hex)

DD Revision 01 (hex)

CFF Revision 01 (hex)

ITK Version 5.0

ITK-Certification Driver-No. IT054600

Link-Master (LAS) cabable yes

Link Master / Basic Device selectable yes; Default: Basic Device

Number VCRs 44

Number of Link-Objects in VFD 50

Virtual communication references (VCRs)

Permanent Entries 44

Client VCRs 0

Server VCRs 5

Source VCRs 8

Sink VCRs 0

Subscriber VCRs 12

Publisher VCRs 19

Link Settings

Slot time 4

Min. Inter PDU delay 12

Max. response delay 10

Transducer Blocks

Block Content Output values

TRD1 Block contains all parameters related to the measurement • Pressure or level (channel 1)
• Process temperature (channel 2)

Service Block contains service information • Pressure after damping (channel 3)


• Pressure drag indicator (channel 4)
• Counter for max. pressure transgres-
sion (channel 5)

Diagnostic Block contains diagnostic information Error code via DI channels (channel 0 to
16)

Display Block contains parameters to configure the local display no output values

Endress+Hauser 13
Cerabar S

Function Blocks

Block Content Number of Execution Functionality


Function Blocks time

Resource Block The Resource Block contains all the data that enhanced
uniquely identifies the field device. It is an elec-
tronic version of a nameplate of the device.

Analog Input The AI block takes the manufacturer's input data, 45 ms enhanced
Block 1 selected by channel number, and makes it avail-
Analog Input able to other function blocks at its output.
Block 2 Enhancement: digital outputs for process alarms,
fail safe mode

Digital Input This block contains the discrete data of the diag- 40 ms standard
Block nose block (selectable via a channel number 0 to
16) and provides them for the blocks at the out-
put.

Digital Output This block converts the discrete input and thus 60 ms standard
Block initiates an action (selectable via a channel num-
ber) in the dp flow block or in the service block.
Channel 1 resets the counter for max. pressure
transgressions..

PID Block The PID block serves as proportional-integral- 120 ms standard


derivative controller and is used almost universally
to do closed-loop-control in the field including
cascade and feedforward. Input IN can be indi-
cated on the display. The selection is performed in
the display block
(DISPLAY_MAIN_LINE_CONTENT).

Arithmetic Block This block is designed to permit simple use of pop- 50 ms standard
ular measurement math functions. The user does
not have to know how to write equations. The
math algorithm is selected by name, chosen by the
user for the function to be done.

Input Selector The input selector block provides selection of up 35 ms standard


Block to four inputs and generates an output based on
the configured action. This block normally
receives its inputs from AI blocks. The block per-
forms maximum, minimum, middle, average and
‘first good’ signal selection. INPUT IN1 to IN4 can
be indicated on the display. The selection is per-
formed in the display block
(DISPLAY_MAIN_LINE_CONTENT).

Signal Charac- The signal characterizer block has two sections, 30 ms standard
terizer Block each with an output that is a non-linear function
of the respective input. The non-linear function is
determined by a single look-up table with 21 arbi-
trary x-y pairs.

Integrator Block The Integrator Function Block integrates a vari- 35 ms standard


able as a function of the time or accumulates the
counts from a Pulse Input block. The block may
be used as a totalizer that counts up until reset or
as a batch totalizer that has a setpoint, where the
integrated or accumulated value is compared to
pre-trip and trip settings, generating discrete
signals when these settings are reached.

Analog Alarm This block contains all process alarm conditions 35 ms standard
Block (working like a comparator) and represents them
at the output.

Additional Function Block informations:

Instantiate Function Block YES

Number of instantiate blocks 15

14 Endress+Hauser
Cerabar S

Power supply
Electrical connection Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
→ 90 ff, sections "Safety Instructions" and "Installation/Control Drawings".
• Devices with integrated overvoltage protection must be earthed. → 29.
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.

4...20 mA HART

1 6 10.5 V DC
7 11.5 V DC

4 to 20 mA
Test

Test

2 4... 20mA Test

3 5
8
4 to 20mA Test

4
P01-xMx7xxxx-04-xx-xx-xx-001

Electrical connection 4 to 20 mA HART


1 Housing
2 Jumper for 4 to 0 mA test signal
→ 17, section "Measuring the 4 to 20 mA test signal".
3 Internal earth terminal
4 External earth terminal
5 4 to 20 mA test signal between plus and test terminal
6 Minimum supply voltage 10.5 V DC, if the jumper is inserted in accordance with the illustration.
7 Minimum supply voltage 11.5 V DC, if the jumper is inserted in "Test" position.
8 Devices with integrated overvoltage protection are labelled OVP (overvoltage protection) here (→ 29).

PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA034S
"Guidelines for planning and commissioning PROFIBUS DP/PA" and the PNO Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA034S
Guidelines for planning and commissioning PROFIBUS DP/PA", PNO Guideline 2.092 "
PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).

Endress+Hauser 15
Cerabar S

FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA013S
"FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA013S "FOUNDATION
Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).

Devices with Harting plug Han7D

+
+ –
– 8
7
6
1
2 5
Han7D 3 4

+–
P01-PMx7xxxx-04-xx-xx-xx-001

Left: electrical connection for devices with Harting plug Han7D


Right: view of the plug connector at the device

Devices with M12 plug

+ – – +

M12

+– P01-PMx7xxxx-04-xx-xx-xx-000

Left: electrical connection for devices with M12 plug


Right: view of the plug at the device

Endress+Hauser offers for devices with M12 plug the following accessories:
Plug-in jack M 12x1, straight
• Material: Body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: Body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 51006327
Cable 4x0.34 mm2 with M12 socket, elbowed, screw plug, 5 m length
• Material: Body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP67
• Order number: 52010285

16 Endress+Hauser
Cerabar S

Devices with 7/8" plug


+ –

7/8” +

+–
P01-xxx7xxxx-04-xx-xx-xx-003

Left: electrical connection for devices with 7/8" plug


Right: view of the plug at the device

Cabel gland

Approval Typ Clamping range

Standard, II1/2G Exia, IS Plastic M20x1.5 5 to 10 mm (0.2 to 0.4")

ATEX II1/2D, II1/3D,


II1/2GD Exia, II1GD Exia Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.3 to 0.4")
II3G Ex nA

Terminals
for wire cross-sections of 0.5 to 2.5 mm2 (20 to 14 AWG)

Measuring the 4 to 20 mA test signal


A 4 to 20 mA signal may be measured via the positive and test terminal without interrupting the measurement.
The minimum supply voltage of the device can be reduced by simply changing the position of the jumper. As
a result, operation is also possible with lower voltage sources. Observe the position of the jumper in accordance
with the following table.

Jumper position for test signal Description

– Measuring the 4 to 20 mA test signal via plus and test terminal:


Test possible. (Thus, the output current can be measured without
interruption via the diode.)
– Delivery status
– minimum supply voltage: 11.5 V DC

– Measuring the 4 to 20 mA test signal via plus and test terminal:


Test not possible.
– minimum supply voltage: 10.5 V DC

Endress+Hauser 17
Cerabar S

Supply voltage Note!


• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
• All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
→ 90 ff sections "Safety Instructions" and "Installation/Control Drawings".

4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position (delivery status):
11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position: 10.5 to 45 V DC

PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC

FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC

Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21

Cable entry → 77 ff, feature 30 "Ordering information".

Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables.


• Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable external diameter: 5 to 9 mm (0.2 to 0.4")

Residual ripple Without influence on 4 to 20 mA signal up to ± 5% residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]

Influence of power supply ≤ 0.0006% of URL/1 V

18 Endress+Hauser
Cerabar S

Performance characteristics – general


Reference operating • As per IEC 60770
conditions • Ambient temperature TU = constant, in the range of: +21 to +33°C (+69.8 to +91.4°F)
• Humidity ϕ = constant, in the range of: 5 to 80 % r.H
• Ambient pressure pU = constant, in the range of: 860 to 1060 mbar (12.5 to 15 psi)
• Position of the measuring cell: constant, in the range of: ±1°
• Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value
• Zero based span
• Process isolating diaphragm material PMC71: Al2O3 (Aluminum oxide ceramic)
• Process isolating diaphragm material PMP71 and PMP75: AISI 316L SS/1.4435
• Filling oil PMP71 and PMP75: silicone oil
• Supply voltage: 24 V DC ± 3 V DC
• Load with HART: 250 Ω

Uncertainty of measurement The smallest extended uncertainty of measurement that can be returned by our standards is:
for small absolute pressure • 0.4% of the set span in the range of 1 to 30 mbar (0.01 to 0.4 psi) and
ranges • 1% of the set span in the range < 1 mbar (0.01psi).

Long-term stability PMC71/PMP75:


• For measuring ranges ≥ 1 bar (15 psi): ± 0.05 % of URL/year
PMC71:
• 100 mbar to 40 bar (1.5 to 580 psi): ±0.2 % of URL/10 years
• 100 mbar to 40 bar (1.5 to 580 psi), absolute pressure sensor: ±0.3 % of URL/10 years

PMP71 gauge pressure sensors:


1 year 5 years 10 year

Measuring range, bar % of URL

1 (15 psi) ±0.020 ±0.080 ±0.180

10 (150 psi) ±0.025 ±0.050 ±0.075

40 (600 psi) ±0.025 ±0.075 ±0.100

100 (1500 psi) ±0.050 ±0.150 ±0.200

400 (6000 psi) ±0.05 -- ±1

Influence of the installation • PMC71 1: ≤ 0.18 mbar


position • PMP71 1, 2
– Process connections thread G 1 A, G 1 1/2, G 2, 1 1/2 MNPT, 2 MNPT, M44x1.25, EN/DIN, ANSI and
JIS flanges: ≤ 10 mbar (0.15 psi)
– Process connections thread: G 1/2, 1/2 MNPT, JIS G 1/2, JIS R 1/2, M20x1.5: ≤ 4 mbar (0.06 psi)

1) Device rotated 180°, process connection pointing upwards.


2) This value is doubled for devices with inert oil.

Note!
Position-dependent zero shift can be corrected. → 24, section "General installation instructions" and → 74
ff section "Installation instructions".

Endress+Hauser 19
Cerabar S

Performance characteristics – ceramic process isolating


diaphragm
Reference accuracy – PMC71 The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and
non-reproducibility as per IEC 60770. The data refer to the calibrated span.

Measuring cell Gauge pressure sensor Absolute pressure sensor

% of the set span

• TD 1:1 to TD 10:1 = ±0.075 • TD 1:1 to TD 5:1 = ±0.075


100 mbar (1.5 psi)
• TD > 10:1 = ±0.0075 x TD • TD > 5:1 = ±0.015 x TD

• TD 1:1 to TD 15:1 = ±0.075 • TD 1:1 to TD 10:1 = ±0.075


250 mbar (4 psi)
• TD > 15:1 = ±0.005 x TD • TD > 10:1 = ±0.0075 x TD

400 mbar, 1 bar, 2 bar,


• TD 1:1 to TD 15:1 = ±0.075 • TD 1:1 to TD 15:1 = ±0.075
4 bar, 10 bar
• TD > 15:1 = ±0.005 x TD • TD > 15:1 = ±0.005 x TD
(6, 15, 30, 60, 150 psi)

• TD 1:1 to TD 10:1 = ±0.075 • TD 1:1 to TD 10:1 = ±0.075


40 bar (600 psi)
• TD > 10:1 = ±0.0075 x TD • TD > 10:1 = ±0.0075 x TD

Platinum version:
1 bar, 2 bar, 4 bar, 10 bar • TD 1:1 = ±0.05 • TD 1:1 = ±0.05
(15, 30, 60, 150 psi)

Total performance – PMC71 The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as
well as the thermal change of the zero point.

Measuring cell PMC71 PMC71 High temperature version

% of URL

100 mbar, 250 mbar, 400 mbar


±0.2 ±0.46
(1.5, 4, 6 psi)

1 bar, 2 bar, 4 bar, 10 bar, 40 bar


±0.15 ±0.46
(15, 30, 60, 150, 600 psi)

All specifications apply to the temperature range –10 to +60°C (+14 to +140°F).

Total Error - PMC71 The total error comprises the long-term stability and the total performance:

Measuring cell PMC71 PMC71 High temperature version

% of URL/year

100 mbar, 250 mbar, 400 mbar


±0.25 ±0.51
(1.5, 4, 6 psi)

1 bar, 2bar, 4 bar, 10 bar, 40 bar


±0.2 ±0.51
(15, 30, 60, 150, 600 psi)

Warm-up period – PMC71 • 4 to 20 mA HART : < 10 s


• PROFIBUS PA: 6 s
• FOUNDATION Fieldbus: 50 s

20 Endress+Hauser
Cerabar S

Thermal change of the zero PMC71


output and the output span –
PMC71 Measuring cell –10 to +60°C –20 to –10°C, +60 to +125°C
(+14 to +140°F) (–4 to +14°F, +140 to +257°F)

% of the set span

100 mbar, 250 mbar, 400 mbar


±(0.088 x TD + 0.088) ±(0.138 x TD + 0.138)
(1.5, 4, 6 psi)

1 bar, 2bar, 4 bar, 10 bar, 40 bar


±(0.088 x TD + 0.04) ±(0.175 x TD + 0.075)
(15, 30, 60, 150, 600 psi)

PMC71 High temperature version

Measuring cell –10 to +60°C –20 to –10°C, +60 to +150°C


(+14 to +140°F) (–4 to +14°F, +140 to +302°F)

% of the set span

100 mbar, 250 mbar, 400 mbar


±(0.088 x TD + 0.088) ⎯
(1.5, 4, 6 psi)

1 bar, 2bar, 4 bar, 10 bar, 40 bar


±(0.088 x TD + 0.04) ±(0.50 x TD)
(15, 30, 60, 150, 600 psi)

100 mbar (Absolute pressure sensor)


⎯ ±(1.25 x TD)
(1.5 psi)

250 mbar, 400 mbar, 1 bar, 2 bar,


4 bar, 10 bar (Absolutdrucksensor) ⎯ ±(0.75 x TD)
(4, 6, 15, 30, 60, 150 psi)

40 bar (Absolute pressure sensor)


⎯ ±(0.50 x TD)
(600 psi)

Endress+Hauser 21
Cerabar S

Performance characteristics – metallic process isolating


diaphragm
Reference accuracy – The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and
PMP71, PMP75 non-reproducibility as per IEC 60770. The data refer to the calibrated span.

Measuring Sensor without capillary with capillary


cell (PMP71 and PMP75) (only PMP75)

% of the set span

400 mbar Gauge pressure/ • TD 1:1 = ±0.15 • TD 1:1 = ±0.15


(6 psi) Absolute pressure • TD > 1:1 = ±0.15 x TD • TD > 1:1 = ±0.15 x TD

Gauge pressure/ • TD 1:1 to TD 2.5:1 = ±0.075 • TD 1:1 to TD 2.5:1 = ±0.1


1 bar (15 psi)
Absolute pressure • TD > 2.5:1 = ±0.03 x TD • TD > 2.5:1 = ±0.04 x TD

• TD 1:1 to TD 5:1 = ±0.075 • TD 1:1 to TD 2.5:1 = ±0.1


2 bar (30 psi) Gauge pressure
• TD > 5:1 = ±0.015 x TD • TD > 2.5:1 = ±0.04 x TD

• TD 1:1 to TD 5:1 = ±0.075 • TD 1:1 to TD 5:1 = ±0.075


2 bar (30 psi) Absolute pressure
• TD > 5:1 = ±0.015 x TD • TD > 5:1 = ±0.015 x TD

Gauge pressure/ • TD 1:1 to TD 10:1 = ±0.075 • TD 1:1 to TD 10:1 = ±0.075


4 bar (60 psi)
Absolute pressure • TD > 10:1 = ±0.0075 x TD • TD > 10:1 = ±0.0075 x TD

10 bar, 40 bar Gauge pressure/ • TD 1:1 to TD 15:1 = ±0.075 • TD 1:1 to TD 15:1 = ±0.075
(150, 600 psi) Absolute pressure • TD > 15:1 = ±0.005 x TD • TD > 15:1 = ±0.005 x TD

100 bar Gauge pressure/ • TD 1:1 to TD 10:1 = ±0.075 • TD 1:1 to TD 10:1 = ±0.075
(1500 psi) Absolute pressure • TD > 10:1 = ±0.0075 x TD • TD > 10:1 = ±0.0075 x TD

400 bar Gauge pressure/ • TD 1:1 to TD 5:1 = ±0.15 • TD 1:1 to TD 5:1 = ±0.15
(6000 psi) Absolute pressure • TD > 5:1 = ±0.03 x TD • TD > 5:1 = ±0.03 x TD

700 bar • TD 1:1 to TD 5:1 = ±0.15


(10,150 psi) Absolute pressure • TD > 5:1 = ±0.03 x TD ⎯
(only PMP71)

Platinum Gauge pressure/ • TD 1:1 = ±0.05


version 1) Absolute pressure
1, 2 , 4, 10,
40, 100 bar ⎯
(15, 30, 60,
150, 600,
1500 psi)

1) Platinum version not for flush-mounted process connections G 1/2 and M20.

Total performance – PMP71 The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as
well as the thermal change of the zero point.

Measuring cell PMP71 PMP71 with Gold-Rhodium-coated


process isolating diaphragm

% of URL

400 mbar (6 psi) ±0.25 ±1.25

1 bar (15 psi) ±0.15 ±0.75

2 bar (30 psi) ±0.15 ±0.45

4 bar (60 psi) ±0.15 ±0.3

10, 40 bar (150, 600 psi) ±0.15 ±0.15

100 bar (1500 psi) ±0.25 ±0.25

400 bar (6000 psi) ±0.3 ±0.3

700 bar (10,150 psi) ±0.3 ±0.3

All specifications apply to the temperature range –10 to +60°C (+14 to +140°F).

22 Endress+Hauser
Cerabar S

Total Error - PMP71 The total error comprises the long-term stability and the total performance:

Measuring cell % of URL/year

400 mbar (6 psi) • ±0.3

1 bar, 2 bar, 4 bar, 10 bar, 40 bar • ±0.2


(15, 30, 60, 150, 600 psi)

100 bar (1500 psi) • ±0.3

400 bar (6000 psi) • ±0.35

700 bar (10,150 psi) • ±0.35

Warm-up period – • 4 to 20 mA HART : < 10 s


PMP71, PMP75 • PROFIBUS PA: 6 s
• FOUNDATION Fieldbus: 50 s

Thermal change of the zero PMP71 and PMP75 (basic device)


output and the output span –
PMP71 and PMP75 Measuring cell –10...+60 °C –40...–10 °C, +60...+85 °C
(+14...+140°F) (–40...+14°F, +140...+185°F)

% of the set span

400 mbar (6 psi) ±(0.2 x TD + 0.015) ±(0.4 x TD + 0.03)

1 bar, 2 bar, 4 bar, 10 bar, 40 bar ±(0.1 x TD + 0.01) ±(0.4 x TD + 0.02)


(15, 30, 60, 150, 600 psi)

100 bar (1500 psi) ±(0.2 x TD + 0.015) ±(0.4 x TD + 0.03)

400 bar (6000 psi) ±(0.35 x TD + 0.02) ±(0.7 x TD + 0.04)

700 bar (10,150 psi) ±(0.35 x TD + 0.02) ±(0.7 x TD + 0.04)

Note!
When using a PMP75, the influence from the respective diaphragm seal must be taken into account.
(→ 68 ff "Planning instructions, diaphragm seal systems" and → 47 ff "Process connections PMP75 (with
metallic process isolating diaphragm)").

Endress+Hauser 23
Cerabar S

Operating conditions (installation)


General installation • For PMP75: → 74, "Installation instructions" section.
instructions • The position-dependent zero shift can be corrected directly at the device via operating key, for devices with
external operation even in hazardous areas. Diaphragm seals also shift the zero point, depending on the
installation position.
(→ 74 ff, section "Installation instructions").
• The housing of the Cerabar S can be rotated up to 380°. → 27, section "Turn the housing".
• Endress+Hauser offers a mounting bracket for installing on pipes or walls. → 25, section "Wall and pipe-
mounting".

Installation instructions for Cerabar S transmitters without diaphragm seal are mounted as per the norms for a manometer (DIN EN 837-
devices without diaphragm 2). We recommend the use of shut-off devices and siphons. The orientation depends on the measuring
seal – PMC71 and PMP71 application.

Pressure measurement in gases


• Mount Cerabar S with shut-off device above the tapping point so that condensate can flow into the process.

Pressure measurement in steams


• Mount Cerabar S with siphon above the tapping point.
The siphon reduces the temperature to almost ambient temperature.
• Fill the siphon with fluid before commissioning.

Pressure measurement in liquids


• Mount Cerabar S with shut-off device below or at the same level as the tapping point.

Level measurement
• Mount Cerabar S below the lowest measuring point.
• Do not mount the device at the following positions:
In the fill flow, in the tank outlet or at a point in the container which could be affected by pressure pulses
from an agitator or a pump.
• The calibration and functional test can be carried out more easily if you mount the device after a shut-off
device.

Heat insulation – The PMC71 high temperature version and the PMP75 must only be insulated up to a certain height. The
PMC71 high temperature maximum permitted insulation height is labelled on the devices and applies to an insulation material with a
version and PMP75 heat conductivity ≤ 0.04 W/(m x K) and to the maximum permitted ambient and process temperature (→ see
table below). The data were determined under the most critical application "quiescent air".

l £ 0.04 W
TA m•K

TP
P01-PMx7xxxx-11-xx-xx-xx-010

Maximum insulation height, here e.g. PMC71 with flange

PMC71 high temperature version PMP75

Ambient temperature (TA) ≤ 70°C (158°F) ≤ 70°C (158°F)

Process temperature (TP) ≤ 150°C (302°F) max. 350°C (662°F), depending on the
diaphragm seal filling oil used (→ 69)

24 Endress+Hauser
Cerabar S

Mounting with temperature Endress+Hauser recommends the use of temperature isolators in the event of constant extreme fluid
isolator temperatures which lead to the maximum permissible ambient temperature of +85°C (+185°F) being
exceeded. Depending on the filling oil used, Cerabar S devices with temperature isolators can be used for
maximum temperatures of up to 260°C (+500°F). → For the temperature application limits of filling oils,
→ 69, "Diaphragm seal filling oil" section.
To minimize the influence of rising heat, Endress+Hauser recommends the device be mounted horizontally or
with the housing pointing downwards.
The additional installation height also brings about a zero point shift of maximum 21 mbar (0.3 psi) due to the
hydrostatic columns in the temperature isolator. The position-dependent zero shift can be corrected.

max.
4.53”
(115)
P01-PMx7xxxx-11-xx-xx-xx-005

PMP75 with temperature isolator

Wall and pipe-mounting Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. → 77 ff, feature 110,
"Additional options 2".

3.98”
(101)

4.65”
(118)

4.65”
(70)
P01-PMx7xxxx-06-xx-xx-xx-001

Endress+Hauser 25
Cerabar S

"Remote housing" version With the "remote housing" version, you are able to mount the housing with the electronics insert at a distance
from the measuring point. This facilitates zero-interference measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or difficult to
access)
• If rapid cleaning of the measuring point is required
• If the measuring point is exposed to vibrations.
You can choose between different cable versions:
• PE (2 m, 5 m and 10 m / 6, 16, 33 feet)
• FEP (5 m / 16 feet).
→ 77 ff, Feature 110, "Additional options 2", Version "G".
For the dimensions, → 60.

4
IP xx
FEP cable: (see chapter
IP 69K “Ordering information”)
IP 66/68 NEMA 4/6P 3
PE cable:
IP 66/68 NEMA 4/6P
r ³ 4.72”
1
(120 mm)
2

P01-PMx7xxxx-11-xx-xx-en-012

In the case of the "remote housing" version, the sensor is delivered with the process connection and cable ready mounted.
The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both ends. These
sockets are simply connected to the housing and the sensor.
1 Process connection with sensor
2 Cable, both ends are fitted with a socket
3 Mounting bracket provided, suitable for pipe and wall mounting
4 Housing with electronic insert

Degree of protection for the process connection with sensor with the use of
• FEP cable:
– IP 69K
– IP 66 (NEMA 4/6P)
– IP 68 (1.83 mH2O for 24 h), NEMA 4/6P
• PE cable:
– IP 66 (NEMA 4/6P)
– IP 68 (1.83 mH2O for 24 h), NEMA 4/6P
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 inch)
• Cable extraction force: max. 450 N (101 lbf)
• Resistance to UV light
Use in hazardous area:
• Intrinsically safe installations (Ex ia/IS)
• FM/CSA IS: for Div.1 installatin only

26 Endress+Hauser
Cerabar S

Turn the housing The housing can be rotated up to 380° after loosening the Allen screw.
Your benefits
• Simple mounting by optimally aligning the housing
• Good, accessible device operation
• Optimum readability of the on-site display (optional).

FIELD TERMINALS
max. 380°

P01-PMx7xxxx-17-xx-xx-xx-000

Align the housing by loosening the Allen screw.


T14 housing: 2 mm Allen key; T17 housing: 3 mm Allen key

Oxygen applications Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other things, the
following precautions must be taken:
– All components of the system, such as measuring devices, must be cleaned in accordance with the BAM
(DIN 19247) requirements.
– Dependent on the materials used, a certain maximum temperature and a maximum pressure for oxygen
applications must not be exceeded.
The devices suitable for gaseous oxygen applications are listed in the following table with the specification pmax.

Order code for devices cleaned for pmax for oxygen applications Tmax for oxygen
oxygen applications applications

PMC71 – * * * ** * ** 2 * *, Overpressure limit (OPL) of sensor1, 2 60°C (140°F)


Devices with sensors,
nominal value < 10 bar (145 psi)

PMC71 – * * * ** * ** 2 * *, 30 bar (435 psi) 60°C (140°F)


Devices with sensors,
nominal value ≥ 10 bar (145 psi)

PMP71 – * * * ** * * ** N * * Depends on the weakest link in terms of 85°C (185°F)


pressure of the selected components: over
pressure limit (OPL) of sensor1 or process
connection (1.5 x PN) or filling fluid
(160 bar / 2320 psi)

PMP75 – * * * ** * * * ** N * * Depends on the weakest link in terms of 85°C (185°F)


pressure of the selected components: over
pressure limit (OPL) of sensor1 or process
connection (1.5 x PN) or filling fluid
(160 bar / 2320 psi)

1) → 77 ff "Ordering information", feature 40 "Sensor range; sensor overload limit (= OPL)"


2) PMC71 with PVDF thread or flange pmax = 15 bar (225 psi)

Silicone-free applications Cleaning of the transmitter for the use e.g. in paint shops → 79 "Ordering information PMC71", feature 80
"Seal", version "L" and "M".

Ultra pure gas applications Endress+Hauser also offers the degreased device for special applications, such as ultra pure gas.
No special restrictions regarding the process conditions apply to this device.
→ 79, "Ordering information PMC71", feature 80 "Seal" or → 83, "Ordering information PMC71", feature
90 "Fill fluid".

Endress+Hauser 27
Cerabar S

Applications with hydrogen With regard to materials in which hydrogen build-up takes place, hydrogen atoms can diffuse through the metal
process isolating diaphragm. This can result in incorrect measurement results.
Endress+Hauser offers process isolating diaphragms with Gold-Rhodium coating for this application.
→ 82 "Ordering information PMP71" and → 86 "Ordering information PMP75", feature 60 "Membrane
material" version "6".

Operating conditions (environment)

Ambient temperature limits • PMC71:


– –40 to +85°C (–40 to +185°F)
– High temperature version: –20 to +70°C (–4 to +158°F)
(Version "T" for feature 100 "Additional options 1" or feature 110 "Additional options 2"),
→ For the maximum insulation height see → 25.
• PMP71: –40 to +85°C (–40 to +185°F)
devices for lower temperatures on request
• PMP75: –40 to +85°C (–40 to +185°F)
devices for lower temperatures on request
→ For the maximum insulation height see → 25.
• On-site display: –20 to +70°C (–4 to +158°F)
Extended temperature application range with restrictions in optical properties such as display speed and
contrast: –40 to +85°C (–40 to +185°F)
• Remote housing: –40 to +60°C (–40 to +140°F)
Note!
For high-temperature applications, either a PMP75 with a temperature isolator or with a capillary can be used.
If vibrations also occur in the application, Endress+Hauser recommends you use a PMP75 with a capillary. If
a PMP75 with a temperature isolator or capillary is used, we recommend a suitable retaining unit for mounting
(see "Wall and pipe-mounting" Section on → 25).

For devices for use in hazardous areas, see Safety instructions, Installation or Control Drawing. (→ 90,
sections "Safety Instructions" and "Installation/Control Drawings".)
The device can be used in this temperature range. The values of the specification, such as thermal change, may
be exceeded. → DIN 16086.

Storage temperature range • –40 to + 90°C (–40 to + 194°F)


• On-site display: –40 to +85°C (–40 to +185°F)
• Separate housing: –40 to +60°C (–40 to +140°F)

Degree of protection • → 77 ff, feature 30 "Housing, Cable entry, Protection".


• Degree of protection IP 68 for T17 housing: 1.83 mH2O for 24 h
• Seperate housing → 26.

Climate class Class 4K4H (air temperature: –20 to 55°C/–4 to +131°F, relative humidity: 4 to 100%) fulfilled as per
DIN EN 60721-3-4 (condensation possible)

1) With PMC71, avoid condensate in the device (avoid moisture collecting in the device).

28 Endress+Hauser
Cerabar S

Vibration resistance Device/Additional option Test standard Vibration resistance


1
PMC71 GL guaranteed for
3 to 25 Hz: ±1.6 mm (0.06");
PMP71 25 to 100 Hz: 4 g
PMP75 2, 3 in all 3 planes

with mounting bracket IEC 61298-3 guaranteed for


10 to 60 Hz: ±0.15 mm (0.006");
60 to 500 Hz: 2 g
in all 3 planes

1) not for high temperature version with Ex d[ia], CSA XP or FM XP


2) with aluminum T14 housing only
3) For applications with high temperatures, either a PMP75 with a temperature isolator or with a capillary can be used.
If vibrations also occur in the application, Endress+Hauser recommends using a PMP75 with a capillary. If a PMP75
with a temperature isolator or capillary is used, it must be mounted with a mounting bracket. (→ 25).

Electromagnetic compatibility • Electromagnetic compatibility to EN 61326 and NAMUR recommendation EMC (NE21). For details refer
to the declaration of conformity.
• With enhanced immunity against electromagnetic fields as per EN 61000-4-3:
30 V/m with closed cover 1
• Maximum deviation: < 0.5% of span
• All EMC measurements were performed with a turn down (TD) = 2:1.

1) for devices with T14 housing

Overvoltage protection • Overvoltage protection:


– Nominal functioning DC voltage: 600 V
– Nominal discharge current: 10 kA
• Surge current check î = 20 kA as per DIN EN 60079-14: 8/20 μs satisfied
• Arrester AC current check I = 10 A satisfied
→ 79 ff, feature 100 "Additional options 1" and feature 110 "Additional options 2", version "M Overvoltage
protection".
Note!
Devices with integrated overvoltage protection must be earthed.

Endress+Hauser 29
Cerabar S

Operating conditions (Process)

Process temperature limits PMC71 (with ceramic process isolating diaphragm)


• –25 to +125°C (–13 to +257°F)
• High temperature version: –20 to +150°C (–4 to +302°F)
→ 79, feature 100 "Additional options 1", Version "T".
• Observe the process temperature range of the seal. See also the following section "Process temperature range,
seals".

Extreme jumps in temperature can result in temporary measuring errors. Temperature compensation takes effect after several
minutes. Internal temperature compensation is faster the smaller the temperature jump and the longer the time interval.

PMP71 (with metallic process isolating diaphragm)

Description Temperature operating range

Process connections with internal process isolating diaphragm –40 to +125°C (–40 to +257°F)
(+150 °C/302°F for max. one hour)

Process connections with flush-mounted process isolating –40 to +100°C (–40 to +212°F)
diaphragm, G 1 A, G 1 1/2 A, G 2 A, 1 NPT, 1 1/2 NPT, 2 NPT,
M 44 x 1.25, EN/DIN, ANSI and JIS flanges

Process connections with flush-mounted process isolating –20 to +85°C (–4 to +185°F)
diaphragm, G 1/2 A, M 20

Lower temperatures on request.

PMP75 (with metallic process isolating diaphragm)


• depending on the diaphragm seal and filling oil from -70°C (-94°F) up to +400°C (+752°F). Observe the
temperature application limits of the diaphragm seal oil. → 69, section "Diaphragm seal filling oils".
Note!
• Do not use diaphragm seals with 0.09 mm (0.004") PTFE foil on AISI 316L SS(1.4435/1.4404) for vacuum
applications, upper temperature limit +204°C (+400°F).
• For oxygen applications, observe → 27, section "Oxygen applications".

30 Endress+Hauser
Cerabar S

Process temperature range, PMC71 (with ceramic process isolating diaphragm)


seals
Feature 80 in Seal Process temperature range
order code

A, L FKM Viton –25 to +125°C/150°C 1 (–13 to +257°F/302°F)

B , 2 3
EPDM (FDA 21CFR177.2600; 3A Class II; –20 to +125°C/150°C 1 (–4 to +257°F/302°F)
USP Class VI) DVGW (KTW, W270,
W534), WRAS, ACS, NSF61

B3 EPDM –20 to +125°C (–4 to +257°F)

D, M Kalrez, Compound 4079 +5 to +125°C/150°C 1 (+41 to +257°F/302°F)

E Chemraz, Compound 505 –10 to +125°C/150°C 1 (+14 to +257°F/302°F)

F 2, 4 HNBR (FDA 21CFR177.2600; 3A Class II; –25 to +125°C (–13 to +257°F)


KTW; AFNOR; BAM)

F4 NBR –10 to +100°C (+14 to +212°F)

G FKM Viton, FDA –5 to +125°C (+23 to +257°F)

1 FKM Viton, cleaned from oil and greace –10 to +125°C/150°C 1 (+14 to +257°F/302°F)

2 FKM Viton, cleaned for oxygen service –10 to +60 °C (+14 to +140°F)

The process temperature ranges specified here refer to permanent application of the PMC71. They may be exceeded for a
short time (e.g. for cleaning).

1) +150°C (+302°F): for high temperature version


→ 79, feature 100 "Additional options 1" and feature 110 "Additional options 2", Version "T".
2) These seals are used for devices with 3A-approved process connections.
3) With applications of saturated steam a Cerabar S with metallic process isolating diaphragm is to be used.
4) For devices with NBR or HNBR seals, the values for "Toatal Performance" (→ 20) and "Thermal change" (→ 21)
must be multiplied by the factor 3.

Pressure specifications • The maximum pressure for the measuring device is dependent on the lowest-rated element with regard to
pressure, see the following sections for this:
– → 7 ff, section "Measuring range"
– chapter "Mechanical construction".
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference
temperature of 20°C (68°F) or 100°F for ANSI flanges and may be applied to the device for an unlimited
time. Observe temperature dependency.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 18 1
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B 2220.
• The test pressure corresponds to the over pressure limit of the measuring instrument (Over Pressure Limits
OPL = 1.5 x MWP 2) and may fit only temporally limited, so that no permanent damage develops.
• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The abbreviation
"PS" corresponds to the MWP (maximum working pressure) of the measuring device.
• In the case of sensor range and process connections where the OPL (Over pressure limit) of the pressure
connection is smaller than the nominal value of the sensor, the device is set at the factory, at the very
maximum, to the OPL value of the process connection. If you want to use the entire sensor range, select a
process connection with a higher OPL value (1.5 x PN; PN = MWP).
• In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per → 27, "Oxygen
applications" may not be exceeded.

1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO
in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
2) The equation does not apply for PMP71 and PMP75 with a 40 bar (600 psi) or 100 bar (1500 psi) measuring cell.

Endress+Hauser 31
Cerabar S

Mechanical construction
Housing dimensions T14
5.98”
(152) 4.37” 4.37”
(111) (111)

FIELD TERMINALS
P01-PMx7xxx-06-00-xx-xx-000

Front view, left-hand side view, top view


→ See the process connection in question for installation height. Housing weight → 61.

Housing dimensions T17


5.98” 5.20”
(152) (132)
4.37” 4.37”
(111)
4.02” (111)
4.53”
(102) (115)
FIELD TERMINALS

P01-PMx7xxxx-06-00-xx-xx-001

Front view, left-hand side view, top view


→ See the process connection in question for installation height. Housing weight → 61.

32 Endress+Hauser
Cerabar S

Process connections PMC71 Note!


(with ceramic process Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
isolating diaphragm) (→ 77, feature 70 "Process connection") has to be ordered with a CSA approval ( → 77, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10525.5C.

Thread, internal process isolating diaphragm

1 G 1/2A 2 G 1/2A G 1/4 3 G 1/2A 11.4 mm

H H H

ø8 17 20 17 20 17 20
13

ø3 G 1/4 ø11.4
5
ø6 ø17.5 ø17.5
G 1/2 G 1/2 G 1/2
P01-PMC71xxx-06-09-xx-xx-001

Process connections PMC71, thread ISO 228


Installation height → 34.
1 Thread ISO 228 G 1/2 A EN 837;
Material version GA: AISI 316L, version GB: Alloy C276/2.4819, version GC: Monel,
Version GD: PVDF (max.: 15 bar/225 psi, max.: –10...+60°C/+14...+140°F); mount version "GD" with a mounting
bracket only (→ 25); Weight: 0.63 kg
2 Thread ISO 228 G 1/2 A G 1/4 (female);
Material version GE: AISI 316L, version GF: Alloy C276/2.4819, version GG: Monel; Weight: 0.63 kg
3 Thread ISO 228 G 1/2 A hole 11.4 mm;
Material version GH: AISI 316L, version GJ: Alloy C276/2.4819, version GK: Monel; Weight: 0.63 kg

1 1/2” MNPT 1/4” FNPT 2 1/2” MNPT 11.4 mm 3 1/2” MNPT 3 mm 4 1/2” FNPT

H H H H

0.98” 0.98” 0.98” 0.98”

ø0.45” ø0.45” ø0.12”


(3) 1/2” NPT
(11.4) (11.4)
1/2” NPT ø1.04”
1/4” NPT 1/2” NPT
(26.5)
1/2” NPT
P01-PMC71xxx-06-09-xx-xx-002

Process connections PMC71, thread ANSI


Installation height → 34.
1 Thread ANSI 1/2 MNPT 1/4 FNPT;
Material version RA: AISI 316L, version RB: Alloy C276/2.4819, version RC: Monel; Weight: 0.63 kg
2 Thread ANSI 1/2 MNPT hole 11.4;
Material version RD: AISI 316L, version RE: Alloy C276/2.4819, version RF: Monel; Weight: 0.63 kg
3 Thread ANSI 1/2 MNPT hole 3 mm;
Material version RG: PVDF(max.: 15 bar/225 psi, max.: –10...+60°C/+14...+140°F),
mount with mounting bracket only ( → 25); Weight: 0.63 kg
4 Thread ANSI 1/2 FNPT;
Material version RH: AISI 316L, version RJ: Alloy C276/2.4819, version RK: Monel; Weight: 0.63 kg

Endress+Hauser 33
Cerabar S

1 G 1/2 2 R 1/2

H
H

ø8 20 23
13.2

ø3 3 ø11.4
ø5 R 1/2
G 1/2
P01-PMC71xxx-06-09-xx-xx-003

Process connections PMC71, thread JIS


Installation height → 34.
1 Version GL: thread JIS B0202 G 1/2 (male), material: AISI 316L; Weight: 0.63 kg
2 Version RL: thread JIS B0203 R 1/2 (male), material: AISI 316L; Weight: 0.63 kg

M20x1.5

ø8 17 20

ø3
ø6 5
M20x1.5
P01-PMC71xxx-06-09-xx-xx-004

Process connections PMC71 thread DIN 13 M 20x1.5 hole 3 mm


Material version GP: AISI 316L, version GQ: Alloy C276/2.4819
Installation height → 34; Weight: 0.63 kg.

Installation height H for devices with thread connection and internal process isolating diaphragm

Description Housing T14 Housing T17

PMC71 155 mm (6.10") 171 mm (6.73")

PMC71 with Ex d[ia], CSA XP or FM XP 225 mm (8.86") 241 mm (9.41"), Ex d = 311 mm (12.2")

PMC71 High temperature version 1 235 mm (9.25") 251 mm (9.88")


1
PMC 71 High temperature version with 305 mm (12.0") 321 mm (12.6"), Ex d = 391 mm (15.4")
Ex d[ia], CSA XP or FM XP

1) High temperature version, → 79, feature 100 "Additional options 1" and
feature 110 "Additional options 2", versions "T"

34 Endress+Hauser
Cerabar S

Thread, flush-mounted process isolating diaphragm

1 G 1-1/2 2 G2

SW 60 SW 60
60 AF 60 AF

H H

25 28 30 33.5

G 1-1/2 G2
ø55 ø68

3 1-1/2” NPT 4 2” NPT 5 M44x1.25


SW 60 SW 60
SW 60 60 AF 60 AF
60 AF
H H
H

1.06” 1.32” 0.87”


(27) (33.5) (22)

ø1.59”
1 -1/2” NPT 2” NPT 1.18” 0.43”
(40.5)
ø2.68” (30) (11)
M44x1.25
(68)
P01-PMC71xxx-06-09-xx-xx-005

Process connections PMC71,


→ Installation height see table below.
1 Thread ISO 228 G 1 1/2 A;
Material version 1G: AISI 316L, version 1H: Alloy C276/2.4819, version 1J: Monel; Weight: 0.63 kg (1.4 lb)
2 Thread ISO 228 G 2 A;
Material version 1K: AISI 316L, version 1L: Alloy C276/2.4819, version 1M: Monel; Weight: 0.63 kg (1.4 lb)
3 Thread ANSI 1 1/2 MNPT;
Material version 2D: AISI 316L, version 2E: Alloy C276/2.4819, version 2F: Monel; Weight: 0.63 kg (1.4 lb)
4 Thread ANSI 2 MNPT;
Material version 2G: AISI 316L, version 2H: Alloy C276/2.4819, version 2J: Monel; Weight: 0.63 kg (1.4 lb)
5 Thread DIN 13 M 44x1.25;
Material version 1R: AISI 316L, version 1S: Alloy C276/2.4819; Weight: 0.63 kg (1.4 lb)

Installation height H for devices with thread connection and flush-mounted process isolating
diaphragm

Description Housing T14 Housing T17

PMC71/PMC71 high temperature version 215 mm (8.46") 231 mm (9.09")

PMC71/PMC71 high temperature version: 280 mm (11.0") 296 mm (11.7")


with Ex d[ia], CSA XP or FM XP

Endress+Hauser 35
Cerabar S

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527

H
g2
2
b

g
k
D
P01-PMC71xxx-06-09-xx-xx-006

Process connection PMC71, EN/DIN flange with raised face (flush-mounted process isolating diaphragm)
Installation height → 38.

Flange1 Bolt holes

Version Material Nominal Nominal Shape 2 Diameter Thick- Raised Quantity Diameter Bolt circle Flange
diameter pressure ness face weight 3

D b g g2 k

[mm] [mm] [mm] [mm] [mm] [kg]

CP AISI 316L DN 32 PN 10-40 B1 (D) 140 18 77 4 18 100 1.9

CQ AISI 316L DN 40 PN 10-40 B1 (D) 150 18 87 4 18 110 2.2

BR PVDF 4 DN 50 PN 10-16 B1 (D) 165 21.4 102 4 18 125 0.6

B3 AISI 316L DN 50 PN 10-40 B1 (D) 165 20 102 4 18 125 3.0

C3 AISI 316L DN 50 PN 63 B2 (D) 180 26 108 4 22 135 4.6


4
BS PVDF DN 80 PN 10/16 B1 (D) 200 21.4 138 8 18 160 1.0

B4 AISI 316L DN 80 PN 10-40 B1 (D) 200 24 138 8 18 160 5.4

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation in brackets as per DIN 2527
3) Housing weight → 61
4) Max.: 15 bar (225 psi), max.: –10 to +60°C (+14 to +140°F)

36 Endress+Hauser
Cerabar S

ANSI flange, connection dimensions as per ANSI B 16.5, raised face RF

0.06” H
(1.6) g2

g
k
D
P01-PMC71xxx-06-09-xx-xx-007

Process connection PMC71, ANSI flange with raised face (flush-mounted process isolating diaphragm)
Installation height → 38.

Flange 1 Bolt holes

Version Material Nominal Class Diameter Thickness Raised face Quantity Diameter Bolt circle Flange
diameter weight 2

D b g g2 k

inches lb./sq.in in (mm) in (mm) in (mm) in (mm) in (mm) lbs (kg)

AE AISI 316/316L 3 1-1/2 150 5 (127) 0.69 (17.5) 2.88 (73.2) 4 0.62 (15.7) 3.88 (98.6) 2.2 (1.0)
3
AQ AISI 316/316L 1-1/2 300 6.12 (155.4) 0.81 (20.6) 2.88 (73.2) 4 0.88 (22.4) 4.5 (114.3) 5.7 (2.6)

AF AISI 316/316L 3 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)

JR ECTFE 4 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)
5
A3 PVDF 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 1.1 (0.5)
3
AR AISI 316/316L 2 300 6.5 (165.1) 0.88 (22.4) 3.62 (91.9) 8 0.75 (19.1) 5 (127) 7.1 (3.2)

AG AISI 316/316L 3 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)

JS ECTFE 4 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)
5
A4 PVDF 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 2.0 (0.9)
3
AS AISI 316/316L 3 300 8.25 (209.5) 1.12 (28.4) 5 (127) 8 0.88 (22.4) 6.62 (168.1) 15 (6.8)

AH AISI 316/316L 3 4 150 9 (228.6) 0.94 (23.9) 6.19 (157.2) 8 0.75 (19.1) 7.5 (190.5) 16 (7.1)

JT ECTFE 4 4 150 9 (228.6) 0.94 (23.9) 6.19 (157.2) 8 0.75 (19.1) 7.5 (190.5) 16 (7.1)
3
AT AISI 316/316L 4 300 10 (254) 1.25 (31.8) 6.19 (157.2) 8 0.88 (22.4) 7.88 (200.2) 26 (11.6)

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30μin (0.8 μm). Lower surface roughness on request.
2) Housing weight → 61
3) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
4) ECTFE coating on AISI 316L SS/1.4435
When operating in hazardous area, avoid electrostatic charge of the plastic surface.
5) max.: 15 bar (225 psi), max.: –10 to +60°C (+14 to +140°F)

Endress+Hauser 37
Cerabar S

JIS flange, connection dimensions as per JIS B 2220 BL, raised face RF

H
g2
2
b

g
k

D
P01-PMC71xxx-06-09-xx-xx-008

Process connection PMC71, JIS flange with raised face RF (flush-mounted process isolating diaphragm), AISI 316L/
1.4435
→ Installation height see table below.

Flange 1 Boltholes

Versions Nominal Nominal Diameter Thickness Raised face Quantity Diameter Hole circle Flange
dimension pressure weight 2

D b g g2 k

[mm] [mm] [mm] [mm] [mm] [kg]

KF 50 A 10 K 155 16 96 4 19 120 2.0

KL 80 A 10 K 185 18 127 8 19 150 3.3

KH 100 A 10 K 210 18 151 8 19 175 4.4

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8. Lower surface roughness on request.
2) Housing weight see → 61

Installation height H for devices with flange

Description T14 housing T17 housing

PMC71 215 mm (8.46") 231 mm (9.09")

PMC71 with Ex d[ia], CSA XP or FM XP 280 mm (11.0") 296 mm (11.7")

38 Endress+Hauser
Cerabar S

Hygienic connections, flush-mounted process isolating diaphragm


Note!
Many process connections with an EPDM or HNBR seal are in accordance with the 3A-sanitary standard
approved for PMC71. This means that a 3A-approved process connection in combination with an EPDM or
HNBR seal must be selected when ordering for the 3A approval for the PMC71 version to be valid.
→ For ordering information on EPDM or HNBR seals, → 79 "Ordering information PMC71", feature 80
"Sensor seal", version B or F.

1 DIN 11851 DN 40

2 DIN 11851 DN 50
H
H

21 10 22 11

ø48 ø61
Rd 65 x 1/6 Rd 78 x 1/6

3 Clamp ISO 2852 DN 51 (2")/ 4 Clamp ISO 2852 DN 76.1 (3")


DIN 32676 DN 50

H
H

ø 2.22” ø 3.29”
(56.5) (83.5)
ø 2.52” ø 3.58”
(64) (91)

5 DRD 65 mm 6 Varivent N DN 40 – DN 162


H
4 x ø11.5 H

16
ø 2.68”
ø65 (68)
ø84 ø 3.31”
ø105 (84)

P01-PMC71xxx-06-09-xx-xx-011

Process connections PMC71, Hygienic connections, material AISI 316L


surface roughness of the surfaces in contact with the medium ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on
request.
1 Version MP: DIN 11851 DN 40 PN 25, 3A with HNBR or EPDM seal
2 Version MR: DIN 11851 DN 50 PN 25, 3A with HNBR or EPDM seal
3 Version TD: Tri-Clamp ISO 2852 (2"), DIN 32675 DN 50, 3A with HNBR or EPDM seal
4 Version TF: Tri-Clamp ISO 2852 (3"), 3A with HNBR or EPDM seal
5 Version TK: DRD DN50 (65 mm) PN 25, 3A with HNBR or EPDM seal
6 Version TR: Varivent Type N for pipes 40 – 162, PN 40, 3A with HNBR or EPDM seal

Installation height H for devices with hygienic connection and flush-mounted process isolating
diaphragm

Description T14 housing T17 housing

PMC71/PMC71 high temperature version 215 mm (8.46") 231 mm (9.09")

PMC71/PMC71 high temperature version: 280 mm (11.0") 296 mm (11.7")


with Ex d[ia], CSA XP or FM XP

Endress+Hauser 39
Cerabar S

Process connections PMP71 Note!


(with metallic process Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
isolating diaphragm) (→ 78, feature 70 "Process connection") has to be ordered with a CSA approval (→ 77, feature 10
"Approval"). These devices are fitted with a separate plate bearing the registration number 0F10525.5C.

Thread, internal process isolating diaphragm

1 G 1/2A 2 G 1/2A G 1/4 3 G 1/2A 11.4

H H H

ø11.4 ø11.4
3
20 17 20 17 20
13
ø3 ø17.5
3 G 1/4
ø3.2 G 1/2 A
ø17.5
ø17.5
G 1/2 A
G 1/2 A
P01-PMP71xxx-06-09-xx-xx-000

Process connections PMP71, thread ISO 228


Installation height H → 41.
1 Thread ISO 228 G 1/2 A EN 837;
Material version GA: AISI 316L, version GB: Alloy C276/2.4819; Weight: 0.6 kg (1.3 lb)
2 Thread ISO 228 G 1/2 A G 1/4 (female);
Material version GE: AISI 316L, version GF: Alloy C276/2.4819; Weight: 0.6 kg(1.3 lb)
3 Thread ISO 228 G 1/2 A hole 11.4 mm;
Material version GH: AISI 316L, version GJ: Alloy C276/2.4819; Weight: 0.6 kg (1.3 lb)

1 1/2” MNPT 1/4” FNPT 2 1/2” MNPT 11.4 mm 3 1/2” FNPT


0.28” H
(7) 0.39”
H (10)
H
ø0.45”
(11.4) ø0.84”
0.98” (21.4) 0.98”
ø0.84” (25) (25)
(21.4)
0.59” ø 0.45”
1/4” NPT (15) 1/2” NPT 0.31” 0.79”
(11.4)
ø1.50” (8) (20)
1/2” NPT 1/2” NPT
(38)
P01-PMP71xxx-06-09-xx-xx-001

Process connections PMP71, thread ANSI


Installation height → 41.
1 Thread ANSI 1/2 MNPT 1/4 FNPT;
Material version RA: AISI 316L, version RB: Alloy C276/2.4819; Weight: 0.6 kg (1.3 lb)
2 Thread ANSI 1/2 MNPT; hole: 400 bar (6000 psi)= 11.4 mm, 700 bar (10,150 psi) = 3.2 mm
Material version RD: AISI 316L, version RE: Alloy C276/2.4819; Weight: 0.6 kg (1.3 lb)
3 Thread ANSI 1/2 FNPT;
Material version RH: AISI 316L, version RJ: Alloy C276/2.4819; Weight: 0.7 kg (1.5 lb)

40 Endress+Hauser
Cerabar S

1 G 1/2 2 R 1/2

H H

ø8
3 ø21.4
23 23

ø3 ø11.4
ø5
R 1/2
G1/2
P01-PMP71xxx-06-09-xx-xx-002

Process connections PMP71, thread JIS


→ Installation height H see table below.
1 Version GL: thread JIS B0202 G 1/2 (male), material: AISI 316L; Weight: 0.6 kg (1.3 lb)
2 Version RL: thread JIS B0203 R 1/2 (male), material: AISI 316L; Weight: 0.6 kg (1.3 lb)

M 20x1.5

ø11.4
17 20

ø17.5
M20x1.5
P01-PMP71xxx-06-09-xx-xx-003

Process connections PMP71 thread DIN 13 M 20x1.5 hole 11.4 mm


Material version GP: AISI 316L, version GQ: Alloy C276/2.4819; Weight: 0.6 kg (1.3 lb)
→ Installation height H see table below.

Installation height H for devices with thread connection and internal flush-mounted process
isolating diaphragm

T14 housing T17 housing

Height H 165 mm (6.50") 181 mm (7.13")

Note!
The versions with 700 bar (10,150 psi) sensor are approx. 20 mm (0.79")
higher.

Endress+Hauser 41
Cerabar S

Thread, flush-mounted process isolating diaphragm

1 G 1/2A 2 G 1A 3 G 1-1/2A 4 G 2A
H H H
H
8 1
3.5 3
ø30 3.5
3
ø18.4
26 31
14 18

ø17.5 2 ø30 2 ø36 2 ø56.3 2


G 1/2A G 1A G 1-1/2A G2A
ø36
ø23.6 ø55 ø68
ø39
ø26.5
P01-PMP71xxx-06-09-xx-xx-004

Process connections PMP71, thread ISO 228


Installation height → 43.
1 Thread ISO 228 G 1/2 A DIN 3852 (viton seal provided);
Material version 1A: AISI 316L, version 1B: Alloy C276/2.4819; Weight: 0.4 kg (0.9 lb)
2 Thread ISO 228 G 1 A;
Material version 1D: AISI 316L, version 1E: Alloy C276/2.4819; Weight: 0.7 kg(1.5 lb)
3 Thread ISO 228 G 1 1/2 A
Material version 1G: AISI 316L, version 1H: Alloy C276/2.4819; Weight: 1.1 kg(2.4 lb)
4 Thread ISO 228 G 2 A
Material version 1K: AISI 316L, version 1L: Alloy C276/2.4819; Weight: 1.5 kg(3.3 lb)

1 1” MNPT 2 1-1/2” MNPT 3 2” MNPT

H H
H

1.32”
0.91” 1.06”
(33.5)
(23) (27)

∅ 1.10” ∅ 1.10” ∅ 1.10”


(28) (28) (28)
1” NPT 1-1/2” NPT 2” NPT
P=1-PMP71xxx-06-09-xx-xx-005

Process connections PMP71, thread ANSI


Installation height → 43.
1 Thread ANSI 1 MNPT;
Material version 2A: AISI 316L, version 2B: Alloy C276/2.4819; Weight: 0.7 kg (1.5 lb)
2 Thread ANSI 1 1/2 MNPT;
Material version 2D: AISI 316L, version 2E: Alloy C276/2.4819; Weight: 1.0 kg (2.2 lb)
3 Thread ANSI 2 MNPT
Material version 2G: AISI 316L, version 2H: Alloy C276/2.4819; Weight: 1.3 kg(2.9 lb)

42 Endress+Hauser
Cerabar S

1 M 20x1.5 2 M 44x1.25
H 0.31” H)
(8)
0.12”
0.14” (3)
ø0.70” (3.5)
(17.7)
0.91”
(23)

ø0.69” 0.08” 0.55” ø1.59”


(14) (40.5) 0.08”
(17.5) (2) (2)
M20x1.5 M44x1.25
ø0.93” ø2.17”
(23.6) (55)
ø1.04”
(26 5) P01-PMP71xxx-06-09-xx-xx-006

Process connections PMP71, thread DIN


→ Installation height see table, below.
1 Thread DIN 16288 M20;
Material version 1N: AISI 316L, version 1P: Alloy C276/2.4819; Weight: 0.4 kg (0.9 lb)
2 Thread DIN 13 M 44 x 1.25;
Material version 1R: AISI 316L, version 1S: Alloy C276/2.4819; Weight: 1.1 kg (2.4 lb)

Installation height H for devices with thread connection and flush-mounted process isolating
diaphragm

Description Housing T14 Housing T17

G 1/2 163 mm 179 mm

G1 167 mm 183 mm

G 1 1/2 A 163 mm 179 mm

G2A 162 mm 178 mm

1 MNPT 162 mm (6.38") 178 mm (7.01")

1 1/2 MNPT 165 mm (6.38") 181 mm (7.13")

2 MNPT 159 mm (6.26") 175 mm (6.89")

M 20x1.5 163 mm 179 mm

M 44x1.25 170 mm 186 mm

Endress+Hauser 43
Cerabar S

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527

h H
g2
2
b

dM = ø28
60 m
g
k
D
P01-PMP71xxx-06-09-xx-xx-008

Process connection PMP71, EN/DIN flange with raised face, material AISI 316L SS
H: device height = height of device without flange h + flange thickness b
Height h → 46.

Flange 1 Bolt holes


2
Version Nominal Nominal Shape Diameter Thicknes Raised Width of Quantity Diameter Bolt circle Flange
diameter pressure s face the raised weight 3
face

D b g m g2 k

mm mm mm mm mm mm kg
4
CN DN 25 PN 10-40 B1 (D) 115 18 66 4 4 14 85 1.2
4
CP DN 32 PN 10-40 B1 (D) 140 18 77 8.5 4 18 100 1.9
4
CQ DN 40 PN 10-40 B1 (D) 150 18 87 - 4 18 110 2.2

B3 DN 50 PN 10-40 B1 (D) 165 20 102 - 4 18 125 3.0

B4 DN 80 PN 10-40 B1 (D) 200 24 138 - 8 18 160 5.3

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) Housing weight → 61
4) With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a
manufacturer of seals or your local Endress+Hauser Sales Center.

44 Endress+Hauser
Cerabar S

ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF


JIS flanges, connection dimensions as per B 2220 BL, Raised face RF

h H
0.08” g2
(2)
b
dM = ø1.1”
(28)
2.36” m
(60)
g
k
D
P01-PMP71xxx-06-09-xx-xx-009

Process connection PMP71, ANSI flange or JIS flange with raised face RF; material AISI 316L SS
H: device height = height of device without flange h + flange thickness b. For the height h → 46.

Flange 1 Bolt holes

Ver- Material Nominal Class/ Diameter Thickness Diameter Width of Qty. Diameter Bolt Flange
sion diameter Nominal raised face the raised circle weight 2
pressure face

D b g (m) g2 k

inches in (mm) in (mm) in (mm) in (mm) in (mm) in (mm) lbs (kg)

ANSI flange

AN AISI 316/316L 3 1 300 lb./sq.in 4.88 (124) 0.69 (17.5) 2.76 4 (70) 0.2 (5) 4 0.75 (19.1) 3.5 (88.9) 2.9 (1.3)
3 4
AE AISI 316/316L 1-1/2 150 lb./sq.in 5 (127) 0.69 (17.5) 2.88 (73.2) 0.52 (6.6) 4 0.62 (15.7) 3.88 (98.6) 3.3 (1.5)

AQ AISI 316/316L 3 1-1/2 300 lb./sq.in 6.12 (155.4) 0.81 (20.6) 2.88 4 (73.2) 0.52 (6.6) 4 0.88 (22.4) 4.5 (114.3) 5.7 (2.6)
3
AF AISI 316/316L 2 150 lb./sq.in 6 (152.4) 0.75 (19.1) 3.62 (91.9) - 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)
3
AR AISI 316/316L 2 300 lb./sq.in 7.5 (190.5) 0.88 (22.3) 3.62 (91.9) - 8 0.75 (19.1) 5 (127) 7.1 (3.2)
3
AG AISI 316/316L 3 150 lb./sq.in 7.5 (190.5) 0.94 (23.9) 5 (127) - 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)

AS AISI 316/316L 3 3 300 lb./sq.in 8.25 (209.5) 1.12 (28.4) 5 (127) - 8 0.88 (22.4) 6.62 (168.1) 14.8 (6.7)

AH AISI 316/316L 3 4 150 lb./sq.in 9 (228.6) 0.94 (23.9) 6.19 (157.2) - 8 0.75 (19.1) 7.5 (190.5) 15.6 (7.1)
3
AT AISI 316/316L 4 300 lb./sq.in 10 (254) 1.25 (31.8) 6.19 (157.2) - 8 0.88 (22.4) 7.88 (200.2) 26 (11.6)

JIS flange

KA AISI 316L 25 A 20 K 125 16 67 0.14 4 19 90 1.5

KF AISI 316L 50 A 10 K 155 16 96 - 4 19 120 2.0

KL AISI 316L 80 A 10 K 185 18 127 - 8 19 150 3.3

KH AISI 316L 100 A 10 K 210 18 151 - 8 19 175 4.4

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30 μin (0.8 μm). Lower surface roughness on request.
2) Housing weight → 61
3) Combination of AISI 316 for required pressure resistance and AISI 316L SS for required chemical resistance (dual rated)
4) With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a
manufacturer of seals or your local Endress+Hauser Sales Center.

Endress+Hauser 45
Cerabar S

Height h for devices with flange

T14 housing T17 housing

Height h 165 mm (6.50") 181 mm (7.13")

Oval flange

3.09”
(78.5)
2.50”
(63.5)

2.91” 1/4”-18 NPT


(75) 7/16”-20 UNF

P01-PMP71xxx-06-09-xx-xx-007

Version UR: oval flange adapter 1/4-18 NPT according to IEC 61518, mounting: 7/16-20 UNF; Weight: 1.9 kg (4.2 lb)

Prepared for diaphragm seal mount

1 2 3
h

ø0.09”
0.19” (2.5) ø0.31”
(5) (7.95)
P01-PMP75xxx-06-09-xx-xx-xx-005

Version U1: prepared for diaphragm seal mount


1 Hole for filling fluid
2 Bearing
3 Threaded pin with an internal hexagon 4 mm

T14 housing T17 housing

Height h 190 mm (7.48") 204 mm (8.03")

46 Endress+Hauser
Cerabar S

PMP75 Basic unit

P01-PMP75xxx-06-09-xx-xx-012

PMP75 Basic unit with diaphragm seal


1 PMP75 Basic unit
2 Diaphragm seal, here e.g. flange diaphragm seal

T14 housing T17 housing

Height 190 mm (7.48") 204 mm (8.03")

Process connections PMP75 Note!


(with metallic process • Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
isolating diaphragm) (→ 86, feature 70 "Process connection") has to be ordered with a CSA approval (→ 85, feature 10
"Approval"). Devices with capillary are not CRN-approved. These devices are fitted with a separate plate
bearing the registration number 0F10525.5C.
• Specifications for the "TK Process" are listed in the following tables. These are typical values. The temperature
coefficients apply to silicone oil and the process isolating diaphragm material AISI 316L SS/1.4435. For other
filling oils, this temperature coefficient must be multiplied by the TK correction factor of the corresponding
filling oil. For the TK correction factors, → 69, section "Diaphragm seal filling oils".
• With regard to the temperature coefficient "TK Ambient", devices with a temperature isolator behave like
devices with the same process connection with 0.1 m capillary.
• In addition, the temperature coefficient "TK Ambient" is listed in relation to the capillary length for the
diaphragm seal versions which can be supplied with capillaries as standard. This information is found on
→ 69 ff, section "Influence of the temperature on the zero point".
• The weights of the diaphragm seals are given in the tables. → 61 for the weight of the housing.
• The following drawings are drawings that illustrate how the system works in principle. In other words, the
dimensions of a diaphragm seal supplied can deviate from the dimensions given in this document.

Endress+Hauser 47
Cerabar S

Thread, flush-mounted process isolating diaphragm

SW SW
AF AF

h h

x1 x1

dM dM
d1 NPT
G d2
d2
P01-PMP75xxx-06-09-xx-xx-003

Process connections PMP75, left: thread ISO 228, right: thread ANSI

Threaded connection Diaphragm seal


1
Ver- Material Thread Nomi- Dia- Dia- Screw-in Across max. Dia- TK TK TK Height Dia-
sion nal meter meter length flats phragm Ambient Ambient Process phragm
pres- diameter ≤ 40 bar > 40 bar seal
sure weight

PN d1 d2 x1 SW/AF dM h

[mm] [mm] [mm] [mm] [mbar/10 K] [mm] [kg]

1D AISI 316L G1A 400 30 39 21 2 41 30 +16.03 +24.33 +4.70 19 0.4

1E Alloy C276 – – – 0.5

1G AISI 316L G 1 1/2 A 400 44 55 30 50 42 +5.4 +8.18 +3.50 20 0.9

1H Alloy C276 – – – 1.0

1K AISI 316L G2 400 56 68 30 65 50 +1.76 +2.68 +1.60 20 1.9

1L Alloy C276 – – – 2.1

2A AISI 316L 1" MNPT 6000 psi – 1.89" 1.10" 41 0.94" +15.66 +24.42 +8.50 1.46" 1.3 lbs
(48) (28) (24) (37)
2B Alloy C276 – – – 1.5 lbs

2D AISI 316L 1-1/2" 6000 psi – 1.97" 1.18" 46 1.42" +8.14 +12.39 +3.90 0.79" 2.0 lbs
MNPT (52) (30) (36) (20)
2E Alloy C276 – – – 2.2 lbs

2G AISI 316L 2" MNPT 6000 psi – 3.07" 1.18" 65 1.50" +5.4 +8.18 +2.59 1.38" 4.0 lbs
(78) (30) (38) (35)
2H Alloy C276 – – – 4.4 lbs

1) AISI 316L; Alloy C276/2.4819


2) 28 mm (1.1") in conjucntion with high temperature oil

Note!
With the use of high temperature oils the design can deviate strongly.
For further information please contact your local Endress+Hauser Sales Center.

48 Endress+Hauser
Cerabar S

Tri-Clamp ISO 2852

dM
C7

P01-FMD78xxx-06-09-xx-xx-005

Process connection PMP75, material: AISI 316L SS, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.

Version Nominal Nominal Nominal Diameter max. Height TK TK TK Diaphragm


diameter diameter diameter Diaphragm Ambient Ambient Process seal weight
ISO 2852 DIN 32676 diameter ≤ 40 bar > 40 bar

C7 dM h

inch in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)

TB DN 25 DN 25 1 2.0 (50.5) 0.93 (24) 1.46 (37) +15.33 +24.0 +4.25 3.7 (0.32)
1
TC DN 38 DN 40 1-1/2 2.0 (50.5) 1.34 (34) 1.18 (30) +8.14 +12.39 +1.91 2.2 (1.0)
1
TD DN 51 DN 50 2 2.5 (64) 1.89 (48) 1.18 (30) +3.45 +4.81 +1.25 2.4 (1.1)

TF DN 76.1 – 3 3.6 (91) 2.87 (73) 1.18 (30) +0.3 +0.35 +0.18 2.6 (1.2)

1) Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra ≤ 0.38 μm (15.75 μin; 180 grit),
electropolished; to be ordered using feature 60 "Additional option", version "P" in the order code

Endress+Hauser 49
Cerabar S

Tri-Clamp pipe diaphragm seal ISO 2852

D d2

L
P01-FMD78xxx-06-09-xx-xx-001

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.

Version Nominal Nominal Diameter Diameter Height Face-to- TK TK TK Dia-


diameter diameter face- Ambient Ambient Process phragm seal
ISO 2852 length ≤ 40 bar > 40 bar weight

D d2 h L

inches in (mm) in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)

SB DN 25 1 0.98 (22.5) 2.0 (50.5) 2.64 (67) 4.96 (126) +7.75 +8.69 +4.49 3.7 (1.7)

SC 1 DN 38 1-1/2 1.40 (35.5) 2.0 (50.5) 2.64 (67) 4.96 (126) +5.17 +5.69 +3.46 2.2 (1.0)
1
SD DN 51 2 1.91 (48.6) 2.5 (64) 3.11 (79) 3.94 (100) +3.56 +3.91 +2.69 3.7 (1.7)

1) Including 3.1 and pressure test as per Pressure Equipment Directive, category II

Varivent N for pipes DN 40 – DN 162

1.57”
(40)

dM = 1.81”
(46)
ø2.68”
(68)
P01-FMD78xxx-06-09-xx-xx-006

Process connection PMP75, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm as standard. Lower
surface roughness on request.

Version Material Nominal TK TK TK Process Diaphragm


pressure Ambient Ambient seal weight
≤ 40 bar > 40 bar

[mbar/10 K] kg

TR 1 AISI 316L PN 40 +2.26 +3.11 +1.65 1.3 (2.9 lbs)

1) Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces
Ra ≤ 0.38 μm (15.75 μin; 180 grit), electropolished; to be ordered using feature 60 "Additional option", version "P"
in the order code

50 Endress+Hauser
Cerabar S

DRD DN50 (65 mm)

41
23.6

dM=50 4 x ø11.5
ø65–1.2
ø84
ø105
P01-FM78xxx-06-09-xx-xx-002

Process connection PMP75, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm as standard. Lower
surface roughness on request.

Version Material Nominal TK TK TK Process Diaphragm


pressure Ambient Ambient seal weight
≤ 40 bar > 40 bar

[mbar/10 K] kg

TK AISI 316L PN 25 +2.26 +3.11 +1.65 0.75 (1. 6 lbs)

SMS nozzles with coupling nut

h
m f

dM
G
D
P01-PMP75xxx-06-09-xx-xx-009

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.

Version Nominal Nominal Dia- Adapter Thread Height Height max. dia- TK TK TK Weight
diameter pressure meter height phragm Ambient Ambient Process dia-
diameter ≤ 40 bar > 40 bar phragm
seal

D f G m h dM

[inch] [bar] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] kg

TG 1 PN 25 54 3.5 Rd 40 – 1/6 20 42.5 24 +15.66 +24.22 +7.25 0.25

TH 1 1/2 PN 25 74 4 Rd 60 – 1/6 25 57 36 +8.18 +12.39 +2.59 0.65

TI 2 PN 25 84 4 Rd 70 – 1/6 26 62 48 +5.4 +8.18 +1.10 1.05

Endress+Hauser 51
Cerabar S

APV-RJT nozzles with coupling nut

h
m f

dM
G
D
P01-PMP75xxx-06-09-xx-xx-010

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.

Version Nomi- Nomi- Dia- Adapter Thread Height Height max. TK TK TK Weight
nal dia- nal meter height diaphragm Ambient Ambient Process dia-
meter pres- diameter ≤ 40 bar > 40 bar phragm
sure seal

PN D f G m h dM

[inch] [bar] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] kg

TL 1 PN 40 77 6.5 1 13/16 – 1/8" 22 42.6 21 +15.66 +24.42 +4.21 0.45

TM 1-1/2 PN 40 72 6.4 2 5/16 – 1/8" 22 42.6 28 +8.18 +12.39 +2.59 0.75

TN 2 PN 40 86 6.4 2 7/8 – 1/8" 22 42.6 38 +5.4 +8.18 +1.76 1.2

APV-ISS nozzles with coupling nut

h
f
m

SW/AF dM
G
D
P01-PMP75xxx-06-09-xx-xx-011

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.

Version Nomi- Nomi- Dia-meter Adap- Thread Height Across Height max. TK TK TK Weight
nal nal ter flat diaphragm Ambient Ambient Process Dia.
dia. pres- height seal ≤ 40 bar > 40 bar seal
sure

D f G m AF h dM

inch [bar] in (mm) in (mm) in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)

TP 1 PN 40 2.13 (54.1) 0.16 (4) 1-1/2" – 1/8" 1.18 (30) 46.8 1.97 (50) 0.94 (24) +15.66 +24.42 +4.21 1 (0.4)

TQ 1-1/2 PN 40 2.83 (72) 0.16 (4) 2" – 1/8" 1.18 (30) 62 1.97 (50) 1.34 (34) +8.14 +12.39 +2.59 1.3 (0.6)

TS 2 PN 40 3.50 (89) 0.16 (4) 2-1/2" – 1/8" 1.18 (30) 77 1.97 (50) 1.77 (45) +5.4 +8.18 +1.76 2.4 (1.1)

52 Endress+Hauser
Cerabar S

Taper adapter with coupling nut, DIN 11851

40

f m k

dM
D
G
P01-FMD78xxx-06-09-xx-xx-007

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.

Taper adapter Slotted nut Diaphragm seal

Version Nominal No- Dia- Adapter Thread Height Height max. Dia- TK TK TK Dia-
diameter minal meter height phragm Ambient Ambient Process phragm
pres- diameter ≤ 40 bar > 40 bar seal
sure weight

D f G k m dM

mm mm mm mm [mm [mbar/10 K] kg

MR DN 50 PN 25 68.5 11 Rd 78 x 1/6" 22 19 52 +2.21 +3.02 +1.40 1.1

MS DN 65 PN 25 86 12 Rd 95 x 1/6" 35 21 66 +1.6 +2.1 +0.60 2.0

MT DN 80 PN 25 100 12 Rd 110 x 1/4" 30 26 81 +0.66 +0.81 +0.40 2.55

Threaded adapter, DIN 11851

dM
d1
G
P01-FMD78xxx-06-09-xx-xx-008

Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.

Threaded adapter Diaphragm seal

Version Nominal Nominal Diameter Thread Height max. TK TK TK Process Diaphragm


diameter pressure Diaphragm Ambient Ambient seal weight
diameter ≤ 40 bar > 40 bar

d1 G h dM

mm mm mm [mbar/10 K] kg

M3 DN 50 PN 25 54 Rd 78 x 1/6" 35 52 +2.21 +3.02 +0.88 0.9

M4 DN 65 PN 25 71 Rd 95 x 1/6" 40 66 +1.6 +2.1 +0.60 1.7

M5 DN 80 PN 25 85 Rd 110 x 1/4" 40 81 +0.66 +0.81 +0.40 2.0

Endress+Hauser 53
Cerabar S

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527 and DIN 2501-1

g2
40

dM L
f
60 (m)
g dM
k g
D

P01-PMP75xxx-06-09-xx-xx-002

Process connection PMP75, EN/DIN flange with flush-mounted process isolating diaphragm, material AISI 316L

Flange 1 Bolt holes Diaphragm seal

Ver- No- Nominal Shape Dia- Thick- Raised face Quan- Dia- Bolt max. Dia- TK Ambient TK Dia-
2
sion minal pressure meter ness tity meter circle phragm Pro- phragm
≤ 40 bar > 40 bar
dia- dia- cess seal
meter meter weight

D b g f (m) g2 k dM

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]

CN DN 25 PN 10-40 B1 (D) 115 18 66 3 33 4 14 85 32 +16.03 +24.33 +3.20 2.1

DN DN 25 PN 63-160 E 140 24 68 2 - 4 18 100 28 +16.03 +24.33 +3.20 2.5

EN DN 25 PN 250 E 150 28 68 2 - 4 22 105 28 +16.03 +24.33 +5.17 3.7

E1 DN 25 PN 400 E 180 38 68 2 - 4 26 130 28 +16.03 +24.33 +5.17 7.0

CP DN 32 PN 10-40 B1 (D) 140 18 77 2.6 8.5 3 4 18 100 34 +8.14 +12.39 +2.59 1.9

CQ DN 40 PN 10-40 B1 (D) 150 18 87 2.6 - 4 18 110 48 +5.40 +8.18 +2.15 2.2

B3 DN 50 PN 10-40 B1 (D) 165 26 102 3 - 4 18 125 59 +2.21 +3.02 +1.50 3.0

C3 DN 50 PN 63 B2 (E) 180 26 102 3 - 4 22 135 59 +2.21 +3.02 +1.00 4.6

EF DN 50 PN 100/160 E 195 30 102 3 - 4 26 145 59 +2.21 +3.02 +1.00 6.2

ER DN 50 PN 250 E 200 38 102 3 - 8 26 150 59 +2.21 +3.02 +1.15 7.7

E3 DN 50 PN 400 E 235 52 102 3 - 8 30 180 59 +2.21 +3.02 +1.15 14.7

B4 DN 80 PN 10-40 B1 (D) 200 24 138 3.5 - 8 18 160 89 +0.19 +0.25 +0.20 5.3

C4 DN 80 PN 100 B2 (E) 230 32 138 4 - 8 24 180 89 +0.19 +0.25 +0.35 8.9

C5 DN 100 PN 100 B2 (E) 265 36 175 5 - 8 30 210 89 +0.19 +0.25 +0.11 13.7
4 4
D3 DN 50 PN 10-40 B1 (D) 165 20 102 3 - 4 18 125 47 +3.45 +4.81 +1.67

D4 4 DN 80 PN 10-40 B1 (D) 200 24 138 3.5 - 8 18 160 72 +0.19 +0.25 +0.70 4

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) With these process connections the width of the raised face is smaller than described in the standard. Due to a smaller width of the raised face a special seal
must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center.
4) 50 mm, 100 mm or 200 mm extension selectable, for extension diameter and weight see the following table.

54 Endress+Hauser
Cerabar S

Version Nominal Nominal Extension Extension Diaphragm seal


diameter pressure length diameter d3 weight

[mm] [mm] [kg]

D3 DN 50 PN 10-40 50 / 100 / 200 48.3 3.2 / 3.8 / 4.4

D4 DN 80 PN 10-40 50 /100 / 200 76 6.2 / 6.7 / 7.8

ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF

1.57” g2
(40)
b

dM L
2.36” (m)
Class 150, 300
(60)
0.06 in
(1.6 mm) g dM
k g
Class 400 – 2500
0.25 in D
(6.4 mm)

P01-PMP75xxx-06-09-xx-xx-001

Process connection PMP75, ANSI flange with and without extended diaphragm seal

Flange 1 Bolt holes Diaphragm seal


2
Ver- Material No- Class Dia- Thick- Raised face Qty Dia- Bolt max. TK Ambient TK Dia-
sion minal meter ness meter circle Dia- Pro- phragm
≤ 40 > 40
dia- phragm cess seal
meter dia- bar bar weight
(600 (600
meter
psi) psi)

D b g (m) g2 k dM

inch [lb./ in (mm) in (mm) in (mm) in in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)
sq.in] (mm)

AC AISI 316/ 1 150 4.25 0.56 2 - 4 0.62 3.12 1.26 +16.03 +24.33 +3.65 2.6 (1.2)
316L (108) (14.2) (50.8) (15.7) (79.2) (32)

AN AISI 316/ 1 300 4.88 0.69 2.76 0.2 4 0.75 3.5 1.26 +16.03 +24.33 +3.65 2.9 (1.3)
316L (124) (17.5) (70) (5) 3 (19.1) (88.9) (32)

HC AISI 316/ 1 400/ 4.88 0.69 2 - 4 0.75 3.5 1.26 +16.03 +24.33 +5.17 3.1 (1.4)
316L 600 (124) (17.5) (50.8) (19.1) (88.9) (32)

HN AISI 316/ 1 900/ 5.88 1.12 2 - 4 1 4 1.26 +16.03 +24.33 +5.17 7 (3.2)
316L 1500 (149.4) (28.4) (50.8) (25.4) (101.6) (32)

HO AISI 316/ 1 2500 6.25 1.38 2 - 4 1 4.25 1.26 +16.03 +24.33 +5.17 10 (4.6)
316L (158.8) (35.1) (50.8) (25.4) (108) (32)

AE AISI 316/ 1 1/2 150 5 0.69 2.88 0.3 4 0.62 3.88 1.89 +8.14 +12.39 +1.90 3.3 (1.5)
316L (127) (17.5) (73.2) (6.6) 3 (15.7) (96.6) (48)

AQ AISI 316/ 1 1/2 300 6.12 0.81 2.88 0.3 4 0.88 4.5 1.89 +8.14 +12.39 +2.59 5.7 (2.6)
316L (155.4) (20.6) (73.2) (6.6) 3 (22.4) (114.3) (48)

AF AISI 316/ 2 150 6 0.75 3.62 - 4 0.75 4.75 2.32 +2.21 +3.02 +1.60 4.9 (2.2)
316L (152.4) (19.1) (91.9) (19.1) (120.7) (59)

J3 4 AISI 316/ 2 150 6 0.75 3.62 - 4 0.75 4.75 1.85 +3.45 +4.81 +1.67 4

316L (152.4) (19.1) (91.9) (19.1) (120.7) (47)

AR AISI 316/ 2 300 6.5 0.88 3.62 - 8 0.75 5 2.32 +2.21 +3.02 +0.85 7.5 (3.4)
316L (165.1) (22.4) (91.9) (19.1) (127) (59)

HF AISI 316/ 2 400/ 6.5 1 3.62 - 8 0.75 5 2.32 +2.21 +3.02 +0.85 9.5 (4.3)
316L 600 (165.1) (25.4) (91.9) (19.1) (127) (59)

Endress+Hauser 55
Cerabar S

Flange 1 Bolt holes Diaphragm seal


2
Ver- Material No- Class Dia- Thick- Raised face Qty Dia- Bolt max. TK Ambient TK Dia-
sion minal meter ness meter circle Dia- Pro- phragm
≤ 40 > 40
dia- phragm cess seal
bar bar
meter dia- weight
meter (600 (600
psi) psi)

D b g (m) g2 k dM

inch [lb./ in (mm) in (mm) in (mm) in in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)
sq.in] (mm)

HR AISI 316/ 2 900/ 8.5 1.5 3.62 - 8 1 6.5 2.32 +2.21 +3.02 +0.75 23 (10.3)
316L 1500 (215.9) (38.1) (91.9) (25.4) (165.1) (59)

H3 AISI 316/ 2 2500 9.25 2 3.62 - 8 1.12 6.75 2.32 +2.21 +3.02 +0.75 35 (15.8)
316L (235) (50.8) (91.9) (28.4) (171.5) (59)

AG AISI 316/ 3 150 7.5 0.94 5 - 4 0.75 6 3.50 +0.19 +0.25 +0.18 11.2 (5.1)
316L (190.5) (23.9) (127) (19.1) (152.4) (89)

AS AISI 316/ 3 300 8.25 1.12 5 - 8 0.75 6 3.5 +0.19 +0.25 +0.11 15.4 (7.0)
316L (209.5) (28.4) (127) (19.1) (152.4) (89)

J4 4 AISI 316/ 3 150 7.5 0.94 5 - 4 0.75 6 2.83 +0.19 +0.25 +0.70 4

316L (190.5) (23.9) (127) (19.1) (152.4) (72)

J7 4 AISI 316/ 3 300 8.25 1.12 5 - 8 0.88 6.62 2.83 +0.19 +0.25 +0.70 4

316L (209.5) (28.4) (127) (22.4) (168.1) (72)

AH AISI 316/ 4 150 9 0.94 6.19 - 8 0.75 7.5 3.50 +0.19 +0.25 +0.33 17 (7.2)
316L (228.6) (23.9) (157.2) (19.1) (190.5) (89)

AT AISI 316/ 4 300 10 1.25 6.19 - 8 0.88 7.88 3.50 +0.19 +0.25 +0.11 26 (11.7)
316L (254) (31.8) (157.2) (22.4) (200.2) (89)

J5 4 AISI 316/ 4 150 9 0.94 6.19 - 8 0.75 7.5 3.50 +0.19 +0.25 +0.11 4

316L (228.6) (23.9) (157.2) (19.1) (190.5) (89)

J8 4 AISI 316/ 4 300 10 1.25 6.19 - 8 0.88 7.88 3.50 +0.19 +0.25 +0.11 4

316L (254) (31.8) (157.2) (22.4) (200.2) (89)

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30 μin (0.8 μm). Lower surface roughness on request.
2) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
3) With these process connections the width of the raised face is smaller than described in the standard. Due to a smaller width of the raised face a special seal
must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center.
4) 2", 4", 6" or 8" extension selectable, for extension diameter and weight see the following table

Version Nominal Class Extension Extension Diaphragm seal


diameter length (L) diameter weight

inch lb./sq.in in (mm) in (mm) lbs (kg)

J3 2 150 – 2 (50.8) 1.9 (48.3) – 6.6 (3.0)


– 4 (101.6) – 7.5 (3.4)
– 6 (152.4) – 8.6 (3.9)
– 8 (203.2) – 9.7 (4.4)

J4 3 150 – 2 (50.8) 2.99 (75.9) – 13.2 (6.0)


– 4 (101.6) – 14.6 (6.6)
– 6 (152.4) – 15.7 (7.1)
– 8 (203.2) – 17.2 (7.8)

J7 3 300 – 2 (50.8) 2.99 (75.9) – 17.4 (7.9)


– 4 (101.6) – 18.7 (8.5)
– 6 (152.4) – 19.8 (9.0)
– 8 (203.2) – 21.2 (9.6)

56 Endress+Hauser
Cerabar S

Version Nominal Class Extension Extension Diaphragm seal


diameter length (L) diameter weight

J5 4 150 – 2 (50.8) 3.7 (94) – 19.0 (8.6)


– 4 (101.6) – 21.8 (9.9)
– 6 (152.4) – 24.7 (11.2)
– 8 (203.2) – 27.3 (12.4)

J8 4 300 – 2 (50.8) 3.7 (94) – 28.9 (13.1)


– 4 (101.6) – 31.7 (14.4)
– 6 (152.4) – 34.6 (15.7)
– 8 (203.2) – 37.3 (16.9)

JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF

f 40

dM

D
P01-PMP75xxx-06-09-xx-xx-000

Process connection PMP75, JIS flange with raised face RF, material AISI 316L SS

Flange 1 Bolt holes Diaphragm seal

Ver- No- No- Dia- Thick- Dia- Height Quan- Dia- Bolt max. TK Ambient TK Dia-
sion minal minal meter ness meter raised tity meter circle Dia- Process phragm
dia- pres- raised face phragm seal
≤ 40 bar > 40 bar
meter sure face dia- weight 2
meter

D b g f g2 k dM

mm mm mm mm mm mm mm [mbar/10 K] kg

KC 25 A 10 K 125 14 67 1 4 19 90 32 +16.03 +24.33 +5.17 1.5

KF 50 A 10 K 155 16 96 2 4 19 120 59 +2.21 +3.02 +1.00 2.3

KL 80 A 10 K 185 18 127 2 8 19 150 89 +0.19 +0.25 +0.11 3.3

KH 100 A 10 K 210 18 151 2 8 19 175 89 +0.19 +0.25 +0.11 4.4

1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Housing weight → 61

Endress+Hauser 57
Cerabar S

Thread 1/2" NPT and 1" NPT, seperator

Ø 4.65” Ø 4.65”
(118) (118)

2.99”
(76) 3.72”
(94.5)

1.02”
0.75” (26)
(19) 1.75”
1.06” (44.5)
1/2” NPT (27)
0.47”
27AF (12)
1” NPT
Ø 1.18” 0.59”
(30) 36 AF (15)
Ø 2.05”
(52)
P01-PMP75xxx-06-09-xx-xx-008

Process connection PMP75, versions "UG" and "UH", screwed, material AISI 316L SS, seal Viton

Version Description Nominal TK Ambient TK Process Diaphragm seal


pressure weight

[mbar/10 K] lbs (kg)

UG 1/2" NPT 3625 psi (PN 250) +3.45 +1.28 10.5 (4.75)

UH 1" NPT 3625 psi (PN 250) +3.45 +1.28 11.0 lbs (5.0)

Thread ISO 228 G 1/2 A and ANSI 1/2" MNPT, seperator

ø2.86”
ø72.6
(72.6)

2.76”
70 0.55” (70)
(14)

SW 30 AF 30
14
ø18.4
17 20 0.85”
(21.5)

ø4 ø0.45”
ø6 3 (11.4)
G 1/2A 1/2” - 14 NPT
P01-PMP75xxx-06-09-xx-xx-004

Process connection PMP75, versions "UA" and "UB", welded, material AISI 316L

Version Description Nominal TK Ambient TK Process Diaphragm


pressure seal weight

[mbar/10 K] lbs (kg)

UA ISO 228 G 1/2 A PN 160 +0.9 +0.30 3.2 (1.43)

UB ANSI 1/2" MNPT 2320 psi +0.9 +0.30 3.2 (1.43)

58 Endress+Hauser
Cerabar S

3.94” 3.94”
(100) (100)

3.54” 3.50”
(90) 1 (89) 1

SW22 SW22
22 AF 22 AF

0.24” 1/2” NPT


(6)

P01-PMP75xxx-06-09-xx-xx-013

Process connection PMP75, left: version "UC" with threaded connection ISO 228 G 1/2 B, right: version "UD" with
threaded connection ANSI 1/2" MNPT
1 PTFE seal as standard max. 260°C/500°F (higher temperatures on request)

Version Measuring range Description Nominal pressure TK Process Diaphragm seal weight

[mbar/10 K] lbs (kg)

UC ≤ 40 bar ISO 228 G 1/2 B PN 40 +0.75 3.2 (1.43)

UD ≤ 600 psi ANSI 1/2" MNPT 600 psi +0.55 3.2 (1.43)

Ø 4.53” Ø 4.53”
(115) (115)

3.31”
(84) 3.64”
(92.5)

AF 36 AF 36
0.75”
(19) AF 22 0.67” 0.79”
(17) (20)
Ø 0.1”
(2.5)
1/2” NPT Ø 0.16”
(4)
0.12”
Ø 0.24”
(3)
(6)
G 1/2A
P01-PMP75xxx-06-09-xx-xx-007

Process connection PMP75, versions "UC" and "UD", threaded, with integrated sealing lip, material AISI 316L

Version Measuring Description Nominal TK Ambient TK Process Diaphragm


range pressure seal weight

[mbar/10 K] lbs (kg)

UC > 40 bar ISO 228 G 1/2 A PN 400 +3.45 +1.28 10.5 (4.75)

UD > 600 psi ANSI 1/2" MNPT 6000 psi +3.45 +1.28 10.5 (4.75)

Note!
With the use of high temperature oils the design can deviate strongly.
For further information please contact your local Endress+Hauser Sales Center.

Endress+Hauser 59
Cerabar S

"Remote housing" version


101 84 118
(3.97”) (3.31”) (4.65”)

131
(5.16”)

45.5
(1.79”)

ø51.7
(2.04”)
P01-xxxxxxxx-06-xx-xx-xx-000

Dimensions T14 housing, optional display on the side. Housing weight see → 61.

101 76
(3.98”) 118
(2.99”)
(4.65”)

147
(5.79”)

45.5
(1.79”)

ø51.7
(2.04”)
P01-xxxxxxxx-06-xx-xx-xx-001

Dimensions T17 housing, optional display on the side. Housing weight see → 61.

r ³ 4.72” r ³ 4.72” r ³ 4.72”


(120 mm) T17
(120 mm) (120 mm)
T14

2.17” 2.17”
(55) (55) ø2.13”
(54.1)

2.80”
1 1 1 (71)

P01-xxxxxxxx-06-xx-xx-xx-002

Reduction of the mounting height of the process connection, for application of the remote housing.
1 Process connection adapter.

If the remote housing is used, the mounting height of the process connection is reduced by approx. 45 mm
(1.8") as compared to the dimensions of the standard version.
The minimum bending radius (r) for the cable is 120 mm (4.7").

60 Endress+Hauser
Cerabar S

Weight Housing

T14 T17 Remote housing

Aluminum AISI 316L AISI 316L

With electronic insert and on-site 2.6 lb (1.2 kg) 4.6 lb (2.1 kg) 2.6 lb (1.2 kg) Weight of housing T14 or T17 + 1.1 lb (0.5 kg).
display Weight of sensor + 1.1 lb (0.5 kg).

With electronic insert without on-site 2.4 lb (1.1 kg) 4.4 lb (2.0 kg) 2.4 lb (1.1 kg)
display

Process connections
• Process connections PMC71 (with ceramic process isolating diaphragm): → 33 ff
• Process connections PMP71 (with metallic process isolating diaphragm): → 40 ff
• Process connections PMP75 (with metallic process isolating diaphragm): → 47 ff

Material T14 housing:


• T14 housing, selectable:
– Die-cast aluminum with protective powder-coating on polyester basis: RAL 5012 (blue),
cover: RAL 7035 (grey)
– Precision cast stainless steel AISI 316L (1.4435)
• External operation (keys and key covering): Polycarbonate PC-FR,
RAL 7035 (grey)
• Sight glass: Mineral glass
• Cable gland: Polyamid (PA)
• Pressure compensation filter: PA6 GF10
• Blind plug: PBT-GF30 FR, for Dust Ex, Ex d, FM XP and CSA XP: AISI 316L (1.4435)
• Seals:
– Cable and blind plug seal: Silicone (VMQ)
– Pressure compensation filter o-ring: Silicone (VMQ)
– Cover: EPDM
– Sight glass: Silicone (VMQ)
• Nameplates: AISI 304 (1.4301)
T17 housing:
• Housing: Stainless steel AISI 316L (1.4404)
• Sight glass:
– Version for non-hazardous area, ATEX Ex ia, NEPSI Zone 0/1 Ex ia, IECEx Zone 0/1 Ex ia, FM NI, FM
IS, CSA IS: Polycarbonate (PC)
– ATEX 1/2 D, ATEX 1/3 D, ATEX 1 GD, ATEX 1/2 GD, ATEX 3 G, FM DIP, CSA Dust Ex: Mineral glass
• Cable gland: Polyamid PA, for Dust-Ex: CuZn nickel-plated
• Blind plug: PBT-GF30 FR, for Dust-Ex: AISI 316L (1.4435)
• Pressure compensation filter: PA6 GF10
• Seals:
– Cable and blind plug seal: Silicone (VMQ)
– Pressure compensation filter o-ring: Silicone (VMQ)
– Cover: EPDM
– Sight glass: EPDM
• Nameplates: lasered

Process connection
• "Clamp connections" and "Hygienic connections" (see also Chapter "Ordering information"): AISI 316L/
1.4435
• "Threaded connection" and "DIN/EN flanges" (see also Chapter "Ordering information"): stainless steel AISI
316L with the material number 1.4435 or 1.4404
• With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together
under 13E0 in EN 1092-1 Tab.18. The chemical composition of the two materials can be identical.

Endress+Hauser 61
Cerabar S

Cable for remote housing:


• PE cable:
Slip-resistant cable with strain-relief members made of Dynemo; shielded using aluminium-coated film;
insulated with polyethylene (PE-LD), black; copper wires, twisted, UV resistant
• FEP cable:
Slip-resistant cable; shielded using galvanized steel wire netting; insulated with fluorinated ethylene
propylene (FEP), black; copper wires, twisted, UV resistant

TSE Certificate of Suitability


The following applies to all process wetted device components:
• They do not contain any materials derived from animals.
• No auxiliaries or operating materials derived from animals are used in production or processing.

! Note!
Process wetted device components are listed in the "Mechanical construction" (→ 32) and "Ordering
information" (→ 77) sections.

Miscellaneous:
• Process isolating diaphragm PMC71: Al2O3 Aluminum-oxide-ceramic (FDA 21CFR186.1256, USP Class
VI), ultrapure 99.9% (→ www.endress.com/ceraphire)
• Mounting accessories: Mounting kit with screws AISI 304 (1.4301)
• Capillary: AISI 316 Ti (1.4571)
• Protective hose for capillary: AISI 304 (1.4301)
• External ground terminal: AISI 304 (1.4301)
→ For process connections, process diaphragms, seals and filling oils see ordering information, → 77 ff.

62 Endress+Hauser
Cerabar S

Human interface
Operating elements On-site display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The on-site display shows measured
values, dialog text as well as fault and notice messages in plain text, thereby supporting the user in every stage
of operation. The liquid crystal display of the device can be turned in 90° steps.
Depending on the installation position of the device, this makes it easy to operate the device and read the
measured value.
Functions:
• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as current
display or for PROFIBUS PA as graphical display of the scaled value of the AI Block
• Simple and complete menu guidance thanks to seperation of the parameters into three levels
• Ech parameter is given as 3-digit ID number for easy navigation
• Option for configuring the display according to individual requirements and desires, such as language,
alternating display, display of other measured values such as sensor temperature, contrast setting
• Comprehensive diagnostic functions (fault and warning message, peak-hold indicators, etc.)
• Rapid and safe commissioning with the Quick Setup menus

Measured value display Parameter


Identification
Function name Value number

Header line
Main line
Unit
Information
line
– + E Symbol
Bargraph
Editing modes

Operating keys
Selection
options

Value that
can be edited

Current measured value


P01-xxxxxxxx-07-xx-xx-en-011

Endress+Hauser 63
Cerabar S

Operating elements Operating keys on the exterior of the device


The operating keys of the housing T14 (aluminum or stainless steel) are located either outside of the housing,
under the protection cap or upon the electronic insert. The operating keys of the housing T17 (ironing stainless
steel) are located inside the housing upon the electronic insert

4 to 20 mA HART

PROFIBUS PA/
FOUNDATION Fieldbus

0%
Zero

P01-PMx7xxxx-19-xx-xx-xx-038

The operating keys located externally on the device work on the Hall sensor principle. As a result, no additional
openings are required in the device. This guarantees:
• Complete protection against environmental influences such as moisture and contamination
• Simple operation without any tools
• No wear.

Operating keys and elements located internally on the electronic insert

t t
Sim.
on on on

off off 0% off 1 2


0%

Zero
Sensor Display Zero
Sensor Display
Simulation

on on ON CK S D A 0 8 HW
on
1 2 1 2 off off 1 2 3 4 5 6 7 8
PC

1 2 off
PC

PC
1 2 3 4 5 6 7 8
Address
Histo ROM

Histo ROM
SW
HW
HART
R
250002271-–

TM
250002272-–

FIELD COMMUNICATION PROTOCOL


250002273-–

HW-Version: 1 FOUNDATION
SW-Version: 2 HW-Version: 1 HW-Version: 1
SW-Version: 2 SW-Version: 2

P01-xxxxxxxx-19-xx-xx-xx-104 P01-xxxxxxxx-19-xx-xx-xx-105 P01-xxxxxxxx-19-xx-xx-xx-106

Electronic insert HART Electronic insert PROFIBUS PA Electronic insert FOUNDATION Fieldbus
1 Operating keys 1 Green LED to indicate value being accepted 1 Green LED to indicate value being accepted
2 Slot for optional display 2 Key for position calibration and device reset 2 Key for position calibration and device reset
3 Slot for optional HistoROM®/M-DAT 3 DIP-switch for bus address 3 Slot for optional display
4 DIP-switch for locking/unlocking 4 Slot for optional display 4 Slot for optional HistoROM®/M-DAT
measured-value-relevant parameters 5 Slot for optional HistoROM®/M-DAT 5 DIP-switch for locking/unlocking
5 DIP-switch for damping on/off 6 DIP-switch for locking/unlocking measured-value-relevant parameters
6 Green LED to indicate value being accepted measured-value-relevant parameters 6 DIP-switch for simulation mode on/off
7 DIP-switch for damping on/off

64 Endress+Hauser
Cerabar S

Local operation Function External operation Internal operation Display (optional)


(operation keys, (electronic insert)
optional, not T17 hous-
ing)
Position calibration
X X X
(zero point correction)
Setting lower-range value
and upper-range value - X X
X
reference pressure present (HART only) (HART only)
at the device
Device Reset X X X
Locking and unlocking
measured-value-relevant ⎯ X X
parameters
Value acceptance indi-
X X X
cated by green LED
Switching damping on and X
⎯ X
off (HART and PA only)
Setting bus address (PA) ⎯ X X
Switching simulation
mode on and off (FOUN- ⎯ X X
DATION Fieldbus)

Remote operation Depending on the position of the write protection switch at the device, all software parameters are accessible.

HART
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- and Software for local and remote
operation" → 66)
• FieldCare (see Chapter "Hard- und Software for on-site and remote operation" → 66 ff) with
– Commubox FXA191 (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
– Commubox FXA195 (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
• Field Xpert:
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows
Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART
device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520. Field Xpert also works
as a stand-alone device for asset management applications. For details refer to BA060S/00/en.

PROFIBUS PA
Remote operation via:
• FieldCare (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
– Profiboard: For the Connection of a Personal Computer to PROFIBUS
– Proficard: For the Connection of a Laptop to PROFIBUS

FOUNDATION Fieldbus
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- and Software for local and remote
operation" → 66 ff)
• Use an FF-configuration program for e.g. NI-FBUS configurator, to
– connect devices with "FOUNDATION Fieldbus signal" into an FF-network
– set FF-specific parameter
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops and a
schedule based on the fieldbus concept.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
– Set block and device tags
– Set device addresses
– Create and edit function block control strategies (function block applications)
– Configure vendor -defined function and transducer blocks
– Create and edit schedules
– Read and write to function block control strategies (function block applications)

Endress+Hauser 65
Cerabar S

– Invoke Device Description (DD) methods


– Display DD menus
– Download a configuration
– Verify a configuration and compare it to a saved configuration
– Monitor a downloaded configuration
– Replace a virual device by a real device
– Save and print a configuration

! Note!
For further information please contact your local Endress+Hauser Sales Center.

Hard- and Software for local Commubox FXA191


and remote operation
For intrinsically safe communication with FieldCare via the RS232C interface. For details refer to
TI237F700/en.

Commubox FXA195
For intrinsically safe communication with FieldCare via the USB interface. For details TI404F/00/en.

Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field instruent with CDI interface (=Endress+Hauser
Common Data Interface) to the USB interface of a personal computer or a notebook.
For details TI405C/07/en.

Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70

ToF Adapter FXA291


The ToF Adapter FXA291 connects the Commubox FXA291 with instruments of the ToF platform, pressure
instruments and Gammapilot via the USB interface of a personal computer or a notebook. For details refer to
KA271F.

Field Communicator 375


With a handheld terminal, all the parameters can be configured anywhere along the 4 to 20 mA line via menu
operation.

HistoROM®/M-DAT (optional)
HistoROM®/M-DAT is a memory module, which is attached to the electronic insert. The HistoROM®/M-DAT
can be retrofitted at any stage (Order number: 52027785).

Your benefits
• Quick and safe commissioning of the same measuring points by copying the configuration data of one
transmitter to another transmitter
• Reliable process monitoring thanks to cyclical recording of pressure and sensor temperature measured values
• Simple dagnosis by recording diverse events such as alarms, configuration changes, counters for measuring
range undershoot and overshoot for pressure and temperature as well as user limit overshoot and undershoot
for pressure and temperature etc.
• Analysis and graphic evaluation of the events and process parameters via software (contained in scope of
supply).
HistoROM®/M-DAT can be ordered via feature 100 "Additional options 1" or feature 110 "Additional options
2" or as spare parts. → 77 ff. A CD with Endress+Hauser operating program is also included in the scope of
delivery.
You can copy data from one transmitter to another transmitter when operating a FOUNDATION Fieldbus
device via an FF configuration program. You need the Endress+Hauser FieldCare operating program and the
Commubox FXA291 service interface and the ToF Adapter FXA291 to be able to access the data and events
saved in the HistoROM®/M-DAT.

66 Endress+Hauser
Cerabar S

FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can
configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT
standard.
FieldCare supports the following functions:
• Configuration of transmitter in offline and online operation
• Loading and saving device data (upload/download)
• HistoROM®/M-DAT analysis
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA191 and the RS232C serial interface of a computer
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
• FOUNDATION Fieldbus via Commubox FXA193 and the RS232C serial interface of a computer
• Service interface with adapter Commubox FXA291 and ToF Adapter FXA291 (USB).
For further information www.endress.com

Endress+Hauser 67
Cerabar S

Planning instructions, diaphragm seal systems


With the Endress Hauser selection tool "Applicator" you will find the optimum diaphragm seal for your
application. Online on "www.endress.com/applicator" or offline on CD.
For further information please contact your local Endress+Hauser Sales Center.

Applications Diaphragm seal systems should be used if the process media and the device should be separated. Diaphragm
seal systems offer clear advantages in the following instances:
• In the case of high process temperatures (→ 30, section "Process temperature limits".)
• For aggressive media
• If good and rapid measuring point cleaning is necessary
• If the measuring point is exposed to vibrations
• For mounting locations that are difficult to access
• For very humid mounting locations

Planning instructions Diaphragm seals are separating equipment between the measuring system and the process medium.
A diaphragm seal system consists of:
• A diaphragm seal in a one-sided system
• Capillary tube
• Fill fluid and
• A pressure transmitter.
The process pressure acts via the process isolating diaphragm of a diaphragm seal on the liquid-filled system,
which transfers the process pressure via the capillary tube onto the sensor of the pressure transmitter.
Endress+Hauser delivers all diaphragm seal systems as welded versions. The system is hermetically sealed,
which ensures the highest reliability.
Note!
The correlations between the individual diaphragm seal components are presented in the following section.
For further information and comprehensive diaphragm seal system designs, please contact your local
Endress+Hauser Sales Center.

Diaphragm seal
The diaphragm seal determines the application range of the system by
• the process isolating diaphragm diameter
• the diaphragms: stiffness and material
• the design (oil volume).

Process isolating diaphragm diameter


The larger the process isolating diaphragm diameter (less stiffness), the smaller the temperature effect on the
measurement result.
Note: To keep the temperature effect in practice-oriented limits, you should select diaphragm seals with a
nominal diameter of ≥ DN 80 (3"), in as far as the process connection allows for it.

Process isolating diaphragm stiffness


The stiffness is dependent on the process isolating diaphragm diameter, the material, any available coating and
on the process isolating diaphragm thickness and shape. The process isolating diaphragm thickness and the
shape are defined constructively. The stiffness of a process isolating diaphragm of a diaphragm seal influences
the temperature operating range and the measuring error caused by temperature effects.

Capillary
Capillaries with an internal diameter of 1 mm (0.04") are used as standard.
The capillary tube influences the TK zero point, the ambient temperature operating range and the response
time of a diaphragm seal system as a result of its length and internal diameter.
→ 69 ff, sections "Influence of the temperature on the zero point" and "Ambient temperature range".
→ Observe the installation instructions regarding capillary tubes. → 74 ff, section "Installation instructions".

68 Endress+Hauser
Cerabar S

Filling oil
When selecting the filling oil, fluid and ambient temperature as well as the operating pressure are of crucial
importance. Observe the temperatures and pressures during commissioning and cleaning. A further selection
criterion is the compatibility of the filling oil with the requirements of the process medium. For this reason,
only filling oils that are harmless to health are used in the food industry, such as vegetable oil or silicone oil
→ See also the following section "Diaphragm seal filling oils" section.
The filling oil used influences the TK zero point and the temperature operating range of a diaphragm seal system
and the response time. → 69 ff, section "Influence of the temperature on the zero point".

Pressure transmitter
The pressure transmitter influences the temperature operating range, the TK zero point and the response time
as a result of its volume change. The volume change is the volume that has to be shifted to pass through the
complete measuring range.
Pressure transmitters from Endress+Hauser are optimised with regard to minimum volume change.

Diaphragm seal filling oils

Version 1 Filling oil Permissible Permissible Density Viscosity Coefficient TK Note


temperature range 2 at temperature 2 range of thermal correction
0.05 bar ≤ pabs ≤ 1 bar at pabs ≥ 1 bar expansion factor
(0.7 psi ≤ pabs ≤ 14 psi) (pabs ≥ 14 psi)
g/cm3 cSt at 1/K
25°C
(77°F)

A, H, Silicone oil –40 to +180°C –40 to +250°C 0.96 100 0.00096 1 suitable for foods
1 or 2 (DC 200) (–40 to +356°F) (–40 to +482°F) FDA 21 CFR 175.105

G, 3 or 4 High temp. oil –10 to +200°C –10 to +400°C 1.07 37 0.0007 0.72 high temperatures
(DC 704) (+14 to +392°F) (+14 to +752°F)

F or N Inert oil –40 to +80°C –40 to +175°C 1.87 27 0.000876 0.91 for ultra pure gas and
(Halocarbon) (–4 to +176°F) (–40 to +347°F) oxygen
applications

D, 5 or 6 Vegetable oil –10 to +120°C –10 to +200°C 0.94 9.5 0.00101 1.05 suitable for foods
(Neobee M-20) (+14 to +248°F) (+14 to +392°F) FDA 21 CFR 172.856

7 or 8 Low –70 to +80°C –70 to +180°C 0.92 4.4 0.00108 1.12 low temperatures
temperature oil –94 to +176°F –94 to +356°F

1) Version for feature 90 in the order code


2) Observe temperature limits of the device (→ 28 and → 30).

Influence of the temperature A temperature change results in a volume change of the filling oil. The volume change is dependent on the
on the zero point coefficient of thermal expansion of the filling oil and on the volume of the filling oil at calibration temperature
(constant in the range: +21 to +33°C (+69.8 to 91.4°F)). → 69, "Filling oil" section.
For example, the filling oil expands in the event of a temperature increase. The additional volume presses
against the process isolating diaphragm of a diaphragm seal. The stiffer a process isolating diaphragm is, the
greater its return force, which counteracts a volume change and acts on the measuring cell together with the
operating pressure, thus shifting the zero point. For the "TK Process" and "TK Ambient (for devices without
capillary)", see → 47 ff, section "Process connections PMP75".
The following diagrams display the temperature coefficient "TK Ambient" dependent on the capillary length.
The following application is displayed: capillary temperature and transmitter temperature (ambient
temperature) change, the process temperature corresponds to the calibration temperature.
The temperature coefficients obtained from the diagrams apply to silicone oil and the process isolating
diaphragm material AISI 316L/1.4435. For other filling oils, these temperature coefficients must be multiplied
by the TK correction factor of the corresponding filling oil. For the TK correction factors, see → 69,
section "Diaphragm seal filling oils".
With regard to the temperature coefficient "TK Ambient", devices with temperature isolator behave like devices
with the same process connection and 0.1 m capillary.

Endress+Hauser 69
Cerabar S

PN < 40 bar
TK Ambient 16
[mbar/10 K]
14
6
12

10
mbar
8.4 8
10 K

0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-007

Diagram TK Ambient dependent on the capillary length for PMP75, PN < 40 bar (600 psi)

Example for:
– Diaphragm seal versions "B3, EN/DIN flange DN 50 PN 10-40 B1, AISI 316L"
– Capillary length: 5 m (16 ft)
– Ambient temperature, capillary/transmitter: 45°C
– Filling oil: silicone oil
1. Select characteristic curve type for the diaphragm seal versions "B3" in accordance with the following
table.
Result: characteristic curve type 6
2. Obtain value for TK Ambient from the diagram.
Result: 8.4 mbar/10 K
3. TAmbient – TCalibration = 45°C – 25°C = 20°C ⇒ 8.4 mbar/10 K x 20 K = 16.8 mbar (0.24 psi)
Result: In this application, the zero point is shifted by 16.8 mbar (0.24 psi).

Note!
• The influence of temperature on the zero point can be corrected with position calibration.
• The temperature influence can be minimised by using a filling oil with a smaller coefficient of thermal
expansion, shorter capillary, diaphragm seal with larger process isolating diaphragm diameter or by using a
smaller capillary internal diameter.

70 Endress+Hauser
Cerabar S

PN ³ 40 bar
TK Ambient 16 7
[mbar/10 K] 6
14

12
5
10
4
8

6
7
4
3
2 2
1
0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-005

Diagram TK Ambient dependent on the capillary length for PMP75, PN ≥ 40 bar (600 psi)

Characteristic Version Diaphragm seal


curve type
1 B4 EN/DIN flange DN 80 PN 10-40 B1, AISI 316L
C4 EN/DIN flange DN 80 PN 100 B2, AISI 316L
C5 EN/DIN flange DN 100 PN 100 B2, AISI 316L
KL JIS flange 10K 80A RF, AISI 316L
KH JIS flange 10K 100A RF, AISI 316L
D4 EN/DIN flange DN 80, PN 10-40 B1, Extensions: 50 mm/100 mm/200 mm, AISI 316L
AG ANSI flange 3" 150 lbs RF, AISI 316/316L
AS ANSI flange 3" 300 lbs RF, AISI 316/316L
AH ANSI flange 4" 150 lbs RF, AISI 316/316L
AT ANSI flange 4" 300 lbs RF, AISI 316/316L
J4 ANSI flange 3" 150 lbs RF, Extensions: 2"/4"/6"/8", AISI 316/316L
J7 ANSI flange 3" 300 lbs RF, Extensions: 2"/4"/6"/8", AISI 316/316L
J5 ANSI flange 4" 150 lbs RF, Extensions: 2"/4"/6"/8", AISI 316/316L
J8 ANSI flange 4" 300 lbs RF, Extensions: 2"/4"/6"/8", AISI 316/316L
2 TF Tri-Clamp, ISO 2852 DN 76.1 (3"), AISI 316L/1.4435
3 MT DIN 11851 DN 80 PN 25, AISI 316L/1.4435
M5 DIN 11851 DN 80 PN 25 socket, AISI 316L/1.4435
4 SD Pipe diaphragm seal Tri-Clamp, ISO 2852 DN 51 (2"), AISI 316L
5 SC Pipe diaphragm seal Tri-Clamp, ISO 2852 DN 38 (1 1/2"), AISI 316L
6 B3 EN/DIN flange DN 50 PN 1040 B1, AISI 316L
C3 EN/DIN flange DN 50 PN 63 B2, AISI 316L
EF EN/DIN flange DN 50 PN 100-160 E, AISI 316L
ER EN/DIN flange DN 50 PN 250 E, AISI 316L
E3 EN/DIN flange DN 50 PN 400 E, AISI 316L
AF ANSI flange 2" 150 lbs RF, AISI 316/316L
AR ANSI flange 2" 300 lbs RF, AISI 316/316L
HF ANSI flange 2" 400/600 lbs RF, AISI 316/316L
HR ANSI flange 2" 900/1500 lbs RF, AISI 316/316L
H3 ANSI flange 2" 2500 lbs RF, AISI 316/316L
KF JIS 10K 50A RF, AISI 316L
MR DIN 11851 DN 50 PN 25, AISI 316L/1.4435
MS DIN 11851 DN 65 PN 25, AISI 316L/1.4435
M3 DIN 11851 DN 50 PN 25 socket, AISI 316L/1.4435
M4 DIN 11851 DN 65 PN 25 socket, AISI 316L/1.4435
7 TR Varivent Type N for tubes DN 40 – DN 162, PN 40, AISI 316L/1.4435
TK DRD DN50 (65 mm), PN 25, AISI 316L/1.4435

Endress+Hauser 71
Cerabar S

PN £ 40 bar
TK Ambient 160
[mbar/10 K]
140
13
120
12
100

80
11
60
10
40
9
20
8

0
0 1 2 3 4 5 6 7 8 9 10

Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-008

Diagram TK Ambient dependent on the capillary length for PMP75, PN < 40 bar (600 psi)

PN > 40 bar
TK Ambient 160
[mbar/10 K]
140
13
120
12
100

80
11
60
10
40
9
20 8

0
0 1 2 3 4 5 6 7 8 9 10

Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-009

Diagram TK Ambient dependent on the capillary length for PMP75, PN ≥ 40 bar (600 psi)

72 Endress+Hauser
Cerabar S

Characteristic Version Diaphragm seal


curve type
8 SB Pipe diaphragm seal Tri-Clamp, ISO 2852 DN 25 (1"), AISI 316L
9 D3 EN/DIN flange PN10-40 B1, Extensions: 50 mm/100 mm/200 mm, AISI 316L
J3 ANSI flange 2" 150 lbs, Extensions: 2"/4"/6"/8", AISI 316/316L
TD Tri-Clamp, ISO 2852 DN 51 (2"), AISI 316L/1.4435
10 CQ EN/DIN flange DN 40 PN 10-40 B1, AISI 316L
TI SMS 2" PN 25, AISI 316L/1.4435
TN APV-RJT 2" PN 40, AISI 316L/1.4435
TS APV-ISS 2" PN 40, AISI 316L/1.4435
11 CP EN/DIN flange DN32 PN 10-40 B1, AISI 316L
AE ANSI flange 1 1/2" 150 lbs RF, AISI 316/316L
AQ ANSI flange 1 1/2" 300 lbs RF, AISI 316/316L
TC Tri-Clamp, ISO 2852 DN 38 (1 1/2"), DIN 32676 DN 40, AISI 316L/1.4435
TH SMS 1 1/2" PN 25, AISI 316L/1.4435
TM APV-RJT 1 1/2" PN 40, AISI 316L/1.4435
TS APV-ISS 1 1/2" PN 40, AISI 316L/1.4435
12 CN EN/DIN flange PN 10-40 B1, AISI 316L
DN EN/DIN flange PN 64-160 E, AISI 316L
EN EN/DIN flange PN 250 E, AISI 316L
E1 EN/DIN flange PN 400 E, AISI 316L
AC ANSI flange 1" 150 lbs RF, AISI 316/316L
AN ANSI flange 1" 300 lbs RF, AISI 316/316L
HC ANSI flange 1" 400/600 lbs RF, AISI 316/316L
HN ANSI flange 1" 900/1500 lbs RF, AISI 316/316L
HO ANSI flange 1" 2500 lbs RF, AISI 316/316L
KC JIS flange 10K 25 A RF, AISI 316L
13 TB Tri-Clamp, ISO 2852 DN 25 (1"), DIN 32676 DN 25, AISI 316L/1.4435

Ambient temperature range The operating temperature range of a diaphragm seal system depends on Fill fluid, "Capillary length and
internal diameter, Process temperature and Diaphragm seal oil volume.
The range of application can be extended by using a fill fluid with a smaller expansion coefficient and a shorter
capillary. The permitted operating temperature ranges in relation to the capillary length can be calculated
online at "Applicator Sizing Diaphragm Seal":
http://www.endress.com/applicator -> Applicator Sizing Diaphragm Seal -> Horncurve

P01-xxxxxxxx-20-xx-xx-en-001

Note!
• Endress+Hauser recommends you use a low temperature oil for applications that require short response
times or are close to the lower temperature limit (see "diaphragm seal fill fluid").
• Please contact your Endress+Hauser sales office for further information, comprehensive diaphragm seal
system designs and measuring technology solutions that are close to the application limits.

Endress+Hauser 73
Cerabar S

Installation instructions Instructions for diaphragm seal systems


• Endress+Hauser offer flushing rings as accessory to clean process isolating diaphragms without taking the
transmitters out of process.
For further information please contact your local Endress+Hauser Sales Center.
• The diaphragm seal together with the transmitter form a closed, calibrated system, which is filled through
ports in the diaphragm seal and in the measurement system of the transmitter. These ports are sealed and
must not be opened.
• In the case of devices with diaphragm seals and capillaries, the zero point shift caused by the hydrostatic
pressure of the filling liquid column in the capillaries must be taken into account when selecting the
measuring cell. If a measuring cell with a small measuring range is selected, a position adjustment can cause
an overdrive. See the following diagram and the following example.
• For devices with temperature isolator or capillary a suitable fastening device (mounting bracket) is
recommended.
• When using a mounting bracket, sufficient strain relief must be allowed for in order to prevent the capillary
bending down (bending radius ≥ 100 mm / 4").

Installation instructions for capillaries


In order to obtain more precise measurement results and to avoid a defect in the device, mount the capillaries
as follows:
• vibration-free (in order to avoid additional pressure fluctuations)
• not in the vicinity of heating or cooling lines
• insulate if the ambient temperature is below ore above the reference temperature
• with a bending radius of ≥ 100 mm. (4")

Vacuum applications
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the
diaphragm seal. A vacuum load of the diaphragm seal caused by the presence of fill fluid in the capillary
prevents is hereby prevented.
When the pressure transmitter is mounted above the diaphragm seal, the maximum height difference H1 in
accordance with the following illustration on the left must not be exceeded. The maximum height difference
is dependent on the density of the filling oil and the smallest ever pressure that is permitted to occur at the
diaphragm seal (empty tank), see the following illustration, on the right.

39
FIELD TERMINALS

(12) Low temperature oil


33
Height difference H1 ft (m)

(10) Vegetable oil


26
(8)
Silicone oil
H1 20
(6) High temperature
13 oil
(4)

6.5 Inert oil


(2)

0.0
0.7 1.45 2.9 4.3 5.8 7.3 8.7 10.1 11.6 13.0 14.5
(50) (100) (200) (300) (400) (500) (600) (700) (800) (900) (1000)
Pressure at diaphragm seal psia (mbarabs)

P01-PMx7xxxx-11-xx-xx-xx-008 P01-PMP75xxx-05-xx-xx-en-011

Installation above the diaphragm seal Diagram of maximum installation height above the diaphragm seal for
vacuum applications

74 Endress+Hauser
Cerabar S

Certificates and approvals


CE mark The device meets the legal requirements of the relevant EC directives.
Endress+Hauser confirms that the device has been successfully tested by applying the CE mark.

Ex approvals • ATEX
• FM
• CSA
• NEPSI
• IECEx
• GOST
• also combinations of different approvals
All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
→ 90 ff, sections "Safety Instructions" and "Installation/Control Drawings".

Suitability for hygenic The Cerabar S is suitable for the employment in hygenic processes.
processes Overview of permitted process connections from page 32.
Many versions meet the requirements of 3A-Sanitary Standard No. 74 and
are certified by the EHEDG.

Note!
The gap-free connections can be cleaned without residue using the usual
cleaning methods.
TYPE EL 74 -
October 2007

Marine certificate • GL
• ABS

Functional Safety SIL / IEC The Cerabar S with 4 to 20 mA output signal have been developed to IEC 61508 standard. These devices can
61508 Declaration of confor- be used for process pressure and level measurement monitoring up to SIL 3.
mity (optional) For a detailed description of the safety functions with Cerabar S, settings and characteristic quantities for
functional safety, please refer to the "Manual for Functional Safety- Cerabar S" SD190.
For devices with SIL / IEC 61508 declaration of conformity see → 77 ff, Feature 100 "Additional option 1"
and Feature 110 "Additional option 2" version E "SIL / IEC 61508, declaration of Conformity".

Overspill protection WHG

CRN approvals Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
(→ 78, feature 70 "Process connection") has to be ordered with a CSA approval (→ 77, feature 10
"Approval"). PMP75 devices with capillary are not CRN-approved. These devices are fitted with a separate plate
bearing the registration number 0F10525.5C.

Pressure Equipment Directive The devices PMC71, PMP71 and PMP75 correspond to Article 3 (3) of the EC directive 97/23/EC (Pressure
(PED) Equipment Directive) and has been designed and manufactured according to good engineering practice.
Additionally applies:
– PMP71 with threaded connection and internal process isolating diaphragm PN > 200 (2900 psi) as well as
oval flange adapter PN > 200 (2900 psi):
Suitable for stable gases in group 1, category I
– PMP75 with pipe diaphragm seal ≥ 1.5"/PN 40 (600 psi):
Suitable for stable gases in group 1, category II
– PMP75 with separator PN > 200 (2900 psi):
Suitable for stable gases in group 1, category 1
– PMP75 with threaded connection PN > 200 (2900 psi)

Endress+Hauser 75
Cerabar S

Standards and guidelines DIN EN 60770 (IEC 60770):


Transmitters for use in industrial-process control systems
Part 1: Methods for inspection and routine testing
DIN 16086:
Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure measuring
instruments, concepts, specifications in data sheets
EN 61326-X:
EMC product family standard for electrical equipment for measurement, control and laboratory use.

Accessories

Block and bleed valves

Part No. Type Description MWP


Block & Bleed Valves
71037610 316 SS Block & Bleed Block & Bleed Valve, hard seat configuration 6,000 psi at 200 F
Valve with Teflon packing Inlet: 1/2" MNPT, Outlet:1/2" FNPT 4,000 psi at 450 F Max
Body: 316 Stainless, 3.1 Mat. Cert. Included
Stem/tip: 316SS/Carbide Ball w/ Nickel Chrome Binder
Seat Material: Integral, Packing: PTFE
71037611 316 SS Block & Bleed Block & Bleed Valve, hard seat configuration 6,000 psi at 200 F
Valve with Grafoil Inlet: 1/2" MNPT, Outlet:1/2" FNPT 1,500 psi at 1,000 F Max
packing Body: 316 Stainless, 3.1 Mat. Cert. Included
Stem/tip: 316SS/Carbide Ball w/ Nickel Chrome Binder
Seat Material: Integral, Packing: grafoil
Assembly to Transmitter
71038037 Valve Assembly Assemble Block & Bleed Valve to transmitter

76 Endress+Hauser
Cerabar S

Ordering information
PMC71 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
E Combi-certification
ATEX II Ex ia + FM IS + CSA IS
ATEX II 1/2G Ex ia IIC T6 +
FM/CSA IS Class I, II, III Division 1 Group A - G
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D Ex ia IIC T6
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d[ia] IIC T6
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
1 R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
G NEPSI Ex d[ia] IIC T4/T6
– + E H NEPSI Ex ia IIC T6
L TIIS Ex d (ia) IIC T6
M TIIS Ex d (ia) IIC T4
I IECEx Zone 0/1 Ex ia IIC T6

20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
B 4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ C 4...20 mA HART, operation inside (→ see Fig.o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (→ see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (→ see Fig. ➀, o)
Q FOUNDATION Fieldbus, operation inside, LCD (→ see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (→ see Fig. o)

30 Housing; Cable entry; Protection:


T14 A Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
E Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
T17 F Aluminum T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover

40 Sensor range; Sensor overload limit (= OPL):


Sensors for gauge pressure
Measurement limits: –100 % (–1 bar)...+100 % of sensor nominal range
Sensor nominal value (URL) OPL (Over pressure limit)
1C 100 mbar/10 kPa/1.5 psi g 4 bar/400 kPa/60 psi g
1E 250 mbar/25 kPa/3.75 psi g 5 bar/500 kPa/75 psi g
1F 400 mbar/40 kPa/6 psi g 8 bar/800 kPa/120 psi g
1H 1 bar/100 kPa/15 psi g 10 bar/1 MPa/150 psi g
1K 2 bar/200 kPa/30 psi g 18 bar/1.8 MPa/270 psi g
1M 4 bar/400 kPa/60 psi g 25 bar/2.5 MPa/375 psi g
1P 10 bar/1 MPa/150 psi g 40 bar/4 MPa/600 psi g
1S 40 bar/4 MPa/600 psi g 60 bar/6 MPa/900 psi g

Endress+Hauser 77
Cerabar S

40 Sensor range; Sensor overload limit (= OPL):


Sensors for absolute pressure
Sensor nominal value (URL) OPL (Over pressure limit)
2C 100 mbar/10 kPa/1.5 psi abs 4 bar/400 kPa/60 psi abs
2E 250 mbar/25 kPa/3.75 psi abs 5 bar/500 kPa/75 psi abs
2F 400 mbar/40 kPa/6 psi abs 8 bar/800 kPa/120 psi abs
2H 1 bar/100 kPa/15 psi abs 10 bar/1 MPa/150 psi abs
2K 2 bar/200 kPa/30 psi abs 18 bar/1.8 MPa/270 psi abs
2M 4 bar/400 kPa/60 psi abs 25 bar/2.5 MPa/375 psi abs
2P 10 bar/1 MPa/150 psi abs 40 bar/4 MPa/600 psi abs
2S 40 bar/4 MPa/600 psi abs 60 bar/6 MPa/900 psi abs

50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification

70 Process connection; Material:


Thread, internal process isolating diaphragm
GA Thread ISO 228 G 1/2 A EN 837, AISI 316L (CRN)
GB Thread ISO 228 G 1/2 A EN 837, Alloy C (CRN)
GC Thread ISO 228 G 1/2 A EN 837, Monel
GD Thread ISO 228 G 1/2 A EN 837, PVDF
(max. 15 bar/225 psi, –10...+60°C/+14...+140°F)
GE Thread ISO 228 G 1/2 A G 1/4 (female), AISI 316L (CRN)
GF Thread ISO 228 G 1/2 A G 1/4 (female), Alloy C (CRN)
GG Thread ISO 228 G 1/2 A G 1/4 (female), Monel
GH Thread ISO 228 G 1/2 A hole 11.4 mm, AISI 316L (CRN)
GJ Thread ISO 228 G 1/2 A hole 11.4 mm, Alloy C (CRN)
GK Thread ISO 228 G 1/2 A hole 11.4 mm, Monel
RA Thread ANSI 1/2 MNPT 1/4 FNPT, AISI 316L (CRN)
RB Thread ANSI 1/2 MNPT 1/4 FNPT, Alloy C (CRN)
RC Thread ANSI 1/2 MNPT 1/4 FNPT, Monel
RD Thread ANSI 1/2 MNPT, hole 11.4 mm, AISI 316L (CRN)
RE Thread ANSI 1/2 MNPT, hole 11.4 mm, Alloy C (CRN)
RF Thread ANSI 1/2 MNPT, hole 11.4 mm, Monel
RG Thread ANSI 1/2 MNPT hole 3 mm, PVDF
(max. 15 bar/225 psi, –10...+60°C/+14...+140°F)
RH Thread ANSI 1/2 FNPT, AISI 316L (CRN)
RJ Thread ANSI 1/2 FNPT, Alloy C (CRN)
RK Thread ANSI 1/2 FNPT, Monel
GL Thread JIS B0202 G 1/2 (male), AISI 316L
RL Thread JIS B0203 R 1/2 (male), AISI 316L
GP Thread DIN 13 M 20x1.5 EN 837 hole 3 mm, AISI 316L
GQ Thread DIN 13 M 20x1.5 EN 837 hole 3 mm, Alloy C
For continuation "Process connection, Material" see next page.
Thread, flush-mounted process isolating diaphragm
1G Thread ISO 228 G 1 1/2 A, AISI 316L
1H Thread ISO 228 G 1 1/2 A, Alloy C
1J Thread ISO 228 G 1 1/2 A, Monel
1K Thread ISO 228 G 2 A, AISI 316L
1L Thread ISO 228 G 2 A, Alloy C
1M Thread ISO 228 G 2 A, Monel
2D Thread ANSI 1 1/2 MNPT, AISI 316L (CRN)
2E Thread ANSI 1 1/2 MNPT, Alloy C (CRN)
2F Thread ANSI 1 1/2 MNPT, Monel
2G Thread ANSI 2 MNPT, AISI 316L (CRN)
2H Thread ANSI 2 MNPT, Alloy C (CRN)
2J Thread ANSI 2 MNPT, Monel
1R Thread DIN 13 M 44x1.25, AISI 316L
1S Thread DIN 13 M 44x1.25, Alloy C
EN/DIN flanges, flush-mounted process isolating diaphragm

78 Endress+Hauser
Cerabar S

70 Process connection; Material:


CP DN 32 PN 10-40 B1, AISI 316L
CQ DN 40 PN 10-40 B1, AISI 316L
BR DN 50 PN 10-16 A, PVDF (max. 15 bar/150 psi, –10...+60°C/+14...+140°F)
B3 DN 50 PN 10-40 B1, AISI 316L
C3 DN 50 PN 63 B2, AISI 316L
BS DN 80 PN 10-16 A, PVDF (max. 15 bar/150 psi, –10...+60°C/+14...+140°F)
B4 DN 80 PN 10-40 B1, AISI 316L
ANSI flanges, flush-mounted process isolating diaphragm
AE 1 1/2" 150 lbs RF, AISI 316/316L (CRN)
AQ 1 1/2" 300 lbs RF, AISI 316/316L (CRN)
AF 2" 150 lbs RF, AISI 316/316L (CRN)
JR 2" 150 lbs RF, AISI 316L with ECTFE-coating
A3 2" 150 lbs RF, PVDF (max. 15 bar/225 psi, –10...+60°C/+14...+140°F)
AR 2" 300 lbs RF, AISI 316/316L (CRN)
AG 3" 150 lbs RF, AISI 316/316L (CRN)
JS 3" 150 lbs RF, AISI 316L with ECTFE-coating
A4 3" 150 lbs RF, PVDF (max. 15 bar/225 psi, –10...+60°C/+14...+140°F)
AS 3" 300 lbs RF, AISI 316/316L (CRN)
AH 4" 150 lbs RF, AISI 316/316L (CRN)
JT 4" 150 lbs RF, AISI 316L with ECTFE-coating
AT 4" 300 lbs RF, AISI 316/316L (CRN)
JIS flanges, flush-mounted process isolating diaphragm
KF 10K 50A RF, AISI 316L
KL 10K 80A RF, AISI 316L
KH 10K 100A RF, AISI 316L
Hygienic connections, flush-mounted process isolating diaphragm
MP DIN 11851 DN 40 PN 25, AISI 316L, EHEDG, 3A with HNBR/EPDM seal (CRN)
MR DIN 11851 DN 50 PN 25, AISI 316L, EHEDG, 3A with HNBR/EPDM seal (CRN)
TD Tri-Clamp ISO 2852 DN 51 (2"), AISI 316L, EHEDG, 3A with HNBR/EPDM seal (CRN)
TF Tri-Clamp ISO 2852 DN 76.1 (3"), AISI 316L, EHEDG, 3A with HNBR/EPDM seal (CRN)
TK DRD DN50 (65 mm), PN 25, AISI 316L, EHEDG, 3A with HNBR/EPDM seal
TR Varivent type N for tubes DN 40 – DN 162, PN 40, AISI 316L, EHEDG,
3A with HNBR/EPDM seal (CRN)

80 Seal:
A FKM Viton
B EPDM
D Kalrez
E Chemraz
F NBR/3A: HNBR (FDA)
L FKM Viton, cleaned for silicone-free service
M Kalrez, cleaned for silicone-free service
1 FKM Viton, cleaned from oil and greace
2 FKM Viton, oxygen service
Note application limits pressure/temp.

100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
T High temperature version
B Material test certificate for wetted parts, inspection certificate as per EN 10204 3.1
acc. to specification 52005759
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL (German Lloyd)/ABS marine certificate
V Mounting on shut-off valve from above
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
T High temperature version
M Overvoltage protection
J Software adjustment, see additional spec.

Endress+Hauser 79
Cerabar S

110 Additional option 2:


N HistoROM/M-DAT
S GL (German Lloyd)/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1
5 Helium leak test EN 1518 with test certificate,
inspection certificate as per EN 10204 3.1

995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.

PMC71 order code

80 Endress+Hauser
Cerabar S

PMP71 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
1
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6
– + E
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
L TIIS Ex d IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II 2 G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates:
ATEX II Ex ia / Ex d + FM/CSA IS + XP
ATEX II 1/2G Ex ia IIC T6+
ATEX II 2G Ex d IIC T6+
FM/CSA IS + XP Cl.I Div.1 Gr.A-D

20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ B
C 4...20 mA HART, operation inside (→ see Fig. o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (→ see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (→ see Fig. ➀, o)
Q FOUNDATION Fieldbus, operation inside, LCD (→ see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (→ see Fig. o)

30 Housing; Cable entry; Protection:


T14
A Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
E Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
F Aluminum T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
T17 2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover

40 Sensor range; Sensor overload limit (= OPL):


Sensors for gauge pressure
Measurement limits: –100 % (–1 bar)...+100 % of sensor nominal range
Sensor nominal value (URL) OPL (Over pressure limit)
1F 400 mbar/40 kPa/6 psi g 6 bar/600 kPa/90 psi g
1H 1 bar/100 kPa/15 psi g 10 bar/1 MPa/150 psi g
1K 2 bar/200 kPa/30 psi g 20 bar/2 MPa/300 psi g

Endress+Hauser 81
Cerabar S

40 Sensor range; Sensor overload limit (= OPL):


1M 4 bar/400 kPa/60 psi g 28 bar/2.8 MPa/420 psi g
1P 10 bar/1 MPa/150 psi g 40 bar/4 MPa/600 psi g
1S 40 bar/4 MPa/600 psi g 160 bar/16 MPa/2400 psi g
1U 100 bar/10 MPa/1500 psi g 400 bar/40 MPa/6000 psi g
1W 400 bar/40 MPa/6000 psi g 600 bar/60 MPa/9000 psi g
1X 700 bar/70 MPa/10500 psi g 1050 bar/105 MPa/15700 psi g
Sensors for absolute pressure
Sensor nominal value (URL) OPL (Over pressure limit)
2F 400 mbar/40 kPa/6 psi abs 6 bar/600 kPa/90 psi abs
2H 1 bar/100 kPa/15 psi abs 10 bar/1 MPa/150 psi abs
2K 2 bar/200 kPa/30 psi abs 20 bar/2 MPa/300 psi abs
2M 4 bar/400 kPa/60 psi abs 28 bar/2.8 MPa/420 psi abs
2P 10 bar/1 MPa/150 psi abs 40 bar/4 MPa/600 psi abs
2S 40 bar/4 MPa/600 psi abs 160 bar/16 MPa/2400 psi abs
2U 100 bar/10 MPa/1500 psi g 400 bar/40 MPa/6000 psi g
2W 400 bar/40 MPa/6000 psi g 600 bar/60 MPa/9000 psi g
2X 700 bar/70 MPa/10500 psi g 1050 bar/105 MPa/15700 psi g

50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification

60 Membrane material:
1 AISI 316L
2 Alloy C276
6 AISI 316L with Gold-Rhodium coating

70 Process connection; Material:


Thread, internal process isolating diaphragm
GA Thread ISO 228 G 1/2 A EN 837, AISI 316L
GB Thread ISO 228 G 1/2 A EN 837, Alloy C
GE Thread ISO 228 G 1/2 A G 1/4 (female), AISI 316L
GF Thread ISO 228 G 1/2 A G 1/4 (female), Alloy C
GH Thread ISO 228 G 1/2 A hole 11.4 mm, AISI 316L
GJ Thread ISO 228 G 1/2 A hole 11.4 mm, Alloy C
RA Thread ANSI 1/2 MNPT 1/4 FNPT, AISI 316L (CRN)
RB Thread ANSI 1/2 MNPT 1/4 FNPT, Alloy C (CRN)
RD Thread ANSI 1/2 MNPT hole, AISI 316L (CRN)
RE Thread ANSI 1/2 MNPT hole, Alloy C (CRN)
RH Thread ANSI 1/2 FNPT, AISI 316L
RJ Thread ANSI 1/2 FNPT, Alloy C (CRN)
GL Thread JIS B0202 G 1/2 (male), AISI 316L
RL Thread JIS B0203 R 1/2 (male), AISI 316L
For continuation "Process connection; Material", see next page.
Thread, internal process isolating diaphragm (continued)
GP Thread DIN 13 M 20x1.5 EN 837 hole 11.4 mm, AISI 316L
GQ Thread DIN 13 M 20x1.5 EN 837 hole 11.4 mm, Alloy C
Thread, flush-mounted process isolating diaphragm
1A Thread ISO 228 G 1/2 A, DIN 3852, AISI 316L
1B Thread ISO 228 G 1/2 A, DIN 3852, Alloy C
1D Thread ISO 228 G 1 A, AISI 316L
1E Thread ISO 228 G 1 A, Alloy C
1G Thread ISO 228 G 1 1/2 A, AISI 316L
1H Thread ISO 228 G 1 1/2 A, Alloy C
1K Thread ISO 228 G 2 A, AISI 316L
1L Thread ISO 228 G 2 A, Alloy C
2A Thread ANSI 1 MNPT, AISI 316L (CRN)
2B Thread ANSI 1 MNPT, Alloy C (CRN)
2D Thread ANSI 1 1/2 MNPT, AISI 316L (CRN)
2E Thread ANSI 1 1/2 MNPT, Alloy C (CRN)

82 Endress+Hauser
Cerabar S

70 Process connection; Material:


2G Thread ANSI 2 MNPT, AISI 316L (CRN)
2H Thread ANSI 2 MNPT, Alloy C (CRN)
1N Thread DIN 16288 M 20x1.5, AISI 316L
1P Thread DIN 16288 M 20x1.5, Alloy C
1R Thread DIN 13 M 44x1.25, AISI 316L
1S Thread DIN 13 M 44x1.25, Alloy C
EN/DIN flanges, flush-mounted process isolating diaphragm
CN DN 25 PN 10-40 B1, AISI 316L
CP DN 32 PN 10-40 B1, AISI 316L
CQ DN 40 PN 10-40 B1, AISI 316L
B3 DN 50 PN 10-40 B1, AISI 316L
B4 DN 80 PN 10-40 B1, AISI 316L
ANSI flanges, flush-mounted process isolating diaphragm
AN 1" 300 lbs RF, AISI 316/316L (CRN)
AE 1 1/2" 150 lbs RF, AISI 316/316L (CRN)
AQ 1 1/2" 300 lbs RF, AISI 316/316L (CRN)
AF 2" 150 lbs RF, AISI 316/316L (CRN)
AR 2" 300 lbs RF, AISI 316/316L (CRN)
AG 3" 150 lbs RF, AISI 316/316L (CRN)
AS 3" 300 lbs RF, AISI 316/316L (CRN)
AH 4" 150 lbs RF, AISI 316/316L (CRN)
AT 4" 300 lbs RF, AISI 316/316L (CRN)
JIS flanges, flush-mounted process isolating diaphragm
KA 20K 25A RF, AISI 316L
KF 10K 50A RF, AISI 316L
KL 10K 80A RF, AISI 316L
KH 10K 100A RF, AISI 316L
Other
UR Ovalflange adapter 1/4-18 NPT, mounting: 7/16-20 UNF, AISI 316L (CRN)
U1 Prepared for diaphragm seal mount, AISI 316L (CRN)

90 Fill fluid:
A Silicone oil fill
F Inert oil fill
K Inert oil fill, cleaned from oil and greace
N Inert oil fill, cleaned for oxygen services
(Note application limits pressure/temperature)

100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted parts, inspection certificate as per
EN 10204 3.1 acc. to specification 52005759
C NACE MR0175 (wetted parts)
D Material test certificate for wetted parts as per EN 10204 3.1 and NACE
MR0175 material, inspection certificate as per EN 10204 acc. to specification
52010806
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL (German Lloyd)/ABS marine certificate
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL (German Lloyd)/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204
3.1
5 Helium leak test EN 1528 with test certificate, inspection certificate as
per EN 10204 3.1

Endress+Hauser 83
Cerabar S

995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.

PMP71 order code

84 Endress+Hauser
Cerabar S

PMP75 This overview does not mark options which are mutually exclusive.

10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
1
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6

7 ATEX II 3 G Ex nA II T6
+ E

S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
L TIIS Ex d IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II 2 G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates:
ATEX II Ex ia / Ex d + FM/CSA IS + XP
ATEX II 1/2G Ex ia IIC T6+
ATEX II 2G Ex d IIC T6+
FM/CSA IS + XP Cl.I Div.1 Gr.A-D

20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ B
C 4...20 mA HART, operation inside (→ see Fig. o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC

O PROFIBUS PA, operation inside (→ see Fig. o)


P FOUNDATION Fieldbus, operation outside, LCD (→ see Fig. ➀, o)
Q FOUNDATION Fieldbus, operation inside, LCD (→ see Fig. ➀, o)
R FOUNDATION Fieldbus, operation inside (→ see Fig. o)

30 Housing; Cable entry; Protection:


T14 A Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
B Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
C Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
D Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug,
T17 E Aluminum T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
F Aluminum T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
1 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Gland M 20x1.5
2 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread G 1/2
3 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, Thread 1/2 NPT
4 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, M 12x1 PA plug
5 AISI 316L T14 housing, optional display on the side, IP 66/67/NEMA 4X/ 6P, 7/8" FF plug
6 AISI 316L T14 housing, optional display on the side, IP 65/NEMA 4X, Hand 7D plug 90°
R T17 316L Hygiene IP66/68 NEMA6P; M20 gland, T17 = side cover
S T17 316L Hygiene IP66/68 NEMA6P; G1/2 thread, T17 = side cover
T T17 316L Hygiene IP66/68 NEMA6P; NPT1/2 thread, T17 = side cover
U T17 316L Hygiene IP66/68 NEMA6P; M12 plug, T17 = side cover
V T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover

40 Sensor range; Sensor overload (= OPL):


Sensors for gauge pressure
Measurement limits: –100 % (–1 bar)...+100 % of sensor nominal range
Sensor nominal value (URL) OPL (Over pressure limit)
1F 400 mbar/40 kPa/6 psi 6 bar/600 kPa/90 psi
1H 1 bar/100 kPa/15 psi 10 bar/1 MPa/150 psi
1K 2 bar/200 kPa/30 psi 20 bar/2 MPa/300 psi

Endress+Hauser 85
Cerabar S

40 Sensor range; Sensor overload (= OPL):


1M 4 bar/400 kPa/60 psi 28 bar/2.8 MPa/420 psi
1P 10 bar/1 MPa/150 psi 40 bar/4 MPa/600 psi
1S 40 bar/4 MPa/600 psi 160 bar/16 MPa/2400 psi
1U 100 bar/10 MPa/1500 psi 400 bar/40 MPa/6000 psi
1W 400 bar/40 MPa/6000 psi 600 bar/60 MPa/9000 psi
Sensors for absolute pressure
Sensor nominal value (URL) OPL (Over pressure limit)
2F 400 mbar/40 kPa/6 psi abs 6 bar/600 kPa/90 psi abs
2H 1 bar/100 kPa/15 psi abs 10 bar/1 MPa/150 psi abs
2K 2 bar/200 kPa/30 psi abs 20 bar/2 MPa/300 psi abs
2M 4 bar/400 kPa/60 psi abs 28 bar/2.8 MPa/420 psi abs
2P 10 bar/1 MPa/150 psi abs 40 bar/4 MPa/600 psi abs
2S 40 bar/4 MPa/600 psi abs 160 bar/16 MPa/2400 psi abs
2U 100 bar/10 MPa/1500 psi abs 400 bar/40 MPa/6000 psi abs
2W 400 bar/40 MPa/6000 psi abs 600 bar/60 MPa/9000 psi abs

50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD calibration: see additional specification

60 Membrane material:
1 AISI 316L
2 Alloy C276
3 Monel
5 Tantal
6 AISI 316L with Gold-Rhodium coating
7 AISI 316L with 0.09 mm PTFE foil (not for vacuum applications)
8 AISI 316L with 0.25 mm PTFE foil (not for vacuum applications, only for non-hazardous areas)

70 Process connection, Material:


Thread, flush-mounted process isolating diaphragm
1D Thread ISO 228 G 1 A, AISI 316L
1E Thread ISO 228 G 1 A, Alloy C
1G Thread ISO 228 G 1 1/2 A, AISI 316L
1H Thread ISO 228 G 1 1/2 A, Alloy C
1K Thread ISO 228 G 2 A, AISI 316L
1L Thread ISO 228 G 2 A, Alloy C
2A Thread ANSI 1 MNPT, AISI 316L
2B Thread ANSI 1 MNPT, Alloy C (CRN)
2D Thread ANSI 1 1/2 MNPT, AISI 316L (CRN)
2E Thread ANSI 1 1/2 MNPT, Alloy C (CRN)
2G Thread ANSI 2 MNPT, AISI 316L
2H Thread ANSI 2 MNPT, Alloy C (CRN)
Clamp connections
TB Tri-Clamp, ISO 2852 DN 25 (1"), DIN 32676 DN 25, AISI 316L (CRN), EHEDG
TC Tri-Clamp, ISO 2852 DN 38 (1 1/2"), DIN 32676 DN 40, AISI 316L (CRN), EHEDG
TD Tri-Clamp, ISO 2852 DN 40 – DN 51 (2")/DN 50, AISI 316L (CRN), EHEDG
TF Tri-Clamp, ISO 2852 DN 70 – DN 76.1 (3"), AISI 316L (CRN), EHEDG
Pipe diaphragm seal, Clamp
SB Tri-Clamp, ISO 2852 DN 25 (1"), AISI 316L (CRN)
SC Tri-Clamp, ISO 2852 DN 38 (1 1/2"), AISI 316L, 3.1 +
Pressure test acc. to PED Cat.II (CRN)
SD Tri-Clamp, ISO 2852 DN 51 (2"), AISI 316L, 3.1 + Pressure test acc. to PED Cat.II
(CRN)
Hygienic connections
MR DIN 11851 DN 50 PN 25, AISI 316L, EHEDG
MS DIN 11851 DN 65 PN 25, AISI 316L, EHEDG
MT DIN 11851 DN 80 PN 25, AISI 316L, EHEDG
M3 DIN 11851 DN 50 PN 25 thread, AISI 316L, EHEDG
M4 DIN 11851 DN 65 PN 25 thread, AISI 316L, EHEDG
M5 DIN 11851 DN 80 PN 25 thread, AISI 316L, EHEDG
TG SMS 1" PN 25, AISI 316L, EHEDG
TH SMS 1 1/2" PN 25, AISI 316L, EHEDG
TI SMS 2" PN 25, AISI 316L, EHEDG

86 Endress+Hauser
Cerabar S

70 Process connection, Material:


TL APV-RJT 1" PN 40, AISI 316L
TM APV-RJT 1 1/2" PN 40, AISI 316L
TN APV-RJT 2" PN 40, AISI 316L
TP APV-ISS 1" PN 40, AISI 316L
TQ APV-ISS 1 1/2" PN 40, AISI 316L
TS APV-ISS 2" PN 40, AISI 316L
TK DRD DN50 (65 mm) PN 25, AISI 316L
TR Varivent Type N for pipes DN 40 – DN 162 PN 40, AISI 316L, EHEDG
EN/DIN flanges, flush-mounted process isolating diaphragm
CN DN 25 PN 10-40 B1, AISI 316L
DN DN 25 PN 63-160 E, AISI 316L
EN DN 25 PN 250 E, AISI 316L
E1 DN 25 PN 400 E, AISI 316L
CP DN 32 PN 10-40 B1, AISI 316L
CQ DN 40 PN 10-40 B1, AISI 316L
B3 DN 50 PN 10-40 B1, AISI 316L
C3 DN 50 PN 63 B2, AISI 316L 2
EF DN 50 PN 100-160 E, AISI 316L
ER DN 50 PN 250 E, AISI 316L
E3 DN 50 PN 400 E, AISI 316L
B4 DN 80 PN 10-40 B1, AISI 316L
C4 DN 80 PN 100 B2, AISI 316L
C5 DN 100 PN 100 B2, AISI 316L
EN/DIN flanges with extended diaphragm seal, flush-mounted process
isolating diaphragm
D3 DN 50 PN 10-40 B1, Tubus 50 mm/100 mm/200 mm, AISI 316L
D4 DN 80 PN 10-40 B1, Tubus 50 mm/100 mm/200 mm, AISI 316L
ANSI flanges, flush-mounted process isolating diaphragm
AC 1" 150 lbs RF, AISI 316/316L (CRN)
AN 1" 300 lbs RF, AISI 316/316L (CRN)
HC 1" 400/600 lbs RF, AISI 316/316L (CRN)
HN 1" 900/1500 lbs RF, AISI 316/316L (CRN)
H0 1" 2500 lbs RF, AISI 316/316L (CRN)
AE 1 1/2" 150 lbs RF, AISI 316/316L (CRN)
AQ 1 1/2" 300 lbs RF, AISI 316/316L (CRN)
AF 2" 150 lbs RF, AISI 316/316L (CRN)
AR 2" 300 lbs RF, AISI 316/316L (CRN)
HF 2" 400/600 lbs RF, AISI 316/316L (CRN)
HR 2" 900/1500 lbs RF, AISI 316/316L (CRN)
H3 2" 2500 lbs RF, AISI 316/316L (CRN)
AG 3" 150 lbs RF, AISI 316/316L (CRN)
AS 3" 300 lbs RF, AISI 316/316L (CRN)
AH 4" 150 lbs RF, AISI 316/316L (CRN)
AT 4" 300 lbs RF, AISI 316/316L (CRN)
ANSI flanges with extended diaphragm seal
J3 2" 150 lbs RF, Tubus 2"/4"/6"/8", AISI 316/316L (CRN)
J4 3" 150 lbs RF, Tubus 2"/4"/6"/8", AISI 316/316L (CRN)
J7 3" 300 lbs RF, Tubus 2"/4"/6"/8", AISI 316/316L (CRN)
J5 4" 150 lbs RF, Tubus 2"/4"/6"/8", AISI 316/316L (CRN)
J8 4" 300 lbs RF, Tubus 2"/4"/6"/8", AISI 316/316L (CRN)
JIS flanges, flush-mounted process isolating diaphragm
KC 10K 25A RF, AISI 316L
KF 10K 50A RF, AISI 316L
KL 10K 80A RF, AISI 316L
KH 10K 100A RF, AISI 316L
Other
UA Thread ISO 228 G 1/2 A PN 160, seperator, EN 837, welded, AISI 316L
UB Thread ANSI 1/2 MNPT PN 160, seperator, welded, AISI 316L (CRN)
UC Thread ISO 228 G 1/2 B, seperator, EN 837, threaded, AISI 316L
UD Thread ANSI 1/2 MNPT, seperator, threaded, AISI 316L
UG Thread 1/2 NPT PN 250, seperator, threaded, AISI 316L
UH Thread 1 NPT PN 250, seperator, threaded, AISI 316L

90 Fill fluid:
A Silicone oil
B ...m capillary, inert oil
C ...ft capillary, inert oil
D Vegetable oil
F Inert oil

Endress+Hauser 87
Cerabar S

90 Fill fluid:
G High temperature oil, Temp. isolator 100 mm
H Silicone oil, Temp. isolator 100 mm
K Inert oil, cleaned from oil and greace
N Inert oil, cleaned for oxygen services
1 ... m capillary, silicone oil
2 ... ft capillary, silicone oil
3 ... m capillary, high temperature oil
4 ... ft capillary, high temperature oil
5 ... m capillary, vegetable oil
6 ... ft capillary, vegetable oil
7 ... m capillary, Low temperature oil
8 ... ft capillary, Low temperature oil

100 Additional option 1:


A not selected
E SIL/IEC 61508 Declaration of conformity
B Material test certificate for wetted parts, inspection certificate as per EN
10204 3.1 acc. to specification 52005759
C NACE MR0175 (wetted parts)
D Material test certificate for wetted parts, inspection certificate as per EN
10204 3.1 and NACE MR0175 material, inspection certificate as per
EN 10204 acc. to specification 52010806
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
S GL (German Lloyd)/ABS marine certificate
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate, inspection certificate as per EN 10204 3.1

110 Additional option 2:


A not selected
E SIL/IEC 61508 Declaration of conformity
G Separate housing, cable length see additional spec. + mounting bracket,
wall/pipe, 316L
M Overvoltage protection
J Software adjustment, see additional spec.
N HistoROM/M-DAT
P Ra < 0.38 μm/15.75 μin, electropolished +
EN10204-3.1 material (wetted) inspection certificate;
in conjunction with process connection versions "TC", "TD" and "TR"
please order roughness test separetely
S GL (German Lloyd)/ABS marine certificate
U Mounting bracket for wall/pipe, AISI 304
2 Test report acc. to EN 10204 2.2
3 Routine test with certificate, inspection certificate as per EN 10204 3.1
4 Overpressure test with certificate,
inspection certificate as per EN 10204 3.1

995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.

PMP75 order code

88 Endress+Hauser
Cerabar S

Additional documentation
Field of Activities • Pressure measurement, Powerful instruments for process pressure, differential pressure, level and flow:
FA004P/00/en

Technical Information • Deltabar S: TI382P/24/ae


• Deltapilot S: TI416P/24/ae
• EMC test basic principles TI241F/00/en

Operating Instructions 4 to 20 mA HART:


• Cerabar S: BA271P/00/de
• Description of device functions Cerabar S/Deltabar S/Deltapilot S: BA274P/00/en
PROFIBUS PA:
• Cerabar S: BA295P/00/de
• Description of device functions Cerabar S/Deltabar S/Deltapilot S: BA296P/00/en
FOUNDATION Fieldbus:
• Cerabar S: BA302P/00/de
• Description of device functions Cerabar S/Deltabar S: BA303P/00/en

Brief operating instructions • 4 to 20 mA HART, Cerabar S: KA1019P/00/en


• PROFIBUS PA, Cerabar S: KA1022P/00/en
• FOUNDATION Fieldbus, Cerabar S: KA1025P/00/en

Manual for Functional Safety • Cerabar S (4 to 20 mA): SD190P/00/en


(SIL)

Endress+Hauser 89
Cerabar S

Safety Instructions Certificate/Type of Protection Device Electronic insert Documentation Version in the
order code

ATEX II 1/2 G Ex ia IIC T6 PMC71, – 4 to 20 mA HART, – XA244P 1


PMP71, PROFIBUS PA,
PMP75 FOUNDATION Fieldbus

ATEX II 1/2 D PMP71, – 4 to 20 mA HART – XA246P 2


PMP75 – PROFIBUS PA, – XA289P
FOUNDATION Fieldbus

ATEX II 1/2 D Ex ia IIC PMC71 – 4 to 20 mA HART – XA247P 2


– PROFIBUS PA, – XA290P
FOUNDATION Fieldbus

ATEX II 1/3 D PMP71, – 4 to 20 mA HART – XA248P 4


PMP75 – PROFIBUS PA, – XA291P
FOUNDATION Fieldbus

ATEX II 2 G Ex d IIC T6 PMP71, – 4 to 20 mA HART, – XA249P 5


PMP75 PROFIBUS PA,
FOUNDATION Fieldbus

ATEX II 2 G Ex d[ia] IIC T6 PMC71 – 4 to 20 mA HART, – XA250P 5


PROFIBUS PA.,
FOUNDATION Fieldbus

ATEX II 3 G Ex nA II T6 PMC71, – 4 to 20 mA HART, – XA251P 7


PMP71, PROFIBUS PA,
PMP75 FOUNDATION Fieldbus

ATEX II 1/2 GD PMC71, – 4 to 20 mA HART, – XA253P 3


Ex ia IIC T6 PMP71, PROFIBUS PA,
PMP75 FOUNDATION Fieldbus

ATEX II 1 GD Ex ia IIC T6 PMC71, – 4 to 20 mA HART, – XA276P 8


PMP71, PROFIBUS PA,
PMP75 FOUNDATION Fieldbus

ATEX II 1/2 G Ex ia IIC T6 + PMP71, – 4 to 20 mA HART, – XA252P B


ATEX II 2 G Ex d IIC T6 PMP75 PROFIBUS PA,
FOUNDATION Fieldbus

Certificate/Type of Protection Device Electronic insert Documentation Version in the


order code

IECEx Zone 0/1 Ex ia IIC T6 PMC71, – 4 to 20 mA HART – XB005P I


PMP71,
PMP75

Certificate/Type of Protection Device Electronic insert Documentation Version in the


order code

NEPSI Ex ia IIC T6 PMC71, – 4 to 20 mA HART, – XC003P H


PMP71, PROFIBUS PA,
PMP75 FOUNDATION Fieldbus

NEPSI Ex d IIC T6 PMP71, – 4 to 20 mA HART, – XC005P G


PMP75 PROFIBUS PA,
FOUNDATION Fieldbus

NEPSI Ex d[ia] IIC T6 PMC71 – 4 to 20 mA HART, – XC005P G


PROFIBUS PA,
FOUNDATION Fieldbus

90 Endress+Hauser
Cerabar S

Installation/Control Drawings Certificate/Type of Device Electronic Insert Documentation Version in the


Protection order code

FM IS Class I, II, III, PMC71, – 4 to 20 mA HART – ZD147P S


Division 1, Groups A – G; PMP71, – PROFIBUS PA, – ZD188P
NI, Class I Division 2, PMP75 FOUNDATION Fieldbus
Groups A – D; AEx ia

CSA IS Class I, II, III, PMC71, – 4 to 20 mA HART – ZD148P U


Division 1, Groups A – G; PMP71, – PROFIBUS PA, – ZD189P
Class I Division 2, PMP75 FOUNDATION Fieldbus
Groups A – G

FM IS + XP Class , PMP71, – 4 to 20 mA HART – ZD187P C


Division 1, Groups A – D PMP75 – PROFIBUS PA, – ZD190P
FOUNDATION Fieldbus

CSA IS + XP Class I PMP71, – 4 to 20 mA HART – ZD154P D


Division 1, Groups A – D PMP75 – PROFIBUS PA, – ZD191P
FOUNDATION Fieldbus

FM/CSA IS + XP Class I PMP71, – 4 to 20 mA HART – ZD154P + ZD187P E


Division 1, Groups A – D PMP75 – PROFIBUS PA, – ZD190P + ZD191P
FOUNDATION Fieldbus

CSA +XP Class I Division 1, PMP71, – 4 to 20 mA HART – in Vorbereitung -


Groups B - D, Class II PMP75 – PROFIBUS PA,
Division 1, Groups E - G, FOUNDATION Fieldbus
Class III

Overspill protection • WHG: ZE260P/00/de

Endress+Hauser 91
United States Canada Mexico

Endress+Hauser, Inc. Endress+Hauser Canada Endress+Hauser, México, S.A. de C.V.


2350 Endress Place 1075 Sutton Drive Fernando Montes de Oca 21 Edificio A Piso 3
Greenwood, IN 46143 Burlington, ON L7L 5Z8 Fracc. Industrial San Nicolás
Tel. 317-535-7138 Tel. 905-681-9292 54030. Tlalnepantla de Baz
Sales 888-ENDRESS 800-668-3199 Estado de México
(888-363-7377) Fax 905-681-9444 México
Service 800-642-8737 [email protected] Tel: +52 55 5321 2080
fax 317-535-8498 www.ca.endress.com Fax +52 55 5321 2099
[email protected] [email protected]
www.us.endress.com www.mx.endress.com

TI383P/24/ae/12.09
© 2009 Endress+Hauser, Inc.

You might also like