Pressure Transmitter
Pressure Transmitter
TI383P/24/ae/12.09
Cerabar S
Table of contents
2 Endress+Hauser
Cerabar S
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Block and bleed valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 77
PMC71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
PMP71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
PMP75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Additional documentation . . . . . . . . . . . . . . . . . . . . . 89
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Brief operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Manual for Functional Safety (SIL) . . . . . . . . . . . . . . . . . . . . . . . 89
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Overspill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
3 Endress+Hauser
Cerabar S
With capacitive measuring cell and With piezoresistive measuring cell With diaphragm seal
ceramic measuring process isolating and metallic welded process isolating
diaphragm (Ceraphire®) diaphragm
Process connections – Diverse thread – Diverse thread – Wide range of diaphragm seals, → see
– DN 32 – DN 80 – DN 25 – DN 80 the following section "Overview of
– ANSI 1 1/2" – 4" – ANSI 1 1/2" – 4" diaphragm seal for PMP 75"
– JIS 50 A – 100 A – JIS 25 A – 100 A
– Oval flange adapter
– Prepared for diaphragm seal mount
Measuring ranges from -100/0 to 100 mbar from -100/0 to 100 mbar from -400/0 to 400 mbar
(-1.5/0 to 1.5 psi) (-1.5 to 1.5 psi) (-6/0 to 6 psi)
to -1/0 to 40 bar to -1/0 to 700 bar to -1/0 to 400 bar
(-14.5/0 to 600 psi) (-14.5/0 to 10,150 psi) (-14.5/0 to 6000 psi)
OPL 1 max. 60 bar (870 psi) max. 1050 bar (15,200 psi) max. 600 bar (8700 psi)
2
Process temperature range –25 to +125°C/–20 to +150°C –40 to +125°C -70 to 400°C (-94 to +752°F)
(–13 to +257°F/–4 to +302°F) (–40 to +257°F)
Ambient temperature range –40 to +85°C (–40 to +185°F) –40 to +85°C (–40 to +185°F) 3 –40 to +85°C (–40 to +185°F)
Reference accuracy – Up to ±0.075% of the set span Up to ±0.075% of the set span
– PLATINUM version: up to ±0.05% of the set span
Specialities – Metal-free measurement with PVDF – Oil volume-minimized process – Wide range of diaphragm seals
connection connections – For high media temperatures
– Cleaning of the transmitter for the use – gas-tight, elastomer-free – Oil volume-minimized process
in paint shops connections
– Completely welded versions
1) OPL = Over pressure limit; dependent on the lowest-rated element, with regard to pressure, of the selected components
2) High temperature version "T" for feature 100 "Additional option 1" or for feature 110 "Additional option 2"
3) lower temperature on request
4 Endress+Hauser
Cerabar S
Measuring principle
Ceramic process isolating diaphragm used for PMC71 (Ceraphire®) Metallic process isolating diaphragm used for PMP71 and PMP75
1 2 3
1
2
4 3
4
p p
P01-PMC71xxx-03-xx-xx-xx-000 P01-PMP7xxxx-03-xx-xx-xx-000
PMP71
The operating pressure deflects the process isolating diaphragm and a fill fluid transfers the pressure to a
resistance measuring bridge (semi-conductor technology). The pressure-dependent change of the bridge output
voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 700 bar (10,150 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Second process barrier (Secondary Containment) for enhanced integrity
• Significantly less thermal effect compared to diaphragm seal systems
PMP75
The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is transferred to the
process isloating diaphragm of the sensor by a diaphragm seal fill fluid. The process isolating diaphragm is
deflected and a fill fluid transfers the pressure to a resistance measuring bridge. The pressure-dependent change
of the bridge output voltage is measured and evaluated.
Advantages:
• Can be used for process pressure up to 400 bar (5800 psi)
• High long-term stability
• Guaranteed overload resistance up to 4 times the nominal pressure
• Second process barrier (Secondary Containment) for enhanced integrity
Endress+Hauser 5
Cerabar S
p
h= ρ g
P01-PMx7xxxx-15-xx-xx-xx-000
Your benefits
• Choice of three level operating modes in the device software
• Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve
• Choice of diverse level units with automatic unit conversion
• A customised unit can be specified
• Has a wide range of uses, as well
– in the event of foam formation
– in tanks with agitators of screen fittings
– in the event of liquid gases
6 Endress+Hauser
Cerabar S
Input
Measured variable Absolute pressure and gauge pressure, from which level (level, volume or mass) is derived
Measuring range PMC71 – with ceramic process measuring diaphragm (Ceraphire®) for gauge pressure
bar (psi) bar (psi) bar (psi) bar (psi) bar (psi) barabs (psia)
100 mbar –0.1 (-1.5) +0.1 (+1.5) 0.005 (0.07) 2.7 (39) 4 (60) 0.7 (10.1) 1C
250 mbar –0.25 (-3.75) +0.25 (+3.75) 0.005 (0.07) 3.3 (48) 5 (80) 0.5 (7.3) 1E
400 mbar (6 psi) –0.4 (-6) +0.4 (+6) 0.005 (0.07) 5.3 (77) 8 (120) 0 1F
40 bar (600 psi) –1 (-15) +40 (+600) 0.4 (6) 40 (600) 60 (900) 0 1S
PMC71 – with ceramic process measuring diaphragm (Ceraphire®) for absolute pressure
barabs (psia) barabs (psia) bar (psi) barabs (psia) barabs (psia)
100 mbar(1.5 psi) 0 +0.1 (+1.5) 0.005 (0.07) 2.7 (39) 4 (60) 2C
250 mbar (4 psi) 0 +0.25 (+3.75) 0.005 (0.07) 3.3 (48) 5 (80) 2E
400 mbar (6 psi) 0 +0.4 (+6) 0.005 (0.07) 5.3 (77) 8 (120) 2F
10 bar (150 psi) 0 +10 (+150) 0.1 (1.5) 26.7 (387) 40 (600) 2P
1) The MWP (maximum working pressure) for the measuring device depends on the weakest element of the
components selected with regard to pressure, i.e. the process connection (→ 32 ff) has to taken into consideration
in addition to the sensor (→ see Table above). Pay attention to the pressure-temperature dependence also. For the
appropriate standards and further information, see → 31, "Pressure specification".
2) OPL: Over Pressure Limit; depends on the weakest link in terms of pressure of the selected components.
3) Versions in the order code → 77 ff, feature 40 "Sensor range; Sensor overload limit (= OPL)"
4) Turn down > 100:1 on request or can be set at the device
Endress+Hauser 7
Cerabar S
PMP71 and PMP75 – with metallic process isolating diaphragm for gauge pressure
bar (psi) bar (psi) bar (psi) barrel (psi) barrel (psi) barabs (psia)
400 mbar (6 psi) –0.4 (-6) +0.4 (6) 0.005 (0.07) 4 (60) 6 (90) 0.01/0.04 (0.14/0.58) 1F
1 bar (15 psi) –1 (-15) +1 (15) 0.01 (0.15) 6.7 (100) 10 (150) 0.01/0.04 (0.14/0.58) 1H
2 bar (30 psi) –1 (-15) +2 (30) 0.02 (0.30) 13.3 (200) 20 (300) 0.01/0.04 (0.14/0.58) 1K
4 bar (60 psi) –1 (-15) +4 (60) 0.04 (0.6) 18.7 (270) 28 (400) 0.01/0.04 (0.14/0.58) 1M
10 bar (150 psi) –1 (-15) +10 (150) 0.1 (1.5) 26.7 (400) 40 (600) 0.01/0.04 (0.14/0.58) 1P
40 bar (600 psi) –1 (-15) +40 (600) 0.4 (6) 100 (1500) 160 (2320) 0.01/0.04 (0.14/0.58) 1S
PMP71 and PMP75 – with metallic process isolating diaphragm for absolute pressure
400 mbar (6 psi) 0 +0.4 (6) 0.005 (0.07) 4 (60) 6 (90) 0.01/0.04 (0.14/0.58) 2F
1 bar (15 psi) 0 +1 (15) 0.01 (0.15) 6.7 (100) 10 (150) 0.01/0.04 (0.14/0.58) 2H
2 bar (30 psi) 0 +2 (30) 0.02 (0.30) 13.3 (200) 20 (300) 0.01/0.04 (0.14/0.58) 2K
4 bar (60 psi) 0 +4 (60) 0.04 (0.6) 18.7 (270) 28 (400) 0.01/0.04 (0.14/0.58) 2M
10 bar (150 psi) 0 +10 (150) 0.1 (1.5) 26.7 (400) 40 (600) 0.01/0.04 (0.14/0.58) 2P
40 bar (600 psi) 0 +40 (600) 0.4 (6) 100 (1500) 160 (2320) 0.01/0.04 (0.14/0.58) 2S
1) The MWP (maximum working pressure) for the measuring device depends on the weakest element of the
components selected with regard to pressure, i.e. the process connection (→ 32 ff) has to taken into consideration
in addition to the sensor (→ see Table above). Pay attention to the pressure-temperature dependence. For the
appropriate standards and further information, → 31, "Pressure specifications".
2) OPL: Over pressure limit (= Sensor overload limit)
3) The vacuum resistance applies to the measuring cell at a reference conditions. The pressure and temperature
application limits of the selected filling oil must also be observed for the PMP75. → 69, section "Diaphragm seal
filling oils".
4) Versions in the order code → 77 ff, feature 40 "Sensor range; Sensor Overload limit (= OPL)"
5) Turn down > 100:1 on request or can be set at the device
6) PMP71 only, PMP75 on request
8 Endress+Hauser
Cerabar S
Case 1:
• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value (URV)⏐ 1 = 2
Case 2:
• ⏐Lower range value (LRV)⏐ ≤ ⏐Upper range value (URV)⏐ 1 = 2
Example: LRL LRV URV URL
• Lower range value (LRV) = 0 bar
• Upper range value (URV) = 0.5 bar (7 psi) –14.5 psi 0 7 psi +14.5 psi
(–1 bar) (0.5 bar) (+1 bar)
• Nominal value (URL) = 1 bar (14.5 psi)
Turn down:
3
• TD = URL / ⏐URV⏐ = 2:1
set span: 4
• URV – LRV = 0.5 bar (7 psi)
This span is based on the zero point.
5
P01-PMx7xxxx-05-xx-xx-xx-007
Case 3:
• ⏐Lower range value⏐ ≥ ⏐Upper range value⏐ 1 = 2
Example: LRL LRV URV URL
• Lower range value (LRV) = –0.6 bar (-8 psi)
• Upper range value (URV) = 0 bar -14.5 psi -8 psi 0 +14.5 psi
• Nominal value (URL) = 1 bar (14.5 psi) (-1 bar) (-0.6 bar) (+1 bar)
Turn down:
• TD = URL / ⏐LRV⏐ = 1.67:1 3
set span:
4
• URV – LRV = 0.6 bar (8 psi)
This span is based on the zero point.
5
P01-PMx7xxxx-05-xx-xx-xx-008
Endress+Hauser 9
Cerabar S
Output
Output signal • 4...20 mA with superimposed digital communication protocol HART 5.0, 2-wire
• Digital communication signal PROFIBUS PA (Profile 3.0)
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
• Digital communication signal FOUNDATION Fieldbus, 2-wire
– signal coding: Manchester Bus Powered (MBP); Manchester II
– data transmission rate: 31.25 KBit/s, voltage mode
Load – 4 to 20 mA HART
1 R Lmax R Lmax £
U – 10.5 V 2 R Lmax R Lmax £
U – 11.5 V
23 mA 23 mA
[W] [W]
Test 1500 Test
1456
1282 1239
847 804
4
413 4
369
3 3
10.5 20 30 40 45 U 11.5 20 30 40 45 U
[V] [V]
U – 11 V U – 12 V
R Lmax R Lmax £ R Lmax R Lmax £
23 mA 23 mA
[W] [W]
1478 1434
1260 1217
826 782
5 5
391 347
11 20 30 40 45 U 12 20 30 40 45 U
[V] [V]
P01-PMx7xxxx-05-xx-xx-xx-003
Load diagram, observe the position of the jumper and the explosion protection. (→ 17, section "Measuring the 4 to 20
mA test signal" .)
1 Jumper for the 4 to 20 mA test signal inserted in "Non-test" position
2 Jumper for the 4 to 20 mA test signal inserted in "Test" position
3 Supply voltage 10.5 (11.5) to 30 V DC for 1/2 G, 1 GD, 1/2 GD, FM IS, CSA IS, IECEx ia, NEPSI Ex ia
4 Supply voltage10.5 (11.5) to 45 V DC for devices for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA,
FM XP, FM DIP, FM NI, CSA XP, CSA Dust-Ex, NEPSI Ex d
5 Supply voltage 11 (12) to 45 V DC for PMC71, Ex d[ia], NEPSI Ex d[ia]
RLmax Maximum load resistance
U Supply voltage
Note!
When operating via a handheld terminal or via PC with an operating program, a minimum communication
resistance of 250 Ω must exist within the loop.
10 Endress+Hauser
Cerabar S
I
100 %
90 %
63 %
t1 t2 t
P01-xxxxxxxx-05-xx-xx-xx-007
PMC71 90 ms 120 ms
PMC71 90 ms 120 ms
Reading cycle
• HART commands: on average 3 to 4 per second on average.
The Cerabar S commands the BURST MODE functionfor cyclic value transmission via the HART
communication protocol.
Response time
≤ 250 ms
Endress+Hauser 11
Cerabar S
Response time
• cyclic: approx. 10 ms per request
• acyclic: < 50 ms
All values are typical values.
Reading cycle
• cyclic: up to 5/s, dependent on the number and type of function blocks used in a closed-control loop
• acyclic: 10/s
Response time
• cyclic: < 80 ms
• acyclic: < 40 ms
All values are typical values.
12 Endress+Hauser
Cerabar S
DD Revision 01 (hex)
Number VCRs 44
Permanent Entries 44
Client VCRs 0
Server VCRs 5
Source VCRs 8
Sink VCRs 0
Subscriber VCRs 12
Publisher VCRs 19
Link Settings
Slot time 4
Transducer Blocks
TRD1 Block contains all parameters related to the measurement • Pressure or level (channel 1)
• Process temperature (channel 2)
Diagnostic Block contains diagnostic information Error code via DI channels (channel 0 to
16)
Display Block contains parameters to configure the local display no output values
Endress+Hauser 13
Cerabar S
Function Blocks
Resource Block The Resource Block contains all the data that enhanced
uniquely identifies the field device. It is an elec-
tronic version of a nameplate of the device.
Analog Input The AI block takes the manufacturer's input data, 45 ms enhanced
Block 1 selected by channel number, and makes it avail-
Analog Input able to other function blocks at its output.
Block 2 Enhancement: digital outputs for process alarms,
fail safe mode
Digital Input This block contains the discrete data of the diag- 40 ms standard
Block nose block (selectable via a channel number 0 to
16) and provides them for the blocks at the out-
put.
Digital Output This block converts the discrete input and thus 60 ms standard
Block initiates an action (selectable via a channel num-
ber) in the dp flow block or in the service block.
Channel 1 resets the counter for max. pressure
transgressions..
Arithmetic Block This block is designed to permit simple use of pop- 50 ms standard
ular measurement math functions. The user does
not have to know how to write equations. The
math algorithm is selected by name, chosen by the
user for the function to be done.
Signal Charac- The signal characterizer block has two sections, 30 ms standard
terizer Block each with an output that is a non-linear function
of the respective input. The non-linear function is
determined by a single look-up table with 21 arbi-
trary x-y pairs.
Analog Alarm This block contains all process alarm conditions 35 ms standard
Block (working like a comparator) and represents them
at the output.
14 Endress+Hauser
Cerabar S
Power supply
Electrical connection Note!
• When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions or Installation or Control Drawings.
→ 90 ff, sections "Safety Instructions" and "Installation/Control Drawings".
• Devices with integrated overvoltage protection must be earthed. → 29.
• Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
4...20 mA HART
1 6 10.5 V DC
7 11.5 V DC
4 to 20 mA
Test
Test
3 5
8
4 to 20mA Test
4
P01-xMx7xxxx-04-xx-xx-xx-001
PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA034S
"Guidelines for planning and commissioning PROFIBUS DP/PA" and the PNO Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA034S
Guidelines for planning and commissioning PROFIBUS DP/PA", PNO Guideline 2.092 "
PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
Endress+Hauser 15
Cerabar S
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the
auxiliary energy. For further information on the network structure and grounding and for further bus system
components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA013S
"FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Cable specifications:
• Use a twisted, shielded two-wire cable, preferably cable type A
Note!
For further information on the cable specifications, see Operating Instructions BA013S "FOUNDATION
Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
+
+ –
– 8
7
6
1
2 5
Han7D 3 4
+–
P01-PMx7xxxx-04-xx-xx-xx-001
+ – – +
M12
+– P01-PMx7xxxx-04-xx-xx-xx-000
Endress+Hauser offers for devices with M12 plug the following accessories:
Plug-in jack M 12x1, straight
• Material: Body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: Body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP67
• Order number: 51006327
Cable 4x0.34 mm2 with M12 socket, elbowed, screw plug, 5 m length
• Material: Body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP67
• Order number: 52010285
16 Endress+Hauser
Cerabar S
–
+ –
7/8” +
+–
P01-xxx7xxxx-04-xx-xx-xx-003
Cabel gland
Terminals
for wire cross-sections of 0.5 to 2.5 mm2 (20 to 14 AWG)
Endress+Hauser 17
Cerabar S
4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position (delivery status):
11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position: 10.5 to 45 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Residual ripple Without influence on 4 to 20 mA signal up to ± 5% residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
18 Endress+Hauser
Cerabar S
Uncertainty of measurement The smallest extended uncertainty of measurement that can be returned by our standards is:
for small absolute pressure • 0.4% of the set span in the range of 1 to 30 mbar (0.01 to 0.4 psi) and
ranges • 1% of the set span in the range < 1 mbar (0.01psi).
Note!
Position-dependent zero shift can be corrected. → 24, section "General installation instructions" and → 74
ff section "Installation instructions".
Endress+Hauser 19
Cerabar S
Platinum version:
1 bar, 2 bar, 4 bar, 10 bar • TD 1:1 = ±0.05 • TD 1:1 = ±0.05
(15, 30, 60, 150 psi)
Total performance – PMC71 The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as
well as the thermal change of the zero point.
% of URL
All specifications apply to the temperature range –10 to +60°C (+14 to +140°F).
Total Error - PMC71 The total error comprises the long-term stability and the total performance:
% of URL/year
20 Endress+Hauser
Cerabar S
Endress+Hauser 21
Cerabar S
10 bar, 40 bar Gauge pressure/ • TD 1:1 to TD 15:1 = ±0.075 • TD 1:1 to TD 15:1 = ±0.075
(150, 600 psi) Absolute pressure • TD > 15:1 = ±0.005 x TD • TD > 15:1 = ±0.005 x TD
100 bar Gauge pressure/ • TD 1:1 to TD 10:1 = ±0.075 • TD 1:1 to TD 10:1 = ±0.075
(1500 psi) Absolute pressure • TD > 10:1 = ±0.0075 x TD • TD > 10:1 = ±0.0075 x TD
400 bar Gauge pressure/ • TD 1:1 to TD 5:1 = ±0.15 • TD 1:1 to TD 5:1 = ±0.15
(6000 psi) Absolute pressure • TD > 5:1 = ±0.03 x TD • TD > 5:1 = ±0.03 x TD
1) Platinum version not for flush-mounted process connections G 1/2 and M20.
Total performance – PMP71 The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as
well as the thermal change of the zero point.
% of URL
All specifications apply to the temperature range –10 to +60°C (+14 to +140°F).
22 Endress+Hauser
Cerabar S
Total Error - PMP71 The total error comprises the long-term stability and the total performance:
Note!
When using a PMP75, the influence from the respective diaphragm seal must be taken into account.
(→ 68 ff "Planning instructions, diaphragm seal systems" and → 47 ff "Process connections PMP75 (with
metallic process isolating diaphragm)").
Endress+Hauser 23
Cerabar S
Installation instructions for Cerabar S transmitters without diaphragm seal are mounted as per the norms for a manometer (DIN EN 837-
devices without diaphragm 2). We recommend the use of shut-off devices and siphons. The orientation depends on the measuring
seal – PMC71 and PMP71 application.
Level measurement
• Mount Cerabar S below the lowest measuring point.
• Do not mount the device at the following positions:
In the fill flow, in the tank outlet or at a point in the container which could be affected by pressure pulses
from an agitator or a pump.
• The calibration and functional test can be carried out more easily if you mount the device after a shut-off
device.
Heat insulation – The PMC71 high temperature version and the PMP75 must only be insulated up to a certain height. The
PMC71 high temperature maximum permitted insulation height is labelled on the devices and applies to an insulation material with a
version and PMP75 heat conductivity ≤ 0.04 W/(m x K) and to the maximum permitted ambient and process temperature (→ see
table below). The data were determined under the most critical application "quiescent air".
l £ 0.04 W
TA m•K
TP
P01-PMx7xxxx-11-xx-xx-xx-010
Process temperature (TP) ≤ 150°C (302°F) max. 350°C (662°F), depending on the
diaphragm seal filling oil used (→ 69)
24 Endress+Hauser
Cerabar S
Mounting with temperature Endress+Hauser recommends the use of temperature isolators in the event of constant extreme fluid
isolator temperatures which lead to the maximum permissible ambient temperature of +85°C (+185°F) being
exceeded. Depending on the filling oil used, Cerabar S devices with temperature isolators can be used for
maximum temperatures of up to 260°C (+500°F). → For the temperature application limits of filling oils,
→ 69, "Diaphragm seal filling oil" section.
To minimize the influence of rising heat, Endress+Hauser recommends the device be mounted horizontally or
with the housing pointing downwards.
The additional installation height also brings about a zero point shift of maximum 21 mbar (0.3 psi) due to the
hydrostatic columns in the temperature isolator. The position-dependent zero shift can be corrected.
max.
4.53”
(115)
P01-PMx7xxxx-11-xx-xx-xx-005
Wall and pipe-mounting Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. → 77 ff, feature 110,
"Additional options 2".
3.98”
(101)
4.65”
(118)
4.65”
(70)
P01-PMx7xxxx-06-xx-xx-xx-001
Endress+Hauser 25
Cerabar S
"Remote housing" version With the "remote housing" version, you are able to mount the housing with the electronics insert at a distance
from the measuring point. This facilitates zero-interference measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or difficult to
access)
• If rapid cleaning of the measuring point is required
• If the measuring point is exposed to vibrations.
You can choose between different cable versions:
• PE (2 m, 5 m and 10 m / 6, 16, 33 feet)
• FEP (5 m / 16 feet).
→ 77 ff, Feature 110, "Additional options 2", Version "G".
For the dimensions, → 60.
4
IP xx
FEP cable: (see chapter
IP 69K “Ordering information”)
IP 66/68 NEMA 4/6P 3
PE cable:
IP 66/68 NEMA 4/6P
r ³ 4.72”
1
(120 mm)
2
P01-PMx7xxxx-11-xx-xx-en-012
In the case of the "remote housing" version, the sensor is delivered with the process connection and cable ready mounted.
The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both ends. These
sockets are simply connected to the housing and the sensor.
1 Process connection with sensor
2 Cable, both ends are fitted with a socket
3 Mounting bracket provided, suitable for pipe and wall mounting
4 Housing with electronic insert
Degree of protection for the process connection with sensor with the use of
• FEP cable:
– IP 69K
– IP 66 (NEMA 4/6P)
– IP 68 (1.83 mH2O for 24 h), NEMA 4/6P
• PE cable:
– IP 66 (NEMA 4/6P)
– IP 68 (1.83 mH2O for 24 h), NEMA 4/6P
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 inch)
• Cable extraction force: max. 450 N (101 lbf)
• Resistance to UV light
Use in hazardous area:
• Intrinsically safe installations (Ex ia/IS)
• FM/CSA IS: for Div.1 installatin only
26 Endress+Hauser
Cerabar S
Turn the housing The housing can be rotated up to 380° after loosening the Allen screw.
Your benefits
• Simple mounting by optimally aligning the housing
• Good, accessible device operation
• Optimum readability of the on-site display (optional).
FIELD TERMINALS
max. 380°
P01-PMx7xxxx-17-xx-xx-xx-000
Oxygen applications Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other things, the
following precautions must be taken:
– All components of the system, such as measuring devices, must be cleaned in accordance with the BAM
(DIN 19247) requirements.
– Dependent on the materials used, a certain maximum temperature and a maximum pressure for oxygen
applications must not be exceeded.
The devices suitable for gaseous oxygen applications are listed in the following table with the specification pmax.
Order code for devices cleaned for pmax for oxygen applications Tmax for oxygen
oxygen applications applications
Silicone-free applications Cleaning of the transmitter for the use e.g. in paint shops → 79 "Ordering information PMC71", feature 80
"Seal", version "L" and "M".
Ultra pure gas applications Endress+Hauser also offers the degreased device for special applications, such as ultra pure gas.
No special restrictions regarding the process conditions apply to this device.
→ 79, "Ordering information PMC71", feature 80 "Seal" or → 83, "Ordering information PMC71", feature
90 "Fill fluid".
Endress+Hauser 27
Cerabar S
Applications with hydrogen With regard to materials in which hydrogen build-up takes place, hydrogen atoms can diffuse through the metal
process isolating diaphragm. This can result in incorrect measurement results.
Endress+Hauser offers process isolating diaphragms with Gold-Rhodium coating for this application.
→ 82 "Ordering information PMP71" and → 86 "Ordering information PMP75", feature 60 "Membrane
material" version "6".
For devices for use in hazardous areas, see Safety instructions, Installation or Control Drawing. (→ 90,
sections "Safety Instructions" and "Installation/Control Drawings".)
The device can be used in this temperature range. The values of the specification, such as thermal change, may
be exceeded. → DIN 16086.
Climate class Class 4K4H (air temperature: –20 to 55°C/–4 to +131°F, relative humidity: 4 to 100%) fulfilled as per
DIN EN 60721-3-4 (condensation possible)
1) With PMC71, avoid condensate in the device (avoid moisture collecting in the device).
28 Endress+Hauser
Cerabar S
Electromagnetic compatibility • Electromagnetic compatibility to EN 61326 and NAMUR recommendation EMC (NE21). For details refer
to the declaration of conformity.
• With enhanced immunity against electromagnetic fields as per EN 61000-4-3:
30 V/m with closed cover 1
• Maximum deviation: < 0.5% of span
• All EMC measurements were performed with a turn down (TD) = 2:1.
Endress+Hauser 29
Cerabar S
Extreme jumps in temperature can result in temporary measuring errors. Temperature compensation takes effect after several
minutes. Internal temperature compensation is faster the smaller the temperature jump and the longer the time interval.
Process connections with internal process isolating diaphragm –40 to +125°C (–40 to +257°F)
(+150 °C/302°F for max. one hour)
Process connections with flush-mounted process isolating –40 to +100°C (–40 to +212°F)
diaphragm, G 1 A, G 1 1/2 A, G 2 A, 1 NPT, 1 1/2 NPT, 2 NPT,
M 44 x 1.25, EN/DIN, ANSI and JIS flanges
Process connections with flush-mounted process isolating –20 to +85°C (–4 to +185°F)
diaphragm, G 1/2 A, M 20
30 Endress+Hauser
Cerabar S
B , 2 3
EPDM (FDA 21CFR177.2600; 3A Class II; –20 to +125°C/150°C 1 (–4 to +257°F/302°F)
USP Class VI) DVGW (KTW, W270,
W534), WRAS, ACS, NSF61
1 FKM Viton, cleaned from oil and greace –10 to +125°C/150°C 1 (+14 to +257°F/302°F)
2 FKM Viton, cleaned for oxygen service –10 to +60 °C (+14 to +140°F)
The process temperature ranges specified here refer to permanent application of the PMC71. They may be exceeded for a
short time (e.g. for cleaning).
Pressure specifications • The maximum pressure for the measuring device is dependent on the lowest-rated element with regard to
pressure, see the following sections for this:
– → 7 ff, section "Measuring range"
– chapter "Mechanical construction".
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference
temperature of 20°C (68°F) or 100°F for ANSI flanges and may be applied to the device for an unlimited
time. Observe temperature dependency.
• The pressure values permitted at higher temperatures can be found in the following standards:
– EN 1092-1: 2001 Tab. 18 1
– ASME B 16.5a – 1998 Tab. 2-2.2 F316
– ASME B 16.5a – 1998 Tab. 2.3.8 N10276
– JIS B 2220.
• The test pressure corresponds to the over pressure limit of the measuring instrument (Over Pressure Limits
OPL = 1.5 x MWP 2) and may fit only temporally limited, so that no permanent damage develops.
• The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The abbreviation
"PS" corresponds to the MWP (maximum working pressure) of the measuring device.
• In the case of sensor range and process connections where the OPL (Over pressure limit) of the pressure
connection is smaller than the nominal value of the sensor, the device is set at the factory, at the very
maximum, to the OPL value of the process connection. If you want to use the entire sensor range, select a
process connection with a higher OPL value (1.5 x PN; PN = MWP).
• In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per → 27, "Oxygen
applications" may not be exceeded.
1) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO
in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
2) The equation does not apply for PMP71 and PMP75 with a 40 bar (600 psi) or 100 bar (1500 psi) measuring cell.
Endress+Hauser 31
Cerabar S
Mechanical construction
Housing dimensions T14
5.98”
(152) 4.37” 4.37”
(111) (111)
FIELD TERMINALS
P01-PMx7xxx-06-00-xx-xx-000
P01-PMx7xxxx-06-00-xx-xx-001
32 Endress+Hauser
Cerabar S
H H H
ø8 17 20 17 20 17 20
13
ø3 G 1/4 ø11.4
5
ø6 ø17.5 ø17.5
G 1/2 G 1/2 G 1/2
P01-PMC71xxx-06-09-xx-xx-001
1 1/2” MNPT 1/4” FNPT 2 1/2” MNPT 11.4 mm 3 1/2” MNPT 3 mm 4 1/2” FNPT
H H H H
Endress+Hauser 33
Cerabar S
1 G 1/2 2 R 1/2
H
H
ø8 20 23
13.2
ø3 3 ø11.4
ø5 R 1/2
G 1/2
P01-PMC71xxx-06-09-xx-xx-003
M20x1.5
ø8 17 20
ø3
ø6 5
M20x1.5
P01-PMC71xxx-06-09-xx-xx-004
Installation height H for devices with thread connection and internal process isolating diaphragm
PMC71 with Ex d[ia], CSA XP or FM XP 225 mm (8.86") 241 mm (9.41"), Ex d = 311 mm (12.2")
1) High temperature version, → 79, feature 100 "Additional options 1" and
feature 110 "Additional options 2", versions "T"
34 Endress+Hauser
Cerabar S
1 G 1-1/2 2 G2
SW 60 SW 60
60 AF 60 AF
H H
25 28 30 33.5
G 1-1/2 G2
ø55 ø68
ø1.59”
1 -1/2” NPT 2” NPT 1.18” 0.43”
(40.5)
ø2.68” (30) (11)
M44x1.25
(68)
P01-PMC71xxx-06-09-xx-xx-005
Installation height H for devices with thread connection and flush-mounted process isolating
diaphragm
Endress+Hauser 35
Cerabar S
H
g2
2
b
g
k
D
P01-PMC71xxx-06-09-xx-xx-006
Process connection PMC71, EN/DIN flange with raised face (flush-mounted process isolating diaphragm)
Installation height → 38.
Version Material Nominal Nominal Shape 2 Diameter Thick- Raised Quantity Diameter Bolt circle Flange
diameter pressure ness face weight 3
D b g g2 k
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation in brackets as per DIN 2527
3) Housing weight → 61
4) Max.: 15 bar (225 psi), max.: –10 to +60°C (+14 to +140°F)
36 Endress+Hauser
Cerabar S
0.06” H
(1.6) g2
g
k
D
P01-PMC71xxx-06-09-xx-xx-007
Process connection PMC71, ANSI flange with raised face (flush-mounted process isolating diaphragm)
Installation height → 38.
Version Material Nominal Class Diameter Thickness Raised face Quantity Diameter Bolt circle Flange
diameter weight 2
D b g g2 k
AE AISI 316/316L 3 1-1/2 150 5 (127) 0.69 (17.5) 2.88 (73.2) 4 0.62 (15.7) 3.88 (98.6) 2.2 (1.0)
3
AQ AISI 316/316L 1-1/2 300 6.12 (155.4) 0.81 (20.6) 2.88 (73.2) 4 0.88 (22.4) 4.5 (114.3) 5.7 (2.6)
AF AISI 316/316L 3 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)
JR ECTFE 4 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)
5
A3 PVDF 2 150 6 (152.4) 0.75 (19.1) 3.62 (91.9) 4 0.75 (19.1) 4.75 (120.7) 1.1 (0.5)
3
AR AISI 316/316L 2 300 6.5 (165.1) 0.88 (22.4) 3.62 (91.9) 8 0.75 (19.1) 5 (127) 7.1 (3.2)
AG AISI 316/316L 3 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)
JS ECTFE 4 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)
5
A4 PVDF 3 150 7.5 (190.5) 0.94 (23.9) 5 (127) 4 0.75 (19.1) 6 (152.4) 2.0 (0.9)
3
AS AISI 316/316L 3 300 8.25 (209.5) 1.12 (28.4) 5 (127) 8 0.88 (22.4) 6.62 (168.1) 15 (6.8)
AH AISI 316/316L 3 4 150 9 (228.6) 0.94 (23.9) 6.19 (157.2) 8 0.75 (19.1) 7.5 (190.5) 16 (7.1)
JT ECTFE 4 4 150 9 (228.6) 0.94 (23.9) 6.19 (157.2) 8 0.75 (19.1) 7.5 (190.5) 16 (7.1)
3
AT AISI 316/316L 4 300 10 (254) 1.25 (31.8) 6.19 (157.2) 8 0.88 (22.4) 7.88 (200.2) 26 (11.6)
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30μin (0.8 μm). Lower surface roughness on request.
2) Housing weight → 61
3) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
4) ECTFE coating on AISI 316L SS/1.4435
When operating in hazardous area, avoid electrostatic charge of the plastic surface.
5) max.: 15 bar (225 psi), max.: –10 to +60°C (+14 to +140°F)
Endress+Hauser 37
Cerabar S
JIS flange, connection dimensions as per JIS B 2220 BL, raised face RF
H
g2
2
b
g
k
D
P01-PMC71xxx-06-09-xx-xx-008
Process connection PMC71, JIS flange with raised face RF (flush-mounted process isolating diaphragm), AISI 316L/
1.4435
→ Installation height see table below.
Flange 1 Boltholes
Versions Nominal Nominal Diameter Thickness Raised face Quantity Diameter Hole circle Flange
dimension pressure weight 2
D b g g2 k
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8. Lower surface roughness on request.
2) Housing weight see → 61
38 Endress+Hauser
Cerabar S
1 DIN 11851 DN 40
2 DIN 11851 DN 50
H
H
21 10 22 11
ø48 ø61
Rd 65 x 1/6 Rd 78 x 1/6
H
H
ø 2.22” ø 3.29”
(56.5) (83.5)
ø 2.52” ø 3.58”
(64) (91)
16
ø 2.68”
ø65 (68)
ø84 ø 3.31”
ø105 (84)
P01-PMC71xxx-06-09-xx-xx-011
Installation height H for devices with hygienic connection and flush-mounted process isolating
diaphragm
Endress+Hauser 39
Cerabar S
H H H
ø11.4 ø11.4
3
20 17 20 17 20
13
ø3 ø17.5
3 G 1/4
ø3.2 G 1/2 A
ø17.5
ø17.5
G 1/2 A
G 1/2 A
P01-PMP71xxx-06-09-xx-xx-000
40 Endress+Hauser
Cerabar S
1 G 1/2 2 R 1/2
H H
ø8
3 ø21.4
23 23
ø3 ø11.4
ø5
R 1/2
G1/2
P01-PMP71xxx-06-09-xx-xx-002
M 20x1.5
ø11.4
17 20
ø17.5
M20x1.5
P01-PMP71xxx-06-09-xx-xx-003
Installation height H for devices with thread connection and internal flush-mounted process
isolating diaphragm
Note!
The versions with 700 bar (10,150 psi) sensor are approx. 20 mm (0.79")
higher.
Endress+Hauser 41
Cerabar S
1 G 1/2A 2 G 1A 3 G 1-1/2A 4 G 2A
H H H
H
8 1
3.5 3
ø30 3.5
3
ø18.4
26 31
14 18
H H
H
1.32”
0.91” 1.06”
(33.5)
(23) (27)
42 Endress+Hauser
Cerabar S
1 M 20x1.5 2 M 44x1.25
H 0.31” H)
(8)
0.12”
0.14” (3)
ø0.70” (3.5)
(17.7)
0.91”
(23)
Installation height H for devices with thread connection and flush-mounted process isolating
diaphragm
G1 167 mm 183 mm
Endress+Hauser 43
Cerabar S
h H
g2
2
b
dM = ø28
60 m
g
k
D
P01-PMP71xxx-06-09-xx-xx-008
Process connection PMP71, EN/DIN flange with raised face, material AISI 316L SS
H: device height = height of device without flange h + flange thickness b
Height h → 46.
D b g m g2 k
mm mm mm mm mm mm kg
4
CN DN 25 PN 10-40 B1 (D) 115 18 66 4 4 14 85 1.2
4
CP DN 32 PN 10-40 B1 (D) 140 18 77 8.5 4 18 100 1.9
4
CQ DN 40 PN 10-40 B1 (D) 150 18 87 - 4 18 110 2.2
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) Housing weight → 61
4) With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a
manufacturer of seals or your local Endress+Hauser Sales Center.
44 Endress+Hauser
Cerabar S
h H
0.08” g2
(2)
b
dM = ø1.1”
(28)
2.36” m
(60)
g
k
D
P01-PMP71xxx-06-09-xx-xx-009
Process connection PMP71, ANSI flange or JIS flange with raised face RF; material AISI 316L SS
H: device height = height of device without flange h + flange thickness b. For the height h → 46.
Ver- Material Nominal Class/ Diameter Thickness Diameter Width of Qty. Diameter Bolt Flange
sion diameter Nominal raised face the raised circle weight 2
pressure face
D b g (m) g2 k
ANSI flange
AN AISI 316/316L 3 1 300 lb./sq.in 4.88 (124) 0.69 (17.5) 2.76 4 (70) 0.2 (5) 4 0.75 (19.1) 3.5 (88.9) 2.9 (1.3)
3 4
AE AISI 316/316L 1-1/2 150 lb./sq.in 5 (127) 0.69 (17.5) 2.88 (73.2) 0.52 (6.6) 4 0.62 (15.7) 3.88 (98.6) 3.3 (1.5)
AQ AISI 316/316L 3 1-1/2 300 lb./sq.in 6.12 (155.4) 0.81 (20.6) 2.88 4 (73.2) 0.52 (6.6) 4 0.88 (22.4) 4.5 (114.3) 5.7 (2.6)
3
AF AISI 316/316L 2 150 lb./sq.in 6 (152.4) 0.75 (19.1) 3.62 (91.9) - 4 0.75 (19.1) 4.75 (120.7) 5.3 (2.4)
3
AR AISI 316/316L 2 300 lb./sq.in 7.5 (190.5) 0.88 (22.3) 3.62 (91.9) - 8 0.75 (19.1) 5 (127) 7.1 (3.2)
3
AG AISI 316/316L 3 150 lb./sq.in 7.5 (190.5) 0.94 (23.9) 5 (127) - 4 0.75 (19.1) 6 (152.4) 10.8 (4.9)
AS AISI 316/316L 3 3 300 lb./sq.in 8.25 (209.5) 1.12 (28.4) 5 (127) - 8 0.88 (22.4) 6.62 (168.1) 14.8 (6.7)
AH AISI 316/316L 3 4 150 lb./sq.in 9 (228.6) 0.94 (23.9) 6.19 (157.2) - 8 0.75 (19.1) 7.5 (190.5) 15.6 (7.1)
3
AT AISI 316/316L 4 300 lb./sq.in 10 (254) 1.25 (31.8) 6.19 (157.2) - 8 0.88 (22.4) 7.88 (200.2) 26 (11.6)
JIS flange
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30 μin (0.8 μm). Lower surface roughness on request.
2) Housing weight → 61
3) Combination of AISI 316 for required pressure resistance and AISI 316L SS for required chemical resistance (dual rated)
4) With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a
manufacturer of seals or your local Endress+Hauser Sales Center.
Endress+Hauser 45
Cerabar S
Oval flange
3.09”
(78.5)
2.50”
(63.5)
P01-PMP71xxx-06-09-xx-xx-007
Version UR: oval flange adapter 1/4-18 NPT according to IEC 61518, mounting: 7/16-20 UNF; Weight: 1.9 kg (4.2 lb)
1 2 3
h
ø0.09”
0.19” (2.5) ø0.31”
(5) (7.95)
P01-PMP75xxx-06-09-xx-xx-xx-005
46 Endress+Hauser
Cerabar S
P01-PMP75xxx-06-09-xx-xx-012
Endress+Hauser 47
Cerabar S
SW SW
AF AF
h h
x1 x1
dM dM
d1 NPT
G d2
d2
P01-PMP75xxx-06-09-xx-xx-003
Process connections PMP75, left: thread ISO 228, right: thread ANSI
PN d1 d2 x1 SW/AF dM h
2A AISI 316L 1" MNPT 6000 psi – 1.89" 1.10" 41 0.94" +15.66 +24.42 +8.50 1.46" 1.3 lbs
(48) (28) (24) (37)
2B Alloy C276 – – – 1.5 lbs
2D AISI 316L 1-1/2" 6000 psi – 1.97" 1.18" 46 1.42" +8.14 +12.39 +3.90 0.79" 2.0 lbs
MNPT (52) (30) (36) (20)
2E Alloy C276 – – – 2.2 lbs
2G AISI 316L 2" MNPT 6000 psi – 3.07" 1.18" 65 1.50" +5.4 +8.18 +2.59 1.38" 4.0 lbs
(78) (30) (38) (35)
2H Alloy C276 – – – 4.4 lbs
Note!
With the use of high temperature oils the design can deviate strongly.
For further information please contact your local Endress+Hauser Sales Center.
48 Endress+Hauser
Cerabar S
dM
C7
P01-FMD78xxx-06-09-xx-xx-005
Process connection PMP75, material: AISI 316L SS, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.
C7 dM h
TB DN 25 DN 25 1 2.0 (50.5) 0.93 (24) 1.46 (37) +15.33 +24.0 +4.25 3.7 (0.32)
1
TC DN 38 DN 40 1-1/2 2.0 (50.5) 1.34 (34) 1.18 (30) +8.14 +12.39 +1.91 2.2 (1.0)
1
TD DN 51 DN 50 2 2.5 (64) 1.89 (48) 1.18 (30) +3.45 +4.81 +1.25 2.4 (1.1)
TF DN 76.1 – 3 3.6 (91) 2.87 (73) 1.18 (30) +0.3 +0.35 +0.18 2.6 (1.2)
1) Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra ≤ 0.38 μm (15.75 μin; 180 grit),
electropolished; to be ordered using feature 60 "Additional option", version "P" in the order code
Endress+Hauser 49
Cerabar S
D d2
L
P01-FMD78xxx-06-09-xx-xx-001
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.
D d2 h L
SB DN 25 1 0.98 (22.5) 2.0 (50.5) 2.64 (67) 4.96 (126) +7.75 +8.69 +4.49 3.7 (1.7)
SC 1 DN 38 1-1/2 1.40 (35.5) 2.0 (50.5) 2.64 (67) 4.96 (126) +5.17 +5.69 +3.46 2.2 (1.0)
1
SD DN 51 2 1.91 (48.6) 2.5 (64) 3.11 (79) 3.94 (100) +3.56 +3.91 +2.69 3.7 (1.7)
1) Including 3.1 and pressure test as per Pressure Equipment Directive, category II
1.57”
(40)
dM = 1.81”
(46)
ø2.68”
(68)
P01-FMD78xxx-06-09-xx-xx-006
Process connection PMP75, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm as standard. Lower
surface roughness on request.
[mbar/10 K] kg
1) Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces
Ra ≤ 0.38 μm (15.75 μin; 180 grit), electropolished; to be ordered using feature 60 "Additional option", version "P"
in the order code
50 Endress+Hauser
Cerabar S
41
23.6
dM=50 4 x ø11.5
ø65–1.2
ø84
ø105
P01-FM78xxx-06-09-xx-xx-002
Process connection PMP75, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm as standard. Lower
surface roughness on request.
[mbar/10 K] kg
h
m f
dM
G
D
P01-PMP75xxx-06-09-xx-xx-009
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.
Version Nominal Nominal Dia- Adapter Thread Height Height max. dia- TK TK TK Weight
diameter pressure meter height phragm Ambient Ambient Process dia-
diameter ≤ 40 bar > 40 bar phragm
seal
D f G m h dM
Endress+Hauser 51
Cerabar S
h
m f
dM
G
D
P01-PMP75xxx-06-09-xx-xx-010
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.
Version Nomi- Nomi- Dia- Adapter Thread Height Height max. TK TK TK Weight
nal dia- nal meter height diaphragm Ambient Ambient Process dia-
meter pres- diameter ≤ 40 bar > 40 bar phragm
sure seal
PN D f G m h dM
h
f
m
SW/AF dM
G
D
P01-PMP75xxx-06-09-xx-xx-011
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 30 μin (0.8 μm) as standard. Lower surface roughness on request.
Version Nomi- Nomi- Dia-meter Adap- Thread Height Across Height max. TK TK TK Weight
nal nal ter flat diaphragm Ambient Ambient Process Dia.
dia. pres- height seal ≤ 40 bar > 40 bar seal
sure
D f G m AF h dM
inch [bar] in (mm) in (mm) in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)
TP 1 PN 40 2.13 (54.1) 0.16 (4) 1-1/2" – 1/8" 1.18 (30) 46.8 1.97 (50) 0.94 (24) +15.66 +24.42 +4.21 1 (0.4)
TQ 1-1/2 PN 40 2.83 (72) 0.16 (4) 2" – 1/8" 1.18 (30) 62 1.97 (50) 1.34 (34) +8.14 +12.39 +2.59 1.3 (0.6)
TS 2 PN 40 3.50 (89) 0.16 (4) 2-1/2" – 1/8" 1.18 (30) 77 1.97 (50) 1.77 (45) +5.4 +8.18 +1.76 2.4 (1.1)
52 Endress+Hauser
Cerabar S
40
f m k
dM
D
G
P01-FMD78xxx-06-09-xx-xx-007
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.
Version Nominal No- Dia- Adapter Thread Height Height max. Dia- TK TK TK Dia-
diameter minal meter height phragm Ambient Ambient Process phragm
pres- diameter ≤ 40 bar > 40 bar seal
sure weight
D f G k m dM
mm mm mm mm [mm [mbar/10 K] kg
dM
d1
G
P01-FMD78xxx-06-09-xx-xx-008
Process connection PMP75, material AISI 316L, surface roughness of the surfaces in contact with the medium
Ra ≤ 0.8 μm as standard. Lower surface roughness on request.
d1 G h dM
mm mm mm [mbar/10 K] kg
Endress+Hauser 53
Cerabar S
EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527 and DIN 2501-1
g2
40
dM L
f
60 (m)
g dM
k g
D
P01-PMP75xxx-06-09-xx-xx-002
Process connection PMP75, EN/DIN flange with flush-mounted process isolating diaphragm, material AISI 316L
Ver- No- Nominal Shape Dia- Thick- Raised face Quan- Dia- Bolt max. Dia- TK Ambient TK Dia-
2
sion minal pressure meter ness tity meter circle phragm Pro- phragm
≤ 40 bar > 40 bar
dia- dia- cess seal
meter meter weight
D b g f (m) g2 k dM
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg]
CP DN 32 PN 10-40 B1 (D) 140 18 77 2.6 8.5 3 4 18 100 34 +8.14 +12.39 +2.59 1.9
B4 DN 80 PN 10-40 B1 (D) 200 24 138 3.5 - 8 18 160 89 +0.19 +0.25 +0.20 5.3
C5 DN 100 PN 100 B2 (E) 265 36 175 5 - 8 30 210 89 +0.19 +0.25 +0.11 13.7
4 4
D3 DN 50 PN 10-40 B1 (D) 165 20 102 3 - 4 18 125 47 +3.45 +4.81 +1.67
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Designation as per DIN 2527 in brackets
3) With these process connections the width of the raised face is smaller than described in the standard. Due to a smaller width of the raised face a special seal
must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center.
4) 50 mm, 100 mm or 200 mm extension selectable, for extension diameter and weight see the following table.
54 Endress+Hauser
Cerabar S
1.57” g2
(40)
b
dM L
2.36” (m)
Class 150, 300
(60)
0.06 in
(1.6 mm) g dM
k g
Class 400 – 2500
0.25 in D
(6.4 mm)
P01-PMP75xxx-06-09-xx-xx-001
Process connection PMP75, ANSI flange with and without extended diaphragm seal
D b g (m) g2 k dM
inch [lb./ in (mm) in (mm) in (mm) in in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)
sq.in] (mm)
AC AISI 316/ 1 150 4.25 0.56 2 - 4 0.62 3.12 1.26 +16.03 +24.33 +3.65 2.6 (1.2)
316L (108) (14.2) (50.8) (15.7) (79.2) (32)
AN AISI 316/ 1 300 4.88 0.69 2.76 0.2 4 0.75 3.5 1.26 +16.03 +24.33 +3.65 2.9 (1.3)
316L (124) (17.5) (70) (5) 3 (19.1) (88.9) (32)
HC AISI 316/ 1 400/ 4.88 0.69 2 - 4 0.75 3.5 1.26 +16.03 +24.33 +5.17 3.1 (1.4)
316L 600 (124) (17.5) (50.8) (19.1) (88.9) (32)
HN AISI 316/ 1 900/ 5.88 1.12 2 - 4 1 4 1.26 +16.03 +24.33 +5.17 7 (3.2)
316L 1500 (149.4) (28.4) (50.8) (25.4) (101.6) (32)
HO AISI 316/ 1 2500 6.25 1.38 2 - 4 1 4.25 1.26 +16.03 +24.33 +5.17 10 (4.6)
316L (158.8) (35.1) (50.8) (25.4) (108) (32)
AE AISI 316/ 1 1/2 150 5 0.69 2.88 0.3 4 0.62 3.88 1.89 +8.14 +12.39 +1.90 3.3 (1.5)
316L (127) (17.5) (73.2) (6.6) 3 (15.7) (96.6) (48)
AQ AISI 316/ 1 1/2 300 6.12 0.81 2.88 0.3 4 0.88 4.5 1.89 +8.14 +12.39 +2.59 5.7 (2.6)
316L (155.4) (20.6) (73.2) (6.6) 3 (22.4) (114.3) (48)
AF AISI 316/ 2 150 6 0.75 3.62 - 4 0.75 4.75 2.32 +2.21 +3.02 +1.60 4.9 (2.2)
316L (152.4) (19.1) (91.9) (19.1) (120.7) (59)
J3 4 AISI 316/ 2 150 6 0.75 3.62 - 4 0.75 4.75 1.85 +3.45 +4.81 +1.67 4
AR AISI 316/ 2 300 6.5 0.88 3.62 - 8 0.75 5 2.32 +2.21 +3.02 +0.85 7.5 (3.4)
316L (165.1) (22.4) (91.9) (19.1) (127) (59)
HF AISI 316/ 2 400/ 6.5 1 3.62 - 8 0.75 5 2.32 +2.21 +3.02 +0.85 9.5 (4.3)
316L 600 (165.1) (25.4) (91.9) (19.1) (127) (59)
Endress+Hauser 55
Cerabar S
D b g (m) g2 k dM
inch [lb./ in (mm) in (mm) in (mm) in in (mm) in (mm) in (mm) [mbar/10 K] lbs (kg)
sq.in] (mm)
HR AISI 316/ 2 900/ 8.5 1.5 3.62 - 8 1 6.5 2.32 +2.21 +3.02 +0.75 23 (10.3)
316L 1500 (215.9) (38.1) (91.9) (25.4) (165.1) (59)
H3 AISI 316/ 2 2500 9.25 2 3.62 - 8 1.12 6.75 2.32 +2.21 +3.02 +0.75 35 (15.8)
316L (235) (50.8) (91.9) (28.4) (171.5) (59)
AG AISI 316/ 3 150 7.5 0.94 5 - 4 0.75 6 3.50 +0.19 +0.25 +0.18 11.2 (5.1)
316L (190.5) (23.9) (127) (19.1) (152.4) (89)
AS AISI 316/ 3 300 8.25 1.12 5 - 8 0.75 6 3.5 +0.19 +0.25 +0.11 15.4 (7.0)
316L (209.5) (28.4) (127) (19.1) (152.4) (89)
J4 4 AISI 316/ 3 150 7.5 0.94 5 - 4 0.75 6 2.83 +0.19 +0.25 +0.70 4
J7 4 AISI 316/ 3 300 8.25 1.12 5 - 8 0.88 6.62 2.83 +0.19 +0.25 +0.70 4
AH AISI 316/ 4 150 9 0.94 6.19 - 8 0.75 7.5 3.50 +0.19 +0.25 +0.33 17 (7.2)
316L (228.6) (23.9) (157.2) (19.1) (190.5) (89)
AT AISI 316/ 4 300 10 1.25 6.19 - 8 0.88 7.88 3.50 +0.19 +0.25 +0.11 26 (11.7)
316L (254) (31.8) (157.2) (22.4) (200.2) (89)
J5 4 AISI 316/ 4 150 9 0.94 6.19 - 8 0.75 7.5 3.50 +0.19 +0.25 +0.11 4
J8 4 AISI 316/ 4 300 10 1.25 6.19 - 8 0.88 7.88 3.50 +0.19 +0.25 +0.11 4
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 30 μin (0.8 μm). Lower surface roughness on request.
2) Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
3) With these process connections the width of the raised face is smaller than described in the standard. Due to a smaller width of the raised face a special seal
must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center.
4) 2", 4", 6" or 8" extension selectable, for extension diameter and weight see the following table
56 Endress+Hauser
Cerabar S
JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF
f 40
dM
D
P01-PMP75xxx-06-09-xx-xx-000
Process connection PMP75, JIS flange with raised face RF, material AISI 316L SS
Ver- No- No- Dia- Thick- Dia- Height Quan- Dia- Bolt max. TK Ambient TK Dia-
sion minal minal meter ness meter raised tity meter circle Dia- Process phragm
dia- pres- raised face phragm seal
≤ 40 bar > 40 bar
meter sure face dia- weight 2
meter
D b g f g2 k dM
mm mm mm mm mm mm mm [mbar/10 K] kg
1) The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards), made of Hastelloy C, Monel or Tantalum is
Ra 0.8 μm. Lower surface roughness on request.
2) Housing weight → 61
Endress+Hauser 57
Cerabar S
Ø 4.65” Ø 4.65”
(118) (118)
2.99”
(76) 3.72”
(94.5)
1.02”
0.75” (26)
(19) 1.75”
1.06” (44.5)
1/2” NPT (27)
0.47”
27AF (12)
1” NPT
Ø 1.18” 0.59”
(30) 36 AF (15)
Ø 2.05”
(52)
P01-PMP75xxx-06-09-xx-xx-008
Process connection PMP75, versions "UG" and "UH", screwed, material AISI 316L SS, seal Viton
UG 1/2" NPT 3625 psi (PN 250) +3.45 +1.28 10.5 (4.75)
UH 1" NPT 3625 psi (PN 250) +3.45 +1.28 11.0 lbs (5.0)
ø2.86”
ø72.6
(72.6)
2.76”
70 0.55” (70)
(14)
SW 30 AF 30
14
ø18.4
17 20 0.85”
(21.5)
ø4 ø0.45”
ø6 3 (11.4)
G 1/2A 1/2” - 14 NPT
P01-PMP75xxx-06-09-xx-xx-004
Process connection PMP75, versions "UA" and "UB", welded, material AISI 316L
58 Endress+Hauser
Cerabar S
3.94” 3.94”
(100) (100)
3.54” 3.50”
(90) 1 (89) 1
SW22 SW22
22 AF 22 AF
P01-PMP75xxx-06-09-xx-xx-013
Process connection PMP75, left: version "UC" with threaded connection ISO 228 G 1/2 B, right: version "UD" with
threaded connection ANSI 1/2" MNPT
1 PTFE seal as standard max. 260°C/500°F (higher temperatures on request)
Version Measuring range Description Nominal pressure TK Process Diaphragm seal weight
UD ≤ 600 psi ANSI 1/2" MNPT 600 psi +0.55 3.2 (1.43)
Ø 4.53” Ø 4.53”
(115) (115)
3.31”
(84) 3.64”
(92.5)
AF 36 AF 36
0.75”
(19) AF 22 0.67” 0.79”
(17) (20)
Ø 0.1”
(2.5)
1/2” NPT Ø 0.16”
(4)
0.12”
Ø 0.24”
(3)
(6)
G 1/2A
P01-PMP75xxx-06-09-xx-xx-007
Process connection PMP75, versions "UC" and "UD", threaded, with integrated sealing lip, material AISI 316L
UC > 40 bar ISO 228 G 1/2 A PN 400 +3.45 +1.28 10.5 (4.75)
UD > 600 psi ANSI 1/2" MNPT 6000 psi +3.45 +1.28 10.5 (4.75)
Note!
With the use of high temperature oils the design can deviate strongly.
For further information please contact your local Endress+Hauser Sales Center.
Endress+Hauser 59
Cerabar S
131
(5.16”)
45.5
(1.79”)
ø51.7
(2.04”)
P01-xxxxxxxx-06-xx-xx-xx-000
Dimensions T14 housing, optional display on the side. Housing weight see → 61.
101 76
(3.98”) 118
(2.99”)
(4.65”)
147
(5.79”)
45.5
(1.79”)
ø51.7
(2.04”)
P01-xxxxxxxx-06-xx-xx-xx-001
Dimensions T17 housing, optional display on the side. Housing weight see → 61.
2.17” 2.17”
(55) (55) ø2.13”
(54.1)
2.80”
1 1 1 (71)
P01-xxxxxxxx-06-xx-xx-xx-002
Reduction of the mounting height of the process connection, for application of the remote housing.
1 Process connection adapter.
If the remote housing is used, the mounting height of the process connection is reduced by approx. 45 mm
(1.8") as compared to the dimensions of the standard version.
The minimum bending radius (r) for the cable is 120 mm (4.7").
60 Endress+Hauser
Cerabar S
Weight Housing
With electronic insert and on-site 2.6 lb (1.2 kg) 4.6 lb (2.1 kg) 2.6 lb (1.2 kg) Weight of housing T14 or T17 + 1.1 lb (0.5 kg).
display Weight of sensor + 1.1 lb (0.5 kg).
With electronic insert without on-site 2.4 lb (1.1 kg) 4.4 lb (2.0 kg) 2.4 lb (1.1 kg)
display
Process connections
• Process connections PMC71 (with ceramic process isolating diaphragm): → 33 ff
• Process connections PMP71 (with metallic process isolating diaphragm): → 40 ff
• Process connections PMP75 (with metallic process isolating diaphragm): → 47 ff
Process connection
• "Clamp connections" and "Hygienic connections" (see also Chapter "Ordering information"): AISI 316L/
1.4435
• "Threaded connection" and "DIN/EN flanges" (see also Chapter "Ordering information"): stainless steel AISI
316L with the material number 1.4435 or 1.4404
• With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together
under 13E0 in EN 1092-1 Tab.18. The chemical composition of the two materials can be identical.
Endress+Hauser 61
Cerabar S
! Note!
Process wetted device components are listed in the "Mechanical construction" (→ 32) and "Ordering
information" (→ 77) sections.
Miscellaneous:
• Process isolating diaphragm PMC71: Al2O3 Aluminum-oxide-ceramic (FDA 21CFR186.1256, USP Class
VI), ultrapure 99.9% (→ www.endress.com/ceraphire)
• Mounting accessories: Mounting kit with screws AISI 304 (1.4301)
• Capillary: AISI 316 Ti (1.4571)
• Protective hose for capillary: AISI 304 (1.4301)
• External ground terminal: AISI 304 (1.4301)
→ For process connections, process diaphragms, seals and filling oils see ordering information, → 77 ff.
62 Endress+Hauser
Cerabar S
Human interface
Operating elements On-site display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The on-site display shows measured
values, dialog text as well as fault and notice messages in plain text, thereby supporting the user in every stage
of operation. The liquid crystal display of the device can be turned in 90° steps.
Depending on the installation position of the device, this makes it easy to operate the device and read the
measured value.
Functions:
• 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as current
display or for PROFIBUS PA as graphical display of the scaled value of the AI Block
• Simple and complete menu guidance thanks to seperation of the parameters into three levels
• Ech parameter is given as 3-digit ID number for easy navigation
• Option for configuring the display according to individual requirements and desires, such as language,
alternating display, display of other measured values such as sensor temperature, contrast setting
• Comprehensive diagnostic functions (fault and warning message, peak-hold indicators, etc.)
• Rapid and safe commissioning with the Quick Setup menus
Header line
Main line
Unit
Information
line
– + E Symbol
Bargraph
Editing modes
Operating keys
Selection
options
Value that
can be edited
Endress+Hauser 63
Cerabar S
4 to 20 mA HART
PROFIBUS PA/
FOUNDATION Fieldbus
0%
Zero
P01-PMx7xxxx-19-xx-xx-xx-038
The operating keys located externally on the device work on the Hall sensor principle. As a result, no additional
openings are required in the device. This guarantees:
• Complete protection against environmental influences such as moisture and contamination
• Simple operation without any tools
• No wear.
t t
Sim.
on on on
Zero
Sensor Display Zero
Sensor Display
Simulation
on on ON CK S D A 0 8 HW
on
1 2 1 2 off off 1 2 3 4 5 6 7 8
PC
1 2 off
PC
PC
1 2 3 4 5 6 7 8
Address
Histo ROM
Histo ROM
SW
HW
HART
R
250002271-–
TM
250002272-–
HW-Version: 1 FOUNDATION
SW-Version: 2 HW-Version: 1 HW-Version: 1
SW-Version: 2 SW-Version: 2
Electronic insert HART Electronic insert PROFIBUS PA Electronic insert FOUNDATION Fieldbus
1 Operating keys 1 Green LED to indicate value being accepted 1 Green LED to indicate value being accepted
2 Slot for optional display 2 Key for position calibration and device reset 2 Key for position calibration and device reset
3 Slot for optional HistoROM®/M-DAT 3 DIP-switch for bus address 3 Slot for optional display
4 DIP-switch for locking/unlocking 4 Slot for optional display 4 Slot for optional HistoROM®/M-DAT
measured-value-relevant parameters 5 Slot for optional HistoROM®/M-DAT 5 DIP-switch for locking/unlocking
5 DIP-switch for damping on/off 6 DIP-switch for locking/unlocking measured-value-relevant parameters
6 Green LED to indicate value being accepted measured-value-relevant parameters 6 DIP-switch for simulation mode on/off
7 DIP-switch for damping on/off
64 Endress+Hauser
Cerabar S
Remote operation Depending on the position of the write protection switch at the device, all software parameters are accessible.
HART
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- and Software for local and remote
operation" → 66)
• FieldCare (see Chapter "Hard- und Software for on-site and remote operation" → 66 ff) with
– Commubox FXA191 (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
– Commubox FXA195 (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
• Field Xpert:
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows
Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART
device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520. Field Xpert also works
as a stand-alone device for asset management applications. For details refer to BA060S/00/en.
PROFIBUS PA
Remote operation via:
• FieldCare (see Chapter "Hard- and Software for local and remote operation" → 66 ff)
– Profiboard: For the Connection of a Personal Computer to PROFIBUS
– Proficard: For the Connection of a Laptop to PROFIBUS
FOUNDATION Fieldbus
Remote operation via:
• Handheld terminal Field Communicator 375 (see Chapter "Hard- and Software for local and remote
operation" → 66 ff)
• Use an FF-configuration program for e.g. NI-FBUS configurator, to
– connect devices with "FOUNDATION Fieldbus signal" into an FF-network
– set FF-specific parameter
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops and a
schedule based on the fieldbus concept.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
– Set block and device tags
– Set device addresses
– Create and edit function block control strategies (function block applications)
– Configure vendor -defined function and transducer blocks
– Create and edit schedules
– Read and write to function block control strategies (function block applications)
Endress+Hauser 65
Cerabar S
! Note!
For further information please contact your local Endress+Hauser Sales Center.
Commubox FXA195
For intrinsically safe communication with FieldCare via the USB interface. For details TI404F/00/en.
Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field instruent with CDI interface (=Endress+Hauser
Common Data Interface) to the USB interface of a personal computer or a notebook.
For details TI405C/07/en.
Note!
For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory:
• Cerabar S PMC71, PMP7x
• Deltabar S PMD7x, FMD7x
• Deltapilot S FMB70
HistoROM®/M-DAT (optional)
HistoROM®/M-DAT is a memory module, which is attached to the electronic insert. The HistoROM®/M-DAT
can be retrofitted at any stage (Order number: 52027785).
Your benefits
• Quick and safe commissioning of the same measuring points by copying the configuration data of one
transmitter to another transmitter
• Reliable process monitoring thanks to cyclical recording of pressure and sensor temperature measured values
• Simple dagnosis by recording diverse events such as alarms, configuration changes, counters for measuring
range undershoot and overshoot for pressure and temperature as well as user limit overshoot and undershoot
for pressure and temperature etc.
• Analysis and graphic evaluation of the events and process parameters via software (contained in scope of
supply).
HistoROM®/M-DAT can be ordered via feature 100 "Additional options 1" or feature 110 "Additional options
2" or as spare parts. → 77 ff. A CD with Endress+Hauser operating program is also included in the scope of
delivery.
You can copy data from one transmitter to another transmitter when operating a FOUNDATION Fieldbus
device via an FF configuration program. You need the Endress+Hauser FieldCare operating program and the
Commubox FXA291 service interface and the ToF Adapter FXA291 to be able to access the data and events
saved in the HistoROM®/M-DAT.
66 Endress+Hauser
Cerabar S
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can
configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT
standard.
FieldCare supports the following functions:
• Configuration of transmitter in offline and online operation
• Loading and saving device data (upload/download)
• HistoROM®/M-DAT analysis
• Documentation of the measuring point
Connection options:
• HART via Commubox FXA191 and the RS232C serial interface of a computer
• HART via Commubox FXA195 and the USB port on a computer
• PROFIBUS PA via segment coupler and PROFIBUS interface card
• FOUNDATION Fieldbus via Commubox FXA193 and the RS232C serial interface of a computer
• Service interface with adapter Commubox FXA291 and ToF Adapter FXA291 (USB).
For further information www.endress.com
Endress+Hauser 67
Cerabar S
Applications Diaphragm seal systems should be used if the process media and the device should be separated. Diaphragm
seal systems offer clear advantages in the following instances:
• In the case of high process temperatures (→ 30, section "Process temperature limits".)
• For aggressive media
• If good and rapid measuring point cleaning is necessary
• If the measuring point is exposed to vibrations
• For mounting locations that are difficult to access
• For very humid mounting locations
Planning instructions Diaphragm seals are separating equipment between the measuring system and the process medium.
A diaphragm seal system consists of:
• A diaphragm seal in a one-sided system
• Capillary tube
• Fill fluid and
• A pressure transmitter.
The process pressure acts via the process isolating diaphragm of a diaphragm seal on the liquid-filled system,
which transfers the process pressure via the capillary tube onto the sensor of the pressure transmitter.
Endress+Hauser delivers all diaphragm seal systems as welded versions. The system is hermetically sealed,
which ensures the highest reliability.
Note!
The correlations between the individual diaphragm seal components are presented in the following section.
For further information and comprehensive diaphragm seal system designs, please contact your local
Endress+Hauser Sales Center.
Diaphragm seal
The diaphragm seal determines the application range of the system by
• the process isolating diaphragm diameter
• the diaphragms: stiffness and material
• the design (oil volume).
Capillary
Capillaries with an internal diameter of 1 mm (0.04") are used as standard.
The capillary tube influences the TK zero point, the ambient temperature operating range and the response
time of a diaphragm seal system as a result of its length and internal diameter.
→ 69 ff, sections "Influence of the temperature on the zero point" and "Ambient temperature range".
→ Observe the installation instructions regarding capillary tubes. → 74 ff, section "Installation instructions".
68 Endress+Hauser
Cerabar S
Filling oil
When selecting the filling oil, fluid and ambient temperature as well as the operating pressure are of crucial
importance. Observe the temperatures and pressures during commissioning and cleaning. A further selection
criterion is the compatibility of the filling oil with the requirements of the process medium. For this reason,
only filling oils that are harmless to health are used in the food industry, such as vegetable oil or silicone oil
→ See also the following section "Diaphragm seal filling oils" section.
The filling oil used influences the TK zero point and the temperature operating range of a diaphragm seal system
and the response time. → 69 ff, section "Influence of the temperature on the zero point".
Pressure transmitter
The pressure transmitter influences the temperature operating range, the TK zero point and the response time
as a result of its volume change. The volume change is the volume that has to be shifted to pass through the
complete measuring range.
Pressure transmitters from Endress+Hauser are optimised with regard to minimum volume change.
A, H, Silicone oil –40 to +180°C –40 to +250°C 0.96 100 0.00096 1 suitable for foods
1 or 2 (DC 200) (–40 to +356°F) (–40 to +482°F) FDA 21 CFR 175.105
G, 3 or 4 High temp. oil –10 to +200°C –10 to +400°C 1.07 37 0.0007 0.72 high temperatures
(DC 704) (+14 to +392°F) (+14 to +752°F)
F or N Inert oil –40 to +80°C –40 to +175°C 1.87 27 0.000876 0.91 for ultra pure gas and
(Halocarbon) (–4 to +176°F) (–40 to +347°F) oxygen
applications
D, 5 or 6 Vegetable oil –10 to +120°C –10 to +200°C 0.94 9.5 0.00101 1.05 suitable for foods
(Neobee M-20) (+14 to +248°F) (+14 to +392°F) FDA 21 CFR 172.856
7 or 8 Low –70 to +80°C –70 to +180°C 0.92 4.4 0.00108 1.12 low temperatures
temperature oil –94 to +176°F –94 to +356°F
Influence of the temperature A temperature change results in a volume change of the filling oil. The volume change is dependent on the
on the zero point coefficient of thermal expansion of the filling oil and on the volume of the filling oil at calibration temperature
(constant in the range: +21 to +33°C (+69.8 to 91.4°F)). → 69, "Filling oil" section.
For example, the filling oil expands in the event of a temperature increase. The additional volume presses
against the process isolating diaphragm of a diaphragm seal. The stiffer a process isolating diaphragm is, the
greater its return force, which counteracts a volume change and acts on the measuring cell together with the
operating pressure, thus shifting the zero point. For the "TK Process" and "TK Ambient (for devices without
capillary)", see → 47 ff, section "Process connections PMP75".
The following diagrams display the temperature coefficient "TK Ambient" dependent on the capillary length.
The following application is displayed: capillary temperature and transmitter temperature (ambient
temperature) change, the process temperature corresponds to the calibration temperature.
The temperature coefficients obtained from the diagrams apply to silicone oil and the process isolating
diaphragm material AISI 316L/1.4435. For other filling oils, these temperature coefficients must be multiplied
by the TK correction factor of the corresponding filling oil. For the TK correction factors, see → 69,
section "Diaphragm seal filling oils".
With regard to the temperature coefficient "TK Ambient", devices with temperature isolator behave like devices
with the same process connection and 0.1 m capillary.
Endress+Hauser 69
Cerabar S
PN < 40 bar
TK Ambient 16
[mbar/10 K]
14
6
12
10
mbar
8.4 8
10 K
0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-007
Diagram TK Ambient dependent on the capillary length for PMP75, PN < 40 bar (600 psi)
Example for:
– Diaphragm seal versions "B3, EN/DIN flange DN 50 PN 10-40 B1, AISI 316L"
– Capillary length: 5 m (16 ft)
– Ambient temperature, capillary/transmitter: 45°C
– Filling oil: silicone oil
1. Select characteristic curve type for the diaphragm seal versions "B3" in accordance with the following
table.
Result: characteristic curve type 6
2. Obtain value for TK Ambient from the diagram.
Result: 8.4 mbar/10 K
3. TAmbient – TCalibration = 45°C – 25°C = 20°C ⇒ 8.4 mbar/10 K x 20 K = 16.8 mbar (0.24 psi)
Result: In this application, the zero point is shifted by 16.8 mbar (0.24 psi).
Note!
• The influence of temperature on the zero point can be corrected with position calibration.
• The temperature influence can be minimised by using a filling oil with a smaller coefficient of thermal
expansion, shorter capillary, diaphragm seal with larger process isolating diaphragm diameter or by using a
smaller capillary internal diameter.
70 Endress+Hauser
Cerabar S
PN ³ 40 bar
TK Ambient 16 7
[mbar/10 K] 6
14
12
5
10
4
8
6
7
4
3
2 2
1
0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-005
Diagram TK Ambient dependent on the capillary length for PMP75, PN ≥ 40 bar (600 psi)
Endress+Hauser 71
Cerabar S
PN £ 40 bar
TK Ambient 160
[mbar/10 K]
140
13
120
12
100
80
11
60
10
40
9
20
8
0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-008
Diagram TK Ambient dependent on the capillary length for PMP75, PN < 40 bar (600 psi)
PN > 40 bar
TK Ambient 160
[mbar/10 K]
140
13
120
12
100
80
11
60
10
40
9
20 8
0
0 1 2 3 4 5 6 7 8 9 10
Capillary length
[m]
P01-PMP75xxx-05-xx-xx-en-009
Diagram TK Ambient dependent on the capillary length for PMP75, PN ≥ 40 bar (600 psi)
72 Endress+Hauser
Cerabar S
Ambient temperature range The operating temperature range of a diaphragm seal system depends on Fill fluid, "Capillary length and
internal diameter, Process temperature and Diaphragm seal oil volume.
The range of application can be extended by using a fill fluid with a smaller expansion coefficient and a shorter
capillary. The permitted operating temperature ranges in relation to the capillary length can be calculated
online at "Applicator Sizing Diaphragm Seal":
http://www.endress.com/applicator -> Applicator Sizing Diaphragm Seal -> Horncurve
P01-xxxxxxxx-20-xx-xx-en-001
Note!
• Endress+Hauser recommends you use a low temperature oil for applications that require short response
times or are close to the lower temperature limit (see "diaphragm seal fill fluid").
• Please contact your Endress+Hauser sales office for further information, comprehensive diaphragm seal
system designs and measuring technology solutions that are close to the application limits.
Endress+Hauser 73
Cerabar S
Vacuum applications
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the
diaphragm seal. A vacuum load of the diaphragm seal caused by the presence of fill fluid in the capillary
prevents is hereby prevented.
When the pressure transmitter is mounted above the diaphragm seal, the maximum height difference H1 in
accordance with the following illustration on the left must not be exceeded. The maximum height difference
is dependent on the density of the filling oil and the smallest ever pressure that is permitted to occur at the
diaphragm seal (empty tank), see the following illustration, on the right.
39
FIELD TERMINALS
0.0
0.7 1.45 2.9 4.3 5.8 7.3 8.7 10.1 11.6 13.0 14.5
(50) (100) (200) (300) (400) (500) (600) (700) (800) (900) (1000)
Pressure at diaphragm seal psia (mbarabs)
P01-PMx7xxxx-11-xx-xx-xx-008 P01-PMP75xxx-05-xx-xx-en-011
Installation above the diaphragm seal Diagram of maximum installation height above the diaphragm seal for
vacuum applications
74 Endress+Hauser
Cerabar S
Ex approvals • ATEX
• FM
• CSA
• NEPSI
• IECEx
• GOST
• also combinations of different approvals
All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
→ 90 ff, sections "Safety Instructions" and "Installation/Control Drawings".
Suitability for hygenic The Cerabar S is suitable for the employment in hygenic processes.
processes Overview of permitted process connections from page 32.
Many versions meet the requirements of 3A-Sanitary Standard No. 74 and
are certified by the EHEDG.
Note!
The gap-free connections can be cleaned without residue using the usual
cleaning methods.
TYPE EL 74 -
October 2007
Marine certificate • GL
• ABS
Functional Safety SIL / IEC The Cerabar S with 4 to 20 mA output signal have been developed to IEC 61508 standard. These devices can
61508 Declaration of confor- be used for process pressure and level measurement monitoring up to SIL 3.
mity (optional) For a detailed description of the safety functions with Cerabar S, settings and characteristic quantities for
functional safety, please refer to the "Manual for Functional Safety- Cerabar S" SD190.
For devices with SIL / IEC 61508 declaration of conformity see → 77 ff, Feature 100 "Additional option 1"
and Feature 110 "Additional option 2" version E "SIL / IEC 61508, declaration of Conformity".
CRN approvals Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection
(→ 78, feature 70 "Process connection") has to be ordered with a CSA approval (→ 77, feature 10
"Approval"). PMP75 devices with capillary are not CRN-approved. These devices are fitted with a separate plate
bearing the registration number 0F10525.5C.
Pressure Equipment Directive The devices PMC71, PMP71 and PMP75 correspond to Article 3 (3) of the EC directive 97/23/EC (Pressure
(PED) Equipment Directive) and has been designed and manufactured according to good engineering practice.
Additionally applies:
– PMP71 with threaded connection and internal process isolating diaphragm PN > 200 (2900 psi) as well as
oval flange adapter PN > 200 (2900 psi):
Suitable for stable gases in group 1, category I
– PMP75 with pipe diaphragm seal ≥ 1.5"/PN 40 (600 psi):
Suitable for stable gases in group 1, category II
– PMP75 with separator PN > 200 (2900 psi):
Suitable for stable gases in group 1, category 1
– PMP75 with threaded connection PN > 200 (2900 psi)
Endress+Hauser 75
Cerabar S
Accessories
76 Endress+Hauser
Cerabar S
Ordering information
PMC71 This overview does not mark options which are mutually exclusive.
10 Approval:
A For non-hazardous areas
E Combi-certification
ATEX II Ex ia + FM IS + CSA IS
ATEX II 1/2G Ex ia IIC T6 +
FM/CSA IS Class I, II, III Division 1 Group A - G
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D Ex ia IIC T6
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d[ia] IIC T6
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
1 R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
G NEPSI Ex d[ia] IIC T4/T6
– + E H NEPSI Ex ia IIC T6
L TIIS Ex d (ia) IIC T6
M TIIS Ex d (ia) IIC T4
I IECEx Zone 0/1 Ex ia IIC T6
20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
B 4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ C 4...20 mA HART, operation inside (→ see Fig.o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC
Endress+Hauser 77
Cerabar S
50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification
78 Endress+Hauser
Cerabar S
80 Seal:
A FKM Viton
B EPDM
D Kalrez
E Chemraz
F NBR/3A: HNBR (FDA)
L FKM Viton, cleaned for silicone-free service
M Kalrez, cleaned for silicone-free service
1 FKM Viton, cleaned from oil and greace
2 FKM Viton, oxygen service
Note application limits pressure/temp.
Endress+Hauser 79
Cerabar S
995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.
80 Endress+Hauser
Cerabar S
PMP71 This overview does not mark options which are mutually exclusive.
10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
1
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6
– + E
7 ATEX II 3 G Ex nA II T6
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
L TIIS Ex d IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II 2 G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates:
ATEX II Ex ia / Ex d + FM/CSA IS + XP
ATEX II 1/2G Ex ia IIC T6+
ATEX II 2G Ex d IIC T6+
FM/CSA IS + XP Cl.I Div.1 Gr.A-D
20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ B
C 4...20 mA HART, operation inside (→ see Fig. o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC
Endress+Hauser 81
Cerabar S
50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD certificate; see additional specification
K Platinum; see additional specification
L Platinum and factory certificate 5-point; see additional specification
M Platinum and DKD certificate; see additional specification
60 Membrane material:
1 AISI 316L
2 Alloy C276
6 AISI 316L with Gold-Rhodium coating
82 Endress+Hauser
Cerabar S
90 Fill fluid:
A Silicone oil fill
F Inert oil fill
K Inert oil fill, cleaned from oil and greace
N Inert oil fill, cleaned for oxygen services
(Note application limits pressure/temperature)
Endress+Hauser 83
Cerabar S
995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.
84 Endress+Hauser
Cerabar S
PMP75 This overview does not mark options which are mutually exclusive.
10 Approval:
A For non-hazardous areas
1 ATEX II 1/2 G Ex ia IIC T6
6 ATEX II 1/2 G Ex ia IIC T6, overspill protection WHG
2 ATEX II 1/2 D
4 ATEX II 1/3 D
1
8 ATEX II 1 GD Ex ia IIC T6
3 ATEX II 1/2 GD Ex ia IIC T6
5 ATEX II 2 G Ex d IIC T6
–
7 ATEX II 3 G Ex nA II T6
+ E
S FM IS, Class I, II, III Division 1, Groups A – G; NI Class I Division 2, Groups A – D; AEx ia
T FM XP, Class I Division 1, Groups A – D; AEx d
Q FM DIP, Class II, III Division 1, Groups E – G
R FM NI, Class I, Division 2, Groups A – D
U CSA IS, Class I, II, III Division 1, Groups A – G; Class I Division 2, Groups A – D, Ex ia
V CSA XP, Class I Division 1, Groups B – D; Ex d
W CSA Class II, III Division 1, Groups E – G (Dust Ex)
G NEPSI Ex d IIC T6
H NEPSI Ex ia IIC T6
L TIIS Ex d IIC T6
I IECEx Zone 0/1 Ex ia IIC T6
B Combined certificates: ATEX II 1/2 G Ex ia IIC T6 + II 2 G Ex d IIC T6
C Combined certificates: FM IS and XP Class I Division 1, Groups A – D
D Combined certificates: CSA IS and XP Class I Division 1, Groups A – D
E Combined certificates: FM/CSA IS and XP Class I Division 1, Groups A – D
F Combined certificates:
ATEX II Ex ia / Ex d + FM/CSA IS + XP
ATEX II 1/2G Ex ia IIC T6+
ATEX II 2G Ex d IIC T6+
FM/CSA IS + XP Cl.I Div.1 Gr.A-D
20 Output; Operation:
n A 4...20 mA HART, operation outside, LCD (→ see Fig. ➀, n)
4...20 mA HART, operation inside, LCD (→ see Fig. ➀, o)
➂ B
C 4...20 mA HART, operation inside (→ see Fig. o)
M PROFIBUS PA, operation outside, LCD (→ see Fig. ➀, n)
1 2
N PROFIBUS PA, operation inside, LCD (→ see Fig. ➀, o)
PC
Endress+Hauser 85
Cerabar S
50 Calibration; Unit:
1 Sensor range; mbar/bar
2 Sensor range; kPa/MPa
3 Sensor range; mmH2O/mH2O
4 Sensor range; inH2O/ftH2O
6 Sensor range; psi
B Customised; see additional specification
C Factory certificate 5-point; see additional specification
D DKD calibration: see additional specification
60 Membrane material:
1 AISI 316L
2 Alloy C276
3 Monel
5 Tantal
6 AISI 316L with Gold-Rhodium coating
7 AISI 316L with 0.09 mm PTFE foil (not for vacuum applications)
8 AISI 316L with 0.25 mm PTFE foil (not for vacuum applications, only for non-hazardous areas)
86 Endress+Hauser
Cerabar S
90 Fill fluid:
A Silicone oil
B ...m capillary, inert oil
C ...ft capillary, inert oil
D Vegetable oil
F Inert oil
Endress+Hauser 87
Cerabar S
90 Fill fluid:
G High temperature oil, Temp. isolator 100 mm
H Silicone oil, Temp. isolator 100 mm
K Inert oil, cleaned from oil and greace
N Inert oil, cleaned for oxygen services
1 ... m capillary, silicone oil
2 ... ft capillary, silicone oil
3 ... m capillary, high temperature oil
4 ... ft capillary, high temperature oil
5 ... m capillary, vegetable oil
6 ... ft capillary, vegetable oil
7 ... m capillary, Low temperature oil
8 ... ft capillary, Low temperature oil
995 Marking:
1 Tagging (TAG), see additional spec.
2 Bus adress, see additional spec.
88 Endress+Hauser
Cerabar S
Additional documentation
Field of Activities • Pressure measurement, Powerful instruments for process pressure, differential pressure, level and flow:
FA004P/00/en
Endress+Hauser 89
Cerabar S
Safety Instructions Certificate/Type of Protection Device Electronic insert Documentation Version in the
order code
90 Endress+Hauser
Cerabar S
Endress+Hauser 91
United States Canada Mexico