Open and Short Circuit
Open and Short Circuit
Supervised by:
Eng. Ali AL - Yaqahbi.
Prepared by:
Hussein Abdel-Moeen – 202270380
Introduction
The open circuit and short circuit test are performed for determining the
parameter of the transformer like their efficiency, voltage regulation,
circuit constant etc. These tests are performed without the actual loading
and because of this reason the very less power is required for the test.
The open circuit and the short circuit test gives a very accurate result as
compared to the full load test.
Experiment tools :
1. Transformer 220 / 110
2. Ammeters and voltmeters
3. Wattmeter
4. Connecting wires and switches
V
X 0=
Im
1. The open terminal from the open circuit test was shorted.
2. An ammeter was connected across the remaining terminals and the
Variac.
3. The Variac voltage was slowly increased until the short-circuit
current (I_SC) reached the transformer's rated current.
4. The short-circuit voltage (V sc ) and power ( PSC ) were recorded at
this point.
Calculations
For O.C.T
I 0.155
G= V = 220
=0.704 s
P 14
∅ =cos−1 ( )=cos ( )=66 deg
−1
VI 220∗0.155
Y = G - Jβ = 0.288 - 0.643j Ω
1 1 1
G 0.288 =3.472Ω
= ;
Rc= Xn= =1.55 Ω
0.643
For S.C.T
P 3.9
∅ =cos−1 ( )=cos ( )=48 deg
−1
VI 0.99∗5.9
Vsc 5.9
Z= = =5.96 ∠ 48 Ω
isc 0.99
Z eq=Req+JXeq=3.99+2.429jΩ
Vp 220
a = vs = 110 =2
Req 3.99
Rs= a
2
=
4
=1 Ω
Xeq 2.429
Rs= a
2
=
4
=0.607 Ω
Discussion:
3.472
Rc refer ¿ low voltage side= =0.868 ohm
4
And
1.55
Xn= =0.38 75 Ω
4
2. From values obtained above , determine𝑅𝐶 and 𝑋𝑀 referred to
high voltage side.
Rc =3.472Ω ; X m=1.55 Ω