OptiFlex OFHI CS
OptiFlex OFHI CS
INTEGRATOR
HIGH SPEED ROUTING AND INTEGRATION
Part Number Part# EQT2
24 Vac Models: TBPL-24-H-A, TBPL-24-HM-A
The OptiFlex Integrator, model OFHI, supports routing between multiple BACnet networks. It also
supports custom control programs to easily integrate with third party BACnet or Modbus equipment
such as variable speed drives, boilers, and lighting.
The WebCTRL building automation system gives you the ability to understand
your building operations and analyze the results. Integrate environmental, energy,
security and safety systems into one powerful management tool that helps you
reduce energy consumption, increase occupant comfort, and achieve sustainable
building operations.
1
SPECIFICATIONS
Part # OFHI
OptiFlex Integrator
Conforms to the BACnet Building Controller (B-BC), Standard Profile as defined in ANSI/ASHRAE Standard 135-2012
BACnet Conformance (BACnet) Annex L, Protocol revision 14.
BTL Listing | PICS | WPSCert Conformance Certificate
Control Program
Maximum number of control programs: 999 depending upon available memory.
Execution
BACnet Objects Maximum number of BACnet objects: 12,000 for programming purposes, depending upon available memory.
Third-Party Integration Supports up to 1,500 third-party BACnet integration points, and 1,000 Modbus integration points
Communication
Gig-E Port 10/100/1000 BaseT Ethernet port for BACnet/IP and/or BACnet/Ethernet and/or Modbus full duplex
Rnet Port Supports Up to 15 ZS wireless and/or ZS sensors, and one Equipment Touch or OptiPoint™ interface
Microprocessor To m
32-bit ARM Cortex-A8, 600 MHz, processor oumulti-level
with nt the Gcache
5REmemory, two Ethernet controllers, and USB 2.0 host port
Environmental Range 32 to 140º F (0 to 60º C); 10 - 90% relative humidity, non-condensing
The G5RE must be mounted in a metal enclosure or cabinet which is properly rated for the location
where
16 GBs eMMC Flash memory (120 MB available it is being
for use) installed.
and 256 MB DDR3 DRAM. User data is archived to non-volatile Flash
Memory
memory when parameters are changed, every 90 seconds, and when the firmware is deliberately shutdown or restarted.
Real Time Clock Real-time clock keeps track of time in the event of a power failure for up to 3 days
DIN rail mount
United States: FCC compliant to Title CFR47, Part 15, Subpart
1 Push B,pull
down and ClassoutA.the
ULcenter
Listed, File
tabs E143900;
shown below CCN PAZX,
to clear UL916,
the din Energy
rail trough on the back of the
Management Equipment; AS/NZS: RCM Mark 61000-6-3; router. Canada: UL Listed File E143900, CCN PAZX7, CAN/CSA C22.2 No.
Compliance 205 Signal Equip., Industry Canada Compliant, ICES-003, Class A; CE Mark Compliant with 2014/30/EU, and RoHS Compliant:
2015/863/EU; UKCA Mark compliant with Electromagnetic Compatibility Regulations 2016 – Gov.UK and RoHS for Electrical
and Electronic Equipment 2012.
Device is protected by a replaceable, fast acting, 250Vac, 2A, 5mm x 20mm glass fuse.
Protection
The power and network ports comply with the EMC requirements EN50491-5-2
2 Place the router on the DIN rail so that the rail is in the trough on the back of the router.
in. cm
Width: 7.1 18.03
Height: 6.95 17.65
Depth: 2.09 5.31
Weight: 1.1 lbs .48 kg