0% found this document useful (0 votes)
108 views

NEC Rules For Fire Pumps

The document discusses NEC rules for fire pump installations from Article 695. Key points include: - Fire pumps must operate regardless of risk to conductors to keep facilities from burning down. Article 695 aims to keep pumps running. - Power sources must be reliable and carry locked-rotor current indefinitely to minimize pump downtime. Acceptable power sources are listed. - Circuits supplying fire pumps must be supervised to prevent inadvertent disconnection. Wiring requirements aim to keep pumps energized. - Disconnects for normal power sources must be lockable and marked "Fire Pump Disconnecting Means" to help ensure pumps remain powered.

Uploaded by

alf.powerchina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
108 views

NEC Rules For Fire Pumps

The document discusses NEC rules for fire pump installations from Article 695. Key points include: - Fire pumps must operate regardless of risk to conductors to keep facilities from burning down. Article 695 aims to keep pumps running. - Power sources must be reliable and carry locked-rotor current indefinitely to minimize pump downtime. Acceptable power sources are listed. - Circuits supplying fire pumps must be supervised to prevent inadvertent disconnection. Wiring requirements aim to keep pumps energized. - Disconnects for normal power sources must be lockable and marked "Fire Pump Disconnecting Means" to help ensure pumps remain powered.

Uploaded by

alf.powerchina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

6/13/2018 NEC Rules for Fire Pumps

NATIONAL ELECTRICAL CODE > CODE BASICS

NEC Rules for Fire Pumps


Understanding the circuit protection requirements of Art. 695 and why
they’re di erent from other parts of the NEC

http://www.ecmweb.com/print/16540 1/10
6/13/2018 NEC Rules for Fire Pumps

Mike Holt | Apr 16, 2013

The general philosophy behind most Code requirements is to provide circuit


protection that will shut down equipment before the supply conductors become
overloaded, overheated, and damaged. But Art. 695 is based on a different
philosophy: The fire pump motor must run, regardless of the risk to the conductors.

A fire pump supplies water to a facility’s fire protection piping. If the pump doesn’t
run, not only will those conductors be damaged, but the entire facility will also be in
danger of burning down. Consequently, the many requirements of Art. 695 aim to
keep the pump running.

Obviously, the pump is more likely to keep running if its location minimizes
exposure to fire, and doing so is an NEC requirement. This doesn’t conflict with
other requirements, but many Art. 695 requirements do. For example, contrary to
what other articles require, the disconnect must be lockable in the closed position
[695.4(B)(3)(a)(2)].

According to the scope statement of Art. 695, it covers the installation of the fire
pump supply and controls. It doesn’t cover the jockey pumps or the internal wiring
of the system (Photo).

http://www.ecmweb.com/print/16540 2/10
6/13/2018 NEC Rules for Fire Pumps

The rules covering the installation of electric power sources and interconnecting circuits for switching and
control equipment dedicated to fire pump drivers are very specific.

Power sources

With the 2011 NEC, the power requirements found in Art. 695 have changed
extensively (see SIDEBAR: Power Source(s) for Electric Motor-Driven Fire Pumps ).
However, as with previous NEC editions, you must supply power from a reliable
source. This source must be able to carry the locked-rotor current of the fire pump
motor(s) and pressure maintenance pump motors, plus the full-load current of
associated fire pump equipment [695.3(A)].

Electric motor-driven fire pumps must have a reliable source of power, which is
subject to the approval of the AHJ. It needs to be one or more of the following:

• A separate electric utility service [695.3(A)(1)].

• A connection located ahead of (but not within) the service disconnecting means [695.3(A)(1)].

http://www.ecmweb.com/print/16540 3/10
6/13/2018 NEC Rules for Fire Pumps

• An on-site power supply, such as a generator, located and protected to minimize damage by
fire [695.3(A)(2)].

• A dedicated feeder derived from a service connection in accordance with 695.3(A)(1)


[695.3(A)(3)].

If reliable power can’t be obtained from one of these sources, then it must be
supplied by one of the following multiple sources [695.3(B)]:

1. Individual sources. An approved combination of two or more of the sources from 695.3(A).

2. Individual source and on-site standby generator. An approved combination of one of the
sources in 695.3(A) and an on-site standby generator.

Exception to 695.3(B)(1) and (B)(2): An alternate source of power isn’t required


where a back-up engine-driven or back-up steam turbine-driven fire pump is
installed.

If you have:

• A multi-building, campus-style installation where the sources just discussed aren’t


practicable, follow the requirements of 695.3(C).

• An on-site standby generator as an alternate source, follow the requirements of 695.3(D).

Arrange multiple sources so that a fire at one source won’t cause an interruption at
the other source [695.3(E)]. Phase converters are not permitted for a fire pump
service [695.3(F)].

Continuity

Circuits that supply electric motor-driven fire pumps must be supervised from
inadvertent disconnection whether the conductors connect directly or through a
disconnecting means and overcurrent device [695.4].

http://www.ecmweb.com/print/16540 4/10
6/13/2018 NEC Rules for Fire Pumps

If you have a direct connection, the supply conductors must directly connect the
power source either to a listed fire pump controller or to a listed combination fire
pump controller and power transfer switch [695.4(A)].

If you connect through a disconnect and an overcurrent protective device (OCPD),


then you can use a single disconnecting means and associated OCPD(s) between the
fire pump power source and one of the following [695.4(B)(1)]:

1. Listed fire pump controller.

2. Listed fire pump power transfer switch.

3. Listed combination fire pump controller and power transfer switch.

Select or set the OCPD to carry indefinitely the sum of the locked-rotor current of
the fire pump and pressure maintenance pump motor(s), and 100% of the ampere
rating of the fire pump’s accessory equipment.

If the locked-rotor current value doesn’t correspond to a standard OCPD size, then
use the next standard OCPD size per 240.6 (Fig. 1). The requirement to carry the
locked-rotor current indefinitely doesn’t apply to fire pump motor conductors
[695.4(B)(2)(a)].

http://www.ecmweb.com/print/16540 5/10
6/13/2018 NEC Rules for Fire Pumps

Fig. 1. If the locked-rotor current doesn’t correspond to a standard overcurrent protective device (OCPD), then
use the next size up per 240.6. In this example, the locked rotor current is shown as 404A. Therefore, you
should use a 450A OCPD.

Disconnecting means

The disconnecting means for the normal power source must be [695.4(B)(3)]:

• Identified as suitable for use as service equipment.

• Lockable in the closed position.

• Not located within equipment that feeds loads other than the fire pump.

• Located sufficiently remote from other building or other fire pump source disconnecting
means.

• Marked “Fire Pump Disconnecting Means.” The letters must be at least 1 in. high. People must
be able to see them without opening enclosure doors or covers [695.4(B)(3)(c)].

What if an on-site generator is the alternate power source? In that case, install its
disconnect per 700.10(B)(5) for emergency circuits, and ensure the disconnect can
be locked in the closed position [695.4(B)(3)(a)(2)].
http://www.ecmweb.com/print/16540 6/10
6/13/2018 NEC Rules for Fire Pumps

Transformers

If a transformer supplies an electric fire pump motor, size it at least 125% of the sum
of the fire pump and pressure maintenance pump(s) motor loads, and 100% of the
ampere rating of the fire pump’s accessory equipment [695.5(A)].

Size the primary OCPD to carry indefinitely the sum of the locked-rotor current of
the fire pump and pressure maintenance pump motor(s), and 100% of the ampere
rating of the fire pump’s accessory equipment. The requirement to carry the locked-
rotor currents indefinitely does not apply to fire pump motor conductors. Secondary
overcurrent protection is not permitted [695.5(B)].

Power wiring

Service conductors and conductors supplied by on-site power production facilities


must be physically routed outside buildings [695.6]. Install them per Art. 230. If
these conductors cannot be routed outside of buildings, then encase them in 2 in. of
concrete or brick [230.6(1) or (2)].

Keep fire pump supply conductors entirely independent of all other wiring. They can
supply only those loads directly associated with the fire pump system. Make sure
they are protected from potential damage by fire, structural failure, or operational
accident [695.6(A)(2)]. You can route fire pump conductors through a building by
one of the following methods [695.6(A)(2)(d)]:

• Encase them in a minimum 2 in. of concrete.

• Run them within an enclosed construction dedicated to the fire pump circuit(s) and having a
minimum of a 2-hr fire-resistive rating.

• Use a listed electrical circuit protective system protected by a fire-rated assembly listed to
achieve a minimum fire rating of 2 hr and dedicated to the fire pump circuit(s).

http://www.ecmweb.com/print/16540 7/10
6/13/2018 NEC Rules for Fire Pumps

Fig. 2. Branch circuit conductors to a single fire pump motor must have a rating of not less than 125% of the
motor FLC as listed in Tables 430.248 or 430.250.

Conductors supplying only a fire pump motor must have a minimum ampacity of at
least 125% of the motor full-load current rating as required by 430.22 [695.6(B)(2)],
as shown in Fig. 2. If these conductors also supply related equipment, such as
another fire pump motor, pressure maintenance pumps, and associated fire pump
accessory equipment, they must have a minimum ampacity of at least 125% of the
sum of the fire pump motors and pressure maintenance motors full-load currents —
and 100% of the associated fire pump accessory equipment [695.6(B)(1)].

Wiring from the fire pump controller to the fire pump motor (not installed through a
building, as covered in 695.6(B)) must be in rigid metal conduit, intermediate metal
conduit, electrical metallic tubing, liquidtight flexible metal conduit, liquidtight
flexible nonmetallic conduit Type B, listed Type MC cable with an impervious
covering, or Type MI cable [695.6(D)]. This requirement also applies to the control
wiring [695.14(E)].

The voltage at the line terminals of the fire pump controller, when the motor starts
(locked-rotor current), must not drop more than 15% below the controller’s rated
voltage [695.7(A)].

http://www.ecmweb.com/print/16540 8/10
6/13/2018 NEC Rules for Fire Pumps

In addition, the voltage at the motor terminals must not drop more than 5% below
the voltage rating of the motor when the motor operates at 115% of the fire pump
full-load current rating [695.7(B)].

Regardless of the voltage drop calculations, size the branch circuit conductors no
smaller than required by [695.6(B)].

GFCI

Ground-fault protection of equipment is not allowed on fire pump equipment


[695.6(G)]. The NEC doesn’t prohibit you from installing GFCI-protected
receptacles in a fire pump location for portable equipment or other outlets required
by the NEC to be GFCI protected.

In summary

Because the circuit protection requirements of Art. 695 differ from — and
philosophically conflict with — the NEC’s other circuit protection requirements,
correct application can be confusing. The central question to answer when installing
fire pumps and related equipment is, “How do I make sure the pump runs no matter
what?”

Remember, the fire pump must be kept in service, even if doing so damages or
destroys the pump. It’s better to run the pump until its windings melt than to save
the fire pump and lose the facility. The intent of Art. 695 is to save the facility.

SIDEBAR: Power Source(s) for Electric Motor-Driven Fire


Pumps

Section 695.3 is the most heavily revised portion of Art. 695 in the 2011 NEC. Three
key revisions worth noting include:

http://www.ecmweb.com/print/16540 9/10
6/13/2018 NEC Rules for Fire Pumps

• Feeders originating from a separate service (or a connection upstream of the service) are now
addressed and permitted as a power source.

• The provisions for multiple sources have been expanded to address on-site standby generators
and combinations of services and on-site generation. The use of a generator as an alternate
source has also been addressed.

• Lastly, phase converters are now specifically prohibited as a power source for fire pumps.

Source URL: http://www.ecmweb.com/code-basics/nec-rules-fire-pumps

http://www.ecmweb.com/print/16540 10/10

You might also like