Sicam Fsi B Sensor Catalog en

The document provides information on the SICAM Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor), including a description of its functions, technical documentation, specifications, and ordering information. The B-Sensor is used to improve reliability and reduce downtime on MV overhead distribution grids by continuously measuring phase current and detecting phase and ground faults. It indicates temporary and permanent faults using optical LED flashing and can be mounted in junction points, branching points, and frequent fault areas.

Uploaded by

Jaime Paiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views10 pages

Sicam Fsi B Sensor Catalog en

The document provides information on the SICAM Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor), including a description of its functions, technical documentation, specifications, and ordering information. The B-Sensor is used to improve reliability and reduce downtime on MV overhead distribution grids by continuously measuring phase current and detecting phase and ground faults. It indicates temporary and permanent faults using optical LED flashing and can be mounted in junction points, branching points, and frequent fault areas.

Uploaded by

Jaime Paiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

SICAM

Fault Sensor Indicator (FSI)


V2.0 Basic Sensor (B-Sensor)
Catalog, Edition 1.0
Content

SICAM SICAM FSI V2.0 B-Sensor 1

Fault Sensor Indicator Description and Functions 1.1

(FSI) V2.0 Basic Sensor Technical Documentation 2


(B-Sensor) Technical Data 2.1

Type Test Specifications 2.2

Catalog Case Dimensions 2.3

Ordering Information 3

Ordering Information - SICAM FSI V2.0 B-Sensor 3.1

SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 3
SICAM FSI V2.0 B-Sensor
Description and Functions

Description
SICAM Fault Sensor Indicator (FSI) is developed using the latest
generation of hardware technology and is a member of the
1.1
Siemens SICAM short-circuit indicator product family.
The device is used to improve the reliability and to reduce the
downtime on the MV overhead distribution grid.
The device measures the phase current continuously and
detects the phase fault and ground fault when it is mounted
on the MV overhead line network.
The device indicates both the temporary fault and the perma-
nent fault via optical indication (LED flashing).
The device can be mounted in junction points/branching points
and areas of frequent fault. [sc_fsiv2_devicephoto1, 1, --_--]

Figure 1.1/1 SICAM FSI V2.0 B-Sensor


Applications
• This device is suitable for outdoor applications on MV over- Benefits
head line. Higher availability of overhead line networks
• Supports application on solidly grounded or resistive star- • Quick fault detection and localization, reduced downtime.
point grounded systems.
Ease of use
• The device is to be configured in close coordination with
the protection systems in the MV network. This results in • The device is effortlessly powered ON/OFF for installation,
improved fault detection and localization. storage and transportation using a single switch activation.

• The device can be mounted in groups of 3, one device on • The device is ready to install with factory configuration of
each phase. 11 kV and 18 mm cable diameter. Additionally, it includes
an auto threshold feature for convenient adjustment of fault
• To facilitate fault identification, a distinct LED flashing thresholds in dynamic load conditions.
sequence is generated by the device providing a clear indica-
tion of whether the fault is temporary or permanent. Installation

Functions • Supports installation on both insulated and non-insulated


overhead lines
Multiple settings available for fault detection
Simple configuration
• Threshold settings, auto-threshold, and di/dt settings. • Easy configuration of device parameters using SICAM FSI
Auto threshold algorithm Configurator
• Self-Adjustment of trip threshold based on phase current. Safe mounting
Inrush restraint • Safely mountable on the MV overhead line by using a hot stick
• Avoids false fault detection due to transformer magnetization with shotgun or hot stick (telescopic) with device adaptor.
during the voltage restoration on the MV overhead line. Long range fault indication visibility
Auto reclosure restraint • Fault localization becomes easier with the device's fault LED,
• Blocks the redundant fault detection during the auto-reclo- which offers visibility for up to 400 m during the day and
sure retries which are made to restore the MV overhead line. 800 m at night.1

Multiple fault indication reset functionalities Long battery life

• Voltage restoration in MV overhead line, auto timer reset and • 10 years of battery life, under standard operating conditions.
magnetic reset • Configurable blinking interval of LEDs for optimal battery life.
Self-Test Maintenance free
• Self-test by magnetic reset to verify the battery health of the • The device housing is weatherproof, UV stabilized, and flame
device. The sucess/failure of self-test is indicated by a specific retardant with an IP68 rating for durability.
LED flashing pattern.
Conformal coating
Low temperature cutoff
• The conformal coating on device electronic modules increases
• Built-in with an automatic cutoff feature when the tempera- protection against harmful environmental influences such as
ture falls below -40°C.1 extreme moisture, corrosive gases and aggressive dust.

1 Only applicable for B-Sensor Type 2. Refer to Ordering Information – SICAM FSI V2.0 B-Sensor, Page 10 for information on B-Sensor Type 1 and
Type 2.

4 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Technical Data

Indication of Conformity Fault-Detection Parameters

This product complies with the directive of the Fault current threshold (Iset) 10 A to 1500 A
Council of the European Communities on the harmo-
nization of the laws of the Member States relating • 10 A to 100 A (steps of 10 A)
to electromagnetic compatibility (EMC Directive • 100 A to 300 A (steps of 25 A)
2014/30/EU) and concerning electrical equipment • 300 A to 800 A (steps of 50 A)
for use within specified voltage limits (Low Voltage • 800 A to 1500 A (steps of 100 A)
Directive 2014/35/EU) as well as restriction on usage Auto threshold fault factor 2X to 4X (steps of 1X) 2.1
of hazardous substances in electrical and electronic Range change monitoring 20 s to 120 s (steps of 10 s)
equipment (RoHS Directive 2011/65/EU). time (T1)
This conformity has been proved by tests conducted Range change memorize 0 s to 120 s (steps of 30 s)
by Siemens AG in accordance of the Council time (T2)
Directive in accordance with the product standard DI current 5 A to 80 A (steps of 5 A), 120 A, 160 A
IEC/EN 61326-1 for the EMC directives, and with
Starting from 10 A phase current
the standard IEC/EN 61010-1 for the low-voltage
directive. RoHS directive 2011/65/EU is met using Fault-indication time B-Sensor Type 1: 2 h to 16 h (steps of 1 h)
the standard IEC/EN 63000. The device has been B-Sensor Type 2: 2 h to 4 h (steps of 1 h)
designed and produced for industrial use.
Permanent-fault verifica- 3 s, 35 s, and 70 s
tion time
Application Data Inrush restraint time 3 s, 30 s, and 60 s
Auto reclosure time 0.1 s to 99.9 s
Rated voltage (Vrated) 6.6 kV, 11 kV, 12.5 kV, 13.8 kV, 22 kV, 25
kV, 33 kV, 34.5 kV, 44 kV, 45 kV, 66 kV,
and 69 kV Reset Device
Maximum operating 83 kV
voltage Voltage restoration reset Vrated > 70%
Maximum operating 1500 A Magnet reset Using magnetic adaptor
current Auto timer reset B-Sensor Type 1: 2 h to 16 h (steps of 1 h)
Maximum continuous oper- 800 A
B-Sensor Type 2: 2 h to 4 h (steps of 1 h)
ating current
Operating current range 0 A to 1500 A
Fault Indication – LEDs
System frequency 50 Hz or 60 Hz network
as per IEC 62689-1 Indication 6 red LEDs
Grounding type Solidly grounded system or resistive star- Luminous flux 40 lm
point grounded systems
Visibility angle 360° (from ground level)
Voltage presence > 70% of Vrated
Visibility range (for fault B-Sensor Type 1: 100 m at day time, 500
Voltage absence < 45% of Vrated indication only) m at night time
Fault detection time 2 cycles ± 1 cycle B-Sensor Type 2: 400 m at day time, 800
Current measurement ± 10 % or ± 5 A whichever is greater from m at night time2
accuracy 0 A to 800 A MTBF of LEDs 45000 h
Power source Lithium-thionyl chloride batteries
Total fault-indication time B-Sensor Type 1: 1500 h of LED flashing Mechanical Data
B-Sensor Type 2: 400 h of LED flashing
Cable overall diameter 5 mm to 40 mm (non-insulated) Weight B-Sensor Type 1: approximately 1.04 kg

15 mm to 40 mm (insulated) B-Sensor Type 2: approximately 1.15 kg


Non-insulated conductor Aluminum Conductor Steel Reinforced Dimensions Diameter Height
type (ACSR), All Aluminum Alloy Conductor 116.8 mm 241.4 mm
(AAAC)
Insulated conductor type Single core, aluminum conductor steel Environmental Conditions
reinforced with/without waterblocking,
XLPE insulated
Outdoor applications as per IEC 61010-1
Temperature withstand of 230°C continuous
Degree of pollution Category 2
clamping material
Maximum altitude above 5000 m
sea level

2 B-Sensor Type 2 to have fault indication visibility range of 400 m at day time and 800 m at night time with 2 s blinking interval only.

SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 5
Technical Documentation
Type Test Specifications

This section describes about the type testing performed on Environmental Tests
SICAM FSI V2.0 B-Sensor according to IEC 61326-1, IEC 62689-1,
and IEC 61010-1. Test Reference Standard Test Requirement
EMI/EMC Tests Dry heat test IEC 62689-1 +75 °C
IEC 60068-2-2 Duration:
Test Reference Standard Test Requirement 16 h with device turned
Electrostatic IEC 62689-1, Table 16 Severity class 3 OFF
discharge test
IEC 61000-4-2 6 kV contact discharge, 16 h with device turned
8 kV air discharge ON
IEC 61326-1
2.2
Dry heat test IEC 60068-2-2 (+85 ±2) °C
Power frequency IEC 62689-1, Table 16 Severity class 4
magnetic field (storage)3 Duration: 16 h
IEC 61000-4-8 30 A/m continuous,
immunity 50 Hz/60 Cold test IEC 62689-1
300 A/m for 1 s to 3 s -40 °C4
Hz IEC 61326-1
As per IEC 61326; 30 A/m IEC 60068-2-1 Duration:
50 Hz, 60 Hz (magneti-
16 h with device turned
cally sensitive equipment)
OFF
Pulse magnetic IEC 62689-1, Table 16 Severity class 4
field immunity 16 h with device turned
IEC 61000-4-9 300 A/m peak value; 20 ON
positive and 20 negative
IEC 61326-1 Cold test (Storage)3 IEC 60068-2-1 (-40 ± 2) °C4
Radiated emission CISPR 32 Class A Duration: 16 h
test
EN 55032 30 MHz to 1000 MHz Damp heat steady IEC 60068-2-78 (-40 ±2) °C, (95 ±3)%
state test
IEC 61326-1 (30 MHz to 230 MHz): Duration: 4 days
40 dB (µV/m) QP (at Damp heat cyclic IEC 60068-2-30 Lower temperature: 25 °C
10 m) test (12 h + 12 h)
Upper temperature: 55 °C
(230 MHz to 1000 MHz):
47 dB (µV/m) QP Relative humidity: 95 %,
(at 10 m) ±3%

1 GHz to 6 GHz No of cycles: 6 cycles


Change of temper- IEC 62689-1 (-40 ±2) °C, (+75 ±2) °C
(1 GHz to 3 GHz):
ature test
56 dB (µV/m) AV, 76 dB IEC 60068-2-14 Rate of change:
(µV/m) PK (at 3 m) (1 ± 0.2) K/min
(3 GHz to 6 GHz): Dwell at upper and lower
60 dB (µV/m) AV, temperatures 3 h + 3 h
80 dB (µV/m) PK (at 3 m)
50 h 25 min OFF +
Damped oscillatory IEC 62689-1 Severity class 4, 50 h 25 min ON
magnetic field test Salt mist test ASTM B117 Salt solution: 95 parts
IEC 61000-4-10 30-A/m peak value
distilled water by weight
IEC 60068-2-11
Oscillation frequency: & 5 parts sodium chloride
0.1 MHz and 1 MHz, by weight
± 10%
Duration of exposure:
Orientation: XYZ 168 h
Test duration: 2 s or Exposure to solar IEC 62689-1 1000 W/m2
continuous for 1 min radiation
IEC 60068-2-5 Duration: 8 h
Radio frequency, IEC 62689-1 Severity class 3
Exposure to direct ASTM G155-13 Exposure cycle 1
electromagnetic
IEC 61000-4-3 0.08 GHz to 1 GHz sunlight (UV)
field immunity Irradiance for wave
IEC 61326-1 10 V/m, 80% AM 1 kHz, lengths: 340 nm/W
1 % step (m² ⋅ nm)
1 GHz to 6 GHz Duration of light: 102
min
3 V/m, 80 % AM 1 kHz,
1 % step Total exposure time: 14
days
Dwell time: 2.85 s
Wind pressure test Withstand wind speed of
200 km/h

3 For optimum battery capacity, it is recommended to store the device below 30°C; 30% RH
4 Only applicable for B-Sensor Type 2. -25 °C applicable for B-Sensor Type 1.

6 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Type Test Specifications

Mechanical Tests Safety Test

Test Reference Standard Test Requirement Test Reference Test Requirement


Vibration response IEC 62689-1 Frequency: 10 Hz to Standard
test (sinusoidal) 500 Hz Product safety test EN/IEC 61010-1 Tests as per clause no. 4
IEC 60068-2-6
10 m/s2
amplitude Marking and documentation
0.075 mm, 23 min as per clause no. 5
Sweep rate: 1 oct./min Protection against electric
shock as per clause no. 6
Number of sweep cycles:
2/axis in 3 directions Protection against mechanical 2.2
Vibration endurance IEC 60255-21-1 Class 1 hazard as per clause no. 7
(Sinusoidal) Resistance to mechanical
IEC 60068-2-6 Frequency: 10 Hz to
150 Hz stresses (shock and impact) as
per clause no. 8
Amplitude: 1 g (10 m/s2)
Protection against the spread
Number of sweep cycles: of fire as per clause no. 9
20/axis in 3 directions
Equipment temperature limits
Sweep rate: 1 oct./min and resistance to heat as per
Shock response test IEC 60068-2-27 Class 1, 5 g, 11 ms, 6 clause no. 10
pulses in each X, Y, Z axis Protection against liberated
IEC 60255-21-2
Shock withstand test IEC 60068-2-27 Class 1, 15 g, 11 ms, 6 gases and substances, explo-
pulses in each X, Y, Z axis sion, and implosion as per
IEC 60255-21-2 clause no. 13
Bump test IEC 60068-2-27/IEC 400 m/s2, 40 g Components and subassem-
60068-2-29 blies as per clause no. 14
Duration of pulse: 6 ms
Number of sweeps: 2000 Hazards resulting from appli-
positive and 2000 nega- cation as per clause no. 16
tive shocks Risk assessment as per clause
Number of axes: 3 (X, Y, no. 17
and Z)
Number of bumps: 1000 Electrical Test
per direction
Number of directions: 2 Test Reference Standard Test Requirement
per axis Dielectric withstand IEC/EN 61010-1 125 kV with the help
of hotstick
Total number of bumps:
6000 shocks in 3 axes Overvoltage IEC/EN 61010-1 Category IV
Seismic test IEC 60068-3-3 Class 1 Degree of pollution IEC/EN 61010-1 Category 2
IEC 60255-21-3 Frequency: 5 Hz to 35 Hz Maximum altitude IEC/EN 61010-1 5000 m
above sea level
IEC TR 62271-300 Sweep rate: 1 octave/min
Short-circuit current IEC 62689-1 12.5 kA @ 1 s
10 min for test cycle withstand test
25 kA @ 170 ms
Frequency: 5 Hz to 8 Hz Short time current/ IEC62689-1 25 kA RMS for 3 s and
(horizontal), 3.5 mm Dynamic test 62.5 kA peak
amplitude
40 kA RMS for 1 s and
Frequency: 5 Hz to 8 Hz 100 kA peak
(vertical), 1.5 mm ampli-
Switching impulse test IEC 60060-1 33 kV/175 kV, and 66
tude
kV/250 kV
Frequency: 8 Hz to 35 Hz
250 µs/2500 µs, no of
(horizontal), 1 g (10 m/s2)
shots: 5
acceleration
Line voltage 33 kV,
Frequency: 8 Hz to 35 Hz
switching impulse
(vertical), 0.5 g (5 m/s2)
voltage 175 kV
acceleration
Ingress of protection IEC 62689-1 IP68 category 1 Line voltage 66 kV,
test switching impulse
IEC 60529 voltage 250 kV
Mechanical impact IEC 62689-1 IK09, Impact energy: 10 J
test
IEC 62262

SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 7
Technical Documentation
Type Test Specifications

Test Reference Standard Test Requirement


Lightning impulse test IEC 60060-1 33 kV/200 kV, and 66
kV/350 kV
1.2 µs/50 µs, no of
shots: 5
Line voltage 33 kV,
switching impulse
voltage 200 kV
Line voltage 66 kV,
2.2 switching impulse
voltage 350 kV
Average rainfall test — Average rainfall per
year: 3500 mm

Optical Tests

Test Reference Standard Test Requirement


Lumens test LM 79 40 lumens
Goniometry test LM79 360° visibility

8 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Case Dimensions

Device Dimensions

2.3

[dw_fsibsensordimensions, 1, en_US]

Figure 2.3/1 Device Dimensions

SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 9
Ordering Information
Ordering Information - SICAM FSI V2.0 B-Sensor

Ordering Information – SICAM FSI V2.0 B-Sensor

Description Versions Order no.


1 2 3 4 5 6 7 8 9 10 11 12

6 M D 2 3 1 4 - 2 B C □ 0

SICAM FSI V2.0 B-Sensor │
• Phase-fault detection
• Ground-fault (di/dt) detection
B-Sensor Type 1 • UV stabilized polycarbonate IP68 rated housing 2
• Operating temperature range: -25°C to +75°C
• Fault indication visibility: 100 m during daytime, 500 m during
night time
• Phase-fault detection
• Ground-fault (di/dt) detection
3.1 B-Sensor Type 2 • UV stabilized polycarbonate IP68 rated housing 3
• Operating temperature range: -40°C to +75°C
• Fault indication visibility: 400 m during daytime, 800 m during
night time
Spare parts and accessories 6 M D 2 3 1 8 - 4 □ □ 0 □
▲ ▲ ▲
Spare part │ │ │
SICAM FSI V2.0 B-Sensor Lithium-thionyl chloride battery set (pack
B B 1
of 6)
Accessories │ │ │
Magnet adaptor for device reset, accessory for hot stick with
M A 4
shotgun
Device adaptor for SICAM FSI V2.0 mounting via hot stick (tele-
M A 6
scopic)
Accessory Description
Recommended brand: Terex hot stick with shotgun, Ritz, catalog number: RC403-0295
Hot stick with shotgun for SICAM FSI For more detailed information visit: http://www.terexutilities.com.br
V2.0 B-Sensor mounting, 4 m Recommended brand: Hubbell hot stick with shotgun, catalog number: C4030295
For more detailed information visit: https://www.hubbell.com/hubbellpowersystems/en/
Hot stick (telescopic) for SICAM FSI Recommended brand: Terex Ritz, catalog no.: VTT-1/9
V2.0 B-Sensor mounting, 12 m For more detailed information visit: http://www.terexutilities.com.br
USB Type-C cable for SICAM FSI V2.0
Standard off-the-shelf USB Type C cable for device configuration using FSI configurator.
B-Sensor configuration

Table 3.1/1 SICAM FSI V2.0 B-Sensor Selection and Ordering Data

10 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Published by and copyright © 2023 Subject to changes and errors.

Siemens AG The information given in this document


Smart Infrastructure only contains general descriptions and / or
Digital Grid performance features which may not always
Humboldtstraße 59 specifically reflect those described or which
90459 Nuremberg may undergo modification in the course of
Germany further development of the products.
Web: www.siemens.com/sicam-fsi
Customer Support: www.siemens.com/csc The requested performance features are
binding only when they are expressly
For enquires please contact our agreed upon in the concluded contract.
Customer Support Center
Phone: +49 911 2155 4466
Email: [email protected]

Article No: E50417-X8940-C657-A1

© 2023 by Siemens AG, Berlin and Munich