Sicam Fsi B Sensor Catalog en
Sicam Fsi B Sensor Catalog en
Ordering Information 3
SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 3
SICAM FSI V2.0 B-Sensor
Description and Functions
Description
SICAM Fault Sensor Indicator (FSI) is developed using the latest
generation of hardware technology and is a member of the
1.1
Siemens SICAM short-circuit indicator product family.
The device is used to improve the reliability and to reduce the
downtime on the MV overhead distribution grid.
The device measures the phase current continuously and
detects the phase fault and ground fault when it is mounted
on the MV overhead line network.
The device indicates both the temporary fault and the perma-
nent fault via optical indication (LED flashing).
The device can be mounted in junction points/branching points
and areas of frequent fault. [sc_fsiv2_devicephoto1, 1, --_--]
• The device can be mounted in groups of 3, one device on • The device is ready to install with factory configuration of
each phase. 11 kV and 18 mm cable diameter. Additionally, it includes
an auto threshold feature for convenient adjustment of fault
• To facilitate fault identification, a distinct LED flashing thresholds in dynamic load conditions.
sequence is generated by the device providing a clear indica-
tion of whether the fault is temporary or permanent. Installation
• Voltage restoration in MV overhead line, auto timer reset and • 10 years of battery life, under standard operating conditions.
magnetic reset • Configurable blinking interval of LEDs for optimal battery life.
Self-Test Maintenance free
• Self-test by magnetic reset to verify the battery health of the • The device housing is weatherproof, UV stabilized, and flame
device. The sucess/failure of self-test is indicated by a specific retardant with an IP68 rating for durability.
LED flashing pattern.
Conformal coating
Low temperature cutoff
• The conformal coating on device electronic modules increases
• Built-in with an automatic cutoff feature when the tempera- protection against harmful environmental influences such as
ture falls below -40°C.1 extreme moisture, corrosive gases and aggressive dust.
1 Only applicable for B-Sensor Type 2. Refer to Ordering Information – SICAM FSI V2.0 B-Sensor, Page 10 for information on B-Sensor Type 1 and
Type 2.
4 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Technical Data
This product complies with the directive of the Fault current threshold (Iset) 10 A to 1500 A
Council of the European Communities on the harmo-
nization of the laws of the Member States relating • 10 A to 100 A (steps of 10 A)
to electromagnetic compatibility (EMC Directive • 100 A to 300 A (steps of 25 A)
2014/30/EU) and concerning electrical equipment • 300 A to 800 A (steps of 50 A)
for use within specified voltage limits (Low Voltage • 800 A to 1500 A (steps of 100 A)
Directive 2014/35/EU) as well as restriction on usage Auto threshold fault factor 2X to 4X (steps of 1X) 2.1
of hazardous substances in electrical and electronic Range change monitoring 20 s to 120 s (steps of 10 s)
equipment (RoHS Directive 2011/65/EU). time (T1)
This conformity has been proved by tests conducted Range change memorize 0 s to 120 s (steps of 30 s)
by Siemens AG in accordance of the Council time (T2)
Directive in accordance with the product standard DI current 5 A to 80 A (steps of 5 A), 120 A, 160 A
IEC/EN 61326-1 for the EMC directives, and with
Starting from 10 A phase current
the standard IEC/EN 61010-1 for the low-voltage
directive. RoHS directive 2011/65/EU is met using Fault-indication time B-Sensor Type 1: 2 h to 16 h (steps of 1 h)
the standard IEC/EN 63000. The device has been B-Sensor Type 2: 2 h to 4 h (steps of 1 h)
designed and produced for industrial use.
Permanent-fault verifica- 3 s, 35 s, and 70 s
tion time
Application Data Inrush restraint time 3 s, 30 s, and 60 s
Auto reclosure time 0.1 s to 99.9 s
Rated voltage (Vrated) 6.6 kV, 11 kV, 12.5 kV, 13.8 kV, 22 kV, 25
kV, 33 kV, 34.5 kV, 44 kV, 45 kV, 66 kV,
and 69 kV Reset Device
Maximum operating 83 kV
voltage Voltage restoration reset Vrated > 70%
Maximum operating 1500 A Magnet reset Using magnetic adaptor
current Auto timer reset B-Sensor Type 1: 2 h to 16 h (steps of 1 h)
Maximum continuous oper- 800 A
B-Sensor Type 2: 2 h to 4 h (steps of 1 h)
ating current
Operating current range 0 A to 1500 A
Fault Indication – LEDs
System frequency 50 Hz or 60 Hz network
as per IEC 62689-1 Indication 6 red LEDs
Grounding type Solidly grounded system or resistive star- Luminous flux 40 lm
point grounded systems
Visibility angle 360° (from ground level)
Voltage presence > 70% of Vrated
Visibility range (for fault B-Sensor Type 1: 100 m at day time, 500
Voltage absence < 45% of Vrated indication only) m at night time
Fault detection time 2 cycles ± 1 cycle B-Sensor Type 2: 400 m at day time, 800
Current measurement ± 10 % or ± 5 A whichever is greater from m at night time2
accuracy 0 A to 800 A MTBF of LEDs 45000 h
Power source Lithium-thionyl chloride batteries
Total fault-indication time B-Sensor Type 1: 1500 h of LED flashing Mechanical Data
B-Sensor Type 2: 400 h of LED flashing
Cable overall diameter 5 mm to 40 mm (non-insulated) Weight B-Sensor Type 1: approximately 1.04 kg
2 B-Sensor Type 2 to have fault indication visibility range of 400 m at day time and 800 m at night time with 2 s blinking interval only.
SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 5
Technical Documentation
Type Test Specifications
This section describes about the type testing performed on Environmental Tests
SICAM FSI V2.0 B-Sensor according to IEC 61326-1, IEC 62689-1,
and IEC 61010-1. Test Reference Standard Test Requirement
EMI/EMC Tests Dry heat test IEC 62689-1 +75 °C
IEC 60068-2-2 Duration:
Test Reference Standard Test Requirement 16 h with device turned
Electrostatic IEC 62689-1, Table 16 Severity class 3 OFF
discharge test
IEC 61000-4-2 6 kV contact discharge, 16 h with device turned
8 kV air discharge ON
IEC 61326-1
2.2
Dry heat test IEC 60068-2-2 (+85 ±2) °C
Power frequency IEC 62689-1, Table 16 Severity class 4
magnetic field (storage)3 Duration: 16 h
IEC 61000-4-8 30 A/m continuous,
immunity 50 Hz/60 Cold test IEC 62689-1
300 A/m for 1 s to 3 s -40 °C4
Hz IEC 61326-1
As per IEC 61326; 30 A/m IEC 60068-2-1 Duration:
50 Hz, 60 Hz (magneti-
16 h with device turned
cally sensitive equipment)
OFF
Pulse magnetic IEC 62689-1, Table 16 Severity class 4
field immunity 16 h with device turned
IEC 61000-4-9 300 A/m peak value; 20 ON
positive and 20 negative
IEC 61326-1 Cold test (Storage)3 IEC 60068-2-1 (-40 ± 2) °C4
Radiated emission CISPR 32 Class A Duration: 16 h
test
EN 55032 30 MHz to 1000 MHz Damp heat steady IEC 60068-2-78 (-40 ±2) °C, (95 ±3)%
state test
IEC 61326-1 (30 MHz to 230 MHz): Duration: 4 days
40 dB (µV/m) QP (at Damp heat cyclic IEC 60068-2-30 Lower temperature: 25 °C
10 m) test (12 h + 12 h)
Upper temperature: 55 °C
(230 MHz to 1000 MHz):
47 dB (µV/m) QP Relative humidity: 95 %,
(at 10 m) ±3%
3 For optimum battery capacity, it is recommended to store the device below 30°C; 30% RH
4 Only applicable for B-Sensor Type 2. -25 °C applicable for B-Sensor Type 1.
6 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Type Test Specifications
SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 7
Technical Documentation
Type Test Specifications
Optical Tests
8 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Technical Documentation
Case Dimensions
Device Dimensions
2.3
[dw_fsibsensordimensions, 1, en_US]
SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog 9
Ordering Information
Ordering Information - SICAM FSI V2.0 B-Sensor
6 M D 2 3 1 4 - 2 B C □ 0
▲
SICAM FSI V2.0 B-Sensor │
• Phase-fault detection
• Ground-fault (di/dt) detection
B-Sensor Type 1 • UV stabilized polycarbonate IP68 rated housing 2
• Operating temperature range: -25°C to +75°C
• Fault indication visibility: 100 m during daytime, 500 m during
night time
• Phase-fault detection
• Ground-fault (di/dt) detection
3.1 B-Sensor Type 2 • UV stabilized polycarbonate IP68 rated housing 3
• Operating temperature range: -40°C to +75°C
• Fault indication visibility: 400 m during daytime, 800 m during
night time
Spare parts and accessories 6 M D 2 3 1 8 - 4 □ □ 0 □
▲ ▲ ▲
Spare part │ │ │
SICAM FSI V2.0 B-Sensor Lithium-thionyl chloride battery set (pack
B B 1
of 6)
Accessories │ │ │
Magnet adaptor for device reset, accessory for hot stick with
M A 4
shotgun
Device adaptor for SICAM FSI V2.0 mounting via hot stick (tele-
M A 6
scopic)
Accessory Description
Recommended brand: Terex hot stick with shotgun, Ritz, catalog number: RC403-0295
Hot stick with shotgun for SICAM FSI For more detailed information visit: http://www.terexutilities.com.br
V2.0 B-Sensor mounting, 4 m Recommended brand: Hubbell hot stick with shotgun, catalog number: C4030295
For more detailed information visit: https://www.hubbell.com/hubbellpowersystems/en/
Hot stick (telescopic) for SICAM FSI Recommended brand: Terex Ritz, catalog no.: VTT-1/9
V2.0 B-Sensor mounting, 12 m For more detailed information visit: http://www.terexutilities.com.br
USB Type-C cable for SICAM FSI V2.0
Standard off-the-shelf USB Type C cable for device configuration using FSI configurator.
B-Sensor configuration
Table 3.1/1 SICAM FSI V2.0 B-Sensor Selection and Ordering Data
10 SICAM ⋅ Fault Sensor Indicator (FSI) V2.0 Basic Sensor (B-Sensor) ⋅ Catalog
Published by and copyright © 2023 Subject to changes and errors.