Micom P141

This document is a test certificate for a MICOM P141 relay. It provides details of the nameplate, service settings, secondary injection testing results, general checkup, and remarks. The secondary injection testing verified the operation of the overcurrent, earth fault, undervoltage, and overvoltage protection settings within acceptable times. Differential testing also showed the relay operating current to be close to the calculated differential current. The relay passed all tests and was found to be in working order.

Uploaded by

jalaj bisen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
220 views3 pages

Micom P141

This document is a test certificate for a MICOM P141 relay. It provides details of the nameplate, service settings, secondary injection testing results, general checkup, and remarks. The secondary injection testing verified the operation of the overcurrent, earth fault, undervoltage, and overvoltage protection settings within acceptable times. Differential testing also showed the relay operating current to be close to the calculated differential current. The relay passed all tests and was found to be in working order.

Uploaded by

jalaj bisen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

P a g e | 81

DESIGN, ENGINEERING, TESTING & COMMISSIONING

TEST CERTIFICATE OF MICOM P141 RELAY AKSHAR LEEPANT


Client M/S. INOX AIR PRODUCTS PVT. LTD., SIMEJ Tested On 06/09/2022
Plant CRP RELAY Tested By DHARMESH
Location CRP RELAY Comp. Code -

1.0 NAME PLATE DETAILS OF RELAY:


MAKE TYPE SR. NO. CT RATIO AUX. VOLT.
ALSTOM P-141 34232675/10/17 100/1 A 110-250 VAC/DC

2.0 SERVICE SETTINGS:


SR. NO. PARAMETER SERVICE SETTING
O/C PROTECTION STANDARD
1 I > 1 FUNCTION IEC INVERSE
2 I > 1 DIRECTIONAL FORWARD
3 I > 1 CURRENT SET 1.520 A
4 I > 1 TMS 0.280
5 I > 1 DT ADDRESS 0.00 sec
6 I > 1 tRESET 0.00 sec
7 I > 3 STATUS ENABLED
8 I > 3 DIRECTIONAL NON-DIRECTIONAL
9 I > 3 CURRENT SET 15.74 A
10 I > 3 TIME DELAY 0.10 sec
E/F PROTECTION
1 IN1 > 1 INPUT MEASURED
2 IN1 > 1 FUNCTION IEC S. INVERSE
3 IN1 > 1 DIRECTION FORWARD
4 IN1 > 1 CURRENT 0.280 A
5 IN1 > 1 TMS 0.250
6 IN1 > 1 DT ADDRESS 0.00 sec
7 IN1 > 1 tRESET 0.00 sec
8 IN1 > 3 STATUS ENABLED
9 IN1 > 3 DIRECTIONAL NON-DIRECTIONAL
10 IN1 > 3 CURRENT 6.00 A
11 IN1 > 3 TIME DELAY 0.10 sec
U/V PROTECTION
1 U < MEASUREMENT MODE PHASE-PHASE
2 U < OPERATED MODE ANY PHASE
3 U < FUNCTION DT
4 U < VOLTAGE 88.0 V

Date Date Date 08/09/2022


Witness by Witness by Prepared JAIMITA
by
Sign Sign Sign
AKSHAR LEEPANT
P a g e | 82

DESIGN, ENGINEERING, TESTING & COMMISSIONING

5 U < TIME DELAY 5.0 sec


6 U > 2 MEASUREMENT MODE PHASE-PHASE
7 U > 1 OPERATED MODE ANY PHASE
8 U > 1 FUNCTION DT
9 U > 1 VOLTAGE 154 V
10 U > 1 TIME DELAY 100 msec
FREQUENCY SETTING
1 F < 1 SETTING 49.50 Hz
2 F < 1 TIME DELAY 5.0 sec
3 F < 2 SETTING 49.00 Hz
4 F < 2 TIME DELAY 1.0 sec
5 F > 1 SETTING 50.50 Hz
6 F > 1 TIME DELAY 5.0 sec
7 F > 2 SETTING 51.00 Hz
8 F > 2 TIME DELAY 1.0 sec

3.0 SECONDARY INJECTION TEST:


3.1 I>1:
OPER. TIME IN SECS (TMS = 1.00)
SET CURRENT IN AMP PSM
R Y B
2 9.56 9.51 9.54
0.10 5 4.30 4.34 4.23
10 2.91 2.97 2.91

3.2 I>>:
SET CURRENT
OPR. CURRENT (AMP) SET TIME (SECS) OPR. TIME (SECS) OPER. INDI.
(AMP)
15.00 15.03 0.10 0.104 OK

3.3 IN>:
OPER. TIME IN SECS (TMS = 1.00)
SET CURRENT IN AMP PSM
E/F
2 9.51
0.28 5 4.16
10 2.94

3.4 IN>>:
SET CURRENT (AMP) OPR. CURRENT (AMP) SET TIME (SECS) OPR. TIME (SECS) OPER. INDI.
Date Date Date 08/09/2022
Witness by Witness by Prepared JAIMITA
by
Sign Sign Sign
AKSHAR LEEPANT
P a g e | 83

DESIGN, ENGINEERING, TESTING & COMMISSIONING

6.00 6.07 0.10 0.108 OK

4.0 GENERAL CHECKUP :


4.1 INSPECTION FOR PHYSICAL DAMAGE OK
4.2 WIRING CHECK OK
4.3 SERVICE SETTING RESET OK

5.0 REMARKS : TESTED OK

Time Relay Differential


Relay Set %Slop set Phase side Neutral Side
phase delay Operating Current
Amp at current Current
set current calculated
R 0.05 0.1 10% 0.08 0.3175 0.074 0.075
Y 0.05 0.1 50% 0.72 0.21 0.51 0.525
B 0.05 0.1 10% 0.075 0.3225 0.073 0.075

Date Date Date 08/09/2022


Witness by Witness by Prepared JAIMITA
by
Sign Sign Sign
AKSHAR LEEPANT