1j - Overcurrent Protection and EF
1j - Overcurrent Protection and EF
Busbars
Auto-Transformers
TRANSMISSION NETWORK Interconnected Feeders
Busbars
Interconnectors
Double Wound Transformers
DISTRIBUTION Radial Feeders
NETWORK Ring Mains
Embedded Generation
Motors
G M
UTILISATION
Current increases
Short
with load
circuit
MOTOR MOTOR
3 Phase
Fuses Overcurrent
Relay
3 Phase Fault Detect and interrupt overcurrents
2 Phase
2 Phase Fault Overcurrent
Relay
3 PH - E Fault
Zero output
for balanced
or phase fault
PH - E Fault Residually conditions
connected
relay
EF current path thru
transformer earth
EARTHING REACTANCE
PETERSON COIL Smaller and less
TRANSFORMER Reactance chosen to expensive than resistance.
Used where system equal system capacitance Can cause high over-volts.
neutral not available
2 Phase Overcurrent and Earth Fault 3 Phase Overcurrent and Earth Fault
Non-unit protection
630A (Equivalent
Fault Max. 13100A 8800A 2900A 1200A 600A HV Currents)
current Min. 6850A 5400A 2400A 1100A E
MV
F1 Load
Relay at 'A' set to
F2 F
operate for max. fault 8800A
current at remote end
A RADIAL B C D
DISTRIBUTION
SYSTEM
D C B A
AIM - Protection co-ordinated to ensure minimum unfaulted load is t
disconnected
Unreliable Scheme
Currents F1 and F2 may be similar - loss of discrimination
For minimum infeed A - B may be unprotected
NOTE: Max. fault at S/Stn. E < min. fault current between D-E Amps
63
12
29
88
0A
00
00
00
A
A
Protection notice / Copyright notice
Page 11 Kevin Hearfield Reyrolle Protection Devices
4.2) Time Graded Protection
Infeed E
MV
Load
F
1.4s 1.0s 0.6s 0.2s
A B C D
Operating Time
Definite minimum time
10s
Numeric IDMT relay operating algorithm:
3s
2s
0.14
t= 0.02
×T.M.
⎛I ⎞
⎜⎜ ⎟⎟ −1 2x 10x 30x
⎝ IS ⎠ Multiple of Current Setting
Current Setting 1A
Current Setting 1A Current Setting 1.5A
Time Multiplier 1.5
Time Multiplier 1.0 Time Multiplier 1.0
Time Multiplier 0.1
15s 24.5s
10s
4.5s
3s 3.62s
3s
2s 2.27s
1s
0.3s
0.2s
10000
IDMT Curve - General applications
0.14
t= 0.02
× T .M .
⎛ I ⎞
⎜⎜ ⎟⎟ −1
⎝ IS ⎠
1000
VIDMT Curve
Closer grading where fault
levels differ significantly
13.5
t= × T .M . 100
⎛ I ⎞
⎜⎜ ⎟⎟ − 1
⎝ IS ⎠
Time
(sec)
EIDMT Curve – Grading with fuses
10
80
t= 2
× T .M .
⎛ I ⎞
⎜⎜ ⎟⎟ − 1 Long Time Inverse
⎝ IS ⎠
Normal Inverse
120
t= × T .M . Very Inverse
⎛ I ⎞
⎜⎜ ⎟⎟ − 1
⎝ IS ⎠
0.1
Extremely Inverse
Characteristics can be supplemented with LS and HS 1 2 3 4 5 6 8 10 20 30 50 70 100
Stages e.g. to assist grading with complex characteristics
Current (multiples of setting)
Between Fuse
two characteristics
fuses
Required Relay
Time Overshoot
Delay Between
"Grading relay Recommended current ratio > 2:1
Margin" Arcing
and
fuse
Safety
Margin
Minimum
Relay Pre-Arcing Pre-
Arcing
Operating Arcing
Time 0 ms Pre-
Arcing
t' = 0.4tf + 0.15s 0 ms
R2 R1
Safety
Margin
Overshoot
(R2) Overshoot
Required Required
Time Circuit Time
Delay Breaker Delay
"Grading Between Between
Tripping "Grading Arcing
Margin" two Time Margin"
relay and
relays fuse
CT Error
- IDMT only
Minimum
Maximum Pre-
Relay
Relay Arcing
Minimum Operating
Operating Time
Relay 0 ms
Time
Operating
Time
0 ms
Older System
Safety
Margin
Newer System
Overshoot Safety
Margin
Min. Op.
Time 0 ms
165A 50A
X = 7% 95A 80A
33kV Bus 11kV Bus
PROCEDURE
A 125% 0.375
B 100% 0.275
C 75% 0.175
B A
@ D: P.S.M. = 626/(100 x 1.25) = 5 D 125% 0.05
For p.s.m. 5: NI operating time = 4.3s C
t
4.3 x TMS = 4.3 x 0.05 = 0.215s D
28
57
6
10
82
53
Protection notice / Copyright notice
Page 20 Kevin Hearfield Reyrolle Protection Devices
4.4a) Industrial System Protection Co-ordination Study
280 MVA
Relay Characteristics
450A
Protection notice / Copyright notice
Page 21 Kevin Hearfield Reyrolle Protection Devices
Protection Grading Software – OC & EF Studies
33/11kV
15MVA 11.8MVA
20.4% X'd = 23% NE
600/5
1
1000/5 2J
1C
6.6kV S/S 20A
Max/min 3PF
@ 6.6kV
1000/5 1L 16.8 / 12.7kA
2D
R2
10.00
10.00
2J
NE
1
1L
2D
1.00 1.00
11kV Max. Fault
12.5MVA Tx. Let Thru
Device Is TM Inst.
15MVA Tx. Let Thru
11kV EF 600A
Gamma See generator prot. report SEF 0.2 x In 0.4s
OC 1.50 x In 1.0 EI 12.0 x In
2D AG2-
SEF 0.2 x In 0.4s DTL
OC 1.50 x In 0.6 NI
2J FM-
EF 0.4 x In 0.65 NI
OC 1.25 x In 0.2 NI
1L AG1-
EF 0.4 x In 0.45 NI
0.01
0.01
10 100 1000 10000
100 1000 Current (Amps @ 11kV) 10000 100000 Current (Amps @ 11kV)
FAULT
R3 R2 R1 Clashing conductors or re-sealing cable
% of Algorithm
TRIP
Disc Travel
Time Time
Some compromise may be necessary where more than two relay points are in series
Power Flow
HS1 HS1
50ms 50ms
DTL DTL
Incomer
Pow er flow
Block
HS1 Trip
IDMT
HS1
RADIAL SUBSTATION
IDMT
F1
OC/EF Earth
fault
HV CB tripped
NVD
by local
protection
MV CB must therefore be tripped by:
Balanced
System R phase EF
EF on non-effectively earthed system voltages
Inverse
Inverse time element
time element
Set above max. fault Instantaneous high-set
current at s/stn. B primary setting 7000A Plain Feeder
Transformer Feeder
Protection notice / Copyright notice
Page 33 Kevin Hearfield Reyrolle Protection Devices
6b) HSOC Example - Calculating System Impedances
33kV
Transformer Feeder
Max fault 1000 MVA
33/11kV
Min fault 650 MVA
24MVA
Z = 22.5% 11kv
20km (0.3 + j0.43) Ohms/km
Instantaneous high-set
33kV Source
33/11kV
Max impedance = j1.68 Ohms
j10.21 Ohms 11kV
Min impedance = j1.09 Ohms 6 + j8.6 Ohms
IDMT element
Min infeed: 3ph max infeed
HSOC 3ph fault 1601A 917A @ 33kV
ph-ph fault 1387A
SPECIAL CONSIDERATIONS
IYC
IBC
IC
F1 Delta or Un -
Earthed Star IYC
Winding
VR
IC
IBC
Instantaneous earth fault protection can be used to protect
feeder and un-earthed transformer winding, however:
VB VY
IYC
IBC
IC
F1
IYC = 21.8A
VR
IC = 37.8A
On occurence of an EF (F1) the affected phase will be earthed. 33kV
system is resistance earthed, healthy phase voltage rises to line
volts level. IBC
Earthed Winding
F1
F3 E1
F2
Provides inst. prot for transformer feeder phase and earth faults
I I
K K
3 3
I
SOURCE K I
3
I F
SOURCE
F
I 2I
I K I I
K I I 3 K
3 3
Earth faults on star side of transformer is seen as a phase fault on Delta side
A phase fault on the star side of the transformer requires an additional current grading margin of :
HV Source HV Source
DTL
Stage
2 Trip
IDMT IDMT
2 Stage Overcurrent
Protection
Separate
HV and LV Improved discrimination
Overcurrent Reduced grading margin
Protection
CT and Relay cost saving
F1
F2
Interlocked Overcurrent Relay
Busbar
Normally Inhibited - Until
Protection
Operation of Busbar Prot.
NETWORK
Generator
100
Tap Setting as % of Tap
75 Volts Controlled OC
25 50 75 100
Input Voltage (% of rated voltage)
51 A C 51
LOAD
51 B D 51
I1 I1 + I2
A&B
51 A C 51
I2
LOAD
C&D
51 B D 51
Conventional grading:
Grade A with C
Grade B with D Faulted feeder:
A and B have the same setting Fault current can flow in both directions
C and D have the same setting Relays C and D operate together
Both feeders will be tripped
51 E LOAD
51 B D 67
Load current always flows in non-operate direction Grade A and B with E, assuming one
feeder in service
Any current flowing in operate direction is indicative
of a fault condition. Grade A with D (and B with C)
assuming both feeders in service
Therefore relays C and D may have sensitive setting,
fast operating time
RMU
A B' B C' C D'
67 67 67 67
51 67
67 67 67 67
51 67
LOAD LOAD
With ring closed both load and fault current may flow in either direction - directional relays are required
RMU
67 67
51 67
RMU RMU
67 67
51
RMU RMU
F1
A B' B C'
67 67 67 67
Source
Substation 67 67 67 67
A' F2 D D' C
RMU
Option 2 Source 2
Option 1
Fit pilot wire protection to Substation
Trip least important
circuit A - B source instantaneously
50
Consider S/Stns A & B as Then treat as ring main
common source busbar with single source
A B' B C'
67 67 67 67
87 87
Source 1
Substation
67 67 67 67
A' D D' C
RMU
Directional OC protection required if current can flow in both directions through relay location e.g.
Parallel feeders, Ring main circuits
Direction of a.c. is by inference not an absolute quantity, it is measured relative to some reference quantity alternating at
the same frequency - the system voltage.
I = OPERATING QUANTITY
Reference V = POLARISING QUANTITY
Comparing phase current (e.g. IRED) with relevant phase voltage (e.g. VRED) would indicate dirn of current flow, however;
USE OF FAULT VOLTAGE IS UNRELIABLE (System volts at point of fault will collapse towards zero)
Each phase of directional overcurrent relays must be polarised with a voltage which will not be reduced excessively (close
up 3-phase faults notwithstanding)
Red
IR VR-B IR-Y VR-B IR -VB-N IR VY-B
Phase
Yellow
IY VY-R IY-B VY-R IY -VR-N IY VB-R
Phase
Blue
IB VB-Y IB-R VB-Y IB -VY-N IB VR-Y
Phase
VR VR-B VR VR
VR VR-B
IR-
300 IR IR
IR Y 600
-VB-N
0
60
VY-B
VB VY VB VY VB VY
VB VY
3 phase relays
4 types of fault
3P, P-E, P-P, 2P-E
4 types of connections
300, 600-1, 600-2, 900
R IR VY-B I
MTA
MTA = displacement of
Y IY VB-R 30 I'
current and voltage
300
applied to relay
B IB VR-Y V
R IR VY-B I
MTA 90 - 45 Relay ITzero
Balanced
primary
Y IY VB-R 45 I' system
conditions -450
450 V
B IB VR-Y V 450 IUPF
1350
ITzero
For balanced system conditions:
90 - 30 Relay ImaxT
90 - 45 Relay
MTA: Primary system volts leads primary system current by 450 W.K Sonnemann:
Zero torque limits: Primary system volts leads primary system current by 1350 This relay gives the best characteristic
Primary system volts lags primary system current by 450 to fit the spread of possible phase angles
Protection notice / Copyright notice
Page 55 Kevin Hearfield Reyrolle Protection Devices
10e) 2 out of 3 Logic
When used the DOC elements will only operate where currents in 2 or more phases are detected in the
operate direction.
Can be used to ensure protection security against operation by load currents during power system faults
when very low current settings are applied.
Will limit the use of DOC elements against earth faults i.e. DEF elements may be required.
Require:
OPERATING QUANTITY, POLARISING QUANTITY
Operating Signal
Obtained from residual connection of line CTs IOP = 3Io
Polarising Signal
Ph - Ph or Ph - E voltages used in overcurrent protection
become inappropriate.
Residual voltage is used as the polarising quantity
Protection notice / Copyright notice
Page 57 Kevin Hearfield Reyrolle Protection Devices
11b) DEF - Extracting Residual Voltage
Open delta VT
secondary
S ZS R ZL F
Source Line
impedance impedance
System
Volts
ZS/ZL high
VR =
VR Residual
Residual VR
Volts Voltage
System
Volts
ZS/ZL low
VR May limit
Residual use of voltage VR
Volts polarised relays
- modern relays
very sensitive
CHECK FOR SUFFICIENT POLARISING VOLTAGE!
Protection notice / Copyright notice
Page 59 Kevin Hearfield Reyrolle Protection Devices
11d) DEF - Residual Volts for Non-Effectively Earthed Systems
S R F
Z
ZS
L
S Volts drop S
R due to earth R
resistance Neutral point
System raised above
Volts earth potential
Resistance
Earthed VR
VR
VR (may
Residual approach
Volts 3VPH)
SUFFICIENT
POLARISING
VOLTAGE SHOULD
ALWAYS BE
AVAILABLE Neutral
System fully
Insulated or Volts displaced
Peterson
Coil
Earthed
Residual
Volts
VR VR VR
MTA (I wrt V)
O0 -150 -450 -650 -900
Resistive Neutral Reactive Neutral
VRES VRES
VRES
VRES
VRES
IRES IRES
IRES
Resistance IRES
Earthing Transformer IRES
Earthed
Systems with Resistor Distribution System Transmission System Reactance
- Solidly Earthed - Solidly Earthed Earthed
Systems
VRES VRES
CORRECT
POL OP
DEF Relay
POL OP
CORRECT
DEF Relay
POL OP POL OP
INCORRECT INCORRECT
Protection notice / Copyright notice
Page 63 Kevin Hearfield Reyrolle Protection Devices