ITI MASTER LAYOUT FOR PREFAB


INFRASTRUCTURE
for
Govt. UTTAR PRADESH

Technology Lab & Workshop Lab

Layout Type – Option 1:

Rajnikant Upadhyay
Mobile # 977 141 7020

1 © Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Layout Type – Option 1

Workshop
Buildup Area : Size 161.5 X 63.5 (Ft.)

Civil- Electrical Infra Prerequisites

2 © Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) CIVIL LAYOUT FOR MACHINES PLACED
Layout Type Option 1 IN WORKSHOP

Note: The layout for the Technology lab is prepared considering the VSAT studio as part of layout, It is applicable at location where the VSAT studio is provided, Other wise the
space can
© Copyright 2022be used asAll an
Tata Technologies. rights extra classroom
reserved. All to
other trademarks are which
trademarks the
of their furniture
respective owners. and other equipment required for classroom to be provided by the ITI.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) RCC Flooring Requirements
Layout Type Option 1

RCC Floor Requirements - Whole Floor (161.5 X 63.5 sq. Ft) RCC 6 inches except the Car Lift area as marked
requires 12 Inches of RCC.

NOTE – Please refer next slide for RCC Details


© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) RCC Flooring Requirements
Layout Type Option 1

RCC Floor Requirements - Note : 12” RCC for Car Lift in Machine 8 Area only (Increase the depth)
Top surface area will be plain.

12” RCC for Car Lift in


Machine 8 Area

23.5’ from wall


A
2’ TYP

7’
2’ A
TYP
18.5’

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab Electrical and Networking


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
Layout Type Option 1 Prerequisites

12’

12’

Floor Trenching is required for power


cable for Carlift -Machine NOTE – Please refer next slide for LEGENDS
© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) Machine Wise Electrical
Layout Type Option 1 Prerequisites

Legends MACHINE QUANTITY SPECIFICATIONS DETAILS


1 16A Industrial Car Charging Socket
1 Ph , 6/16A Switch and Sockets (Dia 2.5sq MACHINE 1 EV
6 Single Ph,6+16A Combined (2No’s for each location)
mm multi core wiring)
combined (2 Nos for each location) MACHINE 2 LASER CUTTER 2 Single Ph,6+16A Combined (2No’s for each location)

1 3ɸ - 32A MCB
MACHINE 3 CNC 1 Single Ph,6+16A Combined (2No’s for each location)
3ɸ 32A MCB (Dia 10sq mm multi core 1 1ɸ - 10A MCB
wiring) 1 3ɸ - 63A MCB
MACHINE 4 VMC
1 Single Ph,6+16A Combined (2No’s for each location)
3ɸ 63A MCB (Dia 10sq mm multi core
wiring) MACHINE 5 PAINT BOOTH 2 3ɸ - 32A MCB

1 Single Ph,6+16A Combined (2No’s for each location)


Earth pit
MACHINE 6 ROBOTICS 1 3ɸ - 32A MCB
1 3ɸ - 63A MCB
Lan port
MACHINE 7 PLUMBING 4 Single Ph,6+16A Combined (2No’s for each location)

Electric vehicle charging socket – 16A MACHINE 8 AUTO MRO 12 Single Ph,6+16A Combined (2No’s for each location)
Industrial Socket
MACHINE 9 AVEVA 2 3ɸ - 32A MCB
1ɸ 10A MCB (Dia 10sq mm multi core
wiring) MACHINE 10 VFD 1 3ɸ - 63A MCB

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) Electrical Rating
Layout Type Option 1

2.8KVA 3KVA 12.5 KVA 12.5KVA 3KVA 34KVA 2KVA 2.8KVA 2KVA

Technology LAB

10KVA
© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners. 25KVA
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
Typical Classroom Layout and
Layout Type Option 1 Prerequisites

8’ 5’ 5’ 5’ 5’ 5’
Following Items to be provided by ITI in Technology Lab area
• False Ceiling
4’
• Vitrified Tiling
• Power Supply 230 V AC, 50 HZ with electrical wiring through
14’ trenching connected up to the points on tables as shown in layout
• Ethernet Wiring connected to Lan Port as shown in layout
• 230V AC, 6/16A combined Plug Socket - 4 Nos at each table.
• Split AC 2 Ton with wiring & Switching - 2 nos. in Each Room
6’
• Indoor Wall Painting in the room as per standard of the Institution
• UPS and Network Switch in UPS & Server Room
• Instructor Table & Chairs, White Board and Curtains in all
LEGENDS Classrooms.
• Lighting and its switches, wiring.
1 Ph ,230V AC 50HZ, 6/16A • CCTV Cameras
combined (2 Nos for each
location)
OPTIONAL :
• Projectors and Screen with sound output for classrooms.
Lan port

Note : Floor Trenching or conduit can be used for routing wires and networking cables. Separate conduits to be used for electrical and networking cables.

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) Electrical & Networking Layout
Layout Type Option 1 Technology LAB Area

Note : Floor Trenching or conduit can be used for routing wires and networking cables. Separate conduits to be used for electrical and networking cables.

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) SERVER Room Requirements
Layout Type Option 1

UPS Room Requirements


UPS SERVER 30 KVA (3Phase In & 3Phase Out) - 30
ROOM ROOM KVA online ups with battery Bank.
12’X8’ 12’X8’ 12V/65AH Sealed Maintenance Free
Batteries suitable for 30 mins backup (32
Nos for 65 AH)

LT Panel

AC 2T (6/16 Amp) - 4 units Electrical


Switch and Socket

Server Room Requirements


24 port Networking Switch in the server room for (6/16 Amp) - 6 units Electrical Switch and Socket
connectivity to each Workstation from Server for each from ground.
through Networking Switch along with 24 Port
Loaded Patch Panel
- 2 QTY
01 Unit of patch cord (CAT6 Cable – 2 Mtr.) D-Link
01 Units of LAN Port for Network cable
switch

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
TECHNOLOGY LABS: PDD, PVA, IOT
Layout Type Option 1 FURNITURE INSTALLATION

1st stage of tech lab readiness required. 2nd stage of tech lab readiness required.
• All electrical cables and networking as per layout. Before need • 2 days furniture the working progress first day they will all
to be finished the all-civil work should completed. furniture fixed it. Next day the site electrical and networking
• All electrical and networking cables are in ground or in wall persons required.
concealed. • All electrical 6/16 switches fixed it in table simultaneously. As
• Before furniture installation start all electrical networking and well networking 6J45 Lan Port same prosses
civil work completed. (Kind of Fans, Led’s, AC and networking &
electrical cables routing)

6/16 Switches
In-progress
© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
and Lan port
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) VSAT STUDIO & Moderator Room
Layout Type Option 1 Specifications

Studio Details:
Dimensions : Height – 4ft , Length – 24.20 ft, Width – 12.15 ft.

Requirements:
• We recommend RCC / Concrete roof for sound proofing.
• 10 ft brick wall is needed for studio and Moderator room
• Need brick wall partition in-between control room and live room.
• Need DGU sandwich glass window (Size – width 6ft and height 4ft)
middle of the partition.
• Need sandwich glass door (Size – width 3ft and Height 7ft) left side
of the partition.
• The live room should be soundproof and with good acoustic.
• Green screen for live room.
• Need movable light track in the live room (Size – 12ft*12ft)
• Need electrical points as per the diagram.
• We recommend carpet flooring.
• Need live room table, control room table and server rack.
• Need Furniture (live room table, control room table, server rack and
Chairs)

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab CHARGER FOR TIGOR EV (PRE-


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
Layout Type Option 1 INSTALLATION)

CHARGER FOR TIGOR EV (PRE-INSTALLATION)

• 16A single phase MCB with


industrial socket to be fixed
for Tigor EV charging

• The location is Battery EV


(Machine 1) section which is
represented in the layout
electrical

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) Dish placement of the VSAT
Layout Type Option 1 classroom

Side View Front View

At VSAT classroom, a platform of size 6’ x 5’ to be provided to fix the VSAT antenna, (base size is 3”x3”) with
approaching staircase on wall outside the VSAT classroom window.

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) ELECTRICAL ROUTING TRAY
Layout Type Option 1

Electrical Routing
Tray

Electrical tray routing for workshop surrounding wall should be like this.
The surrounding area is required for placing the posters as shown.

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) LASER Cutter Pipe Insert for
Layout Type Option 1 Exhaust

• At the time of construction there should be 4” dia. Pipe insert in the wall to put PVC T-pipe so that exhaust pipes insert wall area
between 3 and 4 pillars center and from ground 8’’
• The straight pipe approx. 2’ long should be brought outside the wall so that the smoke after laser operation can go outside workshop.
• Material required
• 4’’ T-Pipe and 4’’ PVC pipe

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab ELECTRICAL EARTHING/ GROUNDING


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
Layout Type Option 1 REQUIREMENTS

To prevent personnel injury due to any abnormal current surges which may
result from electrical malfunction, proper earthing has to be done.

Earthing Requirements
• It is recommended to use copper wire/strip for earthing connection as it has
high conductance and is also anti-corrosive.
• Earthing wire should be insulated copper wire (10 sq.mm).
• Earthing should be isolated from the earthing of electric discharging machine,
electrical welders and punch presses etc… Earth pits
• Ground resistance shall be below 100 ohms and earth neutral voltage should Machine #
Required
always be less than 2Vac.
• Personal injury malfunctioning of machine. Proper earthing also safeguards the Robotics Cell 2
operator. VMC 1
• Machine should be earthed independently to prevent the machine from
malfunctioning due to leakage current/electrical noise CNC 1

Laser Cutter 1

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab ELECTRICAL EARTHING/ GROUNDING


Workshop Location New Building (Size – 161.5 X 63.5 Ft.)
Layout Type Option 1 REQUIREMENTS

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) ELECTRICAL RATING
Layout Type Option 1

Specification/
Machine Electrical Load Location Qty Remarks
Rating
General Purpose Four 6/16Amp combined plug socket (2 Nos for
Machines. 230 V AC , 1Ph, On the Back Wall at each location) Tentative location shown in earlier
1 6
Typical 5/15A 3Ft from Ground slide With one 16A industrial socket for EV
Inductive load charging &one 63A MCB
Machine 230V AC, 1 Ph, On the Back Wall at 6/16 Amp combined plug socket(2 Nos for each location)
2 1
Inductive Load 5/15A 3Ft from Ground . Tentative location shown in earlier slide.
Machine 440V AC, 3 Ph, On the Back Wall at
3 1 32A MCB For machine
inductive load 32A 3Ft from Ground
Machine inductive 440V AC, 3 Ph, On the Back Wall at 3Ft One 32A MCB for machine and one 32A MCB for
4 2
load 32A from Ground compressor
Machine 440V AC, 3 Ph, On the Back Wall at One 32A MCB for machine and one 32A MCB
5 2
inductive load 32A 3Ft from Ground for compressor
Between section 5
Machine 440V AC, 3 Ph, & section6 (3Ft
6 2 Two 32A MCB for machines
inductive load 32A/63A from Ground on
wall)
Provide 16+6 Amp combined plug socket(2 Nos for
Equipment 230V AC, 1 Ph, On the Back Wall at
7 3 each location) . Tentative location shown in earlier
inductive load 5/15A 3Ft from Ground
slide
© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) ELECTRICAL RATING
Layout Type Option 1

Specification/
Machine Electrical Load Location Qty Remarks
Rating

Machine Inductive 440V AC, 3 On the Back Wall at 3Ft


8.1 1 32A MCB For machine
Load Ph, 32A from Ground

Machine Inductive 440V AC, 3 On the Back Wall at 3Ft


8.2 1 32A MCB For machine
Load Ph, 32A from Ground
Provide 6/16 Amp combined plug socket(2 Nos
Machine Inductive 230V AC, 1 On the Back Wall at 3Ft
8.3 1 for each location) . Tentative location shown in
Load Ph, 5/15A from Ground
earlier slide
Provide 6/16 Amp combined plug socket(2 Nos
Machine Inductive 230V AC, 1 On the Back Wall at 3Ft
8.4 1 for each location) . Tentative location shown in
Load Ph, 5/15A from Ground
earlier slide
Provide 6/16 Amp combined plug socket(2 Nos
230 V AC, On the Back Wall at 3Ft
Machine Inductive 6 for each location) . Tentative location shown in
8.5 1Ph, 5/15A from Ground
Load earlier slide
On the floor surface Provide 6/16 Amp combined plug socket(2 Nos
230 V AC,
Machine Inductive flushed to ground 1 for each location) . Tentative location shown in
8.6 1Ph, 5/15A
Load (Trenching required) earlier slide

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology Lab


Workshop Location New Building (Size – 161.5 X 63.5 Ft.) ELECTRICAL RATING
Layout Type Option 1

Specification/
Machine Electrical Load Location Qty Remarks
Rating
Refer the color coding for 3Ph.
4C X 10 Sq. mm
Common Cable for heavy machines Concealed in the Length: Running length up to machine
power cable -
Requirement 440V AC, 3 Ph, 32A/63A wall from
(copper)
DB.
Earthing cable for heavy 1C X 10 Sq. mm Refer the color coding
Common Earth pit to
machines 440V AC, 3 Ph, earthing cable - for 3Ph Length: Approx.
Requirement machine
32A/63A (copper) 15 ft.
High Speed 3 On the Back Wall Provide 16+6 Amp combined plug
Common Blade Speed: at 10Ft from - socket. Tentative location shown in
Requirement Exhaust fan Inductive Load
1350 rpm Ground earlier slide
Common Equipped with fine IR LEDs for clearer
IR Range of 125 ft At the entrance -
Requirement Surveillance camera night vision
Refer the color coding for 3Ph.
4C X 10 Sq. mm
Cable for heavy machines Concealed in the Length: Running length up to machine
Common power cable -
440V AC, 3 Ph, 32A/63A wall from
Requirement (copper)
DB.
Earthing cable for heavy 1C X 10 Sq. mm Refer the color coding
Common Earth pit to
machines 440V AC, 3 Ph, earthing cable - for 3Ph Length: Approx.
Requirement machine
32A/63A (copper) 15 ft.

© Copyright 2022 Tata Technologies. All rights reserved. All other trademarks are trademarks of their respective owners.
Classification: Public

Lab Type Workshop + Technology LAB


161.5’ X 63.5’ Civil, Electrical & Networking Prerequisite
Layout Type Option 1

Electrical wiring in the Workstation Furniture


provided by TTL from the TTL located Server UPS setup in the Server Room. (30 KVA
Room. (Workstation Electrical wiring (2.5 sq [3Phase in & 3Phase Out] - 30 KVA online
mm) and cabling to each workstation and ups with battery Bank 12V/65AH Sealed
room/lab through UPS connected via LT Panel Maintenance Free Batteries suitable for 30
with 16 Amp MCB Set for each room & lab – mins backup [32 Nos for 65 AH])
with Cable trenching).

Each TTL provided furniture (30 Nos.) –


should provide (6/16 Amp) - 4 units Electrical
Switch and Socket for each workstation and
02 Unit of patch cord (CAT6 Cable – 2 Mtr.)
additionally to each equipment/machines 03
cable in each Workstation and additionally
Units as per the marked position on the
one unit to each equipment/machines.
respective layout.
4 Units each Workstation
3 units for each machines

Two units of 24 port Networking Switch in the


For each machines in the Technology lab
server room for connectivity to each
provided by TTL, need to provide (6/16 Amp)
Workstation from Server through Networking
- 2 units Electrical Switch and Socket each
Switch along with 24 Port Loaded Patch
like – 3D Printers, Simulators for Server (6/16
Panel.
Amp) - 4 units require additionally with other
electrical Points.
2 Units
Classification: Public

Lab Type Workshop + Technology LAB


161.5’ X 63.5’ Civil, Electrical & Networking Prerequisite
Layout Type Option 1

OPTIONAL - Standard Quality Glass Door - 3ft Wide as per


Projector with Screen for each the Layout or as per the
Lab – total 3 units existing door size.

2Ton air conditioner in all the


Vinyl Flooring for the entire
Rooms/Lab (2 Nos) with 32 Amp
area of Technology Lab,
MCB
except the Server Room as
per the layout.

Aluminum Framed Glass


Aluminum Partition Wall for sliding window with Iron Grill
Rooms Partition as per the with mesh
Layout.
1 Set for each window
Classification: Public

Lab Type Workshop + Technology LAB


161.5’ X 63.5’ Civil, Electrical & Networking Prerequisite
Layout Type Option 1

20 Student Chairs for VSAT White Board for Each Lab,


Classroom. total 03 Units.

Office Type MS Almirah for


5 Units of 2X4 ft Tables with VSAT Class Room, Simulators
Chairs. Lab, 3D Printer Lab, IoT Lab
and Server Room, total 05
Units – Standard size.

All the visible Walls need to be


Painted (Indoor Area - snow All Rooms and Labs need to
white Colour plastic paint) & have false ceiling with 2X2 ft
(Out Door Area snow white with Ceiling Lights
Colour Emulsion Painting).
Classification: Public

Lab Type Workshop + Technology LAB


161.5’ X 63.5’ Civil, Electrical & Networking Prerequisite
Layout Type Option 1

Drinking Water Dispenser with


Refrigerator and Proper
CCTV Camera
Arrangement for Male & Female
Washrooms.

Fire Safety System (fire


Floor Epoxy – Workshop floor
extinguisher Co2 Type) – 06
only
Units for Technology Lab.

Flood Light (50W)


Minimum 25mbps Broadband
Internet connection in the
At Workshop Roof
Server Room
Classification: Public

Lab Type Workshop + Technology LAB


161.5’ X 63.5’ Civil, Electrical & Networking Prerequisite
Layout Type Option 1

Out Door Flood Light (30W)

Motorized (GI) rolling Shutter


for Workshop Main Gate. Manual
cum
Motorized
- Slider should be fixed on rolling
the outer wall. Shutter
Switch

LED Signage board on the


Outer side of left wall – for
workshop building

CENTER OF EXCELLENCE
Classification: Public

Lab Type Workshop + Technology Lab Workshop Area


161.5’ X 63.5’ Perusal
Layout Type Option 1
Classification: Public

Lab Type Workshop + Technology Lab Workshop Area


161.5’ X 63.5’ Perusal
Layout Type Option 1