The document provides information on the TYCO DV-5a Automatic Water Control Valve, Single Interlock Preaction, Electric Actuation fire protection system valve. It is a diaphragm-style valve used in single interlock preaction systems, with double seat design that actuates fire alarms upon operation. When electrically actuated by detection systems like heat/smoke detectors, it allows water flow into sprinkler piping and discharge from opened sprinklers. The valve is available in sizes from 1 1/2 to 8 inches, with various end connection and coating options, and can be reset without opening covers. Replacement part numbers are listed for common components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
137 views

TFP1421 08 2023

The document provides information on the TYCO DV-5a Automatic Water Control Valve, Single Interlock Preaction, Electric Actuation fire protection system valve. It is a diaphragm-style valve used in single interlock preaction systems, with double seat design that actuates fire alarms upon operation. When electrically actuated by detection systems like heat/smoke detectors, it allows water flow into sprinkler piping and discharge from opened sprinklers. The valve is available in sizes from 1 1/2 to 8 inches, with various end connection and coating options, and can be reset without opening covers. Replacement part numbers are listed for common components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

Worldwide

www.tyco-fire.com
Contacts

DV-5a Automatic Water Control Valve, Single


Interlock Preaction, Electric Actuation, Fire
Protection Systems 1 1/2 to 8 Inch (DN40 to DN200)
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Scan the QR code or enter the URL


in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.

Available End Connections and Weights — lb (kg)

Nominal Valve Size


End Connection ANSI Inches
(DN)
1 1/2 2 3 4 6 165,1 8
Inlet Outlet (40) (50) (80) (100) (150) mm (200)
26 25
Thread Thread N/A N/A N/A N/A N/A
(11,8) (11,3)
25 25 60 95 177 177 327
Groove Groove
docs.jci.com/tycofire/tfp1421 (11,3) (11,3) (27,2) (43,1) (80,3) (80,3) (148,3)
66 106 190 346
Flange Groove N/A N/A N/A
(30,0) (48,1) (86,2) (157,0)
General Flange Flange N/A N/A 72 116 204 N/A 365

Description
(32,7) (52,6) (92,5) (165,6)

a clapper and/or latch mechanism. The DV-5a Single Interlock Preaction


The TYCO DV-5 a Automatic Water Simply re-pressurizing the diaphragm Electric Actuation Valve utilizes auto-
Control Valve Single Interlock Preaction chamber resets the valve. matic sprinklers and a supplemental
Electric Actuation is a diaphragm type The DV-5a features internal and exter- detection system, comprised of electric
valve that can be used in single inter- nal coating of the valve to provide detection comprised of heat detectors,
lock preaction fire protection systems. corrosion resistance. The external cor- smoke detectors, and manual pull sta-
When properly trimmed, the double rosion resistance of the epoxy coating tions. Actuation of the detection system
seat design of the DV-5a Valve also permits the use of the DV-5a in cor- automatically operates (releases) the
provides actuation of fire alarms upon rosive atmospheres associated with DV-5a Valve, allowing water to flow
system operation. many types of industrial processing into the sprinkler piping system and to
The diaphragm style design of the plants and outdoor installations. be discharged from any sprinklers that
DV-5a Valve allows external resetting, may subsequently open.
The DV-5 a Single Interlock Preac-
providing for easy resetting of a deluge tion Electric Actuation Valve is offered
system without having to open a valve with or without a System Main Control
handhole cover to manually reposition Valve.

Page 1 of 18 AUGUST 2023 TFP1421


TFP1421
Page 2 of 18

Nominal Valve Size ANSI Inch (DN)


Item Description Qty. 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)e 8 (DN200)
P/N P/N P/N P/N P/N P/N
1 Valve Body 1 N/R N/R N/R N/R N/R N/R
2 Diaphragm 1 545000020 545000020 545000030 545000040 545000060 545000080
3 Diaphragm Cover 1 N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a 545100001 545100001 545100002 545100003 545100004 545100003
5 Hex Bolt, Long 2 545100011 545100011 545100012 545100013 545100014 545100015
6 Lift Washer 2b N/A N/A 545100021 545100022 545100023 545100022
7 Hex Nut 2 545100031 545100031 545100032 545100033 545100034 545100033
8 Hoist Ring 2 545100041 545100041 545100041 545100041 545100041 545100041
9 Flat Washer 2 N/A N/A 545100024 545100025 545100026 545100025
NOTES d. Order replacements parts only via Part Numbers given, do not replace Hex Bolt, Hex
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies. Nut, Lift Washer or Hoist Ring with common hardware parts.
b. Lift Washer not used in 1 1/2 and 2 inch (DN40 and DN50) assemblies. e. Also applicable to metric 165,1 mm size.
c. N/R = Not Replaceable.

1
1
3
2
7 5
5 3 1-1/2 AND 2 INCH
9 VALVES ONLY
6

3
7 1
4
8

6
4
9 7 5
6 AND 8 INCH
1 2
VALVES ONLY
FIGURE 1
DV-5 a VALVE ASSEMBLY AND REPLACEMENT PARTS

Flange Drilling Specification Dim. A


Nominal Bolt Circle
Valve Nominal Dimensions in Inches and (mm) Diameter
Size
ANSI ANSI B16.1a ISO 7005-2 JIS B 2210 AS 2129 Dim. B
Inches (Class 125) (PN16)b (10K) (Table E)
(DN) Bolt Hole
Diameter
A B N A B N A B N A B N

3 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71 Qty. N


4 (160,0) 8 (150,0) 8 (146,0) 4 Number of
(80) (152,4) (19,0) (19,0) (15,0) (18,0)
Bolt Holes
4 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71
8 (180,0) 8 (175,0) 8 178,0) 8
(100) (190,5) (19,0) (19,0) (15,0) (18,0) NOTES:
a. Same drilling as for
6 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 ANSI B16.5 (Class 150) and
8 (240,0) 8 (240,0) 8 8
(150) (241,3) (22,2) (23,0) (19,0) (235) (22,0) ANSI B16.42 (Class 150)
b. Same drilling as for
8 11.75 0.88 11.61 0.91 12 11.42 0.75 12 11.50 0.87 BS 4504 Section 3.2 (PN16) and
8 (295,0) 8 DIN 2532 (PN16)
(200) (298,5) (22,2) (23,0) (290,0) (19,0) (292,0) (22,0)

TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP1421
Page 3 of 18

Port Sizes, NPT Inch per ANSI B1.20.1


Port Port Description
1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150)a 8 (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1 1/4 2 2 2
P7 System Air Supply 1/2 1/2 1/2 1/2 1/2 1/2
NOTES
a. Also applicable to metric 165,1 mm.
SYSTEM OPEN TO ATMOSPHERE WATERFLOW TO SYSTEM

VALVE SYSTEM
WATERWAY AIR
DIAPHRAGM SUPPLY
SEAT
VALVE
WATERWAY ALARM PORT
DIAPHRAGM WATERFLOW
CHAMBER TO ALARM
DIAPHRAGM
CHAMBER
OPEN TO
AUTOMATIC ATMOSPHERE
DRAIN VALVE AUTOMATIC
OPEN TO DRAIN VALVE
DIAPHRAGM
DIAPHRAGM ATMOSPHERE CLOSED
RETRACTS
CHAMBER
OPENING
SUPPLY
VALVE
FROM
WATERWAY
UPSTREAM WATER SUPPLY
SIDE OF PRESSURE &
SHUT-OFF ALARM TEST
VALVE
WATER SUPPLY WATERFLOW FROM WATER SUPPLY
FIGURE 2A FIGURE 2B
SET CONDITION OPERATED CONDITION

DRAIN FROM SYSTEM RESIDUAL DRAIN FROM SYSTEM

VALVE
WATERWAY
DIAPHRAGM
SEAT

VALVE DIAPHRAGM
WATERWAY AUTOMATICALLY
SYSTEM FLEXES TO SYSTEM
DRAIN ITS SEATED DRAIN
DIAPHRAGM OPEN OPEN
CHAMBER POSTION
OPEN TO
ATMOSPHERE

DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
MAIN SIDE OF MAIN
DRAIN SHUT-OFF DRAIN
OPEN VALVE CLOSED
WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF
FIGURE 2C FIGURE 2D
SYSTEM DRAIN CONDITION RESIDUAL DRAIN CONDITION
FIGURE 2
DV-5 a VALVE OPERATION, PREACTION SYSTEMS
TFP1421
Page 4 of 18

DIMENSIONS SHOWN
ARE APPLICABLE TO
Typically, the system designer selects
the detection components for a single Technical
ALL END CONNECTION
CONFIGURATIONS
interlock preaction system that will
respond to a fire sooner than the auto- Data
AVAILABLE PER matic sprinklers. Consequently, the Approvals
VALVE SIZE system will experience a minimal delay UL and C-UL Listed
in water delivery over that for a wet pipe LPCB Approved
sprinkler system because the system FM Approved
will have essentially filled with water Listing and Approvals are based on DV-5a
10-3/16" before a sprinkler operates. The DV-5a Single Interlock Preaction Electric Actua-
(260 mm) Single Interlock Preaction Electric tion Valve being trimmed as described in
Actuation Valve automatically super- Figure 5.
vises the integrity of the overall system. DV-5A Valve
1-1/2 Inch (DN40) Supervision is provided by monitoring a Components for the 1 1/2 in. to 8 in. (DN40
relatively low air pressure in the system to DN200) DV-5a Valve are shown in Figure 1.
via a low pressure alarm switch so as The DV-5a Valve is for vertical installations.
to detect leaks in the system that oth- It is rated for use at service pressures of 20
to 300 psi (1,4 to 20,7 bar).
erwise would result in unwanted water
10-3/16" discharge should the system operate in The take-out dimensions are shown in
a fire condition. Figure 3, and flanged connections are
(260 mm) available drilled per ANSI, ISO, AS, and JIS
Supervised single interlock preac- specifications (see Table A). Threaded inlet
tion systems are generally used to and outlet connections are available in NPT
protect areas where there is danger or ISO 7-1. Threaded port connections are
2 Inch (DN50) NPT threaded.
of serious water damage that might
result from damaged automatic sprin- Note: PN16 flanges are pressure rated to
klers or piping. Typically, such areas 16 bar.
include computer rooms, storage Valve Trim
areas for valuable artifacts, libraries, The maximum pressure rating for the single
13-3/4" and archives. interlock preaction electric actuation is
(349 mm) dependent on the separately ordered
Single interlock preaction systems are solenoid valve per Technical Data Sheet
also effectively used to protect proper- TFP2180.
ties where a pre-alarm of a possible fire When the system pressure is greater than
3 Inch (DN80) condition may allow time for fire extin- 175 psi (12,1 bar), provision is to be made
guishment by alternate suppression to replace the standard order 300 psi (20,7
means, prior to a sprinkler discharge. bar) water pressure gauges with separately
In the event the fire cannot otherwise ordered 600 psi (41,4 bar) water pressure
gauges.
be extinguished, the preaction sprinkler
system will then perform as the primary If the addition of an alarm control valve is
16-3/4" fire protection system. desired or required by the local AHJ, the
(425 mm) alarm control valve noted as Item H in Figure
8 is to be a separately ordered electronically
NOTICE supervised normally open valve.
The DV-5a Single Interlock Preaction External trim connections are NPT threaded.
Electric Actuation Valve described EMEA trim is provided with NPT x ISO 7-1
4 Inch (DN100) thread adapters.
herein must be installed and main-
tained in compliance with this docu- Pressure Loss
ment, as well as with the applicable See Graph A
standards of the NATIONAL FIRE PRO- Detection System
TECTION ASSOCIATION (NFPA), in See the Electric Actuation subsection
addition to the standards of any other
22-3/8" authorities having jurisdiction. Failure System Air Pressure Requirements
(569 mm) to do so may impair the performance The supervisory air (nitrogen) pressure is to
of these devices. be 10 ± 2 psi (0,69 ±0,07 bar). The use of
a higher supervisory pressure is subject to
The owner is responsible for main- approval by the authority having jurisdiction,
6 Inch (DN150) and it should be understood that the use of
taining their fire protection system
a higher supervisory pressure may increase
and devices in proper operating con- water delivery time. The use of a lower
dition. Contact the installing contrac- supervisory pressure may prevent clearing
tor or product manufacturer with any the alarm of the supervisory low pressure
questions. switch (Item T - Figure 8), which is factory
set to alarm at 5 ± 1 psi (0,34 ± 0,07 bar) on
decreasing pressure. The supervisory air
27-7/16" supply pressure of 10 ± 2 psi (0,69 ± 0,07
(697 mm) bar) can be provided by any of the following
methods. Refer to the applicable data sheet
for laboratory approval information.
• Model G16AC812 (self contained)
8 Inch (DN200) Automatic Supervisory Air Supply
described in Technical Data Sheet
FIGURE 3 TFP1620.
DV-5 a VALVE
TAKE-OUT DIMENSIONS
TFP1421
Page 5 of 18

FLOW RATE IN LITERS PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000 15000
9.0 0,600
8.0
7.0 0,500
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

6.0 0,400
5.0
0,300
)
40

4.0
DN
H(

NOMINAL PRESSURE DROP IN BAR


NC

)
3.0 50
0,200
2I

DN
/
1-1

H(

(1 PSI = 0,06895 BAR)


)
80
NC

DN
2I

2.0
H(

0)
NC

10

mm
DN
3I

0,100

5,1
H( 0,090
NC

16
0,080
4I

0),
15

0)
1.0 0,070

20
DN
0.9

DN
0,060
0.8 H(

H(
NC
0,050

NC
0.7
6I

8I
0.6 0,040
0.5
0,030
0.4

0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5 a VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the Materials of Common Hardware Trim
• Common hardware pipe fittings are
Model AMD-1 Air Maintenance Device
described in Technical Data Sheet Construction galvanized or black as required and
are malleable per ASME B16.3.
TFP1221.
Valve Body • Common hardware pipe nipples are
• A maximum 3000 psi (206,9 bar) Epoxy coated ductile iron per ASTM galvanized or black as required and
nitrogen cylinder in combination A536-77, Grade 65-45-12 are Schedule 40 per ASTM A53 or
with the Model AMD-3 Nitrogen
Diaphragm Cover A135.
Maintenance Device described in
Technical Data Sheet TFP1241. Epoxy coated ductile iron per ASTM • Common hardware compression
Note: The dew point of the air or nitrogen A536-77, Grade 65-45-12 fittings are brass per ASTM B16.
supply for a system exposed to freezing con- Diaphragm • Common hardware tubing is Type L
ditions must be maintained below the lowest
ambient temperature to which the system Polyester fabric reinforced, TEFLON copper per ASTM B88.
piping will be exposed. Introduction of mois- coated, EPDM rubber per ASTM D2000
ture into the system piping can create ice
build-up that could prevent proper operation Diaphragm Cover Fasteners
of the system. Aluminum zinc coated steel
The supervisory low pressure switch (Item
T - Figure 8) is factory set at 5 ± 1 psi (0,34 ±
0,07 bar) on decreasing pressure. The pres-
sure relief valve (Item S - Figure 8) is factory
set to fully open at 25 ± 2 psi (1,72 ± 0,14 bar)
and it begins to crack open at a pressure of
about 18 psi (1,24 bar).
TFP1421
Page 6 of 18

SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY

ELECTRIC DETECTION SYSTEM


(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.
DELUGE VALVE SOLENOID
RELEASING PANEL VALVE
(AUTOMATIC (TYPICALLY
CONTROL UNIT 24 VOLTS DC)
WITH BATTERY
BACK-UP)
WATERFLOW SYSTEM DRAIN VALVE
DV-5A DRAIN (NORMALLY CLOSED)
PRESSURE VALVE
POWER AUTOMATIC ALARM
SUPPLY SUPERVISORY SWITCH MAIN
(TYPICALLY AIR/NITROGEN DRAIN VALVE
120 VOLTS AC) SUPPLY DIAPHRAGM CHAMBER (NORMALLY
DRAIN CLOSED)
8 TO 12 PSI PRESSURE GAUGE

SUPERVISORY
LOCAL
LOW PRESSURE RESTRICTION DRAIN MANUAL
ALARM SWITCH DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
SYSTEM AIR CHAMBER SUPPLY (NORMALLY
PRESSURE CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
GAUGE (NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 4
DV-5 a VALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION SCHEMATIC DIAGRAM

Operation Upon opening of the DV-5a valve, the


Model MRA-1 manual reset actuator
Dimensions are provided in Figure 7.
Notes:
The TYCO DV-5a Valve is a diaphragm opens to constantly vent the DV-5a dia- The normally closed, de-energized,
style valve that depends upon water phragm chamber to hydraulically latch
solenoid valve is separately ordered and
pressure in the diaphragm chamber the DV-5a in the tripped position until
selected based on the required laboratory
(see Figure 2A) to hold the Diaphragm manually reset.
approval acceptable to the authority having
closed against the water supply In standby mode, the integrity of the jurisdiction. Refer to Technical Data Sheet
pressure. system piping is supervised by a low TFP2180 for specific laboratory approvals.
When the DV-5a valve is set for service, pressure alarm switch. Consult with the applicable standards of
the diaphragm chamber is pressurized See the Electric Actuation section for the Approval agency regarding installation
through the trim connections from the additional information. criteria pertaining to electric actuation
inlet side of the system’s main control circuitry.
valve.
Opening the electric actuation trim
Electric Due to the functionality of the Model
MRA-1 manual reset actuator, the
trips the Model MRA-1 manual reset
actuator. Tripping the MRA-1 releases
Actuation release circuit of the releasing panel
need only provide the typical ten
water from the DV-5 a diaphragm The electric actuation trim forms a part minutes of alarm condition intended
chamber faster than it can be replen- of the laboratory approval of the DV-5a to energize the solenoid valve to open.
ished through a 1/8 in. (3,2 mm) restric- valves and is necessary for their proper After the ten minute duration, at which
tion located in the diaphragm chamber operation. point should the solenoid valve become
supply connection. Release of water The electric actuation trim is required de-energized and close (especially
through the MRA-1 results in a rapid for electric operation of the DV-5 a while operating under battery back-
pressure drop in the DV-5a diaphragm valve by a detection system consisting up), the MRA-1 will have already auto-
chamber. The force differential applied of electrical devices such as heat sen- matically opened, thereby preventing
through the diaphragm to hold the sitive thermostats, smoke detectors, the DV-5a diaphragm chamber from
diaphragm in the set position is then and/or electric manual pull stations as becoming re-pressurized, and prevent-
reduced below the valve trip point. The shown in Figure 4. ing an inadvertent closing of the DV-5a
water supply pressure then forces the during a fire event.
diaphragm open permitting water to Note: For single interlock preaction
flow into the system piping, as well as systems with electric actuation, the system
through the alarm port to actuate the designer typically selects electric detection
system alarms (see Figure 2B). devices that will operate sooner than the
automatic sprinklers chosen for use on the
sprinkler piping.
TFP1421
Page 7 of 18

Installation The DV-5a valve is to be installed in


accordance with the following criteria:
Step 8. Unused pressure alarm switch
connections must be plugged.
The TYCO DV-5A Single Interlock Pre- Step 1. All nipples, fittings, and devices Step 9. A suitable automatic supervi-
action Electric Actuation Trim Valve is must be clean and free of scale and sory air (nitrogen) supply, as described
to be installed in accordance with this burrs before installation. Use pipe in the Technical Data section, is to be
section. thread sealant sparingly on male pipe installed in accordance with the appli-
threads only. cable technical data sheet and set for
NOTICE 10 ± 2 psi (0,69 ± 0,14 bar).
Step 2. The DV-5a single interlock pre-
DV-5A automatic water control valves action electric actuation valve must be Step 10. A desiccant dryer, when
are designed to be used in freshwa- trimmed in accordance with the trim required for the supervisory air supply,
ter systems. When the supply is from illustration shown in Figure 5. is to be installed between a drip leg
an alternative source such as brackish and the Model AMD-1 air mainte-
water, saltwater, or contains additives Note: If the addition of an alarm control
valve is desired or required by the local nance device or between the Model
such as foam, the limited warranty is G16AC812 automatic supervisory air
reduced to one year from the time of AHJ, the alarm control valve noted as
Item H in Figure 8 is to be a separately supply and the preaction trim.
installation. An increase in frequency of
inspections is required when the valve ordered electronically supervised normally Step 11. The supervisory low pressure
is exposed to such supplies and other open valve. switch is to be wired to the supervisory
corrosive conditions or chemicals that Step 3. Care must be taken to ensure alarm initiating circuit of an alarm panel.
could impact valve materials or the that check valves, strainers, globe Step 12. Conduit and electrical con-
operation of the assembly. The system valves, etc. are installed with the flow nections are to be made in accordance
and all components must be designed arrows in the proper direction. with the applicable standards of the
accordingly for the increased demand. approval agency.
Step 4. Drain tubing to the drip funnel
It is required to thoroughly flush the
must be installed with smooth bends Step 13. Before a system hydrostatic
valve and trim assembly with freshwa-
that will not restrict flow. test is performed, the DV-5a diaphragm
ter and reset to the set condition after
Step 5. The main drain and drip funnel chamber is to be depressurized, the
each operation.
drain may be interconnected provided automatic drain valve is to be tem-
Proper operation of the DV-5a single porarily replaced with a plug, and the
a check valve is located at least 12 in.
interlock preaction electric actua- diaphragm cover bolts must be uni-
(300 mm) below the drip funnel.
tion valve depends upon their trim formly and securely tightened using
being installed in accordance with the Step 6. Suitable provision must be a cross-draw sequence. After tight-
instructions given in this technical data made for disposal of drain water. Drain- ening, double-check to make certain
sheet. Failure to follow the appropriate age water must be directed such that that all of the diaphragm cover bolts
trim diagram may prevent the DV-5a it will not cause accidental damage to are securely tightened. See Table B in
valve from functioning properly, as well property or danger to persons. the Care and Maintenance section for
as void approvals and the manufactur- Step 7. Connect the diaphragm supply torque specifications.
er’s warranties. valve to the inlet side of the system
The DV-5a valve must be installed in a main control valve in order to facilitate
readily visible and accessible location. setting of the DV-5a valve (see Figure
8).
The DV-5a valve and associated trim
must be maintained at a minimum tem-
perature of 40°F (4°C).
Heat tracing of the DV-5a valve or its
associated trim is not permitted. Heat
tracing can result in the formation of
hardened mineral deposits that are
capable of preventing proper operation.
Always open the system control valves
slowly to avoid a sudden rush of water
entering the system.
TFP1421
Page 8 of 18

A2

C5 L

D
C
C3
F
P4 E
P7
A2
A
P5

C2 C4 P6
C7 A6

H P3 A1
J
B
P1 C6
P2
G
A4
K
A3

A4 C1

A5
1-1/2" (DN40) AND 2" (DN50) Assemble in order
VALVES ONLY from A to L
A7

A9
A8

Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Trim" or pre-assembled "DV-5A Valve with Galvanized Trim and Butterfly Valve", Items A1
through A9 are provided, as applicably related to valve size, and Item A6 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180.
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A9 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.

FIGURE 5
DV-5a VALVES WITH SINGLE INTERLOCK PREACTION
ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED
TFP1421
Page 9 of 18

A2

39 27
28 36
C5

26 51 27
52 57
21
22 1
42 41 47 34
17
P4 30
P7 49 A6
36
20 29 10
A2 P5 55 36
8
36
C4 14
13 4 36
C2 31
P6 54 20 24 6
32
53 16 C3
44 A1 33 43 39
P3
23 15 40
32 C7 29
P1
P2 C6 Notes:
48 12 1. Port Connections P1 through
59 3
19 50 A4 37 P7 are described in Figure 2.
24 58 2. External Trim Connections C1
38 5 46 through C5 are
56
31 A3 11 56 described in Figure 8.
35 37 18 3. When ordering pre-assembled
"DV-5A Valve with Galvanized
25 2 Trim" or pre-assembled "DV-
27 1 21 9 5A Valve with Galvanized Trim
37 27 and Butterfly Valve", Items
7 45
19 17 A1 through A9 are provided,
37 as applicably related to valve
A4 size, and Item A7 is provided
C1 7 as P/N 52-287-1-124 described
A5 in Technical Data Sheet
TFP2180.
A9 4. When ordering DV-5A Trim
A7 A8
separately from the DV-5A
Valve, Items A1 through A9
1-1/2" (DN40) AND 2" (DN50) are separately ordered, as ap-
VALVES ONLY plicably related to valve size.
Water Pressure Gauges for
EMEA valve trim are also
separately ordered.

ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) b 8 IN. (DN200)
1 2 1/4” GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 1 1/4” PRESSURE RELIEF VALVE, 25 PSI 923431019 923431019 923431019 923431019 923431019 923431019
7 2 1/2” BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
8 1 1/2” GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
9 1 1/2” SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
10 1 1/2” SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
11 1 1/2” Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4” ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
15 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 2 COMP. FITTING 90° 1/2” MNPT x 1/2” OD TUBE ✓ — — — — — —
18 1 COMP. FITTING 90° 1/2” FNPT x 1/2” OD TUBE ✓ — — — — — —
19 2 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4” NPT x 3/4” TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2 PIPE PLUG ✓ 1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
22 1 PIPE PLUG ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”

FIGURE 6 (1 OF 2)
DV-5a VALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1421
Page 10 of 18

ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) b 8 IN. (DN200)
23 1 PIPE PLUG ✓ 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
24 2 UNION ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
25 1 STREET ELBOW ✓ 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90°
26 1 ELBOW ✓ 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45°
27 4 ELBOW ✓ 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90°
28 1 CROSS ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
29 2 TEE ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
30 1 REDUCING TEE ✓ 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2”
31 2 REDUCING TEE ✓ 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4”
32 2 REDUCING TEE ✓ 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4”
33 1 REDUCING TEE ✓ 3/4” x 3/4” x 3/4” 3/4” x 3/4” x 3/4” 1 1/4” x 1 1/4” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4”
34 1 PIPE NIPPLE ✓ 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE
35 1 PIPE NIPPLE ✓ 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2”
36 4 PIPE NIPPLE ✓ 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE
37 4 PIPE NIPPLE ✓ 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2”
38 1 PIPE NIPPLE ✓ 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2”
39 2 PIPE NIPPLE ✓ 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2”
40 1 PIPE NIPPLE ✓ 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2”
41 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5”
42 1 PIPE NIPPLE ✓ 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2”
43 1 PIPE NIPPLE ✓ 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2”
44 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2”
45 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
46 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
47 1 TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
48 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
49 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
50 1 PIPE NIPPLE ✓ 1/2” x 3 1/2” 1/2” x 3 1/2” 1/2” x 4 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 3/4”
51 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 1/2”
52 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 4 1/2” 1/2” x 5” 1/2” x 7 1/2” 1/2” x 9 1/2”
53 1 PIPE NIPPLE ✓ 3/4” x 5” 3/4” x 5” 3/4” x 6” 3/4” x 7” 3/4” x 9” 3/4” x 11 1/2”
54 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 1 1/4” x 3 1/4” 2” x 3” 2” x 3” 2” x 3”
55 1 PIPE NIPPLE ✓ 3/4” x 6 1/2” 3/4” x 6 1/2” 1 1/4” x 5 1/2” 2” x 5” 2” x 6” 2” x 8”
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
56
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
AIR PRESSURE GAUGE, 80 PSI / 550 kPa
57 1 923431012 923431012 923431012 923431012 923431012 923431012
RETARDED TO 250PSI / 1750 kPa
58 1 LABEL 545003005 545003005 545003005 545003005 545003005 545003005
59 1 LABEL WIRE — — — — — —
A1 1 DV-5A VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102
DOUBLE CONTACTS (APAC)
WATERFLOW PRESSURE ALARM SWITCH,
A2 1 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101
SINGLE CONTACTS (EMEA)
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
DOUBLE CONTACTS (AMER)
1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A3
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A4
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A5 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A6 1 SOLENOID VALVE NORMALLY CLOSED REFER TO TFP2180
A7 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
NOTES
a. Not VdS Approved.
b. Also applicable to metric 165,1 mm size.
CH - Common Hardware - See Materials of Construction section for specifications.

FIGURE 6 (2 OF 2)
DV-5 a VALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1421
Page 11 of 18

Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1 1/2 2.8 9.7 9.8 15.7 16.0 7.4 10.2 8.02 1.2
(40) (71) (246) (249) (399) (406) (188) (259) (204) (31)
2 2.8 9.7 9.8 15.7 16.0 7.4 10.2 8.09 2.9
(50) (71) (246) (249) (399) (406) (188) (259) (205) (74)
3 4.0 10.7 11.5 16.3 18.4 6.2 13.8 3.79 3.6
(80) (102) (272) (292) (414) (467) (158) (351) (96) (91)
4 4.5 11.9 12.6 16.5 21.0 5.5 16.8 4.54 4.3
(100) (114) (302) (320) (419) (533) (140) (427) (115) (109)
63 5.7 13.4 14.5 18.4 24.8 3.8 22.4 5.83 5.7
(150) (145) (340) (368) (467) (630) (97) (569) (148) (145)
8 6.8 16.1 16.7 19.5 29.2 3.3 27.5 5.24 6.7
(200) (174) (409) (424) (495) (742) (84) (699) (133) (170)
NOTES:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.
3. Also applicable to metric 165,1 mm size.

J B C D
A

H F

FIGURE 7
DV-5 a VALVE
SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
NOMINAL DIMENSIONS
TFP1421
Page 12 of 18

Valve Setting Step 9. Operate (open) the manual


control station (M) and then open
Step 13. Partially open the system
main control valve (B). Slowly close the
Procedure the diaphragm supply valve (P). After
unaerated water ceases to discharge
main drain valve (D) as soon as water
discharges from the main drain valve
Perform Steps 1 through 16 when ini- from the manual control station (M) (D). Observe the automatic drain valve
tially setting the TYCO DV-5a Electric drain tube, slowly close the operating (F) for leaks. If there are leaks, deter-
Actuation Valve, after an operational lever by pushing it up. Do not close the mine/correct the cause of the leakage
test of the fire protection system, or hinged cover at this time. problem before proceeding.
after system operation due to a fire. Step 10. After allowing water to flow
See Figure 8. out of the manual reset actuator (N) NOTICE
Step 1. Close the system main control drain tube until aerated water ceases When the system main control valve
valve (B). to discharge, reset the manual reset (B) is partially opened, the pressure
actuator (N) by pressing the reset knob on the DV-5a diaphragm chamber may
Step 2. Close the diaphragm supply and hold until water stops flowing from increase. This increase in pressure is
valve (P). its drain tube and the pressure builds normal, and if the pressure is greater
Step 3. Close the supervisory air and reaches approximately 15 psi (1,0 than 300 psi (20,7 bar), the pressure is
supply valve (S). bar) on the diaphragm gauge (K). Pres- to be relieved by partially and temporar-
sure will then build up in the DV-5a dia- ily opening the manual control station
Step 4. Open the main drain valve (D), phragm chamber. (M); however, do not allow the pressure
system drain valve (E), and all auxiliary as indicated on the diaphragm gauge
drains in the system. Close the auxiliary Step 11. Verify the ability for the DV-5a
diaphragm to hold pressure as follows: (K) to drop below the supply pressure
drain valves and the system drain valve shown on the water supply gauge (J),
(E) after water ceases to discharge. • With the diaphragm chamber pres- since this action may result in tripping
Leave the main drain valve (D) open. surized per Step 10, temporarily of the DV-5a valve.
At this time make certain that the pres- close the diaphragm supply valve
(P), and then observe the diaphragm Step 14. Close the hinged cover of the
sure gauge valves and the alarm control manual control station (M) and insert a
valve (H), as applicable, are open. gauge (K) for a drop in pressure.
new break rod in the small hole through
Step 5. Depress the plunger of the • If a drop in pressure is noted, the the top of the enclosing box.
automatic drain valve (F) to verify that DV-5a diaphragm is to be replaced
and/or any leaks must be corrected Step 15. Fully open the system main
it is open. control valve (B).
before proceeding to the next step.
Step 6. Clean the diaphragm supply Step 16. After setting a fire protec-
strainer (Q) by removing the clean- • If the diaphragm gauge (K) indicates
no drop in pressure, re-open the tion system, notify the proper authori-
out plug and strainer basket. The dia- ties and advise those responsible for
phragm supply strainer (Q) may be diaphragm supply valve (P) and
proceed to the next step. monitoring proprietary and/or central
flushed out by momentarily opening station alarms.
the diaphragm supply valve (P). Step 12. Open the supervisory air
Step 7. Replace any operated sprin- supply valve (S) to reestablish supervi-
klers on the system piping, as sory system air pressure at nominally
applicable. 10 psi (0,68 bar).
Step 8. Reset the automatic actuation
system. Reset the electric detection
system in accordance with the manu-
facturer’s instructions to de-energize
the solenoid valve.
TFP1421
Page 13 of 18

Item Description Item Description External Trim Connections


A DV-5a Valve L System Gauge C1 Diaphragm Supply Connection
B System Main Control Valve M Manual Control Station C2 Water Motor Alarm Connection
C Waterflow Pressure Switch N Manual Reset Actuator C3 Supervisory Air Supply Connection
D Main Drain Valve P Diaphragm Supply Valve C4 Waterflow Pressure Alarm Switch
E System Drain Valve Q Diaphragm Supply Strainer Connection
F Automatic Drain Valve R Inverted Flare Shut-Off Valve C5 Low Air Pressure Alarm Switch
G Alarm Test Valve S Supervisory Air Supply Valve Connection
H Alarm Control Valve (Optional) T Supervisory Air Pressure Relief Valve C6 Main Drain Connection
J Water Supply Gauge U Supervisory Low Pressure Switch C7 Drip Funnel Drain Connection
K Diaphragm Gauge V Solenoid Valve

C5
L
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
C N.O. ALARM
CONTROL P4
P7 V
VALVE
F
S
P5
C2 T
C4

D
P6

H A C3
P3

P1 C7 M
P2 C6
E

J K
B

Q
G
P
C1
R

Note:
Port Connections P1 through P7 are described in Figure 2.

FIGURE 8
DV-5 a VALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION
(See Figure 6 for specific Bills of Materials)
TFP1421
Page 14 of 18

Care and Drop in Water Supply Pressure


Below Normal Range
Supervisory Low Pressure Alarm
Test Procedure
Maintenance NOTICE
Proper operation of the supervisory low
pressure switch (U) must be performed
The following procedures and inspec- If the water supply pressure is signif- as follows:
tions must be performed as indicated, icantly reduced below the normally Step 1. Open the system drain valve
in addition to any specific require- expected static pressure range (as (E) just enough to slowly relieve super-
ments of the NFPA and any applicable could occur in the case of a water main visory air pressure from the system.
standards recognized by the Approval break or repair), and there is a subse- Verify that the supervisory low pressure
agency. Any impairment must be imme- quent drop in the diaphragm chamber switch (U) is operational and that the
diately corrected. See Figure 8. water pressure below its normal range low pressure set point is approximately
(for example, due to a leak in a piping 5 psi (0,34 bar).
NOTICE connection to or from the diaphragm
chamber or, a leak in the diaphragm Step 2. Close the system drain valve
If the water supply needs to be shut off chamber check valve caused by dirt or (E) and allow the system supervisory
to the DV-5a valve and trim and cannot debris in the check valve seal area), a pressure of 10 ± 2 psi (0,69 ± 0,14 bar)
be shut off upstream of the system, deluge valve such as the DV-5a could to be automatically re-established. The
close the system main control valve (B), inadvertently trip, if its water supply supervisory low pressure switch (U)
the diaphragm supply valve (P), and the pressure is quickly restored. should return to its normal condition.
inverted flare shut-off valve (R). This will
A drop in the water supply pressure Pressure Relief Valve Maintenance
allow any trim above the system main Over pressurization of the system
to below its normal range (as in the
control valve (B) to be taken apart for piping with air will result in the opening
case of an interrupted water supply
service if necessary. of the supervisory air pressure relief
condition) constitutes an emergency
The frequency at which the following impairment. valve (T). If the supervisory air pres-
procedures and inspections are to be sure relief valve (T) continues to bleed
Should this condition occur, immedi- air after the system pressure has
performed are to be in accordance with
ately close the system main control been reduced to its normal super-
the NFPA and any applicable specific
valve (B) and use the following proce- visory pressure range of 10 ± 2 psi
requirements of the standards recog-
dure to reset the system: (0,69 ± 0,14 bar), most likely debris
nized by the Approval agency.
Step 1. Prior to the water supply pres- became lodged in the seating area. To
Before closing a fire protection system help clean the seating area, slowly pull
sure being restored to the closed
main control valve for maintenance up on the ring at the top of the supervi-
system main control valve (B), note the
work on the fire protection system that sory air pressure relief valve (T) to allow
pressure indicated by the diaphragm
it controls, permission to shut down a full flow of air through the supervisory
gauge (K) and determine if the pressure
the affected fire protection systems air pressure relief valve (T), and then
is within the normally expected range.
must first be obtained from the proper release the ring to allow the supervi-
authorities and all personnel who may Step 2. If the diaphragm chamber pres-
sory air pressure relief valve (T) to snap
be affected by this action must be sure is below the normal range, check
closed. Repeat the cleaning procedure
notified. for and correct any source of leakage
as necessary.
from the diaphragm chamber prior to
The owner is responsible for the
resetting the system. Electric Actuation Solenoid Valve
inspection, testing, and maintenance
of their fire protection system and Step 3. After the water supply pres- Test Procedure
devices in compliance with this docu- sure is restored to the system main Proper operation of the solenoid valve
ment, as well as with the NFPA and any control valve (B), reset the DV-5a valve (V) for electric actuation must be veri-
applicable standards recognized by the in accordance with the Valve Setting fied at as follows:
Approval agency. Contact the install- Procedure section. Step 1. Close the system main control
ing contractor or product manufacturer valve (B).
with any questions. NOTICE Step 2. Open the main drain valve (D).
Some procedures in this section result For fire protection systems subject to
Step 3. Test the deluge releasing panel
in the operation of the associated an emergency impairment caused by
in accordance with the manufacturer’s
alarms. Notify the owner and the fire an interrupted water supply condition,
instructions to energize the solenoid
department, central station, or other it is recommended that consideration
valve.
signal station to which the alarms are be given to installing a low water supply
connected before performing the tests. pressure switch with the appropriate Step 4. Verify that there is a flow of
alarm/indications to monitor the water water from the solenoid valve drain
It is recommended that automatic
supply pressure. connection.
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec- Waterflow Alarm Test Procedure Step 5. Verify that the diaphragm
tion Service in accordance with the To test the waterflow alarm, open the chamber pressure has decreased
NFPA and any applicable standards alarm est valve (G), which will allow a to below 25% of the water supply
recognized by the Approval agency. flow of water to the waterflow pressure pressure.
switch (C) and/or water motor alarm.
Upon satisfactory completion of the
test, close the alarm test valve (G).
To ensure drainage of the alarm line,
depress the plunger on the automatic
drain valve (F).
TFP1421
Page 15 of 18

Step 6. Reset the electric detection To perform internal valve inspection


system in accordance with the manu- between Steps 4 and 5 of the Valve Torque
facturer’s instructions to de-energize Setting Procedure remove the dia- Nominal lb-ft
Valve Sizes (N∙m)
the solenoid valve (V), and proceed as phragm cover as follows: ANSI
follows: Inches Short
Step 1. Close the inverted flare shut-
(DN) Nuts Hex
• Water should cease draining from the off valve (R). Bolts
solenoid valve (V) but remain drain-
Step 2. Remove the copper tube fitting
ing from the manual reset actuator 1 1/2 44 35
between the diaphragm supply valve
(N). (40) (59,7) (47,5)
(P) and the inverted flare shut-off valve
• Press the reset knob on the manual (R). 2 44 35
reset actuator (N) and hold it a few (50) (59,7) (47,5)
Step 3. Loosen the union securing the
seconds until water stops flowing 3 125 125
electric actuation trim and remove the
from its drain tube. (80) (169,5) (169,5)
electric actuation trim.
• Pressure will then build up in the 4 150 150
Step 4. Loosen and remove the union
DV-5a diaphragm chamber. (100) (203,4) (203,4)
between the diaphragm cover and the
• After system pressure is restored MRA-1 manual reset actuator (N) and 61 150 150
in the DV-5a diaphragm chamber, remove the MRA-1 manual reset actua- (150) (203,4) (203,4)
inspect the solenoid valve (U) and tor (N) subassembly. 8 188 188
manual reset actuator (N) for leaks (200) (254,9) (254,9)
Step 5. Remove the diaphragm valve
at the drain tube. Any leaks must be
cover hardware, then slowly remove the
corrected before proceeding to the NOTES
diaphragm cover and perform internal 1. Also applicable to metric 165,1 mm size.
next step.
valve inspection. Clean the valve inte- TABLE B
Step 7. Partially open the system main rior and replace parts as necessary. DIAPHRAGM COVER BOLTS
control valve (B). Slowly close the main MINIMUM TORQUE
After cleaning and inspecting valve
drain valve (D) as soon as water dis-
interior, and replacing parts as nec-
charges from the main drain valve (D). Step 8. Ensure that the unions and flare
essary, reinstall the diaphragm cover
Observe the automatic drain valve fittings are securely tightened.
by completing the following steps to
(F) for leaks. If there are leaks, deter-
assure the diaphragm cover fasteners Step 9. With the diaphragm supply
mine/correct the cause of the leakage
are uniformly and securely tightened. valve (P) closed, fully open the inverted
problem. If there are no leaks, the
DV-5a valve is ready to be placed in Step 1. With reference to Figure 1, flare shut-off valve (R) stainless steel
service and the system main control ensure that the diaphragm is properly screw (approximately 1/2 in.) until resis-
valve (B) must then be fully opened. oriented and that the proper hardware tance is met so as not to break the
arrangement is utilized when assem- internal roll-pin. The internal roll-pin
Internal Valve Inspection bling the diaphragm covers. The hard- stops the removal of the inverted flare
Once every five years during the ware arrangements differ depending on shut-off valve (R) stainless steel screw.
annual operational test procedure and the size of the DV-5a valve.
prior to the DV-5a valve being reset Step 10. Proceed with Step 5 of the
and with the DV-5a valve de-pressur- Step 2. By first using the long hex Valve Setting Procedures section in this
ized, the interior of the DV-5a valve bolts, support of the diaphragm cover data sheet.
must be cleaned and inspected for will be provided before installing the
wear and damage. Damaged or worn short hex bolts. Align diaphragm in NOTICE
parts must be replaced. (Replace- proper orientation with valve body, and
If the water supply contains chemicals
ment of the diaphragm every ten years then align diaphragm cover in proper
which tend to attack a polyester fab-
is recommended, or more frequently orientation with valve body. Hand-
ric-reinforced, EPDM rubber or the five
if inspections and/or wear and tear tighten all fasteners.
year inspection indicates a build-up of
warrant more frequent replacement.) Step 3. Using crossdraw sequence to debris within the DV-5a valve that could
assure uniformity, wrench-tighten long affect its proper operation, then the
NOTICE hex bolts and short hex bolts to appro- frequency of the internal valve inspec-
The diaphragm cover may be removed priate torque values. Repeat crossdraw tion procedure must be appropriately
between Steps 4 and 5 of the reset- sequence two to three times at incre- increased.
ting instructions, since at that point the mental torque valves until reaching the With reference to Figure 1, make
DV-5a valve should be de-pressurized torque valves found in Table B. certain that the diaphragm is correctly
as evident by a zero gauge reading on Step 4. Inspect to assure all hex bolts oriented; otherwise, the DV-5a valve
the diaphragm gauge (K) and water are securely tightened. cannot be properly set.
supply gauge (J), as well as no water
discharging from the automatic drain Step 5. Using the union, secure the Under-tightening the diaphragm cover
valve (F). MRA-1 manual reset actuator (N) to the bolts can result in internal and external
diaphragm cover. leakage.
Step 6. Using the union, secure the Use only TYCO replacement fasteners
electric actuation trim. as specified in Figure 1.
Step 7. Replace the copper tube fitting Do not apply adhesives, lubricants,
between the diaphragm supply valve or other substances to the diaphragm
(P) and the inverted flare shut-off valve valve body.
(R).
TFP1421
Page 16 of 18

Limited Flange x Grove ANSI


3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031330
EMEA
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550031340 DV-5A Valves with Galvanized Trim
Warranty 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550031360
8 in. (DN200) �������������������������������������� 550031380
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, (specify)
For warranty terms and conditions, visit T x T NPT end connection with assembled galva-
www.tyco-fire.com. 1 1/2 in. (DN40) �����������������������������������550061315 nized EMEA Single Interlock Preaction
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061320
Electric Actuation Trim, P/N (specify):
Ordering Separate DV-5A Valves without Trim
See Table A for flange drilling
Groove x Groove

Procedure
1 1/2 in. (DN40) ����������������������������������� 550111315
specifications. 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550111320
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550111330
The TYCO DV-5a Automatic Water Specify: Size (specify), DV-5 a Auto- 4 in. (DN100) ��������������������������������������� 550111340
Control Valves may be ordered as matic Water Control Valve, (specify) 6 in. (DN150) ��������������������������������������� 550111360
follows: end connection, P/N (specify): 165,1 mm . . . . . . . . . . . . . . . . . . . . . . . 550111366
8 in. (DN200) ��������������������������������������� 550111380
Groove x Groove
Pre-Assembled Valves 1 1/2 in. (DN40) ���������������������������������� 530010015 Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550121330
with Trim 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030 4 in. (DN100) ���������������������������������������550121340
DV-5A Valves with Galvanized Trim 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 6 in. (DN150) ���������������������������������������550121360
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060 8 in. (DN200) ���������������������������������������550121380
and Butterfly Valve
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
Specify: Size (specify), DV-5 a Auto- Flange x Groove ANSI
matic Water Control Valve, G x G con- Flange x Flange ANSI 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550131330
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 4 in. (DN100) ���������������������������������������550131340
nections with assembled galvanized 6 in. (DN150) ���������������������������������������550131360
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
Americas Single Interlock Preaction 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 8 in. (DN200) ���������������������������������������550131380
Electric Actuation Trim, complete with 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Flange ISO
assembled Model BFV-300 Butterfly 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550141330
Flange x Grove ANSI
Valve, P/N (specify): 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030 4 in. (DN100) ���������������������������������������550141340
Groove x Groove 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040 6 in. (DN150) ���������������������������������������550141360
1 1/2 in. (DN40) ����������������������������������� 551011315 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060 8 in. (DN200) ���������������������������������������550141380
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 551011320 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080 Flange x Groove ISO
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 551011330 T x T NPT 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550151330
4 in. (DN100) ��������������������������������������� 551011340 1 1/2 in. (DN40) ���������������������������������� 530060015 4 in. (DN100) ���������������������������������������550151340
6 in. (DN150) ��������������������������������������� 551011360 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 6 in. (DN150) ���������������������������������������550151360
8 in. (DN200) ��������������������������������������� 551011380 8 in. (DN200) ���������������������������������������550151380
Notes:
Notes: Valves are typically provided with flange
T x T ISO
AMERICAS DV-5A Valve with Trim and 1 1/2 in. (DN40) ����������������������������������� 550171315
drilling per ANSI B16.1 (Class 125) or ISO 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550171320
Butterfly Valve: Americas pressure (7005-2 PN16).
switches, P/N 52-287-1-124 solenoid valve, Notes:
and psi/kPa water pressure gauges are Upon request, valves can be provided with Pressure switches, P/N 52-287-1-124
provided. flange drilling per JIS B 2210 or AS 2129. In solenoid valve, bar/psi water pressure
which case part numbers are not assigned. gauges, and NPT to ISO threaded trim
This arrangement is available for EMEA
and APAC upon request. Contact your DV-5A Valve Trim adaptors for external connections are
local distributor. Specify: Size (specify), finish (specify), provided.
Electric Actuation Trim for DV-5a Auto- Separate DV-5A Valves without Trim
AMERICAS matic Water Control Valves used in See Table A for flange drilling
DV-5A Valves with Galvanized Trim Single Interlock Preaction Fire Protec- specifications.
Specify: Size (specify), DV-5 a Auto- tion System, P/N (specify):
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, (specify) Galvanized matic Water Control Valve, (specify)
end connection with assembled gal- 1 1/2 in. (DN40) ���������������������������������� 540001320
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001320 end connection, P/N (specify):
vanized Americas Single Interlock 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001330 Groove x Groove
Preaction Electric Actuation Trim, P/N 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001340 1 1/2 in. (DN40) ���������������������������������� 530010015
(specify): 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001360 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
Groove x Groove 8 in. (DN200) �������������������������������������� 540001380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
1 1/2 in. (DN40) ����������������������������������� 550011315 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040
Note: 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011320
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011330
Pressure switches and/or solenoid valves 165,1 mm . . . . . . . . . . . . . . . . . . . . . . 530010066
4 in. (DN100) ���������������������������������������550011340 for electric actuation are separately 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
6 in. (DN150) ���������������������������������������550011360 ordered. Flange x Flange ANSI
8 in. (DN200) ���������������������������������������550011380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030
Flange x Flange ANSI 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021330 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021340 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021360 Flange x Grove ANSI
8 in. (DN200) �������������������������������������� 550021380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080
TFP1421
Page 17 of 18

T x T NPT T x T NPT DV-5A Valve Trim


1 1/2 in. (DN40) ���������������������������������� 530060015 1 1/2 in. (DN40) �����������������������������������550061315 Specify: Size (specify), finish (specify),
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061320
Electric Actuation Trim for DV-5a Auto-
Flange x Flange ISO Flange x Flange ISO matic Water Control Valves used in
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530040030 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550041330 Single Interlock Preaction Fire Protec-
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530040040 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550041340
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530040060 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550041360
tion System, P/N (specify):
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530040080 8 in. (DN200) �������������������������������������� 550041380 Galvanized
1 1/2 in. (DN40) ���������������������������������� 540001320
Flange x Groove ISO Flange x Groove ISO
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001320
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530050030 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550051330
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001330
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530050040 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550051340
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001340
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530050060 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550051360
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001360
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530050080 8 in. (DN200) �������������������������������������� 550051380
8 in. (DN200) �������������������������������������� 540001380
T x T ISO Note: Pressure switches, P/N 52-287-1-124 Note: Pressure switches and/or solenoid
1 1/2 in. (DN40) ���������������������������������� 530070015 solenoid valve, and psi/kPa water pressure
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530070020 valves for electric actuation are separately
gauges are provided. ordered.
Notes: Separate DV-5A Valves without Trim
Valves are typically provided with flange DV-5A Valve Trim Accessories
See Table A for flange drilling
drilling per ANSI B16.1 (Class 125) or ISO (for separately ordered valve trim)
specifications.
(7005-2 PN16). Specify: Specify Accessory Descrip-
Specify: Size (specify), DV-5 a Auto- tion), P/N (specify):
Upon request, valves can be provided with matic Water Control Valve, (specify)
flange drilling per JIS B 2210 or AS 2129. In Waterflow Pressure Alarm Switch
end connection, P/N (specify): PS10-2 (America) ���������������������������������������25710
which case part numbers are not assigned. Waterflow Pressure Alarm Switch
Groove x Groove
DV-5A Valve Trim 1 1/2 in. (DN40) ���������������������������������� 530010015 (APAC) . . . . . . . . . . . . . . . . . . . 25710 OR 100102
Waterflow Pressure Alarm Switch
Specify: Size (specify), finish (specify), 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
(EMEA) . . . . . . . . . . . . . . . . . . . . . 0260 or 100101
Electric Actuation Trim for DV-5a Auto- 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 Supervisory Air Pressure Alarm Switch,
matic Water Control Valves used in 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060 PS40-2 (America) �������������������������������������� 25730
Single Interlock Preaction Fire Protec- 165,1 mm . . . . . . . . . . . . . . . . . . . . . . 530010066 Supervisory Air Pressure Alarm Switch,
tion System, P/N (specify): 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080 (APAC) . . . . . . . . . . . . . . . . . . . . 25730 or 100402
Supervisory Air Pressure Alarm Switch
Galvanized Flange x Flange ANSI (EMEA) . . . . . . . . . . . . . . . . . . . . . 0262 or 100401
1 1/2 in. (DN40) �����������������������������������540101320 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 Model WMA-1 Water Motor Alarm
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 540101320 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040 (America/APAC) ������������������������������ 526301001P
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 540101330 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 Model WMA-1 Water Motor Alarm
4 in. (DN100) ���������������������������������������540101340 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 (EMEA) . . . . . . . . . . . . . . . . . . . . . . . 526301021R
6 in. (DN150) ���������������������������������������540101360 Model G16AC812 Automatic Supervisory
8 in. (DN200) ���������������������������������������540101380 Flange x Grove ANSI
Air Supply . . . . . . . . . . . . . . . . . . . . . . 521201001
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
Model AMD-1 Air Maintenance Device
Note: Pressure switches, solenoid valves 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Supervisory Air Supply ���������������������� 523242002
for electric actuation, water pressure 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
Model AMD-3 Nitrogen Maintenance Device
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080
gauges, and BFV-300 Butterfly Valve are Supervisory Air Supply ���������������������� 523282001
separately ordered. NPT to ISO threaded T x T NPT Water Gauges
adaptors are provided for External Trim 1 1/2 in. (DN40) ���������������������������������� 530060015 with bar/psi . . . . . . . . . . . . . . . . . . . . 025500013
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 600 psi Water Gauge psi/kPa
Connections (drains, pressure switches, (service pressure over 300 psi) �������� 923431004
water motor alarms, etc.). Flange x Flange ISO Solenoid Valve for
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530040030 Releasing Service . . . . . . . . . . Refer to Technical
APAC 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530040040
Data Sheet TFP2180
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530040060
DV-5A Valves with Galvanized Trim 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530040080 DV-5A Valve Replacement Parts
Specify: Size (specify), DV-5 a Auto- Flange x Groove ISO Specify: (Description) for use with
matic Water Control Valve, (specify) 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530050030 (specify size) DV-5a Automatic Water
end connection with assembled galva- 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530050040 Control Valve, P/N (See Figure 1)
nized APAC Single Interlock Preaction 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530050060
Electric Actuation Trim, P/N (specify): 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530050080 DV-5A Valve Trim Replacement
Groove x Groove T x T ISO Parts
1 1/2 in. (DN40) ����������������������������������� 550011315 1 1/2 in. (DN40) ���������������������������������� 530070015 Specify: (Description) for use with
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011320 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530070020 DV-5a Valve Trim, P/N (See Figure 6)
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011330
4 in. (DN100) ���������������������������������������550011340 Notes:
6 in. (DN150) ���������������������������������������550011360 Valves are typically provided with flange
165,1 mm . . . . . . . . . . . . . . . . . . . . . . . 550011366 drilling per ANSI B16.1 (Class 125) or ISO
8 in. (DN200) ���������������������������������������550011380 (7005-2 PN16).
Flange x Flange ANSI Upon request, valves can be provided with
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021330
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021340
flange drilling per JIS B 2210 or AS 2129. In
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021360 which case part numbers are not assigned.
8 in. (DN200) �������������������������������������� 550021380
Flange x Groove ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031330
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550031340
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550031360
8 in. (DN200) �������������������������������������� 550031380
TFP1421
Page 18 of 18

1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220


© 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
Worldwide
www.tyco-fire.com
Contacts

DV-5A Appendix A
Poster Printing
Instructions
General W

Description
The appendix found at the end of this
document provides valve setting and
Valve Setting Procedure 7. Pressure will then build up in DV-5A Diaphragm Chamber.
1. Close System Main Control Valve (B), Diaphragm Supply Valve (P), and Air Supply Control 8. After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
Valves (X) and (Y). (N) for leaks. Any leaks must be corrected before proceeding.
2. Open Main Drain Valve (D), System Drain Valve (E), and all auxiliary drains in system. Also,

testing/inspection procedures summa-


Worldwide 9. Reestablish battery and main power to releasing panel in accordance with manufacturer’s
www.tyco-fire.com remove plug from Air Supply Strainer (W) to drain any water and ensure it is clean and free
Contacts instructions.
of debris. Close auxiliary drain valves, System Drain Valve (E), and reassemble Air Supply
10. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
Strainer (W) after water stops discharging. Leave Main Drain Valve (D) open. discharges from Main Drain Valve (D), then close Main Drain Valve (D). Observe Automatic
3. Ensure Pressure Gauge Valves and Alarm Control Valve (H), as applicable, are open.

rized from the Care and Maintenance


Drain Valve (F) for leaks and correct the leakage problem. If there are no leaks, place DV-5A

Summary Instructions
4. Depress plunger of Automatic Drain Valve (F) to verify it is open. Valve in service and open System Main Control Valve (B).
5. Clean Diaphragm Supply Strainer (Q). Flush strainer by opening the Diaphragm Supply Supervisory Low Pressure Alarm Test Procedure and Validation of Normally Closed
DV-5A Automatic Water Control Valve Valve (P). Solenoid Valve (S)

section.
6. Replace operated automatic sprinklers on system piping. 1. Close System Main Control Valve (B), and open Main Drain Valve (D).
Preaction Type A Systems 7. Reset DV-5A Valve Releasing Panel in accordance with manufacturer instructions.
8. Re-establish system air pressure to reset Model DP-1 Dry Pilot Actuator (T) by opening Air
2. Crack open system’s Inspector’s Test Connection to relieve air pressure from system.
Verify Supervisory Low Pressure Alarm Switch (V) is operational and low pressure set point
(EN12845 Compliance) Supply Control Valve (X). Do not open Air Supply Control Valve (Y) at this time. Observe Dry
Pilot Actuator (T) air pressure on Dry Pilot Gauge (Z).
is approximately 0,4 bar under minimum system air pressure.
3. Allow system air pressure to decay to 0 psig. Verify no water draining from Dry Pilot Actu-
9. Open Manual Control Station (M), then open Diaphragm Supply Valve (P). After aerated ator (T).

Some jurisdictions require a copy of the


NOTICE
water stops discharging from Manual Control Station (M) drain tube, slowly close operating 4. Close system’s Inspector’s Test Connection and allow system supervisory pressure to auto-
The procedures provided are summary instructions of the complete procedures appearing in lever. Do not close hinged cover at this time. matically re-established. As necessary, open, then close quick fill air supply control valve in
Technical Data Sheet TFP1485. If problems occur, consult full document. 10. After aerated water stops discharging, reset Manual Reset Actuator (N) until water stops automatic air maintenance device. Supervisory Low Pressure Alarm Switch (V) should return
flowing from its drain tube and pressure reaches approximately 15 psi (1,0 bar) on Diaphragm to “normal” condition.

Summary Instructions appendix to be


Gauge (K). 5. Verify system air pressure is normal and DV-5A Diaphragm Chamber remains pressurized.
Z
11. With diaphragm chamber pressurized, temporarily close Diaphragm Supply Valve (P), and 6. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
V
L Y
observe Diaphragm Gauge (K) for a drop in pressure. If pressure drop is noted, replace DV-5A discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there
Diaphragm and correct any leaks before proceeding. are leaks, correct the leakage problem. If there are no leaks, place DV-5A Valve in service and

displayed in proximity to a DV-5A Auto-


12. If Diaphragm Gauge (K) indicates no drop in pressure, re-open Diaphragm Supply Valve open System Main Control Valve (B).
(P) and proceed. Operation Test Procedure
13. Open Air Supply Control Valve (Y) to pressurize system piping. 1. To prevent water from flowing beyond riser, close System Main Control Valve (B). Open
Main Drain Valve(D).

matic Control Valve riser supplying a


X
14. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water
R discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there 2. Open System Main Control Valve (B) one turn beyond which water begins to flow from Main
S
C
are leaks, correct the leakage problem. Drain Valve (D). Slowly close Main Drain Valve (D).
T 15. Close hinged cover of Manual Control Station (M) and insert new break rod in small hole 3. Test deluge releasing panel in accordance with manufacturer’s instructions to energize

fire protection system.


F U through the top of the enclosing box. Solenoid Valve (R).

H
16. Open System Main Control Valve (B). 4. Verify DV-5A Valve has tripped, as indicated by water flow into system.
17. After setting fire protection system, notify proper authorities and advise those responsible 5. Close System Main Control Valve (B).
D
W for monitoring proprietary and/or central station alarms. 6. Close Diaphragm Supply Valve (P) and Air Supply Control Valves (X) and (Y).
H A
Waterflow Alarm Test Procedure 7. Reset DV-5A Valve with Preaction Type A Trim in accordance with Valve Setting Procedure.
M 1. Open Alarm Test Valve (G), allowing water to flow to Waterflow Pressure Switch (C) and/or

Reproduce as an individual poster by


Internal Valve Inspection
Water Motor Alarm. Close Alarm Test Valve (G) when test is completed. 1. Ensure that Steps 1 to 4 of the Valve Setting Procedure are completed prior to proceeding
E 2. Depress plunger on the Automatic Drain Valve (F) to drain alarm line. with the Internal Valve Inspection.
Solenoid Valve Test Procedure For Electric Actuation 2. Ensure Diaphragm Supply Valve (P) is closed. If provided as part of the valve trim, close

printing on appropriate media.


J
B
K 1. Close System Main Control Valve (B) and open Main Drain Valve (D). Inverted Flare Shut-Off Valve (AA).
N
2. Test deluge releasing panel in accordance with manufacturer’s instructions to energize 3. Remove the Supply Line between the Diaphragm Supply Valve (P) and the System Main
the Solenoid Valve (R). Control Valve (B). If provided as part of the valve trim, remove the Supply Line between the
Q 3. Verify that water is flowing from Solenoid Valve (R) drain connection. Diaphragm Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
G
4. Verify Diaphragm Chamber pressure has decreased to below 25% of water supply pressure. 4. Loosen union securing Actuation Trim and remove Actuation Trim.
P
AA
5. Reset electric detection system in accordance with manufacturer’s instructions to de-ener- 5. Remove union between Diaphragm Cover and MRA-1 Manual Reset Actuator (N). Remove

A form of protection is recommended


gize Solenoid Valve (R). Water should top draining from Solenoid Valve (R) but remain draining MRA-1 Manual Reset Actuator (N) subassembly.
from Manual Reset Actuator (N). 6. Remove Diaphragm Valve Cover hardware, slowly remove Diaphragm Cover and perform
6. Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water stops internal valve inspection. Clean valve interior and replace parts as necessary.
flowing. 7. Ensure Diaphragm is properly oriented and proper hardware arrangement is utilized.

to prevent damage which could render


Item Description Item Description 7. After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator 8. Insert Long Hex Bolts. Align Diaphragm with Valve Body, and then align Diaphragm Cover
A DV-5a Valve P Diaphragm Supply Valve (N) for leaks. Correct any leaks before proceeding. with Valve Body. Insert Short Hex Bolts. Hand-tighten all fasteners.
B System Main Control Valve Q Diaphragm Supply Strainer 8. Partially open System Main Control Valve (B). Slowly close Main Drain Valve (D) as water 9. Using crossdraw sequence, wrench-tighten Long Hex Bolts and Short Hex Bolts. Repeat
C Waterflow Pressure Switch R Solenoid Valve (NC) De-Energized #1
discharges from Main Drain Valve (D). Observe Automatic Drain Valve (F) for leaks. If there crossdraw sequence two to three times at incremental torque valves.

the poster illegible. Conditions to avoid


D Main Drain Valve S Solenoid Valve (NC) Energized #2
E System Drain Valve T Dry Pilot Actuator are leaks, correct the leakage problem. If there are no leaks, place DV-5A Valve in service and 10. Inspect to assure all Hex Bolts are securely tightened.
F Automatic Drain Valve U Pressure Relief Valve open System Main Control Valve (B).
G Alarm Test Valve V Supervisory Low Pressure Alarm Switch
11. Using the union, secure the MRA-1 Manual Reset Actuator (N) to the Diaphragm Cover.
H Alarm Control Valve (Optional) W Air Supply Strainer Solenoid Valve and Dry Pilot Actuator Test Procedure 12. Using union, secure Actuation Trim.
1. Close System Main Control Valve (B) and open Main Drain Valve (D).

include moisture infiltration, fading,


J Water Supply Gauge X Air Supply Control Valve "A" 13. Replace the Supply Line between the Diaphragm Supply Valve and the System Main
K Diaphragm Gauge Y Air Supply Control Valve "B" 2. Simulate power failure by disconnecting main power to releasing panel, and disconnecting
L System Gauge Z Dry Pilot Gauge Control Valve (B). If provided as part of the valve trim, replace Supply Line between Diaphragm
battery back-up. Refer to releasing panel manufacturer’s instructions for specific details. This Supply Valve (P) and Inverted Flare Shut-Off Valve (AA).
M Manual Control Station AA Inverted Flare Shut-Off Valve
N Manual Reset Actuator step allows Solenoid Valve (S) to open.
14. Ensure unions and flare fittings are securely tightened.

mutilation, etc.. Protective measures


3. Open system’s Inspector’s Test Connection to relieve system air pressure.
15. If provided with the valve trim, and with Diaphragm Supply Valve (P) closed, fully open
4. Verify water flow from Dry Pilot Actuator (T) drain connection. Inverted Flare Shut-Off Valve (AA) stainless steel screw (approximately 1/2 in.) until resis-
Scan the QR code or enter the URL 5. Verify Diaphragm Chamber pressure decreased to below 25% of water supply pressure.
in a web browser to access the most tance is met.
6. Close Inspector’s Test Connection and allow the system air pressure to re-establish. Water 16. Proceed with Step 5 of the Valve Setting Procedures.

may include lamination, placement


up-to-date electronic version of this
document. Data rates may apply. stops draining from Dry Pilot Actuator (T) but continues to drain from Manual Reset Actua-
TFP1485 APPENDIX A tor (N). Press Reset Knob on Manual Reset Actuator (N) and hold a few seconds until water 1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220

AUGUST 2022 docs.jci.com/tycofire/tfp1485 stops flowing from drain tube. © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.

within an impact- and water-resistant


frame, etc.
Imperial Metric
The format shown in this document is Format in. mm
landscape orientation on US Tabloid
size, also known as ANSI B drawing W H W H
format, both roughly comparable to US Tabloid
ISO A3 size format. 17 11 — —
ANSI B
To avoid potential cropping of content
when printing to A3 format, select ISO A3 — — 420 297
options such as print to fit or scale PRINT FORMAT DIMENSIONS
to fit. Depending on printer capabil-
ity content will be slightly reduced but
should remain readable.
See Print Format Dimensions Table for
details.

APPENDIX A INSTRUCTIONS TFP1421


Valve Setting Procedure Electric Actuation Solenoid Valve Test Procedure
1. Close system main control valve (B) and diaphragm supply valve (P). 1. Close system main control valve (B).
2. Close supervisory air supply valve (S). 2. Open main drain valve (D).
Worldwide 3. Open main drain valve (D), system drain valve (E), and all auxiliary drains in the system. 3. Test deluge releasing panel in accordance with manufacturer’s instructions to energize
www.tyco-fire.com
Contacts Close auxiliary drain valves and system drain valve (E) after water stops discharging. Leave solenoid valve.
main drain valve (D) open. Ensure pressure gauge valves and alarm control valve (H) are open. 4. Verify water flow from solenoid valve (V) drain connection.
4. Depress plunger of automatic drain valve (F) to verify it is open. 5. Verify diaphragm chamber pressure decreases to below 25% of water supply pressure.
5. Clean diaphragm supply strainer (Q). Flush strainer by opening the diaphragm supply valve 6. Reset electric detection system in accordance with manufacturer’s instructions to de-
Summary Instructions (P).
6. Replace operated sprinklers on system piping, as applicable.
energize solenoid valve (V).
7. Water should cease draining from solenoid valve (V) but remain draining from manual reset
DV-5a Automatic Water Control Valve 7. Reset electric detection system in accordance with manufacturer’s instructions to de-
energize solenoid valve (V).
actuator (N)
8. Press reset knob on manual reset actuator (N) and hold it a few seconds until water stops
Single Interlock Preaction Electric 8. Open manual control station (M) and diaphragm supply valve (P). After aerated water tops
discharging, slowly close the operating lever. Do not close the hinged cover at this time.
flowing from its drain tube

Actuation Fire Protection Systems 9. After aerated water stops discharging, reset the manual reset actuator (N) until pressure
9. Pressure will then build up in DV-5a diaphragm chamber.
10. After system pressure is restored, inspect solenoid valve (V) and manual reset actuator
reaches approximately 15 psi (1,0 bar) on the diaphragm gauge (K) and water stops flowing (N) for leaks at drain tube. Any leaks must be corrected before proceeding.
NOTICE from its drain tube. 11. Partially open system main control valve (B). Slowly close main drain valve (D) as soon
10. With the diaphragm chamber pressurized, temporarily close diaphragm supply valve as water discharges from main drain valve (D). Observe automatic drain valve (F) for leaks. If
The procedures provided are summary instructions of the complete procedures appearing in (P), and observe diaphragm gauge (K) for a drop in pressure. If a pressure drop is noted,
Technical Data Sheet TFP1421. If problems occur, consult full document. there are leaks, correct the leakage problem. If there are no leaks, the DV-5a valve is ready to
replace DV-5A diaphragm and correct any leaks before proceeding. be placed in service and system main control valve (B) must then be fully opened.
11. If diaphragm gauge (K) indicates no drop in pressure, re-open the diaphragm supply
U Internal Valve Inspection
valve (P) and proceed.
1. Ensure diaphragm supply valve (P) is closed prior to closing inverted flare shut-off valve
12. Open supervisory air supply valve (S) to reestablish supervisory system air pressure at (R). Close inverted flare shut-off valve (R).
nominally 10 psi (0,68 bar).
L
2. Remove copper tube fitting between diaphragm supply valve (P) and inverted flare shut-
13. Partially open system main control valve (B). Slowly close main drain valve (D) when water off valve (R).
discharges from main drain valve (D). Observe automatic drain valve (F) for leaks. If there are
3. Loosen union securing actuation trim and remove actuation trim.
leaks, correct the leakage problem before proceeding.
4. Remove union between diaphragm cover and MRA-1 manual reset actuator (N). Remove
C 14. When system main control valve (B) is partially opened, the pressure on DV-5a diaphragm
chamber may increase. If pressure is greater than valve trim maximum pressure, relieve pres- MRA-1 manual reset actuator (N) subassembly.
V
F
S sure to at least valve trim pressure rating. Do not allow pressure to drop below supply pres- 5. Remove diaphragm valve cover hardware, slowly remove diaphragm cover and perform
T sure shown on water supply gauge (J) which may result in tripping of DV-5a valve. internal valve inspection. Clean valve interior and replace parts as necessary.
15. Close hinged cover of manual control station (M). Insert a new break rod in the small hole 6. Ensure diaphragm is properly oriented and proper hardware arrangement is utilized.
D
through the top of the enclosing box. 7. Insert long hex bolts. Align diaphragm with valve body, and then align diaphragm cover
16. Open system main control valve (B). with valve body. Insert short hex bolts. Hand-tighten all fasteners.
H A
17. After setting fire protection system, notify proper authorities and advise those responsible 8. Using crossdraw sequence, wrench-tighten long hex bolts and short hex bolts. Repeat
M
for monitoring proprietary and/or central station alarms. crossdraw sequence two to three times at incremental torque valves.
E 9. Inspect to assure all hex bolts are securely tightened.
Drop in Water Supply Pressure Below Normal Range
1. Note water supply pressure by the diaphragm gauge (K) and determine if the pressure is 10. Using the union, secure the MRA-1 manual reset actuator (N) to the diaphragm cover.
J
B
K within normally expected range. 11. Using union, secure actuation trim.
N 2. If below normal range, correct any leakage from diaphragm chamber prior to resetting the 12. Replace copper tube fitting between diaphragm supply valve (P) and inverted flare shut-
system. off valve (R).
Q 3. When water supply pressure is restored, reset DV-5a valve in accordance with the Valve 13. Ensure unions and flare fittings are securely tightened.
G
Setting Procedure. 14. With diaphragm supply valve (P) closed, fully open inverted flare shut-off valve (R) stain-
P
Waterflow Alarm Test Procedure less steel screw (approximately 1/2 in.) until resistance is met.
R
1. Open alarm test valve (G), allowing water to flow to waterflow pressure switch (C) and/or 15. Proceed with Valve Setting Procedures.
water motor alarm. Close the alarm test valve (G) when test is completed.
2. Depress plunger on automatic drain valve (F) to drain alarm line.
Electric Actuation Operation Test Procedure
Item Description Item Description 1. To prevent water from flowing beyond the riser, close system main control valve (B) and
open main drain valve (D).
A DV-5a Valve L System Gauge
B System Main Control Valve M Manual Control Station 2. Open system main control valve (B) one turn beyond position which water begins to flow
C Waterflow Pressure Switch N Manual Reset Actuator from main drain valve (D). Slowly close main drain valve (D).
D Main Drain Valve P Diaphragm Supply Valve 3. Test deluge releasing panel in accordance with manufacturer’s instructions to energize
E System Drain Valve Q Diaphragm Supply Strainer solenoid valve (V).
F Automatic Drain Valve R Inverted Flare Shut-Off Valve
G Alarm Test Valve S Supervisory Air Supply Valve 4. Verify DV-5a valve has tripped, indicated by flow of water into system.
H Alarm Control Valve (Optional) T Supervisory Air Pressure Relief Valve 5. Close system main control valve (B).
J Water Supply Gauge U Supervisory Low Pressure Switch
K Diaphragm Gauge V Solenoid Valve 6. Close diaphragm supply valve (P).
7. Reset DV-5a valve in accordance with the Valve Setting Procedure.

Scan the QR code or enter the URL


in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
TFP1421 APPENDIX A
JUNE 2023 docs.jci.com/tycofire/tfp1421 © 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.
Worldwide
www.tyco-fire.com
Contacts

TFP1421
Change History Appendix

ISSUE DATE NOTES

Pages 16 and 17, Ordering Procedure, removed all instances of Black trim; Page 17, Valve Trim Acces-
sories sub-section, updated Waterflow Pressure Alarm Switch nomenclature, PS10-2 (America) part
08-23
number to 25710, previously 25720, removed PS10-2 and PS10-1 model numbers from APAC and EMEA
descriptions, expanded part numbers for EMEA to included 0260 OR 100101, formerly just 0260.
Page 10, Figure 6 (2 of 2), Item A2, Waterflow Pressure Alarm Switch, Single Contacts (EMEA), added
05-23
alternate P/N 100101.
Page 1, updated QR code and URL; Page 10, Figure 6 (2 of 2), Item A2, updated Waterflow Pressure
Alarm Switch part numbers and regional applicability; Page 11, Figure 7, updated dimensions; Page
01-23 18, changed corporate address and telephone number to 1467 Elmwood Avenue, Cranston, RI 02910 |
Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-
362-0700; Incorporated Appendix A into document, including print instructions.
Page 1, added QR code and URL to allow convenient access to electronic version from printed docu-
06-22 ment; Page 15, Table B, updated Diaphragm Chamber Cover Bolt minimum torque specifications for all
valve sizes. Separate Appendix A also updated to reflect TFP1421 issue date.
06-21 Added metric 165,1 mm size. Separate Appendix A also updated to reflect TFP1421 issue date.
Update dimension H values (inlet of butterfly valve or welded tee to DV-5A valve inlet). Separate Appen-
03-21
dix A is also updated to reflect TFP1421 issue date.
Corrected Valve Setting Procedure, Supervisory Air Supply Valve item reference letter changed from R
12-20
to S to correspond with Figure 8. Separate Appendix A is also updated to reflect TFP1421 issue date.
New Technical Data Sheet TFP1421 describes DV-5A Automatic Water Control Valve with Preaction
Fire Protection System Single-Interlock Electric Actuation Trim, formerly described in now-obsolete
05-20
technical data sheet TFP1425. Separate Appendix A operation and setting procedure poster issued in
conjunction with TFP1421.

1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220


© 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.