TFP1421 08 2023
TFP1421 08 2023
www.tyco-fire.com
Contacts
Description
(32,7) (52,6) (92,5) (165,6)
1
1
3
2
7 5
5 3 1-1/2 AND 2 INCH
9 VALVES ONLY
6
3
7 1
4
8
6
4
9 7 5
6 AND 8 INCH
1 2
VALVES ONLY
FIGURE 1
DV-5 a VALVE ASSEMBLY AND REPLACEMENT PARTS
TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP1421
Page 3 of 18
VALVE SYSTEM
WATERWAY AIR
DIAPHRAGM SUPPLY
SEAT
VALVE
WATERWAY ALARM PORT
DIAPHRAGM WATERFLOW
CHAMBER TO ALARM
DIAPHRAGM
CHAMBER
OPEN TO
AUTOMATIC ATMOSPHERE
DRAIN VALVE AUTOMATIC
OPEN TO DRAIN VALVE
DIAPHRAGM
DIAPHRAGM ATMOSPHERE CLOSED
RETRACTS
CHAMBER
OPENING
SUPPLY
VALVE
FROM
WATERWAY
UPSTREAM WATER SUPPLY
SIDE OF PRESSURE &
SHUT-OFF ALARM TEST
VALVE
WATER SUPPLY WATERFLOW FROM WATER SUPPLY
FIGURE 2A FIGURE 2B
SET CONDITION OPERATED CONDITION
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE DIAPHRAGM
WATERWAY AUTOMATICALLY
SYSTEM FLEXES TO SYSTEM
DRAIN ITS SEATED DRAIN
DIAPHRAGM OPEN OPEN
CHAMBER POSTION
OPEN TO
ATMOSPHERE
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
MAIN SIDE OF MAIN
DRAIN SHUT-OFF DRAIN
OPEN VALVE CLOSED
WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF
FIGURE 2C FIGURE 2D
SYSTEM DRAIN CONDITION RESIDUAL DRAIN CONDITION
FIGURE 2
DV-5 a VALVE OPERATION, PREACTION SYSTEMS
TFP1421
Page 4 of 18
DIMENSIONS SHOWN
ARE APPLICABLE TO
Typically, the system designer selects
the detection components for a single Technical
ALL END CONNECTION
CONFIGURATIONS
interlock preaction system that will
respond to a fire sooner than the auto- Data
AVAILABLE PER matic sprinklers. Consequently, the Approvals
VALVE SIZE system will experience a minimal delay UL and C-UL Listed
in water delivery over that for a wet pipe LPCB Approved
sprinkler system because the system FM Approved
will have essentially filled with water Listing and Approvals are based on DV-5a
10-3/16" before a sprinkler operates. The DV-5a Single Interlock Preaction Electric Actua-
(260 mm) Single Interlock Preaction Electric tion Valve being trimmed as described in
Actuation Valve automatically super- Figure 5.
vises the integrity of the overall system. DV-5A Valve
1-1/2 Inch (DN40) Supervision is provided by monitoring a Components for the 1 1/2 in. to 8 in. (DN40
relatively low air pressure in the system to DN200) DV-5a Valve are shown in Figure 1.
via a low pressure alarm switch so as The DV-5a Valve is for vertical installations.
to detect leaks in the system that oth- It is rated for use at service pressures of 20
to 300 psi (1,4 to 20,7 bar).
erwise would result in unwanted water
10-3/16" discharge should the system operate in The take-out dimensions are shown in
a fire condition. Figure 3, and flanged connections are
(260 mm) available drilled per ANSI, ISO, AS, and JIS
Supervised single interlock preac- specifications (see Table A). Threaded inlet
tion systems are generally used to and outlet connections are available in NPT
protect areas where there is danger or ISO 7-1. Threaded port connections are
2 Inch (DN50) NPT threaded.
of serious water damage that might
result from damaged automatic sprin- Note: PN16 flanges are pressure rated to
klers or piping. Typically, such areas 16 bar.
include computer rooms, storage Valve Trim
areas for valuable artifacts, libraries, The maximum pressure rating for the single
13-3/4" and archives. interlock preaction electric actuation is
(349 mm) dependent on the separately ordered
Single interlock preaction systems are solenoid valve per Technical Data Sheet
also effectively used to protect proper- TFP2180.
ties where a pre-alarm of a possible fire When the system pressure is greater than
3 Inch (DN80) condition may allow time for fire extin- 175 psi (12,1 bar), provision is to be made
guishment by alternate suppression to replace the standard order 300 psi (20,7
means, prior to a sprinkler discharge. bar) water pressure gauges with separately
In the event the fire cannot otherwise ordered 600 psi (41,4 bar) water pressure
gauges.
be extinguished, the preaction sprinkler
system will then perform as the primary If the addition of an alarm control valve is
16-3/4" fire protection system. desired or required by the local AHJ, the
(425 mm) alarm control valve noted as Item H in Figure
8 is to be a separately ordered electronically
NOTICE supervised normally open valve.
The DV-5a Single Interlock Preaction External trim connections are NPT threaded.
Electric Actuation Valve described EMEA trim is provided with NPT x ISO 7-1
4 Inch (DN100) thread adapters.
herein must be installed and main-
tained in compliance with this docu- Pressure Loss
ment, as well as with the applicable See Graph A
standards of the NATIONAL FIRE PRO- Detection System
TECTION ASSOCIATION (NFPA), in See the Electric Actuation subsection
addition to the standards of any other
22-3/8" authorities having jurisdiction. Failure System Air Pressure Requirements
(569 mm) to do so may impair the performance The supervisory air (nitrogen) pressure is to
of these devices. be 10 ± 2 psi (0,69 ±0,07 bar). The use of
a higher supervisory pressure is subject to
The owner is responsible for main- approval by the authority having jurisdiction,
6 Inch (DN150) and it should be understood that the use of
taining their fire protection system
a higher supervisory pressure may increase
and devices in proper operating con- water delivery time. The use of a lower
dition. Contact the installing contrac- supervisory pressure may prevent clearing
tor or product manufacturer with any the alarm of the supervisory low pressure
questions. switch (Item T - Figure 8), which is factory
set to alarm at 5 ± 1 psi (0,34 ± 0,07 bar) on
decreasing pressure. The supervisory air
27-7/16" supply pressure of 10 ± 2 psi (0,69 ± 0,07
(697 mm) bar) can be provided by any of the following
methods. Refer to the applicable data sheet
for laboratory approval information.
• Model G16AC812 (self contained)
8 Inch (DN200) Automatic Supervisory Air Supply
described in Technical Data Sheet
FIGURE 3 TFP1620.
DV-5 a VALVE
TAKE-OUT DIMENSIONS
TFP1421
Page 5 of 18
6.0 0,400
5.0
0,300
)
40
4.0
DN
H(
)
3.0 50
0,200
2I
DN
/
1-1
H(
DN
2I
2.0
H(
0)
NC
10
mm
DN
3I
0,100
5,1
H( 0,090
NC
16
0,080
4I
0),
15
0)
1.0 0,070
20
DN
0.9
DN
0,060
0.8 H(
H(
NC
0,050
NC
0.7
6I
8I
0.6 0,040
0.5
0,030
0.4
0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5 a VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the Materials of Common Hardware Trim
• Common hardware pipe fittings are
Model AMD-1 Air Maintenance Device
described in Technical Data Sheet Construction galvanized or black as required and
are malleable per ASME B16.3.
TFP1221.
Valve Body • Common hardware pipe nipples are
• A maximum 3000 psi (206,9 bar) Epoxy coated ductile iron per ASTM galvanized or black as required and
nitrogen cylinder in combination A536-77, Grade 65-45-12 are Schedule 40 per ASTM A53 or
with the Model AMD-3 Nitrogen
Diaphragm Cover A135.
Maintenance Device described in
Technical Data Sheet TFP1241. Epoxy coated ductile iron per ASTM • Common hardware compression
Note: The dew point of the air or nitrogen A536-77, Grade 65-45-12 fittings are brass per ASTM B16.
supply for a system exposed to freezing con- Diaphragm • Common hardware tubing is Type L
ditions must be maintained below the lowest
ambient temperature to which the system Polyester fabric reinforced, TEFLON copper per ASTM B88.
piping will be exposed. Introduction of mois- coated, EPDM rubber per ASTM D2000
ture into the system piping can create ice
build-up that could prevent proper operation Diaphragm Cover Fasteners
of the system. Aluminum zinc coated steel
The supervisory low pressure switch (Item
T - Figure 8) is factory set at 5 ± 1 psi (0,34 ±
0,07 bar) on decreasing pressure. The pres-
sure relief valve (Item S - Figure 8) is factory
set to fully open at 25 ± 2 psi (1,72 ± 0,14 bar)
and it begins to crack open at a pressure of
about 18 psi (1,24 bar).
TFP1421
Page 6 of 18
SUPERVISORY
LOCAL
LOW PRESSURE RESTRICTION DRAIN MANUAL
ALARM SWITCH DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
SYSTEM AIR CHAMBER SUPPLY (NORMALLY
PRESSURE CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
GAUGE (NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 4
DV-5 a VALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION SCHEMATIC DIAGRAM
A2
C5 L
D
C
C3
F
P4 E
P7
A2
A
P5
C2 C4 P6
C7 A6
H P3 A1
J
B
P1 C6
P2
G
A4
K
A3
A4 C1
A5
1-1/2" (DN40) AND 2" (DN50) Assemble in order
VALVES ONLY from A to L
A7
A9
A8
Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Trim" or pre-assembled "DV-5A Valve with Galvanized Trim and Butterfly Valve", Items A1
through A9 are provided, as applicably related to valve size, and Item A6 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180.
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A9 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.
FIGURE 5
DV-5a VALVES WITH SINGLE INTERLOCK PREACTION
ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED
TFP1421
Page 9 of 18
A2
39 27
28 36
C5
26 51 27
52 57
21
22 1
42 41 47 34
17
P4 30
P7 49 A6
36
20 29 10
A2 P5 55 36
8
36
C4 14
13 4 36
C2 31
P6 54 20 24 6
32
53 16 C3
44 A1 33 43 39
P3
23 15 40
32 C7 29
P1
P2 C6 Notes:
48 12 1. Port Connections P1 through
59 3
19 50 A4 37 P7 are described in Figure 2.
24 58 2. External Trim Connections C1
38 5 46 through C5 are
56
31 A3 11 56 described in Figure 8.
35 37 18 3. When ordering pre-assembled
"DV-5A Valve with Galvanized
25 2 Trim" or pre-assembled "DV-
27 1 21 9 5A Valve with Galvanized Trim
37 27 and Butterfly Valve", Items
7 45
19 17 A1 through A9 are provided,
37 as applicably related to valve
A4 size, and Item A7 is provided
C1 7 as P/N 52-287-1-124 described
A5 in Technical Data Sheet
TFP2180.
A9 4. When ordering DV-5A Trim
A7 A8
separately from the DV-5A
Valve, Items A1 through A9
1-1/2" (DN40) AND 2" (DN50) are separately ordered, as ap-
VALVES ONLY plicably related to valve size.
Water Pressure Gauges for
EMEA valve trim are also
separately ordered.
ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) b 8 IN. (DN200)
1 2 1/4” GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 1 1/4” PRESSURE RELIEF VALVE, 25 PSI 923431019 923431019 923431019 923431019 923431019 923431019
7 2 1/2” BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
8 1 1/2” GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
9 1 1/2” SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
10 1 1/2” SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
11 1 1/2” Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4” ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
15 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 2 COMP. FITTING 90° 1/2” MNPT x 1/2” OD TUBE ✓ — — — — — —
18 1 COMP. FITTING 90° 1/2” FNPT x 1/2” OD TUBE ✓ — — — — — —
19 2 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4” NPT x 3/4” TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2 PIPE PLUG ✓ 1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
22 1 PIPE PLUG ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
FIGURE 6 (1 OF 2)
DV-5a VALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1421
Page 10 of 18
ITEM QTY DESCRIPTION CH 1 1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) b 8 IN. (DN200)
23 1 PIPE PLUG ✓ 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
24 2 UNION ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
25 1 STREET ELBOW ✓ 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90°
26 1 ELBOW ✓ 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45°
27 4 ELBOW ✓ 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90°
28 1 CROSS ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
29 2 TEE ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
30 1 REDUCING TEE ✓ 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2”
31 2 REDUCING TEE ✓ 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4”
32 2 REDUCING TEE ✓ 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4”
33 1 REDUCING TEE ✓ 3/4” x 3/4” x 3/4” 3/4” x 3/4” x 3/4” 1 1/4” x 1 1/4” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4”
34 1 PIPE NIPPLE ✓ 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE
35 1 PIPE NIPPLE ✓ 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2”
36 4 PIPE NIPPLE ✓ 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE
37 4 PIPE NIPPLE ✓ 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2”
38 1 PIPE NIPPLE ✓ 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2”
39 2 PIPE NIPPLE ✓ 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2”
40 1 PIPE NIPPLE ✓ 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2”
41 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5”
42 1 PIPE NIPPLE ✓ 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2”
43 1 PIPE NIPPLE ✓ 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2”
44 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2”
45 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
46 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
47 1 TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
48 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
49 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
50 1 PIPE NIPPLE ✓ 1/2” x 3 1/2” 1/2” x 3 1/2” 1/2” x 4 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 3/4”
51 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 1/2”
52 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 4 1/2” 1/2” x 5” 1/2” x 7 1/2” 1/2” x 9 1/2”
53 1 PIPE NIPPLE ✓ 3/4” x 5” 3/4” x 5” 3/4” x 6” 3/4” x 7” 3/4” x 9” 3/4” x 11 1/2”
54 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 1 1/4” x 3 1/4” 2” x 3” 2” x 3” 2” x 3”
55 1 PIPE NIPPLE ✓ 3/4” x 6 1/2” 3/4” x 6 1/2” 1 1/4” x 5 1/2” 2” x 5” 2” x 6” 2” x 8”
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
56
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
AIR PRESSURE GAUGE, 80 PSI / 550 kPa
57 1 923431012 923431012 923431012 923431012 923431012 923431012
RETARDED TO 250PSI / 1750 kPa
58 1 LABEL 545003005 545003005 545003005 545003005 545003005 545003005
59 1 LABEL WIRE — — — — — —
A1 1 DV-5A VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102 25710 or 100102
DOUBLE CONTACTS (APAC)
WATERFLOW PRESSURE ALARM SWITCH,
A2 1 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101 0260 or 100101
SINGLE CONTACTS (EMEA)
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
DOUBLE CONTACTS (AMER)
1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A3
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A4
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A5 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
A6 1 SOLENOID VALVE NORMALLY CLOSED REFER TO TFP2180
A7 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A8 1 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A9 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
NOTES
a. Not VdS Approved.
b. Also applicable to metric 165,1 mm size.
CH - Common Hardware - See Materials of Construction section for specifications.
FIGURE 6 (2 OF 2)
DV-5 a VALVES — SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1421
Page 11 of 18
Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1 1/2 2.8 9.7 9.8 15.7 16.0 7.4 10.2 8.02 1.2
(40) (71) (246) (249) (399) (406) (188) (259) (204) (31)
2 2.8 9.7 9.8 15.7 16.0 7.4 10.2 8.09 2.9
(50) (71) (246) (249) (399) (406) (188) (259) (205) (74)
3 4.0 10.7 11.5 16.3 18.4 6.2 13.8 3.79 3.6
(80) (102) (272) (292) (414) (467) (158) (351) (96) (91)
4 4.5 11.9 12.6 16.5 21.0 5.5 16.8 4.54 4.3
(100) (114) (302) (320) (419) (533) (140) (427) (115) (109)
63 5.7 13.4 14.5 18.4 24.8 3.8 22.4 5.83 5.7
(150) (145) (340) (368) (467) (630) (97) (569) (148) (145)
8 6.8 16.1 16.7 19.5 29.2 3.3 27.5 5.24 6.7
(200) (174) (409) (424) (495) (742) (84) (699) (133) (170)
NOTES:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.
3. Also applicable to metric 165,1 mm size.
J B C D
A
H F
FIGURE 7
DV-5 a VALVE
SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION TRIM
NOMINAL DIMENSIONS
TFP1421
Page 12 of 18
C5
L
LOCATION
FOR OPTIONAL
ELECTRICALLY
SUPERVISED
C N.O. ALARM
CONTROL P4
P7 V
VALVE
F
S
P5
C2 T
C4
D
P6
H A C3
P3
P1 C7 M
P2 C6
E
J K
B
Q
G
P
C1
R
Note:
Port Connections P1 through P7 are described in Figure 2.
FIGURE 8
DV-5 a VALVE - SINGLE INTERLOCK PREACTION ELECTRIC ACTUATION
(See Figure 6 for specific Bills of Materials)
TFP1421
Page 14 of 18
Procedure
1 1/2 in. (DN40) ����������������������������������� 550111315
specifications. 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550111320
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550111330
The TYCO DV-5a Automatic Water Specify: Size (specify), DV-5 a Auto- 4 in. (DN100) ��������������������������������������� 550111340
Control Valves may be ordered as matic Water Control Valve, (specify) 6 in. (DN150) ��������������������������������������� 550111360
follows: end connection, P/N (specify): 165,1 mm . . . . . . . . . . . . . . . . . . . . . . . 550111366
8 in. (DN200) ��������������������������������������� 550111380
Groove x Groove
Pre-Assembled Valves 1 1/2 in. (DN40) ���������������������������������� 530010015 Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550121330
with Trim 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030 4 in. (DN100) ���������������������������������������550121340
DV-5A Valves with Galvanized Trim 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 6 in. (DN150) ���������������������������������������550121360
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060 8 in. (DN200) ���������������������������������������550121380
and Butterfly Valve
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
Specify: Size (specify), DV-5 a Auto- Flange x Groove ANSI
matic Water Control Valve, G x G con- Flange x Flange ANSI 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550131330
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 4 in. (DN100) ���������������������������������������550131340
nections with assembled galvanized 6 in. (DN150) ���������������������������������������550131360
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
Americas Single Interlock Preaction 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 8 in. (DN200) ���������������������������������������550131380
Electric Actuation Trim, complete with 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Flange ISO
assembled Model BFV-300 Butterfly 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550141330
Flange x Grove ANSI
Valve, P/N (specify): 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030 4 in. (DN100) ���������������������������������������550141340
Groove x Groove 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040 6 in. (DN150) ���������������������������������������550141360
1 1/2 in. (DN40) ����������������������������������� 551011315 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060 8 in. (DN200) ���������������������������������������550141380
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 551011320 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080 Flange x Groove ISO
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 551011330 T x T NPT 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550151330
4 in. (DN100) ��������������������������������������� 551011340 1 1/2 in. (DN40) ���������������������������������� 530060015 4 in. (DN100) ���������������������������������������550151340
6 in. (DN150) ��������������������������������������� 551011360 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 6 in. (DN150) ���������������������������������������550151360
8 in. (DN200) ��������������������������������������� 551011380 8 in. (DN200) ���������������������������������������550151380
Notes:
Notes: Valves are typically provided with flange
T x T ISO
AMERICAS DV-5A Valve with Trim and 1 1/2 in. (DN40) ����������������������������������� 550171315
drilling per ANSI B16.1 (Class 125) or ISO 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550171320
Butterfly Valve: Americas pressure (7005-2 PN16).
switches, P/N 52-287-1-124 solenoid valve, Notes:
and psi/kPa water pressure gauges are Upon request, valves can be provided with Pressure switches, P/N 52-287-1-124
provided. flange drilling per JIS B 2210 or AS 2129. In solenoid valve, bar/psi water pressure
which case part numbers are not assigned. gauges, and NPT to ISO threaded trim
This arrangement is available for EMEA
and APAC upon request. Contact your DV-5A Valve Trim adaptors for external connections are
local distributor. Specify: Size (specify), finish (specify), provided.
Electric Actuation Trim for DV-5a Auto- Separate DV-5A Valves without Trim
AMERICAS matic Water Control Valves used in See Table A for flange drilling
DV-5A Valves with Galvanized Trim Single Interlock Preaction Fire Protec- specifications.
Specify: Size (specify), DV-5 a Auto- tion System, P/N (specify):
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, (specify) Galvanized matic Water Control Valve, (specify)
end connection with assembled gal- 1 1/2 in. (DN40) ���������������������������������� 540001320
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001320 end connection, P/N (specify):
vanized Americas Single Interlock 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001330 Groove x Groove
Preaction Electric Actuation Trim, P/N 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001340 1 1/2 in. (DN40) ���������������������������������� 530010015
(specify): 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001360 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
Groove x Groove 8 in. (DN200) �������������������������������������� 540001380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
1 1/2 in. (DN40) ����������������������������������� 550011315 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040
Note: 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011320
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011330
Pressure switches and/or solenoid valves 165,1 mm . . . . . . . . . . . . . . . . . . . . . . 530010066
4 in. (DN100) ���������������������������������������550011340 for electric actuation are separately 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
6 in. (DN150) ���������������������������������������550011360 ordered. Flange x Flange ANSI
8 in. (DN200) ���������������������������������������550011380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030
Flange x Flange ANSI 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021330 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021340 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021360 Flange x Grove ANSI
8 in. (DN200) �������������������������������������� 550021380 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080
TFP1421
Page 17 of 18
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
Worldwide
www.tyco-fire.com
Contacts
DV-5A Appendix A
Poster Printing
Instructions
General W
Description
The appendix found at the end of this
document provides valve setting and
Valve Setting Procedure 7. Pressure will then build up in DV-5A Diaphragm Chamber.
1. Close System Main Control Valve (B), Diaphragm Supply Valve (P), and Air Supply Control 8. After system pressure is restored, inspect Solenoid Valve (R) and Manual Reset Actuator
Valves (X) and (Y). (N) for leaks. Any leaks must be corrected before proceeding.
2. Open Main Drain Valve (D), System Drain Valve (E), and all auxiliary drains in system. Also,
Summary Instructions
4. Depress plunger of Automatic Drain Valve (F) to verify it is open. Valve in service and open System Main Control Valve (B).
5. Clean Diaphragm Supply Strainer (Q). Flush strainer by opening the Diaphragm Supply Supervisory Low Pressure Alarm Test Procedure and Validation of Normally Closed
DV-5A Automatic Water Control Valve Valve (P). Solenoid Valve (S)
section.
6. Replace operated automatic sprinklers on system piping. 1. Close System Main Control Valve (B), and open Main Drain Valve (D).
Preaction Type A Systems 7. Reset DV-5A Valve Releasing Panel in accordance with manufacturer instructions.
8. Re-establish system air pressure to reset Model DP-1 Dry Pilot Actuator (T) by opening Air
2. Crack open system’s Inspector’s Test Connection to relieve air pressure from system.
Verify Supervisory Low Pressure Alarm Switch (V) is operational and low pressure set point
(EN12845 Compliance) Supply Control Valve (X). Do not open Air Supply Control Valve (Y) at this time. Observe Dry
Pilot Actuator (T) air pressure on Dry Pilot Gauge (Z).
is approximately 0,4 bar under minimum system air pressure.
3. Allow system air pressure to decay to 0 psig. Verify no water draining from Dry Pilot Actu-
9. Open Manual Control Station (M), then open Diaphragm Supply Valve (P). After aerated ator (T).
H
16. Open System Main Control Valve (B). 4. Verify DV-5A Valve has tripped, as indicated by water flow into system.
17. After setting fire protection system, notify proper authorities and advise those responsible 5. Close System Main Control Valve (B).
D
W for monitoring proprietary and/or central station alarms. 6. Close Diaphragm Supply Valve (P) and Air Supply Control Valves (X) and (Y).
H A
Waterflow Alarm Test Procedure 7. Reset DV-5A Valve with Preaction Type A Trim in accordance with Valve Setting Procedure.
M 1. Open Alarm Test Valve (G), allowing water to flow to Waterflow Pressure Switch (C) and/or
AUGUST 2022 docs.jci.com/tycofire/tfp1485 stops flowing from drain tube. © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision date and are subject to change without notice.
Actuation Fire Protection Systems 9. After aerated water stops discharging, reset the manual reset actuator (N) until pressure
9. Pressure will then build up in DV-5a diaphragm chamber.
10. After system pressure is restored, inspect solenoid valve (V) and manual reset actuator
reaches approximately 15 psi (1,0 bar) on the diaphragm gauge (K) and water stops flowing (N) for leaks at drain tube. Any leaks must be corrected before proceeding.
NOTICE from its drain tube. 11. Partially open system main control valve (B). Slowly close main drain valve (D) as soon
10. With the diaphragm chamber pressurized, temporarily close diaphragm supply valve as water discharges from main drain valve (D). Observe automatic drain valve (F) for leaks. If
The procedures provided are summary instructions of the complete procedures appearing in (P), and observe diaphragm gauge (K) for a drop in pressure. If a pressure drop is noted,
Technical Data Sheet TFP1421. If problems occur, consult full document. there are leaks, correct the leakage problem. If there are no leaks, the DV-5a valve is ready to
replace DV-5A diaphragm and correct any leaks before proceeding. be placed in service and system main control valve (B) must then be fully opened.
11. If diaphragm gauge (K) indicates no drop in pressure, re-open the diaphragm supply
U Internal Valve Inspection
valve (P) and proceed.
1. Ensure diaphragm supply valve (P) is closed prior to closing inverted flare shut-off valve
12. Open supervisory air supply valve (S) to reestablish supervisory system air pressure at (R). Close inverted flare shut-off valve (R).
nominally 10 psi (0,68 bar).
L
2. Remove copper tube fitting between diaphragm supply valve (P) and inverted flare shut-
13. Partially open system main control valve (B). Slowly close main drain valve (D) when water off valve (R).
discharges from main drain valve (D). Observe automatic drain valve (F) for leaks. If there are
3. Loosen union securing actuation trim and remove actuation trim.
leaks, correct the leakage problem before proceeding.
4. Remove union between diaphragm cover and MRA-1 manual reset actuator (N). Remove
C 14. When system main control valve (B) is partially opened, the pressure on DV-5a diaphragm
chamber may increase. If pressure is greater than valve trim maximum pressure, relieve pres- MRA-1 manual reset actuator (N) subassembly.
V
F
S sure to at least valve trim pressure rating. Do not allow pressure to drop below supply pres- 5. Remove diaphragm valve cover hardware, slowly remove diaphragm cover and perform
T sure shown on water supply gauge (J) which may result in tripping of DV-5a valve. internal valve inspection. Clean valve interior and replace parts as necessary.
15. Close hinged cover of manual control station (M). Insert a new break rod in the small hole 6. Ensure diaphragm is properly oriented and proper hardware arrangement is utilized.
D
through the top of the enclosing box. 7. Insert long hex bolts. Align diaphragm with valve body, and then align diaphragm cover
16. Open system main control valve (B). with valve body. Insert short hex bolts. Hand-tighten all fasteners.
H A
17. After setting fire protection system, notify proper authorities and advise those responsible 8. Using crossdraw sequence, wrench-tighten long hex bolts and short hex bolts. Repeat
M
for monitoring proprietary and/or central station alarms. crossdraw sequence two to three times at incremental torque valves.
E 9. Inspect to assure all hex bolts are securely tightened.
Drop in Water Supply Pressure Below Normal Range
1. Note water supply pressure by the diaphragm gauge (K) and determine if the pressure is 10. Using the union, secure the MRA-1 manual reset actuator (N) to the diaphragm cover.
J
B
K within normally expected range. 11. Using union, secure actuation trim.
N 2. If below normal range, correct any leakage from diaphragm chamber prior to resetting the 12. Replace copper tube fitting between diaphragm supply valve (P) and inverted flare shut-
system. off valve (R).
Q 3. When water supply pressure is restored, reset DV-5a valve in accordance with the Valve 13. Ensure unions and flare fittings are securely tightened.
G
Setting Procedure. 14. With diaphragm supply valve (P) closed, fully open inverted flare shut-off valve (R) stain-
P
Waterflow Alarm Test Procedure less steel screw (approximately 1/2 in.) until resistance is met.
R
1. Open alarm test valve (G), allowing water to flow to waterflow pressure switch (C) and/or 15. Proceed with Valve Setting Procedures.
water motor alarm. Close the alarm test valve (G) when test is completed.
2. Depress plunger on automatic drain valve (F) to drain alarm line.
Electric Actuation Operation Test Procedure
Item Description Item Description 1. To prevent water from flowing beyond the riser, close system main control valve (B) and
open main drain valve (D).
A DV-5a Valve L System Gauge
B System Main Control Valve M Manual Control Station 2. Open system main control valve (B) one turn beyond position which water begins to flow
C Waterflow Pressure Switch N Manual Reset Actuator from main drain valve (D). Slowly close main drain valve (D).
D Main Drain Valve P Diaphragm Supply Valve 3. Test deluge releasing panel in accordance with manufacturer’s instructions to energize
E System Drain Valve Q Diaphragm Supply Strainer solenoid valve (V).
F Automatic Drain Valve R Inverted Flare Shut-Off Valve
G Alarm Test Valve S Supervisory Air Supply Valve 4. Verify DV-5a valve has tripped, indicated by flow of water into system.
H Alarm Control Valve (Optional) T Supervisory Air Pressure Relief Valve 5. Close system main control valve (B).
J Water Supply Gauge U Supervisory Low Pressure Switch
K Diaphragm Gauge V Solenoid Valve 6. Close diaphragm supply valve (P).
7. Reset DV-5a valve in accordance with the Valve Setting Procedure.
TFP1421
Change History Appendix
Pages 16 and 17, Ordering Procedure, removed all instances of Black trim; Page 17, Valve Trim Acces-
sories sub-section, updated Waterflow Pressure Alarm Switch nomenclature, PS10-2 (America) part
08-23
number to 25710, previously 25720, removed PS10-2 and PS10-1 model numbers from APAC and EMEA
descriptions, expanded part numbers for EMEA to included 0260 OR 100101, formerly just 0260.
Page 10, Figure 6 (2 of 2), Item A2, Waterflow Pressure Alarm Switch, Single Contacts (EMEA), added
05-23
alternate P/N 100101.
Page 1, updated QR code and URL; Page 10, Figure 6 (2 of 2), Item A2, updated Waterflow Pressure
Alarm Switch part numbers and regional applicability; Page 11, Figure 7, updated dimensions; Page
01-23 18, changed corporate address and telephone number to 1467 Elmwood Avenue, Cranston, RI 02910 |
Telephone +1-401-781-8220, formerly 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-
362-0700; Incorporated Appendix A into document, including print instructions.
Page 1, added QR code and URL to allow convenient access to electronic version from printed docu-
06-22 ment; Page 15, Table B, updated Diaphragm Chamber Cover Bolt minimum torque specifications for all
valve sizes. Separate Appendix A also updated to reflect TFP1421 issue date.
06-21 Added metric 165,1 mm size. Separate Appendix A also updated to reflect TFP1421 issue date.
Update dimension H values (inlet of butterfly valve or welded tee to DV-5A valve inlet). Separate Appen-
03-21
dix A is also updated to reflect TFP1421 issue date.
Corrected Valve Setting Procedure, Supervisory Air Supply Valve item reference letter changed from R
12-20
to S to correspond with Figure 8. Separate Appendix A is also updated to reflect TFP1421 issue date.
New Technical Data Sheet TFP1421 describes DV-5A Automatic Water Control Valve with Preaction
Fire Protection System Single-Interlock Electric Actuation Trim, formerly described in now-obsolete
05-20
technical data sheet TFP1425. Separate Appendix A operation and setting procedure poster issued in
conjunction with TFP1421.