SP & SSP
SP & SSP
1 2 3 4 PERFORATED NOTES:
1.ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS UNLESS OTHERWISE
COVER SLAB ONE LAYER OF MENTIONED.
3580 3565 3565 2.THE FGL (FINISHED GROUND LEVEL) AT THE BUILDING LOCATION IS ASSUMED AS 0.0 m LVL.
INLET PIPE 40mm METAL
F.G.L 3.ALL PLAIN AND REINFORCED CONCRETE WORK TO BE CONFORMED TO IS 456:200 CODE OF
PRACTICE.
RISE-150 MM BRICK ON EDGE
350 250
4.ALL EXTERNAL WALLS ARE 230 THK. BRICK WALL WITH CM (1:6) U.N.O.
ALL INTERNAL WALLS ARE 115 THK. BRICK WALL WITH CM (1:4) U.N.O.
THREAD-300 MM ALROUND
5.GRADE OF CONCRETE FOR RCC-M25 WITH 20MM GRADE STONE AGGREGATE AND FOR
PCC-1:2:4 WITH 20MM GRADE STONE AGGREGATE.
RWP
RWP
FINE SAND 6.DAMP PROOF COURSE : 40MM THK. P.C.C. 1:2:4 TO BE PROVIDED WITH TWO COATS OF
W W W BITUMEN OVER IT IN BETWEEN BRICK WALL AND PLINTH BEAM.
7.PLASTERING AND SURFACE TREATMENT:
A
2000
500
i)PLASTER: 15-19 MM THK. IN CM 1:4 ON ALL OUTER AND INNER WALLS. INNER WALLS AND
20mm METAL STONE
200 600 250 850 200 50 600 800 50 800 200 UNDERSIDE OF SLABS SHALL BE FINALLY FINISHED WITH POP.
200
BATTERY
BATTERY
600 670 REAR REAR ii)INTERIOR FINISH: TWO COATS OF 1ST QUALITY OIL BOUND DISTEMPER OF APPROVED
TELECOM
BATT.
BATT.
CHARG.
CHARG.
VRLA
SMPS 1
VRLA
RACK
600
600
SHADE OVER POP COATING. 3RD COAT SHALL BE DONE BEFORE HANDING OVER TO ASSETS.
624
SMPS 2
1220
200 iii)EXTERIOR FINISH: TWO COATS OF 1ST QUALITY CEMENT PAINT OVER POP COATING. 3RD
COAT SHALL BE DONE BEFORE HANDING OVER TO ASSETS.
900
FRONT FRONT
800
BATTERY BANK-1
S&T EQUIPMENT
40mm METAL STONE 8.FLOORING:
i)BATTERY ROOM: ACID PROOF TILES CONFORMING TO IS 4457-1967, OVER 20MM CM 1:4,
2148
1100
BATTERY ROOM
OVER 10MM THK. CC 1:4:8. ACID PROOF TILES ALSO TO BE PROVIDED IN DADO AS PER
DETAIL-'A'
EQUIPMENT ROOM
FRONT
4000 x 3350
3 2 1 REQUIREMENT UPTO 1M. HEIGHT.
610
1575
4000 x 6900
ii)RELAY ROOM,IPS ROOM AND OTHER S& T STRUCTURES : 1ST QUALITY (600X600)MM
VITRIFIED FLOOR TILES CONFIRMING TO IS 13630-1993 LAID OVER 20MM THK. CM 1:4 OVER
SECTION X-X
2350
4230
4000
CORRIDOR 100MM THK. CC 1:4:8.
800
500
9.ROOF SLAB SHALL BE FINISHED WITH CEMENT PLASTER TO A SLOPE OF 1 IN 200 USING
2900
760
CRP
649 SCALE 1:100 WATER PROOFING COMPOUND.
FRONT 800 10.PAINTING: TWO COATS OF SYNTHETIC ENAMEL PAINT OF 1ST QUALITY OVER A PRIMING
COAT OF APPROVED QUALITY ON ALL EXPOSED STEEL AND WOODEN SURFACES.
800
500
800
700
RTU
11.DOORS AND WINDOWS:
610
115
2150 216 764 i)30MM THK. FLUSH DOOR SHUTTER TO BE CONNECTED TO MS TEE 40MMX40MMX6MM DOOR
REAR REAR FRAMES
1000 1000
700
FRONT C.I. GRATING
ii)WINDOWS/VENTILATORS:STEEL WINDOWS OF STANDARD ROLLED STEEL SECTIONS, GLASS
650
PANES 4MM THK. WITH GLAZING CLIPS AND SPECIAL METAL SASH PUTTY.
700
BATTERY BANK-2 500
AFL
800
F.F.L SLOPE
iii)WINDOWS IN RELAY ROOM SHALL BE MIX OF DOUBLE SHUTTERS/FIXED PANES. RDSO TYPE
800
FRONT FLOW
300
FRONT REAR VENTILATORS FOR CIRCULATION OF AIR TO BE PROVIDED AS PER DRAWING.
199 DCDB ACDB 100 100 75 12.STAINLESS STEEL/ SINKS TO BE PROVIDED IN BATTERY ROOM WITH WATER TAP
B 220
100
50
SLAB
CONNECTION .
600 230
W W BRICK WALL LEGEND:-
FGL - FINISHED GROUND LEVEL
3 DETAILS OF TYPICAL SUNSHADE 3000 FFL - FINISHED FLOOR LEVEL
AT 2.550 m LVL DETAILS OF KHURRA RWP - RAIN WATER PIPE
2 SCALE: 1:10 SCALE 1:25 X X RTL - ROOF TOP LEVEL
3000
AROUND THE
BUILDING 115 DPC - DAMP PROOF COURSE
WALL PL - PLINTH LEVEL
115 NGL - NATURAL GROUND LEVEL
FFL
TYP. - TYPICAL
1000
1150 115 THK. CLASS I TOS - TOP OF SLAB
450 75 100 PB
INLET PIPE
BRICK WALL (CM- 1:4)
WATER PROOFING COURSE
F.G.L. LAID TO SLOPE
100 SAND
WALL TYP PLAN OF PIT
SCHEDULE OF DOORS&WINDOWS
GROUND FLOOR PLAN 100 THK.
PCC (1:4:8)
PCC
TERRACE T.O.S.
SCALE 1:100
DOORS
WINDOWS
1300X2500
1600X230X1500
PARAPET DETAIL
TYP.PLINTH PROTECTION DETAIL SCALE 1:25
SCALE 1:25
RCC SLAB
115 THK. WATER PROOFING
1 2 3 4 PARAPET WALL B COURSE LAID TO A 500 LITRE CAPACITY
(BRICK WALL) SLOPE (1:200) OVER HEAD WATER TANK
600
600
900
A SLOPE
600 R.T.L.+4.050
600
'v'
PE
SLO
PE
SLO
SLO
SLO
PE
SLO
PE
PE
SLO
3600
450 600
4230
5660
TANK
BATTERY ROOM
PVC R.W.P
115 THK.
450
PARAPET WALL
100 450
(TOP) FFL+0.450
450
B ACID PROOF TILES
600
20 THK. CM (1:4)
100 THK. PCC (1:4:8)
SECTION A-A
ROOF FLOOR PLAN SCALE 1:40 NOT FOR CONSTRUCTION
SCALE 1:75
NOTES:-
4302
RB3
RB6
RB4
RB5
C1/F1 C1/F1 C1/F1 C1/F1
B
RB2
B
1 2 3 4
3615 3565 3600
A
PB1
PLINTH LVL.
PB1
500
N.G.L.
4302
PB3
PB6
PB4
PB5
RCC. COL.
COLUMNS COLUMN SIZE
COL. REINF.
AS/DETAIL
C1 300X300
COLUMN TIES
PB2 AS PER SCHEDULE
2500
B FOUNDATION FOUNDATION SIZE
PLINTH BEAM (230X380 mm) F1 1900X1900X450
1 2 3 4
(TYP.)
500
300
3615 3565 3600 (TYP.)
A
PB1 75 1500
(TYP.)
75
PCC.(1:4:8)
SECTION A-A
(SCALE 1:25)
4302
PB3
PB6
PB4
PB5
PB2
B