Neutral Protection
Presentation
A long time overcurrent protection function is dedicated to the neutral protection.
Availability
Neutral protection is available on:
MicroLogic 2.0 X, 5.0 X, 6.0 X, and 7.0 X control units for IEC standard
MicroLogic 3.0 X, 5.0 X, and 6.0 X control units for UL standard
3-pole circuit breakers with the ENCT option (External Neutral Current Transformer) to measure
the neutral current
4-pole circuit breakers
Description
Where the cross-sectional area of the neutral conductor is at least equivalent to that of the phase
conductor, and the current in the neutral is expected not to exceed the value in the phase conductor, it
Pact Series MasterPact MTZ - for theneutral
conductor.
is not necessary to provide overcurrent protection
MicroLogic X Control Unit –
The
User
neutral
Guideconductor must have protection against overcurrent if:
The cross-sectional area of the neutral conductor is less than the cross-sectional area of the
phase conductors
Non-linear loads generating third order harmonics (or multiples thereof) are installed
It may be necessary to switch off the neutral for operational reasons (multiple source diagram) or
safety reasons (working with power off).
MicroLogic X control units are suitable for all protection types. They incorporate the oversized neutral
(OSN) function, which manages protection of the neutral conductor when third-order harmonic
currents (and multiples thereof) are present.
Operating Principle
Neutral protection has the same characteristics as phase protection:
On the MicroLogic X display screen, at Home > Configuration > Measures > System Type >
ENCT
With EcoStruxure Power Commission software
By sending a setting command using the communication network (password-protected).
The following table shows the setting values of the neutral long-time protection and threshold for the
type of neutral protection selected:
N Ir