Company Introduction
DTGen is the UK’s leading generator specialist. We supply, We are recognised industry expert in a variety
install and maintain diesel and gas generators across the of sectors including:
country, providing our customers with products and support • Health
throughout the lifecycle of their generator set. We are backed • Retail stores and distribution centres
by a global generator manufacturer with a wealth of experience • Data centres
in the power industry. • Rail
• Utilities
Whatever your power requirement, you can trust us to meet it. • Construction
warehouse space accommodates workshops, parts distribution solutions from initial concept design through to on site
depot, a dedicated training station, the biggest load test cell commissioning and client training in:
in the country and the largest stock of generators in the UK. • High/low voltage power generation
• Multiple set and multiple mains synchronising systems
We hold up to £2m of generators in stock, from six to 3,000kVA • Sound attenuation and ventilation systems
– this ensures that we can quickly react to provide the right • Bespoke acoustic enclosures
solution for your power needs. • Bulk fuel storage tanks and transfer systems
• Extended exhaust systems
• Power management systems
Our team of experts, including high voltage and skilled • Associated civil works
service engineers, operate the length and breadth of the • Electrical and mechanical installations
country providing comprehensive support across a range
of industry sectors.
5 6
Generator Basics
7
Generator Basics Rating Definitions The KW rating will never change but the kVA
rating is variable depending on the power
maximum power available, average load factor, i.e.:
factors, hours of usage per year, peak demand
and typical applications. These broad
Generator Set
of industrial and commercial uses.
later the remainder of the load can be applied, For most installations this is not viable and
i.e.: fully loaded generator within 20 seconds attenuation is then required. The industry
from a mains failure signal.
se
ise
oi
eN
No
It is recommended that that a diesel generator suitable for most installations however
in
n
Fa
g
En
is loaded to at least 60 % of its prime rating special considerations must be taken into
to avoid any issues relating to light loading, account when the installation is in an area
which is typically carbon build-up on the where planning applications are required.
cylinders caused by un-burnt fuel on light load Typically residential areas fall into this category
applications. and the noise level must then be reduced
further. Noise levels can be reduced to 60 dBA
High Velocity High Velocity Operational Requirements
Air Flow Air Flow Generator sets require two key elements to For larger engines, 65 dBA is a more realistic
function correctly: target noise level.
11 12
Methods for reducing noise: When reducing noise, important considerations General Maintenance Should the site load be less than 30–40%,
must be taken into account. Each method, It is recommended that the end user of a
• Attenuation (sound absorption)
excluding distance, has its own associated standby generator system starts the generator be brought in on an annual basis to run the
• Vibration isolation on a weekly basis and allows the machine to generator at 100 % load – this will prevent
• Barriers this restriction does not exceed that which carbon build up.
the cooling system is capable of overcoming. the machine is operational and is likely to start
• Distance
We must also take into consideration that in the event of a mains failure signal. The load bank can either be connected at the
LV switchgear by disconnecting the output
generated when we are trying to force ventilate Once a month, a mains failure simulation test cables from the generator circuit breaker or by
an enclosure or plant room and typically is should be carried out and the generator run on
generated when the louvers or attenuation are the available site load for up to one hour. This
sized incorrectly. will prove that the changeover arrangement is The additional set mounted three pole load
operational and that the generator can support
the site load. shunt facility to automatically disconnect the
load bank in the event of a mains failure during
On a quarterly basis, the generator supplier / a load test. This will allow the generator to
specialist should be called in to carry out the
manufacturers recommended maintenance load bank.
may be necessary.
-13 dBA -13 dBA -17 dBA -20 dBA -23 dBA -26 dBA -29 dBA -31 dBA -32 dBA -33 dBA -34 dBA
1. Cooling requirements to create cross approximately 1.5 metres clear of any other prevent re-circulation into the plant room/enclosure.
buildings / obstacles for maintenance access
2. Access for installation and maintenance
3. Noise levels level and would typically measure between 700mm W x 700mm H for a small 50
Types of installation in order of preference kVA to a 3.5m W x 3.5m H louvre for a 2.5 mVA.
Installation methods: to cost, lead time, practicality and future
• External canopied generator set maintenance:
(Standard canopy)
• External drop over enclosed generator set 1. Externally located within a canopy
(for special noise applications) or container
• External containerised generator set 2. Ground level plant room with two
• Plant room installation external walls
3. Roof top external canopy or container
4. Roof top plant room set with two
external walls
5. Internal or basement plant room
with restricted outside walls
150 kVA: 230 m³/min 200 kVA: 310 m³/min 250 kVA: 350 m³/min
700 kVA: 1150 m³/min 1000 kVA: 1200 m³/min 1250 kVA: 1250 m³/min
2000 kVA: 2100 m³/min 2250 kVA: 2300 m³/min 2500 kVA: 2900 m³/min
Note: Typical duct allowance (back pressure) would be in the region of 25mm water gauge/250 pascals
15 16
Fuel & Fuel Storage Systems Most readily available fuels will have a The engine’s fuel system works on a continuous
Diesel generators run on red diesel, which small bio content of up to 5 %, this does with base mounted fuel tanks with capacities ring which requires a feed line from the base/
is readily available via all fuel distribution free standing tank and a return line to the base/
manufacturer’s warranty. Guidance should load running. free standing tank. This is to allow any unused
be taken for higher bio contents which may fuel during combustion to be returned to the
Due to torsional vibration at start up, tank as shown below:
engine type.
Winter grade fuel oil is recommended for the standing fuel tanks.
UK as it has a lower waxing temperature (circa
-15°C) than standard diesel. only one third of fuel burnt being converted
into electrical power. The remaining is lost via
heat from the cooling package and the exhaust
system as shown below:
Radiator
Electricity 33%
20–40%
17
Bulk Tanks & Transfer Systems Where the bulk fuel tank is feeding a base/day Fuel Consumptions
tank via gravity, fuel transfer controls are then
12 hours of fuel storage is not enough, bulk required. Float switches would be installed
fuel storage tanks are then required. A typical into the generator base/day tank and these 10 kVA 4 Lts 300 kVA 60 Lts 1000 kVA 220 Lts
example of this is on NHS sites where their 30 kVA 7 Lts 350 kVA 70 Lts 1250 kVA 260 Lts
storage on site.
the base/day tank. At the feed from the bulk
To achieve applications like these we introduce tank a motorised ball valve would be installed. 100 kVA 22 Lts 500 kVA 100 Lts 1700 kVA 350 Lts
bulk fuel storage tanks, these range in size
from 500 litres up to 100,000 litres plus. Various system control panel would signal the valve 150 kVA 40 Lts 600 kVA 120 Lts 2000 kVA 425 Lts
types of bulk fuel installations can be utilised, open or close depending on the level of the
200 kVA 45 Lts 730 kVA 150 Lts 2250 kVA 470 Lts
the most common methods are as follows:
• Bulk fuel tank directly feeding generator set
• Bulk fuel tank feeding base/day tank via Where the bulk fuel tank is feeding a base/
automatic gravity feed (bulk tank must be day tank via a pumpset, further fuel transfer
at a higher level) controls are required. Float switches would
• Bulk fuel tank feeding base/day tank be installed into the generator base/day tank
via automatic pump set (single pumpset and these would be installed at preset levels.
or duplex)
Where the bulk tank directly feeds the within the base/day tank. At the feed from the
generator sets engine, no enhanced controls bulk tank a motorised ball valve and pumpset
are required. A feed and return fuel line is (single or duplex) would be installed. As the
Bulk Tank Transfer System
required as previously detailed under fuel and
fuel storage systems. fuel system control panel, the pumpset will
run and the ball valve will open. When the fuel
19 20
Exhausts
The exhaust fumes must be discharged to 50mm dia to 700mm dia depending on the
atmosphere and where practical take the engine size, noise level, route length and good engineering practice should always be
shortest route to avoid any unnecessary bends number of bends. applied and particular care should be taken
in the system - excessive bends and long to avoid personnel contact and fumes venting
distances create back pressure restrictions on An engine will either have one or two exhaust into windows/air intakes. The ideal location of
the engine. This can be overcome by increasing manifolds depending on the type and size, but an exhaust termination point is above the air
discharge louvre as the high volume air passing
through the louvre will assist in diluting the
Exhaust gases can reach temperatures of up to have twin manifolds.
600°C; therefore care must be taken to avoid highest point of the building.
heat transfer onto any building structures/
surfaces and also to ensure that the gas is not 5m³/minute for the smallest generator set to
discharging onto any personnel access areas. 600m³/minute for a 2.5 mVA generator set.
21 22
External
Generator Sets
Ai
r
r
in
in
ta
ta
ke
ke
s
ke
ta
in
r
Ai
Ai
r
Typical dimensions:
di
sc
har
33 kVA – 65 kVA: 2.3m L x 1.2m W x 1.6m H (1,300 Kg)
ge
25 26
Realistic maximum reductions in noise: Containerised Sets Bespoke built containers can also
For external generator sets typically be made to suit sets smaller than
above 730 kVA, containerised 730 kVA with reductions in noise
generator sets are used. These are possible to a level of 60 dBA.
bespoke built depending on the The industry standard noise level
required noise level on site, which
typically ranges from 65 dBA to also provides the most cost
27
• Multi-cable entry access points
containerised set: •
• ISO type container with corrugated side breaker (>900 kVA)
sheets fully welded construction • Internal luminous panic release buttons
• on doors
• • Emergency stop button located
conveniently by each personnel access door
oil, coolant and on board fuel • Floor with textured non slip heavy duty
• Walls and roof lined with 75mm thick surface for safety and durability
mineral wool retained by galvanised • Day fuel tanks up to 3,000 litre
perforated steel sheet •
• Two personnel access doors complete
with panic release bolts are included for acrylic painted to our standard paint
access to the generator
• Inlet end removable • All external components and surfaces
• Fully integrated AC lighting and power treated with anti-corrosion coatings
distribution system
• Inboard or roof mounted gas exhaust
silencer assembly
29 30
£200 million investment in the future
HSBC Headquarters
Plant Room
Silent basement backup generator since 2019
Installations
31 32
Plant Room Installations Ideal Room Layouts
The two examples below show the correct installation method. Air would be
drawn over the entire set and ensure correct alternator and engine cooling.
generator set cool. The plant room should ideally have direct
vehicle access to it. This would allow the
Access to the room is normally through an Incorrect Room Layouts
acoustic single/double door which can be for an easier installation. This also enables The two examples below show an incorrect installation method. Air would short
used for equipment installation/removal. In easier future maintenance, repairs and plant circuit the alternator and most of the engine causing heat spots. This in turn
replacement. would cause the generator set to shut down due to over heating.
attenuation built in.
X
33 34
Key Components of Careful consideration must be taken when 33 kVA to 220 kVA Plant Room Installations
designing a system incorporating all of the
Plant Room Installation
above items.
1. Generator set
2.
weather louver
3. Key considerations are:
weather louver • Ensure system is designed to
4. Exhaust gas silencer
account for all allowable
5. Exhaust gas silencer support stand/
steel work pressure drops and limits
6. Exhaust bellows • Ensure system provides
7.
adequate air for combustion
8. Flexible air outlet plenum/duct
and cooling
• Ensure adequate space for
mainetance access
Equipment dimensions:
Key components
Generator set: 2.6m L x 1.1m W x 1.7m H
Please Note: The above information is provided for reference only and can be treated as preliminary only.
It assumes that the plant room is at ground level with two external walls and is constructed of acoustically
compatible materials. Please contact [email protected] for bespoke solutions or further information.
35 36
250 kVA to 330 kVA Plant Room Installations 730 kVA to 1000 kVA Plant Room Installations
Equipment Dimensions: Equipment dimensions:
Generator set: 3.3m L x 1.1m W x 1.9m H Generator set: 5m L x 2.1m W x 2.3m H
400 kVA to 700 kVA Plant Room Installations 1250 kVA to 1700 kVA Plant Room Installations
Equipment dimensions: Equipment dimensions:
Generator set: 3.9m L x 1.5m W x 2.3m H Generator set: 5.2m L x 2.2m W x 2.5m H
Air inlet and outlet louver openings: 1.5m W x 2.2m H Air inlet and outlet louver openings: 3m W x 3.4m H
Exhaust gas silencer: 2m L x 1.5m W x 1.5m H Exhaust gas silencer: 3m L x 2.4m W x 1.5m H
Maintenance access around set: 1m Maintenance access around set: 1m
Recommended room dimensions: 10.2m L x 5.2m W x 5.9m H
Please Note: The above information is provided for reference only and can be treated as preliminary only. Please Note: The above information is provided for reference only and can be treated as preliminary only.
It assumes that the plant room is at ground level with two external walls and is constructed of acoustically It assumes that the plant room is at ground level with two external walls and is constructed of acoustically
compatible materials. Please contact [email protected] for bespoke solutions or further information. compatible materials. Please contact [email protected] for bespoke solutions or further information.
37
1750 kVA to 2500 kVA Plant Room Installations Mid Building or Roof Top Plant Rooms Basement Room Plans
Ground level installations are the most Similarly to mid building and roof top plant
Equipment dimensions:
economical and provide the best access for rooms, basement installations can also be
Generator set: 6m L x 2.3m W x 3.5m H initial installation and future maintenance. problematic.
However it is not always possible or practical to
install the generator set at ground level. Careful Key considerations when designing this type
consideration should be given at design stage. of plant room, include:
• Installation method – can the generator
The following key considerations must be and equipment be easily installed into
Exhaust gas silencer: 3m L x 2.4m W x 2m H
taken into account: the area
Maintenance access around set: 1m
• • Can the generator be installed as a single
into the plant room unit or is dismantling and re-building in situ
• The position of the crane at street level required?
• Are road closures required, how will they • Ventilation requirements – are there any
impact on programme/costs external walls?
• The overall weight and load of the • Duct work requirements – for air inlet and
air discharge
must be supported • Plant replacement strategy in the event of
• Re-fuelling – fuel transfer system would be major plant failure
required introducing new costs to project • General access for regular maintenance
• Extended cable runs from the switchroom, • Re-fuelling – fuel transfer system would be
usually at ground level required introducing new costs to project
• Plant replacement strategy in the event of • Extended exhaust route required
major plant failure
• General access for regular maintenance As with roof top plant rooms, basement plant
rooms should only be considered when there is
no possibility of installing the generator set in
installation should be used over mid building
or roof top installation.
Please Note: The above information is provided for reference only and can be treated as preliminary only.
It assumes that the plant room is at ground level with two external walls and is constructed of acoustically
compatible materials. Please contact [email protected] for bespoke solutions or further information.
39 40
Keeping you connected
Complex backup power
Control Systems
solutions for over 50 years
41 42
Control Systems Typical HMI/Scada Screen
Control Systems
Depending on the application there are various types
of controls and control philosophy that we would adopt.
This allows you to monitor and control your generator set with
ease, whilst ensuring your unit operates within safe parameters
and provides important diagnostic information when needed.
43 44
Base Load Application
Base Load Schematic
A base load application is when the generator set is the only
source of electric power on site. Typical examples where the
generator set is required to provide the base load on site are
as follows:
• Remote sites
•
• New construction projects where mains power supply has
not yet been installed
• Sites where the mains supply is not large enough for the load
Key notes:
• Basic key start generator control panel required
• Control panel to be manually operated at generator set
or operated via remote switch
• Generator breaker normally closed and distribution
panel supply breaker normally open (to prevent run up
against load)
• When generator is switched on, runs up to speed and
voltage, power available within approximately 15 seconds
• Once the generator is up to speed/voltage close the
distribution panel feeder breaker
•
periods of time (longer than 12 hours) a timer control circuit
will be installed – this will automatically start the generator
set allowing the starter battery to be charged
• When power is no longer required, the generator can be
45 46
Automatic Mains Failure (AMF) Application
Automatic Mains Failure Schematic
Automatic mains failure application is when the generator
set is the secondary supply on site for use during a mains/utility
supply failure. This type of application is the most commonly
used in the industry and requires an automatic change over
panel in addition to the generator control panel.
Key notes:
• The automatic change over panel monitors utility
supply voltage
• In the event of a mains utility failure, the changeover
panel sends a two wire start command to the generator set.
This start command is provided via the mains sensing unit
• When the generator receives this volt free start signal,
it automatically starts
• The generator runs up to speed and voltage and is available
to take load within approximately 15 seconds
• The changeover panel now sensing generator voltage,
opens the mains breaker and closes the generator breaker
to load the generator and supply the building load
• On return of a mains utility supply, the changeover panel
via the mains sensing unit starts a variable timer to ensure the
mains utility supply is healthy and not an intermittent return
•
the changeover panel opens the generator breaker and
closes the mains breaker
• The mains utility supply now feeds the building’s load
• The generator runs on cool down and then shuts down
47
Automatic Mains Failure (AMF) • On loss of utility mains power, the
generator control panel will monitor the Automatic Mains Failure With No Break Return Schematic
With No Break Return Application
loss of mains for an approximate period of
Automatic mains failure with no break return is
three seconds. If it is a true loss of mains,
when the generator set is the secondary supply
and not a brown out, the generator set will
on site. When the mains utility supply fails, the
then automatically start and provide a
generator set automatically starts and provides
signal to the DC power pack to open the
power to the building’s load as described in
mains breaker
the previous AMF application section. The
• When the generator set is up to speed
and voltage (approximately 15 seconds)
the generator set synchronises with the mains
the generator control panel will send a
utility supply and both the utility supply and
signal for the generator breaker to close
generator supply run in parallel for a short
and the generator set will then support the
building load
and the generator breaker automatically opens
• On return of mains utility power, the
allowing the mains utility supply to take the full
generator control will monitor the mains
building load.
voltage for an approximate period of three
minutes
Please see opposite schematic of typical AMF
•
with no break return installation.
truly healthy, the generator control panel
will then begin to match the voltage and
Key notes:
frequency of the generator set with the
• For this application a more advanced
mains supply, this is achieved by speeding
generator control panel is required such as
up and slowing down the generator engine
– ComAp, DSE or EasyGen
via the electronic governor
• The generator control panel will control
• When the mains utility and generator
the full change over process however key
voltages then match, the generator control
items must be included by the switchboard
panel will send the signal to close the
supplier
mains breaker – the set and mains are now
• Key inclusions on switchboard – motorised
running in parallel
breakers (gen and mains), CTs and VTs for
•
mains and current sensing, DC power pack
ramp down and send the signal to open the
for breaker control, parallel limit timer and
generator breaker, the mains is now fully
G59 protection if not part of generator
taking the load and the generator set will
control panel
begin its cool down period
• The generator control panel monitors the
• The DNO (supply authority) will require
mains utility voltage and current through the
protections to be installed to ensure that
CTs and VTs installed in the switchboard
in the event of a fault either the mains or
generator breakers can be tripped open
(see below comments on G59 and parallel
limit timer)
49 50
G59 Protection Parallel Limit Timer
Example of full power control system:
When running in parallel with the mains utility A parallel limit timer is another type of
supply, the DNO (supply authority) requires protection device which should be used for this
additional protections to be installed. It is the type of installation.
responsibility of the client and not the DNO
to ensure these protections are installed. The The DNO dictates that for short term paralleling
DNO will witness test these protections on site time limits are in place for disconnection of
before permitting the generator set to run in one of the supplies. The parallel limit timer will
parallel with the mains supply. monitor the time the set and mains have run
in parallel and should this be longer than the
The DNO requires G59 protection to be installed programmed allowance, the parallel limit timer
at the point of set to mains synchronising, this will instantaneously trip the generator breaker.
is usually at the switchboard.
Full Power Control System
A G59 compliant mains protection relay is an Full power control systems can include:
electronic monitoring device which looks at • Multiple sets synchronising with each other
the quality and stability of the mains electricity. • Multiple sets synchronising with each other
and the mains utility supply
dictated by the DNO. These typically include • Multiple sets synchronising together and
voltage, frequency, ROCOF (rate of change of synchronising with multiple mains
frequency), phase angle and so on. Should • Single set synchronising with multiple mains
any of these areas go outside the programmed • Control of bus tie and feeder breaker
limits, then the relay will cause a protective • Full control of each type of system through
device such as an MCCB or other type of a dedicated HMI panel
circuit breaker to open, thereby instantly
disconnecting the generator from the grid. The preferred control solution for these types
of system would be utilising either the ComAp
The DNO will require a full G59 application to or DSE control modules.
be submitted prior to any installations or tests
taking place. The client should be aware that
there are costs associated with the application
and testing of this protective device.
51 52
Jargon Buster
53 54
Combined heat and power (CHP) Delta
Air circuit breaker Backup protection
Use of a generating set or sets for the purpose of utilising the
Circuit breaker contacts open to the air (atmosphere);
heat produced (via the exhaust and the radiator) as well as of a transformer or electrical rotating machine where
see also circuit breaker. protective device(s) has failed to operate.
producing electricity. the three phase-coils are connected in series in a ê(delta)
AC generator Base load
Compound generator for both three and four wire circuits e.g. open delta,
Electrical generator that produces alternating current The portion of load of a generator or building which
A generator whose excitation system takes elements of Edison delta, (sometime referred to as high-leg delta or
(preferred term). Aka alternator. is constant.
both voltage and current or derivatives of these in order to red-leg delta), and jack-leg delta etc. A two coil three wire
connection would be an open delta.
Active power Biodiesel
AC power with a unity power factor. Measured in watts. Diesel fuel with all or part content derived from
Contactor Deviation factor
vegetable oils.
An electrically operated heavy current switching device. The maximum instantaneous deviation of a generator
Alternator
voltage waveform, as a percentage of the true sine wave
Electrical generator that produces alternating current Black start
Cross current compensation of the same RMS value.
(non-preferred term). Refers to starting of a power system without the use of
System whereby the current loading of a generator in
an external power source, i.e. The building or application.
parallel with another is used to adjust the excitation of the Diesel bug
Amortisseur winding
second generator, so that the two generators share the load The generic term for the microbial growth found within fuel
Windings embedded in the pole face of a synchronous Brown out
equally, with minimum impact on the combined voltage systems and fuel storage tanks. Formed of a variety
generator, whose function is to dampen oscillations of the An intentional or unintentional drop in voltage in the utility
level.
mains power supply. Intentional brownouts are used
for load reduction in an emergency. The reduction may
Current transformer Diesel rotary UPS
Ampere last for minutes or hours, as opposed to short-term voltage
A current transformer will provide a reduced current, A diesel engine driven generating set which includes an
The unit of electrical current (amp). sag (or dip) lasting seconds caused by other factors. It is
known that such voltage drops can be harmful to certain
proportional to the current in the main circuit being
Analogue controls sensitive electrical devices, such as computers; therefore
measured. generator. When the mains supply fails the diesel engine is
Controls using variable voltage or current to pass accentuating the importance of a resilient backup regime
information. including a generating set for a business.
Cycle
The complete reversal of an alternating current or voltage whilst the engine is starting up.
Apparent power Bulk tank
from zero to positive maximum down to negative maximum
The product of current and voltage in an alternating current A large storage tank from which the generating set may
and back to zero. Dielectric strength
circuit which has a reactive element. take its immediate supply of fuel or may be used to provide
The maximum electric strength that an insulating material
a supply to a day tank.
can withstand intrinsically without breaking down. i.e.
Armature
Damper winding without experiencing failure of its insulating properties.
The assembly of windings and iron core in which the Bunding
More commonly used term for amortisseur winding.
generator output is produced. Sometimes referred to as This relates to the provision for containing leakage of fuel,
the Stator to avoid confusion. contaminated water, oil etc.
Day tank
A small storage tank from which the generating set takes points of a series connecting electrical circuit.
Asynchronous Busbar
Term applied to motors or generators which operate at Copper or aluminium (usually rigid) conductors of a
working hours and designed into the base frame of the Direct current
rectangular, square, round or hollow section, to inter-
generating set.
connect high current circuits in a switchboard or building.
Attenuators
Decibels Droop
Devices for reduction of the emission of sound
Decibels dB or dB(A) are abbreviations for decibel. It is the
(also known as silencers). Circuit
“unit” for both sound pressure and sound power level. It is (usually that of frequency or voltage) with increasing load.
An electrical circuit is an interconnection of electrical
not a unit because it is the logarithm of a quotient. That’s In the context of generating sets the term is usually applied
Automatic transfer switch elements such as resistors, inductors, capacitors,
why Lp (pressure) and Lw (power) are both expressed in dB, to the governor or automatic voltage regulator and to the
A device used to automatically switch a power supply transmission lines and switches, with a power source and
speed or voltage reference respectively. Introducing a droop
from normal to emergency when a power failure occurs a closed loop return path for the current.
The A is a weighting value, as in dB(A), but this is not characteristic for frequency and voltage is one method that
supported by ISO standards. To be meaningful the A must is used to introduce stability to generating sets operating in
Auto transformer starter Circuit breaker
be contained in LpA or LwA and with a proper description. parallel with one another.
Transformer switching arrangement to reduce voltage
See also sound pressure v sound power.
applied to an electric motor during starting. of current in a circuit when the current level exceeds a
Double skin
certain value.
The extra layer inside a fuel tank and pipework to minimise
AVR droop
Term used in specifying vibration mounts, indicating the risk of potential leakage. Equally applies to any toxic
AVR voltage reference is reduced as load increases.
capacity to accommodate ‘on site’ conditions. liquid around a generating set.
A generic term for an enclosure or canopy which is designed
57
Make before break Noise pollution
Load acceptance Parallel operation
An arrangement for electrical switchgear whereby two
Percentage of the rated set load that can be applied to a Operating two or more generating sets or generating sets
switching devices close to make a circuit in parallel before machines near to buildings and people which may require
generator set and is capable of accepting in one step and and the mains, networked together to supply a common
load (also see synchronisation).
parallel electrical power supplies, for arrangements where, consideration.
when changing from one power supply to another, there is
Load balancing Peak lopping/shaving
no interruption between supplies. Note that it is extremely Non-linear load
Common term used to describe best practice of balancing A term used to describe the use of a generating set system
important when considering parallel AC electrical supplies A load in which there is a non-linear relationship between
a load evenly across three phases where possible. to reduce load on the utility or mains supply, usually in
that consideration is made to ensure that the supplies are current and voltage. Commonly the result of electronic
times of peak demand. The generator may be used to
synchronised. This means making sure that voltages, phase switching during the cycle in the load circuits, typically in
Load bank
angles and frequencies are matched. Attempted parallel most electronic controllers. See also harmonics.
Resistors and/or inductors that can be connected to a with the generator taking up the variations; alternatively
operation of supplies that are not synchronised can result in
generating set either for test purposes to simulate a real load
damage to equipment or risk personal injury. Normally closed/open contact
or to provide a method to absorb power where regenerative the mains supply taking up variations. The precise mode of
Description of the status of a relay contact when the relay
operation should be agreed with the supply authority before
Main set breaker is de-energised.
commencing work.
The main breaker is the circuit breaker through which the
Load factor
The ratio of average load to the generating set power rating. Pipe-In-Pipe
Octave band
Mains breaker Frequency range where the highest frequency is double
Load step conveyance of fuel aimed to eliminate leaks. The interstitial
A circuit breaker that is usually positioned at the electricity the lowest, with eight bands 63Hz, 125Hz, 250Hz being used
Normally a percentage load applied to a generating set. space between the inner and outer pipe can be used with a
services intake of a premises and which may be interlocked most frequently to analyse and quantify sound.
leak detection system to guard against potential leaks in to
with a generator circuit breaker to form a changeover from
Lube oil make up system the environment (see double skin).
mains to generator power.
All engines consume lubricating oil when they run.
Therefore, the autonomy of an engine (time for which the PCL controls
Mechanical bridge
engine can run without requiring human intervention) is Programmable logic controller – a programmable hardware
A support for power cabling, fuel lines, exhaust, radiator etc.
determined by how much oil in the engine is available to be control system which includes digital and analogue inputs
consumed. To supplement this, a lube oil make up system and outputs.
Meg-ohm (MW)
can be added. This normally consists of a small lubricating
oil tank connected to the engine with a make up valve. Pole(s)
resistance to current leakage. The unit of electrical resistance; it is the ratio of 1 volt to
1 amp.
to match the consumption of oil. It is important for a generator or motor. It can also refer to the electrodes of
Motoring
any engine that the autonomy of the lubricating oil system a DC battery or the number of contacts on a contactor or
This is the term applied when a generator remains Out-of-phase
matches or exceeds the autonomy of the fuel system. circuit breaker. Pole-pairs – four poles of the most common
connected to a network or other generators but its drive Referring to alternating currents or voltages of the same
generator designs, arranged in pairs at 120° to one another
engine fails to deliver power – the generating set continues frequency, which are not passing through their zero points
in the construction of a generator.
to run with the generator now driving the engine i.e. the at the same time.
Magnetic pick up
generator becomes a motor.
Pole slip
Overload
prime mover, typically an engine or turbine. They are the A condition whereby a generator, or group of generators,
Moulded case circuit breaker (MCCB) Term referring to the amount by which an electrical circuit
communication link between the engine and an electronic terminal voltage angles (or phases) go past allowable
A circuit breaker which is enclosed in a plastic insulating is exceeding its rating.
case and which trips when the current exceeds a pre-
gear which is made of a material that reacts to a magnetic of the connected power system.
determined value for a given time. Overshoot aka overspeed
The amount by which voltage or frequency exceeds the
1.0mm of the MPU, the tooth interrupts the MPU’s magnetic Positive phase sequence current
nominal value following a load change.
Element of fault current vector in same phase sequence
Negative phase sequence current
of this voltage is translated by the speed control into a signal as the supply voltage.
In any three phase system, the currents that make up the
that accurately depicts the speed of the prime mover.
system can be resolved to positive, negative and zero phase
Power factor (Pf)
sequence phases. Thus the positive sequence components
In AC circuits, the power factor is the ratio of the real
59 60
When all the power is reactive with no real power (usually Regenerative power Single bearing closed coupled Star – delta starter
inductive loads, such as motors) – the power factor is zero. See motoring. The AC generator has no bearing at the DE (i.e. engine Device for switching electric motor windings to reduce
When all the power is real power with no reactive power starting current.
(resistive loads, such as heat elements) – the power factor Reverse power housing with a bolted adaptor.
is one. Power absorbed by a generator from a paralleled system Starting current
due to engine failure. Active power absorbed by a generator Solid state controls High current drawn by an electric motor during starting.
from the connected system. This may be another paralleled Electronic control (switching) devices e.g. transistors,
in three phase systems and 1.0pf, or unity, for single phase generator, the utility supply or possibly a motor such as a thyristors. Stator
systems. Figures between 0 to +1 are referred to as leading crane hoist that is being driven by the load. The stationary wound assembly of an AC generator or
Sound power v pressure levels exciter.
power factors. ROCOF The sound power level indicates the total acoustic energy
Rate of change of frequency. that a machine, (in our industry a generating set/s), radiates Sub-transient reactance
Prime power to its environment. The sound pressure level is a measure of Initial reactance of generator at instant of short circuit fault
The maximum power which a generating set is capable Root mean square condition.
of delivering continuously whilst supplying a variable of sources) and depends on the distance to the source(s)
load when operating for an unlimited number of hours (equivalent DC) value of the sinusoidal alternating quantity. and acoustic properties of the surroundings of that source. Surge
per year under the agreed operating conditions with the A term applied to both current and voltage – it refers to an
maintenance intervals and procedures being carried out Rotor the sound pressure level always depends on position and exceptionally high increase in the quantity over a very short
as prescribed by the manufacturer. Rotating part of an electrical generator. environment. time period. Usually the result of load switching or lightning
strikes.
The permissible average power over 24 hours of operation
must not exceed 70% of the prime power agreed by the SCR (selective catalytic reduction) • SI (international system of units) only contains units Surge suppressor
for pressure and power, not for levels. A general term used for a device to prevent externally
of turbo charged petrol, diesel and gas engine exhaust promoted voltage surges from destroying other devices.
gas emissions. They are used to remove nitrogen oxides Levels are described in ISO standards, using the following Commonly employed on the exciters of brushless generators
Radiator (NOx) and help reduce the amount of particulate matter in abbreviations or descriptors: to prevent rotating diode failure.
Typically, heat exchangers used to transfer thermal energy emissions which are known to directly damage health and • Sound pressure level – LpA
from one medium to another for the purpose of cooling convert the nitrox oxide to nitrogen and water vapour to • Sound power level – LwA Synchronisation
cause less harm to the environment. The act of matching the voltage magnitude, frequency
water jacket cooling the engine, a charge air circuit used The A relates to audio frequency referencing against an and zero crossing times (phase), of two alternating current
to cool directly the compressed air from an engine turbo Secondary contained ‘A-weighted’ table of logarithmic values where the decibel sources for the purposes of connecting them
chargers, prior to entry into the engine for combustion; A safeguarding method used to prevent unplanned releases values of sounds at low frequencies are reduced, compared in parallel.
of hazardous liquids such as diesel (see biodiesel) into with unweighted decibel values, in which no correction
cooled charge air coolers (WCCAC). uncontrolled areas, typically used when referring to fuel is made for audio frequency. As such in addition to the SI Synchronous reactance
pipe work (see binding).
set sound attenuation shown as dBA or dB(A) however
Self-excited generator without the distance from the sound sources being included
A generator whose excitation system takes power from e.g. one meter, seven meters or sometimes 15 meters the
its own output. Related to non sinusoidal voltage waveform and the
noise source. magnetic linkage between power and telephone cables,
an electric motor remote from the generating set. Separately excited generator
A generator whose excitation system takes power from a Sound power level on telephone operation.
Ratings separate source. Usually a secondary generator or exciter. Sound level in dB (or dBA) relative to reference power level
in watts. Thermistor
Short term operating reserve A thermistor is a type of resistor whose resistance varies
• Continuous power (COP) Short term operating reserve is a service for the provision Sound pressure level
• Prime power (PRP) of additional active power from generation an/or demand Sound level in dB (or dBA) relative to reference pressure resistors. Thermistors are widely used as inrush current
• Limited-time running power (LTP) reduction. level in pascals. limiters, temperature sensors, self-resetting overcurrent
• Emergency standby power (ESP) protectors and self-regulating heating elements.
Shunt trip Speed droop
Radiometric This is a feature added to circuit breakers in order to Governor speed reference is reduced as load (or fuelling)
A term used in electronic circuits (or system) where the remotely trip the breaker from an externally derived signal; increases. See droop. (RTDs) in that the material used in a thermistor is generally
output has a direct proportional relationship to the input. such as a generator controller or switchgear control system. a ceramic or polymer, while RTDs use pure metals, such as
Star connection
Reactance A connection of a three phase system or machine whereby are useful over larger temperature ranges, while thermistors
the line voltage equals 1.73 times the phase voltage, and the typically achieve a higher precision within a limited
commonly connected phase ends form a neutral connection. temperature range, typically -90° to 130°C.
61 62
Thermocouple Voltage regulation
Undershoot
Bi-metal junction producing signal voltage proportional to
Refers to the amount by which frequency or voltage drops
temperatures – used for temperature measurement. steady state voltage as a percentage of the nominal voltage.
below the nominal value as a result of load changes.
Zone 22
the cable construction, length, installation method and
temperature.
the manufacturer can be used.