Turbine Generator Governor Droop Isochronous Fundamentals - A Graphical Approach
Turbine Generator Governor Droop Isochronous Fundamentals - A Graphical Approach
Abstract - To promote a better understanding of industrial frequency change as load is applied; additionally, this one
turbine/generator speed control, the fundamentals of droop generator governor droop example shows the effect of
and isochronous turbine/generator control are discussed via changing the no-load frequency above and below rated
graphical examples for typical industrial islanding applications frequency. Two paralleled generator examples follow with
with bus connected generators. A mathematical analysis of identical generators operating with the same per cent droop;
several examples illustrates the validity of a practical the resulting system frequency is shown when the no-load
graphical approximation approach. By comprehending these frequency is the same for both generators and also when the
fundamental concepts, industrial application engineers can two generators have different no-load frequencies.
more thoroughly investigate advanced governor control
topics, such as, isochronous load sharing with
communications lines between governors, manual operator G1 G2
control of multiple generators, and load sharing via automatic
power management systems.
This paper discusses fundamental droop and isochronous Mathematical computations are included for several
turbine/generator governor control applied through modern examples to illustrate that the graphical analysis and the
electronic governors for islanding, bus connected generator analytical computations provide approximately the same
applications (Fig. 1). Simplified block diagrams with summing results.
points illustrate basic turbine/generator governor concepts of Additional graphical illustrations show combined
droop and isochronous control. Graphical examples of droop isochronous and droop operation and the change in power
and isochronous governor control are provided to promote a output as the droop line is shifted.
better understanding of typically encountered industrial Governor dynamic response capability limit discussions are
islanding applications. beyond the scope of this paper but available in [1].
The graphical approach discussions begin with To better focus on the real power aspects related to
isochronous control for one generator operating governor actions, automatic voltage regulator (AVR)
independently. A two generator isochronous discussion considerations are not included in this paper; however, a
follows to illustrate why operating two generators in future paper with advanced governor control strategies will
independent isochronous governor control mode is not include AVR considerations.
recommended. Next, one generator is operated
independently in droop mode, showing the resulting
2
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
readily understood and appropriate corrective action taken by the offline turbine/generator powers the load and does not trip
facility operations. on reverse power. Therefore, for this example, assume G1 is
operating at 60.0 Hz and G2 is operating with 60.1 Hz
III. ISOCHRONOUS OPERATION EXAMPLES frequency (speed) reference. When paralleled, G2 governor
senses a slightly greater than 60.0 Hz system frequency;
Consider an islanding electrical power system with one therefore, G2 summation point output is a negative number
turbine/generator and associated governor operating in which commands the G2 fuel valve to open with a resulting
isochronous mode. Fig. 3A is a steady-state graph of the increase in turbine/generator speed. As system frequency
generator MW output power versus frequency with an increases, the turbine/generator G2 begins to power the load.
isochronous governor control strategy operating at 60.0 Hz G1 summation point senses an increased speed and the
frequency reference, ignoring response to transients. As the summation point output is positive; this results in a command
load increases from no-load to 100% load, frequency is to close G1 fuel valve with a subsequent decrease of G1 MW
maintained at a constant steady-state magnitude of 60.0 Hz. power output. This iterative condition continues until G2
As previously shown in Fig. 2B, the speed summation point powers all loads and G1 fuel valve closes to a minimum;
compares the speed reference with the measured speed, eventually G2 powers G1. With G1 in a motoring condition,
and the fuel valve is modulated for load increases or the G1 reverse power protection device may trip the G1
decreases because the summation point output difference is generator circuit breaker; thereby tripping G1 offline.
maintained at zero after a load change. For this example, the
isochronous control strategy maintains a constant speed and
a 60.0 Hz frequency. IV. DROOP OPERATION EXAMPLES WITH ONE
GENERATOR
3
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
Operating with a full load frequency of 57.6 Hz may be operating frequency). With the generator operating at 50%
objectionable to facility operations because traditional load, 60.0 Hz would be the operating frequency. If the
turbine/generator underfrequency alarm or trip limits (95% of generator operated at 75% load, this would result in an
rated) may be marginal. operating frequency of 59.4 Hz and could be considered as a
The Fig. 4A example illustrates the dilemma of accepting frequency compromise when droop mode is selected in a
reduced operating frequency when a 4% droop is applied system islanding configuration. As previously stated,
with a 60.0 Hz no-load frequency. Since there is a linear isochronous load sharing could be considered, but the
relationship between the droop setting and the no-load isochronous load sharing discussions are reserved for a
frequency (speed), Fig. 4B shows the result of changing the future paper.
no-load frequency from 60.0 Hz to 62.4 Hz while retaining the When two identical generators operate in parallel in an
same 4% droop setting and 4% droop line slope for a 60 Hz islanding configuration and have the same turbine/generator
no-load frequency. MW rating and governor per cent droop setting at the same
Operating with a no-load frequency of 62.4 Hz may be no-load frequency, each turbine/generator should operate as
objectionable to operations because at no-load traditional described in this section with the load shared equally
turbine overfrequency alarm or trip limits (105% x rated between the generators.
frequency) may be marginal. Turbine/generator frequency
(speed) limits vary with size and manufacture of V. GRAPHICAL APPROACH – AN
turbine/generator and should be reviewed. Only when 100% APPROXIMATION
load is applied is the frequency reduced to 60.0 Hz; therefore,
a compromise to reduce the no-load frequency to less than The graphical approach is an approximation because the
62.4 Hz could be considered. droop line slope is based on a 60 Hz (or 50 Hz) no-load
frequency and is used throughout the graphical analysis from
60 Hz no-load frequency to 62.4 HZ no-load frequency (or
from 50 Hz no-load frequency to 52 Hz no-load frequency),
rather than slightly adjust the droop line slope for each no-
load frequency investigated.
Although this droop slope line approximation is used per
turbine throughout the graphical illustrations, the
mathematical comparison examples of this paper illustrate
the very close approximation and minimal difference between
the graphical approach and exact mathematical
computations. This very close approximation is considered
to be suitable for engineering evaluation because the
graphical results are almost the same as the detailed
calculations shown in the examples of this paper and a
Fig. 4B One Generator Example with 4% Droop visual, intuitive understanding provides a more in-depth
and NLF = 62.4 Hz comprehension of the application, as well as the
mathematical calculations.
4
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
PFL turbine/generator output power at full-load. the same 6 MW full-load turbine/generator power rating and
4% droop setting but with different no-load frequencies fNL.
A. One Generator Droop Example Initially, G1 and G2 are synchronized at 60.0 Hz; however,
G1 no load frequency set point is increased until fG1NL = 62.4
Fig. 5A is an example of one generator with the following Hz. The purpose of this example is to illustrate what could
system and governor parameters: occur when it is desirable for an incoming droop generator to
Turbine rated power = PFL = 6 MW accept load.
Power at no-load = PNL = 0 MW Determine the power output of each generator and the
Droop setting = 4% with fNL = 60.0 Hz and fFL = 57.6 Hz system frequency when the total load is 6 MW.
Note: Except for fNL, the parameters of Fig. 5A Appendix B calculations show PG1 = 6 MW and PG2 = 0 MW.
turbine/generator are used for the following examples of this
section. This confirms Fig. 5B graphical representation because G1
Determine the operating frequency with a 3MW load. accepts the load from 62.4 Hz until 60.0 Hz; whereas G2
does not begin to accept load until the system frequency
From above and [3], reduces to 60.0 Hz or less. Hence, G1 accepts loads from
0MW to 6MW (100% of G1) before G2 begins to provide MW
fSYSTEM = [(fFL – fNL)/(PFL – PNL)] * PSYSTEM + fNL (3) power output.
f(Hz)
59.4
58.8
G1 = G2 = DROOP = 4%
NO-LOAD FREQUENCY = 60Hz
58.2
57.6
5
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
But what happens as the load is reduced from 9 MW to 6
MW? Inspection of Fig. 5C shows that at 60.6 Hz, PG1 = 4.5 f(Hz)
MW and PG2 = 1.5 MW. Hence, the load is reduced and Note:
divided between the two generators according to the droop 62.4 Same slope,
based on NLF =
line for each turbine/generator and the system frequency 60 Hz, is used for
61.8 G2 : DROOP = 4%
increases from 60.0 Hz to 60.6 Hz. Further load reduction to each droop line.
3MW is shown at 61.2 Hz where PG1 = 3 MW and PG2 = 0
61.2
MW. This example illustrates the unequal load sharing G1 : ISOCHRONOUS = 60.0Hz
based on the droop line settings of G1 and G2.
60.6
57.6
fNL = 60.0Hz
VIII. SUMMARY
6
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
automatic load sharing control, isochronous load sharing via project engineer for E. I. DuPont and the former Amoco Oil
load sharing lines, and turbine/generator governor control via Company. He also served as an electrical operations
a power management system. engineer for nine years in Saudi Aramco’s Northern Area
Producing Department. Currently, he is working in Chevron’s
X. REFERENCES Engineering Technology Center as a Technical Team Lead.
He is a Professional Engineer in Georgia. He is an IEEE and
[1] E.R. Hamilton, P.S. Hamer, J. Undrill, S. Manson, IEEE IAS member.
"Considerations for Generation in an Islanded
Operation,” IEEE Transactions on Industry
Applications, vol. 46-6, pp. 2289-2298, Nov/Dec 2010.
[2] Governing Fundamentals and Power Management,
Woodward Reference Manual 26260, document
number 06/03/F, 2004, Chapter 3, pg. 31.
[3] Stephen J. Chapman, Electric Machinery
Fundamentals, First Edition, McGraw-Hill, Inc., 1985,
pp. 462-477.
XI. VITA
7
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.
APPENDIX A
Calculations for Fig. 5A
PG1 rated = PG2 rated = 6 MW
G1 droop = G2 droop = 4%
fG1NL = fG2NL = 60.0 Hz.
Determine PG1, PG2, and fSYSTEM when the total system load is 6 MW.
PG1 = [(PG1FL-PG1NL)/(fG1FL-fG1NL)] (fG1NL – fSYSTEM) (5)
PG2 = [(PG2FL-PG2NL)/(fG2FL-fG2NL)] (fG2NL – fSYSTEM) (6)
Adding the two equations together provides the following resulting equation
PG1 + PG2 = 6MW = [(PG1FL-PG1NL)/(fG1FL-fG1NL)] (fG1NL
– fSYSTEM) + [(PG2FL-PG2NL)/(fG2FL-fG2NL)] (fG2NL –
fSYSTEM) (7)
6MW=(6MW/2.4 Hz)(60.0 Hz–fSYSTEM)+ (6MW/2.4
Hz) (60.0 Hz –fSYSTEM) (8)
fSYSTEM = 58.8 Hz
PG1=PG2=(6 MW/2.4 Hz) * (60.0 Hz–58.8 Hz) =3 MW (9)
APPENDIX B
Calculations for Fig. 5B
APPENDIX C
Calculations for Fig. 5C
PG1 rated = PG2 rated = 6 MW
G1 droop = G2 droop = 4%
fG1NL = 62.4 Hz and fG2NL = 61.2 Hz.
Determine PG1, PG2 , and fSYSTEM when the total system load is 9MW.
9MW = (6 MW/2.4 Hz)(62.4 Hz – fSYSTEM) + (6 MW/2.4 Hz)(61.2 Hz – fSYSTEM) (13)
fSYSTEM = 60.0 Hz
PG1 = (6 MW/2.4 Hz) * (62.4 Hz – 60.0 Hz) = 6 MW (14)
PG2 = (6 MW/2.4 Hz) * (61.2 Hz – 60.0 Hz) = 3 MW (15)
8
Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY ROORKEE. Downloaded on January 25,2024 at 09:03:49 UTC from IEEE Xplore. Restrictions apply.