Electrical Installation-Introduction To Design by Eng. Pathum
Electrical Installation-Introduction To Design by Eng. Pathum
• Initiate a design.
Brief Begins
Clarification of outstanding
information
Advise client of
Record
Test Assumptions assumptions
Assumptions
made
Brief ends
What should contain in a design brief.
• Occupancy details of the building.
Number of workstations, if it is a office
Number of beds, if it is a Hospital
Number of machines, if it is a factory
Planning
Has the
design brief
Yes changed
No
Start Detail
Design Sample Design
A
Brief
Design development process.
A
A Does the
design meet
the DB and Re design
Planning No
Yes
Prepare drawings and
start implementation
(Installation)
Re design or revise the
installation to comply with
the design
Does
installation
same as the
No design
Yes
Testing and
Verification
Start detail design.
Start Detail
Design
Record planned
Plan permissible Refer to assigned voltage
voltage drop on
voltage drops drop in sub circuits
schematics
Determine Maximum
Demand
Yes Is max.
demand differ
Review planning & check
from planning
estimate?
No
Detail design process.
Determine the fault level starting at the initial connection point
of the cable considered & then for the start of each cable in
turn.
B
Is fault impedance
No less than maximum
permissible for the
device selected?
Yes
Detail design process.
B
Record the cable
size & impedance
Record the
Review the selection Determine the protective device to suit the
protective device
and setting. load & prospective SCC.
& switchboard
details
Do the protective
No
device discrimination
under fault condition
Yes
Detail design process.
End of Design
process
Inputs required for the design process.
• Design requirements.
Client’s specific requirements – get through the design brief.
Fire department.
Environmental authority.
• All installations after 31st December 2018 shall be complied 18th edition .
18th Edition of IEE Regulation.
Chapter 46: • Non-automatic local and remote isolation and switching measures
Isolation and
switching
Major changes in 18th Edition
Part Changes
Chapter 52: • Installation of cables
Selection and erection of
wiring systems
Chapter 53: • General requirements for Protection, isolation, switching, control and
Protection, isolation,
switching, control and
monitoring
monitoring • Section 534: Devices for protection against overvoltage.
Chapter 54: • Earthing Arrangements:
Earthing Arrangement and
Protective Conductors
411.3.2.1.
4 – Part
1 – Chapter
1 – Section
3 – Group
2 - Sub-set of Regulations
1 - Regulation
Part 1:Scope Object and Fundamental
principles.
• Chapter 11: Scope-Indicates the range and type of installations
covered by the Regulation.
Ex: Residential, commercial, public, industrial premises, external light, Low
• 313 – Supplies
Parameters of supply authority such as V, I, Hz, IPSCC, Ze shall be evaluated.
Importance of consider standby power source for safety and fire system.
Each final circuit shall be electrically separated from every other final circuit.
Part 3: Assessment of General Characteristics.
• Chapter 32 – Classification of external influences
Each condition of external influence is designated by a code.
Key factors are
Environment – Ambient temp., Altitude, Presence of water & foreign bodies, Vibration etc.
Utilisation – Capability of persons (Children, handicapped, skilled), Contact with persons
with earth potential, Condition of evacuation in emergency etc.
Construction of building – Construction of building (combustible or not), Design of Building
(Movement, fire rated)
• Chapter 33 – Compatibility
Assessment shall be made of any characteristic of equipment likely to have harmful effect
upon others. Ex. Patrol station, shop within a shop.
Due to the effect of Harmonics, leakage current, unbalanced load, high frequency
oscillations, power factor etc. must be assessed.
All fixed installation must be in accordance with EMC regulation.
Part 3: Assessment of General Characteristics.
• Chapter 34 – Maintainability
An assessment shall be made and consulted the party responsible for operation.
fundament rule is that live part shall not be accessible, and accessible live part shall
not be hazards.
Protective measures can be taken
Automatic disconnection of supply
Double or reinforced insulation
Electrical separation for the supply to one item of current-using equipment
Extra-low voltage (SELV and PELV)
• Design drawings
Schematics drawings
Single line drawings for distribution boards
Layout drawing for lighting, socket outlets
Layout drawings for generator, transformer etc.
Earthing and lightning projection drawings.
• Bill of Quantity
• Technical specification
OUT PUT OF THE DESIGN.
Drawings
Start with Design
Start Detail Design
Brief
BOQ
Standards &
Technical
Regulations specification
OUT PUT OF THE DESIGN.
• Preparation of Design calculation sheets.
Lighting selection sheets, Lux level distribution charts.
Load calculation sheets
Cable selection sheets
Short circuit calculation sheets
• Design drawings
Schematics drawings / Single line drawings for distribution boards / Layout drawing
for lighting, socket outlets / Layout drawings for generator, transformer / Earthing
and lightning projection drawings.
• BOQ Preparation
• Technical specification
Implementation and Execution
• Project implementation will be done by the project team. If there is a special reason
which require a design change, designer shall review the design again to see the
possibility of implementation.
R1+R2
Testing and Verification
• Insulation Resistance testing
Final Distribution system Industrial application
Testing and Verification
• Insulation Resistance testing
Group circuits
Testing and Verification
• Polarity testing
Visual checks where colored cables are used
Checks as part of the continuity testing using shorted out cable
Neon and similar voltage probes
Multimeters
Indicators on ELI testers and similar.
Testing and Verification
• Earth Loop Impedance test (ELI - Ze)
External ELI and Total ELI
TT 21
TN C S 0.35
TN S 0.8
Testing and Verification
• Prospective fault current testing
Testing and Verification
• Testing RCDs and other functional tests
Testing and Verification
• Testing RCDs and other functional tests
Testing and Verification
• Verification of voltage drop
Regulation 612.14 gives two methods for checking voltage drop,
either by measuring a circuit’s impedance or by checking design criteria.
The regulation only suggests doing this where it is necessary to verify compliance with the voltage drop
requirements. In practice, this will mean where there is a voltage drop problem.