Moulded Case Circuit Breakers: Standard Type (S) Higher Type (H)
Moulded Case Circuit Breakers: Standard Type (S) Higher Type (H)
NM1
2. Type designation
N M 1- □ □ □ / □ □ □ □
3. Classification
According to breaking capacity of breaker:
S H
> >> 68
Moulded Case Circuit Breakers
NM1
Front connection
Direct operation with handle Operation with rotary handle Motor-driven operation
2P 3P 4P
4. Operating conditions
4.1 Temperature: -5℃ ~+40℃ ; the average value within 24h 4.3 Pollution grade: Grade 3 ;
shall not exceed +35℃.(please refer to coefficients on P107 4.4 Air conditions :
for temperature compensation correction); for the circuit At mounting site, relative humidity not exceed 50% at the
breaker with thermo-magnetic release, +40℃ is set to be max temperature of +40℃ , higher relative humidity is
the standard temperature for ratings. For temperature not allowable under lower temperature. For example, RH could
between -5℃ ~+40℃ , please contact us for temperature be 90% at +20℃ , special measures should be taken to
compensation correction. ; occurrence of dews. .
4.2 Altitude: not exceed 2000m (Please contact with us for
reduction coefficient if altitude at the mounted site beyond
2000m). .
69 > >>
Moulded Case Circuit Breakers
NM1
5. Technical data
Frame size current 63 125 250 400 630 800 1250
Electric characteristics as per IEC 60947-2, EN 60947-2
Rated current (A) In 40℃ 10, 16, 20, 25, 30, 32, 40, 50, 60, 63 25, 30, 32, 40, 50, 60, 63, 75, 80, 100, 125 100, 125, 140, 150, 160, 175, 180, 200, 225, 250 225, 250, 300, 315, 350, 400 400, 450, 500, 630 630, 700, 800 700, 800, 900, 1000, 1250
Rated insulation voltage (V) Ui 500 800 800 800 800 800 800
Rated impulse withstand voltage(kV) Uimp 6 8 8 8 8 8 8
Rated operational voltage (V) Ue AC 50/60Hz 415 690 690 690 690 690 690
Arcing distance (mm) ≤50 ≤50 ≤50 ≤100 ≤100 ≤100 ≤100
Breaking capacity code S H C S H R S H R S H R S H R H R H
Number of poles 3 3 4 3 3 2 3 4 3 1 3 2 3 4 2 3 3 4 3 3 3 4 3 3 3 4 3 3
Rated ultimate short-circuit AC 220/230/240V 20 42 42 25 42 65 65 65 85 20 42 65 65 65 85 85 50 50 85 100 50 50 85 100 85 85 100 85
breaking capacity
AC 380/400/415V 15 35 35 20 25 50 50 50 65 _ 25 50 50 50 65 65 35 35 50 70 35 35 50 70 60 60 70 65
Icu (kA, rms)
AC 660/690V _ _ _ 3 3 _ 8 8 10 _ 5 _ 8 8 _ 10 10 10 12 15 12 12 15 15 20 20 20 20
Test sequence:O-t-CO
Rated service short-circuit breaking capacity Ics (%Icu)
50% 50% 50% 50% 50% 50% 50%
Test sequence:O-t-CO-t-CO
Isolation function ■ ■ ■ ■ ■ ■ ■
Utilization class A A A A A A A
Front connection ■ ■ ■ ■ ■ ■ ■
Rear connection ■ ■ ■ ■ ■ ■
Plug in type ■ ■ ■ ■ ■ ■
Shunt release ■ ■ ■ ■ ■ ■ ■
Under-voltage release ■ ■ ■ ■ ■ ■ ■
Auxiliary contact ■ ■ ■ ■ ■ ■ ■
Alarm contact ■ ■ ■ ■ ■ ■
Note:
The symbols O-t-Co, O-t-Co-t-Co are used for defining the sequence of operations.
O: breaking operation; t: the time interval between two successive short-circuit operations;
CO: a making operation followed, after the appropriate opening time, by a breaking operation.
5 Auxiliary contact
9
11
6
Rated current(%)
Tripping time(s)
> >> 76
Moulded Case Circuit Breakers
NM1
Rated current(%)
Tripping time(s)
77 > >>
Moulded Case Circuit Breakers
NM1
Fig.9 NM1-630, NM1-800 Characteristic Curve Fig.10 NM1-630, NM1-800 Adjustment curve of temperature
Rated current(%)
Tripping time(s)
> >> 78
Moulded Case Circuit Breakers
NM1
9. Wiring
Front connection(Fixed connection)
Extended connection terminals (for products 10~1250A, extended terminals are available) Connection screws
C B A
79 > >>
Moulded Case Circuit Breakers
NM1
Front connection screw Front connection screw
Breaking Breaking
Frame Current Frame Current
capacity Hexagonal Hexagonal Cross capacity Hexagonal Hexagonal Cross
level (A) level (A)
code head screw (A) socket screw (B) screw (C) code head screw (A) socket screw (B) screw (C)
S ■ C ■ ■
10
H ■ S ■ ■
S ■ 80 H ■ ■
16
H ■ R ■ ■
S ■ C ■ ■
20
H ■ S ■ ■
63 S ■ 125 100
25 H ■ ■
H ■ R ■ ■
30 S ■ C ■ ■
H ■ S ■ ■
S ■ 125
32 H ■ ■
H ■ R ■ ■
40 S ■ S ■
H ■ H ■
100
50 S ■ R ■
H ■ S ■
60 S ■ H
125 ■
H ■ R ■
63 S ■
S ■
H ■
140 H ■
C ■ ■
R ■
S ■ ■
25 S ■
H ■ ■
150 H ■
R ■ ■
R ■
C ■ ■
S ■
30 S ■ ■
125 160 H ■
H ■ ■ 250 R ■
R ■ ■
S ■
C ■ ■
175 H ■
S ■ ■
32 R ■
H ■ ■
S ■
R ■ ■
C 180 H ■
■ ■
S ■ ■ R ■
40 S ■
H ■ ■
R ■ ■ 200 H ■
C ■ ■ R ■
S ■ ■ S ■
50 H ■ ■ 225 H ■
R ■ ■ R ■
C ■ ■ S ■
S ■ ■ 250 H ■
60 H ■ ■ R ■
R ■ ■ S ■ ■
C ■ ■ 225 H ■ ■
S ■ ■ R ■ ■
63
H ■ ■ S ■ ■
R ■ ■ 400 250 H ■ ■
C ■ ■ R ■ ■
S ■ ■ S ■ ■
75
H ■ ■ 300 H ■ ■
R ■ ■ R ■ ■
> >> 80
Moulded Case Circuit Breakers
NM1
Front connection screw Cage clamp terminals (for products 16~630A, cage clamp
Breaking
Frame Current terminals are available)
capacity Hexagonal Hexagonal Cross
level (A)
code head screw (A) socket screw (B) screw (C)
S ■ ■
315 H ■ ■
R ■ ■
S ■ ■
400 350 H ■ ■
R ■ ■
S ■ ■ A ty pe B ty pe
400 H ■ ■
R ■ ■
S ■
400 H ■
R ■
LINE LOAD LOAD
S ■
450 H ■
LINE
LOAD
LOAD
LINE LINE
LOAD
LINE
OFF
R ■ ON ON
OFF
ON
S ■ ON
OFF LINE OFF
LOAD LOAD
630 500 H ■
(2)
R ■
LOAD LINE LINE
S ■
(1) (3) (4)
630 H ■
R ■
H ■ Modes of down-lead (1) and (2) illustrated in the figure are
630 available for your wiring operation. For its breaking capacity may
R ■
be affected, mode of down-lead (3) is not recommended, before
H ■ reception of any authorized announcement from the
800 700
R ■ manufacturer; the mode of down-lead (4) is prohibited for your
H ■ wiring.
800
R ■
81 > >>
Moulded Case Circuit Breakers
NM1
10. Overall and mounting dimensions
Fig.15a NM1-63, 125, 250 fixed connection
G1
G1
Under-voltage release
Under-voltage release
G1
H4
F F
L1
L2
C
B
E
L
E
L2
C
B
E
L
22
22
H3
6×Φ d
4×φd H
H1(max)
W1 W1 W1 W1 W1 W1
W4 W3 W W2
2P 3P 4P
(mm)
> >> 82
Moulded Case Circuit Breakers
NM1
Overall and mounting dimensions of NM1-400, 630, 800, 1250(Fixed type)
G Under-voltage release
Under-voltage release
G1
H5
H4
F F
H3
C1
L1
L2
E
E
C
B
L
22 22
4×φd 6×φd H2
H
W1 W1 W1 W1 W1 H1(max)
W W2
3P 4P
(mm)
NM1-400S NM1-630S
Dimension NM1-400H NM1-630H NM1-800H/R NM1-1250H
NM1-400R NM1-630R
83 > >>
Moulded Case Circuit Breakers
NM1
11. Accessories
Inner accessories
Handle
NM1-63S,H
NM1-125C,S,H,R
NM1-125H,R
Magnetic Compound NM1-250S,H,R
Accessory NM1-250H,R NM1-1250H
only release release NM1-400S,H,R
NM1-630S,H,R
NM1-800H, R
2P 3P 4P 3P
Shunt release,
240 340
auxiliary contact
Shunt release,
250 350
under-voltage release
Two groups of
260 360
auxiliary contacts
Auxiliary contact,
270 370
under-voltage release
Shunt release,
218 318
alarm contact
Auxiliary
228 328
alarm contact
Under-voltage release,
238 338
auxiliary alarm contact
Shunt release, auxiliary
248 348
alarm contact
Two groups auxiliary contact
268 368
of auxiliary alarm contact
Under-voltage release
278 378
auxiliary alarm contact
> >> 84
Moulded Case Circuit Breakers
NM1
11.1 Under-voltage release
a. Un=70~35% Us, reliable operation
b. Un=<35% Us, prevent breaker from making
c. Un=>85% Us, guarantee the breaker making
The rated voltage of the under-voltage release is 50Hz,
230V and 400V.
code A2 A4
voltage AC 230V AC 400V
rated frequency 50Hz 50Hz
code A2 A4 D3
Frame size Conventional heating current Ith (A) Rated current Ie (A) at AC 400 V Rated current Ie (A) at DC 220 V
85 > >>
Moulded Case Circuit Breakers
NM1
a. Auxiliary contact
F12
Circuit breaker is at “breaking” status F11
F14
F12
Circuit breaker is at “making” status F11
F14
b. Alarm contact
When circuit breaker normally makes and breaks, alarm contact
doesn't operate. After free release (or release due to failure)
alarm contact operate; and after the circuit breaker operates
again,alarm contact returns to the original status.
Making
circuit
Breaking
circuit
External accessories
> >> 86
Moulded Case Circuit Breakers
NM1
Making and breaking diagram of
motor-driven operation mechanism(AC/DC)
K2
M
1
K1 Y
X M
K2 K2 M
S3 Y
K1 K1
Making S1 2 S3
X 1 2 3 4
T S1 Making
S2 3
T S2 Breaking
Breaking
Y 20
24
D
MIN=50mm
φ61
53
φ36
45°
chain
2×φ5.5
≥200
Boring diagram of
handle mounting
(mm)
NM1-800H
Model NM1-63 NM1-125 NM1-250 NM1-400 NM1-630
NM1-800R
Mounting
49 51 54 88 89 96
size H
Y value of the
handle related
0 0 0 0 0 0
to the center
of the breaker
87 > >>
Moulded Case Circuit Breakers
NM1
Mounting and boring dimensions
A C A
B
F
8-φd
D
A breaker E B breaker
L
(mm)
Model A B C D E F L Φd
NM1-63 25 117 80 30 80 135 182 4.5
NM1-125 30 130.5 90 30 90 155 210 4.5×6*
NM1-250 35 126 100 30 100 165 240 5.5
NM1-400 44 194 136 30 40 257 330 7
NM1-630 58 200 172 48 62 270 412 7
NM1-800 70 243 167 28 40 280 448 7
Note: :
1. * stands for length of boring. .
2. Install the breaker on the frame first, then install the
mechanical interlock on the breaker. .
> >> 88
Moulded Case Circuit Breakers
NM1
12.6 Tightening torque table
Icu/Ics(kA)
Frame Number
Model Ui (V)
current (A) of poles 220V 230V 240V 380V 400V 415V 660V 690V
89 > >>
Moulded Case Circuit Breakers
NM1
Icu/Icm(kA)
Frame Number
Model Ui (V)
current (A) of poles 220V 230V 240V 380V 400V 415V 660V 690V
1 800 20/40 - -
NM1-250S
3 800 42/88.2 25/52.5 -
> >> 90
Moulded Case Circuit Breakers
NM1
12.8 Cascading
12.8.1 Cascading (220/230/240V)
Upstream: NM1-63~1250
Downstream: DZ47, eB, UB, DZ158, DZ267, NB1, NBH8, NM1-63~1250
Upstream
NM1-63S NM1-63H NM1-125S NM1-125H NM1-125R NM1-250S NM1-250H
Breaking capacity
20 42 25 50 65 25 50
(kA RMS)
DZ267 20 40 20 35 50 20 25
DZ47, eB, UB 20 40 20 35 50 20 25
NBH8 20 40 20 35 50 20 25
NB1(Icn=6000A) 20 42 25 35 50 25 35
NB1(Icn=10000A) 20 42 25 40 50 25 35
DZ158 25 40 50 25 40
NM1-63S 42 25 50 65 25 50
NM1-63H 65
NM1-125S 50 65 50
NM1-125H 65
NM1-250S 50
NM1-250H
NM1-400S
NM1-400H
NM1-630S
NM1-630H
NM1-800H
NM1-1250H
Upstream
NM1-63S NM1-63H NM1-125S NM1-125H NM1-125R NM1-250S NM1-250H
Breaking capacity
15 35 25 50 65 25 50
(kA RMS)
DZ47, eB, UB 10 15 10 15 15 10 15
NB1(Icn=6000A) 15 20 15 20 20 15 20
NB1(Icn=10000A) 15 20 20 25 25 20 25
DZ158 20 25 35 20 25
NM1-63S 35 25 50 65 25 50
NM1-63H 65
NM1-125S 50 65 50
NM1-125H 65
NM1-250S 50
NM1-250H
NM1-400S
NM1-400H
NM1-630S
NM1-630H
NM1-800H
NM1-1250H
91 > >>
Moulded Case Circuit Breakers
NM1
NM1-250R NM1-400S NM1-400H NM1-400R NM1-630S NM1-630H NM1-630R NM1-800H NM1-800R NM1-1250H
65 35 50 70 35 50 70 60 70 65
30
30
30
35
40
50 30 40 50
65
65
65 50 70 50 70 60 70 65
65 70 70 70
65 50 70 50 70 60 70 65
65 70 70 70
50 70 50 70 60 70 65
70 70 70
50 70
70
70
NM1-250R NM1-400S NM1-400H NM1-400R NM1-630S NM1-630H NM1-630R NM1-800H NM1-800R NM1-1250H
65 35 50 70 35 50 70 60 70 65
15
20
25
35 20 25 35
65
65
65 50 70 50 70 60 70 65
65 70 70 70
65 50 70 50 70 60 70 65
65 70 70 70
50 70 50 70 60 70 65
70 70 70
50 70
70
70
> >> 92