The document discusses a Digital Fault Recorder (DFR) device called the SATEC PM180. It has the following key features: 1. It can record up to 20 cycles of pre-fault information from 4 current channels and 3 voltage channels to analyze faults. 2. Faults can be triggered internally via an embedded fault detector or externally through digital inputs. 3. When a fault is detected, it records the fault waveforms and logs details like fault currents, coincident voltages, and duration to a fault log file in COMTRADE/PQDIF format for analysis in PAS software.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views1 page

SITEC-PM180-Datasheet 8

The document discusses a Digital Fault Recorder (DFR) device called the SATEC PM180. It has the following key features: 1. It can record up to 20 cycles of pre-fault information from 4 current channels and 3 voltage channels to analyze faults. 2. Faults can be triggered internally via an embedded fault detector or externally through digital inputs. 3. When a fault is detected, it records the fault waveforms and logs details like fault currents, coincident voltages, and duration to a fault log file in COMTRADE/PQDIF format for analysis in PAS software.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Digital Fault Recording (DFR)

SATEC PM180 includes true Digital Fault PAS POWER QUALITY SETUP PAS FAULT RECORDER SETUP
Recording and Disturbance Recording.
The standard device includes four current
channels for up to 20xIn (100A @ In=5A)
of fault currents. Adding the DFR module
(page 4) allows for separated connection
of measurement CTs and protection CTs
of up to 40xIn (200A). Three AC voltage
channels and one AC/ DC measurement
input channels are also included. Multiple
PM180 devices can cross trigger for up
to 20 cycles of pre-fault information for The Fault Recorder can be triggered events to the Fault Log file and to the
distributed recording. Fault information by the embedded fault detector or Sequence Of Events Log (see pg. 8).
can be exported to PQDIF/COMTRADE externally through any digital input.
The Fault Recorder setup allows you
format via PAS software. External triggers are automatically
to adjust thresholds and hysteresis for
enabled for the Fault Recorder.
The fault recorder provides 4 measured different fault triggers, and to define
and recorded currents (including When the Fault Recorder is enabled, the waveform and data log options for
measured neutral current). The event log it automatically records all internally recording fault events.
is complemented by waveform recording. detected and externally triggered fault

PAS FAULT LOG REPORT

Features
‡‡ IRIG-B/SNTP/DI time synchronization
‡‡ 256 MB memory
‡‡ Programmable fault thresholds and
hysteresis
‡‡ Up to 200 Amps fault currents (40xIn)
‡‡ Separate measurement and
protection CT connection (option)
‡‡ Zero-sequence currents and voltages
‡‡ Current and voltage unbalance
‡‡ Under-voltage, neutral current
Viewing the Fault Log
‡‡ Ready-for-use fault reports—fault
Fault log files are displayed in a tabular currents magnitude and duration,
view, one evernt per row. PAS loads the coincident volts magnitude, fault
entire database table to a window so waveforms and RMS trace
that you can scroll through the entire log ‡‡ Distance to fault calculation
to view its contents or a particular event ‡‡ Waveforms from multiple separate
loaded from the PM180 separately (for locations (via PAS)
fast loading fault).