1) The CNM provides a standardized network device for level 1 integration, replacing multiple commercial off-the-shelf switches. 2) It features a ruggedized design for hazardous environments, copper and fiber ports, and mounting options. 3) The CNM requires no configuration and supports various safety and process network topologies through a selection switch.

Uploaded by

MORO VOLCANO
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
202 views

Control Network Module - HUG2022

1) The CNM provides a standardized network device for level 1 integration, replacing multiple commercial off-the-shelf switches. 2) It features a ruggedized design for hazardous environments, copper and fiber ports, and mounting options. 3) The CNM requires no configuration and supports various safety and process network topologies through a selection switch.

Uploaded by

MORO VOLCANO
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

May 2022

CONTROL NETWORK
MODULE

RAAM THOTAKURA
SENIOR PRODUCT MARKETING MANAGER

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved.


PRESENTERS'
INTRODUCTION

Honeywell staff is expected to introduce themselves. *

Customer presenters are in principle introduced by a


customers Steering Committee member *

*info only: please remove this info from your final presentation
PRESENTATION OVERVIEW
1. Problem Statement 4. Roadmap
Current network solutions Upcoming functions
2. Introduction 5. Summary
CNM concept, design, features and Value and benefits
model numbers
3. Deployment
Installation options across systems

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 2


CURRENT NETWORK
SOLUTIONS

Problem Statement
ICSS L1 NETWORK I/O HIVE
L1 Switches
IO HIVE
• IO over Ethernet to multiple Copper Cables

controllers
• Remote IO connected over Fiber Fiber Optic Cables

• A mix of varied network devices


• Impacting project schedule and
costs

Controller Cabinet I/O Cabinets – UPC or 2 mtr

Impacting project cost, schedule – Using multiple network devices


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 4
ICSS L1 NETWORK SM-SC
SM-SC I/O network

• PUIO and PDIO are connected over


network devices SafeNet I/O network
• SafeNet connections requires
various network devices
‒ Expensive solution
‒ Complicated Limited Fiber optic options FC-SCNT01

SM-SC Cabinet Remote Safety Cabinet

Safety IO Link & SafeNet Integration over multiple network devices


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 5
ICSS L1 NETWORK CC-PCNT02/05
CC-PCNT02
CF9
• C300s are connected over Control Firewall
CC-PCNT05
• Control Firewall, CF9 acts as network
aggregator CC-PCNT02

‒ Connecting 4 C300s over ethernet


CC-PCNT05
• C300 has an embedded Control Firewall

• No external firewall is required


• Network aggregation function of CF9 is lost CC-PCNT02 Cabinet CC-PCNT05 Cabinet

New CC-PCNT05 requires multiple network devices for L1 integration


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 6
ICSS L1 NETWORK PROBLEM STATEMENT
• Increased dependence on COTS switches
• Extended switch lead times with varying costs across the globe
• IT vs OT clash sometimes resulting in plant down time
• Engineering required
‒ For switch configuration, backup & maintenance – Network specialist
• With IO HIVE, C300 (v5) and SM-SC IO L1 network integration
costs have gone up
‒ Expensive network switches
‒ Limited options for ruggedized hazardous areas which are expensive
‒ Expensive SFPs for fiber optic communication
‒ Few of the models have limited fiber optic ports

Network Cabinet

Impact on project cost, schedule and increased risks


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 7
INTRODUCTION

Control Network Module, CNM


CONTROL NETWORK MODULE INTRODUCTION
• Network Device for L1 Integration
‒ Safety Manager and Series C devices DIN/CCA
IOTA

• Ruggedized standard design: Main


Module
Expansion
Module

‒ -40 to +70 Deg C and HAZLOC installations Uplink 4 Copper


Port Ports
‒ CCA and DIN rail mounting options Selector
Switch
‒ Used in UPC/USC and Safe Area cabinet
• 12 port module – Copper Fiber Optic
‒ Single Mode – max.15 Km & Multi Mode – max. 2 Km 4 Combo
4 Combo
Ports
• Unmanaged network device Ports

• ISA Secure Compliant

Control Network Module, CNM

Standard solution - Reduced CAPEX and OPEX


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 9
CNM MODEL NUMBERS
Main Module Expansion Module Filler Plate SFP
Model Number Description

CC-TNWC01 Network Module IOTA

CC-TNWD01 Network Module IOTA - DIN Rail

CC-INWM01 Network Module - Main

CC-INWE01 Network Module - Expansion

Model Number Description


CCA IOTA DIN Rail IOTA
50154761-001 10/100M SFP Single mode 15Km (9/125um SMF)

50154762-002 10/100M SFP Multi mode 2Km (62.5/125um MMF)

50182312-001 1G SPF Single mode 10Km (9/125um SMF)

50185149-001 1G SPF Multi mode 550m (50/125um MMF)

50183493-0011 1G SPF Single mode 70Km (9/125um SMF)

HONEYWELL - One stop shop for L1 integration


Note 1: Planned for future release Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 10
CNM SELECTOR SWITCH
• Function selection switch Main Module Mode Selection

‒ 99 selections with two rotary switches


‒ Various safety and process topologies
‒ Zero configuration footprint
Mode 10 Mode 1 Functions Integration

0 1 Safety: IO Link integration Safety: L1 - SM-SC, PUIO, PDIO

0 2 Safety: SafeNet integration Safety:L1 - SM-SC to SM-SC


Main Module
Process: IO HIVE & Process
0 3 Control integration
Process: L1 - CN100, C300v5

• Device Index Selection


‒ Three rotary switches
‒ ip address setting Device Index

‒ Are not FTE indices

LEAP - One module for multiple functions


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 11
CNM FEATURES
• No additional cable/hardware for configuration
• Plug & Play – No configuration required
• Reduces human/gross errors in file handling
• Reduces engineering hours
• Zero footprint – No external UI clients
• L1 integration in standard 2 mtr cabinet
• Clear demarcation between IT & OT
• Reduced SPARES
• Single module with Fiber and Copper solutions

Plug & Play + No configuration – Reduction in engg effort and schedule


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 12
DEPLOYMENT

L1 integration with Process and Safety


Systems
CNM R100 L1 TOPOLOGY – IO HIVE
• Safe area/HAZLOC mountable
• CCA or DIN rail mountable
• Equivalent replacement for HON L1
devices integration SAFE AREA
HAZARDOUS AREA
CN100 CN100 CN100

SAFE AREA

FRONT REAR FRONT REAR

SAFE AREA
HAZARDOUS AREA

CN100 CN100 CN100

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 14


CNM R100 L1 TOPOLOGY – C300V5
• CCA mountable
• Connects C300v5 with CN100/C300s
for L1 integration
• Equivalent replacement for HON L1
device integration

15
CNM R100 L1 TOPOLOGY–SAFETY SAFENET
• Leaner solution with DIN rail
• More FO ports for remote locations
• Equivalent replacement for HON L1
Safety IO Link device integration

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 16


CNM R100 L1 TOPOLOGY-SAFETY USC
• DIN rail mount
• 4 port CNM in USC
• Allows daisy chaining of multiple USCs
• HAZLOC certified
• Equivalent replacement for HON L1
SafeNet integration

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 17


CNM R100 L1 TOPOLOGY -SAFETY SM-SC IO LINK
• Leaner solution with DIN rail SAFE AREA

• MCAR (CCA) solution for IO cabinets only


• Equivalent replacement for HON L1
SafeNet integration

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 18


ROADMAP

Functions and features timeline


Universal Marshalling Solution – Road Map

Phase 1C
• UPC and USC integration

Phase 1B Dec, 2022


• 12 Port CNM
• HAZLOC Certs

Sep, 2022

Main Module

June, 2022
Phase 1a
• 4 Port CNM
• Safe Area

Honeywell Internal
Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved.
SUMMARY

Value & Benefits


CNM SUMMARY
22

• CNM 12 port – Fiber/Copper options with standard HON SFPs


• Certified for HAZLOC and safe area usage @ extended temperatures -40 to + 70
Deg C
• Single model number used with DCS and Safety applications
− With UPC, USC, SM-SC or C300 (v5)
− L1 integration of DCS FTE and Safety Systems – IO Link and SafeNet
• Standard design across Process and Safety – Reduced spares and OPEX
• ONE STOP SHOP – Honeywell: For L1 Integration
• Project costs significantly reduced by 30%
• Extending LEAP to network integration

Reduced CAPEX, OPEX, Standard solution


Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 22
Honeywell Internal
Venkat Ramanjulu Thotakura
CNM BACKUP

Honeywell Confidential - ©2022 by Honeywell International Inc. All rights reserved. 24


Honeywell Internal
CNM USER INTERFACE
 UI is with a Web Browser on any Experion Node

 Provides the overview status

 Provides connectivity status for ports and devices

 Replaces expensive 3rd party Network Status Monitoring software like Whatssup GOLD etc