INSTALLATION
LEVEL III
Based on October, 2023, Curriculum Version II,
s
Table of Contents.........................................................................................................................................i
Acknowledgement......................................................................................................................................iii
Acronyms....................................................................................................................................................iv
Introduction.................................................................................................................................................1
References...............................................................................................................................................126
Ministry of Labor and Skills wish to extend thanks and appreciation to the many
representatives of TVT instructors and respective industry experts who donated their time and
expertise to the development of this Teaching, Training and Learning Materials (TTLM).
.
Page iii of cxlii Ministry of Labor installation and maintenance for Version -I
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Acronyms
OHS................................................................Occopational health and safety
DSL................................................................Digital subscriber line
VoIP...............................................................Voice over Internet protocol
CSP................................................................Carriage service provider
MDF ..............................................................main distributor frame
IPTV...............................................................Internet Protocol Television
TV ................................................................Television
ADSL.............................................................Automatic Data System Location
ONT...............................................................Optical Network Termination unit
PC ................................................................Personal computer
LAN...............................................................Local Area Network
RG ................................................................Radio Guide
RJ ................................................................Registered Jack
NTD............................................................... Network Termination Device
NBN...............................................................National Broadband Network
CES................................................................communication earthing system
CCP................................................................Costumer connection Premises
FTTP..............................................................Fiber to the premises
Note: When working with telephone wires and connections, there is always the possibility of an
electrical shock. It is generally recommended that premises wiring be disconnected
fromincoming telephone lines. Do this at the NID. You may also choose to lift the handset of one
Telecommunications are the means of electronic transmission of information over distances. The
information may be in the form of voice telephone calls, data, text, images, or video. Today,
telecommunications are used to organize more or less remote computer systems into
telecommunications networks.
This is a broad term that includes a wide range of information-transmitting technologies and
communications infrastructures. Examples include wired phones, cell phones, microwave
communications, fiber optics, satellites, radio and television broadcasting, the internet and
telegraphs.
Data service cabling is the wiring that connects your devices to your network and the internet. It
is essential for any business or organization that relies on data to operate.
When cabling a building for data services, it is important to choose the right type of cable and to
install it properly. The most common type of cable used for data services is twisted pair cable.
Twisted pair cable comes in two categories: Cat5e and Cat6. Cat6 cable is the newer and faster
type of cable, and it is recommended for new installations.
When installing twisted pair cable, it is important to follow these guidelines:
Use cable ties to secure the cable to walls and ceilings.
Avoid running the cable near electrical wires or other sources of interference.
Terminate the cable using RJ-45 connectors.
The following diagram shows an example of how to cable a building for data services using
switches, routers, and hubs:
There are two main types of data service cabling: copper and fiber optic
Scalability: Data service cabling is scalable to meet the needs of your growing business.
If you are considering using data service cabling, it is important to have a qualified professional
design and install the cabling system. This will ensure that the system is installed correctly and
that it meets your specific needs.
Here are some tips for choosing and installing data service cabling:
Choose the right type of cabling for your needs. If you need a high-speed and reliable
network, then fiber optic cabling is the best option. However, if you are on a budget or
need to install the cabling yourself, then copper cabling may be a better choice.
Have a qualified professional design and install the cabling system. This will ensure that
the system is installed correctly and that it meets your specific needs.
Test the cabling system after it is installed to make sure that it is working properly.
Label the cabling so that it is easy to identify and troubleshoot.
Document the cabling system so that you can easily make changes or repairs in the
future.
This way, you can refer to a specific run of cable at any point in the system, and you can put
numbers on the cabling map to refer to each individual cable run.
Wire mapping is the most basic and obvious test for any twisted-pair cable installation. For
twisted-pair cables, you must test each cable run to make sure that the individual wires within the
cable are connected properly; you can select either the T568-A or T568-B pin out configurations
for a twisted-pair installation. Because all of the pairs are wired straight through and the
difference between the two configurations is minimal, there is no functional difference between
them. However, you should select one pin out and stick to it throughout your entire installation.
This way you can perform end-to-end tests as needed without being confused by mixed wire-pair
colors. A perfunctory wire-mapping test can be performed visually by simply checking the pin
outs at both ends of the cable. However, problems can occur that are not visible to the naked eye.
A proper wire-mapping tester can detect any of the following faults: Open pair occurs when one
or more of the conductors in the pair are not connected to a pin at one or the other end. In other
words, the electrical continuity of the conductor is interrupted. This can occur if the conductor
has been physically broken, or because of incomplete or improper punch down on the IDC
connector.
Shorted pair: A short occurs when the conductors of a wire pair are connected to each other at
any location in the cable.
Short between pairs: A short between pairs occurs when the conductors of two wires in different pairs
are connected at any location in the cable.
Reversed pair: A reversed pair (sometimes called a tip/ring reversal) occurs when the two wires in a
single pair are connected to the opposite pins of the pair at the other end of the cable.
Author/Copyright
Table 1. 1 wire connection and conduit chart
Data cable
Data wiring has two components, these are:
Data service delivery
Data network cable
The three most common ways data services are delivered to the home:
ADSL (Automatic Data System Location): ADSL services are typically delivered using the
telephone cabling. So wherever you have a telephone point you can install your ADSL modem.
When you have an ADSL modem you also need to install a filter at every location where you
have a phone plugged in. If you want to install the ADSL modem in a room where you don’t
have any phone point you will need to install a phone point by extending the phone cabling from
the nearest existing phone point.
Cable Modem:cable modems are typically installed in location where there is an existing Pay
TV service outlet. The installation requires the installation of a Pay TV outlet at which point you
connect the cable modem.
Fiberis the least common but it is growing in numbers. If the home has fiber to it, then the fiber
terminates on what is known as an Optical Network Termination unit (ONT) and it has a data
port on it. Cabling from the street to the point where the ONT is installed is fiber and is typically
installed by the service provider.
Author/Copyright
In all three cases the modem supplied or the ONT will have a data port which is an RJ45 socket
and this is the port that needs to be connected to the devices you need to connect to the internet.
This is the data network cabling or LAN cabling.
Data Cable (Network cabling)
To extend the data service from the data port on the ADSL modem, Cable Modem or ONT to
your networking devices (PC, printers, TV etc.) you need to install data cabling also referred to
as LAN (low area networking)) cabling. The cabling used for data networking is similar to the
phone cabling as it is twisted pair but of a much higher quality. The cable is known as Cat 5 or
Cat 6 where Cat stands for Category.
What you need to do is decide where networking devices are and install cabling from the
location where the data modem is located to where you have your PCs or TVs that need to
connect to the internet. The cabling must be installed as a start wired configuration that is the
cabling runs from the point next to the modem uninterrupted up to where you install the outlet
next to the device that needs to be connected to the internet. So unlike the phone wiring where
you could wire from one outlet to the next, here each outlet is wired individually back to the
location next to the modem. Therefore next to the modem you will have what is known as a
patch panel. Note, if all you need to plug into the modem is one computer then you can simply
buy an Ethernet cable of the desired length and connected to between the modem and the PC.
Free to air TV
Author/Copyright
sockets, the “RG” (Radio Guide) designations have no formal status and care needs to be
exercised when selecting cables purported to be “RG6” or “RG11”. (The use of RG11 coaxial
cable is not recommended in homes.)
Today the most common type of cable used for this purpose is RG-6 Tri-shield or quad-shield
cable. The cable is terminated on television outlets. The television outlets are typically an F
connector mounted on a face plate. In cases where you need multiple television outlets then you
run the cable from the antenna to an RF splitter. The RF splitter typically has one input for the
cable from the Antenna and two or more outlets depending on the splitter.
From the splitter you then run a coaxial cable to each outlet you are installing.
‘Additional notes’ On RF splitters, there are a few different types depending on the application.
They range from very basic splitters to active splitters when you install many TV outlets
throughout the home. While most TV outlets use the F connector the Television or digital set top
box usually come with a connector known as Belling Lee so the cable used to connect from the
TV outlet to the television will need to have an F connector in one end and a Belling Lee
connector at the other end.
Author/Copyright
Figure 1. 5 Four TV outlets connected to an FTTP NTD or external TV antenna
Pay TV: The distribution of pay TV through the home uses the same type of cabling used for
Free to Air TV with some variations. The variations are:
There is no antenna as there is either a satellite dish or a cable from the street.
The cabling must be RG-6 quad shield
You may be required to use the cable and cabling connectors approved by your pay TV
provider
A Pay TV Set Top Box needs to be installed at each television where you want to have
access to Pay TV services.
In most cases the Pay TV Company will supply and install the satellite dish or cable from the
street and the cabling to the various locations where your televisions are. While you can pre-wire
for it if you do it must comply with the requirements detailed by the Pay TV Company you
choose. In many cases Pay TV services also require a telephone point so you can access movies
on demand, so if you have a Pay TV point you also need a phone plug.
IPTV: IP TV is television delivered to your home via the internet. So on any device you want to
watch IPTV on must be connected to the internet. To be connected to the internet it must be
connected to your data network.
Distributed Audio: Distributed audio refers to having the ability to have music throughout the
house where the music sources are all centralized. In every room and hallways you have a pair of
Page 15 of 142 Ministry of Labor Installation and maintenance for Version -I
Author/Copyright
speakers and you can select to have all speakers play the same music throughout the house or
have different music in different location or zones as they are referred to. You can also remotely
control the music sources and volume throughout the house. There are a wide range of
distributed audio systems in the market and therefore the cabling you need depends on the
system you are installing. When wiring a distributed audio system the first step is choose your
equipment” and check what wiring is required by the equipment you have purchased.
In summary there are a few ways to wire up the system:
Spear cabling is installed from the central equipment to the speaker location.
Cat 5 or Cat 6 cable is installed from the Central equipment to the speaker location.
Cat 5 or Cat 6 cable is installed to each room where you want the distributed audio and in
each room you have an amplifier and speaker.
1.3.1 Wire Routing Strategies
There are two standard routing strategies:
a. Continuous Loop: In this method a single wire runs from the demarcation point to a jack,
and then another wire runs to the next jack and so on, forming one continuous loop. But,
like Christmas tree lights, if the wire gets cut somewhere, all the jacks beyond the cut will
be disabled. This method may also make it more difficult to add a 2nd or 3rd line
somewhere in the house.
Author/Copyright
b. Star Pattern or “Home Run:” As the name implies each jack is wired separately and
directly to a central point where they can be connected to the telecommunications
company’s wiring. This system may take more time and use more wire, but it more easily
accommodates future growth and trouble-shooting problems.
You may find a combination of these strategies where there is a continuous loop on a floor of a
house, but each floor feeds independently to the demarcation point. In older condo and apartment
buildings you are likely to find a continuous loop, but newer buildings incorporate the “home
run” method.
1.3.2 Traditional cabling methods used for telephone and ADSL services
Traditionally, telephone and ADSL (Asymmetric Digital Subscriber Line)access points (outlets)
have been wired sequentially from an external connection point (e.g. a wall box), as shown in
Figure below. In some cases, a separate cable may be installed between an external Network
Termination Device (NTD) or a central ADSL splitter and an access point for connection of an
ADSL modem (also shown in Figure below).
Author/Copyright
Either telephone cable (two to three pairs) or data cable (four pairs) could be used with this
cabling method.
This type of cabling is often referred to as “legacy cabling” because it is a legacy from a bygone
era when telephones were the primary means of communicating with other persons outside the
home.
This method of cabling is unsuitable for new homes as it will not support modern
telecommunications services, especially data services supplied via the NBN.
Author/Copyright
devices, as shown in Figure below (some cabling providers may prefer to call the CCP a “cross-
connection point”).
Data cable (four pairs) rated at Category 5 or better must be used with this cabling method to
support both telephone and Ethernet (data) connections.
Note:Category 5 is the minimum required to support 100 Mbps Ethernet; however,
telecommunications recommends the installation of Category 6 cable as a minimum.
Figure 1. 9 Home cabling method for modern telecommunications services (e.g. NBN)
Author/Copyright
1.3.4 Telecommunications (telephone) network architecture
Author/Copyright
Figure 1. 11 Typical in building copper twisted pair network architecture
Author/Copyright
Table 1. 2 Cabling system classes and component categories
Author/Copyright
1.4.2. Coaxial cabling
Where a TV antenna distribution system is installed; the outer conductor of the coaxial cabling
may be earthed. Note: HFC coaxial cabling is separate, does not form part of the TV antenna
system and should not be earthed
1.4.3. Data cable screens
Current flow in a cable screen is a result of inductive and capacitive coupling between cable
cores and cable screens. Capacitive coupling is a source of screen and earth currents under no-
load conditions and load conditions. Inductive coupling is a major source of current under load
conditions.
Cable screens are used to control the electric field stress in the cable insulation, provide a
return path for cable neutral and fault current, and shield against electromagnetic radiation. If the
screen is earthed at both ends, it provides shielding for electromagnetic radiation.
If the cable screen is single point bonded, there is no electrical continuity, and mmf generates a
voltage. If the cable screen is bonded at both ends, the mmf will cause circulating current to flow
if there is electrical continuity. If screened data cables are installed, the cable screens should be
earthed at the CCP.
1.4.4. Metallic parts
Metallic parts such as cabling or equipment enclosures do not normally need to be earthed but
may be earthed for screening purposes or additional safety if required. In such cases, it is
important to avoid “fortuitous bonding” (accidental multiple ear thing) of components, which
may create “earth loop” currentsthat could cause noise in the cabling system. For example, if
cable screens and metallic parts need to be earthed, they should be earthed by a single connection
to a common point (such as a metallic enclosure that is earthed) and should not be earthed at any
other point.
1.4.5. Equi-potential bonding
In all cases where earthing is required, the earth should be derived from the electrical earthing
system. This is an important safety requirement to ensure that there is no earth differential at or
in the building.
Author/Copyright
Earthing should not be achieved by driving a separate earth electrode unless that electrode is also
bonded (connected) to the electrical earth electrode or is for the sole purpose of providing a
lightning protection earth for an external antenna.
Telecommunications earthing is obtained from the electrical earthing system by means of
“equipotential bonding”, i.e. by “bonding” (connecting) the two earthing systems together to
ensure that they are at “equal potential”. The equipotential bonding must be done at the electrical
switchboard either inside the switchboard itself by connection to the main earthing bar or main
ear thing conductor, or outside the switchboard by connection to the main ear thing conductor or
to the electrical earth electrode. The three allowable methods of equipotential bonding are
illustrated in Figure below.
It is important that there is a demarcation point between the electrical earthing system and the
telecommunications earthing system so that:
the telecommunications earth can be isolated from the electrical earth at a single, readily
accessible point by either a telecommunications worker or an electrical worker; and
Earthing of telecommunications equipment can be legally performed by a
telecommunications worker who is not also a licensed electrical worker.
This demarcation point will be either a Communications Earth Terminal (CET) located
outside the electrical switchboard or a distinct, removable connection device on the electrical
earth electrode.
Equipotential bonding methods
Figure 1. 12 Equipotential bonding to the earthing bar or terminal of the electrical switchboard
(method 1)
Page 24 of 142 Ministry of Labor Installation and maintenance for Version -I
Author/Copyright
Figure 1. 13 Equipotential bonding to the main earthing conductor outside the electrical
switchboard (method 2)
Author/Copyright
The equipotential bonding conductor must be at least 6 mm² in cross-sectional area (7/1.04 mm)
with green/yellow insulation. Any earthing conductor required for end-user lightning protection
purposes (such as to an ADSL NTD) must also be 6 mm² with green/yellow insulation. In all
other cases, a minimum 2.5 mm² (7/0.67 mm) green/yellow earthing conductor is required,
which must be cabled from the CET or other ear thing terminal. Earthing and bonding
conductors do not need to be installed in conduit within building cavities. The recommended ear
thing conductor arrangement for a generic cabling system is shown in Figure below.
Notes:
1. Only a licensed electrical worker may access the internals of an electrical switchboard.
2. The equipotential bonding conductor between the ear thing bar or terminal of the
electrical switchboard and the CET must be at least 6 mm² (7/1.04 mm) copper conductor
with green/yellow insulation and labeled “Telecommunications Bonding Conductor” or
“Communications Bonding Conductor”
3. The CET should be located in the telecommunications compartment of the CUE, if
provided, in accordance with Figure above or, if a CUE is not provided, the CET should
be located immediately below the electrical switchboard.
4. The ear thing conductor between the CET and the PCD should be at least 6 mm² (7/1.04
mm) copper conductor with green/yellow insulation. There is no need to label this
Author/Copyright
conductor. The total length of bonding/ear thing conductor between the ear thing
bar/terminal in the electrical switchboard and the PCD should preferably be less than 1.5
m but, in any case, should not exceed a length of 10 m.
5. The earthing conductor between the CET and the ear thing terminal at the CCP must be
at least 2.5 mm² (7/0.67 mm) copper conductor with green/yellow insulation. There is no
need to label this conductor. The length of this conductor must not exceed 135 m to
ensure that it does not exceed the maximum specified CES resistance of 1 ohm.
6. For a home networking system, an earthing terminal should be provided at the CCP. All
telecommunications earthing connections (e.g. to cable screens) should be made at the
CCP.
1.5 The work coordination with others infrastructure.
1.5.1 Clearance from other services
a. At poles and in-span: The minimum separation distances required from low voltage (230 V
AC single-phase or 400 V AC three-phase) power mains, associated fittings and terminations on
poles or in-span are set out.
b. At the building: sufficient separation must be provided at the building between the lead-in
cable attachment point and any insulated low voltage power service lead such that 600 mm can
be maintained between the power cables and fittings and the body of a person working on the
lead-in cabling. This means that if the telecommunications worker cannot safely access the lead-
in cable or attachment on the side of the cable or attachment furthest from the power cables and
fittings, a separation of at least 1200 mm will be required between the power cables and fittings
and the lead-in cables and fittings at the building..
c. Use of telecommunication poles for power mains: While telecommunication will not use
any poles installed by the customer to support the LV power mains, telecommunication will
allow telecommunication -owned lead-in poles to be used to support the customer’s low voltage
(LV) power mains (i.e. 230 V AC single-phase or 400 V AC three-phase) under the following
conditions:
Over any private land not traversable by road vehicles--------------------- 2.7 m
Over any residential driveway --------------------------------------------------3.5 m
Over any commercial/industrial driveway or private roadway ------------4.9 m
Author/Copyright
The power mains, associated fittings and terminations must be separated from the aerial
telecommunication cabling, associated fittings and terminations by the following minimum
distances:
Insulated power mains -----------------------------------------At the pole 600 mm
------------------------------------- In span 600 mm
Un insulated power mains -------------------------------------At the pole 1200 mm
---------------------------------In span 600 mm
Light fitting, stay fitting or power conduit ------------------At the pole 50 mm
Author/Copyright
1.6 Material, Tools, equipment and testing devices
1.6.1 Materials
Author/Copyright
b. Coaxial cable elements
Page 32 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Splitters are used to provide two or more access points (outlets) in the home. Cables to multiple
outlets cannot be simply connected together like telephone cables, as this will cause impedance
mismatches, signal reflections and excessive signal loss. Splitters provide a proper termination
for each cable maintain impedance balance and also provide some isolation (called “RF
isolation” or “mutual isolation”) between the outputs of the splitter to prevent mutual
interference between the output cables and the equipment connected to them.
Because splitters divide the signal, they incur signal loss between the input and each output leg.
For example, if the signal is split two ways, each output leg should get half the input signal level,
which equates to a 3 dB loss between the input and the output.
Typical RF splitters
Page 33 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 21A domestic “multiswitch” for distribution of satellite TV and other RF sources
Page 34 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 23Some F-type adaptors
Socket type
8-position 8-contact (8P8C) modular sockets (commonly called “RJ45”) should be used for all
voice/data TOs to ensure compatibility with consumer Ethernet equipment (other types of socket
are available but may not be compatible with RJ45 plugs). The TO sockets should be rated to
match or exceed the cable rating (e.g. if Category 6 cable is installed, the sockets should be rated
at Category 6 or Category 6A).
6-position (6P) modular sockets (commonly called “RJ11” and used for telephone equipment
connections) should not be used as these will negate the generic nature (flexibility) of the cabling
system.
Figure 1. 24typical modular sockets and a typical to with two colour-coded sockets
Page 35 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 25 Socket Terminal unit
a. Cable Stripper
Page 36 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Cable strippers themselves are inherently relatively safe due to their design. Only use them on
the materials they are intended to strip and they will last a long time.
Cable strippers designed for use on coax can be used on structured cables with care.
A coaxial cable stripper has two appropriately spaced cutting blades to prepare the cable for
termination in the connector. A coaxial cable stripper may have adjustable blades for use with
different types of cable. A stripper with incorrect blade settings can score the center conductor or
remove excess outer conductor and degrade cabling performance. A stripper with fixed blades
designed exclusively for use on the type of cable being installed is recommended.
b. Wire-Map Tester
Page 37 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 29 Wire-Map Tester
c. Pair Continuity tester
d. Voltage Meter
There is a right way and a wrong way to determine if an electrical circuit has a live voltage
on it. Touching it is the wrong way. A simple voltage meter such as the one pictured in
Figure 6.18 is a much better solution, and it won’t put your health plan to work. Though not
absolutely necessary in the average data-cabling tool kit, a voltage meter is rather handy.
Page 38 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 31 voltage meter
A punch down tool, also called a punch down tool or a krone tool (named after the KRONE
LSA-PLUS connector), is a small hand tool used by telecommunication and network
technicians. It is used for inserting wire into insulation-displacement connectors on punch
down blocks, patch panels, keystone modules, and surface mount boxes (also known as
biscuit jacks)
RF field strength meters are an essential tool to test signal strength (“RF power level”) and signal
quality at the RF source, wall plates and intermediate points where necessary. Different meters
are generally required to measure HFC (Cable internet/pay TV), TV antenna (and FTTP NTD)
Page 39 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
and satellite signals — although some meters are available that are capable of testing more than
one type of RF source.
Figure 1. 33 meter with a monochrome LCD display and meter with a miniature colourTVscreen
g. Cable cutter
Coaxial cable should be cut squarely prior to termination using a cutting tool that does not
appreciably distort the end of the cable so that it may be properly prepared using a cable stripper
designed for the purpose. Coaxial cable cutters have concave cutting jaws that tend to slice,
rather than crush, the cable.
Page 40 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 1. 34 cheaper cable cutter and cutter for use on copper-clad steel
h. Compression tool
Compression Tools are a type of utility software. Furthermore, these tools help us to compress
and decompress files. An important part of a computer is storage space, it is very important to
maintain this storage. Therefore, we use compression tools to compress big files and decrease
their size.
Page 41 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Test equipment must be in correct operating order. To maintain insulation resistance insulation must
be clean and in very good condition. Ensure that any calibrated equipment is in current test date.
Testing devicesis generally more fragile than ordinary hand tools and more care must be taken.
Always return it to its protective case, keep clean and dry and do not use cleaning chemicals as
this may damage the plastic and seals, use a clean dry cloth.
1.8.4 Tone Generators and Amplifier Probes
The Tone Generator applies a tone signal to a wire pair or single conductor. Amplifier Probe will
trace wires and cables allowing for pin-point identification in cable bundles, a cross connect or
remote end. Cable Tracing Kit is ideal for twisted pair, coax and de-energized AC wiring.
Page 42 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Self-Check -1
Directions: Answer all the questions listed below. Use the Answer sheet provided in the next
page:
Part I. Choose the best answer from the question below
1. Which of the following is the most useful piece of cabling system documentation?
A. cabling map B. cable connector C. wiring system D. all
2. Which of the following is the most common twisted-pair cable for LANs?
Part II. Say true and false for the following question below
1. Straight through cables cables have identical ends and are used for connecting
computers through a hub/switch.
2. UTP is susceptible to crosstalk, radio and electrical frequency interference.
3. Signal cable is used in data transmission applications that demand superior signal
protection.
4. Crossover cables are used for connecting the same devices directly with each other.
5. UTP cable are used for data service and Telephone wiring.
PartIII. Answer the correct for the following question below
Page 43 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Operation sheet 1
Operation Title: Identifying RF splitters
Instruction: Using the types and application of splitters Identifying RF splittersUsed in
telecommunication and data service for TV coaxial cable installationinstructor
must check the installation before you applies power.
Purpose: When you have completed this Unit, the trainee should be able to identify the
equipment used in TV coaxial cable installation.
Required tools and equipment: unit one of this module, tools from workshops like screw
drivers, pliers, measuring instrument,
Precautions:
Safe handling of hand tools, testing instruments and components
Procedures:
Step 1: Properly identify TV coaxial cable installation RF splitters
Step 2: Prepare electricalequipment for the given task
Quality criteria: Reading the circuit properly, safety procedures were followed & all hand tools
were cleaned.
LAP Test 1
Page 44 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Name: __________________________ Date: ____________
Time started: ____________________ Time finished: _______________
Instruction I: Given necessary templates, tools and materials you are required to perform the following
tasks within 1hour.
Page 45 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
following content coverage and topics:
This unit will also assist you to attain the learning outcomes stated in the cover page.
Specifically, upon completion of this learning guide, you will be able to:
Allow sufficient cable ends to facilitate termination and tie Cable safely without
damage the sheath.
Page 46 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Structural support and cable management for catenary systems are two important considerations
for ensuring the safe and reliable operation of these systems.
Structural support
Catenary systems are typically supported by a series of structures, such as poles, towers, or
gantries. These structures must be strong enough to support the weight of the catenary wires and
any associated hardware, as well as any additional loads that may be applied, such as wind,
snow, or ice.
The structural support system must also be designed to allow for the thermal expansion and
contraction of the catenary wires. Catenary wires can expand and contract significantly due to
changes in temperature, so it is important to provide enough slack in the wires to accommodate
this movement.
Cable management
Catenary wires must be carefully managed to ensure that they are properly tensioned and
aligned. This is important for maintaining the electrical conductivity of the wires and preventing
them from contacting other objects.
Catenary wires are typically supported by a series of hangers, which are attached to the structural
support system. The hangers must be spaced at regular intervals and adjusted to ensure that the
wires have the correct tension.
The catenary wires must also be aligned to prevent them from arcing or contacting other objects.
This can be done by using insulators and spacers to keep the wires at a safe distance from each
other and from any other conductive objects.
Additional considerations
In addition to structural support and cable management, there are a few other considerations that
should be taken into account when designing and installing a catenary system. These include:
Grounding: Catenary systems must be properly grounded to prevent the buildup of static
electricity and to protect workers and equipment from electrical shock.
Lightning protection: Catenary systems must be protected from lightning strikes. This can be
done by using lightning rods and surge suppressors.
Page 47 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Maintenance: Catenary systems must be regularly inspected and maintained to ensure their safe
and reliable operation. This includes checking the condition of the structural support system, the
catenary wires, and the hangers.
Page 48 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
b. Use of Steel Trunking
While using steel trunking it is important to ensure that:
All trunking is free from sharp edges and projections likely to cause damage to the
cables contained.
All bends, tees, etc. is of radius or gusset type suitable to allow the installation of
the cables without exceeding the cable bending radii.
Fixings are spaced according to the manufacturer’s recommendations.
All lengths of Steel trunking are earth bonded to meet the 16th Edition IEE
Regulations.
New steel conduits should be able to accommodate a 50% increase in occupancy at
installation.
Newly installed steel trunking shall be selected to have 50% spare capacity after
completion of the works.
c. Use of Cable Trays
In using cable trays the following should be considered:
A. All bends, tees, etc. shall be radius or gusset type suitable to allow the installation of
the cables without exceeding the cable bending radii.
B. Fixings shall be spaced according to the manufacturer’s recommendations.
C. All lengths of Cable Tray shall be earth bonded to meet the 16th Edition IEE
regulations.
D. New cable trays shall not be no more than 50% occupied at installation.
E. Cable trays shall be perforated galvanized mild steel sheet.
F. Minimum steel thickness for cable tray shall be:
1.0mm for trays up to 150mm wide and
1.2mm for trays up to 300mm wide
G. Trays shall have folded edges with minimum height of 20mm.
H. Electrical continuity shall be maintained along the full length of cable trays.
d. Use of Cable Basket
Page 49 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
All bends, tees, etc. shall be radius or gusset type suitable to allow the installation of the
cables without exceeding the cable bending radii.
Fixings shall be spaced according to the manufacturer’s recommendations.
All lengths of Cable Basket shall be earth bonded to meet the 16th Edition IEE
Regulations.
New cable trays shall not be more than 50% occupied at installation.
Page 50 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Review any property documentation (e.g. building plans, electrical specifications, and
plumbing plan).
Visually inspect the site noting the location of conduits, pipes or cables emerging from
the ground at buildings, sheds, swimming pools, fountains, electric barbecues, garden
lights, external power outlets, etc.
Visually inspect the footway and verge for the location of any power, water, gas’
sanitation, storm water, drainage or telecommunications facilities (e.g. pedestals, pits,
poles, meters, kerb markers, drains, conduits/pipes, cables).
Ascertain the likely path of underground services using the above indicators.
Verify the location of services using a cable locator or similar equipment, if available
(note that existing services may not have been installed in a straight line).
Verify the presence or absence of underground services at appropriate points along the
chosen trenching route by careful hand digging.
Where there is evidence of underground services along the chosen trench route but their
position cannot be verified with reasonable accuracy, look for a more suitable route or
excavate by careful hand digging where uncertainty exists. Apply the following precautions
when digging the trench:
Allow for at least one 1 m separation from any suspected underground service.
Except where otherwise required by this document, keep at least one 1 m away from
any pole (to avoid disturbance of the pole footings and to allow for future
replacement of the pole without disturbing the lead-in cabling that will be installed
in the trench).
When hand digging, use non-conductive tools (e.g. with wooden handles) and wear
insulating (rubber) boots.
Do not dig the trench any deeper than the recommended depth (see Table below)
Page 51 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Table2. 2 Trench depth required telecommunication cable wiring
Page 52 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 2. 1use of catenary wire supported to building structure
In telecommunication systems with peripheral equipment powered directly from mains, the
system is earthed via all protective conductors (PE) and via the functional earth conductor (FE).
This arrangement fulfils the requirements against electrical shock.
1. Telecommunication room conductor (TRC) and Protective earthing (PE)
The TRC and the PE must be connected to the equipment on separate terminals, in
accordance with the individual TRC and PE requirements. The manufacturer will indicate
this in the installation manual.
2. TRC or PE Either a PE or a TRC must be connected to this equipment. However in some
uses of the type of equipment, a TRC must be used. (E.g. a CAE mounted behind another
CAE may need earth recall to access the first CAE.
Communication Earth System (CES)
Communication Earth System as defined in AS/CA S009:2013 may be used for any functional or
PE reference. Where either a TRC or a protective earth or both TRC and PE are specified, the
CES can be substituted for these requirements. If a TRC is specified and the CES in not suitable
(noisy, etc.) a TRC compliant to AS/CA S009:2013 will need to be installed.
Reinstalling Recovered CAE
Page 53 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
If a system is recovered from an installation, which originally required aTelecommunications
Service Earth (TSE) – then that system, when reinstalled must use the TRC in place of the TSE.
2.3 Cables and wires handling
General guidelines
While running or installing cables it is important that the following general guidelines are
adhered to;
All UTP cables are to be run internally to the building and must not run between buildings;
No UTP cable is to be run on the exterior of any building;
No cabling is to be run in lift shafts or airflow areas;
A comprehensive survey or an assessment of the cable routes shall be agreed upon prior to
installation of the cable;
All vertical cables shall be secured to installed trays at intervals as recommended by the
cabling manufacturer;
Care must be taken to avoid close proximity of cabling to water pipe work.
2.3.1. Walls and Floors
The following guidelines shall apply to cable runs made through walls and floors;
Holes drilled through walls and floors for the routing of cables shall be suitably covered
to prevent damage to the installed cables. Where cables pass through floors, such
protection shall be extended to at least skirting height.
Where cables, trunking, tray-work or conduit pass through floors or walls, suitable fire
sealing shall be provide
b. Care shall be taken not to distort the twists by excessive pulling or bending of
cables.
Page 54 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
c. Cable bundles shall not rub on or be unduly compressed against or by any cable tray,
building or enclosure penetrations, equipment racking, or other cable support.
Similar forms of protection shall be provided where cables traverse sharp edges.
e. At minimum Cat 5E cables shall be securely fixed to cable trays using Velcro or
manufacturer recommended cable ties only.
f. Cables shall be neatly grouped together based on their destination and bound at
regular intervals.
g. Where cabling is run in cavity walls, surface mounted ducting and similar
enclosures, cables shall be installed in areas free from protrusion of screws and
similar fasteners
h. Care shall be taken to avoid tight twisting of the cable, tearing of the outer jacket,
cutting or wearing through due to abrasion of the cable.
i. When drawing cable through underground conduit, care must be taken to ensure that
the conduit is clear of water and other obstacles and appropriate action taken to
protect the cable from water and soil damage. Cable ends must be sealed
appropriately when being drawn though underground ducts.
2.4.2. Segregation
A. Care shall be taken to ensure UTP Cat 5E cables are not routed adjacent to other services
where electro-magnetic emissions may be generated. UTP Data cable must never be run
in the same containment as mains voltage cables or fire alarm circuits. Where data cables
are run in trunking containing mains cables and outlets the data cable must be segregated
in a separate part of the trunking.
B. Minimum segregation distances shall also comply with the standards laid down by the
cable manufacturer
Page 55 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
C. Cat 5 E (4 pair UTP) cables shall be kept in separate bundles from the multi-pair voice or
fiber cable.
2.5 Install Cables in accordance with telecommunication regulation
1. The minimum horizontal cable bend radius, under no-load conditions, shall be four times
the diameter of the Category 6 cable. The minimum inside bend radius, under no load
conditions, for 4-pair UTP patch cable shall be .25 inches.
2. The maximum tensile loading shall not exceed 25 pounds on the Category 6 cable.
3. Cable ties shall not be installed as to place a strain or compression on the cable jacket.
4. Cables that serve several adjacent rooms shall be grouped together into bundles. A single
large cable bundle is preferable to several small bundles. It is preferred that the cables be
grouped in a way that reduces the quantity of bundles.
5. Cables in service areas such as attics, crawl spaces, mechanical chases, and above lay-in
ceilings shall be held in place with metal J-hooks or cable tray. The J-hooks shall keep
cables neatly bundled and shall be located so as to reduce interference with future
maintenance and construction projects. Cables shall be mounted at least 1' above drop tile
ceilings, shall never lie on the ceiling, and shall always be supported every 4 feet.
7. Electrical or other tape, used for bundling cables during installation, shall be removed
once the cables are in place, to allow the slack in individual cables to be more easily
removed. Duct tape should not be used for this purpose.
Page 56 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
8. It is preferred that pull string be left in conduits, cable trays and cable hooks, after initial
cable installation, to allow for future cabling needs. Pull string shall be left in places that
will be difficult to access in the future.
9. Cables that are part of a bundle shall be of uniform length. Uniform cable length is
achieved by pulling on individual cables in a bundle after the bundle has been placed in
the hooks or raceway and before the cables are terminated.
10. Cable bundles shall hang with minimal tension between the hooks. Check cable bundles
to verify that individual cables do not have excessive tension, or are supporting the
weight of several other cables.
11. At vertical to horizontal transitions, cable bundles shall have a uniform loop containing
one to three feet of recoverable slack. Additional hooks may be required to support this
slack.
12. Long open vertical runs shall require intermediate support. These shall support the weight
of the cable between horizontal transitions. One foot of slack shall be left at each strain-
relief hook so as to insure proper loading of the hooks. Vertically mounted cable tray is
preferred for long vertical runs.
13. Four inches of service slack shall be left at each outlet box.
14. Twenty-four inches of recoverable slack in each cable shall be neatly bundled and
secured in the vertical wire management units located adjacent to the patch panel rack.
15. Slack or extra cable not mentioned in this section is unacceptable and shall be eliminated
prior to termination.
16. Patch cables will be neatly dressed in wire managers from the patch panel insert to
network switch and telephone patch panel. The upper one-half of a patch panel will have
patch cables go directly up to the horizontal wire manager, then right or left to the
vertical wire manager, then up or down to the network switch. The lower one-half of the
patch panel will have patch cables go directly down to the horizontal wire manager, then
right or left to the vertical wire manager, then up or down to the network switch
Page 57 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
2.5.2 Manufacturers Recommendations
B. Cable bundles shall not obstruct the installation and removal of equipment within
equipment enclosures.
C. Jumper wires on wiring frames shall follow clear paths to minimize jumper
lengths and avoid obstructing jumper fields.
D. Equipment and patch panels shall be laid out to minimize patch cord length. Patch
cords shall follow clear paths to avoid patch field obstruction.
Power problems can be traced to various sources. The most dramatic ones are natural disasters as
they completely knock out the power supply by severing the utility lines. The less dramatic
sources include overburdened circuits, the introduction of unseen threats, such as surges,
brownouts, and line noise.
Therefore, every unprotected line that enters the equipment, whether it carries data or power,
represents a potential conduit for power problems.
Surges and spikes refer to the short-term voltage increases. They cause data corruption,
catastrophic equipment damage, and incremental damage that degrade the performance of the
equipment. Surges and spikes occur mostly due to lightning strikes, thunderstorms, ground
faults, and sudden power restoration after an outage.
Surge Protection
Page 58 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Surge protectors trap the voltage that exceeds certain limits.When spikes occur for certain
duration of time, a trapping device known as a Metal Oxide Varistor (MOV) that is present in the
surge protector gets activated. Every surge protector has an MOV, which helps in diverting the
surge current.
The lifespan of an MOV shortens with use as more surge currents are diverted. They do not
display any indication of wear and tear, nor do they provide any forewarning of failure. So, when
they suddenly fail, their temperatures increase rapidly and cause fires.
Most surge protector’s function as a power strip even after their surge trap mechanism is
degraded by power spikes.
This can cause the following dangers:
If another power surge occurs, it damages the equipment that is plugged into this surge
protector.
If sufficient voltage passes through the surge protector during a second power spike, a
resistant short is formed that produces heat and can lead to fire.
Page 59 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Self-Check -2
Directions: Answer all the questions listed below.
Part I. Choose the best answer from the question below.
1. Which of the following is used for cable supports?
A. PVC trunking B. Steel Conduit C. steel trunking D all
3. _________are wire or chain hung and supported at its end, such as wires used in
decorative lighting, electrical cable suspension, train lines and fiber optics.
A. Wire mapping B. Catenaries C.Segregation D. cable support
4. _____________must never be run in the same containment as mains voltage cables or fire
alarm circuits.
A. UTP Data cable B. Telephone cable C. Coaxial cable d. all
Part ll. Say true and false for the following question below
1. New PVC pathways shall not be more than 50% occupied at installation.
2. All trunking is not free from sharp edges and projections likely to cause damage to the
cables contained.
3. New cable trays shall not be more than 50% occupied at installation.
4. No UTP cable is to be run on the exterior of any building.
5. The lifespan of an MOV shortens with use as more surge currents are diverted.
Page 60 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Unit three: Termination and testing of cables and earth wires
This learning unit is developed to provide the trainees the necessary information regarding the
following content coverage and topics:
Page 61 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Referring direction for non-routine events
Checking and rectifying Routine quality termination of cables and devices.
Page 62 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 3. 1 Cable sheath for correct termination length UTP cable for installation
Coaxial cable is a type of transmission line, used to carry high-frequency electrical signals with
low losses. It is used in such applications as telephone trunk lines, broadband internet networking
cables, high-speed computer data busses, cable television signals, and connecting radio
transmitters and receivers to their antennas. It differs from other shielded cables because the
dimensions of the cable and connectors are controlled to give a precise, constant conductor
spacing, which is needed for it to function efficiently as a transmission line
Figure 3. 2 Cable sheath for correct termination length and connection for coaxial cable
Page 63 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
3.2 Terminating modules (cables pairs) with recommended color code
Terminating the cables involves installing some kind of connector on each end (either a
connector or a termination block) so that the cabling system can be accessed by the devices that
are going to use it. This is the part of cabling-system installation that requires the most
painstaking attention to detail, because the quality of the termination greatly affects the quality of
the signal being transmitted.
Though many termination methods are used, they can be classified one of two ways: connect or
patch-panel termination. There are many different types of patch panels, some for copper, some
for fiber. Coppercable patch panels for UTP all have a few similar characteristics, for the most
part.
Page 64 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 2: Insert cable into stripping
tool to the desired strip length.
Strip off only as much cable jacket
needed to properly terminate the
pairs (1 to 1½ inches should be
sufficient to terminate pairs).
Step 3: Holding the cable near the
tool, rotate the tool around the
cable several times.
Page 65 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 6: Remove the rip cord,
binder or crossweb filler if they
are present on the cable, leaving
only the twisted pairs of wire. The
cross-web filler should be cut as
flush as possible to the jacket.
Page 66 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 9: Insert wires down into
IDC terminal slots to position
them before punching down.
Maintain the twist. To “future-
proof” an installation, terminate
all four pairs. The Picture above
shows an outlet being wired to the
T568B wiring scheme.
Step 10: When using a punch-
down tool, make sure the tool is
straight before punching down on
the connector. Make sure the cut-
side of the tool is facing outward.
Step 11: Inspect the connector to
verify that the wires are fully
engaged in the IDC terminals and
they are cut properly.
Page 67 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
b. How to wire Ethernet Cables (data cables for Cross over connection)
The following procedure elaborates the Cross over connection procedure at RJ 45.
Things you'll need:
Page 69 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 4: grasp the wires with your thumb and
index finger of your non-dominant hand.
Take each wire and snug them securely side
by side
Page 70 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 3. 3 crossover cable color code for both end of cable
c. How to wire Ethernet Cables (data cables for straight through connection)
Instructions to prepare a straight through cable
Things you'll need:
RJ-45 Crimp Tool
Cat-5e Cable
RJ-45 Jacks
Table 3. 3 procedure elaborates the straight through connection procedure at RJ 45.
Page 71 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 2 Splice the end by using the splicing
blades to expose the unshielded twisted pairs.
Page 72 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 7 once the first head is made, repeat steps
two through eight. When untwisting the wires
down to sing strands, use the following order:
Striped Green, Green, Striped Orange, Blue,
Striped Blue, Orange, Striped Brown, and
Brown.
Page 73 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Figure 3. 4 Terminating Category 5 or Category 6 cable on a socket
Page 74 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
There are no mandatory requirements for cable sheath colours. However, cables with red sheath
should not be used, as red is normally associated with fire detection/alarm systems. Also, cables
with orange, white, pink or violet sheath should be avoided as they may be mistaken for power
cabling or cabling associated with power control (“home automation”).
It may be beneficial to the installer to use cables with different sheath colours (e.g. blue, grey,
yellow, green) to cable different sockets on the same TO. Alternatively, the cable sheaths may be
marked at each end with the TO socket colours, e.g. “Blue” and “White”, for the corresponding
socket colours, if different coloured sockets are to be used at each TO. In addition, mark the TO
cables at each end by room designation (e.g. “Kitchen”, “Family”, Bed 1”, etc.) or in numerical
sequence (i.e. “1”, “2”, “3”, and so on). The TO wall plates and the corresponding patch panel
sockets at the CCP should be coloured and designated in the same manner so that the end-user
will be able to readily identify them.
Page 75 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
It is called “Cat 5” cable and is the national standard for all new telephone wiring projects.
Step:3. Fasten the jack casing securely to the wall or baseboard using the appropriate metal or
wood screws. Pull the wire through the opening in the jack casing and connect it as depicted here
Step 4.4-Pair Wire Connection: A 4-pair cable is wired to a standard jack as shown in the 3-pair
wire diagram above but also leaving the brown wires aside.
Step 5. Match each colored wire to the appropriate terminal on the jacks as shown inthe
diagrams. In the old standard color scheme the first pair has one greenwire ("tip") and one red
wire ("ring"). The second pair has one black wire("tip")and one yellow wire ("ring"). For a single
Page 76 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
phone line, only the green andred pair is normally used. The black and yellow pair is normally
spare and available to install a second phone line.
Step: 6. Ensure that no copper wire is touching any exposed metal inside the jack or electrical
box.
Step: 8. Place the jack cover over the casing and either snap or screw it into place.
Step :9. Strip the wire sheath and colored wires the same way you did for the jacks.
Step: 10. Connect the wires that come from each jack location to the entry wiring at the
demarcation point. Be sure to match the colors correctly
.How to wire coaxial Cables
Page 77 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Table 3. 4 coaxial cable preparation and compression connector termination
Page 78 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 4: Flare and bend back the remaining
outer braid onto the cable outer jacket.
Make sure to remove any stray or loose
braids. Stray or loose braids can cause
shorts if they touch the center conductor.
Verify that the center conductor and the
insulation are not nicked or scored.
(Note: When handling cables with multiple
braids, such as quad-shield, refer to the
manufacturer’s literature for proper braid
handling techniques.)
Step 5: Insert the sleeve ferrule and BNC
body onto the coaxial cable. Firmly push
the
cable as far as possible or until 1⁄8inch of
the center conductor is protruding from the
connector.
• Make sure the connector is fully seated
and the white dielectric Material is firmly
pushed against the inner stop of the
connector .You can see this by looking into
the open end of some connectors.
Page 79 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
Step 6: Insert the cable and connector into
the crimping device, making sure that it is
positioned firmly. Squeeze the crimp
handle tightly. Use a ratcheting tool that
does not release until the proper crimping
displacement has been applied for the
specific cabling and connector type. Once
the tool releases after the final “click,” the
crimp should be complete.
Step 7: Inspect the connection making sure
no braiding is exposed and that the
connector is firmly attached to the cable.
Page 80 of 142 Ministry of Labor installation and maintenance for Version -II
and Skills October , 2023
Telecommunication and data services cable
Author/Copyright
3.3 Terminating conductors
A wire termination is the work performed to the end of a wire that allows it to connect to a
device (connector, switch, terminal, etc.).
Solder termination. Solder termination is when the open connector is melted and sealed to create
an extremely strong bond, thus forming a permanent connection.
Crimp termination. A crimp termination is performed when the device requires a contact or
terminal. The wire insulation is stripped, and the contact or terminal is attached to the wire using
a crimp tool. The tool crimps the contact or terminal onto the wire conductor.
CCTV operates in a lower frequency range than CATV and requires different cable
constructions. Be sure that the cable used is chosen accordingly. The primary differences are
based on the frequency range differences as shown below
Table 3. 5 Types of Conductor
Cable shields are for signal protection from external influences. This is of a protectivenature not a
functional one associated with the operation of equipment. Hence shields and drain wires shall not
be connected to the TRC except where the TRC is equipotential bonded to the main earthing
bar,Conductor or electrode. The cable shield may be connected to any point on the CES.
Earthing Telecommunication Systems
Definition
The Communications Earth System (CES) is a dual-purpose telecommunications earthing
system used for both functional and protective purposes. Earthing conductors used for this
system have green/yellow insulation. The CES is available for any communications system that
requires and earth, fire, security, data, video or voice equipment/cabling etc. CES wires are
Green/Yellow earthingcolours. The Shield or drain wire of cables is connected to this earth and
the punch down module used for earthing is coloured green.
Figure 3. 6 punch down module
The ‘designated distributor’ is a distributor, near the main or first electrical switchboard in the
building, designated by the cabling provider as the most appropriate distributor for distribution of
the TRC system. Where surge suppression devices are installed at the designated distributor, the
total earthing conductor length between the device and the main earthing bar in the electrical
switchboard should not exceed 10 m. A total earthing/bonding conductor length of 1.5 m or less
is preferred for more effective end-user protection and for protection of customer equipment
connected to the telecommunications line.
TFEE Definition A Telecommunications Functional Earth Electrode (TFEE) may be provided
for operational purposes or to limit the direct current flowing in the communications bonding
conductor.
3.5Test and clearly labels of cable pairs
Ensure that your inside wire is connected properly at the demarcation point. You can determine a
lot about the trouble by listening to sounds on your telephone line:
Static:Wires could be wet or pierced. Wires could be loose at a connecting point. Carefully
check all wires and connections.
Buzzing or Humming:A wire may have come into contact with metal, other than the connection
terminals. Is any exposed copper wire touching the box or other metal around the jack? Check
that colors have been matched correctly. Also, if you are using a cordless phone, you should try
plugging in a wired telephone to ensure that the problem is not with your equipment. Given the
nature of a cordless phone, it is possible that buzzing or humming is coming from the phone
itself and not your wiring.
Dead Air:Wires may be crossed. Is there a contact between any exposed copper from wires of
different colors (red crossed with green if 2-pair wire is being used; or blue crossed with white if
3-pair wire is being used)
Cross Talk:Be sure you are not using a cordless phone, since cross talk is likely from the
wireless nature of the phone. If you have multiple phone lines in the home or are in a multi-unit
dwelling, cross talk could be the result of damages or faulty wiring.
Check that all connections have been made properly.
Are all the colored wires connected to the right terminals?
Is the exposed copper wiring making a solid contact with the right terminals?
Check the wire. Is it broken or split?
Is it pierced by a staple, nail, screw or other object?
The second method for determining the length of a cable is to measure its resistance using a
digital multimeter (DMM). All conductors have a resistance specification, expressed in ohms per
meter (or sometimes ohms per 100 meters or ohms per foot). If you know the resistance
specification for the conductor per unit of length, you can measure the cable’s resistance and
divide the result by the manufacturer’s specification to determine the cable’s length. In the same
way, if you already know the length of the cable from a TDR test, you can use the rating to
determine the cable’s total resistance.
Environmental factors can affect resistance as can the cable’s design and improper installation.
Resistance increases with temperature, so your length calculations will suffer accordingly if you
are measuring in a high- or low-temperature environment too far from the 20˚ C (68˚ F)
temperature the resistance specification is based on. The twist intervals of the pairs also will
influence your resistance measurement. Because the twists increase the actual length of the
conductors, the resistance reading will be higher and result in a longer-than-actual cable length.
And, if the conductor was stretched during installation, high resistance readings will result, again
producing longer-than-actual lengths for the cable.
Figure 3. 10 TDRs are also used to locate breaks and other faults in a cable
Tester OPEN Pulse Reflection
c. Performance Testing
The tests we’ve discussed so far all relate to physical properties of the cable and ascertain if the
cable has been terminated properly and is an acceptable length. They can be performed quickly
and with relatively unsophisticated and inexpensive test devices. They are the basic, minimum
levels of testing that should be performed to ensure your network will work.
But to properly characterize your cabling’s performance, a battery of transmission tests must be
administered; they determine the data-carrying capability of your cables and connectors.
The following characteristics were all defined in Chapter 1, so we won’t explain them further
here other than to note issues related to their testing.
All of the copper-cable tests discussed in the following sections, except for Propagation
Delay and Delay Skew, have formula-based performance requirements along a continuous
frequency spectrum. In the case of Category 5 and 5e, this range is 1MHz through 100MHz.
For Category 6, requirements at additional frequencies up to 250MHz are specified. If at any
point along the spectrum the cable exceeds the specification limits, the cable fails. This is called
sweep testing because the entire frequency range is being scanned.
Testing for transmission performance requires much more sophisticated equipment than
that used for wire mapping, opens, shorts, and crosses—equipment that can cost several
thousands of dollars per test set. However, the testing is essential for qualifying your cabling
installation to a particular level of performance, e.g., Category 5e. If you can’t afford such a
set, either contract with an installation-and-testing company that has one, or rent an appropriate
unit.
d. Impedance
As you learned earlier, variations in impedance cause signal reflections that a TDR uses to
measure the length of a cable. However, these signal reflections can be caused by different
factors, including variations in the cable manufacture, structural damage caused during
installation, or connectors that are a poor match for the cable. The statistic that measures the
uniformity of the cable’s impedance is called its structural return loss (SRL), which is measured
in decibels (dB), with higher values indicating a better cable. Even when the SRL of a particular
cable is acceptable, it is still possible for an installation of that cable to suffer from variations in
impedance that cause signal reflections. When you construct a network to conform to a particular
cabling specification, such as Category 5e UTP, to maintain a consistent level of impedance
throughout the entire length of the cable run you have to use connectors and other hardware that
have the same rating as the cable.
If, for example, during a twisted-pair installation, you fail to maintain the twist of the wire pairs
up to a point no more than 0.5 inches for Category 5 and 5e, and 0.375 inches for Category 6,
from each connection, you run the risk of varying the impedance to the point at which a
reflection occurs (as well as causing additional crosstalk). The cumulative amount of reflection
caused by variations in impedance on a cable run is called its return loss, which, like impedance,
is measured in ohms. If the return loss is too large, signal-transmission errors can occur at high
transmission speeds. The worst-pair performance is reported at the frequency where the result
came closest to the specified limits.
f. Attenuation
Attenuation is one of the most important specifications for high-speed networks; if it is too high,
the signals can degrade prematurely and data can be lost. This is especially true if your network
uses cable lengths that approach the maximum permitted by your networking protocol. Testing
the attenuation of a cable run requires a unit at both ends of the connection: one to transmit a
calibrated signal and another to receive the signal and calculate how much it has degraded during
the trip. Attenuation is measured in decibels (dB), and most good-quality cable testers include
the secondary module needed to perform the test. The worst-case result is reported.
g. Near-End Crosstalk (NEXT)
Along with attenuation, near-end crosstalk (NEXT) is one of the major impediments to
successfully installing and running a high-speed data network on twisted-pair cabling. Figure
below shows NEXT. Testing for NEXT is a relatively simple process with today’s sophisticated
test sets. After terminating the far end of the cable run to prevent any reflections from interfering
with the test, a signal is transmitted over one pair, and the magnitude of the crosstalk signal is
measured on the other pairs (in decibels). For a complete assessment, you must test each wire
pair against each of the three other pairs, for a total of six tests, and you must perform the six
tests from both ends of the cable. The worst-case combination is reported as the cable’s
performance result.
Awire-map tester transmits signals through each wire in a copper twisted-pair cable to determine
if it is connected to the correct pin at each end. Wire mapping is the most basic test for twisted-
pair cables because the eight separate wire connections involved in each cable run are a common
source of installation errors.
Wire-map testers detect transposed wires, opens (broken or unconnected wires), and shorts
(wires or pins improperly connected to each other)—all problems that can render a cable run
inoperable.
Wire-map testing is nearly always included in multifunction cable testers, but in some cases
it may not be worth the expense to spend thousands of dollars on a comprehensive device
b. TDR length testing
A wire-map tester consists of a remote unit that you attach to the far end of a connection and
the battery-operated, handheld main unit that displays the results. Typically, the tester displays
various codes to describe the type of faults it finds. In some cases, you can purchase a tester
withmultiple remote units that are numbered, so that one person can test several connections
without constantly traveling back and forth from one end of the connections to the other to move
the remote unit.
WARNING The one wiring fault that is not detectable by a dedicated wire-map tester is a split
pair, because even though the pinouts are incorrect, the cable is still wired straight through. To
detect split pairs, you must use a device that tests the cable for the near-end crosstalk that split
pairs cause.
c. Continuity Testers
A continuity tester is an even simpler and less expensive device than a wire-map tester. It is
designed to check a copper-cable connection for basic installation problems, such as opens,
shorts, and crossed pairs. These devices usually cannot detect more complicated twisted-pair
wiring faults such as split pairs, but they are sufficient for basic cable testing, especially for
coaxial cables, which have only two conductors that are not easily confused by the installer.
Like a wire-map tester, a continuity tester consists of two separate units that you connect to each
end of the cable to be tested. In many cases, the two units can snap together for storage and easy
testing of patch cables.
d. Tone Generators
The simplest type of copper-cable tester is also a two-piece unit, a tone generator and probe,
also sometimes called a fox and hound wire tracer. With a standard jack, you connect to the cable
the unit that transmits a signal; or, with an alligator clip, you connect the unit to an individual
wire. The other unit is an inductive amplifier, which is a penlike probe that emits an audible tone
when touched to the other end of the conductor. This type of device is most often used to locate a
specific connection in a punch-down block. For example, some installers prefer to run all of the
cables for a network to the central punchdown block without labeling them. Then they use a tone
generator to identify which block is connected to which wall plate and label the punch-down
block accordingly.
3.6 Terminate TRC/CES/Earth wires with connectors.
Communications Earth System (CES) a system of ear thing using common elements to provide
for ear thing of electrical and communications equipment within premises. A CES may be used
for protective and functional ear thing for telecommunications purposes. Communications Earth
Terminal (CET) a terminal provided for the purpose of equipotential bonding of the CES or the
TRC(telecommunications referenceconductor) to the main ear thing bar, main ear thing
conductor or sub-main ear thing conductor of the electrical installation
The CET provides a demarcation between the electrical ear thing system and the
telecommunications ear thing system and was formerly known as a ‘bonding terminal’.
This conductor is generally supplied via the third pin of a power cord. However in some systems
this must be hard wired to the equipment by a licensed electrician. A hard wired PE connection is
specified in those instances where it is required.
Earthing Options
1. TRC and PE
The TRC and the PE must be connected to the equipment on separate terminals, in accordance
with the individual TRC and PE requirements listed above.
2. None. Neither a PE nor a TRC is required to be connected to this equipment.
3. TRC or PE Either a PE or a TRC must be connected to this equipment. However in some uses
of the type of equipment, a TRC must be used. (E.g. a CAE mounted behind another CAE may
need earth recall to access the first CAE. A TRC is required for this functional use).
3.7 Test Reference Cord (TRC) / Communications Earth System (CES) /Earth wire
continuity
Why use a TRC? If you are installing low loss connectors, those connectors may have a loss of ≤
0.15 dB. So testing it with a connector that has a loss greater than 0.15 dB will yield a
pessimistic result. More importantly, if your link is an engineered link operating to custom test
limits - you could be failing a perfectly good link. Another advantage is consistent and
predictable results - something installers often complain about when certifying a cabling system.
Pair Continuity Testers
Continuity testers can be used to check that pairs are not open circuit. They work on a similar
principle to an ohmmeter but usually use light emitting diode or audible tone indicators. Many
modern digital multimeters have built in continuity testers.
Other devices
There are several instruments that can be used to identify low resistance faults such as the Riser
Bond, PET or C2300.Multimeters Two main types of multimeters are in common use, analogue
or digital. Both types share many common features and are equally good for general purpose
testing. The digital multimeter is a battery operated instrument that uses a digital display. The
analogue type is a simpler in design and has an analogue meter display. All multimeters combine
the operations of voltmeters, ammeters and ohmmeters and usually offer the following:
AC and DC voltage ranges from less than one to many hundreds of volts
AC and DC current ranges from a few milliamps to several amps
Resistance ranges from ohms to megohms
Inspection of Work
Inspection of work by a carrier the carriers are responsible for their networks. They also have the
right to inspect cabling work. They may inspect work to ensure it satisfies current AS/CA
technical standards in relation to network integrity, personal safety and proper network
functioning. If a carrier inspection reveals a threat to safety or integrity of their network then
they may disconnect or refuse to connect some or all services.
Maintenance of cabling advice It is the responsibility of the registered cabler to maintain all
necessary installation records. The registered cabler(maintenance licensed person) must maintain
these ‘cabling advices’ in a clear and legible fashion.
TRC/CES /Earthing installation is tested for continuity, insulation resistance and conductive
resistance as per relevant industry standards including AS/ACIF S009. Earthing system is
labeled in accordance with requirements.
What is TRC earthing?
Telecommunications Reference Conductor (TRC) A low noise earthing system providing a zero-
voltage reference point for telecommunications signaling and other functional purposes.
Continuity test
The earth continuity test is a designed to test the resistance of the protective earth of an appliance
and/or the supply lead. It is measured between any accessible earthed parts and the earth pin of
the plug. The test is based on the principles of Ohm's Law.
Insulation resistance test
Insulation resistance can be determined between live, neutral and earth connections with no loads
or appliances connected to any sockets or wiring. Any problems would be shown by a lower-
than-expected resistance being present between them. In domestic wiring anything above 2
megohms is acceptable.
Acabler can determine the approximate resistance of the CES by cable length. If the value is
close to the limit then a measurement will have to be taken which will account for any resistance
included at termination points.
Step 1 – Resistance measurement
(a) Select a pair (or extend one) to run from the:
(i) Protective earth bonding point (or CET if it is adjacent to the point of bonding) to,
(ii) The termination point of the CES at the CSS or LD To use in your measurements
(b) Connect each wire of the reference pair using an appropriate test lead, to the CES cable at the
CSS or LD after removing it from its termination point.
(c) Using a multimeter at the protective earth end, measure and record the loop resistance of the
reference pair. Record this value in the space below.
(i) R1 = _________Ω
(d) Now measure the resistance of each leg of the reference pair to the CES cable. Record this
value below
i) R2 = _________Ω R3 = _________Ω
(e) Before calculating the CES resistances removes all test conductors and reconnect the CES
cable to the earth terminal.
(f) Substitute your values of R1, R2 and R3 into the following formula to calculate the CES
resistance
You should remember that the resistance from the point of connection to the protective earth and
furthermost end of the CES cable should be no more than 1 ohm.
Terminate at CET’s Remove the insulation from the ends of all conductors and terminate them in
the CET’s. Be sure to consolidate all bared conductors by twisting or folding them in two. Make
sure both screws clamp on the conductor in the CET. Alternatively, if you are terminating using
cable lugs, use a sustainable crimp too to fit the lug to the TRC cable.
Joining to the sub main or Main earthing conductor To connect a bonding cable from a CET to
the sub main or main earthing conductor, use a line tap or an equivalent. Do not cut the earthing
conductor and be user to re-insulate the connection. Connecting to the Protective earth electrode
To connect a bonding conductor to an electrode, use an appropriate clamp and fit this below the
protective earth connection. Extend the CES to CSS To extend the CES to the CSS, run the
minimum sized CES cable to the earth terminal of the CSS (or a LD if a CSS is not available).
ACTIVITY – TESTING A CES Test the installation using Section 20 of AS/CA S009:2013 as a
guide. By using table 6 of AS/CA S009:2013 a cabler can determine the approximate resistance
of the CES by cable length. If the value is close to the limit then a measurement will have to be
taken which will account for any resistance included at termination points.
Testing A TRC Test your TRC installation using the testing procedure in AS/CA
S009:2013.
The cable tray should still be earthed to the protective earth from the previous CES activity.
1) Resistance Measurement
(a) Select a cable pair from the BD-FD riser to use in your measurements.
(b) Connect each wire of the reference pair to the TRC connection at the FD using an
appropriate test lead
(c) Disconnect the TRC riser from the earth bar at the BD
(d) Using a digital multimeter measure and record the loop resistance of the reference pair
from the
(i) R1 = _________Ω
(e) Now at the BD measure the resistance of each leg of the reference pair to the TRC
cable. Record this value below.
(f) Before calculating the TRC reisitance remove all test short circuits and reconnect the
TRC to the BD earth bar
(g) Substitute your values of R1, R2 and R3 into the following formula to calculate the
TRC resistance
You should remember that the resistance from the BD link bar to the FD should be no more than
2 ohms. If it was required to test the resistance from the BD link bar to a LD the reference pair
would have to be extended to the LD and the testing process repeated. In this case 5 ohms is the
maximum permissible reading.
Accidental bonding
Once you have measured the resistance of the TRC and found it to be within the limits, it is
necessary to check for accidental equipment bonding.
(a) Remove the main TRC cable from the BD earth bar
(b) Make sure the BD earth bar is connected tot the protective earth at the CET
(c) Set the voltage on the insulation resistance tester to 500Vdc and connect the test leads tothe
TRC cable and the BD earth bar
(e) Reconnect the main TRC cable to the BD earth bar the value you measure should be greater
than 1MΩ to comply with the standards.
3.9 Labeling of earthling system
With the increasing demand for computer network installations, telecommunications grounding
and bonding has become a growing opportunity for electrical contractors. Although similar
grounding principles apply, understanding the telecommunications terminology and special
considerations has been a challenge. As with traditional electrical grounding,
telecommunications networks and equipment should be grounded to the electrical service.
However, simply grounding to structural steel isn’t enough when tackling telecommunications
systems. The sensitivity of the electronic equipment requires that the telecommunications cabling
and power be effectively equalized to prevent loops or transients that can damage the equipment.
This means designing a complete grounding and bonding system that goes beyond the basic
"green-wire
3.9.1. Grounding
The NEC article 100 defines ground as:
3.9.2. Bonding
The NEC article 100 and 250-70 defines bonding as:“The permanent joining of the metallic
conducting parts of equipment and conductor enclosures to assure and electrically conductive
path between them that will ensure electrical continuity and have sufficient capacity to safely
conduct any foreign current likely to be imposed to ground.”
Bonding is required because electrically conductive materials such as structural steel, metal cable
trays, and metallic supporting structures may become energized in the event of making contact
with: lightning, line surges, or unintentional contact with high voltage lines.
The practice of creating effective bonding is to create a reliable path for such fault currents to the
electrical system ground. Effective bonding practices help to equalize potential caused by either
lightning and electrical system faults that would otherwise damage equipment and harm
individuals. The NEC requires that metal raceways, cable trays, racks, enclosures, or metal cable
armoring must be effectively bonded to ensure the capacity to conduct any fault current to
ground.
The NEC Article 250-96 states: “Metal raceways, cable trays, cable armor, cable sheath,
enclosures, frames, fittings, and other metal noncurrent carrying parts that are able to serve as
grounding conductors, with or without the use of supplementary equipment grounding
conductors, shall be effectively bonded where necessary to ensure electrical continuity and the
capacity to conduct safely any fault currents likely to be imposed on them. Any nonconductive
paint, enamel, or similar coating shall be removed at threads, contact points, and contact surfaces
or be connected by means of fittings designed so as to make such removal unnecessary.”
Communication cables have exposure to electrical currents. The NEC Article 800-2 defines a
communication cable as “exposed” when
“The cable or circuit is in such a position that, in case of failure of supports or insulation, contact
with another cable or circuit may result.”
All communication cables are considered exposed to electrical current because of where these
cables are installed in a building or in a campus configuration. Communication cables are
installed in very close proximity to electrical conductors on walls and above ceilings.
The degree of expose is also determined by where the cable is installed. Exposure can be defined
in the following two areas:
All copper communication cables, or any dielectric cables that have a conductive element, are
conductors of electrical energy. When these types of cables are run between buildings, they are
electrically exposed to lightning. These cables would carry a lightning strike along the cable and
into any cables that are connected to these cables.
Key Terms:
Bonding means permanent joining of metallic parts for the purpose of forming an electrically
conductive path to ensure electrical continuity and capacity to safely conduct any current likely
to be imposed.
Bonding conductor for telecommunications is a conductor used to interconnect the
telecommunications bonding infrastructure to the service equipment (power) ground of the
building.
Effectively grounded refers to an intentional connection to earth through a ground connection of
sufficiently low impedance. It must have sufficient current-carrying capacity to be able to
prevent the buildup of voltages that could potentially result in unnecessary hazard to connected
equipment or persons.
Ground is an intentional or accidental conducting connection between an electrical circuit or
equipment and earth or conducting body serving in place of earth.
Ground electrode conductor is a conductor used to connect the grounding electrode to:
The telecommunications grounding and bonding system starts with a physical connection to the
building grounding electrode system and extends to every telecommunications room (TR) in the
building (see the following figure).
Figure 3. 12 The telecommunications grounding and bonding system
The system begins at the electrical service entrance, travels to the TMGB and continues through
to each TGB located in individual telecommunications closets on each floor of the building
structure, finally looping back around to the original TMGB.
The telecommunications entrance facility (TEF) includes the entrance point at the
telecommunications service and also the space where the inter- and intra-building backbone
facilities join. Telecommunication-related antenna entrances and electronic equipment may be
located in the TEF.
The ANSI/EIA/TIA-607 standard requires that all communications bonding conductors be listed
for the intended purpose and approved by a nationally recognized testing laboratory such as UL
or ETL.Bonding conductors must always be insulated wires. The standard also requires that
bonding conductors be made of copper metal. Other metal types are not supported for use aa
bonding conductor by the ANSI/EIA/TIA-607 standard. In addition, the minimum size of all
bonding conductors must be at least a #6 AWG wire.
The TMGB is the dedicated extension of the building grounding electrode system for the
telecommunications infrastructure. Because it is the central attachment point for TBBs and
equipment, the TMGB should provide easy access for telecommunications personnel.
The TMGB is predrilled copper bus bar with standard NEMA bolt-hole sizing and spacing for
the particular lug connection that will be used. It should be large enough to satisfy today’s
applications and accommodate future growth. A minimum of 6-mm thickness and 100-mm width
is required. Many varieties of ground bars are available, and some come as a kit and can be
customized to meet the specific requirements of the application. Pre-weldedCadweld pigtails are
available in a variety of conductor sizes and lengths, insulated or bare, ready to be attached to the
building ground.
For reduced resistance, electro tin plating is preferred. However, if not plated, the mating
surfaces must be completely cleaned. Where telecommunications panelboards are located with
the TMGB, they must have the alternating current equipment ground bus (or a metallic
enclosure) bonded to the TMGB/TGB. All appropriate clearances should be maintained while
locating TMGBs as close as possible to the panel boards.
Connections to the TMGB or lugs should be exothermic welds. Exothermic welds provide a
connection that helps ensure the long-term integrity of the grounding system.
The TBB is a conductor that connects all TGBs with the TMGB. It reduces or equalizes potential
differences between the telecommunications systems to which it is bonded. The TBB should not
be the only conductor that provides a ground fault current return path.
Starting at the TMGB, the TBB loops throughout the building via telecommunications backbone
pathways. It connects TGBs in every telecommunications closet and equipment room within the
building. Multiple TBBs may be necessary, depending on the size of the structure and the
number of TGBs in the building. Water pipes or metallic cable shield should not be used as
telecommunications bonding backbone. Each TBB should be an insulated copper conductor, a
minimum of No. 6 AWG and possibly as large as 750 kc mil often used by telephone and
communications companies. In a multi-story building where more than one TBB is used, the
TBBs must be bonded together with a TBB interconnection bonding conductor (TBBIBC)
located on the top floor and at least every third floor.
A TGB is a predrilled copper bus bar with standard NEMA bolt hole sizing and centrally
connected systems and equipment served by a telecommunications closet. It should be at least 6-
mm thick by 50-mm wide. Just like the TMGB, the TGB should be electrotin-plated or cleaned
prior to connecting the conductors to the bus bar. The bonding conductor between the TBB and
the TGB should be continuous and run in the most direct path possible.
Often, the TGB is installed to the side of the panel board. When the building’s structural steel is
effectively grounded, each TGB should be bonded to the steel within the same room with a No. 6
AWG conductor. Always use the shortest distance possible in the grounding system.
The ANSI/EIA/TIA-607 standard requires that when two or more TBBs are installed vertically
in the intrabuilding backbone pathway, the TBBs must be bonded together. The
telecommunications bonding backbone interconnecting bonding conductor (TBBIBC) is the
component used for this function (see the figure above).The ANSI/EIA/TIA-607 standard
requires that the TBBIBC be installed at the top floor and a minimum of every third floor. The
minimum size of the TBBIBC must be no smaller than the TBB conductor size.
The TBBIBC would also be used to bond two or more TGBs installed in the same TR together.
The TBBIBC is also used to bond the TGBs installed in different TRs that reside on the same
floor of the building. This connection would follow the same requirements as bonding multiple
TBBs at the top floor and a minimum of every third floor.
3.10 Testing and confirming Compatibility of alterations with existing systems
Qualifications of Installer
The Structured Cabling System shall be installed only by accredited firms of the cabling system
components and by suitable qualified personnel(s)
Use the Velcro-based ties every 1 to 2 meters for bundling or securing the cables, and
avoid using the zip ties as they apply pressure on the cables.
Regularly maintain the cabling documentation, labeling, and physical or logical cabling
diagrams.
• Document and regularly update all the cabling components and their mapping.
For new installations or re-cabling of the existing equipment, install the cable guides to
reduce mechanical stress and bending of the data cables, and to enhance the
maintainability.
The installation and usage of cable guides should be independent of the number of cables that are
installed. However, there are products that do use cable guides, or where the cable guides cannot
be installed.
3.12 Routine quality termination of cables and devices
Locate your wire distribution device (connector block) at your demarcation point;
• Disconnect one pair of wires from the distribution device;
• Check to see if your service has been restored at other jack locations in your home;
• Continue disconnecting wire pairs, one pair at a time, to determine which wire is the cause of
the trouble;
Once you have isolated the problem circuit, it is suggested that you replace the entire section of
wire that is defective or the jack if it is causing the problem.
If you are unable to repair or isolate an inside wire trouble yourself, repair service is available
from your local telephone company or an independent contractor.
Self-Check -3
Directions: Answer all the questions listed below. Use the Answer sheet provided in the
next page:
Part I. Choose the best answer from the question below
1. ________________is a type of transmission line, used to carry high-frequency electrical
signals with low losses.
A. Coaxial cable B. UTP cable C. Telephone wire D. none
2. To prevent crosstalk, wire pairs in a Cat5e cable should not be untwisted more
than_____ inches.
A. 0.5 B. 0.4 C. 0.45 D. 0.375
3. To prevent crosstalk, wire pairs in a Cat6 cables should not be untwisted more
than_____ inches.
A. 0.375 B. 0.5 C. 0.35 D. 0.475
4. Which of the following colour is used for earthing conductors for CES
system?
A. green/yellow insulation B. blue/yellow insulation C. white/yellow insulation
5. ____________is one of the most important specifications for high-speed networks.
A. Crosstalk B. Attenuation C. Dead air D. Humming
Operation sheet 3
Instruction: Using the Flip chart and given equipments Identifying material Used in data cable
for socket outlet connection instructor must check the connection after you
finished connection .
Purpose: When you have completed this Unit, the trainee should be able to identify the material
used in data cable for socket outlet connection.
Required tools and equipment: unit one of this module, tools from workshops like Jacket stripper,
Punch-down tool, Wire cutters, testing instrument.
Precautions: Safe handling Jacket stripper, Punch-down tool, Wire cutters, testing instrument and
components
Procedures:
LAP Test 3
Instruction I: Given necessary templates, tools and materials you are required to perform the following
tasks within 2 hours.
Task 1: Identify data cables for socket outlet connectiondevices properly
Figure4. 1 typical work station and cord without cover which make electrical hazard
Most socket extensions are rated 13A (3120w capacity), but many have only 10A (1800w
capacity), or even lower rating. Plugging-in most popular desk equipment should not pose a
problem; laptops and desktop computers generally consume less than 250w each. Note printers
can use up to 800w during printing. While employers might prohibit the use of personal
electric appliances - a kettle or personal heater can eachconsume 3000w, so would instantly
overload and blow the fuse of an extension block - there remains a more serious risk if
employees wanting yet more outletsdecide to plug a second extension block into the first one,
so increasing the risk of overheating; or plug an adaptor into an extension block,
especially as blocky-type adaptors are usually unfused. Accepting the danger of a breach in
H&S policy, putting each rectangular-style socket extension block inside a D-Line Cable Tidy
Unit represents a practical way to reduce such risk; making the socket block lessaccessible or
less inviting to employees, and an adaptor more awkward to fit.
Figure 4. 4 enclosing the extension block reduce the possibility of any drink spill on to live
sockets.
It should be considered that however small the risk assessed, enclosing the extension block
reduces the possibility of any drink spill on to live sockets. While circuit protection should be
effective, all steps should be taken to avoid the surge and heat that can arise should liquids
(conductive) contact with electricity.
Similarly best practice should consider that when copper cables are fully loaded and form a tight
coil to nest around an extension block, some cables can be fully entrapped so their heat cannot
disperse; a danger eliminated by using Cable Tidy Units (note 17th Edition of IET Wiring
Regulations state in BS7671:2008 section Cable
Enclosures that when containing pvc insulated cables ‘not more than 45% of space within a
conduit or trunking must be occupied by cables’; a principle transferable to Cable Tidy Units).
Cable Tidy Units should provide ample space, and require also that the cable from each plug-top
must be routed via one of the three rear exit slots… so further minimizing risks from ‘excessive’
heat build-up. These slotted exits are vents also. Entry and exit cables should be concealed in
D-Line Spiral Wrap, Cable Tidy Tubes or Trunking. D-Line Cable Tidy Units are produced in
the UK using electrically safe material, and have been fully safety tested (when overloaded with
cables, and vents blocked!)
Broken conductor strands disrupt the natural flow of current, creating resistance by forcing high
wattages over a smaller conductor area, and, over periods, where perhaps power is on 24/7,
excessive heat builds up. Becoming glowingly-hot can ignite common office materials such as
paper and waste, to start a fire.
Cable management products — that can protect insulation; stop cords twisting and knotting; and
prevent tugs and pulls — are a small price-to-pay for safeguarding from the worst consequences.
Figure4. 10 select a Floor Cable Cover with a cavity-size that can accommodate the relevant
cables
Mains voltage and low-voltage cables should be segregated in a compartmentalized profile.
- Value-added features such as a ribbed back can make a strip less likely to slip after being
knocked. Likewise a pre-split rear cavity makes it quick and easy to fit the strip over the cables.
Caution 1 - if preferred, after inserting cables, users can affix Floor Cable Covers to a floor by
applying heavy-duty double-sided tape. Take care to ensure the floor is clean and dry so an
effective bond can be made.
Beware such tapes may leave a residue on removal.
Caution 2 - do not put cables under carpet tiles, or under surface tapes. This will provide less
protection for the cable, with a greater likelihood that ‘wear’ will lead to a ‘tear’ in the outer
sheath of the cable, especially any thin rubberized insulation.
- Using only a tape will not offer the same protection against the cable becoming frayed, or
pinched under the leg of a chair or desk. As previously, beware the electrocution risk of exposed
conductors and how brokenconductors can lead to power failures, heat build-ups and fires.
Figure4. 11 beware the electrocution risk of exposed conductors and covered conductors
Advice
The installer(students)shall advise his teacher for the gain approval before undertaking any work
at the practical workstation or on site follow up ,that may or will result in voice, data, security or
other ICT network service disruption or network downtime to existing network infrastructure.
Any work that may result in network down time will require scheduling with school
representatives
4.2Work site safety
Site conditions
The installer shall familiarize themselves with the site conditions prior to undertaking or
providing quote or estimate prices for any work. Specific conditions to be observed at collage
work station during practical session or on site work of cablings OSH requirements, qualification
and identification of personnel and onsite legacy equipment and configurations. Installers are
required to undertake all necessary investigations to fully inform themselves of the site
conditions and other factors that could impact the cost and execution of works
This includes but is not restricted to:
A. Hazards that may be present at the collage practical work station or onsite cabling
B. Heritage registration of buildings
C. Environmental conditions including special precautions for the protection of flora and fauna
D. Local site conditions including weather hazards and cultural significance
E. Easements
F. Safety of students and staff with respect to pit covers and location
G. Existing and projected underground services, note that site maps may not be complete or
available
4.3 Record sheets and plans of cable
The record sheets are generally established and maintained by the carrier or installer
(supervisor) of the cable installation. Network jumpers, distribution line, mainline, color
code mark ,identification at each terminal that is input and output all these and the ext.
connection records will be recorded and established on the sheet and provided for owner and
set for future extension or remove and add
Please note that this frame does/ does not leave each 11th module position blank
Termination records-----------------
Records correct as of______________sheet______________________
4.4Cable pair record books
Creating Cable pair record books to provide accurate record information
In an installation of data cable, Telephone cable, coaxial cable, CCTV- cable, Fiber optics and all
other cable for signal transfer whether for high or low speed Planning is the first critical issue
that discussed at first of all. By doing this all data survey of the area, environment, length, type
of the building and all other information required to for the routing of the cable must be
organized each step by step for the next removal, addition, re installation of the existing or for
new construction of the system, all this records are recorded to the book form for the next option
of constructing to much the coming technology or for better decision of the cost, louber ,
management analysis.
4.5. Documentation and report completion of installing work
A comprehensive strategy for managing power and data cables within IT racks in
telecommunication is critical for the uptime, safety, and cooling efficiency of data centers.
Advancements in IT rack designs have improved power and data cable management
(documentation):
Effective rack power and data cable management leads to a number of IT infrastructure Benefits
including: Enhanced availability through reduced downtime. A system operator or employee can
be easily confused by a mess of cables, which often results in human error. Human error is
widely regarded as the leading cause of data center downtime based on a study by The Uptime
Institute
Effective cable management can help system operators to manage cables and IT devices
easily, so as to reduce human error.
Improved system performance through reduced crosstalk and interference between
power and data cables. Power and data cables in close proximity to each other can
create electromagnetic interference (EMI), which can result in erratic or error-prone
data transfer in network cables. Cable management tends to separate power and data
cables within the racks, which can help reduce the risk of interference.
Improved maintenance and serviceability by allowing easier and safer access to
individual components.
Increased cooling efficiency by allowing hot exhaust air to escape out the back of the
rack. Cable management keeps cables organized and out of critical airflow paths.
Improved scalability by simplifying moves, adds, and changes. Cable management can
make it easier to integrate additional racks and components in the future as the data
center grows
This documentation or guidance on power and data cable management that will improve
Physical appearance, cable traceability, airflow, cooling efficiency, and troubleshooting time
while reducing the risk of human error. Following the steps outlined below can help you achieve
a clean and well organized data center(documentation):
Plan
Determine the routes for power and data cables
Identify cables
Route and retain cables
Secure cables and connectors
Avoid thermal issues
Document and maintain organization
Plan
Planning is the first step for power and data cable management in IT racks, and when done
properly, it facilitates all of the steps below. Planning plays a critical role in any successful cable
management project. If this is your first structured cabling project, we recommend that you hire
a professional cab ling contractor like Schneider Electric to complete the entire project. Table
below shows an example statement of work (SOW) for cable management in documentation. A
key output of the planning step is to determine the number of cables needed. This is done by
calculating the number and type of connections per device and the total number of devices
Activities Description
Management will provide cable management for the servers migrating over to the
new racks in existing and for new installation
will dress cabling into neat and presentable bundles in all locations Install
Installation will install and manage all patch cords into the rack and organize them
with a specific cable management system that allows for proper airflow in
the rack
Labels will professionally label primary and secondary data cables, and primary
and secondary power cables.
Logistics will provide the knowledge and labor required for a well-organized
and professionally maintained data center with minimal downtime.
will utilize a fully tested cable management system.
Activities Description
Advanced coppertesting will physically test each port from the Data Distribution Cables
(DDC) to the switch for compliance to current standards, with
customer approval.
will use a network cabling certification tester, compliant to
TIA/EIA TSB67 Level III specifications.
Advanced crossover and install and manage all patch cords into the rack and organize them
strait through(wide- with a specific cable management system that allows for proper
networkng) airflow in the rack
Basic copper testing Perform a continuity port test and wire map of each port of the
cables (digital mult meter)
Basic coaxial testing Coaxial cable testing
The most often overlooked item during cable installation is the documentation of the new cabling
system. Cabling system documentation includes information about what components make up a
cabling system, how it is put together, and where to find individual cables.
This information is compiled in a set of documents that can be referred to by the network
administrator or cabling installer any time moves, adds, or changes need to be made to the
cabling system.
The most useful piece of cabling system documentation is the cabling map. Just as its name
implies, a cabling map indicates where every cable starts and ends. It also indicates
approximately where each cable runs. Additionally, a cabling map can indicate the location of
workstations, segments, hubs, routers, closets, and other cabling devices. To make an efficient
cabling map, you need to have specific numbers for all parts of your cabling system. For
example, a single cable run from a cabling closet to wall plate should have the same number on
the patch panel port, patch cable, wall cable, and wall plate. This way, you can refer to a specific
run of cable at any point in the system, and you can put numbers on the cabling map to refer to
each individual cable run.
Self-Check -4
Directions: Answer all the questions listed below. Use the Answer sheet provided in the
next page:
Part I. Choose the best answer from the question below
1. Which of the following must be robust enough and adequately protected for the working
environment?
A. Cables B. Plugs C. sockets D. fittings E. all
2. The telecommunication and data service Installer shall comply with_______________
A. all rules and Regulations C. Approved Codes of Practice,
B. All relevant Standards D. Work Safe E. all
3. Safety Overloading socket outlets, especially socket extensions can cause excessive heat
buildup and is a major cause of ___________ from electricity.
A. Overload B. fire C. burn D. heat
4. The record sheets of cables are generally established and maintained by the
______________of the cable installation.
A. carrier or installer B. technician C. Manager D. shopkeeper
5. In creating data book for information about cable installed.
A. Planning is the first pinot of view. C.Condition of the area
B. Information analysis of environmentD. All
6. The cable record book is used for_________
A. Adding cable to the existing C. For extension of the existing
Part II. If statement correct write True and if statement is incorrect write False for the
following question.
.
References
Qualificatio Organization/
No Name Field of Study Region Mobile number E-mail
n (Level) Institution
Industrial Automation Lideta
Mengistu
1 MSc & Control A.A Manufacturing 0913948480 [email protected]
Abiyu
Management College
Industrial Automation
2 Samuel Bekele MSc & Control Oromia Haramaya PTC 910082977 [email protected]
Management
Yidnekachew Electrical Automation
3 BSc A.A Akaki PTC 920137899 [email protected]
Seboka & Control Technology
Electrical Automation Addis
4 Zegeye Girma BSc A.A 926805563 [email protected]
& Control Technology KetemaIn.College
Industrial Automation
HawassaTegibarid
5 Bacha Wake MSc & Control Sidama 987065251 [email protected]
PTC
Management