Test Report - Reg. 30
Test Report - Reg. 30
TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 2500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV: 43.7 / 3333.4 Amps
Maker’s Serial No. : J 1716002 / 002 Oil Quantity: 2800 litres
Year of Manufacture : 2009 Next Due date for Oil filtration: 20th July 2017.
BDV Test Results After Filtration: - TEST GAP BETWEEN ELECTRODES : 2.5mm
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Electrical Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 1b
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION: 20TH JULY 2016.
T R A N S F O R M E R NO. 1 O L T C OIL TEST REPORT
Supply to PCC-1
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.
BDV Test Results after Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Electrical Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 2a
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION: 21ST JULY 2016.
T R A N S F O R M E R NO. 2 O I L TEST REPORT
Supply to PCC-2
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.
TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 2500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV : 43.7 / 3333.4 Amps
Maker’s Serial No. : J 1716002 / 001 Oil Quantity: 2800 litres
Year of Manufacture : 2009 Next Due date for Oil filtration: 21st July 2017.
BDV Test Results After Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Electrical Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 2b
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION: 21ST JULY 2016.
T R A N S F O R M E R NO. 2 O L T C OIL TEST REPORT
Supply to PCC-2
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.
BDV Test Results after Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Electrical Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 3a
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION: 21ST JULY 2016.
T R A N S F O R M E R NO. 3 O I L TEST REPORT
Supply to PCC-3
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.
TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV : 8.7 / 666.7 Amps
Maker’s Serial No. : J 1709001 / 01 Oil Quantity: 1000 litres
Year of Manufacture : 2009 Next Due date for Oil filtration: 21st July 2017.
BDV Test Results After Filtration :- TEST GAP BETWEEN ELECTRODES : 2.5mm
(AUTHORISED SIGNATORY)
TIN 33251085384 DURGA SWITCHGEARS
A-Grade Electrical Contractors EA 2616
CST 872774/08-01-08 (Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,
AREA CODE 0 5 5 Protective relays, Transformer oil filtration and High pot Test)
Branch: PAGE 3b
9, ANBIL NAGAR,
AIRPORT ROAD, Mobile: 9884320732 Office; 044 – 25550453
TIRUCHIRAPPALLI – 620 007. Mail : [email protected]
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051
DATE OF OIL FILTRATION: 21ST JULY 2016.
T R A N S F O R M E R NO. 3 O L T C OIL TEST REPORT
Supply to PCC-3
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.
(AUTHORISED SIGNATORY)
EARTH PITS
Durga Switchgears A-Grade Electrical Contractors – EA 2616 Page 10a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
EARTH RESISTANCE TEST REPORT
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears A-Grade Electrical Contractors – EA 2616 Page 10b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
EARTH RESISTANCE TEST REPORT
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
RELAYS
Durga Switchgears – EA 2616 Page 4a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY
SETTINGS:-
I > 0.90 Delay Type : IEC SI TMS > 1.0 Ie > 0.18 Delay Type : IEC SI TMS > 1.0
I >> 3.6 Instantaneous Ie >> 0.90 Instantaneous
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 4b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 5a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY
SETTINGS:-
I > 0.90 Delay Type : IEC SI TMS > 1.0 Ie > 0.18 Delay Type : IEC SI TMS > 1.0
I >> 3.6 Instantaneous Ie >> 0.90 Instantaneous
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 5b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 6a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY
SETTINGS:-
I > 0.35 Delay Type : IEC SI TMS > 1.0 Ie > 0.175 Delay Type : IEC SI TMS > 1.0
I >> 1.4 Instantaneous Ie >> 0.87 Instantaneous
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 6b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 7a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY
SETTINGS:-
I > 0.80 Delay Type : IEC SI TMS > 1.0 I0 > 0.16 Delay Type : IEC SI TMS > 1.0
I >> 3.2 Instantaneous I02 >> 0.80 Instantaneous
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 7b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 7c
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR NEUTRAL DISPLACEMENT RELAY
The zero sequence current that flows for an earth-fault on an un-earthed network is determined by
the capacitance of the cable to earth. This flow of current leads to a rise in the voltage of the neutral point
of the incoming supply (the star-point of either the generator or transformer). It is this rise that is
detected by a neutral voltage displacement relay.
SETTING :
PLUG TIME LEVER DMT
SETTING SETTING
20 VOLTS 0.2 5.0
TEST RESULTS:-
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 7d
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR NEGATIVE SEQUENCE VOLTAGE RELAY
TEST RESULTS:-
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 8a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR EARTH FAULT RELAY
OPERATING
CURRENT SETTING CURRENT IN
AMPS
0.50 0.51
0.75 0.76
1.00 0.99
1.25 1.24
1.50 1.54
1.75 1.74
2.00 2.01
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 8b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR INSTANT DIFFERENTIAL RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 9a
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR EARTH FAULT RELAY
OPERATING
CURRENT SETTING CURRENT IN
AMPS
0.50 0.50
0.75 0.76
1.00 0.99
1.25 1.25
1.50 1.52
1.75 1.74
2.00 2.01
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears – EA 2616 Page 9b
Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR INSTANT DIFFERENTIAL RELAY
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
TEST REPORT FOR
&
EARTH PITS
AT
NEMAM,
0N