As Built: Smdb-5F

The document provides information on recabling work for a fire fighting pump and distribution boards. It includes a diagram showing the existing and proposed cabling layout between the pump, distribution boards, and main switchboards. Specifications are given for the cable sizes and types to be used such as 4Cx10mm2 XLPE/SWA/PVC cable. Load details are also listed for the existing and new distribution boards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
80 views2 pages

As Built: Smdb-5F

The document provides information on recabling work for a fire fighting pump and distribution boards. It includes a diagram showing the existing and proposed cabling layout between the pump, distribution boards, and main switchboards. Specifications are given for the cable sizes and types to be used such as 4Cx10mm2 XLPE/SWA/PVC cable. Load details are also listed for the existing and new distribution boards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

NOTES:

ROUTE OF THE CABLE TRAY FOR POWER CABLES


IS THROUGH COMMON AREA AS PER ADDC
REQUIREMENT

REPLACEMENT OF OLD FIRE FIGHTING PUMP (RECABLING ONLY)

DB-RF
(RE-WIRING) FF PUMP DB-F1 DB-F2 DB-F3 DB-F4 DB-F1-RF DB-F2-RF
TCL=10.68 kW TCL=37 kW TCL=24.36 kW TCL=24.36 kW TCL=24.56 kW TCL=24.36 kW TCL=24.76 kW TCL=24.66 kW
TDL=6.98 kW (RE-CABLING) TDL=15.99 kW TDL=15.99 kW TDL=16.14 kW TDL=15.91 kW SPARE SPARE TDL=16.29 kW TDL=16.41 kW SPARE SPARE SPARE SPARE

4Cx10mm² XLPE/SWA/PVC CABLE


1Cx10mm² ECC
4Cx25mm² XLPE/SWA/PVC CABLE 4Cx16mm² XLPE/SWA/PVC CABLE 4Cx16mm² XLPE/SWA/PVC CABLE
1Cx16mm² ECC 1Cx10mm² ECC 1Cx10mm² ECC

ADDC ADDC ADDC ADDC ADDC ADDC


M kWh M kWh M kWh M kWh M kWh M kWh
DB-SERVICE LIFT ISO METER METER METER METER METER METER
TCL=11.32 kW TCL=3.5 kW
(EXISTING) (EXISTING)

40A TP 40A TP 40A TP 100A TP 63A TP 63A TP 63A TP 63A TP 63A TP 40A TP 63A TP 63A TP 40A SP 40A SP 40A SP 63A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCB MCB MCB MCCB

RYB1 RYB2 RYB3 RYB4 RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB1 RYB2 R3 Y3 B3 RYB4
4 WAY TPN WITH 125A TPN+E TINNED CU BUSBAR AT 400V / 50Hz 6 WAY TPN WITH 200A TPN+E TINNED CU BUSBAR AT 400V / 50Hz 4 WAY TPN WITH 100A TPN+E TINNED CU BUSBAR AT 400V / 50Hz

SMDB-4F (NEW) BREAKING CAPACITY-36kA SMDB-RF (NEW) BREAKING CAPACITY-36kA


SMDB-SERVICE (EXISTING) LOCATION : SUB E/R 4TH FLOOR LOCATION : SUB E/R ROOF FLOOR
LOCATION : E/R GROUND FLOOR 125A TP 200A TP 100A TP
MCCB T.C.L : 97.64 kW MCCB T.C.L : 49.42 kW MCCB
T.C.L : 62.50 kW
T.D.L : 64.03 kW T.D.L : 32.70 kW
BREAKING CAPACITY-36kA

SMDB-5F
(TYPICAL SMDB-4F)
LOCATION : SUB E/R 5TH FLOOR
T.C.L : 97.64 kW
T.D.L : 64.03 kW
SMDB 2ND FLOOR

SMDB 3RD FLOOR


SMDB 1ST FLOOR

REAPPROVAL FOR CLOUDED AREA


200A TP MCCB

200A TP MCCB

200A TP MCCB

100A TP MCCB

SPARE (200 A)

SPARE (125 A)
SMDB-SHOP

SPARE (40 A)

AS BUILT

CAP.BANK
(60 KVAR)
SMDB-EXISTING

4Cx70mm² XLPE/SWA/PVC CABLE

4Cx70mm² XLPE/SWA/PVC CABLE

4Cx25mm² XLPE/SWA/PVC CABLE

4Cx50mm² XLPE/SWA/PVC CABLE


EXISTING CONNECTED LOAD=344.00KW SPARE 2 FOR ADDC SUBMISSION 02/11/2019
MCCB RATING=600A TP
1 FOR ADDC SUBMISSION 20/10/2019

REV.NO. DESCRIPTION DATE

CLIENT:

1Cx35mm² ECC

1Cx35mm² ECC

1Cx16mm² ECC

1Cx25mm² ECC
MR RASHID SHOAIL AL MAZROEEI

CONSULTANT:

600A TP 200A TP 200A TP 100A TP 160A TP 40A TP


MCCB MCCB MCCB MCCB MCCB MCCB STAR LINE ENGINEERING CONSULTANCY
2x4Cx150mm² XLPE/SWA/PVC CABLE

RYB1 RYB2 RYB3 RYB4 RYB5 RYB6


MAIN CONTRACTOR:
6 WAY TPN WITH 1000A TPN+E TINNED CU BUSBAR AT 400V / 50Hz
MDB (NEW) R Y B
LOCATION : ELEC.ROOM GF
1000A TP MCCB ULTRAMAX GENERAL CONTRACTING
1Cx70mm² ECC

1Cx70mm² ECC
T.C.L : 588.70 kW 50kA A A A V S/S
T.D.L : 384.37 kW
(500 mA ELR)
2x1Cx70mm² ECC

MEP CONTRACTOR:

SUPPLY BY ADDC Amps Electromechanical Contracting


Tel - 02 6767107 / 0553418719/0558405053
P.O. Box-34947
SUPPLY FROM ADDC F.P
Email:[email protected]
ELECTRICAL CONTRACTOR:

EXISTING NEW

PROJECT NAME:
DESCRIPTION EXISTING (KW) NEW (KW) TOTAL (KW)
A/C LOAD 90.00 84.60 174.60
ADDITIONAL TWO FLOORS COMMERCIAL BUILDING
OTHER LOAD 254.00 160.10 414.10
DRAWING TITLE:
TOTAL LOAD 344.00 244.70 588.70
SCHEMATIC DIAGRAM

DRAWING NO.: 6/6 DATE: 02.11.2019 SECTOR: ME-10 DESIGNED & PREPARED: MUHASIN

PROJECT ID: SCALE: 1:100 PLOT: C-311 CHECKED & APPROVED: FASIL